DRY TYPE TRANSFORMERS

Single-phase, Three-phase/Single-phase, Three-phase/Two-phase,Three-phase

1.1 kV to 7.2kV Class

Page 2: DRY TYPE TRANSFORMERS - augier.com

2

Dry Type Transformers

Transformers meant to be installed in a dry and air conditioned room or in a

PTI AUGIER type substation.

ELECTRICAL CHARACTERISTICS :

Power rating and type :

Single-phase : TMAI : 5 - 7.5 - 10 - 16 - 25 - 32 - 50 kVA

Three-single : TTMAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 kVA

Three-two : TTBAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 kVA

Three-phase : TTAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 - 200

250 - 400 - 500 - 630 kVA

Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV

Primary voltage : Every voltage compatible with insulation voltages above.

Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V - 5500 V and

6600 V.

Secondary load voltage : 230 V - 400 V - 950 V - 3200 V - 5500 V and 6600 V.

Couplings :

Standard : Three-phase transformer : Step-down Dyn11 - Step-up YNd1– single-phase transformer :Ii0

Specific : Three-single transformer, Leblanc three-two transformer, other couplings on request.

Manufacturing specifications on request : Inrush current transformer reduced or very reduced.

CONNEXION:

Primary and secondary connesion on copper slots, by the upper side of the transformer.

STANDARD ACCESSORIES :

Empty setting plugs : Three outputs on slots.

Two earthing switches.

Lifting lugs.

Four rollers for 10 kVA and higher power rating transformers.

NOTE :

Transformers mechanical and electrical characteristics are the same

for step-down or step-up transformers. The tranformers are not

reversible.

Step-up transfrormers are built so that inrush currents are

limited.

Single-phase transformer, TMAI type, with IP21 encolsure, fuse terminal 3200 V

and locking.

Page 3: DRY TYPE TRANSFORMERS - augier.com

3

CONSTRUCTION :

Magnetical circuits with crystal made sheet metal, oriented, with low losses.

Copper windings, vacuum impregnated of H class and applying of a fungicide varnish.

Metallic flanges.

Ironed chassis with rollers.

Wooden terminals plate bakelised.

Cooling : in natural air : NA.

Use : use in dry, air conditioned rooms, at a room temperature of -15 °C ; + 40°C.

Color : RAL 7035 gray.

STANDARDS AND TESTS : Conforms to NF C 17-200 - NF C 52-100 - IEC 60076 standards.

Other specifications on request. Routine tests U.T.E made on each transformer, specific tests on request..

Dry type transformer, naked presentation on frame

Connexion plates

Tap changer

MV side view

Dry type transformer

With IP21 enclosure

Lifting lugs

Connexion plates

LV side dismantle panel

Fixation by screw

rollers

Signaletic plate

Firm plate

LV side dismantling panel

Side panel dismantling

(cables passage)

Fixation by screw

Bakélite matter

To be screwed on request

Page 4: DRY TYPE TRANSFORMERS - augier.com

4

ELECTRICAL CHARACTERISTICS

Power rating (kVA) 25 50 100 160 200 250 400 630 16 32 63 80 125 500

Copper losses

at 75°C (W) 470 800 1350 2000 2300 2800 4200 7300 350 550 1000 1100 1400 5600

Iron losses (W) 180 250 450 500 550 650 900 1500 100 200 250 380 450 1250

Voltage drop

(% )

at Cos = 0.83

3 3.14 3.2 3.4 3.2 3.15 3.5 3.5 3.3 3.07 3.4 3 3 3.5

CC tension

(%) at 75°C 3.2 3.5 4 4 4 4 4 5 3.4 3.4 4 3.5 4 4.5

Empty current

(%) 0.7 0.9 0.9 0.7 0.5 0.5 0.8 0.7 1 0.8 0.7 0.8 0.6 0.6

Three-phase dry Type Transformers TTAI

ELECTRICAL CHARACTERISTICS :

Power rating:

16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 - 200 - 250 - 400 - 500 - 630 kVA

Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV

Primary voltage : Every voltage compatible with insulation voltages above.

Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V - 5500 V and

6600 V.

Secondary load voltage : 400 V - 950 V - 3200 V - 5500 V and 6600 V.

Couplings :

Step-down Dyn11 - Step-up YNd1, other couplings on request.

CONNEXION :

Primary and secondary connexions on copper plates, by the upper side of the transformer.

STANDARD ACCESSORIES :

Voltage tapping adjustable out of voltage : +/- 2,5 % or +- 5% output on slots.

Two earthing terminals.

Lifting lugs.

Four rollers for 10 kVA and higher power rating transformers.

Naked presentation on frame : IP00.

OPTIONAL ACCESSORIES Painted sheet metal enclosure with natural airing upwards, IP21.

Connexion on pluggable terminals 3200 V or 5500 V.

HRC fuses protection integrated above the protection envelop.

Thermal protection by thermal probe integrated to windings, one or two thresholds protection.

Tap changers +/- 2,5 % +/- 5%.

