STATE OF QATAR STATE OF QATAR STATE OF QATAR STATE OF QATAR NEW PORT PROJECT STEERING Committee NEW PORT PROJECT STEERING Committee NEW PORT PROJECT STEERING Committee NEW PORT PROJECT STEERING Committee NEW PORT PROJECT NEW PORT PROJECT NEW PORT PROJECT NEW PORT PROJECT CONTAINER TERMINAL, INFRASTRUCTURE AND UTILITY BUILDINGS NPP/0026 Document Title : CONTAINER TERMINAL-1 LV CABLE SIZING CALCULATIONS Document No. DPCT-TCC-CAL-EL-00066 TEYSEER CONTRACTING COMPANY WLL/ CONSOLIDATED CONTRACTORS GROUP S.A.L. (OFFSHORE) (CCC) JV TCC/CCC JV 01 RE-ISSUED FOR APPROVAL Syed. GH C. Ranjit G. Kawash 00 ISSUED FOR APPROVAL Syed. GH C. Ranjit G. Kawash Rev Description Prepared by Reviewed by Approved by Signature: Date: 14.08.2014 14.08.2014 14.08.2014

Electrical Cable sizing

Embed Size (px)

DESCRIPTION

Cable sizing guidelines

Citation preview

  • STATE OF QATARSTATE OF QATARSTATE OF QATARSTATE OF QATAR

    NEW PORT PROJECT STEERING CommitteeNEW PORT PROJECT STEERING CommitteeNEW PORT PROJECT STEERING CommitteeNEW PORT PROJECT STEERING Committee

    NEW PORT PROJECTNEW PORT PROJECTNEW PORT PROJECTNEW PORT PROJECT

    CONTAINER TERMINAL, INFRASTRUCTURE AND UTILITY BUILDINGS

    NPP/0026 Document Title :

    CONTAINER TERMINAL-1

    LV CABLE SIZING CALCULATIONS

    Document No. DPCT-TCC-CAL-EL-00066

    TEYSEER CONTRACTING COMPANY WLL/ CONSOLIDATED CONTRACTORS GROUP S.A.L.

    (OFFSHORE) (CCC) JV TCC/CCC JV

    01 RE-ISSUED FOR APPROVAL Syed. GH C. Ranjit G. Kawash

    00 ISSUED FOR APPROVAL Syed. GH C. Ranjit G. Kawash

    Rev Description Prepared by Reviewed

    by Approved

    by

    Signature:

    Date: 14.08.2014 14.08.2014 14.08.2014

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 2 of 45

    TABLE OF CONTENTS

    1. SCOPE .................................................................................................................................................. 3

    2. REFERENCE DOCUMENTS ................................................................................................................ 3

    3. INITIAL DATA AND ASSUMPTIONS ................................................................................................... 3

    4. CABLE SIZING CRITERIA ................................................................................................................... 4

    4.1. VOLTAGE DROP .................................................................................................................................. 5

    4.2. AMPACITY ............................................................................................................................................ 6

    4.3. SHORT CIRCUIT ................................................................................................................................... 6

    5. CABLE SIZING REQUIREMENTS ....................................................................................................... 7

    5.1. VOLTAGE DROP .................................................................................................................................. 7

    5.2. AMPACITY ............................................................................................................................................ 7

    6. DE-RATING FACTORS FOR CABLES. ............................................................................................... 8

    6.1. De-rating factors for cables installed in Ducts in the ground. ........................................................ 8

    6.2. De-rating factors for cables Installed in Air. ..................................................................................... 9

    6.3. THERMAL SHORT CIRCUIT CAPACITY........................................................................................... 10

    7. APPENDICES ...................................................................................................................................... 14

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 3 of 45

    1. SCOPE

    The objective of this calculation report is to establish the method to be used for the sizing of the Low Voltage power cables for the Low Voltage power distribution system and motors at Container Terminal-1 Utility Buildings and Infrastructure of New Doha Port Project.

    2. REFERENCE DOCUMENTS

    The following documents have been taken into account for the cable sizing calculation:

    Specification Section 21: Electrical Works : 9224-05-EL-SPC-7001 Regulation for Installation of Electrical

    Wiring, Electrical Equipment and Air Conditioning Equipment-Dec 2010 : QGEWC / KAHRAMAA

    IEC Electrical Installation of Buildings : IEC-60364-5-52-2001 Selection and erection of Electrical Equipment Wiring Systems

    DOHA CABLES Catalogue for XLPE Insulated Low Voltage Cables.

    3. INITIAL DATA AND ASSUMPTIONS

    The power cables have been sized taking into consideration the following data and cable type:

    Nominal voltage system: 240 / 415V Cable insulation level BS(IEC) kV: 0.6/1 kV (0.6/1 kV) Conductor material: Cu (Copper) Insulation material: XLPE

    o Maximum conductor operating temperature: 90C o Maximum short circuit temperature: 250C

    Thermal Resistivity values for direct buried cable installations: 2.0C. m/W (KM standards section 3.3.12.1 and Specification Section 21: Electrical Works)

    Design conditions for electrical cables:

    o Underground cable (buried) 40C o In air 50C

    The LV cables for power distribution system and the loads shall be as follows:

    Cable shall comprise of plain copper, stranded circular conductors insulated with an adequate thickness of extruded cross linked polyethylene (XLPE).

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 4 of 45

    Up to 10 Sqmm Cu/XPLE/PVC, unarmoured cable for indoor installations. 16 Sqmm and above Cu/XLPE/SWA/PVC for armoured multicore cable for both indoor and outdoor

    installations. Cu/XLPE/SWA/LSHF armoured cable for the power supply to D & B (Manned) Buildings from the

    Utility Buildings. Armoured multicore cable shall have steel wire armouring and extruded sheath of black PVC. Armoured single core cable shall have aluminium wire armouring and extruded sheath of black PVC.

    The cable sizing will be performed considering multi-core cables up to 240 mm2 for distribution cables. For power, lighting and control cables the minimum cross section shall be 2.5 mm2. Maximum cross section for single-core cables shall be 630mm2. Single core cables may be used for practical and/or economic reasons, e.g., transformer secondary cables or in case of high current ratings where two parallel multicore cables of the largest cross section permitted would not suffice. All three single core cables shall be laid in trefoil formation.

    Sizing of motor feeders and power feeders will be performed taken into account the Full Load Ampacity (FLA) of the equipment (100% loaded). The system voltage is assumed to be at 100% nominal voltage. Standard power factors and efficiencies at 90% load will be used in this calculation, in case of absence of precise data.

    All LV Cables shall be installed in ducts throughout the Container Terminal-1 Area. The uPVC ducts are provided with the concrete encasement for LV Cables at road crossings only. The LV Cables shall be laid at a depth of 600mm as minimum.

    In the Container Terminal-1 Area, all the ducts shall be installed with minimum ground cover of 900mm otherwise it shall be concrete encased.

    All LV cables in Buildings shall be installed on cable trays/ Trunking/ Conduits as per Specification section 21: Electrical Works Doc. No.: 9224-05-EL-SPC-7001 clause 9.3.3.

    The correction factors / de-rating factors for the cables installed in Ducts and in Air are taken from DOHA CABLES Catalogue.

    4. CABLE SIZING CRITERIA

    Sizing of LV cables will be based on the compliance of all of the following criteria:

    Voltage Drop Continuous Current Carrying Capacity (Ampacity) Thermal Short Circuit Capacity

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 5 of 45

    4.1. VOLTAGE DROP

    A feeder shall be sized in such a way that the maximum voltage drop over the cable ensures the proper operation of the associated equipment in normal service. Excessive voltage drop will result in unsatisfactory operation of electrical equipment, and represents energy wasted in the cabling system. Voltage drop can also cause damage to electrical Equipment.

    The following formula will determine the voltage drop:

    For feeders and motors under running conditions (three phases and single phase):

    For motors under starting conditions (three phases and single phase):

    ( )Vn

    XcRclIkV ssstartingd

    100sincos +=

    DC voltage drop can be computed using the formula:

    VnRdclIV Nd

    1002=

    Where: Vd Voltage drop in percentage IN Rated current (FLA for motors) in Amps Istarting Starting rated current in Amps V System voltage in volts n Number of parallel runs

    l Length (km) Rc AC conductor resistance at rated conductor temperature at 90 Degree C in (/km) Xc Reactance of the cable (/km) at 50Hz, (For Rc and Xc Values see Appendix 14). cos Power factor

    cos s Starting power factor k 3 for three-phase consumers and 2 for single phase consumers.

    Note: The voltage drops are related to the terminals of the end equipment, and assumes that the associated main switchboard from which the equipment is fed will normally be operated at a voltage of not less than 100% of system voltage.

    ( )Vn

    XcRclIkV Nd

    100sincos +=

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 6 of 45

    4.2. AMPACITY

    The current carrying capacity of a cable corresponds to the maximum current that it can carry under specified conditions without the conductor exceeding the permissible limit of steady state temperature for the type of insulation concerned. De-rating or correction factors are applied where the installation conditions differ from those for which values of current carrying capacity are defined. The following de-rating factors will be applied depending on the type of installation.

    Installation Trenches and Duct Banks (Below ground)

    o Thermal resistivity of soil : Fs o Depth of laying : Fd o Ground temperature : Ft o Grouping factor : Fg

    Above ground installation (In Air Indoor / Outdoor)

    o Ambient air temperature : Ft o Grouping factor : Fg

    The current carrying capacity required under given conditions can be calculated as follows:

    Where: Icable_amp Cable ampacity (current rating of the cable for the conditions defined in the

    manufacturers catalogue, see Clause 5.2 below) IN Load Current FG Global de-rating factor (FG= Fg Ft Fd Fs) Fg De-rating grouping factor (e.g. 5 cables spaced 0.150m direct buried) Ft De-rating temperature factor (e.g. soil temperature 40C instead of 15C) Fd De-rating factor for depths of laying of cables Fs De-rating factor for thermal resistivity of soil FD Design factor

    4.3. SHORT CIRCUIT

    The minimum conductor sizes suitable to withstand the applicable short circuit conditions are calculated based on the maximum permissible conductor temperature of 250C as follows (valid where t 5sec).

    2

    ln

    1mm

    tIK

    S

    i

    f

    +

    +

    G

    DNampcable F

    FII _

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 7 of 45

    Where: S Minimum cross-section area of the cable (mm2) I Short circuit current t Short circuit time rating (seconds) i Max. permissible continuous conductor temperature C, (XLPE insulation: 90C) f Max. allowable conductor temp. at end of short circuit (XLPE insulation:250 C) It is the reciprocal of the resistance variation of the conductor at 0 C. (Copper =234.5) K Constant. Depends on material of the conductor (Copper K =143.08)

    5. CABLE SIZING REQUIREMENTS

    5.1. VOLTAGE DROP

    As per BS 7671: 4%

    As per QGEWC: 2.5% (From utility LV Connection Point)

    The maximum permissible voltage drop for three phase 415V system shall be 4%.

    The Voltage drop is measured from the LV terminal of the Transformer to the final load in a LV Circuit.

    5.2. AMPACITY

    Cable size will be selected in order to comply with ampacity criterion. The allowable cable ampacities for this project are determined following the application of the appropriate correction/de-rating factors which are applied where the installation and environmental conditions differ from those for which the values of current carrying capacity are defined.

    The following factors (de-rating and over-sizing factors) will be used in the calculation depending on the type of installation:

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 8 of 45

    6. De-rating factors for cables.

    Ampacities data were taken from DOHA CABLES Catalogue (Appendix 1). The data is based upon normal conditions which are:

    Ground temperature: 35C Ambient Air temperature: 40C Depth of laying: 0.5m Soil Thermal resistivity: 1.2 Km/W

    In order to update them to the project conditions the following correction factors from DOHA CABLES Catalogue will be used:

    6.1. De-rating factors for cables installed in Ducts in the ground.

    Total de-rating factors will be as follows:

    De-Rating Factors Value Reference DOHA CABLES Catalogue Ground temperature @ 40C : Ft 0.95 Appendix-3 Depth of laying @ 2m Multi Core : Fd

    0.88 Appendix-5 Depth of laying @ 2m Single Core : Fd

    0.85 Appendix-5 Soil thermal resistivity @ 2.0 Km/W Three Core and Single Core Cables : Fs

    0.80 Appendix-6

    Cable grouping factor Multicore Cables : Fg

    0.67 Appendix-8 Cable grouping factor Single Core Cables : Fg (Trefoil formation)

    0.64 Appendix-7

    Global de-rating factors will be as follows:

    De-Rating Factors Multicore cables Single-core cables Ground temperature : Ft 0.95 0.95

    Depth of laying @ 2m : Fd 0.88 0.85 Soil thermal resistivity @ 2.0 : Fs 0.80 0.80

    Grouping factor : Fg 0.67 0.64 Global De-rating : FG 0.45 0.41

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 9 of 45

    6.2. De-rating factors for cables Installed in Air.

    Ampacities data were taken from DOHA CABLES Catalogue (Appendix 1).

