CA-A360-A RS-485 to RS-232 Converter RS-485 to next controller To PC USB port or RS-232 Port GALEO Wiegand Keypad 2 DGLP/FW Proximitry Reader 1 CT-V900-A 2-Door Controller Keypad 2 Keypad 1 To PC RS-232 Port using DB-9F Reader and keypad wiring may differ from diagram. Please consult your dealer for details. Up to 16 inputs per controller Connect Earth Terminal to Cold Water Pipe Connect to RS-232 PC port if 6-pin modular jack is not used. GEL Type Battery 12Volt, 7Ah GEL Type Battery 12Volt, 7Ah Relay 1 GND GND LK1+ LK2+ LK1- LK2- +24V UNLK1 LED1 LED2 UNLK2 +24V C1 C2 NO1 NO2 NC1 NC2 Relay 2 Fire alarm contact for Lock 1 & 2 Door Strike 1 + - Door Strike 2 + - + - Electromagnetic Lock 1 Electromagnetic Option Electromagnetic Lock 2 + - + - + - Power Supply Power Supply Door Strike Option 1 2 3 5 6 Maximum length 25 feet Input 1 1K Ohm Input 2 2.2K Ohm CA-A110-P Lock Control Module Using CA-A360-USB RS-485 to USB or RS-232Converter Or Always consult the regulatory agency in your area for existing regulations regarding doors designated as emergency exits. 4 TECHNICAL SUPPORT CDV Americas Tel: (450) 682-7945 • Toll free: (866) 610-0102 www.cdvamericas.com Equipment Wire Type Size Max. Length Card reader (1 LED or 1 LED & Buzzer) and Wiegand keypad 6 conductors, stranded, shielded (foil), drain conductor, Belden: 5304FE 18AWG 150m (500ft.) Card reader (2 LEDs & Buzzer) 8 conductors, stranded, shielded (foil), drain conductor, Belden: 5306FE 18AWG 150m (500ft.) Zone input 4 conductors, copper (JKT) 22AWG 600m (2000ft.) Door strike and AC transformer for controller 2 conductors, solid copper 18AWG Door strike: 150m (500ft.), AC transformer: 8m (25ft.) RS-485 bus Ethernet CAT 5 e , 4 pairs 24AWG 1220m (4000ft.) 1 OFF OFF OFF OFF OFF OFF 2 ON OFF OFF OFF OFF OFF 3 OFF ON OFF OFF OFF OFF 4 ON ON OFF OFF OFF OFF 5 OFF OFF ON OFF OFF OFF 6 ON OFF ON OFF OFF OFF 7 OFF ON ON OFF OFF OFF 8 ON ON ON OFF OFF OFF 9 OFF OFF OFF ON OFF OFF 10 ON OFF OFF ON OFF OFF 11 OFF ON OFF ON OFF OFF 12 ON ON OFF ON OFF OFF 13 OFF OFF ON ON OFF OFF 14 ON OFF ON ON OFF OFF 15 OFF ON ON ON OFF OFF 16 ON ON ON ON OFF OFF 17 OFF OFF OFF OFF ON OFF 18 ON OFF OFF OFF ON OFF 19 OFF ON OFF OFF ON OFF 20 ON ON OFF OFF ON OFF 21 OFF OFF ON OFF ON OFF 22 ON OFF ON OFF ON OFF 23 OFF ON ON OFF ON OFF 24 ON ON ON OFF ON OFF 25 OFF OFF OFF ON ON OFF 26 ON OFF OFF ON ON OFF 27 OFF ON OFF ON ON OFF 28 ON ON OFF ON ON OFF 29 OFF OFF ON ON ON OFF 30 ON OFF ON ON ON OFF 31 OFF ON ON ON ON OFF 32 ON ON ON ON ON OFF 33 OFF OFF OFF OFF OFF ON 34 ON OFF OFF OFF OFF ON 35 OFF ON OFF OFF OFF ON 36 ON ON OFF OFF OFF ON 37 OFF OFF ON OFF OFF ON 38 ON OFF ON OFF OFF ON 39 OFF ON ON OFF OFF ON 40 ON ON ON OFF OFF ON 41 OFF OFF OFF OFF OFF ON 42 ON OFF OFF OFF OFF ON 43 OFF ON OFF OFF OFF ON 44 ON ON OFF OFF OFF ON 45 OFF OFF ON OFF OFF ON 46 ON OFF ON OFF OFF ON 47 OFF ON ON OFF OFF ON 48 ON ON ON OFF OFF ON 49 OFF OFF OFF OFF ON ON 50 ON OFF OFF OFF ON ON 51 OFF ON OFF OFF ON ON 52 ON ON OFF OFF ON ON 53 OFF OFF ON OFF ON ON 54 ON OFF ON OFF ON ON 55 OFF ON ON OFF ON ON 56 ON ON ON OFF ON ON 57 OFF