DP300E rev 8.3
1
Show information...Show information...
•Navigation links: Move the cursor across the links and wait for the “hand” symbol
•- then click left mouse key.
•Click the APC logo link to jump back to the previous showed slide.
•Click the left margin area to jump to the index (“Contents of the presentation”)
•From the index -links, you may jump to any other subjects.
• - use the APC-return logo to return to the index slide again .
DP300E rev 8.3
2
Silcon DP300ESilcon DP300EOn-lineOn-line
power protectionpower protection
APC presentationAPC presentation
DurationDuration::
DP300E rev 8.3
3
It’s a world of It’s a world of riskyrisky
businessbusiness
DP300E rev 8.3
4
... 5 minutes... 5 minutes
power down time power down time
in your company !in your company !
Imagine...Imagine...
Sort
• Is your business depending
on IT infrastructure?
• What is the cost of IT
downtime?
• Do you have a strategy for
securing up-time?
• Do you have a strategy for
power availability?
5 minutes 5 minutes power down timepower down time
DP300E rev 8.3
7
Application
ServersNT, UNIX, Novell etc.
File server
DP300EMainframe
Web
DP100E
Gateway
Mini Computers DP10E
Windows 95 Windows NT OS/ and others
Enterprise IT InfrastructureEnterprise IT Infrastructure
Policy...Policy...Protection
of the critical
infrastructure
to ensure:
Up-time
Data safety
Availability
Efficiency
Productivity
Is this the situation…?Is this the situation…?
DP300E rev 8.3
8
Silcon DP300E SeriesSilcon DP300E Series
ContentsContents
of the of the presentationpresentation
Headlines:
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
9
Cost of down time
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
10
Fortune 1000 companies average outage across Fortune 1000 companies average outage across industries that lasts four hours costs….industries that lasts four hours costs….
Source: Find/SVP. Outages includes other than power failures
Cost of IT Power Down timeCost of IT Power Down timeCost of down time
DP300E rev 8.3
11
A typical company experiences A typical company experiences 99 outages per year, outages per year, resulting in annual losses of almost resulting in annual losses of almost
(excluding the cost of lost employee productivity). (excluding the cost of lost employee productivity).
Source: Find/SVP. Outages includes other than power failures
Cost of IT Power Down timeCost of IT Power Down time
Cost of down time
DP300E rev 8.3
12
Financial Brokerage operations
Financial Credit card operations
Media Pay-per-view
Retail Home shopping (TV)
Retail Home catalog sales
Transportation Airline reservations
Media Tele ticket sales
Transportation Package shipping
Finance ATM fees
Source: Dataquest, Perspective, Sept. 30, 1996
Average industry cost of down timeAverage industry cost of down time
$ 6,45 million
$ 2,6 million
$ 150.000
$ 113.000
$ 90.000
$ 89.500
$ 69.000
$ 28.000
$ 14.500
Cost of down time
DP300E rev 8.3
13
...97%...97% of power supply problems are coursed by of power supply problems are coursed by
power disturbances and low supply voltage.power disturbances and low supply voltage.
Source: National Power Laboratories USA
IT Power problems...IT Power problems...Cost of down time
DP300E rev 8.3
14
Did You Know?Did You Know?
Power problemsPower problems are the largest single cause of data loss,
5 times more frequent than viruses.
Power problemsPower problems are the second largest (to theft) cause of hardware loss.
Causes of data loss...Causes of data loss...
Source: Contingency Planning
Power problems are preventable...Power problems are preventable...
Cost of down time
DP300E rev 8.3
15
Industry Trends Drive Demand for...Industry Trends Drive Demand for...
Increased IT usage:
Internet Internet extranetsextranets EDIEDI E-commerceE-commerce DatabasesDatabases
7 x 24 hours up-timenetwork availability
Utility deregulation
Constant-Constant-Clean-Clean-
PowerPower
Cost of down time
DP300E rev 8.3
16
Did you realize that....Did you realize that....
Investment
“nines”
99.9%99.9% uptime per year...
means 525 minutes down time (8½ hours)
99.99%99.99% uptime per year...
means 52 minutes down time
99.999%99.999% uptime per year...
means 5 minutes down time
Cost of down time
DP300E rev 8.3
17
Users Require 7 x 24 hours Availability...Users Require 7 x 24 hours Availability...
“As businesses becomes more internationalized,
7 x 24 hours access to computer systems is a
requirement.
E-mail, group-ware, and similar types of services are
becoming business critical,
- and as a result, highly available systems are now
needed by many more organizations.”
IDC, Highly Available Systems Study
Cost of down time
DP300E rev 8.3
18
Information availability...Information availability...throughout the enterprise networkthroughout the enterprise network
Regional DatacenterRegional Datacenter Regional Datacenter
Localservers
Localservers
Localservers
Localservers
Localservers
Localservers
Localservers
Localservers
Localservers
Corporate Datacenter
Cost of down time
DP300E rev 8.3
19
Enterprise Customer NeedsEnterprise Customer Needs
No shut-down = AvailabilityNo shut-down = Availability
Mainframe class functionality, reliability, Mainframe class functionality, reliability,
availability, and fault toleranceavailability, and fault tolerance
Flexible growthFlexible growth
Round-the-clock, easy manageabilityRound-the-clock, easy manageability
Low cost of ownershipLow cost of ownership
7 x 24 hours system support7 x 24 hours system support
Operate in poor power conditionsOperate in poor power conditions
Cost of down time
DP300E rev 8.3
20
On-line 3 phase UPS systems for…On-line 3 phase UPS systems for…
Data Centers
Corporate network
- and industrial
applications
...to protect any company or organization against losing money in case of power failure at...
Lowest operation cost
Lowest installation cost
Highest performances
Cost of down time
DP300E rev 8.3
21
PerformancePerformance and and
benefitsbenefits
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
22
Silcon DP300E SeriesSilcon DP300E SeriesThe product family offers...The product family offers...
Highest efficiency
Lowest operation cost
Performance and benefits
… from 10 to 480 kVA/ kW in one unit
Cubicles for: UPS + Battery packs + isolation and combinations
“Close to perfect”
DP300E rev 8.3
23
Silcon DP300E Silcon DP300E
Up to 97% efficiency
Input power factor corrected to 1
No mains repercussions
Full rated output power available in kW
200% overload capacity
Compact and small footprint
Expandable for more Power/ Redundancy
““Close to perfect” Close to perfect” means...means...