    In order to update them to the project conditions the following correction factors from DOHA CABLES Catalogue will be used:

    De-rating factors Value Ref. DOHA CABLES Catalogue

    Ambient temperature @ 50C Installed Outdoor / Non Air-conditioned Area : Ft

    0.89 Appendix 4

    Ambient temperature @ 35C Installed Indoor / Air-conditioned Area : Ft

    1.05 Appendix 4

    Cable grouping factor for Multicore cables : Fg 0.93 Appendix 9 Cable grouping factor for Single core cables : Fg 0.90 Appendix 10 Design Factor 125%

    Note: De-rating grouping factor corresponds to a single layer installation in a ladder type cable tray with a maximum grouping of 3 three-phase circuits for single core cables (up to 6 circuits for multi-core cables) and up to 3 levels of cable trays (300mm spacing between trays). The different circuits for single core cables must be installed spaced at least two (2) external diameters of the single-core cable.

    Global De-rating factors will be as follows:

    De-rating factors for cables Installed in Air (Installed Indoor / Air-conditioned Area).

    Multicore cables Single-core cables Temperature factor : Ft 1.05 1.05

    Grouping factor : Fg 0.93 0.90 Global De-rating : FG 0.97 0.94

    De-rating factors for cables Installed in Air (Installed Outdoor / Non Air-conditioned Area).

    Multicore cables Single-core cables Temperature factor : Ft 0.89 0.89

    Grouping factor : Fg 0.93 0.90 Global De-rating : FG 0.82 0.80

    The design factor of 25% will be employed to oversize incoming cables to LV switchgears to allow 25% spare capacity for the future loads on all the incoming cables.

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 10 of 45

    6.3. THERMAL SHORT CIRCUIT CAPACITY

    For incomer cables to all the switchgears the short circuit rating of the switchgear shall be used for the value of short circuit current. The value for t has been taken as 1 sec for incomer circuit breakers.

    According to the equation under paragraph 4.3 and taking into account the above clearance times, the minimum conductor sizes shall be calculated.

    The minimum calculated Short Circuit Ratings of conductor from DOHA CABLES manufacturer are provided in the Appendix-11:

    For switchgear outgoings (feeders and motor starters) the current limiting characteristic of the circuit breaker has been taken into account in order to size the minimum cable sizes. For that purpose, let-through energy curves of circuit breakers to be installed in the switchgear have been analysed.

    The following formulae will be used:

    22

    2mmk

    tIS

    Where:

    I2t = Specific circuit breaker let-through energy k = Constant (k = 143.08 for copper cables and XLPE insulation)

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 11 of 45

    Circuit breakers 63A (ABB Tmax T2 160A)

    Irms = 80Ka I2t = 0.22 106 S > 3.28 mm2, which means minimum cable size 4mm2.

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 12 of 45

    Circuit breakers 160A (ABB Tmax T2 160A)

    Irms = 80Ka I2t = 0.39 106 S > 4.36 mm2, which means minimum cable size 6mm2.

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 13 of 45

    Circuit breakers > 160A & 800A (ABB T6 800A)

    Irms = 80Ka I2t = 19 106 S > 30.46 mm2, which means minimum cable size 35mm2.

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 14 of 45

    7. APPENDICES

    Appendix 1. Current ratings for single and multi-core cables (DOHA CABLES Catalogue). Appendix 2. AC resistance (R) and reactance (X) for Single and multi-core Cables,

    reference from DOHA CABLES catalogue.

    Appendix 3. Rating Factors for Ground Temperature, Reference from DOHA CABLES Catalogue.

    Appendix 4. Rating Factors for Air Temperature, Reference from DOHA CABLES Catalogue.

    Appendix 5.

    Rating Factors for Depth of Laying, Reference from DOHA CABLES Catalogue.

    Appendix 6.

    Rating Factors for Variation in Thermal Resistivity of Soil (average values), Reference from DOHA CABLES Catalogue.

    Appendix 7. Rating Factors for Trefoil Formation for Three Single Core Cables Laid Direct in Ground, Reference from DOHA CABLES Catalogue.

    Appendix 8. Rating Factors for Trefoil Formation for Multi-Core Cables Laid Direct in Ground. Reference from DOHA CABLES Catalogue.

    Appendix 9. Rating Factors for groups of more than one multi-core cable in air To be applied to the current-carrying capacity for one multi-core cable in free air. Reference from DOHA CABLES Catalogue.

    Appendix 10 Rating Factors for groups of more than one circuit of single-core cables To be applied to the current-carrying capacity for one circuit of single-core cables in free air. Reference from DOHA CABLES Catalogue.

    Appendix 11 Short Circuit Ratings of Conductors for 1 Sec in kA. Reference from DOHA CABLES Catalogue.

    Appendix 12 Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables Laid in Air (Indoor) on cable trays (Power Distribution Feeders - From LV Switch Board to Distribution Panels).

    Appendix 13 Cable selection chart for 415V-3 Phase, Multi Core Cu/XLPE/PVC cables Laid in Air (Indoor) on cable trays (From LV Switch Board to Final Loads.).

    Appendix 14 Cable selection chart for 415V-3 Phase, Multi Core Cu/XLPE/SWA/PVC cables Laid in Air (Indoor/Outdoor) on cable trays (Power Distribution Feeders - From LV Switch Board to Distribution Panels).

    Appendix 15 Cable selection chart for 415V-3 Phase, Multi Core Cu/XLPE/SWA/PVC cables Laid in Air (Indoor/Outdoor) on cable (From LV Switch Board to Final Loads).

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 15 of 45

    Appendix 16 Cable selection chart for 415V-3 Phase, Multi Core Cu/XLPE/SWA/PVC cables Laid in Ducts (Outdoor), (Power Distribution Feeders - From LV Switch Board to Distribution Panels).

    Appendix 17 Cable selection chart for 415V-3 Phase, Multi Core Cu/XLPE/SWA/PVC cables Laid in Ducts (Outdoor), (From LV Switch Board to Final Loads).

    Appendix 18 Cable selection chart for 230V-1 Phase, Multi Core Cu/XLPE/PVC cables Laid in Air (Indoor) on cable trays (From LV Switch Board to Final Loads).

    Appendix 19 Cable selection chart for 230V-1 Phase, Multi Core Cu/XLPE/SWA/PVC cables Laid in Air (Indoor/Outdoor) on cable trays (From LV Switch Board to Final Loads).

    Appendix 20 Cable selection chart for 230V-1 Phase, Multi Core Cu/XLPE/SWA/PVC cables Laid in Ducts (Indoor/Outdoor) on cable trays (From LV Switch Board to Final Loads).

    Appendix 21 Cable selection chart for 415V-3 Phase, Single Core Cu/XLPE/SWA/PVC cables Laid in Air (Indoor/Outdoor) on cable trays (Power Distribution Feeders - From LV Switch Board to Distribution Panels).

    Appendix 22 Cable selection chart for 415V-3 Phase, Single Core Cu/XLPE/SWA/PVC cables Laid in Ducts (Outdoor), (Power Distribution Feeders - From LV Switch Board to Distribution Panels).

    Appendix 23 Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables Laid in Air (Indoor) on cable trays (For 3 Phase LV Motor Feeders At Run - From LV Switch Board to LV Motors).

    Appendix 24 Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables Laid in Air (Indoor) on cable trays (For 3 Phase LV Motor Feeders At Starting - From LV Switch Board to LV Motors).

    Appendix 25 Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables Laid in Air (Indoor) on cable trays (For 3 Phase LV Motor Feeders Selection Sheet - From LV Switch Board to LV Motors).

    Appendix 26 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables Laid in Air (Indoor/Outdoor) on cable trays (For 3 Phase LV Motor Feeders At Run - From LV Switch Board to LV Motors).

    Appendix 27 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables Laid in Air (Indoor/Outdoor) on cable trays (For 3 Phase LV Motor Feeders At Starting - From LV Switch Board to LV Motors).

    Appendix 28 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables Laid in Air (Indoor/Outdoor) on cable trays (For 3 Phase LV Motor Feeders Selection Sheet - From LV Switch Board to LV Motors).

    Appendix 29 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables Laid in Ducts (For 3 Phase LV Motor Feeders At Run - From LV Switch Board to LV Motors).

  • NEW PORT PROJECT

    TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 16 of 45

    Appendix 30 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables Laid in Ducts (For 3 Phase LV Motor Feeders At Starting - From LV Switch Board to LV Motors).

    Appendix 31 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables Laid in Ducts (For 3 Phase LV Motor Feeders Selection Sheet - From LV Switch Board to LV Motors).

  • TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 17 of 44

    Appendix 1 & 2. Current ratings and AC resistance (R) & reactance (X) for Single and multi-core Cables, reference from DOHA CABLES catalogue.

    Note: The Current Carrying Capacities, Cable Resistances & Reactances and Cable overall diameter is typical for the LSHF cables (Low Smoke Halogen Free).

  • TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 18 of 44

    Note: The Current Carrying Capacities, Cable Resistances & Reactances and Cable overall diameter is typical for the LSHF cables (Low Smoke Halogen Free).

  • TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 19 of 44

    Appendix 3. Rating Factors for Ground Temperature, Reference from DOHA CABLES Catalogue.

    Appendix 4. Rating Factors for Air Temperature, Reference from DOHA CABLES Catalogue.

    Appendix 5. Rating Factors for Depth of Laying, Reference from DOHA CABLES Catalogue.

  • TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 20 of 44

    Appendix 6. Rating Factors for Variation in Thermal Resistivity of Soil (average values). Reference from DOHA CABLES Catalogue.

    Appendix 7. Rating Factors for Trefoil Formation for Three Single Core Cables Laid Direct in Ground. Reference from DOHA CABLES Catalogue.

  • TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 21 of 44

    Appendix 8. Rating Factors for Trefoil Formation for Multi-Core Cables Laid Direct in Ground. Reference from DOHA CABLES Catalogue.

  • TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 22 of 44

    Appendix 9. Rating Factors for groups of more than one multi-core cable in air To be applied to the current-carrying capacity for one multi-core cable in free air. Reference from DOHA CABLES Catalogue.

  • TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 23 of 44

    Appendix 10. Rating Factors for groups of more than one circuit of single-core cables To be applied to the current-carrying capacity for one circuit of single-core cables in free air. Reference from DOHA CABLES Catalogue.

  • TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L

    (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS

    DOC No.: DPCT-TCC-CAL-EL-00066 Page 24 of 44

    Appendix 11. Short Circuit Ratings of Conductors for 1 Sec in kA. Reference from DOHA CABLES Catalogue.

