Consumer Units and RCBOs

Embed Size (px)

Citation preview

  • 8/4/2019 Consumer Units and RCBOs

    1/12

    Greater

    protection

    UNDERSTANDING THE 17TH EDITIONCONSUMER UNITS / P RO DU CT G UI DE

  • 8/4/2019 Consumer Units and RCBOs

    2/12

    RCD* protection for increased safety, especially for

    the end-user in domestic installations...

    plus reduced likelihood of unwanted tripping by

    sensibly dividing the installation.(*with a rated residual current not exceeding 30 mA - Reg. 415.1.1)

    Simplifyingthe 17th EditionUnderstanding new regulations is never easy...

    thats why weve tried to make it as simple as

    possible.

    To comply with the 17th Edition, weve launched

    a selection of new dual RCD split load units with10 or 16 outgoing ways.

    Existing units can be easily upgraded for a

    17th Edition installation by replacing MCBs withRCBOs on unprotected ways.

    Summary ofchangesRegulation : 411.3.3

    Summary : Socket outlets forgeneral use in

    domestic installations

    require additional

    protection by an RCD*

    Regulation : 522.6.6522.6.7

    Summary : Cables buried in a wallor partition at a depth

    of less than 50 mmand not mechanically

    protected by

    appropriate earthed

    metal require

    additional protection

    by an RCD*

    Regulation : 701.411.3.3

    Summary : All circuits in locations

    containing a bath orshower shall be

    protected by one or

    more RCDs*

    Regulation : 314.1

    Summary : All circuits of aninstallation should not

    be connected to a

    single upstream RCD*

    in order to avoid

    unwanted tripping,

    hazards and minimise

    inconvenience in the

    event of a fault

    * not exceeding 30 mA

    2

  • 8/4/2019 Consumer Units and RCBOs

    3/12

    Split load

    Main switch incomer

    RCD incomer (ideal for immersion heating)

    D ua l R CD sp li t l oad w it h d ed icat ed ma in sw it ch ways Selec t MCB s and RCBO s t o complet e ins ta ll at ion

    Dual RCD split load Select MCBs to complete installation

    Select MCBs and RCBOs to complete installation

    Select RCBOs to complete installation

    Select MCBs to complete installation

    3

  • 8/4/2019 Consumer Units and RCBOs

    4/12

    A flexibleapproach tosafetyWith an array of design innovations and

    practical features making them easy to install,

    Legrands consumer units save valuable timeand money during installation... allowing you

    to reflect on the generous wiring space and the

    all-round extra protection.

    Combining elegance with efficiencyDesigned to match todays modern decor, the

    units offer a streamlined appearance allied with

    magnolia cases, allowing them to blend

    perfectly into their surroundings.

    Features include a removable panassembly, earth terminal holder that

    simply clips into place, and multiple

    cut-outs on the units back, bottom,

    top and sides.

    The units are supported by a selection

    of residential DX-E MCBs, offering

    faster installation with a single fixing

    clip and simple labelling using the

    pre-scored, pre-printed labels

    supplied with each consumer unit.

    4

  • 8/4/2019 Consumer Units and RCBOs

    5/12

    Design innovationsSimplifying installation and improving end user safety

    Rigid base with

    mult iple cut-outs

    Magnolia case with

    high f ire retardancy.