Performance and benefits
DP300E rev 8.3
24
Silcon DP300E Silcon DP300E
Unique patented APC/Silcon technologyUnique patented APC/Silcon technology
True on-line systemTrue on-line system
No phase compensation requiredNo phase compensation required
Saves you the most money in operationSaves you the most money in operation
Lowest installation costLowest installation cost
“Close to perfect”
Performance and benefits
What more to say about Delta-Conversion…What more to say about Delta-Conversion… ?
DP300E rev 8.3
25
Silcon DP300E - power flowSilcon DP300E - power flow
Mains input
Battery
DeltaInverter
MainInverter
Regulating the delta, ± diff. in/out
1. Normal operation
2. Regulated operation
3. Battery operation
4 Recharge battery
Load
Performance and benefits
Delta-Conversion
DP300E rev 8.3
26
Repercussionscaused by UPS
Distortion free no repercussions
Mains repercussions...Mains repercussions...
Delta-Conversion Legacy double conversion
Performance and benefits
DP300E rev 8.3
27
Silcon DP300E - Silcon DP300E - Input/ output efficiencyInput/ output efficiency
The high efficiency
comes from the
unique
Delta-Conversion
Technology
97%97%
Silcon DP300ESilcon DP300E
Legacy UPS SystemsLegacy UPS Systems
% Load% Load
% Efficiency% Efficiency
Performance and benefits
DP300E rev 8.3
28
Energy lossLegacyUPS systems
High efficiencyHigh efficiency
Performance and benefits
Silcon DP300EDelta-ConversionSaves energy
Silcon DP300EDelta-Conversion
UPSUPS
DP300E rev 8.3
29
“Would you accept
0.7Power factor?”
Would you accept 0.7 of a pint?Would you accept 0.7 of a pint?
UPSUPS
Performance and benefits
UPSUPS
DP300E rev 8.3
30
Delta-ConversionDelta-ConversionOn-Line and high efficiency…?On-Line and high efficiency…?
what´s the trick…?
Performance and benefits
DP300E rev 8.3
31
The Energy Saving Trick...The Energy Saving Trick...
Double conversion
4. Floor
5. Floor
Delta Conversion
4. Floor
5. Floor
Performance and benefits
DP300E rev 8.3
32
Who makes the trick...Who makes the trick...
The APC-Delta Conversion Technology is today protected by patents.
APC is the exclusive supplier of this technology - DP300E
The technology is not likely to be available from many other UPS-suppliers for some time
Performance and benefits
DP300E rev 8.3
33
““close to perfect”close to perfect”
Silcon DP300E Series - technologySilcon DP300E Series - technology
The Delta-Conversion Technology
Performance and benefits
DP300E rev 8.3
34
UPS power factor
Headlines:
Cost of down time
Efficiency
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Fans
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
Headlines:
Cost of down time
Performances and benefits
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
35
UPS - power factorUPS - power factor Input - output and loadInput - output and load
The power factor… The power factor…
Load power-factorLoad power-factor
Power factorPower factor
Considerations:Considerations:
UPS Load power factor
LO
AD
INP
UT
Input power-factorInput power-factor Output power-factorOutput power-factor
Power factor
OU
TP
UT
UPS
DP300E rev 8.3
36
Silcon DP300E - power factorSilcon DP300E - power factorInput power factor Input power factor
Load (kW)
Input power-factor is always
1 regardless of load...
This means:This means:
High efficiency
Smaller cables
Smaller fuses
No separate phase
compensation required
Lower installation cost
Input power factor
Supply
Power factor
INP
UT
UPS
DP300E rev 8.3
37
Silcon DP300E
Legacy UPS system
Silcon DP300E Input Power Factor…Silcon DP300E Input Power Factor…and the installationand the installation
Power factor
Power factor 1Power factor 1- means lower- means lowerinput current input current therefore... therefore...
smaller smaller cables and fusescables and fuses
DP300E rev 8.3
38
Silcon DP300E - Output power factorSilcon DP300E - Output power factorkVA and kW - ratings... kVA and kW - ratings...
System rated for...
Unity output power-factor
- means:
Full load capacity specified
in kWatts or kVA at unity PF
Load PF-working range:
0.8 inductive to 0.9
capacitive
Normally smaller UPS size
(compared to competitors)
when pure resistive load
Load
Power factor
OU
TP
UTUPS
DP300E rev 8.3
39
The power-factor on UPS loadsThe power-factor on UPS loadswill increase…will increase…
UPS load power-factor…UPS load power-factor…
Depending on type of load
Computer load: 0.6 to1.0 typ. 0.8 (Trend: load power factor 1)
The UPS must always be power-sizedpower-sized to supply the sum of loads in
UPS Load power factor
LO
AD
Load power-factor
Type of load
kVAkVA
Power factor
DP300E rev 8.3
40
Power sizing the UPS...Power sizing the UPS...
kVA-loadPower factor on mixed loads
Power factor
60 kVA/ kWPF =1
60 kVA/48 kW
PF = 0.8
Legacy UPS
system
?
DP300E
? 60 kVA60 kVA
UPS size = kVA load
Load 1: (8 kW / 0.8) = …..…….. 10 kVA
Load 2: (18 kW / 0.9) = ………. 20 kVA
Load 3: (30 kW / 1) = ……..…... 30 kVA
Sum of loads…... 56 kW…….……..……. Sum of loads…... 56 kW…….……..……. 60 kVA60 kVA
??70 kVA/ 56 kW
PF = 0.8
Legacy UPS system
?70kVA
UPS size = kVA/ kW load
DP300E rev 8.3
41
Power sizing the UPS...Power sizing the UPS...
kW-load
Load 1: = …………..…..….. 10 kW
Load 2: =…………..………. 20 kW
Load 3: = ………..……..….. 30 kW
Sum of loads…………………………. 60 kWSum of loads…………………………. 60 kW
Power factor
60 kVA/ kWPF =1
75 kVA/ 60 kW
PF = 0.8
Legacy UPS system
?DP300E
?75kVA
60 kW
UPS load = Loads/ 0.8
UPS load = Loads/ 1
Power factor on loads = 1
DP300E rev 8.3
42
Silcon DP300E - Silcon DP300E - Power sizing the UPSPower sizing the UPS
Power sizing the DP300E UPSPower sizing the DP300E UPS Calculate the sum of the UPS-load in kVA
Define highest phase load
Choose the DP300E having its full load output power equal to - or bigger than the load
Additional considerations..
• Overload capacity• Redundancy• …….
- see the Power Binderfor further details
Additional considerations..
• Overload capacity• Redundancy• …….