  • APPENDIX : 12

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 25 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01415 V 3-PH POWER FEEDER

    0.6/1 kV, CU/XLPE/PVC (FOUR CORES CABLE - UNARMOURED)50 Hz

    10.97

    4 X 4 4 X 6 4 X 10 - - - - - - - - - - - - - -36 44 60 - - - - - - - - - - - - - -

    34.92 42.68 58.2 - - - - - - - - - - - - - -5.8800 3.9300 2.3300 - - - - - - - - - - - - - -0.0933 0.0888 0.0856 - - - - - - - - - - - - - -

    LOAD RATING

    kW

    INLOAD F.L.C

    AMPS**

    COS SIN

    0.25 0.41 0.85 0.53 1160.19 1728.72 2890.83 - - - - - - - - - - - - - - - -0.37 0.61 0.85 0.53 783.91 1168.05 1953.27 - - - - - - - - - - - - - - - -0.55 0.90 0.85 0.53 527.36 785.78 1314.02 - - - - - - - - - - - - - - - -0.75 1.23 0.85 0.53 386.73 576.24 963.61 - - - - - - - - - - - - - - - -1.50 2.46 0.85 0.53 193.36 288.12 481.81 - - - - - - - - - - - - - - - -2.50 4.09 0.85 0.53 116.02 172.87 289.08 - - - - - - - - - - - - - - - -3.00 4.91 0.85 0.53 96.68 144.06 240.90 - - - - - - - - - - - - - - - -4.00 6.55 0.85 0.53 72.51 108.04 180.68 - - - - - - - - - - - - - - - -5.50 9.00 0.85 0.53 52.74 78.58 131.40 - - - - - - - - - - - - - - - -7.50 12.28 0.85 0.53 38.67 57.62 96.36 - - - - - - - - - - - - - - - -11.00 18.00 0.85 0.53 26.37 39.29 65.70 - - - - - - - - - - - - - - - -15.00 24.55 0.85 0.53 19.34 28.81 48.18 - - - - - - - - - - - - - - - -18.50 30.28 0.85 0.53 15.68 23.36 39.07 - - - - - - - - - - - - - - - -22.00 36.01 0.85 0.53 - 19.64 32.85 - - - - - - - - - - - - - - - -25.00 40.92 0.85 0.53 - 17.29 28.91 - - - - - - - - - - - - - - - -30.00 49.10 0.85 0.53 - - 24.09 - - - - - - - - - - - - - - - -37.00 60.56 0.85 0.53 - - - - - - - - - - - - - - - - - - -45.00 73.65 0.85 0.53 - - - - - - - - - - - - - - - - - - -55.00 90.02 0.85 0.53 - - - - - - - - - - - - - - - - - - -61.00 99.84 0.85 0.53 - - - - - - - - - - - - - - - - - - -75.00 122.75 0.85 0.53 - - - - - - - - - - - - - - - - - - -110.00 180.04 0.85 0.53 - - - - - - - - - - - - - - - - - - -132.00 216.05 0.85 0.53 - - - - - - - - - - - - - - - - - - -150.00 245.51 0.85 0.53 - - - - - - - - - - - - - - - - - - -160.00 261.87 0.85 0.53 - - - - - - - - - - - - - - - - - - -185.00 302.79 0.85 0.53 - - - - - - - - - - - - - - - - - - -200.00 327.34 0.85 0.53 - - - - - - - - - - - - - - - - - - -220.00 360.08 0.85 0.53 - - - - - - - - - - - - - - - - - - -250.00 409.18 0.85 0.53 - - - - - - - - - - - - - - - - - - -280.00 458.28 0.85 0.53 - - - - - - - - - - - - - - - - - - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 x n (SQRT 3 x P.F xVOLT) SQRT(3) x IN x (Rcos + Xsin)

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR

    DERATING FACTOR =

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPSSITE CABLE RATING *CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X)

    CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: FREQUENCYMAXIMUM PERMISSIBLE VOLT DROP = % AT F.L.C

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV POWER FEEDERLAID IN AIR - ON CABLE LADDER (INDOOR)

    Power Distribution Feeders - From LV Switch Board to Distribution Panels

  • APPENDIX : 13

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 26 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01415 V 3-PH POWER FEEDER

    0.6/1 kV, CU/XLPE/PVC (FOUR CORES CABLE - UNARMOURED)50 Hz

    2.50.97

    4 X 4 4 X 6 4 X 10 - - - - - - - - - - - - - -36 44 60 - - - - - - - - - - - - - -

    34.92 42.68 58.2 - - - - - - - - - - - - - -5.8800 3.9300 2.3300 - - - - - - - - - - - - - -0.0933 0.0888 0.0856 - - - - - - - - - - - - - -

    LOAD RATING

    kW

    INLOAD F.L.C

    AMPS**

    COS SIN

    0.25 0.41 0.85 0.53 2900.47 4321.80 7227.08 - - - - - - - - - - - - - - - -0.37 0.61 0.85 0.53 1959.78 2920.13 4883.16 - - - - - - - - - - - - - - - -0.55 0.90 0.85 0.53 1318.40 1964.45 3285.04 - - - - - - - - - - - - - - - -0.75 1.23 0.85 0.53 966.82 1440.60 2409.03 - - - - - - - - - - - - - - - -1.50 2.46 0.85 0.53 483.41 720.30 1204.51 - - - - - - - - - - - - - - - -2.50 4.09 0.85 0.53 290.05 432.18 722.71 - - - - - - - - - - - - - - - -3.00 4.91 0.85 0.53 241.71 360.15 602.26 - - - - - - - - - - - - - - - -4.00 6.55 0.85 0.53 181.28 270.11 451.69 - - - - - - - - - - - - - - - -5.50 9.00 0.85 0.53 131.84 196.45 328.50 - - - - - - - - - - - - - - - -7.50 12.28 0.85 0.53 96.68 144.06 240.90 - - - - - - - - - - - - - - - -11.00 18.00 0.85 0.53 65.92 98.22 164.25 - - - - - - - - - - - - - - - -15.00 24.55 0.85 0.53 48.34 72.03 120.45 - - - - - - - - - - - - - - - -18.50 30.28 0.85 0.53 39.20 58.40 97.66 - - - - - - - - - - - - - - - -22.00 36.01 0.85 0.53 - 49.11 82.13 - - - - - - - - - - - - - - - -25.00 40.92 0.85 0.53 - 43.22 72.27 - - - - - - - - - - - - - - - -30.00 49.10 0.85 0.53 - - 60.23 - - - - - - - - - - - - - - - -37.00 60.56 0.85 0.53 - - - - - - - - - - - - - - - - - - -45.00 73.65 0.85 0.53 - - - - - - - - - - - - - - - - - - -55.00 90.02 0.85 0.53 - - - - - - - - - - - - - - - - - - -61.00 99.84 0.85 0.53 - - - - - - - - - - - - - - - - - - -75.00 122.75 0.85 0.53 - - - - - - - - - - - - - - - - - - -110.00 180.04 0.85 0.53 - - - - - - - - - - - - - - - - - - -132.00 216.05 0.85 0.53 - - - - - - - - - - - - - - - - - - -150.00 245.51 0.85 0.53 - - - - - - - - - - - - - - - - - - -160.00 261.87 0.85 0.53 - - - - - - - - - - - - - - - - - - -185.00 302.79 0.85 0.53 - - - - - - - - - - - - - - - - - - -200.00 327.34 0.85 0.53 - - - - - - - - - - - - - - - - - - -220.00 360.08 0.85 0.53 - - - - - - - - - - - - - - - - - - -250.00 409.18 0.85 0.53 - - - - - - - - - - - - - - - - - - -280.00 458.28 0.85 0.53 - - - - - - - - - - - - - - - - - - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 x n (SQRT 3 x P.F xVOLT) SQRT(3) x IN x (Rcos + Xsin)

    % AT F.L.C

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV POWER FEEDERLAID IN AIR - ON CABLE LADDER (INDOOR)

    From LV Switch Board to Final Loads.

    DERATING FACTOR =

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPSSITE CABLE RATING *CONDUCTOR RESIST. IN OHM/KM (90o C)

    CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: FREQUENCYMAXIMUM PERMISSIBLE VOLT DROP =

    CABLE REACTANCE in OHM/KM (X)

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR

  • APPENDIX : 14

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 27 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01415 V 3-PH POWER FEEDER

    0.6/1 kV, CU/XLPE/PVC (FOUR CORES CABLE - ARMOURED)50 Hz

    10.82

    4 X 4 4 X 6 4 X 10 4 X 16 4 X 25 4 X 35 4 X 50 4 X 70 4 X 95 4 X 120 4 X 150 4 X 185 4 X 240 2X(4 X 120) 2X(4 X 150) 2X(4 X 185) 2X(4 X 240)37 45 61 80 109 131 164 196 243 280 334 365 434 560 668 730 868

    30.34 36.9 50.02 65.6 89.38 107.4 134.48 160.7 199.26 229.6 273.9 299.3 355.9 459.2 547.76 598.6 711.765.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.4940 0.3425 0.2471 0.1964 0.1597 0.1284 0.0988 0.0982 0.0799 0.0642 0.04940.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 0.0740 0.0720 0.0710 0.0710 0.0710 0.0710 0.0355 0.0355 0.0355 0.0355

    LOAD RATING kW

    INLOAD F.L.C

    AMPS**COS SIN

    0.25 0.41 0.85 0.53 1160.52 1729.85 2886.47 4539.39 7044.45 9593.14 12746.06 17738.65 23614.98 28656.19 33819.04 39958.97 48241.67 57312.37 67638.07 79917.94 96483.35 - -0.37 0.61 0.85 0.53 784.14 1168.82 1950.32 3067.16 4759.76 6481.85 8612.20 11985.57 15956.07 19362.29 22850.70 26999.30 32595.72 38724.58 45701.40 53998.61 65191.45 - -0.55 0.90 0.85 0.53 527.51 786.29 1312.03 2063.36 3202.02 4360.52 5793.66 8063.02 10734.08 13025.54 15372.29 18163.17 21928.03 26051.08 30744.58 36326.33 43856.07 - -0.75 1.23 0.85 0.53 386.84 576.62 962.16 1513.13 2348.15 3197.71 4248.69 5912.88 7871.66 9552.06 11273.01 13319.66 16080.56 19104.12 22546.02 26639.31 32161.12 - -1.50 2.46 0.85 0.53 193.42 288.31 481.08 756.56 1174.07 1598.86 2124.34 2956.44 3935.83 4776.03 5636.51 6659.83 8040.28 9552.06 11273.01 13319.66 16080.56 - -2.50 4.09 0.85 0.53 116.05 172.98 288.65 453.94 704.44 959.31 1274.61 1773.86 2361.50 2865.62 3381.90 3995.90 4824.17 5731.24 6763.81 7991.79 9648.33 - -3.00 4.91 0.85 0.53 96.71 144.15 240.54 378.28 587.04 799.43 1062.17 1478.22 1967.92 2388.02 2818.25 3329.91 4020.14 4776.03 5636.51 6659.83 8040.28 - -4.00 6.55 0.85 0.53 72.53 108.12 180.40 283.71 440.28 599.57 796.63 1108.67 1475.94 1791.01 2113.69 2497.44 3015.10 3582.02 4227.38 4994.87 6030.21 - -5.50 9.00 0.85 0.53 52.75 78.63 131.20 206.34 320.20 436.05 579.37 806.30 1073.41 1302.55 1537.23 1816.32 2192.80 2605.11 3074.46 3632.63 4385.61 - -7.50 12.28 0.85 0.53 38.68 57.66 96.22 151.31 234.81 319.77 424.87 591.29 787.17 955.21 1127.30 1331.97 1608.06 1910.41 2254.60 2663.93 3216.11 - -11.00 18.00 0.85 0.53 26.38 39.31 65.60 103.17 160.10 218.03 289.68 403.15 536.70 651.28 768.61 908.16 1096.40 1302.55 1537.23 1816.32 2192.80 - -15.00 24.55 0.85 0.53 19.34 28.83 48.11 75.66 117.41 159.89 212.43 295.64 393.58 477.60 563.65 665.98 804.03 955.21 1127.30 1331.97 1608.06 - -18.50 30.28 0.85 0.53 15.68 23.38 39.01 61.34 95.20 129.64 172.24 239.71 319.12 387.25 457.01 539.99 651.91 774.49 914.03 1079.97 1303.83 - -22.00 36.01 0.85 0.53 - 19.66 32.80 51.58 80.05 109.01 144.84 201.58 268.35 325.64 384.31 454.08 548.20 651.28 768.61 908.16 1096.40 - -25.00 40.92 0.85 0.53 - - 28.86 45.39 70.44 95.93 127.46 177.39 236.15 286.56 338.19 399.59 482.42 573.12 676.38 799.18 964.83 - -30.00 49.10 0.85 0.53 - - 24.05 37.83 58.70 79.94 106.22 147.82 196.79 238.80 281.83 332.99 402.01 477.60 563.65 665.98 804.03 - -37.00 60.56 0.85 0.53 - - - 30.67 47.60 64.82 86.12 119.86 159.56 193.62 228.51 269.99 325.96 387.25 457.01 539.99 651.91 - -45.00 73.65 0.85 0.53 - - - - 39.14 53.30 70.81 98.55 131.19 159.20 187.88 221.99 268.01 318.40 375.77 443.99 536.02 - -55.00 90.02 0.85 0.53 - - - - - 43.61 57.94 80.63 107.34 130.26 153.72 181.63 219.28 260.51 307.45 363.26 438.56 - -61.00 99.84 0.85 0.53 - - - - - 39.32 52.24 72.70 96.78 117.44 138.60 163.77 197.71 234.89 277.21 327.53 395.42 - -75.00 122.75 0.85 0.53 - - - - - - 42.49 59.13 78.72 95.52 112.73 133.20 160.81 191.04 225.46 266.39 321.61 - -110.00 180.04 0.85 0.53 - - - - - - - - 53.67 65.13 76.86 90.82 109.64 130.26 153.72 181.63 219.28 - -132.00 216.05 0.85 0.53 - - - - - - - - - 54.27 64.05 75.68 91.37 108.55 128.10 151.36 182.73 - -150.00 245.51 0.85 0.53 - - - - - - - - - - 56.37 66.60 80.40 95.52 112.73 133.20 160.81 - -160.00 261.87 0.85 0.53 - - - - - - - - - - 52.84 62.44 75.38 89.55 105.68 124.87 150.76 - -185.00 302.79 0.85 0.53 - - - - - - - - - - - - 65.19 77.45 91.40 108.00 130.38 - -200.00 327.34 0.85 0.53 - - - - - - - - - - - - 60.30 71.64 84.55 99.90 120.60 - -220.00 360.08 0.85 0.53 - - - - - - - - - - - - - 65.13 76.86 90.82 109.64 - -250.00 409.18 0.85 0.53 - - - - - - - - - - - - - 57.31 67.64 79.92 96.48 - -280.00 458.28 0.85 0.53 - - - - - - - - - - - - - 51.17 60.39 71.36 86.15 - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 x n

