Completing The Actuated Valve Actuated valve, also referred as shutdown valve, blowdown valve, on-off valve, mainly comprises of valve body and actuator. Here are several accessories that make actuated valve complete. 1. Solenoid Valve Comprises of a solenoid and a valve which form is usually a three-way valve. Solenoid converts electrical energy to mechanical energy resulting three-way valve changes its state. Here is one example how the solenoid valve working in actuated valve that operates in fail safe mode* as shown on above schematic: Refer to the lower box in schematic when there is no electrical current received by the solenoid (in other word “de-energized”), the spring makes the valve in a state of the inlet port (1a) blocked while the outlet port (1b) connects to the vent port (1c), releasing air inside the actuator to the atmosphere.

Completing the Actuated Valve

Embed Size (px)

DESCRIPTION

Actuated Valve

Citation preview

Page 1: Completing the Actuated Valve

Completing The Actuated Valve

Actuated valve, also referred as shutdown valve, blowdown valve, on-off valve, mainly comprises of valve body and actuator. Here are several accessories that make actuated valve complete.

1. Solenoid ValveComprises of a solenoid and a valve which form is usually a three-way valve. Solenoid converts electrical energy to mechanical energy resulting three-way valve changes its state.

Here is one example how the solenoid valve working in actuated valve that operates in fail safe mode* as shown on above schematic:

Refer to the lower box in schematic when there is no electrical current received by the solenoid (in other word “de-energized”), the spring makes the valve in a state of the inlet port (1a) blocked while the outlet port (1b) connects to the vent port (1c), releasing air inside the actuator to the atmosphere.

If the solenoid is energized by electrical current, it will change the valve state. Refer to the upper box in the schematic, the inlet port (1a) connects to the outlet port (1b) allowing the air supply flowing into the actuator and stroking it, while the vent port (1c) is blocked.

*fail safe mode means that the actuated valve shall bring the system to safe condition when instrument air or electrical starts to fail. Shutdown valve

Page 2: Completing the Actuated Valve

(SDV)shall be closed, or referred as FAIL CLOSE, whereas Blowdown valve shall be opened or referred as FAIL OPEN. More description about fail safe mode, read this post.

In some application where there is no electrical power, pneumatic piloted valve is used in lieu of solenoid valve. It has the same principle as solenoid valve, but the power source is pneumatic instead of electrical.Commonly used manufacturers: ASCO, VERSA, and BIFOLD.

2. Limit Switch / Position TransmitterPosition transmitter is used to remotely monitor valve opening from the control room. This instrument is attached on the actuator and transmitting analog electrical signals to indicate the exact position of valve opening. Meanwhile limit switch can only provides remote indication of valve status (open or close position) through electrical discreet signal.Commonly used manufacturers: WESTLOCK

3. Air Filter RegulatorThis device filters the air supply and regulates its pressure, resulting clean air supply with constant pressure fed into actuator.Commonly used manufacturers: FISHER AFSR

4. Quick Exhaust ValveQuick exhaust valve can increase the reaction of actuator spring when valve is required to fail safe. This is achieved by releasing the exerting fluid inside the actuator into the open line (port 4c), rather than back through the supply line (port 4a) which is more restrictive as it has to pass flow regulator valve and solenoid valve.Commonly used manufacturers: VERSA

5. Flow Regulator ValveTo achieve the required closing and/or opening time of actuated valvei. Uni directional flow regulatorThis valve regulates flowrate of air supply in one direction only, while it doesn’t regulate the flowrate of air supply from other directions hence full flow will be passed through. It is used to set the opening time of SDV or closing time of BDV. During start-up the actuator is stroked with rate of movement depends on air supply flowrate flowing into the actuator. FRV will restrict the flow from (5.ia) to (5.ib) resulting the flow rate of air supply into the actuator decreases so that the actuated valve will move slower. If the actuated valve is required to fail safe, the air supply shall be vented from the solenoid vent port (1c). The uni-direction FRV will keep full flow from (5.ib) to (5.ia).ii. Bidirectional flow regulatorUnlike uni-directional FRV, bidirectional FRV applies restriction to both directions. Installing this FRV will set the time required by the actuated valve to change its state to safe position.

Page 3: Completing the Actuated Valve

6. Check ValveIt allows flow from one direction only i.e from (6a) to (6b). Commonly check valve is used to protect the upstream equipment from back flow.

7. Bug Screen/Silencer/Dust ExcluderThis prevents bug or dust entering the pneumatic system from ports open to the atmosphere.