OFF OFF ON ON ON 58 ON OFF OFF ON ON ON 59 OFF ON OFF ON ON ON 60 ON ON OFF ON ON ON 61 OFF OFF ON ON ON ON 62 ON OFF ON ON ON ON 63 OFF ON ON ON ON ON 64 ON ON ON ON ON ON ON OFF DEF/RUN 9.6K/19.2K ADD 32 ADD 16 ADD 8 ADD 4 ADD 2 ADD 1 1 2 3 4 5 6 7 8 Controller address BATT ON: When the jumper is “ON”, the controller enables the RAM and RTC battery backup (default = ON). Once the controller is installed, remove the battery protection tab for correct operation. If you are required to replace the 3V backup battery, we recommend that you set the jumper to “OFF” until the battery is replaced. Note however, if a complete power loss occurs, the time and date as well as all controller programming will be lost. EOL (CONTROLLER NETWORK): Places the EOL termination of the main controller network in circuit (default = off). Jumper should only be on when the controller is the last controller in the network. HIGH/LOW (NETWORK IMPEDANCE): Select the impedance of the RS-485 network (default = high). Set both jumpers to high when running normally. When running the Centaur software and connecting directly to the 9-pin serial port, you must set both jumpers to low. 12V/24V (LOCK #1 & LOCK #2): Selects the output voltage of the “LK1+” & “LK2+” terminal when the Lock#1 and Lock#2 relay is active (default = 12V). When the jumper is on pins 1 & 2 the output will be 12V. If the jumper is on pins 2 & 3 the output will be 24V. EOL (E-BUS NETWORK): Places the EOL termination of the controller’s E-Bus network in circuit (default = on). If the controller is at the end of the E-Bus network, the jumper should be on. If the controller is in the middle of the E-Bus network, the jumper must be off. HIGH/LOW (E-BUS IMPEDANCE): Select the impedance of the E-bus for the RS-485 (default: low). Set to low when running normally. Set to high when running special E-Bus devices. Max. Current: 2.5A AC Loss Indicator: Yes Operating Temperature: 5°C to 55°C (41°F to 133°F) Inputs: 2 readers inputs (multiple protocol support) 2 Wiegand and/or BCD Keypads 8 Multi-Purpose using N.C. or 16 using ATZ with 2R/3R Controller Tamper: Normally Closed (N.C.) Outputs: 2 Lock Outputs: 350mA @12/24VDC 2 Form “C” Relays: 5A 30VDC Resistive (Expandable to 16 with CA-A460-P) 6 Open Collector 25mA Sink System Autonomy: 100% Off-line Operation Controller Network: RS-485/232 @ 9.6K baud/19.2K baud Max. Distance: 1220m (4000ft.) E-Bus and Network Bus On-Board Protection: 24VDC: 2.5A Fuseless Protection 12VDC: 1A Fuseless Protection 5VDC: 1A Fuseless Protection AC Protection: 5A Fuse Battery Protection: 7A Fuse Fuse Failure Indication: Event Generation and LED Display on ALL supplies Battery Backup: Battery capacity: Two 12VDC, 7Ah Low Battery @: 21.6VDC Low Battery Restore @: 24.1VDC Low Battery Cut-Off @: 18.5VDC Firmware: On-Line Upgradable Reset to factory default (default= RUN) 2-Door Controller CT-V900-A Diagram Connection 1 2 3 4 5 6 Specifications may change without prior notice. Printed in Canada 15/12/2006 SPECIFICATIONS JUMPER SETTING DIP SWITCH SETTINGS Controller network speed (default=19.2k)