    (SQRT 3 x P.F xVOLT) SQRT(3) x IN x (Rcos + Xsin)

    % AT F.L.CDERATING FACTOR =

    CABLE REACTANCE in OHM/KM (X)

    SITE CABLE RATING *

    * SITE CABLE RATING = CCC x DERATING FACTOR

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV POWER FEEDERLAID IN AIR - ON CABLE LADDER (INDOOR / OUTDOOR)

    Power Distribution Feeders - From LV Switch Board to Distribution PanelsCABLE SELECTION CHART FOR

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    CURRENT CARRYING CAPACITY (CCC) in AMPSCABLE C.S.A in mm2

    CONDUCTOR RESIST. IN OHM/KM (90o C)

    MAXIMUM PERMISSIBLE VOLT DROP =

    CABLE SPECIFICATION: FREQUENCY

  • APPENDIX : 15

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 28 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01415 V 3-PH POWER FEEDER

    0.6/1 kV, CU/XLPE/PVC (FOUR CORES CABLE - ARMOURED)50 Hz

    2.50.82

    4 X 4 4 X 6 4 X 10 4 X 16 4 X 25 4 X 35 4 X 50 4 X 70 4 X 95 4 X 120 4 X 150 4 X 185 4 X 240 2X(4 X 120) 2X(4 X 150) 2X(4 X 185) 2X(4 X 240)37 45 61 80 109 131 164 196 243 280 334 365 434 560 668 730 868

    30.34 36.9 50.02 65.6 89.38 107.4 134.48 160.7 199.26 229.6 273.9 299.3 355.9 459.2 547.76 598.6 711.765.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.4940 0.3425 0.2471 0.1964 0.1597 0.1284 0.0988 0.098 0.080 0.064 0.0490.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 0.0740 0.0720 0.0710 0.0710 0.0710 0.0710 0.0355 0.0355 0.0355 0.0355

    LOAD RATING kW

    INLOAD F.L.C

    AMPS**COS SIN

    0.25 0.41 0.85 0.53 2901.30 4324.62 7216.18 11348.47 17611.12 23982.84 31865.15 44346.62 59037.45 71640.46 84547.59 99897.42 120604.18 143280.93 169095.18 199794.84 241208.36 - -0.37 0.61 0.85 0.53 1960.34 2922.04 4875.80 7667.89 11899.41 16204.62 21530.50 29963.93 39890.17 48405.72 57126.75 67498.26 81489.31 96811.44 114253.50 134996.51 162978.62 - -0.55 0.90 0.85 0.53 1318.77 1965.74 3280.08 5158.40 8005.06 10901.29 14484.16 20157.55 26835.21 32563.85 38430.72 45407.92 54820.08 65127.69 76861.44 90815.84 109640.17 - -0.75 1.23 0.85 0.53 967.10 1441.54 2405.39 3782.82 5870.37 7994.28 10621.72 14782.21 19679.15 23880.15 28182.53 33299.14 40201.39 47760.31 56365.06 66598.28 80402.79 - -1.50 2.46 0.85 0.53 483.55 720.77 1202.70 1891.41 2935.19 3997.14 5310.86 7391.10 9839.58 11940.08 14091.26 16649.57 20100.70 23880.15 28182.53 33299.14 40201.39 - -2.50 4.09 0.85 0.53 290.13 432.46 721.62 1134.85 1761.11 2398.28 3186.51 4434.66 5903.75 7164.05 8454.76 9989.74 12060.42 14328.09 16909.52 19979.48 24120.84 - -3.00 4.91 0.85 0.53 241.78 360.38 601.35 945.71 1467.59 1998.57 2655.43 3695.55 4919.79 5970.04 7045.63 8324.79 10050.35 11940.08 14091.26 16649.57 20100.70 - -4.00 6.55 0.85 0.53 181.33 270.29 451.01 709.28 1100.70 1498.93 1991.57 2771.66 3689.84 4477.53 5284.22 6243.59 7537.76 8955.06 10568.45 12487.18 15075.52 - -5.50 9.00 0.85 0.53 131.88 196.57 328.01 515.84 800.51 1090.13 1448.42 2015.76 2683.52 3256.38 3843.07 4540.79 5482.01 6512.77 7686.14 9081.58 10964.02 - -7.50 12.28 0.85 0.53 96.71 144.15 240.54 378.28 587.04 799.43 1062.17 1478.22 1967.92 2388.02 2818.25 3329.91 4020.14 4776.03 5636.51 6659.83 8040.28 - -11.00 18.00 0.85 0.53 65.94 98.29 164.00 257.92 400.25 545.06 724.21 1007.88 1341.76 1628.19 1921.54 2270.40 2741.00 3256.38 3843.07 4540.79 5482.01 - -15.00 24.55 0.85 0.53 48.36 72.08 120.27 189.14 293.52 399.71 531.09 739.11 983.96 1194.01 1409.13 1664.96 2010.07 2388.02 2818.25 3329.91 4020.14 - -18.50 30.28 0.85 0.53 39.21 58.44 97.52 153.36 237.99 324.09 430.61 599.28 797.80 968.11 1142.53 1349.97 1629.79 1936.23 2285.07 2699.93 3259.57 - -22.00 36.01 0.85 0.53 - 49.14 82.00 128.96 200.13 272.53 362.10 503.94 670.88 814.10 960.77 1135.20 1370.50 1628.19 1921.54 2270.40 2741.00 - -25.00 40.92 0.85 0.53 - - 72.16 113.48 176.11 239.83 318.65 443.47 590.37 716.40 845.48 998.97 1206.04 1432.81 1690.95 1997.95 2412.08 - -30.00 49.10 0.85 0.53 - - 60.13 94.57 146.76 199.86 265.54 369.56 491.98 597.00 704.56 832.48 1005.03 1194.01 1409.13 1664.96 2010.07 - -37.00 60.56 0.85 0.53 - - - 76.68 118.99 162.05 215.31 299.64 398.90 484.06 571.27 674.98 814.89 968.11 1142.53 1349.97 1629.79 - -45.00 73.65 0.85 0.53 - - - - 97.84 133.24 177.03 246.37 327.99 398.00 469.71 554.99 670.02 796.01 939.42 1109.97 1340.05 - -55.00 90.02 0.85 0.53 - - - - - 109.01 144.84 201.58 268.35 325.64 384.31 454.08 548.20 651.28 768.61 908.16 1096.40 - -61.00 99.84 0.85 0.53 - - - - - 98.29 130.59 181.75 241.96 293.61 346.51 409.42 494.28 587.22 693.01 818.83 988.56 - -75.00 122.75 0.85 0.53 - - - - - - 106.22 147.82 196.79 238.80 281.83 332.99 402.01 477.60 563.65 665.98 804.03 - -110.00 180.04 0.85 0.53 - - - - - - - - 134.18 162.82 192.15 227.04 274.10 325.64 384.31 454.08 548.20 - -132.00 216.05 0.85 0.53 - - - - - - - - - 135.68 160.13 189.20 228.42 271.37 320.26 378.40 456.83 - -150.00 245.51 0.85 0.53 - - - - - - - - - - 140.91 166.50 201.01 238.80 281.83 332.99 402.01 - -160.00 261.87 0.85 0.53 - - - - - - - - - - 132.11 156.09 188.44 223.88 264.21 312.18 376.89 - -185.00 302.79 0.85 0.53 - - - - - - - - - - - - 162.98 193.62 228.51 269.99 325.96 - -200.00 327.34 0.85 0.53 - - - - - - - - - - - - 150.76 179.10 211.37 249.74 301.51 - -220.00 360.08 0.85 0.53 - - - - - - - - - - - - - 162.82 192.15 227.04 274.10 - -250.00 409.18 0.85 0.53 - - - - - - - - - - - - - 143.28 169.10 199.79 241.21 - -280.00 458.28 0.85 0.53 - - - - - - - - - - - - - 127.93 150.98 178.39 215.36 - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 x n

    (SQRT 3 x P.F xVOLT) SQRT(3) x IN x (Rcos + Xsin)

    % AT F.L.C

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV POWER FEEDERLAID IN AIR - ON CABLE LADDER (INDOOR / OUTDOOR)

    From LV Switch Board to Final Loads.

    DERATING FACTOR =

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPSSITE CABLE RATING *CONDUCTOR RESIST. IN OHM/KM (90o C)

    CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: FREQUENCYMAXIMUM PERMISSIBLE VOLT DROP =

    CABLE REACTANCE in OHM/KM (X)

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR

  • APPENDIX : 16

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 29 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01415 V 3-PH POWER FEEDER (LAID IN DUCTS) - OUTDOOR

    0.6/1 kV, CU/XLPE/SWA/PVC (FOUR CORES CABLE - ARMOURED)50 Hz

    10.45

    4 X 4 4 X 6 4 X 10 4 X 16 4 X 25 4 X 35 4 X 50 4 X 70 4 X 95 4 X 120 4 X 150 4 X 185 4 X 240 2X(4 X 120) 2X(4 X 150) 2X(4 X 185) 2X(4 X 240)35 44 58 72 98 116 138 171 200 233 261 295 347 466 522 590 694

    15.75 19.8 26.1 32.4 44.1 52.2 62.1 77.0 90 104.9 117.5 132.8 156.2 209.7 234.9 265.5 312.35.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.4940 0.3425 0.2471 0.1964 0.1597 0.1284 0.0988 0.098 0.080 0.064 0.0490.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 0.0740 0.0720 0.0710 0.0710 0.0710 0.0710 0.0355 0.0355 0.0355 0.0355