- see the Power Binderfor further details
Power factor
DP300E rev 8.3
43
Headlines:
Cost of down time
Efficiency
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Fans
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
EconomyEconomy with with
Silcon DP300ESilcon DP300E
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
44
Purchase PricePurchase Price
Installation CostsInstallation Costs
Operating CostsOperating Costs
Maintenance & RepairMaintenance & Repair
:The total Economy... The total Economy...
Economy
- for a UPS system includes:
DP300E rev 8.3
45
Mains repercussion consists of a mains current out of phase Mains repercussion consists of a mains current out of phase with the mains voltage and a distorted mains current.with the mains voltage and a distorted mains current.
Utilities demand a min. PF or require payment for the kVAhUtilities demand a min. PF or require payment for the kVAhinstead of the kWh.instead of the kWh.
Utilities demand distortion filters installed if other powerUtilities demand distortion filters installed if other powerconsumers are disturbed.consumers are disturbed.
Before comparing UPS prices it must be ensured theyBefore comparing UPS prices it must be ensured theyare equal with respect to mains repercussion:are equal with respect to mains repercussion:
Purchase PricePurchase Price
Economy
DP300E rev 8.3
46
Purchase PricePurchase Price
““To clean” the mains input current in a legacy UPSTo clean” the mains input current in a legacy UPS system with 6-pulse thyristor rectifier normally involves:system with 6-pulse thyristor rectifier normally involves:
Economy
A 12-pulse rectifier.A 12-pulse rectifier.
A harmonic filter.A harmonic filter.
A phase compensating unit.A phase compensating unit.
OPTION
OPTION
OPTION
Above might increase the Above might increase the purchase purchase
price for the UPS with up to 30%price for the UPS with up to 30%
UPS
Legacy UPSLegacy UPS
DP300E rev 8.3
47
The installation costs on the UPS mains input The installation costs on the UPS mains input side are determined by the prescribed input side are determined by the prescribed input fuse for the actual UPS.fuse for the actual UPS.
As a rule a DP300E requires an input fuse one As a rule a DP300E requires an input fuse one step smaller than a legacy UPS system without step smaller than a legacy UPS system without phase compensation. The installation costs are phase compensation. The installation costs are correspondingly lower.correspondingly lower.
High efficiency and unity power factor generally meanslower installation costs on the mains input side of the UPS:
Installation CostsInstallation Costs
Economy
DP300E rev 8.3
48
Annual cost savings with Annual cost savings with Silcon DP300ESilcon DP300E
Silcon DP300E compared to legacy UPS system…
– With harmonic filter
– Incl. cost of air conditioning
– Energy price: USD 0.18/kWh
Savings - pay back your UPS investment within 5 years
kVAkVA RatingRating
0
10000
20000
30000
40000
50000
60000
10 20 40 60 80 120 160 240 320 480
Savings USDSavings USD
USD 1472
USD 50 458
Economy
DP300E rev 8.3
49
Load power
UPS power losses
Air conditioning
Maintenance & repair
The operating costs come from:The operating costs come from:
Operating CostsOperating Costs
Economy
- Let´s focus the power loss and the savings...- Let´s focus the power loss and the savings...
DP300E rev 8.3
50
Power loss costs at 10 kVA...Power loss costs at 10 kVA...
Silcon DP310E
Period:
Efficiency:
Load:
8760 timer, 1 year
95%
100%
Air con. power 33%
Power price: USD 0.18/ kWh
UPS type: DP310E, 10kVA
Power losses = input - output power = (10/0.95)-10 = 0.53 kWCost of power loss: 0.53 x 8760 x 0,18 = USD 835
Cost of air con.: 835 x 0.33 = USD 275
Total to pay: 835 + 275 = USD 11101110
Economy
UPS power losses and air conditioning
have to be paid via the
electricity bill !
DP300E rev 8.3
51
Power loss costs at 10 kVA...Power loss costs at 10 kVA...
Legacy UPS
Period:
Efficiency:
Load:
8760 timer, 1 year
90%
100%
Air con. power 33%
Power price: USD 0.18/ kWh
UPS type: A legacy UPS, 10kVA
Power losses = input - output power = (10/0.9)-10 = 1.11 kW
Cost of power loss: 1.11 x 8760 x 0,18 = USD 1750
Cost of air con.: 1750 x 0.33 = USD 578
Total to pay: 1750 + 578 = USD 2328
A yearly saving of 2328 - 1110 = USD 1218
What about 3, 5 & 10 Years ????What about 3, 5 & 10 Years ????
Economy
The same calculation for a legacy UPS system having an efficiency of 90% results in a bill of
DP300E rev 8.3
52
Power loss costs at Power loss costs at 30 kVA30 kVA
Period:
Efficiency:
Load:
8760 timer, 1 year
96%
100%
Air con. power
33%
Power price: USD 0.18/ kWh
UPS type: DP300E, 30 kVA
8760 timer, 1 year
88%
100%
33%
USD 0.18/ kWh
A legacy UPS, 30 kVA
Legacy UPS power losses per year(30/0.88 - 30) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 8579
Silcon DP300E power losses per year(30/0.96 - 30) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 2621
Saving with DP300E = 8579 - 2621 = 5958 USD first year
Economy
DP300E rev 8.3
53
Power loss costs at Power loss costs at 160 kVA160 kVA
Period:
Efficiency:
Load:
8760 timer, 1 year
97%
100%
Air con. power 33%
Power price: USD 0.18/ kWh
UPS type: DP300E, 160 kVA
8760 timer, 1 year
91%
100%
33%
USD 0.18/ kWh
A legacy UPS, 160 kVA
Legacy UPS power losses per year(160/0.91 - 160) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 33186
Silcon DP300E power losses per year(160/0.97 - 160) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 10378
Saving with DP300E = 33186 - 10378 = 2280822808 USD first year
Economy
54
DP300E rev 8.3
Saving money with DP300ESaving money with DP300ECalculating actual costsCalculating actual costs
EconomyData:
Data: Units Enter value Comments
Energy cost USD/kWh 0,17
UPS data:
UPS power size kW 480
Competitor efficiency % 91 Nominal load operation
APC-Silcon efficiency % 97 Nominal load operation
Yearly energy cost to operate: UPS Aircon. Total
Competitor USD 70696 23330 94026
APC-Silcon DP300E USD 22108 7296 29403
Yearly energy cost savings USD 48588 16034 64623
All Warner model
Competitor system efficiency levels were obtained or calculated from commercially-available documentation. Competitor efficiency levels may be lower, i.e., if harmonic filter options are added.
55
DP300E rev 8.3
Saving money with DP300ESaving money with DP300ECalculate savings for a period of 10 years...Calculate savings for a period of 10 years...