CT V900 a Diagramm

Embed Size (px)

DESCRIPTION

2 door-controller

Citation preview

Page 1: CT V900 a Diagramm

CA-A360-ARS-485 to RS-232 Converter

RS-485 tonext controller

To PC USB portorRS-232 Port

GALEOWiegandKeypad 2

DGLP/FWProximitryReader 1

CT-V900-A2-Door Controller

Keypad 2

Keypad 1

To PCRS-232 Portusing DB-9F

Reader and keypad wiring may differ from diagram. Please consult your dealer for details.

Up to 16inputs percontroller

ConnectEarthTerminal toCold Water Pipe

Connect to RS-232 PC port if 6-pin modular jack is not used.

GEL Type Battery12Volt, 7Ah

GEL Type Battery12Volt, 7Ah

Relay 1

GND

GND

LK1+

LK2+

LK1-

LK2-

+24V

UNLK1

LED1

LED2

UNLK2+24V

C1

C2

NO

1N

O2

NC

1N

C2

Relay 2

Fire alarmcontact forLock 1 & 2

Door Strike 1

+

-

Door Strike 2

+

-

+-

ElectromagneticLock 1

ElectromagneticOption

ElectromagneticLock 2

+-

+-

+-

PowerSupply

PowerSupply

DoorStrikeOption

123

56

Maximum length 25 feet

Input 11K Ohm

Input 22.2K Ohm

CA-A110-PLockControl Module

Using CA-A360-USBRS-485 to USB or RS-232ConverterOr

Always consult the regulatory agency in your area for existing regulations regarding doors designated as emergency exits.

4

Technical SupporTcDV americas

Tel: (450) 682-7945 • Toll free: (866) 610-0102www.cdvamericas.com

equipment Wire Type Size Max. lengthCard reader (1 LED or 1 LED & Buzzer) and

Wiegand keypad 6 conductors, stranded, shielded (foil),

drain conductor, Belden: 5304FE 18AWG 150m (500ft.)

Card reader (2 LEDs & Buzzer) 8 conductors, stranded, shielded (foil),drain conductor, Belden: 5306FE 18AWG 150m (500ft.)

Zone input 4 conductors, copper (JKT) 22AWG 600m (2000ft.)Door strike and AC transformer for controller 2 conductors, solid copper 18AWG Door strike: 150m (500ft.), AC transformer: 8m (25ft.)

RS-485 bus Ethernet CAT 5e, 4 pairs 24AWG 1220m (4000ft.)

1 OFF OFF OFF OFF OFF OFF2 on OFF OFF OFF OFF OFF3 OFF on OFF OFF OFF OFF4 on on OFF OFF OFF OFF5 OFF OFF on OFF OFF OFF6 on OFF on OFF OFF OFF7 OFF on on OFF OFF OFF8 on on on OFF OFF OFF9 OFF OFF OFF on OFF OFF

10 on OFF OFF on OFF OFF11 OFF on OFF on OFF OFF12 on on OFF on OFF OFF13 OFF OFF on on OFF OFF14 on OFF on on OFF OFF15 OFF on on on OFF OFF16 on on on on OFF OFF17 OFF OFF OFF OFF on OFF18 on OFF OFF OFF on OFF19 OFF on OFF OFF on OFF20 on on OFF OFF on OFF21 OFF OFF on OFF on OFF22 on OFF on OFF on OFF23 OFF on on OFF on OFF24 on on on OFF on OFF25 OFF OFF OFF on on OFF26 on OFF OFF on on OFF27 OFF on OFF on on OFF28 on on OFF on on OFF29 OFF OFF on on on OFF30 on OFF on on on OFF31 OFF on on on on OFF32 on on on on on OFF33 OFF OFF OFF OFF OFF on34 on OFF OFF OFF OFF on35 OFF on OFF OFF OFF on36 on on OFF OFF OFF on37 OFF OFF on OFF OFF on38 on OFF on OFF OFF on39 OFF on on OFF OFF on40 on on on OFF OFF on41 OFF OFF OFF OFF OFF on42 on OFF OFF OFF OFF on43 OFF on OFF OFF OFF on44 on on OFF OFF OFF on45 OFF OFF on OFF OFF on46 on OFF on OFF OFF on47 OFF on on OFF OFF on48 on on on OFF OFF on49 OFF OFF OFF OFF on on50 on OFF OFF OFF on on51 OFF on OFF OFF on on52 on on OFF OFF on on53 OFF OFF on OFF on on54 on OFF on OFF on on55 OFF on on OFF on on56 on on on OFF on on57 OFF OFF OFF on on on58 on OFF OFF on on on59 OFF on OFF on on on60 on on OFF on on on61 OFF OFF on on on on62 on OFF on on on on63 OFF on on on on on64 on on on on on on