    LOAD RATING

    kW

    INLOAD F.L.C

    AMPS**

    COS SIN

    0.25 0.41 0.85 0.53 1160.52 1729.85 2886.47 4539.39 7044.45 9593.14 12746.06 17738.65 23614.98 28656.19 33819.04 39958.97 48241.67 57312.37 67638.07 79917.94 96483.35 - -0.37 0.61 0.85 0.53 784.14 1168.82 1950.32 3067.16 4759.76 6481.85 8612.20 11985.57 15956.07 19362.29 22850.70 26999.30 32595.72 38724.58 45701.40 53998.61 65191.45 - -0.55 0.90 0.85 0.53 527.51 786.29 1312.03 2063.36 3202.02 4360.52 5793.66 8063.02 10734.08 13025.54 15372.29 18163.17 21928.03 26051.08 30744.58 36326.33 43856.07 - -0.75 1.23 0.85 0.53 386.84 576.62 962.16 1513.13 2348.15 3197.71 4248.69 5912.88 7871.66 9552.06 11273.01 13319.66 16080.56 19104.12 22546.02 26639.31 32161.12 - -1.50 2.46 0.85 0.53 193.42 288.31 481.08 756.56 1174.07 1598.86 2124.34 2956.44 3935.83 4776.03 5636.51 6659.83 8040.28 9552.06 11273.01 13319.66 16080.56 - -2.50 4.09 0.85 0.53 116.05 172.98 288.65 453.94 704.44 959.31 1274.61 1773.86 2361.50 2865.62 3381.90 3995.90 4824.17 5731.24 6763.81 7991.79 9648.33 - -3.00 4.91 0.85 0.53 96.71 144.15 240.54 378.28 587.04 799.43 1062.17 1478.22 1967.92 2388.02 2818.25 3329.91 4020.14 4776.03 5636.51 6659.83 8040.28 - -4.00 6.55 0.85 0.53 72.53 108.12 180.40 283.71 440.28 599.57 796.63 1108.67 1475.94 1791.01 2113.69 2497.44 3015.10 3582.02 4227.38 4994.87 6030.21 - -5.50 9.00 0.85 0.53 52.75 78.63 131.20 206.34 320.20 436.05 579.37 806.30 1073.41 1302.55 1537.23 1816.32 2192.80 2605.11 3074.46 3632.63 4385.61 - -7.50 12.28 0.85 0.53 38.68 57.66 96.22 151.31 234.81 319.77 424.87 591.29 787.17 955.21 1127.30 1331.97 1608.06 1910.41 2254.60 2663.93 3216.11 - -11.00 18.00 0.85 0.53 - 39.31 65.60 103.17 160.10 218.03 289.68 403.15 536.70 651.28 768.61 908.16 1096.40 1302.55 1537.23 1816.32 2192.80 - -15.00 24.55 0.85 0.53 - - 48.11 75.66 117.41 159.89 212.43 295.64 393.58 477.60 563.65 665.98 804.03 955.21 1127.30 1331.97 1608.06 - -18.50 30.28 0.85 0.53 - - - 61.34 95.20 129.64 172.24 239.71 319.12 387.25 457.01 539.99 651.91 774.49 914.03 1079.97 1303.83 - -22.00 36.01 0.85 0.53 - - - - 80.05 109.01 144.84 201.58 268.35 325.64 384.31 454.08 548.20 651.28 768.61 908.16 1096.40 - -25.00 40.92 0.85 0.53 - - - - 70.44 95.93 127.46 177.39 236.15 286.56 338.19 399.59 482.42 573.12 676.38 799.18 964.83 - -30.00 49.10 0.85 0.53 - - - - - 79.94 106.22 147.82 196.79 238.80 281.83 332.99 402.01 477.60 563.65 665.98 804.03 - -37.00 60.56 0.85 0.53 - - - - - - 86.12 119.86 159.56 193.62 228.51 269.99 325.96 387.25 457.01 539.99 651.91 - -45.00 73.65 0.85 0.53 - - - - - - - 98.55 131.19 159.20 187.88 221.99 268.01 318.40 375.77 443.99 536.02 - -55.00 90.02 0.85 0.53 - - - - - - - - - 130.26 153.72 181.63 219.28 260.51 307.45 363.26 438.56 - -61.00 99.84 0.85 0.53 - - - - - - - - - 117.44 138.60 163.77 197.71 234.89 277.21 327.53 395.42 - -75.00 122.75 0.85 0.53 - - - - - - - - - - - 133.20 160.81 191.04 225.46 266.39 321.61 - -

    110.00 180.04 0.85 0.53 - - - - - - - - - - - - - 130.26 153.72 181.63 219.28 - -132.00 216.05 0.85 0.53 - - - - - - - - - - - - - - 128.10 151.36 182.73 - -150.00 245.51 0.85 0.53 - - - - - - - - - - - - - - - 133.20 160.81 - -160.00 261.87 0.85 0.53 - - - - - - - - - - - - - - - 124.87 150.76 - -185.00 302.79 0.85 0.53 - - - - - - - - - - - - - - - - 130.38 - -200.00 327.34 0.85 0.53 - - - - - - - - - - - - - - - - - - -220.00 360.08 0.85 0.53 - - - - - - - - - - - - - - - - - - -250.00 409.18 0.85 0.53 - - - - - - - - - - - - - - - - - - -280.00 458.28 0.85 0.53 - - - - - - - - - - - - - - - - - - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 x n

    (SQRT 3 x P.F xVOLT) SQRT(3) x IN x (Rcos + Xsin)

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR

    DERATING FACTOR =

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPSSITE CABLE RATING *CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X)

    CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: FREQUENCYMAXIMUM PERMISSIBLE VOLT DROP = % AT F.L.C

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV POWER FEEDERLAID IN DUCTS (INDOOR / OUTDOOR)

    Power Distribution Feeders - From LV Switch Board to Distribution Panels

  • APPENDIX : 17

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 30 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01415 V 3-PH POWER FEEDER

    0.6/1 kV, CU/XLPE/SWA/PVC (FOUR CORES CABLE - ARMOURED)50 Hz

    2.50.45

    4 X 4 4 X 6 4 X 10 4 X 16 4 X 25 4 X 35 4 X 50 4 X 70 4 X 95 4 X 120 4 X 150 4 X 185 4 X 240 2X(4 X 120) 2X(4 X 150) 2X(4 X 185) 2X(4 X 240)35 44 58 72 98 116 138 171 200 233 261 295 347 466 522 590 694

    15.75 19.8 26.1 32.4 44.1 52.2 62.1 77.0 90 104.9 117.5 132.8 156.2 209.7 234.9 265.5 312.35.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.4940 0.3425 0.2471 0.1964 0.1597 0.1284 0.0988 0.098 0.080 0.064 0.0490.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 0.0740 0.0720 0.0710 0.0710 0.0710 0.0710 0.0355 0.0355 0.0355 0.0355

    LOAD RATING

    kW

    INLOAD F.L.C

    AMPS**

    COS SIN

    0.25 0.41 0.85 0.53 2901.30 4324.62 7216.18 11348.47 17611.12 23982.84 31865.15 44346.62 59037.45 71640.46 84547.59 99897.42 120604.18 143280.93 169095.18 199794.84 241208.36 - -0.37 0.61 0.85 0.53 1960.34 2922.04 4875.80 7667.89 11899.41 16204.62 21530.50 29963.93 39890.17 48405.72 57126.75 67498.26 81489.31 96811.44 114253.50 134996.51 162978.62 - -0.55 0.90 0.85 0.53 1318.77 1965.74 3280.08 5158.40 8005.06 10901.29 14484.16 20157.55 26835.21 32563.85 38430.72 45407.92 54820.08 65127.69 76861.44 90815.84 109640.17 - -0.75 1.23 0.85 0.53 967.10 1441.54 2405.39 3782.82 5870.37 7994.28 10621.72 14782.21 19679.15 23880.15 28182.53 33299.14 40201.39 47760.31 56365.06 66598.28 80402.79 - -1.50 2.46 0.85 0.53 483.55 720.77 1202.70 1891.41 2935.19 3997.14 5310.86 7391.10 9839.58 11940.08 14091.26 16649.57 20100.70 23880.15 28182.53 33299.14 40201.39 - -2.50 4.09 0.85 0.53 290.13 432.46 721.62 1134.85 1761.11 2398.28 3186.51 4434.66 5903.75 7164.05 8454.76 9989.74 12060.42 14328.09 16909.52 19979.48 24120.84 - -3.00 4.91 0.85 0.53 241.78 360.38 601.35 945.71 1467.59 1998.57 2655.43 3695.55 4919.79 5970.04 7045.63 8324.79 10050.35 11940.08 14091.26 16649.57 20100.70 - -4.00 6.55 0.85 0.53 181.33 270.29 451.01 709.28 1100.70 1498.93 1991.57 2771.66 3689.84 4477.53 5284.22 6243.59 7537.76 8955.06 10568.45 12487.18 15075.52 - -5.50 9.00 0.85 0.53 131.88 196.57 328.01 515.84 800.51 1090.13 1448.42 2015.76 2683.52 3256.38 3843.07 4540.79 5482.01 6512.77 7686.14 9081.58 10964.02 - -7.50 12.28 0.85 0.53 96.71 144.15 240.54 378.28 587.04 799.43 1062.17 1478.22 1967.92 2388.02 2818.25 3329.91 4020.14 4776.03 5636.51 6659.83 8040.28 - -11.00 18.00 0.85 0.53 - 98.29 164.00 257.92 400.25 545.06 724.21 1007.88 1341.76 1628.19 1921.54 2270.40 2741.00 3256.38 3843.07 4540.79 5482.01 - -15.00 24.55 0.85 0.53 - - 120.27 189.14 293.52 399.71 531.09 739.11 983.96 1194.01 1409.13 1664.96 2010.07 2388.02 2818.25 3329.91 4020.14 - -18.50 30.28 0.85 0.53 - - - 153.36 237.99 324.09 430.61 599.28 797.80 968.11 1142.53 1349.97 1629.79 1936.23 2285.07 2699.93 3259.57 - -22.00 36.01 0.85 0.53 - - - - 200.13 272.53 362.10 503.94 670.88 814.10 960.77 1135.20 1370.50 1628.19 1921.54 2270.40 2741.00 - -25.00 40.92 0.85 0.53 - - - - 176.11 239.83 318.65 443.47 590.37 716.40 845.48 998.97 1206.04 1432.81 1690.95 1997.95 2412.08 - -30.00 49.10 0.85 0.53 - - - - - 199.86 265.54 369.56 491.98 597.00 704.56 832.48 1005.03 1194.01 1409.13 1664.96 2010.07 - -37.00 60.56 0.85 0.53 - - - - - - 215.31 299.64 398.90 484.06 571.27 674.98 814.89 968.11 1142.53 1349.97 1629.79 - -45.00 73.65 0.85 0.53 - - - - - - - 246.37 327.99 398.00 469.71 554.99 670.02 796.01 939.42 1109.97 1340.05 - -55.00 90.02 0.85 0.53 - - - - - - - - - 325.64 384.31 454.08 548.20 651.28 768.61 908.16 1096.40 - -61.00 99.84 0.85 0.53 - - - - - - - - - 293.61 346.51 409.42 494.28 587.22 693.01 818.83 988.56 - -75.00 122.75 0.85 0.53 - - - - - - - - - - - 332.99 402.01 477.60 563.65 665.98 804.03 - -110.00 180.04 0.85 0.53 - - - - - - - - - - - - - 325.64 384.31 454.08 548.20 - -132.00 216.05 0.85 0.53 - - - - - - - - - - - - - - 320.26 378.40 456.83 - -150.00 245.51 0.85 0.53 - - - - - - - - - - - - - - - 332.99 402.01 - -160.00 261.87 0.85 0.53 - - - - - - - - - - - - - - - 312.18 376.89 - -185.00 302.79 0.85 0.53 - - - - - - - - - - - - - - - - 325.96 - -200.00 327.34 0.85 0.53 - - - - - - - - - - - - - - - - - - -220.00 360.08 0.85 0.53 - - - - - - - - - - - - - - - - - - -250.00 409.18 0.85 0.53 - - - - - - - - - - - - - - - - - - -280.00 458.28 0.85 0.53 - - - - - - - - - - - - - - - - - - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 x n (SQRT 3 x P.F xVOLT) SQRT(3) x IN x (Rcos + Xsin)

    % AT F.L.C

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV POWER FEEDERLAID IN DUCTS (INDOOR / OUTDOOR)From LV Switch Board to Final Loads.

