Conventional fire alarm system products 1 / 16 Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808 Conventional fire alarm control panel AW-CFP2166 Introduction: 1. AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard. 2. It is modularized design, the panel can extend from 1 zone to 32 zones easily. 3. It has 2 level control mode by a lock 4. It has 24VDC and 5VDC power supply output. 5. It has FIRE and FAULT signal output. 6. It has 2 general sounders output. 7. Each zone has 1 circuit detectors input . 8. Each zone can be disable by a button. 9. It has RESET button to reset the panel. 10. It has SILENCE button to stop BUZZER and SOUNDERS. 11. It has EVACUATE button to start a manual fire alarm immediately. 12. It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on. 13. It has an optional GSM module for fire alarm by SMS . 14. It is economic, user-friendly and easy maintenance. Parameters:

Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

  • Upload
    doannhu

  • View
    340

  • Download
    21

Embed Size (px)

Citation preview

Page 1: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 1 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

Conventional fire alarm control panel

AW-CFP2166

Introduction:

1. AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4

standard.

2. It is modularized design, the panel can extend from 1 zone to 32 zones easily.

3. It has 2 level control mode by a lock

4. It has 24VDC and 5VDC power supply output.

5. It has FIRE and FAULT signal output.

6. It has 2 general sounders output.

7. Each zone has 1 circuit detectors input .

8. Each zone can be disable by a button.

9. It has RESET button to reset the panel.

10. It has SILENCE button to stop BUZZER and SOUNDERS.

11. It has EVACUATE button to start a manual fire alarm immediately.

12. It has battery low protection function, when battery voltage lower than 21VDC, battery will

be cut off automatically until the mains power is on.

13. It has an optional GSM module for fire alarm by SMS .

14. It is economic, user-friendly and easy maintenance.

Parameters:

Page 2: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 2 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

ITEM 1Zone panel 2Zone panel 4-8 Zone panel 12-32 Zone

panel

Model No. AW-CFP2166-01 AW-CFP2166-02 AW-CFP2166-04-

8

AW-CFP2166-

12-32

Power

specification

Mains supply

voltage

110VAC or 240VAC

Internal power

supply

27.2VDC

Total output

current limited

500mA @

240VAC

500mA @

240VAC

3A @ 240VAC 3A @ 240VAC

Main supply

monitor for fault

Yes

Battery

protection for

low voltage

Yes

Batteries (default

configuration)

12V2AH*2

Detector circuit

specification

Number of

circuit

1 2 4-16 4-32

Line fault

monitor for open

circuit

Yes

Line fault

monitor for short

circuit

Yes

Line fault

monitor for

detector removal

Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor

End of Line

device

6.8k Ω ,5% tolerance, 0.25W (colour code-blue,grey,red,gold)

Detector

continuity diodes

Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit

fitted to give Detector Removal Fault)

Call point resistor

value

470 to 680 Ω , 0.225 or 0.5 watt

Maximum

number of

smoke/heat

20 (based on a total detector current of 2mA, each detector consuming

100μ A).Note: if End of Line Monitor Unit is fitted, for correct operation

maxmum voltage drop must not exceed 12 volts.

Page 3: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 3 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

detectors per

zone

Maximum

number of

manual call

points per zone

No limit

Sounder circuit

specification

Number of

general circuits

2

End of line

resistor value

6.8k Ω ,5% tolerance, 0.25W (colour code-blue,grey,red,gold)

Line fault

monitor for open

circuit

Yes

Line fault

monitor for short

circuit

Yes

Outputs fused AT 400mA

Maximum

number of bells

@ 20mA of each

sounder output

20

Fuses

Battery fuse 1.5A F 20mm

Sounder outputs 500mA F 20mm

Fire and fault

output

Output type NC and NO relay

Maximum

current

100mA

Connection

block

Largest

acceptable

conductor size

2.5mm2

Smallest

acceptable

conductor size

0.75mm2

Size and weight

Dimensions(mm) 272*200*70mm 320*231*90mm 395X502X124 362X565X124

Page 4: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 4 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

Weight (without

batteries)

4kg 5kg 7kg 8kg

Weight (with

batteries)

5.8kg 6.8kg 9.6kg 12.5kg

Conventional smoke detector

More sensitive than old type!