    Self ext inguishing at

    750C

    Removable terminal

    holders with screws in

    backed-off posit ion

    Clear, colour-coded

    labell ing system

    Smoked transparent

    door with smooth

    closing act ion

    Cut-to-length busbar

    for f lex ib le on-si te

    configurat ion

    Insulated shield

    Removable pan

    assemblyRail posit ioned

    for maximum

    cabling space

    Complete safety and peace of mind for instal ler and end user a l ike

    5

  • 8/4/2019 Consumer Units and RCBOs

    6/126

    consumer unitsinsulated and metal

    Dual RCD split load withdedicated main switch ways100 A main switch and

    2 x 80 A 30 mA RCD

    Dual RCD split load100 A main switch and

    2 x 80 A 30 mA RCD

    Split load100 A main switch and

    80 A 30 mA RCD

    Main switch incomer100 A main switch

    RCD incomer80 A 30 mA RCD

    Insulated consumer units

    Total outgoing ways

    Conform to BS EN 60439-3. Magnolia colour. Smoked transparent door opens downwardsSupplied with neutral and earth terminals completely assembled. Supplied with 5 module spare blank plateFactory fitted link leads for both neutral and live connections. Configurable outgoing ways

    Self-extinguishing at 750 C. UL 94 V2 material for improved flame retardancy. Robust thermoplastic construction. 4 fixing holes

    Metal consumer units

    Conform to BS EN 60439-3. Magnolia colour. Smoked transparent door opens downwardsSupplied with neutral and earth terminals completely assembled. Supplied with 5 module spare blank plateFactory fitted link leads for both neutral and live connections. Configurable outgoing waysPre-galvanised steel for strength and rigidity. Epoxy/polyester powder coated base and lid

    (1) Flush mounting

    6 8 10 12 14 16 18 20

    6075 74 6075 76

    6075 54 6075 56

    6075 32 6075 33 6075 34 6075 35 6075 36

    6075 11 6075 12 6075 14 6075 16

    6075 21 6075 22

    Dual RCD split load100 A main switch and

    2 x 80 A 30 mA RCD

    Split load100 A main switch and

    80 A 30 mA RCD

    Main switch incomer100 A main switch

    RCD incomer80 A 30 mA RCD

    Total outgoing ways

    6 8 10 12 14 16 18 20

    6065 54

    6065 56 6065 64(1)

    6065 32 6065 34 6065 36

    6065 11 6065 12 6065 14 6065 16

    6065 21 6065 22

    Dimensions (p. 9-10)

    Dimensions (p. 10-11)

  • 8/4/2019 Consumer Units and RCBOs

    7/12

    0032 70

    7

    6 A

    10 A

    16 A

    20 A

    32 A

    40 A

    50 A

    63 A

    Nominal rating (In)Numberof17.5 mmmodules

    1 0032 66 0033 82 1 6064 16 6064 22

    1 0032 68 0033 84 1 6064 17 6064 23

    1 0032 70 0033 86 1 6064 18 6064 24

    1 0032 71 0033 87 1 6064 19 6064 25

    1 0032 73 0033 89 1 6064 20 6064 26

    1 0032 74 0033 90 1 6064 21 6064 27

    1 0032 75 0033 91 1 6064 28 6064 29

    1 0032 76 0033 92

    protection devicesMCBs and RCBOs

    DX-E residential MCBs - 6 kASingle pole - 230/400 V

    RCBOs (combined MCB/RCD)Single pole and neutral - 240 V

    B curve C curve30 mANumberof

    17.5 mmmodules

    B curve C curve

    DX-E residential MCBs - 6 kABreaking capacity :6 kA to BS EN 60898-1

    RCBOs (combined MCB/RCD)Breaking capacity :10 kA to BS EN 61009-1

    RCD type AC conform toBS EN 61009-1

    Terminal capacity :rigid conductor 35mm2

    flexible conductor 25mm2

    6064 25

  • 8/4/2019 Consumer Units and RCBOs

    8/128

    consumer unitsinsulated, metal and accessories

    Insulated dual RCD split load -surface mounting

    16 module unit (10 ways available)

    1 6075 54 With 100 A main switch and 2 x 80 A 30 mA RCD

    22 module unit (16 ways available)

    1 6075 56 With 100 A main switch and 2 x 80 A 30 mA RCD

    Insulated with main switch incomer -surface mounting

    8 module unit (6 ways available)

    1 6075 11 With 100 A main switch

    12 module unit (10 ways available)

    1 6075 12 With 100 A main switch

    16 module unit (14 ways available)