Keyhole locking of the protection envelop and or pluggable terminals.

NOTE :

Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The

tranformers are not reversible.

Step-up transfrormers are built so that inrush currents are limited.

Page 5: DRY TYPE TRANSFORMERS - augier.com

5

TTAI Dry Transformers

SIZES-WEIGHT (mm) - PRESENTATION ON IP00 FRAME - STEP DOWN TRANSFORMER

Power rating

(kVA) 25 50 100 160 200 250 400 630 16 32 63 80 125 500

A 750 825 930 980 1000 1096 1240 1600 636 825 840 930 950 1400

B 480 500 530 530 570 660 660 900 400 500 520 530 530 830

C 670 718 809 858 889 1086 1134 1650 611 718 734 809 836 1300

D 510 510 580 610 650 690 770 900 380 510 520 580 590 870

E 400 400 440 440 465 520 520 520 295 400 400 440 440 520

Weight (kg) 270 345 465 600 700 940 1185 1800 155 310 365 450 525 1450

SIZES-WEIGHT (mm) - PRESENTATION WITH IP21 ENCLOSURE - STEP DOWN TRANSFORMER

Power rating

(kVA) 25 50 100 160 200 250 400 630 16 32 63 80 125 500

A 960 1040 1140 1190 1220 1310 1550 1810 850 1040 1050 1140 1160 1610

B 630 650 660 680 720 810 810 1050 550 650 660 660 660 980

C 970 1030 1100 1200 1200 1390 1500 1950 900 1020 1040 1100 1140 1600

D 510 510 580 610 650 690 770 900 380 510 520 580 590 870

E 400 400 440 440 465 520 520 520 295 400 400 440 440 520

Weight (kg) 300 400 565 750 900 1150 1450 2050 185 350 405 535 630 1700

Protection degree IP00

Protection degree IP21

Page 6: DRY TYPE TRANSFORMERS - augier.com

6

Single-phase Dry Type Transformers TMAI

ELECTRICAL CHARACTERISTICS :

Power rating: 5 - 7,5 - 10 - 16 - 25 - 32 - 50 kVA

Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV

Primary voltage : Every voltage compatible with insulation voltages above.

Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V.

Secondary load voltage : 230 V - 950 V - 3200 V.

Couplings :

Standard : single-phase transformer : Ii0

CONNEXION :

Primary and secondary connexions on copper plates, by the upper side of the transformer.

STANDARD ACCESSORIES :

Voltage tapping adjustable out of voltage : +/- 2,5 % ou +- 5% sorties sur plages.

Two earthing terminals.

Lifting lugs.

Four rollers for 10 kVA and higher power rating transformers.

Naked presentation on IP00 frame.

OPTIONAL ACCESSORIES Painted sheet metal enclosure with natural airing upwards, IP21.

Connexion on pluggable terminals.

HRC fuses protection integrated above the protection envelop.

Thermal protection by thermal probe integrated to windings, one or two thresholds protection.

Tap changers +/- 2,5 % +/- 5%.

Keyhole locking of the protection envelop and or pluggable terminals.

NOTE :

Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The

tranformers are not reversible.

Step-up transfrormers are built so that inrush currents are limited.

ELECTRICAL CHARACTERISTICS

Power rating (kVA) 5 7,5 10 16 25 32 50

Copper losses

at 75°C (W) 100 120 170 380 500 630 750

Iron losses

(W) 40 60 60 80 120 150 200

Voltage drop (% )

at Cos = 0.83 2.92 2.47 3.35 3.7 3.53 3.55 3.7

Cc tension

(%) at 75°C 2.95 2.67 3.75 3.86 3.78 4 4

Empty current

(%) 3.11 2.53 2.58 2.67 2.52 2.54 2.51

Page 7: DRY TYPE TRANSFORMERS - augier.com

7

TMAI Dry Transformers

SIZES-WEIGHT (mm) - PRESENTATION ON IP00 FRAME

Power rating (kVA) 5 7,5 10 16 25 32 50

A 320 400 400 540 600 630 650

B 320 390 390 400 400 450 460

C 372 560 494 632 652 710 749

D - - 320 300 315 270 270

E - - 218 230 245 270 270

Weight (kg) 45 72 84 140 190 230 265

SIZES-WEIGHT (mm) - PRESENTATION WITH IP21 ENCLOSURE

Power rating(kVA) 5 7,5 10 16 25 32 50

A 380 424 424 570 630 670 700

B 344 414 414 450 460 550 570

C 532 570 600 830 850 960 1020

D - - 320 300 315 270 270

E - - 218 230 245 270 270

Weight (kg) 56 83 98 160 220 270 310

Protection degree IP00

Protection degree IP121

Page 8: DRY TYPE TRANSFORMERS - augier.com

8

AUGIER IS CERTIFIED ISO 9001 SINCE 1995

60 4

0152

Wit

h c

onst

ant

imp

rovem

en

ts,

the

man

ufa

ctu

rer

may a

lter

info

rmat

ion w

itho

ut

pri

or

war

nin

g