DARLEY STANARD PRE-PAC SKID RESIDENTIAL NFPA 13D FIRE PUMP SYSTEM SPECIFICATIONS ELECTRIC MOTOR DRIVEN This specification covers the manufacturing and supplying of 1 (qty.) packaged residential NFPA 13D fire pump system including a 304 Stainless Steel Vertical Inline pump complete with motor, Darley standard manifold system which shall include a standard pressure switch, suction and discharge pressure gauges, check valve, and suction and discharge locking ball valves. The contractor shall provide and install a DARLEY STANDARD MODEL #_____ ________. THE PACKAGE MANUFACTURE MUST HAVE PUMP AND CONTROLLER EXPERIENCE. More information about a Darley Standard System is available from W.S. Darley and Co. at 800.323.0244, or Kevin Sofen direct @ 630.735.3538 or online at www.firesprinklerpumps.com DESIGN: Pump shall be designed to deliver____ GPM when operating at _____PSI. Pump shut off pressure shall NOT exceed ______PSI PUMP: The pump shall be a STAINLESS STEEL VERTICAL INLINE PUMP with; cartridge type mechanical seal, cast iron suction and discharge chambers, with stainless steel impeller(s), shaft, and wet parts. Designed for ______ GPM at a discharge pressure of______ PSI. Pump shall be complete with vertical totally enclosed fan cooled motor rated for _____ HP, 1 Phase, 60 Cycle, 230 volt operation, NO EXCEPTIONS MOTOR: The motor shall be totally enclosed fan cooled with overload protection. It shall also have a service factor of 1.15 and a locked rotor current code letter of G or less. PRESSURE SWITCH: Shall be rated for motor HP Shall include adjustable on/off set points Shall include adjustable reset differential AVAILABLE OPTIONS: SHALL_____SHALL NOT______ INCLUDE A UL LISTED FLOW SWITCH AS PART OF PROVIDED MANIFOLD SYSTEM

DarleySTANARDSpecifications

  • Upload
    darley

  • View
    214

  • Download
    0

Embed Size (px)

DESCRIPTION

 

Citation preview

Page 1: DarleySTANARDSpecifications

 

            DARLEY STANARD PRE-PAC SKID RESIDENTIAL NFPA 13D FIRE PUMP SYSTEM SPECIFICATIONS ELECTRIC MOTOR DRIVEN This specification covers the manufacturing and supplying of 1 (qty.) packaged residential NFPA 13D fire pump system including a 304 Stainless Steel Vertical Inline pump complete with motor, Darley standard manifold system which shall include a standard pressure switch, suction and discharge pressure gauges, check valve, and suction and discharge locking ball valves. The contractor shall provide and install a DARLEY STANDARD MODEL #_____ ________. THE PACKAGE MANUFACTURE MUST HAVE PUMP AND CONTROLLER EXPERIENCE. More information about a Darley Standard System is available from W.S. Darley and Co. at 800.323.0244, or Kevin Sofen direct @ 630.735.3538 or online at www.firesprinklerpumps.com DESIGN: Pump shall be designed to deliver____ GPM when operating at _____PSI. Pump shut off pressure shall NOT exceed ______PSI PUMP: The pump shall be a STAINLESS STEEL VERTICAL INLINE PUMP with; cartridge type mechanical seal, cast iron suction and discharge chambers, with stainless steel impeller(s), shaft, and wet parts. Designed for ______ GPM at a discharge pressure of______ PSI. Pump shall be complete with vertical totally enclosed fan cooled motor rated for _____ HP, 1 Phase, 60 Cycle, 230 volt operation, NO EXCEPTIONS  

MOTOR: The motor shall be totally enclosed fan cooled with overload protection. It shall also have a service factor of 1.15 and a locked rotor current code letter of G or less. PRESSURE SWITCH: Shall be rated for motor HP Shall include adjustable on/off set points Shall include adjustable reset differential AVAILABLE OPTIONS: SHALL_____SHALL NOT______ INCLUDE A UL LISTED FLOW SWITCH AS PART OF PROVIDED MANIFOLD SYSTEM

Page 2: DarleySTANARDSpecifications

More information about a Darley Standard System is available from W.S. Darley and Co. at 800.323.0244, or Kevin Sofen direct @ 630.735.3538 or online at www.firesprinklerpumps.com