Upload
teddyshasha
View
218
Download
0
Embed Size (px)
Citation preview
7/30/2019 Conductor Sizing for Typical Motors-Acromec
1/5
Conductor Sizing For Typical Motor/Power Feeder ACROMEC - SNIFF SENSORY
Step 1: Initial Wire Size
1.1
Initial wire size is derived based on equipment
rating input, conductor load input, and wire type
selection
1.2 The cable is upsized by a safety factor of 1.25
1.3 Determine the wire size based on the NEC Table
Step 2: Adjustable Ampacity
Determine the Adjustable Wire Size Ampacity
2.1 Refer to the NEC table for this value
2.2 Determine the temperature rating of the conductor
2.
3
Since the Temperature Rating of the Conductor (input 2.3) does
not equal the Min. Equipment Terminal Rating (input 3.1), adjust
the wire size ampacity based on the Temperature Rating of the
Conductor
2.4 Initial Adjustable Wire Size Ampacity
Step 3: Ambient Temperature Adjustment : Determine the Ambient Temperature Adjustment
3.1 Determine the highest ambient temperature (input 3.3)
3.2
Based on the ambient temperature of 36-40 and the temp.
rating of 75, determine the temp. adjustment from the
correction factors table
Step 4: Bundle Adjustment : Determine the bundle adjustment factor
4.1 Determine the number of current-carrying conductors (input 3.5)
4.2Based on the current-carrying conductors of 1 - 3, determine the
adjustment factor based on the NEC Table
Step 5: Adjusted Ampacity: Determine the Adjusted Ampacity
5.1
Multiply the Adjustable Wire Size Ampacity (step
2.4) by the Temperature Adjustment (step 3.2) by
the Bundle Adjustment (step 4.2)
5.2 Multiply
5.3 Solve for Adjusted Ampacity
Step 6: Solve
6.1
Since Adjusted Amps is
greater than the Conductor
Load (input 1.2), Wire Size
stays the same
6.2 Final Wire Size
6.3 Final Conductor Load
Reference: Online Calculations : http://www.pumpcalcs.com/calculators/view/97/
http://www.pumpcalcs.com/calculators/view/97/http://www.pumpcalcs.com/calculators/view/97/http://www.pumpcalcs.com/calculators/view/97/7/30/2019 Conductor Sizing for Typical Motors-Acromec
2/5
Conductor Sizing For Typical Motor/Power Feeder ACROMEC SNIFF SENSORY (DX Reheat)
Step 1: Initial Wire Size
1.1
Initial wire size is derived based on equipment
rating input, conductor load input, and wire
type selection
1.2 The cable is upsized by a safety factor of 1.25
1.3
Determine the wire size based on the NEC
Table
Step 2: Adjustable Ampacity : Determine the Adjustable Wire Size Ampacity
2.1 Refer to the NEC table for this value
2.2 Determine the temperature rating of the conductor
2.
3
Since the Temperature Rating of the Conductor (input 2.3)
does not equal the Min. Equipment Terminal Rating (input
3.1), adjust the wire size ampacity based on the
Temperature Rating of the Conductor
2.4 Initial Adjustable Wire Size Ampacity
Step 3: Ambient Temperature Adjustment
Determine the Ambient Temperature Adjustment
3.1 Determine the highest ambient temperature (input 3.3)
3.2
Based on the ambient temperature of 36-40 and the
temperature rating of 75, determine the temperature
adjustment from the correction factors table
Step 4: Bundle Adjustment
Determine the bundle adjustment factor
4.1 Determine the number of current-carrying conductors (input3.5)
4.2Based on the current-carrying conductors of 1 - 3, determine
the adjustment factor based on the NEC Table
Step 5: Adjusted Ampacity : Determine the Adjusted Ampacity
5.1
Multiply the Adjustable Wire Size Ampacity
(step 2.4) by the Temperature Adjustment
(step 3.2) by the Bundle Adjustment (step 4.2)
5.2 Multiply
5.3 Solve for Adjusted Ampacity
Step 6: Solve
6.1
Since Adjusted Amps is greater than the
Conductor Load (input 1.2), Wire Size stays the
same
6.2 Final Wire Size
6.3 Final Conductor Load
7/30/2019 Conductor Sizing for Typical Motors-Acromec
3/5
7/30/2019 Conductor Sizing for Typical Motors-Acromec
4/5
Nominal Size Breaker for Motor
1. This expert calculator provides the nominal and maximum size breaker for motor or feeder circuit given electrical load
requirements.
2. Although the expert calculator provides the maximum size breaker and overload protection allowed by code a smaller size
breaker or overload protection is generally used.
1. NEC Code Compliant
2. Motor /Feeder is less than 700 Amps
3. Motor / Feeder is less than 2000 Volts
1. NEC 2005 Sections 430 and 316
Legend
Step 1: Determine FLC : Determine FLC based on the first three inputs and the NEC tables
1.1 Determine Inputs
1.2 Determine FLC based on the inputs and the NEC tables
Step 2: Motor Branch Circuit - Conductor Size : Determine the motor branch circuit conductor size
2.1 Determine Inputs
2.2 Initial wire size is derived based on equipment rating input,
2.3 Determine Values
2.4 Determine the wire size based on the NEC table
7/30/2019 Conductor Sizing for Typical Motors-Acromec
5/5
Step 3: Adjustable Ampacity : Determine the Adjustable Wire Size Ampacity
3.1 Refer to the NEC table for this value
3.2 Determine the temperature rating of the conductor
3.3 Since the Temperature Rating of the Conductor does not equal the Min.
3.4 Initial Adjustable Wire Size Ampacity
Step 4: Ambient Temperature Adjustment : Determine the Ambient Temperature Adjustment
4.1 Determine the highest ambient temperature
4.2 Based on the ambient temperature of 36-40 and the temperature rating of 75,
Step 5: Bundle Adjustment
5.1 Determine the number of current-carrying conductors
5.2 Based on the current-carrying conductors of 1 - 3, determine the adjustment
Step 6: AA : Determine the Adjusted Ampacity
6.1 Multiply the Adjustable Wire Size Ampacity by the
6.2 Multiply
6.3 Solve for AA
Step 7: Solve
7.1 Since Adjusted Amps is greater than the
7.2 Final Wire Size
7.3 Final Conductor Load
Step 8: Motor Overload Protection
8.1 Based on input 2.1
8.2 Based on input 2.2
8.3 Since the service factor is greater than or equal to 1.15, the
8.4 Determine Values
8.5 Multiply
8.6 Solve
8.7 Determine Values
8.8 Multiply
8.9 Solve
Step 9 : Determine Max Motor Branch Circuit and Ground Fault Protection Device
9.1 Based on input 3.1
9.2 Based on input 2.4
9.3 Determine Value
9.4 Determine Nominal Size Breaker by multiplying
9.5 Multiply
9.6 Solve
9.7 Next larger size breaker may be used if motor