東豐科技 台北市 內湖區 IDC 介紹

Raymond Cheng DongFong Technology Co. Ltd. Vice President Mobile Phone: +886-930-101010 E-mail: [email protected]

Page 2: Dongfong

機櫃 平面配置圖

目前機架配置120個已建置60個,剩餘區域視客戶需求建置

Page 3: Dongfong

機櫃規格 機架規格說明:

機架寬度:19" ( 48.26 cm )

機架深度:120cm 或是110 cm

拖盤高度:1U

Frame 高度:6U

電力:220V/2KVA

機架總高度:42U

Page 4: Dongfong

高架地板 機架規格說明:

機房地板採 CNS500 型合金鋼

採蜂巢板製作按裝,蜂巢板出風率達 25%-50%

恆溫恆濕下吹式空調,地板下並鋪設保溫層

高架地板地網 14 m㎡ 安裝

Page 5: Dongfong

電力系統 機架規格說明:

500KVA UPS 不斷電設施,採 N+1 備援建置,可供應全載 10 分鐘

500KW 1+1 發電機組電力備援措施,24 小時持續運轉容量

電信設備、配電設備、發電機設備、避雷設備、機櫃接地為分離的接地系統

機架電源採雙迴路電源供應

220V125KVA精密配電櫃4組

Page 6: Dongfong

電信供應系統 機架規格說明:

與中華電信、遠傳電信、台灣大電訊、大台北寬頻、中嘉和網…等各家固網業者皆有雙外纜引入口

Page 7: Dongfong

空調系統 機架規格說明:

採 N+1台120RT水冷變頻式冰水機備援設計

保持全機房恆溫、恆濕的室內環境

中興電工30RT恆溫恆濕空調箱4組/15RT空調箱備援

冰水主機及空調箱監控訊號接至NOC值班室,由環控系統監控

各空調隔間室內裝置溫、溼度計,並連線至NOC值班室,供NOC值班人員監控

Page 8: Dongfong

消防系統 機架規格說明:

VESDA 極早煙霧偵測警報系統可比消防系統提前30分鐘預警

Kidde FM200之滅火設備

符合中華民國內政部消署各類場所消防設備設置標準

系統及氣體經中華民國內政部消防署認證許可使用

Page 9: Dongfong

NOC值班系統 機架規格說明:

環境監控系統

固網電信室、機櫃冷通道、UPS室之溫度、溼度監測及記錄及警報

空調系統

空調機運轉、異常狀態監視

空調機之切換控制

空調機之漏水偵測

電力系統

每部 UPS 運轉狀況

目前電力供應來源狀況

發電機電壓電流溫度及各項數值

機櫃各迴路排插用電狀態與紀錄

消防系統

極早期偵煙系統/FM200氣體消防系統

Page 10: Dongfong

東豐科技島內骨幹連線圖

Page 11: Dongfong

Dongfong uses KBT for Domestic Transit

Page 12: Dongfong

NOC值班系統 機架規格說明:

環境監控系統

固網電信室、機櫃冷通道、UPS室之溫度、溼度監測及記錄及警報

空調系統

空調機運轉、異常狀態監視

空調機之切換控制

空調機之漏水偵測

電力系統

每部 UPS 運轉狀況

目前電力供應來源狀況

發電機電壓電流溫度及各項數值

機櫃各迴路排插用電狀態與紀錄

消防系統

極早期偵煙系統/FM200氣體消防系統

Page 13: Dongfong

7x24全天候工程與保全管理 機架規格說明:

7x24 機電工程管理

24 小時機電人員待命值班

不影響供電之定期機電設備維護保養

7x24 大樓保全管理

保全範圍包括 1F/7F機房內的監視錄影、屋頂機房的監視錄影及7F樓層

公共區域監視錄影

24 小時專業保全公司防護管制

緊急狀況處理措施

台電停電緊急處理流程

空調故障緊急處理流程

地震緊急處理流程

火災緊急處理流程

Page 14: Dongfong

網路硬體設備 機架規格說明:

骨幹設備

網路安全設備

網路儲存設備

Page 15: Dongfong

State-of-the-art infrastructure

Data Center’s facilities • Generator:1+1 545KW Perkins generators.(AC 380V / 220V 500KW

continues × 2)

• Electricity:No power failure in the past and future.

• Load:The system can operate even without water and power supply for 7

days individually, according to current workload.

• Structure:Under ground level (SRC), above ground level (SS).

• Anti-seismic-Systems : The design factor 435gal which approached 7 grade , much more than 10 grade of US standard (432gal ).

• Flood control:The lobby 3.8 (meter) is higher than neighborhood for 0.5

meter, according to high standard of floor control in TPE city hall).

• Fire proof:Resist for 1 (hour).

• Load factor:Load bearing structure could reach to 600kg/㎡ and 2000kg/ ㎡

for above and under ground respectively.

• Storage tank:848m3 + 100.8m3

• Fuel tank:2,000 (liter)

• Fire protection system: FM200 (Fire Suppression system).

• Smoke Detector: Very Early Warning Smoke Detection (VESDA).

Page 16: Dongfong

Surpass impossibility

The system can operate even without water and

power supply for 7 days individually.

State-of-the-art infrastructure

World-class fire proof, flood control, UPS supporting,

and anti-seismic systems. All physical and prepared

protection of data center.

Stabilized Rapid response time which is the best of best internet

service.

Safe & Secure

Efficient centralized monitoring system

Best security management

Just in time actions taken

Vision and Mission

Page 17: Dongfong

• U P S:500KVA × 2 (1 + 1).