    DERATING FACTOR =

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPSSITE CABLE RATING *CONDUCTOR RESIST. IN OHM/KM (90o C)

    CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: FREQUENCYMAXIMUM PERMISSIBLE VOLT DROP =

    CABLE REACTANCE in OHM/KM (X)

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR

  • APPENDIX : 18

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066CONTRAT NO: NPP/0026 Page 31 of 44PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01CABLE SELECTION CHART FOR 240 V 1- PH POWER FEEDER (LAID IN AIR - ON CABLE LADDER - INDOOR)

    50 Hz2.5 % AT F.L.C.0.97

    3 X 4 3 X 6 3 X 10 - - - -36.00 45.00 60.00 - - - -34.92 43.65 58.20 - - - -5.8783 3.9274 2.33 - - - -0.0933 0.0888 0.0856 - - - -

    LOAD RATING

    kW

    INLOAD F.L.C

    AMPS**

    COS SIN

    0.25 1.23 0.85 0.53 485.17 723.18 1208.54 - - - -0.37 1.81 0.85 0.53 327.81 488.63 816.58 - - - -0.55 2.70 0.85 0.53 220.53 328.72 549.33 - - - -0.75 3.68 0.85 0.53 161.72 241.06 402.85 - - - -1.50 7.35 0.85 0.53 80.86 120.53 201.42 - - - -2.20 10.78 0.85 0.53 55.13 82.18 137.33 - - - -3.00 14.71 0.85 0.53 40.43 60.26 100.71 - - - -4.00 19.61 0.85 0.53 30.32 45.20 75.53 - - - -5.50 26.96 0.85 0.53 22.05 32.87 54.93 - - - -6.00 29.41 0.85 0.53 20.22 30.13 50.36 - - - -11.00 53.92 0.85 0.53 - - 27.47 - - - -15.00 73.53 0.85 0.53 - - - - - - -18.50 90.69 0.85 0.53 - - - - - - -22.00 107.84 0.85 0.53 - - - - - - -27.50 134.80 0.85 0.53 - - - - - - -32.00 156.86 0.85 0.53 - - - - - - -35.00 171.57 0.85 0.53 - - - - - - -45.00 220.59 0.85 0.53 - - - - - - -58.00 284.31 0.85 0.53 - - - - - - -75.00 367.65 0.85 0.53 - - - - - - -88.00 431.37 0.85 0.53 - - - - - - -110.00 539.22 0.85 0.53 - - - - - - -132.00 647.06 0.85 0.53 - - - - - - -150.00 735.29 0.85 0.53 - - - - - - -175.00 857.84 0.85 0.53 - - - - - - -185.00 906.86 0.85 0.53 - - - - - - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 X n (P.F xVOLT) 2 x INx (Rcos + Xsin)

    CABLE SPECIFICATION:

    * SITE CABLE RATING = CCC x DERATING FACTOR

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    0.6/1 kV, CU/XLPE/PVC (THREE CORES CABLE - UNARMOURED)

    MAXIMUM PERMISSIBLE VOLT DROP =FREQUENCY

    DERATING FACTOR =

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    CABLE REACTANCE in OHM/KM (X)CONDUCTOR RESIST. IN OHM/KM (90o C)

    CABLE C.S.A in mm2

    SITE CABLE RATING *CURRENT CARRYING CAPACITY (CCC) in AMPS

    1- PH POWER FEEDERLAID IN AIR - ON CABLE LADDER (INTDOOR)

    From LV Switch Board to Final Loads.

  • APPENDIX : 19

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066CONTRAT NO: NPP/0026 Page 32 of 44PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01CABLE SELECTION CHART FOR 240 V 1- PH POWER FEEDER (LAID IN AIR - INDOOR / OUTDOOR)

    50 Hz2.5 % AT F.L.C.0.82

    3 X 4 3 X 6 3 X 10 3 X 16 3 X 25 3 X 35 3 X 5037.00 45.00 61.00 80.00 109.00 131.00 164.0030.34 36.90 50.02 65.60 89.38 107.42 134.485.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.4940.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750

    LOAD RATING

    kW

    INLOAD F.L.C

    AMPS**

    COS SIN

    0.25 1.23 0.85 0.53 485.17 723.18 1206.71 1897.73 2944.99 4010.49 5328.590.37 1.81 0.85 0.53 327.81 488.63 815.35 1282.25 1989.86 2709.79 3600.400.55 2.70 0.85 0.53 220.53 328.72 548.51 862.60 1338.63 1822.95 2422.090.75 3.68 0.85 0.53 161.72 241.06 402.24 632.58 981.66 1336.83 1776.201.50 7.35 0.85 0.53 80.86 120.53 201.12 316.29 490.83 668.41 888.102.20 10.78 0.85 0.53 55.13 82.18 137.13 215.65 334.66 455.74 605.523.00 14.71 0.85 0.53 40.43 60.26 100.56 158.14 245.42 334.21 444.054.00 19.61 0.85 0.53 30.32 45.20 75.42 118.61 184.06 250.66 333.045.50 26.96 0.85 0.53 22.05 32.87 54.85 86.26 133.86 182.29 242.216.00 29.41 0.85 0.53 20.22 30.13 50.28 79.07 122.71 167.10 222.0211.00 53.92 0.85 0.53 - - - 43.13 66.93 91.15 121.1015.00 73.53 0.85 0.53 - - - - 49.08 66.84 88.8118.50 90.69 0.85 0.53 - - - - - 54.20 72.0122.00 107.84 0.85 0.53 - - - - - - 60.5527.50 134.80 0.85 0.53 - - - - - - -32.00 156.86 0.85 0.53 - - - - - - -35.00 171.57 0.85 0.53 - - - - - - -45.00 220.59 0.85 0.53 - - - - - - -58.00 284.31 0.85 0.53 - - - - - - -75.00 367.65 0.85 0.53 - - - - - - -88.00 431.37 0.85 0.53 - - - - - - -110.00 539.22 0.85 0.53 - - - - - - -132.00 647.06 0.85 0.53 - - - - - - -150.00 735.29 0.85 0.53 - - - - - - -175.00 857.84 0.85 0.53 - - - - - - -185.00 906.86 0.85 0.53 - - - - - - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 X n (P.F xVOLT) 2 x INx (Rcos + Xsin)

    CONDUCTOR RESIST. IN OHM/KM (90o C)

    CABLE C.S.A in mm2

    SITE CABLE RATING *CURRENT CARRYING CAPACITY (CCC) in AMPS

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    1- PH POWER FEEDERLAID IN AIR - ON CABLE LADDER (INDOOR / OUTDOOR)

    From LV Switch Board to Final Loads.

    CABLE SPECIFICATION:

    * SITE CABLE RATING = CCC x DERATING FACTOR

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    0.6/1 kV, CU/XLPE/SWA/PVC (THREE CORES CABLE - ARMOURED)

    MAXIMUM PERMISSIBLE VOLT DROP =FREQUENCY

    DERATING FACTOR =

    CABLE REACTANCE in OHM/KM (X)

  • APPENDIX : 20

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 33 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01CABLE SELECTION CHART FOR 240 V 1- PH POWER FEEDER (LAID IN DUCTS - INDOOR / OUTDOOR)

    50 Hz2.5 % AT F.L.C.0.45

    3 X 4 3 X 6 3 X 10 3 X 16 3 X 25 3 X 35 3 X 5035 44 58 72 98 116 138

    15.75 19.80 26.10 32.40 44.10 52.20 62.105.8783 3.9274 2.3336 1.4666 0.9273 0.6686 0.4940.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750

    LOAD RATING kW

    INLOAD F.L.C

    AMPS**

    COS SIN

    0.25 1.23 0.85 0.53 485.17 723.18 1206.71 1897.73 2944.99 4010.49 5328.590.37 1.81 0.85 0.53 327.81 488.63 815.35 1282.25 1989.86 2709.79 3600.400.55 2.70 0.85 0.53 220.53 328.72 548.51 862.60 1338.63 1822.95 2422.090.75 3.68 0.85 0.53 161.72 241.06 402.24 632.58 981.66 1336.83 1776.201.50 7.35 0.85 0.53 80.86 120.53 201.12 316.29 490.83 668.41 888.102.20 10.78 0.85 0.53 55.13 82.18 137.13 215.65 334.66 455.74 605.523.00 14.71 0.85 0.53 40.43 60.26 100.56 158.14 245.42 334.21 444.054.00 19.61 0.85 0.53 - 45.20 75.42 118.61 184.06 250.66 333.045.50 26.96 0.85 0.53 - - - 86.26 133.86 182.29 242.216.00 29.41 0.85 0.53 - - - 79.07 122.71 167.10 222.0211.00 53.92 0.85 0.53 - - - - - - 121.1015.00 73.53 0.85 0.53 - - - - - - -18.50 90.69 0.85 0.53 - - - - - - -22.00 107.84 0.85 0.53 - - - - - - -27.50 134.80 0.85 0.53 - - - - - - -32.00 156.86 0.85 0.53 - - - - - - -35.00 171.57 0.85 0.53 - - - - - - -45.00 220.59 0.85 0.53 - - - - - - -58.00 284.31 0.85 0.53 - - - - - - -75.00 367.65 0.85 0.53 - - - - - - -88.00 431.37 0.85 0.53 - - - - - - -110.00 539.22 0.85 0.53 - - - - - - -132.00 647.06 0.85 0.53 - - - - - - -150.00 735.29 0.85 0.53 - - - - - - -175.00 857.84 0.85 0.53 - - - - - - -185.00 906.86 0.85 0.53 - - - - - - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 X n (P.F xVOLT) 2 x INx (Rcos + Xsin)

    CABLE REACTANCE in OHM/KM (X)

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR

    DERATING FACTOR =

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPSSITE CABLE RATING *CONDUCTOR RESIST. IN OHM/KM (90o C)

    CABLE SPECIFICATION: 0.6/1 kV, CU/XLPE/SWA/PVC (THREE CORES CABLE - ARMOURED)FREQUENCYMAXIMUM PERMISSIBLE VOLT DROP =

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    1- PH POWER FEEDERLAID IN DUCTS (OUTDOOR)

    From LV Switch Board to Final Loads.

  • APPENDIX : 21

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 34 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01415 V 3-PH POWER FEEDER

    0.6/1 kV, CU/XLPE/AWA/PVC (SINGLE CORE CABLE - ARMOURED)50 Hz

    1.00.801

    4X(1 X 50) 4X(1 X 70) 4X(1 X 95) 4X(1 X 120) 4X(1 X 150) 4X(1 X 185) 4X(1 X 240) 4X(1 X 300) 4X(1 X 400) 4X(1 X 500) 4X(1 X 630) 4X(2 X 300) 4X(2 X 400) 4X(2 X 500) 4X(2 X 630)154 199 244 287 328 372 453 523 603 687 808 1046 1206 1374 1616

    123.35 159.40 195.44 229.89 262.73 297.97 362.85 418.92 483.00 550.29 647.21 837.85 966.01 1100.57 1294.420.4940 0.3430 0.2480 0.1970 0.1600 0.1290 0.0991 0.0810 0.0638 0.0517 0.0418 0.041 0.032 0.026 0.0210.1140 0.1080 0.1040 0.1010 0.0990 0.0960 0.0930 0.0910 0.0900 0.0870 0.0823 0.0455 0.0450 0.0435 0.0412

