Bryan Steam Deaerator Sizing Prog ram highlighted cells are for job conditions revision date: 9/17/02
and to be entered by user
Capacity 70000 PPH
Steam pressure to the PRV 5 PSI
Saturated steam temperature at bop 228 DegreesDeaerator operating pressure 5 PSI
Saturated temp. at deaerator pressure 228 Degrees
Enthalpy of Steam 960.1 BTU's/ LB
Percentage of incoming Water 100%
Temperature of incoming Water 40 Degrees
Pressure of incoming Water 40 PSI
Percentage of Condensate Return 0%
Temperature of Condensate Return 10 Degrees
Water line informationMake-up water GPM required 117.02 GPM
Incoming line Size (min.size) 3.5'' based on 4ft per secondCV factor for water valve is 23.76
Steam line InformationSteam required in PPH 12606.41
Income line size (min. size) 10'' based on 7000 ft per minute