Economy
DP300E rev 8.3
56
DP300EDP300E in parallel in parallel
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
57
DP300E series in parallel operation…DP300E series in parallel operation…
Parallel operationParallel operation
Parallel operation
1 2 3 4 5 6 7 8 9
- for expansion and redundancy or both.
DP300E rev 8.3
58
Expansion:Expansion:
- up to 9 units can be connected whenever you need more power.
Redundancy:Redundancy:
- to comply with strict requirements for uninterruptible operation
- oversized capacity
Expansion and RedundancyExpansion and Redundancy
Parallel operation
DP300E rev 8.3
59
Advanced Power ManagementAdvanced Power Management
Day 1
Day 2
Day 3
Parallel operation
Optimized redundancy Optimized redundancy operation by control operation by control system.system.
- only systems needed to supply the load are “active”.
- the load can be switched between the systems in a preprogrammed sequence.
DP300E rev 8.3
60
Advanced battery Advanced battery managementmanagement
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
61
Extended battery life time…!Extended battery life time…!
- by “floating voltage compensation”
- by charge voltage / battery temperature compensation
- by advanced battery monitoring, control and alarms
Typical: 2 years more life time !Typical: 2 years more life time !
Silcon DP300E battery life timeSilcon DP300E battery life time
Battery management
DP300E rev 8.3
62
Charge voltage Charge voltage
compensatedcompensatedTypical compensation level
from 2.20 to 2.36
Volts/ cell
No compensationNo compensation
Silcon DP300E battery life timeSilcon DP300E battery life time
Temperature °C
Years
Battery management
DP300E rev 8.3
63
Power ControlPower Control
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
64
Silcon DP300E - Diesel back-upSilcon DP300E - Diesel back-up
Diesel / DP300E installation:Diesel / DP300E installation:
Normal back-up time UPS: 5 to 10 minutes After 5 minutes - Diesel connects to DP300E Legacy UPS: 3-5 times over sizing Using DP300E series: no over sizing because:
– the sinusoidal input cause no distortion feed-back– no distortion of supply from tyristors– programmable soft start - step load from battery to
diesel
Power Control
DP300E rev 8.3
65
Diesels Best Friend...Diesels Best Friend...
Diesel / DP300E installationDiesel / DP300E installation
Power Control
Mains Supply
Diesel Generator
Input Panel
DP310E - DP340E
SBP Distr. Panel
DP300E rev 8.3
66
Diesels Best Friend...Diesels Best Friend...
100 kW
DIESEL
Silcon DP300E
100 kVA
No harmonicsSame size as UPS
100 kVA
DIESEL
TraditionalUPS
300 - 500 kVA
Harmonics3-5 times oversized
Power Control
DP300E rev 8.3
67
CommunicationsCommunications and and
operations operations
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
68
User interfaceUser interface
15 languages15 languages
Communications and operationsCommunications and operations
Key measurements• Utility power• Battery status• Output power• Percent of capacity
Key measurements• Utility power• Battery status• Output power• Percent of capacity
Alarms• Audible alarms for
38 different monitored
functions
Alarms• Audible alarms for
38 different monitored
functions
UPS-events logger• Time stamped events• Log is accessible from
key-pad
UPS-events logger• Time stamped events• Log is accessible from
key-pad
Communication...
DP300E rev 8.3
69
PC-software, DP-Soft CDXPC-software, DP-Soft CDX
Communications and operationsCommunications and operations
Shut-down Manager
Makes unattended safe,
automatic shut-down
of your network if battery
back-up time runs out.
Notify connected users
to make safe shut-down.
Shut-down Manager
Makes unattended safe,
automatic shut-down
of your network if battery
back-up time runs out.
Notify connected users
to make safe shut-down.
Communication...
DP300E rev 8.3
70
DP view - SNMP AdapterDP view - SNMP Adapter
Communications and operationsCommunications and operations
The SNMP Adapter
• Tools for monitoring networked UPS systems
• Links your DP300E to network (RS232)
• Monitoring your UPS from any network location
• Central control of internetworking equipment like:
Routers, servers, gateways, UPS
The SNMP Adapter
• Tools for monitoring networked UPS systems
• Links your DP300E to network (RS232)
• Monitoring your UPS from any network location
• Central control of internetworking equipment like:
Routers, servers, gateways, UPS
Communication...
DP300E rev 8.3
71
Determine the right solutionDetermine the right solution
QuestionsQuestions Do you require monitoring
Do you require shutdown
Number of Servers / Workstations
Network topology
Operating Systems
Communication...
DP300E rev 8.3
72
With the right solution...With the right solution...
Communication...
DP300E rev 8.3
73
Datasave Acrobat Reader UPSDatasave Acrobat Reader UPS DP-SOFT CDX / DP-SOFTDP-SOFT CDX / DP-SOFT
Communication...
DP300E rev 8.3
74
Orderly shutdown of one computer...Orderly shutdown of one computer...
Stand alone architectureStand alone architecture
Communication...
RS232
PC
Power
UPS
DP300E rev 8.3
75
Orderly shutdown
of one computer…
Broadcast to clients
on the network...
Stand alone architectureStand alone architecture
Communication...
Server
Client
UPS
Client
DP300E rev 8.3
76
Orderly shutdown of more Orderly shutdown of more computers...computers...
DP-SOFT CDX - Master/SlaveDP-SOFT CDX - Master/Slave
UPS Power
RS232
Network
Master
ClientsSlaves
Communication...
DP300E rev 8.3
77
UPS
Server 1 Server 2 Server 3 Server 4 Server 5 Server 6
Shutdown of more computers…Shutdown of more computers…
– For all OS supported by Soft+
– Daisy chainable
Multi-Link UnitMulti-Link Unit
Communication...
DP300E rev 8.3
78
14
NMS Application (Snap-in)
NMS
SNMP
TCP/IP
Network Driver
Console User interface NTMonitoring/Shutdown CoreDriver INI FilesUPS Proxy Sub AgentTCP/IPNetwork Driver
Console User interface NTMonitoring/Shutdown CoreDriver INI FilesUPS Proxy Sub AgentTCP/IPNetwork Driver
Monitoring your UPS Monitoring your UPS
through the network...through the network...
NMS Sub Agent for Novell, NT & OS/2NMS Sub Agent for Novell, NT & OS/2
Communication...
DP300E rev 8.3
79
NetNet workworkMonitoring your UPS Monitoring your UPS through the networkthrough the network
DP-View SNMP adapterDP-View SNMP adapter
Communication...
DP300E rev 8.3
80
Graphical user interface (GUI) for HP Graphical user interface (GUI) for HP Open View (NMS system) Open View (NMS system)
22
DP-View NavigatorDP-View Navigator
Windows 95Windows NTHP UNIX
Communication...