• Power generator:545KW × 2 (1+1).

• Ground (electricity) : Electrical impedance is lower 0.18Ω for avoiding thunder and lightning、lower 1.5Ω for telecom system

and 0.5Ω for computing system.

• Illumination:Parking zone 50-100 lux、stairs 50-200 lux and

data center area 500-600 lux.

• Security control:

1. Fire alarm notification appliance

2. Emergency alert

3. Security guard: 24 × 7 × 365 (hour)

4. CCTV is monitoring outside building, all entrance, exit,

elevator, stairs, parking zone and facility area.

Data Center’s facilities

Page 18: Dongfong

Door security system: Security guards is connecting with each other all the time, while unusual case is found, they can take action immediately. Flood control: The lobby 3.8meter is higher than neighborhood for 0.5 meter。 (According to high standard of floor control of TPE city hall) 。 There is a floodgate located at entrance of parking zone under ground level to avoid the flood。 Anti-seismic infrastructure : Located at bedrock of the hill where is relatively firm with no doubt。 The foundation accomplished by 192 piece of pile。 Reportedly said that design factor 435gal which approached 7 grade , much more than 10 grade of US standard (432gal ). The building was made of an amount of concrete which is used on making bridges specifically and produced in Taiwan, can resist earthquake for 4000 pounds。 Above first floor can bear loading for 1000kg per square meter, B1、B2 either can bear loading for 2000kg per square meter。

Internet Data Center summary

Page 19: Dongfong

Security management: There are 20 units of CCTV equipped at each entrance and exit。 Security guards and engineers are on –duty on-site for 24 hours。 The guest has to exchange the pass then be allowed to enter data center. Centralized control: Siemens’ BMS integrated system is able to monitor important system such as environment, fire fight, UPS, power generator, air conditioning and water. In order to manage it well, all of data is consolidated to centralized control room. The smoke detector consists of ionization and photoelectric in pair and working Simultaneously. Once detects the smoke, any one of them will alert. Owing to expensive networking facilities inside co-location, where needs to be equipped with both of carbon dioxide and FM200 extinguishers , in additions, the hall ways come with dry powder and FM200 extinguishers fully. Data Room is equipped with VESDA, which can sense micro particles with laser。 All staffs are qualified and certified with expertise of electrics, fire fight and sewage treatment。 We do regular checking on every kinds of system and device。

Internet Data Center summary

Page 20: Dongfong

Circuit: The data transmission and electric distribution line operating in signal channel, preventing from interference. Fire protection system : The water and foam extinguisher are placed at parking lot of basement。 The FM200 extinguisher are placed at inside electrical control room and server room. UPS (7F): 1 set of UPS can fulfill maximum of loading currently, there are 2 sets of UPS at each floor to operate for 8 hours. Enables UPS firstly while power failure happening and waiting for power generator ready for use until voltages are stabilized at least 10 minutes. UPS is able to remain longer than15 minutes, even over-loading on design load. The parallel host of UPS has 2 sets of backup power supply.

Internet Data Center summary

Page 21: Dongfong

Power generator: There are 2 units of power generator to provide total amount of 1090KW, each provides 545KW (proximate to 681KVA). Backup system is designed by N+1 mode and used cooling water to calm down. Enables UPS firstly while power failure happening and waiting for power generator ready for use until voltages are stabilized at least 5 minutes. There are 2 main fuel tanks with 1000 (liter). The backup of fuel tank can work for 8 hours with 1000 (liter), there are 2000 (liter) available totally. The cooling water is 30000 liter。 It can entirely support the whole building in power failure with only one power generator. The cost of establishment which is 50 millions, over than second-thirds of total cost.

Internet Data Center summary

Page 22: Dongfong

Data room: It’s 3.7 meters height between ground and ceiling. The raised floor is 40cm between ground, consisting of a gridded metal framework to avoid antistatic interruption. The raised floor is 60cm × 60cm, bearing load for 500Kgs. The air conditioner with constant temperature and humidity to keep at 22℃ and 50%. There are 5 units of 30 tons double compressor air conditioner to keep cool. Each server room, hall way and basement, all of them has FM200 and VESDA smoke detector. Networking management:On-duty for 24 Hours. On-site operation:2 guys working on each shift for 24 hours.。 The standard cabinet in 60 cm width and 110 cm or 120cm depth with lock both in front and back of door. Capable of doing customized requests, such as different design of cabinet or independent space with cage.

Internet Data Center summary

Page 23: Dongfong

Quality control

We can provide monitoring service as follows immediately.

Real-time traffic monitoring website.

The notification of maintenance for routine checking.

SMS notification for abnormal scenario and will take action accordingly.

Customized system oriented.

Consultants fully support AS number and IP registration.

Intelligent traffic management system (under construction).

Anti-hacker function development.

The charge formulated based on web traffic.

Page 24: Dongfong

Fuel Tank

Page 25: Dongfong

Centrifugal-type frequency conversion chillers

Page 26: Dongfong

200RT Cooling Tower 2 Set

Page 27: Dongfong

DELTA 500KVA UPS 2 Set

Page 28: Dongfong

30RT CRAC 5 Set

Page 29: Dongfong

Generator Parallel Distributor

Page 30: Dongfong

Battery Room 3 Set

Page 31: Dongfong

120cm Cooling Tunnel

Page 32: Dongfong

80cm Hot Tunnel

Page 33: Dongfong

Precise power distribution cabinet

Every cabinet could provides dual AC220V 30A power supply.

If need, every cabinet could provides forth AC220V 30A power supply.

Page 34: Dongfong

1500KG Freight elevators