    1 6075 14 With 100 A main switch

    22 module unit (20 ways available)

    1 6075 16 With 100 A main switch

    Insulated with RCD incomer -surface mounting

    8 module unit (6 ways available)

    1 6075 21 With 80 A 30 mA RCD

    12 module unit (10 ways available)

    1 6075 22 With 80 A 30 mA RCD

    Metal with RCD incomer -surface mounting

    8 module unit (6 ways available)

    1 6065 21 With 80 A 30 mA RCD

    12 module unit (10 ways available)

    1 6065 22 With 80 A 30 mA RCD

    Insulated split load - surface mounting

    12 module unit (8 ways available)

    1 6075 32 With 100 A main switch and 80 A 30 mA RCD

    14 module unit (10 ways available)

    1 6075 33 With 100 A main switch and 80 A 30 mA RCD

    16 module unit (12 ways available)

    1 6075 34 With 100 A main switch and 80 A 30 mA RCD

    20 module unit (16 ways available)

    1 6075 35 With 100 A main switch and 80 A 30 mA RCD

    22 module unit (18 ways available)

    1 6075 36 With 100 A main switch and 80 A 30 mA RCD

    Conform to BS EN 60439-3. Magnolia colour. Smoked transparent door opens downwardsSupplied with neutral and earth terminals completely assembled. Supplied with 5 module spare blank plateFactory fitted link leads for both neutral and live connections. Configurable outgoing waysInsulated units : Self-extinguishing at 750 C. UL 94 V2 material for improved flame retardancy. Robust thermoplastic construction. 4 fixing holesMetal units : Pre-galvanised steel for strength and rigidity. Epoxy/polyester powder coated base and lid

    6075 74 6075 54

    Dimensions (p. 9-11)

    Pack Cat. Nos. Metal dual RCD split load - surface mounting

    16 module unit (10 ways available)

    1 6065 54 With 100 A main switch and 2 x 80 A 30 mA RCD

    22 module unit (16 ways available)

    1 6065 56 With 100 A main switch and 2 x 80 A 30 mA RCD

    Metal with main switch incomer -surface mounting

    8 module unit (6 ways available)

    1 6065 11 With 100 A main switch

    12 module unit (10 ways available)

    1 6065 12 With 100 A main switch

    16 module unit (14 ways available)

    1 6065 14 With 100 A main switch

    22 module unit (20 ways available)

    1 6065 16 With 100 A main switch

    Metal split load - surface mounting

    12 module unit (8 ways available)

    1 6065 32 With 100 A main switch and 80 A 30 mA RCD16 module unit (12 ways available)

    1 6065 34 With 100 A main switch and 80 A 30 mA RCD

    22 module unit (18 ways available)

    1 6065 36 With 100 A main switch and 80 A 30 mA RCD

    Metal dual RCD split load - flush mounting

    16 module unit (10 ways available)

    1 6065 64 With 100 A main switch and 2 x 80 A 30 mA RCD

    Accessories

    Spare blank plate

    20 6075 89 5 modules - magnolia colour

    Spare busbar

    5 6075 99 21 prongs

    6065 54

    Pack Cat. Nos. Insulated dual RCD split load with dedicatedmain switch ways - surface mounting

    16 module unit (8 + 2 ways available)

    1 6075 74 With 100 A main switch and 2 x 80 A 30 mA RCD

    22 module unit (13 + 3 ways available)

    1 6075 76 With 100 A main switch and 2 x 80 A 30 mA RCD

  • 8/4/2019 Consumer Units and RCBOs

    9/12

    0032 73

    protection devicesMCBs and RCBOs

    Pack Cat. Nos. DX-E residential MCBs - 6 kA

    Breaking capacity : 6 kA to BS EN 60898-1

    Single pole - 230/400 V

    B curve C curve Nominal rating Number of (In) 175 mm modules

    10 0032 66 0033 82 6 A 110 0032 68 0033 84 10 A 110 0032 70 0033 86 16 A 110 0032 71 0033 87 20 A 110 0032 73 0033 89 32 A 110 0032 74 0033 90 40 A 110 0032 75 0033 91 50 A 110 0032 76 0033 92 63 A 1