DP300E rev 8.3
81
DP - Dial UPSDP - Dial UPS
Monitoring your UPSMonitoring your UPS
- through the Public Telephone Network...- through the Public Telephone Network...
Control Centre
Mobile Phone Pager
DP-Dial UPS
RS232
RS232
Public TelephoneNetwork
Service Technician
LocalNetwork
Communication...
DP300E rev 8.3
82
Power AdministratorPower Administrator
Communication...
UPS Power
RS232
Relay
DP-SOFT+ DP-SOFT+ DP-SOFT+ DP-SOFT+
Local MonitoringDP-SOFT CDX
Network
NMS
Power Administrator 800
DP300E rev 8.3
83
Environment AdministratorEnvironment Administrator
Smoke Power Temp Lightning Air Conditioning Intruder Water UPS
Environment Administrator
Pager
Modem
Network ManagementStation
Communication...
84
DP300E rev 8.3
Minimizing the environmental impact...Minimizing the environmental impact...
Green Power with Green Power with Silcon DP300ESilcon DP300E
Green Power with Green Power with Silcon DP300ESilcon DP300EThe green aspects...
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
85
Power consumption
Low heat dissipation
Smaller installation cost
No mains repercussions
- by highest efficiency - less CO2-pollution from your power plant
- by highest possible power factor “1” saves fan energy
- due to the high efficiency -smaller cables and fuses
- saves costly EMC filters and energy losses
Longer battery lifetime - charge-voltage relative to battery temperature
Small space requirement - compact cabinet including many features as standard
Recyclable materials - No PVC´s
Green Power with Green Power with Silcon DP300ESilcon DP300E
Green Power with Green Power with Silcon DP300ESilcon DP300E
Green Power means saving resources in…Green Power means saving resources in…
The green aspects...
DP300E rev 8.3
86
Silcon DP300E - Silcon DP300E - EfficiencyEfficiency
Highest
efficiency
…saves energy
resources
…lower CO2
emission
97%
Silcon DP300E
Legacy UPS Systems
% Load
% Efficiency
The green aspects...
DP300E rev 8.3
87
Green Power with Green Power with Silcon DP300ESilcon DP300E
Charge voltage
compensated
...less battery
resources
No compensation
Temperature °C
Years
The green aspects...
Extended battery lifetime…
DP300E rev 8.3
88
Power factor 1
...less installation
resources
…less power
dissipation
Load (kW)
Input power factor
Green Power with Green Power with Silcon DP300ESilcon DP300EThe green aspects...
Power factor - “1”Power factor - “1”
DP300E rev 8.3
89
APC Silcon Division is the APC Silcon Division is the first UPS vendor withfirst UPS vendor with
ISO 14001 CertificationISO 14001 Certification
Green Power with Green Power with Silcon DP300ESilcon DP300EThe green aspects...
DET NORSKE VERITASENVIRONMENTAL SYSTEM CERTIFICATE
DP300E rev 8.3
90
ServiceService
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
91
AGS - AGS - 7. Division in APC7. Division in APC
AAPCPC
GGLOBALLOBAL
SSERVICEERVICE
Service
DP300E rev 8.3
92
AGS policyAGS policy
Consistent high quality Consistent high quality
““on site” service” on site” service”
- world wide- world wide
Service
DP300E rev 8.3
93
AGS - program...AGS - program...
Custom designed
service solutions
Service program from
buying process to
lifecycle of your UPS
Factory Acceptance Test
FAT
Service response time:within 24 hours
Every service call is completedwith a service report
Service
DP300E rev 8.3
94
Service productsService products
Premium Power Reliability package
Essential Power Reliability package
Annual Maintenance Program
Start-Up Service
Service
DP300E rev 8.3
95
Check of the system 1 - 2 times a year
Exchange of the battery at specified intervals
Exchange of the fans at specified intervals
The maintenance and repair costs are very different
- some gambles and do nothing - if lucky they have no costs.
- Others take out a complete maintenance and repair
insurance with a yearly fee of 20 - 25% of the UPS price.
The maintenance is normally consisting of:The maintenance is normally consisting of:
Maintenance & RepairMaintenance & Repair
Service
DP300E rev 8.3
96
AccessoriesAccessories
Headlines:
Cost of down time
Efficiency
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Fans
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
97
Battery cubicles BDPBattery cubicles BDP
Modularized cubicles for housing batteriesModularized cubicles for housing batteries
Matching cubicles from Matching cubicles from
DP310E to DP380EDP310E to DP380E
Battery storage
Easy battery accessibility
Easy to install
Small foot print
Clean cabinet design
Accessories
DP300E rev 8.3
98
Galvanic isolated transformersGalvanic isolated transformers
Modularized cubicles for housing transformers
Matching cubicles Matching cubicles
for all DP300E unitsfor all DP300E units
Transformer storage for
galvanic isolation
transformers
Accessories
DP300E rev 8.3
99
Remote displayRemote display
A convenient tool for the Facility ManagerA convenient tool for the Facility Manager
Matching the whole Matching the whole
DP300E familyDP300E family
Remote surveillance of UPS
Information identical to
UPS Display
Alarm features
Surveillance tool only
Operation distance - 25m
Accessories
DP300E rev 8.3
100
Service bypass panel -SBP300EService bypass panel -SBP300E
Bypass panel for efficient Bypass panel for efficient installation and safe installation and safe
maintenancemaintenance
Safe bypass operationSafe bypass operation
Switch panel for off-line operation
Intelligent communication to DP300E eliminates fault operation
Signal lamps indicate proper operation of the panel
Accessories
DP300E rev 8.3
101
Service bypass panel - SBP300EService bypass panel - SBP300E
Configurations...Configurations...