ONOFF

DEF/R

UN

9.6K/19.2K

ADD

32

ADD

16

ADD

8

ADD

4

ADD

2

ADD

1

1 2 3 4 5 6 7 8Con

trolle

rad

dres

s

BaTT on:When the jumper is “ON”, the controller enables the RAM and RTC battery backup (default = ON). Once the controller is installed, remove the battery protection tab for correct operation. If you are required to replace the 3V backup battery, we recommend that you set the jumper to “OFF” until the battery is replaced. Note however, if a complete power loss occurs, the time and date as well as all controller programming will be lost.

eol (conTroller neTWorK):Places the EOL termination of the main controller network in circuit (default = off). Jumper should only be on when the controller is the last controller in the network.

hiGh/loW (neTWorK iMpeDance):Select the impedance of the RS-485 network (default = high). Set both jumpers to high when running normally. When running the Centaur software and connecting directly to the 9-pin serial port, you must set both jumpers to low.

12V/24V (locK #1 & locK #2):Selects the output voltage of the “LK1+” & “LK2+” terminal when the Lock#1 and Lock#2 relay is active (default = 12V). When the jumper is on pins 1 & 2 the output will be 12V. If the jumper is on pins 2 & 3 the output will be 24V.

eol (e-BuS neTWorK):Places the EOL termination of the controller’s E-Bus network in circuit (default = on). If the controller is at the end of the E-Bus network, the jumper should be on. If the controller is in the middle of the E-Bus network, the jumper must be off.

hiGh/loW (e-BuS iMpeDance):Select the impedance of the E-bus for the RS-485 (default: low). Set to low when running normally. Set to high when running special E-Bus devices.

Max. current: 2.5Aac loss indicator: Yesoperating Temperature: 5°C to 55°C (41°F to 133°F)inputs: 2 readers inputs (multiple protocol support) 2 Wiegand and/or BCD Keypads 8 Multi-Purpose using N.C. or 16 using ATZ with 2R/3R Controller Tamper: Normally Closed

(N.C.)outputs: 2 Lock Outputs: 350mA @12/24VDC 2 Form “C” Relays: 5A 30VDC

Resistive (Expandable to 16 with CA-A460-P) 6 Open Collector 25mA Sink System autonomy: 100% Off-line Operationcontroller network: RS-485/232 @ 9.6K baud/19.2K baudMax. Distance: 1220m (4000ft.) E-Bus and Network Buson-Board protection: 24VDC: 2.5A Fuseless Protection 12VDC: 1A Fuseless Protection 5VDC: 1A Fuseless Protection AC Protection: 5A FuseBattery protection: 7A FuseFuse Failure indication: Event Generation and LED Display

on ALL suppliesBattery Backup: Battery capacity: Two 12VDC, 7Ah Low Battery @: 21.6VDC Low Battery Restore @: 24.1VDC Low Battery Cut-Off @: 18.5VDCFirmware: On-Line Upgradable

Reset tofactory default(default= RUN)

2-Door controller cT-V900-aDiagram connection

1

2

3

4

5

6

Specifications may change without prior notice. Printed in Canada 15/12/2006

SpeciFicaTionS juMper SeTTinG

Dip SWiTch SeTTinGS

Controller network speed (default=19.2k)