DATA SHEET IMPULSE VALVE PNEUMATIC OPERATOR (IVPO) KIT DESCRIPTION The Impulse Valve Pneumatic Operator (IVPO) provides the means to pneumatically activate the Fike Impulse Valve clean agent container by providing the force required to extend a piston that will open the rupture disc, allowing the agent to be released from the container. The IVPO is installed in systems utilizing multiple clean agent containers.Fike Clean Agent Containers with IVPO are operated by pneumatic pressure from Container with Impulse Valve Operator (IVO). For detailed information, refer to the Impulse Valve Operator Data Sheet IV.1.09.01. SPECIFICATIONS IVPO Material: Stainless Steel (Body) / Brass (End Cap) Pneumatic Connection: 1/8” NPT Temperature Range: 32 to 130°F (0 to 54.4°C) ORDERING INFORMATION Item No. Fike P/N Descripon - 70-280 IVPO Kit (includes all items listed below) 1 02-12729 IVPO 2 02-4543 1/8” (NPT) x ¼” JIC Adaptor 3 02-4977 ¼” JIC x 3.0’ lg. Actuaon Hose 4 70-286 Reset Tool INSTALLATION After the electrical/control system has been checked out and not trouble/ground faults are present; proceed with the IVO and IVPO installation. Note: The IVO should be the last items completed before the system is placed into operation. Remove the Retaining Clip p/n (02-11986) from the actuation port of the Impulse Valve. (see Figure 1) Remove the Plastic Plug from the actuation port of the Impulse Valve. Retain the plug for future use when the container has to be re-filled/serviced. Insert the IVPO into the actuation port of the Impulse Valve and secure by inserting the Retaining Clip provided. (see Figure 1) Important Note: Check IVPO to ensure device is armed before inserting on Impulse Valve. Form No. IV.1.10.01-1 704 SW 10th Street P.O. Box 610 Blue Springs, Missouri 64013-0610 U.S.A. Phone: 8162293405 www.fike.com APPROVALS: UL Listed ULC Listed FM Approved

DATA SHEET - Fire Protection Technologies...DATA SHEET IMPULSE VALVE PNEUMATIC OPERATOR (IVPO) KIT DESCRIPTION The Impulse Valve Pneumatic Operator (IVPO) provides the means to pneumatically

  • Upload
    others

  • View
    15

  • Download
    0

Embed Size (px)

Citation preview

DATA SHEET

IMPULSE VALVE PNEUMATIC OPERATOR (IVPO) KIT

DESCRIPTIONThe Impulse Valve Pneumatic Operator (IVPO) provides the means to pneumatically activate the Fike Impulse Valve clean agent container by providing the force required to extend a piston that will open the rupture disc, allowing the agent to be released from the container.

The IVPO is installed in systems utilizing multiple clean agent containers.Fike Clean Agent Containers with IVPO are operated by pneumatic pressure from Container with Impulse Valve Operator (IVO). For detailed information, refer to the Impulse Valve Operator Data Sheet IV.1.09.01.

SPECIFICATIONSIVPO Material: Stainless Steel (Body) / Brass (End Cap)Pneumatic Connection: 1/8” NPTTemperature Range: 32 to 130°F (0 to 54.4°C)

ORDERING INFORMATION

Item No. Fike P/N Descripti on

- 70-280 IVPO Kit (includes all items listed below)

1 02-12729 IVPO

2 02-4543 1/8” (NPT) x ¼” JIC Adaptor

3 02-4977 ¼” JIC x 3.0’ lg. Actuati on Hose

4 70-286 Reset Tool

INSTALLATIONAfter the electrical/control system has been checked out and not trouble/ground faults are present; proceed with the IVO and IVPO installation.Note: The IVO should be the last items completed before the system is placed into operation.

• Remove the Retaining Clip p/n (02-11986) from the actuation port of the Impulse Valve. (see Figure 1)• Remove the Plastic Plug from the actuation port of the Impulse Valve. Retain the plug for future use when

the container has to be re-filled/serviced.• Insert the IVPO into the actuation port of the Impulse Valve and secure by inserting the Retaining Clip

provided. (see Figure 1)

Important Note: Check IVPO to ensure device is armed before inserting on Impulse Valve.

Form No. IV.1.10.01-1

704 SW 10th Street P.O. Box 610 Blue Springs, Missouri 64013-0610 U.S.A. Phone: 8162293405 www.fike.com

APPROVALS:• UL Listed• ULC Listed• FM Approved

Copyright © Fike Corporation All Rights Reserved.Form No. IV.1.10.01-1, August 2012. Specifications are subject to change without notice.

2 of 2

RESET INSTRUCTIONS Remove IVPO from Impulse Valve by removing Retaining Clip.

Insert IVPO into Reset Tool and secure with Retaining Clip.

Push Reset Tool button (firmly) against a hard surface until IVPO Pin resets (clicks into place).

Remove Retaining Clip, IVPO is reset and ready to be installed on Impulse Valve.Important Note: Check IVPO to ensure device is armed before inserting on Impulse Valve.

IVPO – Fired Position

IVPO – Armed Position