    RCBOs (combined MCB/RCD)

    Breaking capacity : 10 kA to BS EN 61009-1

    RCD type AC conform to BS EN 61009-1Terminal capacity : rigid conductor 35 mm2

    flexible conductor 25 mm2

    Single pole and neutral - 240 V

    B curve C curve Nominal rating Number of (In) 175 mm modules

    30 mA1 6064 16 6064 22 6 A 11 6064 17 6064 23 10 A 11 6064 18 6064 24 16 A 11 6064 19 6064 25 20 A 11 6064 20 6064 26 32 A 11 6064 21 6064 27 40 A 11 6064 28 6064 29 50 A 1

    insulated consumer unitssurface mounting

    9

    B

    A 110

    50

    195

    I Insulated - surface mounting dimensions (mm)

    225

    114

    162

    6 cut-outs

    20 x 25

    8 cut-outs

    25 x 25

    6 cut-outs 20 x 25

    2 cut-outs

    50 x 50

    2 cut-outs

    40 x 50

    40 5

    0

    20

    2 cut-outs

    20 x 25

    I 8 module unitBack box fixing centres and cable entries (mm)

    Modules A (mm) B (mm)

    8 212 225

    12 298 225

    14/16 370 225

    20/22 478 225

    View fromsides

    View frombelow

    View fromabove

    225

    180

    268

    2 cut-outs

    50 x 50

    2 cut-outs

    40 x 50

    40 5

    0

    20

    6 cut-outs

    20 x 25

    2 cut-outs

    20 x 18.5

    2 cut-outs 20 x 18.5

    22 cut-outs

    25 x 20

    2 cut-outs 20 x 25

    2 cut-outs

    20 x 25

    I 12 module unitBack box fixing centres and cable entries (mm)

    View fromsides

    View frombelow

    View fromabove

    6064 16

  • 8/4/2019 Consumer Units and RCBOs

    10/1210

    insulated consumer unitssurface mounting (continued)

    metal consumer unitsflush mounting

    B230

    50

    A 113 min.

    97 min.

    132 max.

    200 min.

    234 max.

    4 cut-outs 32

    6 cut-outs 20

    4 cut-outs 25

    84

    84

    260

    372

    340

    120

    2 obround

    cut-outs

    100 x 50

    2 cut-outs 20

    I 16 module unit

    Back box fixing centres and cable entries (mm)

    Modules A (mm) B (mm)

    16 402 260

    I Metal - flush mounting dimensions (mm)

    View fromsides

    View fromabove

    40 5

    0

    20

    10 cut-outs 20 x 25

    2 cut -outs 50 x 50 2 cut-ou ts 40 x 50

    30 cut-outs 25 x 20

    225

    180

    340

    8 cut-outs 20 x 25

    2 cut-outs

    20 x 25

    I 14/16 module unitBack box fixing centres and cable entries (mm)

    I 20/22 module unitBack box fixing centres and cable entries (mm)

    View fromsides

    View frombelow

    View fromabove

    10 cut-outs 20 x 252 cut-outs 20 x 22

    2 cut-outs 20 x 22 12 cut-outs 20 x 25 42 cut-outs 25 x 20

    225

    180

    448

    2 cut-outs

    20 x 25

    40 5

    0

    20

    2 cut-outs 50 x 50 2 cut-outs 40 x 50

    View fromsides

    View frombelow

    View fromabove

    View frombelow

  • 8/4/2019 Consumer Units and RCBOs

    11/12

    metal consumer unitssurface mounting

    4 cut-outs 32

    1 cut-out 25

    5

    9

    1 obround

    cut-out 100 x 50

    4

    3

    95

    80

    100

    I 8 module unit

    Back box fixing centres and cable entries (mm)

