18
Cool Ideas for your Refrigeration System Zaid Al-Chalabi, P.Eng Energy Management Consultant Dr. Constantin Pitis, P.Eng Specialist Engineer

Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Cool Ideas for your Refrigeration System

Zaid Al-Chalabi, P.Eng

Energy Management Consultant

Dr. Constantin Pitis, P.Eng

Specialist Engineer

Page 2: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

00 5% 10% 15% 20% 25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 75%

of Refrigeration LOAD is Non-Productive

Up to

Varies based on facility type and operating conditions

Page 3: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Presentation Objectives

1. Understanding Refrigeration Systems

2. Benchmarking your Facility Energy Segregation based on Facility types

Equipment Segregation

Refrigeration Loads

Energy Usage Intensity (EUI)

New Concept: Benchmark Energy Factor (BEF)

3. Energy Efficiency Opportunities

Page 4: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Industrial Refrigeration in BC

Estimated Energy consumption for Cooling & Refrigeration

Systems ≈ 485 GWh/year or about 50,000 homes

Facility Types: Cold Storage, Distribution, Processing

Estimated Energy Savings Potential

≈ 75 GWh/year ≈ $4,500,000 per year

Extrapolated based on BC Hydro Conservation Potential Report (CPR) 2007

Page 5: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Vapor-Compression Cycle

Outdoor Fan

Compressor

Ambient conditions

Condenser Coils

Battery Charging

for forklifts

Conditioned Environment

Indoor Fan

Indoor Lighting

Evaporator Coils

High pressure high temp. vapor

Low pressure low temp. liquid + vapor

Low pressure low temp. vapor

High pressure high temp. liquid

Expansion Valve

High Pressure

Side

Low Pressure

Side

C

Underfloor Heating

(Freezers)

Cold Storage

Infiltration Load

Product Product

Product Heat Load

Insulated Walls

Access Doors

Waste Heat

Cold Air Warm Air

Refrigerant Line

Refrigeration Energy

Heat Load

Page 6: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Equipment Segregation

Refrigeration Energy

Compressor

Condenser + Fan motor

Evaporator + Fan motor

Special Refrigerated Processes

(i.e. cooling tunnels) – if applicable

Cold Storage Lighting

Expansion Valve (metering device)

Access Doors

Non-Refrigeration Energy

Office Space HVAC/Lighting

Dry Storage HVAC/Lighting

Non-refrigerated Processes

(if applicable)

Forklift Battery Chargers

Underfloor Heating

(freezers)

Other

Page 7: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Energy Segregation

Non-Refrigeration

Energy

Total Metered

Energy

Refrigeration

Energy

Product

Cooling

Non-Refrigeration Energy

varies based on Facility Type

(10…50%)

Essential

Energy

Wasted Energy

Wasted Energy can be reduced by

applying Energy Conservation

Measures

Minimum Energy Required

to meet refrigeration load

Total Metered

Energy

Based on internal pilot testing on sample site

Page 8: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Energy Segregation on Facility Types

Facility Type Refrigeration

Energy (%)

Non-Refrigeration

Energy (%)

1 Distribution Facility 60 40

2 Storage Warehouse 90 10

3 Processing + Storage 80 20

4 Refrigerated Processing +

Storage 65 35

Based on internal pilot testing on sample sites

Page 9: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Refrigeration Load for Distribution Facilities

Envelope/Infiltration (56…70%)

Product (14…20%)

Lighting (8…12%)

Evaporator Fan (8…12%)

Refrigeration

Energy

(Load)

Based on internal pilot testing on sample site

Page 10: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Product Load: Volume Vs Weight

𝑷𝒓𝒐𝒅𝒖𝒄𝒕 𝒄𝒐𝒐𝒍𝒊𝒏𝒈 𝒍𝒐𝒂𝒅 ≈ 𝑾𝒆𝒊𝒈𝒉𝒕 ∗ 𝑪 ∗ ∆𝑻

Fruit Cases Meat Cases

Volume = 1 m3

Weight = 300 kg C = 3.4 kJ/kg.C

ΔT = 3оF

Volume = 1 m3

Weight = 700 kg C = 3.6 kJ/kg.C

ΔT = 3оF

Heavier products costs more to cool!