System input System output
Parallel/ Redundant System System input System output
Single System
Accessories
DP300E rev 8.3
102
Fuse box - MCCBFuse box - MCCB
Guarding the Silcon DP300E external battery bankGuarding the Silcon DP300E external battery bank
Safe battery Safe battery
installationinstallation
Protects against electric shocks
Enhances safety with coiling
and tripping facilities
Accessories
DP300E rev 8.3
103
Technical DataTechnical Data
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
104
Silcon DP300E: 10 - 480 KVA 3-phaseSilcon DP300E: 10 - 480 KVA 3-phase
120 kVA160 kVA240 kVA320 kVA480 kVA
400V
External Batteries
60 kVA80 kVA
400V
External Batteries
10 kVA20 kVA40 kVA
400V
Built-in Batteries
Technical data
- click for 208/ 480V data
DP300E rev 8.3
105
Silcon DP300E - PerformancesSilcon DP300E - Performances version 3x380/ 400/ 415Vversion 3x380/ 400/ 415V
Output power, kW/ kVA 10
Full load output current, Amp. 14.5
Type - Type - (version 3x380/ 400/ 415V)(version 3x380/ 400/ 415V)
Max input current, Amp. 18.9
Efficiency AC to AC, 100% load, % 94.8
20
29.0
37.6
95.5
40
57.7
74.7
96.5
60
87
112
96.1
80
115
147
96.5
DP310EDP310E DP320EDP320E DP340EDP340E DP360EDP360E DP380EDP380E
Typical losses, nominal load, kW 0.5 0.9 1.5 2.4 2.9
Type - Type - ((version 3x380/ 400/ 415V)version 3x380/ 400/ 415V) DP3120EDP3120E DP3160EDP3160E DP3240EDP3240E DP3320EDP3320E DP3480EDP3480E
Output power, kW/ kVA 120
Full load output current, Amp. 173
Max input current, Amp. 219
Efficiency AC to AC, 100% load, % 95.8
160
231
293
96.3
240
346
450
96.3
320
462
582
96.8
480
693
874
96.8
Typical losses, nominal load, kW 5.3 6.2 9.2 10.6 15.9
Technical data
- click for 208/ 480V data
DP300E rev 8.3
106
Silcon DP300E - General SpecificationsSilcon DP300E - General Specifications version 3x380/ 400/ 415Vversion 3x380/ 400/ 415V
Static bypass switch Built-in
Communication Interface Built-in
GeneralGeneral Specifications - (version 3x380/ 400/ 415V)
Ambient temperature 0-40 °C (above 25 °C the battery life time is reduced)
Humidity Max 95% (non condensing)
Protection Class IP 30
Safety,CE EN50091-1
UL 1778
EN50091-2
Advanced bat. Monitoring Programmable
Auto restart Programmable
CE, Emission and Immunity
Technical data
- click for 208/ 480V data
DP300E rev 8.3
107
Silcon DP300E - Technical input dataSilcon DP300E - Technical input data version 3x380/ 400/ 415Vversion 3x380/ 400/ 415V
Input voltage 3x380/ 400/ 415
Input tolerance, mains opr. ± 15%
InputInput specifications - (version 3x380/ 400/ 415V)
Input tolerance, bypass opr. ± 10% (standard) 4, 6, 8, % prog.
Input frequency 50 Hz ± 6% (standard), 0.5-8% prog.
Input power factor > 0.97 (load 25%), >0.99 (load 100%)
Technical data
- click for 208/ 480V data
DP300E rev 8.3
108
Silcon DP300E - Technical output dataSilcon DP300E - Technical output data version 3x380/ 400/ 415Vversion 3x380/ 400/ 415V
Output voltage 3x380/ 400/ 415
Output tolerance ± 1% static, sym. load
Output specifications Output specifications - (- (version 3x380/ 400/ 415V)version 3x380/ 400/ 415V)
tolerance ± 3% static, asym. load
Voltage distortion Max 3% linear load
tolerance ± 5% 0-100% load step
Max 5% non-linear loaddistortion
Load power factor 0.9 lead to 0.8 lag
Output frequency 50 Hz (mains synchronized)
± 0.1% free funning
Overload capacity, mains opr. 200% - 60 secs., 125% - 10 min.
batt. opr. 150% - 30 secs.,
DP310E - DP 3320E bypass opr. 1000% - 500 msec.
DP3480E bypass opr. 660% - 500 msec.
Technical data
- click for 208/ 480V data
DP300E rev 8.3
109
Benchmarking 10kVA systemsBenchmarking 10kVA systems
Technical data
- click for 208/ 480V data
Product
Output power 10 kW / 10 kVA 8 kW / 12 kVA 8 kW / 12 kVA 8 kW / 12 kVA
Input voltage 208 208 208 208
Run Time (Full Load)
16 - 30 min. 7 - 18 min. 8 min. 8 - 10 min.
AC to AC efficiency 94.8% 89% 89% N/A
Power Factor 0.99 0.96 N/A 0.96
Acoustic noise 57dBA 57dBA 57dBA 57dBA
Dimensions (in)
High 55.12 28.10 36.00 62.00
Width 23.62 34.00 20.50 41.00
Depth 31.50 28.60 23.00 27.00
Weight 803 lbs. 920 lbs. 590 lbs. 702 lbs.
APCDP300E
Exide Powerware
Plus 18
MGEEPS 3000
LiebertUPStation S3
DP300E rev 8.3
110
Silcon DP300E: 10 - 500 KVA 3-phaseSilcon DP300E: 10 - 500 KVA 3-phase
100 kVA(160 kVA)(320 kVA)(500 kVA)
External Batteries
60 kVA80 kVA
External Batteries
10 kVA15 kVA20 kVA30 kVA40 kVA
Built-in Batteries
200V, 208V & 480V 200V, 208V & 480V 480V
Technical data
- bypass 208/480V technical data
DP300E rev 8.3
111
Silcon DP300E - PerformancesSilcon DP300E - Performances version 208V/ 480Vversion 208V/ 480V
Output power, kW/ kVA 10
Full load output current, Amp. 27.8
Type - (version 208V)
Max input current, Amp. 37.5
Efficiency AC to AC, 100% load, % 93.6
15
41.6
56.3
93.6
20
55.5
75.0
94.5
30
83.3
113
94.7
40
110
150
95.0
DP310E DP315E DP320E DP330E DP340E
Typical losses, nominal load, kW 0.7 1.0 1.2 1.7 2.1
Efficiency AC to AC, 50% load, % 91.9 90.0 92.0 92.1 93.8
Output power, kW/ kVA 10
Full load output current, Amp. 12
Type - (version 480V)
Max input current, Amp. 15.6
Efficiency AC to AC, 100% load, % 94.3
15
18
23.5
94.3
20
24.1
31.3
94.9
30
36.1
47.0
94.3
40
48.1
62.5
95.0
DP310E DP315E DP320E DP330E DP340E
Typical losses, nominal load, kW 0.6 0.9 1.1 1.8 2.1
Efficiency AC to AC, 50% load, % 91.3 91.5 93.3 90.8 92.9
Technical data
- bypass 208/480V technical data
DP300E rev 8.3
112
Silcon DP300E - General SpecificationsSilcon DP300E - General Specifications version 208V/ 480Vversion 208V/ 480V
Static bypass switch Built-in
Communication Interface Built-in
General Specifications (version 208V/ 480V)
Ambient temperature 32-104 °F (above 77 °F the battery life time is reduced)
Humidity Max 95% (non condensing)
Protection Class IP 30
Safety,CE EN50091-1
Safety, UL 1778
EN50091-2
Advanced bat. Monitoring Programmable
Auto restart Programmable
CE, Emission and Immunity
Backfeed protection Built-in
Technical data
- bypass 208/480V technical data
DP300E rev 8.3
113
Silcon DP300E - Technical input dataSilcon DP300E - Technical input data version 208V/ 480Vversion 208V/ 480V
Input voltage 3x208V/ 3x480V
Voltage tolerance, mains opr.