    4 cut-outs 32

    2 cut-outs 252 cut-outs 20

    1 obround

    cut-out 100 x 50

    95

    80

    175

    100

    I 12 module unit

    Back box fixing centres and cable entries (mm)

    4 cut-outs 20

    4 cut-outs 324 cut-outs 25

    2 obround

    cut-outs 100 x 50

    95

    80

    250

    120

    175

    I 16 module unit

    Back box fixing centres and cable entries (mm)

    4 cut-outs 25

    4 cut-outs 328 cut-outs 20

    2 obround

    cut-outs 100 x 50

    95

    80

    350

    120

    275

    I 22 module unit

    Back box fixing centres and cable entries (mm)

    View frombelow

    View fromabove View from

    below

    View from

    above

    View frombelow

    View fromabove

    View frombelow

    View fromabove

    11

    B

    A 113

    50

    200

    Modules A (mm) B (mm)

    8 219 235

    12 305 235

    16 377 235

    22 485 235

    I Metal - surface mounting dimensions (mm)

  • 8/4/2019 Consumer Units and RCBOs

    12/12

    Customer Services :

    Tel : 0845 605 4333 Fax : 0845 605 4334

    E-mail : [email protected]

    Technical Support :

    Tel : 0870 608 9020 Fax : 0870 608 9021

    E-mail : [email protected]

    Head office :Legrand Electric LimitedGreat King Street North, Birmingham, B19 2LFTel : 0870 608 9000 Fax : 0870 608 9004

    Website : www.legrand.co.uk 02977-Consumerunitproductguide01/2009.1

    5K

    The Bticino, Cablofil, Electrak, Legrand, Ortronicsand Zucchini logos are trademarks of the Legrandgroup of companies.

    Powered by specialistsThe Legrand Group is the worlds leading manufacturer of wiring devices and cable management systems. Through

    its specialist brands Bticino, Cablofil, Electrak, Ortronics and Zucchini, the Legrand Group also offers cutting edge

    solutions in door entry, connectivity and power distribution.

    Products and systems for electrical

    installations and information networks...

    a specialist in wiring devices, cable

    management, protection devices and

    industrial solutions.

    Tel: 0845 605 4333 Fax: 0845 605 4334

    Email: [email protected]

    Web: www.legrand.co.uk

    Bticino systems present key developers

    with innovative and bespoke door entry

    solutions, supported by pre-sales design

    and enhanced service options.

    Tel: 0845 605 4333 Fax: 0845 605 4334

    Email: [email protected]

    Web: www.bticino.co.uk

    A pioneer of the steel wire cable tray

    system, Cablofil is now one of the worlds

    leading cable management brands for

    both data and power solutions.

    Tel: 0845 130 4628 Fax: 0845 130 4629

    Email: [email protected]

    Web: www.cablofil.co.uk

    Ortronics is a global leader in structured

    cabling systems, offering solutions for

    Cat 5e, Cat 6,10 Gig copper, fibre optic

    and high capacity installations.

    Tel: 0121 515 0669 Fax: 0121 515 0667

    Email: [email protected]

    Web: www.ortronics.co.uk

    Zucchini offers comprehensive power

    distribution ranges, including busbar

    trunking systems from 25 A through to

    6300 A and EdM cast resin transformers

    from 100 kva to 315 mva

    Tel: 0121 458 7070 Fax: 0121 459 7171

    Email: [email protected]

    Web: www.zucchini.uk.com

    Electrak is a leading manufacturer of

    power distribution and lighting control

    solutions. Its power track, floor boxes,

    and desk modules are installed in high

    specification offices around the world.

    Tel: 01207 503400 Fax: 01207 501799

    Email: [email protected]

    Web: www.electrak.co.uk

    Cablofil is part of the Legrand Group and operates independently in the United Kingdom.