Model No.:AW-CSD311

Item Parameters

Operating Voltage Range: 9 to 28 VDC Volts Non-polarized

Standby Current: ≤120µA @ 24 VDC

Maximum Alarm Current (LED on: ) ≤15mA @ 24 VDC

Operating Humidity Range: <=95% Relative Humidity, Non-condensing

Operating Temperature Range: -10 to 50 °C

Smoke Alarm Sensitivity: 1.06±.26%FT Height: 48.2 mm installed in Base Diameter: 99.45 mm

Page 5: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 5 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

Conventional fix temperature heat detector

\

Model No.: AW-CTD321

Item Parameters Operating Voltage Range: 9 to 28 VDC Volts Non-polarized Standby Current: ≤120µA @ 24 VDC Maximum Alarm Current (LED on: ) ≤15mA @ 24 VDC

Operating Humidity Range: <=95% Relative Humidity, Non-condensing

Operating Temperature Range: -10 to 50 °C Fix temperature Alarm: 57° C (135° F) A1R Rate of rise Alarm: 7.1° C/5S A1R Height: 48.2 mm installed in Base

Diameter: 99.45 mm

Page 6: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 6 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

Standalone smoke detector

Model number:AW-SSD603

Item Parameters

Operating Voltage Range: DC9V

Standby Current: ≤10uA@DC9V

Maximum Alarm Current (LED on: ) ≤20mA@DC9V

Operating Humidity Range: 0%~93%RH

Operating Temperature Range: -10 C ~ +50 C

Sensitivity: Adjustable Diameter: 106mm * Deep 35mm

Weight: 5.5 oz. (187 g)

Standalone smoke detector

Page 7: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 7 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

AW-SSD701

Item Parameters

Operating Voltage Range: DC9V

Standby Current: ≤10uA@DC9V

Maximum Alarm Current (LED on: ) ≤20mA@DC9V

Operating Humidity Range: 0%~93%RH

Operating Temperature Range: -10 C ~ +50 C

Sensitivity: Adjustable Diameter: 106mm * Deep 35mm

Weight: 5.5 oz. (187 g)

Conventional smoke and heat combined detector

Page 8: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 8 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

Model No.: AW-CSH831

Item Parameters

Operating Voltage Range: 9 to 28VDC Volts Non-polarized

Standby Current: ≤60µA @ 24 VDC Maximum Alarm Current (LED on: ) ≤30mA @ 24 VDC

Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range: 14°F to 120°F (-10°C to 49°C) Smoke Sensitivity: 1.06±.26%FT.

Fixed Temperature Rating: 135°F (57°C)

Rate of Rise Detection: Responds to greater than 15°F/min

Height: 2.2˝ (55 mm) installed in Base

Diameter: 4.0˝ (103 mm)

Weight: 5.5 oz. (155 g)

Entrance LED

Model No.:AW-EL2166

Manual Call Point

Page 9: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 9 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

Model No. Photo Parameters

AW-CMC2166-

1

(Break glass)

Working voltage:

220VAC/50Hz or 24VDC

Maximum current:

5A (220VAC/50Hz) or

8A(24VDC)

Contactor resistance: ≤0.1

Ω

Working temperature:

-10~+50 ℃

Relative humidity: max ≤93

±2%

AW-CMC2166-

5

Bell AW-CBL2166-A

(with iron base)

Page 10: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 10 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

Bell Base

Model No. Diameter Work voltage

Work

current @

24VDC

Volume(dB)

AW-CBL2166-A-4 4” (100mm) DC6V

DC12V

DC24V

AC110V

AC230V

25 mA

95

AW-CBL2166-A-6 6”(150mm) 100

AW-CBL2166-A-8 8”(200mm) 100

Note: default is including the base.