± 15%
Input specifications (version 208V/ 480V)
Voltage tolerance, bypass opr.
± 10% (standard) 4, 6, 8, % prog.
Input frequency 60 Hz ± 6% (standard), ± 0.5-8% prog.
Input power factor > 0.97 (load 25%), >0.99 (load 100%)
Technical data
- bypass 208/480V technical data
DP300E rev 8.3
114
Silcon DP300E - Technical output dataSilcon DP300E - Technical output data version 208V/ 480Vversion 208V/ 480V
Output voltage 3x208V/ 480V
Output tolerance ± 1% static, sym. load
Output specifications (version 208V/ 480V)
tolerance ± 3% static, asym. load
Voltage distortion Max 3% linear load
tolerance ± 5% 1-100% load step
Max 5% non-linear loaddistortion
Load power factor 0.9 lead to 0.8 lag
Output frequency 60 Hz (mains synchronized)
± 0.1% free funning
Overload capacity, mains opr. 200% - 60 secs., 125% - 10 min.
batt. opr. 150% - 30 secs.,
bypass opr. 125% - cont.
bypass opr. 1000% - 500 msec.
Technical data
- bypass 208/480V technical data
115
DP300E rev 8.3
Benchmarking 10kVA systemsBenchmarking 10kVA systems
Product
Output power 10 kW / 10 kVA 8 kW / 12 kVA 8 kW / 12 kVA 8 kW / 12 kVA
Input voltage 208 208 208 208
Run Time (Full Load)
16 - 30 min. 7 - 18 min. 8 min. 8 - 10 min.
AC to AC efficiency 94.8% 89% 89% N/A
Power Factor 0.99 0.96 N/A 0.96
Acoustic noise 57dBA 57dBA 57dBA 57dBA
Dimensions (in)
High 55.12 28.10 36.00 62.00
Width 23.62 34.00 20.50 41.00
Depth 31.50 28.60 23.00 27.00
Weight 803 lbs. 920 lbs. 590 lbs. 702 lbs.
APCDP300E
Exide Powerware
Plus 18
MGEEPS 3000
LiebertUPStation S3
Technical data
- bypass 208/480V technical data
DP300E rev 8.3
116
Customer Customer references references
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
117
Insurance's - CodanInsurance's - Codan
Statement…
"As an Insurance company, we always rate security highly and therefore the security of the data in our computers must also be at the highest level”
Phrases from the statement:
– We protect all our business data with UPS equipment from Silcon.
– Before choosing Silcon we analysed 2 different suppliers.
– Several power-down situations has been
handled by the Silcon equipment in battery back-up mode or by controlled shut-down.
– In the end - it is a matter of finance
Codan Network - Mr. Lars M. Anker Section Leader, Denmark
Codan is one of Denmark’s biggest and best consolidated insurance companies.Codan has branches throughout the country and the concern has about 2000 employees. The Codan concern comprises banking as well as the insurance business.
Customer references
DP300E rev 8.3
118
Customer ReferenceCustomer ReferenceBankdata - DenmarkBankdata - Denmark
BankingLloyds Bank - London
Annual savings USD 140, 000.-
Bankdata, Denmark
Ove vestergaard, Managing Director,Bankdata
Mr. Julian Baarwell, Lloyds Bank Engineering Manager
Lloyds Bank - London
Installation: 2.7 megawatt of Silcon UPS supplies
“Our original calculations showed
that we would save USD 70,000 in electricity
bills every year. That wasn’t right
DP300E rev 8.3
119
HitachiSemiconductor GmbH
One of the biggest supplier of electronic components in the world.
• 330.000 employees
• 6 billion USD in turn over
Peter NikonowitchHitachi, Tyskland
Semiconductors - Semiconductors - HITACHIHITACHI
Peter Nikonowitch says…
“Quality and safety comes first”
“10 milliseconds of power down is fatal for a whole production batch.
Beside the power security we have achieved essential savings in power consumption.
The technology and the environmental aspects we have achieved with the Silcon DP300E product has also been decisive”.
Customer references
DP300E rev 8.3
120
IT ServicesIT ServicesIBM Megacentre in Portsmouth UKIBM Megacentre in Portsmouth UK
IBM chose Silcon DP300E systems
IBM´s European and Middle East/African organizationhave put their trust in the safetyof their business data in the handsof APC/Silcon-UPS.
“If you have 6 Mega watt to back-upthe efficiency of the UPS system is essential.”
Chris Hayes, UPS ConsultantIT Infrastructure Services
Installation:
6 x DP3440 in parallelCapacity: 2 x 2.64 MWAdditional: 540 kW on vital systems12 minutes back-up at a load of 6 MW2.5 MW generator back-up
“We can’t afford any drops at all”
Customer references
SHELL, Danmark
“We power ensure the whole control center with the Silcon UPS systems.Most essential for us was the low heat emission - meaning lower installation and operation costs”.
SHELL refinery in Fredericia
ChemicalsChemicalsShellShell
Shell in Frederica has the most advanced control system in the world !
Customer references
DP300E rev 8.3
122
Air transportationAir transportationRDM LufthansaRDM Lufthansa
Statement…
“For RDM Lufthansa security and reliability are very important. With round-the-clock working and on-line access to RDM Lufthansa's host system in Germany, a power failure would have very serious financial consequences for the airline company”.
RDM Lufthansa, India
Customer references
“We simply can't afford to go down because of a
power cut.APC´s Silcon UPS systems gives us reliability and we
get the service we need through El-Pan, APC's
partner in India”.
DP300E rev 8.3
123
HospitalsHospitalsLänssjukhuset Ryhov HospitalLänssjukhuset Ryhov Hospital
“It is of vital importance for hospitals to have high quality and constant power supply.
Without power - it is impossible for doctors to help many of there patients - babies in incubators, patients undergoing surgery or dialysis etc.
It is obvious that we put extreme demands on our UPS supplier”
“I feel secure in having chosen Silcon and I know that each UPS system is produced with care and absolute precision
Moreover the Silcon equipment is environmentally friendly with extreme high efficiency”
Länssjukhuset Ryhov is a Swedish hospital.The 200,000 m2
hospital was opened in 1988 and today employs 3700 people.