    LOAD RATING kW

    INLOAD F.L.C

    AMPS**COS SIN

    25.00 40.92 0.85 0.53 - - - 122.00 168.05 220.48 265.38 311.22 365.47 439.53 501.39 576.11 652.26 742.31 1002.79 1152.23 1304.52 1484.62 - - -50.00 81.84 0.85 0.53 - - - 61.00 84.03 110.24 132.69 155.61 182.74 219.76 250.70 288.06 326.13 371.15 501.39 576.11 652.26 742.31 - - -75.00 122.75 0.85 0.53 - - - 40.67 56.02 73.49 88.46 103.74 121.82 146.51 167.13 192.04 217.42 247.44 334.26 384.08 434.84 494.87 - - -100.00 163.67 0.85 0.53 - - - - - 55.12 66.34 77.80 91.37 109.88 125.35 144.03 163.06 185.58 250.70 288.06 326.13 371.15 - - -125.00 204.59 0.85 0.53 - - - - - - 53.08 62.24 73.09 87.91 100.28 115.22 130.45 148.46 200.56 230.45 260.90 296.92 - - -150.00 245.51 0.85 0.53 - - - - - - - 51.87 60.91 73.25 83.57 96.02 108.71 123.72 167.13 192.04 217.42 247.44 - - -175.00 286.42 0.85 0.53 - - - - - - - - 52.21 62.79 71.63 82.30 93.18 106.04 143.26 164.60 186.36 212.09 - - -200.00 327.34 0.85 0.53 - - - - - - - - - 54.94 62.67 72.01 81.53 92.79 125.35 144.03 163.06 185.58 - - -225.00 368.26 0.85 0.53 - - - - - - - - - - 55.71 64.01 72.47 82.48 111.42 128.03 144.95 164.96 - - -250.00 409.18 0.85 0.53 - - - - - - - - - - 50.14 57.61 65.23 74.23 100.28 115.22 130.45 148.46 - - -275.00 450.10 0.85 0.53 - - - - - - - - - - - 52.37 59.30 67.48 91.16 104.75 118.59 134.97 - - -300.00 491.01 0.85 0.53 - - - - - - - - - - - - 54.35 61.86 83.57 96.02 108.71 123.72 - - -325.00 531.93 0.85 0.53 - - - - - - - - - - - - 50.17 57.10 77.14 88.63 100.35 114.20 - - -350.00 572.85 0.85 0.53 - - - - - - - - - - - - - 53.02 71.63 82.30 93.18 106.04 - - -375.00 613.77 0.85 0.53 - - - - - - - - - - - - - 49.49 66.85 76.82 86.97 98.97 - - -400.00 654.68 0.85 0.53 - - - - - - - - - - - - - - 62.67 72.01 81.53 92.79 - - -425.00 695.60 0.85 0.53 - - - - - - - - - - - - - - 58.99 67.78 76.74 87.33 - - -450.00 736.52 0.85 0.53 - - - - - - - - - - - - - - 55.71 64.01 72.47 82.48 - - -475.00 777.44 0.85 0.53 - - - - - - - - - - - - - - 52.78 60.64 68.66 78.14 - - -500.00 818.36 0.85 0.53 - - - - - - - - - - - - - - 50.14 57.61 65.23 74.23 - - -525.00 859.27 0.85 0.53 - - - - - - - - - - - - - - - 54.87 62.12 70.70 - - -550.00 900.19 0.85 0.53 - - - - - - - - - - - - - - - 52.37 59.30 67.48 - - -575.00 941.11 0.85 0.53 - - - - - - - - - - - - - - - 50.10 56.72 64.55 - - -600.00 982.03 0.85 0.53 - - - - - - - - - - - - - - - - 54.35 61.86 - - -625.00 1022.95 0.85 0.53 - - - - - - - - - - - - - - - - 52.18 59.38 - - -650.00 1063.86 0.85 0.53 - - - - - - - - - - - - - - - - 50.17 57.10 - - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 x n (SQRT 3 x P.F xVOLT) SQRT(3) x IN x (Rcos + Xsin)

    % AT F.L.C

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV POWER FEEDERLAID IN AIR - ON CABLE LADDER (INDOOR / OUTDOOR)

    Power Distribution Feeders - From LV Switch Board to Distribution Panels

    DERATING FACTOR =

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPSSITE CABLE RATING *CONDUCTOR RESIST. IN OHM/KM (90o C)

    CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: FREQUENCYMAXIMUM PERMISSIBLE VOLT DROP =

    CABLE REACTANCE in OHM/KM (X)

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR

  • APPENDIX : 22

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 35 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01

    415 V 3-PH POWER FEEDER (LAID IN DUCTS) - OUTDOOR0.6/1 kV, CU/XLPE/AWA/PVC (SINGLE CORE CABLE - ARMOURED)

    50 Hz1.00.41

    4X(1 X 50) 4X(1 X 70) 4X(1 X 95) 4X(1 X 120) 4X(1 X 150) 4X(1 X 185) 4X(1 X 240) 4X(1 X 300) 4X(1 X 400) 4X(1 X 500) 4X(1 X 630) 4X(2 X 300) 4X(2 X 400) 4X(2 X 500) 4X(2 X 630)146 180 217 246 279 317 363 412 464 515 587 824 928 1030 1174

    59.86 73.80 88.97 100.86 114.39 129.97 148.83 168.92 190.24 211.15 240.67 337.84 380.48 422.30 481.340.4940 0.3430 0.2480 0.1970 0.1600 0.1290 0.0991 0.0810 0.0638 0.0517 0.0418 0.041 0.032 0.026 0.0210.1140 0.1080 0.1040 0.1010 0.0990 0.0960 0.0930 0.0910 0.0900 0.0870 0.0823 0.0455 0.0450 0.0435 0.0412

    LOAD RATING

    kW

    INLOAD F.L.C

    AMPS**

    COS SIN

    25.00 40.92 0.85 0.53 - - - 122.00 168.05 220.48 265.38 311.22 365.47 439.53 501.39 576.11 652.26 742.31 1002.79 1152.23 1304.52 1484.62 - - -50.00 81.84 0.85 0.53 - - - - - 110.24 132.69 155.61 182.74 219.76 250.70 288.06 326.13 371.15 501.39 576.11 652.26 742.31 - - -75.00 122.75 0.85 0.53 - - - - - - - - 121.82 146.51 167.13 192.04 217.42 247.44 334.26 384.08 434.84 494.87 - - -

    100.00 163.67 0.85 0.53 - - - - - - - - - - 125.35 144.03 163.06 185.58 250.70 288.06 326.13 371.15 - - -125.00 204.59 0.85 0.53 - - - - - - - - - - - - 130.45 148.46 200.56 230.45 260.90 296.92 - - -150.00 245.51 0.85 0.53 - - - - - - - - - - - - - - 167.13 192.04 217.42 247.44 - - -175.00 286.42 0.85 0.53 - - - - - - - - - - - - - - 143.26 164.60 186.36 212.09 - - -200.00 327.34 0.85 0.53 - - - - - - - - - - - - - - 125.35 144.03 163.06 185.58 - - -225.00 368.26 0.85 0.53 - - - - - - - - - - - - - - - 128.03 144.95 164.96 - - -250.00 409.18 0.85 0.53 - - - - - - - - - - - - - - - - 130.45 148.46 - - -275.00 450.10 0.85 0.53 - - - - - - - - - - - - - - - - - 134.97 - - -300.00 491.01 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -325.00 531.93 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -350.00 572.85 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -375.00 613.77 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -400.00 654.68 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -425.00 695.60 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -450.00 736.52 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -475.00 777.44 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -500.00 818.36 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -525.00 859.27 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -550.00 900.19 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -575.00 941.11 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -600.00 982.03 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -625.00 1022.95 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -650.00 1063.86 0.85 0.53 - - - - - - - - - - - - - - - - - - - - -

    ** IN (FLC) = (LOAD x 1000) ***L = (Vd%) x V x 1000 x n (SQRT 3 x P.F xVOLT) SQRT(3) x IN x (Rcos + Xsin)

    CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: FREQUENCYMAXIMUM PERMISSIBLE VOLT DROP = % AT F.L.C

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV POWER FEEDERLAID IN DUCTS (OUTDOOR)

    Power Distribution Feeders - From LV Switch Board to Distribution Panels

    DERATING FACTOR =

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPSSITE CABLE RATING *CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X)

    *MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR

  • APPENDIX : 23

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 36 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01415 V 3- PH MOTORS RUNNING

    50 Hz2.50.97

    3 X 4 3 X 6 3 X 10 - - - - - - - - - -36.00 45.00 60.00 - - - - - - - - - -34.92 43.65 58.20 - - - - - - - - - -5.8783 3.9274 2.33 - - - - - - - - - -0.0933 0.0888 0.0856 - - - - - - - - - -

    MOTOR RATING

    kW

    INLOAD F.L.C AMPS

    **

    MOTOR L.R.C AMPS

    ****

    COS SIN

    0.25 0.43 2.61 0.80 0.60 2895.38 4312.09 7193.43 - - - - - - - - - -0.37 0.64 3.86 0.80 0.60 1956.34 2913.58 4860.42 - - - - - - - - - -0.55 0.96 5.74 0.80 0.60 1316.08 1960.04 3269.74 - - - - - - - - - -0.75 1.30 7.83 0.80 0.60 965.13 1437.36 2397.81 - - - - - - - - - -1.50 2.61 15.65 0.80 0.60 482.56 718.68 1198.90 - - - - - - - - - -2.20 3.83 22.95 0.80 0.60 329.02 490.01 817.43 - - - - - - - - - -3.00 5.22 31.30 0.80 0.60 241.28 359.34 599.45 - - - - - - - - - -4.00 6.96 41.74 0.80 0.60 180.96 269.51 449.59 - - - - - - - - - -5.50 9.56 57.39 0.80 0.60 131.61 196.00 326.97 - - - - - - - - - -7.50 13.04 78.26 0.80 0.60 96.51 143.74 239.78 - - - - - - - - - -

    11.00 19.13 114.77 0.80 0.60 65.80 98.00 163.49 - - - - - - - - - -15.00 26.09 156.51 0.80 0.60 48.26 71.87 119.89 - - - - - - - - - -18.50 32.17 193.03 0.80 0.60 39.13 58.27 97.21 - - - - - - - - - -22.00 38.26 229.55 0.80 0.60 - 49.00 81.74 - - - - - - - - - -25.00 43.48 260.85 0.80 0.60 - 43.12 71.93 - - - - - - - - - -30.00 52.17 313.02 0.80 0.60 - - 59.95 - - - - - - - - - -37.00 64.34 386.06 0.80 0.60 - - - - - - - - - - - - -45.00 78.26 469.53 0.80 0.60 - - - - - - - - - - - - -55.00 95.65 573.87 0.80 0.60 - - - - - - - - - - - - -61.00 106.08 636.48 0.80 0.60 - - - - - - - - - - - - -75.00 130.43 782.55 0.80 0.60 - - - - - - - - - - - - -110.00 191.29 1147.74 0.80 0.60 - - - - - - - - - - - - -132.00 229.55 1377.29 0.80 0.60 - - - - - - - - - - - - -150.00 260.85 1565.11 0.80 0.60 - - - - - - - - - - - - -160.00 278.24 1669.45 0.80 0.60 - - - - - - - - - - - - -185.00 321.72 1930.30 0.80 0.60 - - - - - - - - - - - - -

    ***L = ****L.R.C = 6 x F.LC SQRT(3) x IN x (Rcos + Xsin)

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: 0.6/1 kV, CU/XLPE/PVC (THREE CORE CABLES - UNARMOURED)FREQUENCY

    CABLE REACTANCE in OHM/KM (X)

    MAXIMUM PERMISSIBLE VOLT DROP = % AT MOTOR F.L.CDERATING FACTOR =

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR ** IN (FLC) = (LOAD x 1000) (Vd%) x V x 1000

    SITE CABLE RATING *CONDUCTOR RESIST. IN OHM/KM (90o C)

    3- PH LV MOTOR FEEDERS - RUNLAID IN AIR - ON CABLE LADDER (INDOOR)

    From LV Switch Board to LV Motors.