Product load TWICE as

high

Page 11: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Energy Use Intensity (EUI)

Traditional approach in assessing facility performance: kWh per cubic foot

𝑬𝑼𝑰 =𝑻𝒐𝒕𝒂𝒍 𝑴𝒆𝒕𝒆𝒓𝒆𝒅 𝑬𝒏𝒆𝒓𝒈𝒚

𝑺𝒑𝒂𝒄𝒆 𝑽𝒐𝒍𝒖𝒎𝒆

EUI does NOT accurately assess your facility’s performance because:

Assumes Total Metered Energy = Refrigeration Energy

Does not take into account Independent Variable Parameters:

Facility Type and Layout

Product Type and Quantity (kg)

Product and Space Temperatures

= 𝑅𝑒𝑓𝑟𝑖𝑔. 𝐸𝑛𝑒𝑟𝑔𝑦 + 𝑁𝑜𝑛. 𝑅𝑒𝑓𝑟𝑖𝑔. 𝐸𝑛𝑒𝑟𝑔𝑦

Varies based on Facility Type

(10%…50%)

Page 12: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Benchmark Energy Factor (BEF)

New approach in assessing facility performance: Unit-less Value

𝑩𝑬𝑭 =𝑹𝒆𝒇𝒓𝒊𝒈𝒆𝒓𝒂𝒕𝒊𝒐𝒏 𝑬𝒏𝒆𝒓𝒈𝒚

𝑬𝒔𝒔𝒆𝒏𝒕𝒊𝒂𝒍 𝑬𝒏𝒆𝒓𝒈𝒚

Example

Site No.* 𝑩𝑬𝑭 =

𝑹𝒆𝒇𝒓𝒊𝒈. 𝑬

𝑬𝒔𝒔𝒆𝒏𝒕𝒊𝒂𝒍 𝑬. 𝑬𝑼𝑰 =

𝑻𝒐𝒕𝒂𝒍 𝑬.

𝑽𝒐𝒍𝒖𝒎𝒆

1 4.8 (Poor Efficiency) 0.46 (Good Efficiency ?)

2 3.5 (Good Efficiency ) 0.85 (Poor Efficiency ?)

BEF method takes into account Independent Variable Parameters such as:

Facility Type

Product Type and Weight

Facility Layout and Location

Operating hours

Space and Product Temperatures

= 𝑇𝑜𝑡𝑎𝑙. 𝑀𝑒𝑡𝑒𝑟𝑒𝑑. 𝐸𝑛𝑒𝑟𝑔𝑦 − 𝑁𝑜𝑛. 𝑅𝑒𝑓𝑟𝑖𝑔. 𝐸𝑛𝑒𝑟𝑔𝑦

Minimum Energy required to meet refrigeration load

*Based on internal pilot testing for sample sites

Page 13: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Monitoring Energetic Performance

Energy Conservation Measure: VFDs on Evaporator Fan Motors

Energy Savings = 206,000 kWh (4 month period)

0

100,000

200,000

300,000

400,000

500,000

600,000

700,000

May June July August September October November December January February March April

kW

h

Month

Wasted Energy

After (2014)

Essential Energy

Before (2013)

Based on internal pilot testing on sample site

ECM implemented

Page 14: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Refrigeration Energy

Efficient Measures

Energy Efficient Measure Potential System Energy Savings

Cost to Implement

High Speed Doors 2-10% Low

High Efficiency Lighting and Controls 5-20% Medium

Variable Frequency Drives on Compressor 10-20% High

Variable Frequency Drives (or EC Motors) on Evaporator/Condenser Fans

2-5% Low-Medium

Central Control System 5-15% Low-Medium

Floating head pressure control 3-12% Low

Sources: (1) Historical Power smart Projects. (2) Wisconsin State Utilities

Potential Refrigeration Energy Savings: up to 45%

Page 15: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Non-Refrigeration Energy

Efficient Measures

Energy Efficient Measures Potential Energy

Savings Cost to

Implement

Potential Non-Refrigeration Energy Savings: up to 35%

Source: (1) Historical Power smart Projects. (2) California Utility Company

Heat Recovery for Underfloor Heating (freezers)

5-10% Low-Medium (new plant)

Forklift Battery Chargers 5-15% Low-Medium

Dry Storage/Other Areas HVAC Upgrades 5-15% Medium

Dry Storage/Other Areas Lighting Upgrade 5-10% Medium

Page 16: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Energy Efficiency Benefits

Energy efficiency can deliver a range of savings, such as:

• Reduced energy costs

• Reduced operation and maintenance costs

• Improved system reliability

• Improved safety

• Increased productivity

• Matching of refrigeration load and equipment capacity

• a better working environment

Page 17: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Summary of Cool Ideas

1. Total Metered Energy = Refrig. Energy + Non.Refrig. Energy

2. Non-Refrigeration Energy varies based on Facility Type

3. Essential Energy = Minimum energy required to meet Refrig. load

4. Product weight is equally important to know as type and quantity

5. Energy Use Intensity (EUI) is not an accurate method to assess facility performance

6. New Concept: Benchmark Energy Factor (BEF) takes into account independent variable parameters

Page 18: Cool Ideas for your Refrigeration System - BC Hydro...Industrial Refrigeration in BC Estimated Energy consumption for Cooling & Refrigeration Systems ≈ 485 GWh/year or about 50,000

Thank You!

Email: [email protected]

Zaid Al-Chalabi, P.Eng

#psforum15

Email: [email protected]

Dr. Constantin Pitis, P.Eng