Mr. Bengt JönssonTechnical Engineer
Customer references
DP300E rev 8.3
124
Banking Banking Bankdata - DenmarkBankdata - Denmark
Statement…“We have always maintained the policy that one power cut per year is acceptable only. But since we have recently suffered three successive power cuts, we took the decision to install our own emergency power supply”.
The project:396 batteries - 11 tons - 10 minutes back-up time4 Silcon DP300E UPS systems1 Diesel generator - takes over after 30 seconds
Ove Vestergaard, Bankdata, Managing Director, …
”We have estimated that in 1996 alone, the Silcon installation has saved us some USD 4 million worth of losses by protecting critical infrastructure against power failures”
Erik Nielsen, Bankdata’s Installation Manager says...With the Silcon equipment we have installed some of the best electrical energy transformer systems with full back-up service.Bankdata can now be added to an already impressive client list.Bankdata is a data centre for 18 banks - employing 225 people - supporting banks with modern EDP systems.
Bankdata, Denmark
Silcon Technology
Customer references
DP300E rev 8.3
125
American ExpressLloyds Bank, UKBGZ PolandQingdao City Bank, ChinaCzech National BankPekao, PolandOrel Bank, RussiaCrediplus, PortugalUBS, SwitzerlandInter-Europa Bank, HungarySlovak Stock ExchangeRaiffeisenbank, GermanyGenerali, IrelandCitibank, DenmarkChase Manhattan Bank, USADen Danske Bank, DenmarkBank of New ZealandBloomberg, JapanBCA, IndonesiaDresdner Bank, Germany
National Bank of SlovakiaBank OTP, HungaryXiosbank, GreecePacific Finance,ThailandUlster Bank, IrelandMBNA Bank, UKSBG, SwitzerlandAlliance & Leicester, UKFINIbanco, PortugalJordan Gulf BankAllied Irish Bank, IrelandParibasSydbank, DenmarkDeutsche Bank, Germany
BankingBanking
Customer references
DP300E rev 8.3
126
Tele communicationTele communicationTelia - UKTelia - UK
””APC´s Silcon products are probably going APC´s Silcon products are probably going to the front in UPS support for to the front in UPS support for telecommunications”telecommunications”
“The Silcon UPS is like having a gentle giant
hidden in your cupboard that you can pull out when ever you fancy. So we are very happy with the Silcon
product".
Mr. Paul MulvenneFacilities Manager
"The main reason for choosing Silcon UPS systems over the
competitors considered, was the electronics.
The electronics gives advantages and behaves in a much more
structured way. This meets the needs of the
Telecoms.
Customer references
DP300E rev 8.3
127
Portugal PTTNokiaFinland PTTEricsson LMTelecom EireannMotorolaMCI USATeleDanmarkSonofonFrance TelecomTelecom New ZealandT.T. Mobiles IndiaAT&TPolish TelecomSwiss PTTGlobal OneAlcatelSwissphoneTeleDanmark MobilVEW Telnet D
FujitsuBritish TelecomPolish Mobile PhoneTeletas TurkeyTelex-Exchange IndonesiaCity Telephone ChinaTaiyan PTT ChinaPTT ChinaGEC AlsthomBosch TelecomTelesystem MobilfunkTMI Telecom ItaliaTeliaDutch PTTOrange TelecomVODAphoneDeutsche TelecomPost UngarnTele NordiaTelecom Malaysia
Tele communicationsTele communicationsCustomer references
DP300E rev 8.3
128
Installation Installation
Headlines:
Cost of down time
Efficiency
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Fans
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
Headlines:
Cost of down time
Efficiency
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Fans
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
129
Consider:Consider:
Size Is there enough space on the installation site? Will it go through the door? Is there free space for servicing and
operation?
Weight Will the floor carry the load? Can the lift carry the load? How can it be lifted off the pallet?
Fuses Which fuses to use in installation?
Cables What cable size to use in the installation? And where to connect to the DP300E (cable entry)?
Where to find information:
Spec SheetInstallation GuideQuick Reference
Data SheetInstallation GuideQuick Reference
Installation GuideQuick Reference
Installation GuideQuick Reference
Installation of DP300EInstallation of DP300E
Installation
DP300E rev 8.3
130
Where to find information:Where to find information:
Installation Guide Quick Reference
Please note on ordering sheet
Consider:Consider:
Heat dissipation:• Ensure correct dimensioning of the air
conditioning system
Diesel generators:• Due to the sinusoidal input current a diesel
generator of only 1.3 times the size of the DP300E can be used. (A diesel for a traditional UPS must be 3-5 times the size of the UPS)
• For very sensitive diesels the DP300E series can be programmed for soft start (diesel
modification).
Installation of DP300EInstallation of DP300E
Installation
DP300E rev 8.3
131
Consider:Parallel operation:
Parallel to increase output power. Redundancy to increase safety. Up to four standard systems can be paralleled (only parallel boards needed). With external static switch up to nine systems
can be paralleled (parallel boards and external static switch needed.
Parallel systems can have common or separate batteries.
Batteries: Configuration sheet for Johnson control
batteries are available. Battery dimensioning for special applications
has to be handled from case to case.
Where to find Where to find informationinformation::
Installation GuideAPC Tech Support
Installation GuideAPC Tech Support
Installation of DP300EInstallation of DP300E
Installation
DP300E rev 8.3
132
Review Review
Headlines:
Cost of down time
Efficiency
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Fans
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
Headlines:
Cost of down time
Performances and benefits
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review
DP300E rev 8.3
133
....On-line UPS ?
....High efficiency ?
....Full kW Rating ?
....No mains repercussions ?
....Input power factor correction ??
What does it mean ?What does it mean ?
Review
DP300E rev 8.3
134
Delta-conversion UPS systems...Delta-conversion UPS systems...
Highest up-time on IT equipment
Low operation costs
Low installation costs
More protection capacity
Environmentally friendly UPS system
Silcon DP300E benefits... Silcon DP300E benefits...
Review
DP300E rev 8.3
135
Silcon DP300ESilcon DP300E Delta TechnologyDelta Technology
Silcon DP300E benefits... Silcon DP300E benefits...
“Close to perfect”
Review
DP300E rev 8.3
136
Questions
End of End of presentationpresentation
Cost of down time
Performance and benefits
UPS power factor
Economy
Parallel operation
Advanced battery management
Power Control - “Diesels best friend”
Communication and operations
Green Power aspects
Service
Accessories
Technical data
Customer references
Installation considerations
Review