Strobe Horn/Hooter

Page 11: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 11 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

AW-CSS2166-2

Parameters:

AW-CSS2166-2

Work Voltage DC20V-DC30V

Work Current (average) 95mA

Flash intensity ≥1.2WS

Flash cycle <2.0s

Flasher life ≥30000times

Max alarm volume ≥100dB

Alarm voice A: pokice car

B: Fire Truck ( default)

C: Ambulance

Size 160*128*54mm 134*115*48mm

Flash light

Model No.: AW-CBL2166

Item Parameters

Color red (default),green, yellow,blue

Work voltage 12VDC, 24VDC(default)

Light head diameter 65mm

Page 12: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 12 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

Beam smoke detector

AW-BK901

Technical Parameters

Model Number AW-BK901

Standard

Compliance EN54-12

Fire Detection and Alarm Systems BS 5839 Part 1:2002

Specifications

Operating Voltage 20 V to 28 V DC

Current Parameters Standby:23mA Commission:40mA Alarm:33mA

Beam Sensor Sensitivity [via

Encoder]

Level 1: 2.6 dB High Sensitivity

Level 2: 3.4 Medium Sensitivity

Level 3: 4.8 dB Low Sensitivity

Beam Path Angle ±0.5ºirectional

Alignment Guide Laser Beam Pointer

Digital Display Guide Nixie Tube

LED Indicator Guide Red: Fire ; Yellow: Fault ; Green:

Alignment

Reset Time Less than 2 Second

Relay Capacity [Fire & Fault] Normally Open/ 2.0 A; 30 VDC

Physical

Page 13: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 13 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

Material / Color ABS / White

Dimension / Weight L:190.87 x W:126.87 x H:91.96 mm

/ 440 gm

Weight 0.130 Kg with base

Environmental

Operating Temperature / Protection -10°C to 55°C / IP30 [IP66 glue seal]

Rating

Humidity 0 to 95% Relative Humidity, Non

condensation

UV flame detector

AW-FD602-UV

SPECIFICATIONS

Operating Voltage Range: 12 to 30 VDC Volts Standby Current: ≤10 mA @ 24 VDC Alarm Current ≤30 mA @ 24 VDC Spectrum: 180~290nm

Page 14: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 14 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

Detection Angle: 110 degree Detection Sensitivity: Grade I, 25m@flame (Container 33cmX33cm,Height 5cm with 2Kg ethanol ) Relay Contact Load: 1A@DC24V Normal Status: LED blinking in 5 seconds interval Alarm Status: LED lit steady Protection rating: IP 32 Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing Operating Temperature Range: -10°C to 50°C (14°F to 122°F) Height: 1.8˝ (45 mm) installed in Base Diameter: 4.0˝ (103 mm) Weight: 5.4 oz. (153g)

FIGURE1 Vertical Detection Angular Sensitivity(Directivity)

FIGURE2 Horizontal Detection Angular Sensitivity(Directivity)

ANODE

CATHODE

90

60 60

30 3 0

0

90

10 0%

80

60

40

20

VERTICAL VIEWING

90

60 60

30 30

0

90

100%

80

60

40

20

ANODE

CATHODE HORIZONTAL VIEWING

VERTICAL VIEWING

HORIZONTAL VIEWING

UV EMISSION POINT

VERTICAL VIEWING

HORIZONTAL VIEWING

UV EMISSION POINT

Page 15: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 15 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

GSM MODULE

System Introduction

Wireless GSM intelligent anti-theft electronic alarm system is an innovative wireless

mobile intelligent warner integrating GSM digital signal processing techniques and

imported STCmicroprocessor, and a variety of technologies including digital voice

announcer, English SMS,learning code, etc.In addition, this alarm system is highly

automatic, giving automatic voice or SMS alert in theevent of emergency without

intensive manual settings required. Features of stability, reliability,safety, and

humanizing control enable it to be widely used for alert in shops, convenience

stores,offices, villa as well as residential communities

Infrared detector installation

The principle of infrared detectors is to sense people’s movement through sensing

Page 16: Conventional fire alarm control panel AW-CFP2166awsafe.weebly.com/uploads/5/2/8/0/52809879/2166_conventional_fire... · It has an optional GSM module for fire alarm ... Line fault

Conventional fire alarm system products 16 / 16

Asenware Ltd. Address: Room 701,Bd8,Dongfangming industry zone,Dabao Rd, Baoan, Shenzhen,China-518101 Email :[email protected] Skype:Asenware-Ana Mobile :+86-136-3251-2808

infrared signals generated by bodies and the detection range is usually 5-12 meters.

Infrared sensor should be installed about 2.2 meters away from ground. Aim straight

at the detection ranges.Moreover, the infrared detector can be only installed in the

room, without facing the sunshine,windows and other places where temperature is

easy to change, because the installed location may influence the detection range and

accuracy.