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPS

    (SQRT 3 x P.F xVOLT)

  • APPENDIX : 24

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 37 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No.01415 V 3- PH MOTORS STARTING

    0.6/1 kV, CU/XLPE/PVC (THREE CORE CABLES - UNARMOURED)50 Hz

    150.97

    3 X 4 3 X 6 3 X 10 - - - - - - - - - -36.00 45.00 60.00 - - - - - - - - - -34.92 43.65 58.20 - - - - - - - - - -5.8783 3.9274 2.33 - - - - - - - - - -0.0933 0.0888 0.0856 - - - - - - - - - -

    MOTOR RATING

    kW

    INLOAD F.L.C AMPS

    **

    MOTOR L.R.C AMPS

    ****

    COS SIN

    0.25 0.43 2.61 0.20 0.98 10873.86 15791.66 25056.81 - - - - - - - - - -0.37 0.64 3.86 0.20 0.98 7347.20 10670.04 16930.28 - - - - - - - - - -0.55 0.96 5.74 0.20 0.98 4942.67 7178.03 11389.46 - - - - - - - - - -0.75 1.30 7.83 0.20 0.98 3624.62 5263.89 8352.27 - - - - - - - - - -1.50 2.61 15.65 0.20 0.98 1812.31 2631.94 4176.13 - - - - - - - - - -2.20 3.83 22.95 0.20 0.98 1235.67 1794.51 2847.36 - - - - - - - - - -3.00 5.22 31.30 0.20 0.98 906.16 1315.97 2088.07 - - - - - - - - - -4.00 6.96 41.74 0.20 0.98 679.62 986.98 1566.05 - - - - - - - - - -5.50 9.56 57.39 0.20 0.98 494.27 717.80 1138.95 - - - - - - - - - -7.50 13.04 78.26 0.20 0.98 362.46 526.39 835.23 - - - - - - - - - -

    11.00 19.13 114.77 0.20 0.98 247.13 358.90 569.47 - - - - - - - - - -15.00 26.09 156.51 0.20 0.98 181.23 263.19 417.61 - - - - - - - - - -18.50 32.17 193.03 0.20 0.98 146.94 213.40 338.61 - - - - - - - - - -22.00 38.26 229.55 0.20 0.98 - 179.45 284.74 - - - - - - - - - -25.00 43.48 260.85 0.20 0.98 - 157.92 250.57 - - - - - - - - - -30.00 52.17 313.02 0.20 0.98 - - 208.81 - - - - - - - - - -37.00 64.34 386.06 0.20 0.98 - - - - - - - - - - - - -45.00 78.26 469.53 0.20 0.98 - - - - - - - - - - - - -55.00 95.65 573.87 0.20 0.98 - - - - - - - - - - - - -61.00 106.08 636.48 0.20 0.98 - - - - - - - - - - - - -75.00 130.43 782.55 0.20 0.98 - - - - - - - - - - - - -110.00 191.29 1147.74 0.20 0.98 - - - - - - - - - - - - -132.00 229.55 1377.29 0.20 0.98 - - - - - - - - - - - - -150.00 260.85 1565.11 0.20 0.98 - - - - - - - - - - - - -160.00 278.24 1669.45 0.20 0.98 - - - - - - - - - - - - -185.00 321.72 1930.30 0.20 0.98 - - - - - - - - - - - - -

    ***L = ****L.R.C = 6 x F.LC

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV MOTOR FEEDERS - STARTINGLAID IN AIR - ON CABLE LADDER (INDOOR)

    From LV Switch Board to LV Motors.

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPSSITE CABLE RATING *

    CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: FREQUENCYMAXIMUM PERMISSIBLE VOLT DROP = % AT MOTOR L.R.CDERATING FACTOR =

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR ** IN (FLC) = (LOAD x 1000) (Vd%) x VL x 1000

    CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X)

    (SQRT 3 x P.F xVOLT) SQRT(3) x I (LRC)x (Rcos + Xsin)

  • APPENDIX : 25

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 38 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01

    415 V 3- PH MOTORS STARTING/ RUNNING

    0.6/1 kV, CU/XLPE/PVC (THREE CORE CABLES - UNARMOURED)50 Hz

    MAXIMUM PERMISSIBLE VOLT DROP (Run) = 2.5MAXIMUM PERMISSIBLE VOLT DROP (Starting) = 15

    0.97

    3 X 4 3 X 6 3 X 10 - - - - - - - - - -36.00 45.00 60.00 - - - - - - - - - -34.92 43.65 58.20 - - - - - - - - - -5.8783 3.9274 2.33 - - - - - - - - - -0.0933 0.0888 0.0856 - - - - - - - - - -

    MOTOR RATING

    kW

    INLOAD F.L.C AMPS

    **

    MOTOR L.R.C AMPS

    ****

    COS SIN

    0.25 0.43 2.61 0.80 0.60 2895.38 4312.09 7193.43 - - - - - - - - - -0.37 0.64 3.86 0.80 0.60 1956.34 2913.58 4860.42 - - - - - - - - - -0.55 0.96 5.74 0.80 0.60 1316.08 1960.04 3269.74 - - - - - - - - - -0.75 1.30 7.83 0.80 0.60 965.13 1437.36 2397.81 - - - - - - - - - -1.50 2.61 15.65 0.80 0.60 482.56 718.68 1198.90 - - - - - - - - - -2.20 3.83 22.95 0.80 0.60 329.02 490.01 817.43 - - - - - - - - - -3.00 5.22 31.30 0.80 0.60 241.28 359.34 599.45 - - - - - - - - - -4.00 6.96 41.74 0.80 0.60 180.96 269.51 449.59 - - - - - - - - - -5.50 9.56 57.39 0.80 0.60 131.61 196.00 326.97 - - - - - - - - - -7.50 13.04 78.26 0.80 0.60 96.51 143.74 239.78 - - - - - - - - - -

    11.00 19.13 114.77 0.80 0.60 65.80 98.00 163.49 - - - - - - - - - -15.00 26.09 156.51 0.80 0.60 48.26 71.87 119.89 - - - - - - - - - -18.50 32.17 193.03 0.80 0.60 39.13 58.27 97.21 - - - - - - - - - -22.00 38.26 229.55 0.80 0.60 - 49.00 81.74 - - - - - - - - - -25.00 43.48 260.85 0.80 0.60 - 43.12 71.93 - - - - - - - - - -30.00 52.17 313.02 0.80 0.60 - - 59.95 - - - - - - - - - -37.00 64.34 386.06 0.80 0.60 - - - - - - - - - - - - -45.00 78.26 469.53 0.80 0.60 - - - - - - - - - - - - -55.00 95.65 573.87 0.80 0.60 - - - - - - - - - - - - -61.00 106.08 636.48 0.80 0.60 - - - - - - - - - - - - -75.00 130.43 782.55 0.80 0.60 - - - - - - - - - - - - -110.00 191.29 1147.74 0.80 0.60 - - - - - - - - - - - - -132.00 229.55 1377.29 0.80 0.60 - - - - - - - - - - - - -150.00 260.85 1565.11 0.80 0.60 - - - - - - - - - - - - -160.00 278.24 1669.45 0.80 0.60 - - - - - - - - - - - - -185.00 321.72 1930.30 0.80 0.60 - - - - - - - - - - - - -

    ***L = ****L.R.C = 6 x F.LC

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV MOTOR FEEDERS - SELECTIONLAID IN AIR - ON CABLE LADDER (INDOOR)

    From LV Switch Board to LV Motors.

    % AT MOTOR L.R.CDERATING FACTOR =

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPS

    SQRT(3) x I (LRC)x (Rcos + Xsin)

    SITE CABLE RATING *

    CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: FREQUENCY

    % AT MOTOR F.L.C

    CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X)

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR ** IN (FLC) = (LOAD x 1000) (Vd%) x VL x 1000 (SQRT 3 x P.F xVOLT)

  • APPENDIX : 26

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 39 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01415 V 3- PH MOTORS RUNNING

    0.6/1 kV, CU/XLPE/SWA/PVC (THREE CORE CABLES - ARMOURED)50 Hz

    2.50.82

    3 X 4 3 X 6 3 X 10 3 X 16 3 X 25 3 X 35 3 X 50 3 X 70 3 X 95 3 X 120 3 X 150 3 X 185 3 X 24036.00 45.00 60.00 79.00 106.00 129.00 159.00 200 238 275 313 359 43029.52 36.90 49.20 64.78 86.92 105.78 130.38 164.00 195.16 225.50 256.66 294.38 352.605.8783 3.9274 2.33 1.4666 0.927 0.6686 0.494 0.343 0.248 0.197 0.160 0.129 0.1000.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 0.0740 0.0720 0.0710 0.0710 0.0710 0.0710

    MOTOR RATING

    kW

    INLOAD F.L.C AMPS

    **

    MOTOR L.R.C AMPS

    ****

    COS SIN

    0.25 0.43 2.61 0.80 0.60 2895.38 4312.09 7193.43 11268.87 17426.83 23640.23 31299.41 43272.61 57028.15 68821.18 80610.81 94499.31 112528.590.37 0.64 3.86 0.80 0.60 1956.34 2913.58 4860.42 7614.10 11774.88 15973.13 21148.25 29238.25 38532.53 46500.80 54466.76 63850.89 76032.830.55 0.96 5.74 0.80 0.60 1316.08 1960.04 3269.74 5122.21 7921.29 10745.56 14227.00 19669.37 25921.88 31282.35 36641.28 42954.23 51149.360.75 1.30 7.83 0.80 0.60 965.13 1437.36 2397.81 3756.29 5808.94 7880.08 10433.14 14424.20 19009.38 22940.39 26870.27 31499.77 37509.531.50 2.61 15.65 0.80 0.60 482.56 718.68 1198.90 1878.15 2904.47 3940.04 5216.57 7212.10 9504.69 11470.20 13435.14 15749.89 18754.762.20 3.83 22.95 0.80 0.60 329.02 490.01 817.43 1280.55 1980.32 2686.39 3556.75 4917.34 6480.47 7820.59 9160.32 10738.56 12787.343.00 5.22 31.30 0.80 0.60 241.28 359.34 599.45 939.07 1452.24 1970.02 2608.28 3606.05 4752.35 5735.10 6717.57 7874.94 9377.384.00 6.96 41.74 0.80 0.60 180.96 269.51 449.59 704.30 1089.18 1477.51 1956.21 2704.54 3564.26 4301.32 5038.18 5906.21 7033.045.50 9.56 57.39 0.80 0.60 131.61 196.00 326.97 512.22 792.13 1074.56 1422.70 1966.94 2592.19 3128.24 3664.13 4295.42 5114.947.50 13.04 78.26 0.80 0.60 96.51 143.74 239.78 375.63 580.89 788.01 1043.31 1442.42 1900.94 2294.04 2687.03 3149.98 3750.95

    11.00 19.13 114.77 0.80 0.60 65.80 98.00 163.49 256.11 396.06 537.28 711.35 983.47 1296.09 1564.12 1832.06 2147.71 2557.4715.00 26.09 156.51 0.80 0.60 48.26 71.87 119.89 187.81 290.45 394.00 521.66 721.21 950.47 1147.02 1343.51 1574.99 1875.4818.50 32.17 193.03 0.80 0.60 - 58.27 97.21 152.28 235.50 319.46 422.96 584.77 770.65 930.02 1089.34 1277.02 1520.6622.00 38.26 229.55 0.80 0.60 - - 81.74 128.06 198.03 268.64 355.68 491.73 648.05 782.06 916.03 1073.86 1278.7325.00 43.48 260.85 0.80 0.60 - - 71.93 112.69 174.27 236.40 312.99 432.73 570.28 688.21 806.11 944.99 1125.2930.00 52.17 313.02 0.80 0.60 - - - 93.91 145.22 197.00 260.83 360.61 475.23 573.51 671.76 787.49 937.7437.00 64.34 386.06 0.80 0.60 - - - 76.14 117.75 159.73 211.48 292.38 385.33 465.01 544.67 638.51 760.3345.00 78.26 469.53 0.80 0.60 - - - - 96.82 131.33 173.89 240.40 316.82 382.34 447.84 525.00 625.1655.00 95.65 573.87 0.80 0.60 - - - - - 107.46 142.27 196.69 259.22 312.82 366.41 429.54 511.4961.00 106.08 636.48 0.80 0.60 - - - - - - 128.28 177.35 233.72 282.05 330.37 387.29 461.1875.00 130.43 782.55 0.80 0.60 - - - - - - - 144.24 190.09 229.40 268.70 315.00 375.10110.00 191.29 1147.74 0.80 0.60 - - - - - - - - 129.61 156.41 183.21 214.77 255.75132.00 229.55 1377.29 0.80 0.60 - - - - - - - - - - 152.67 178.98 213.12150.00 260.85 1565.11 0.80 0.60 - - - - - - - - - - - 157.50 187.55160.00 278.24 1669.45 0.80 0.60 - - - - - - - - - - - 147.66 175.83185.00 321.72 1930.30 0.80 0.60 - - - - - - - - - - - - 152.07

    ***L = ****L.R.C = 6 x F.LC SQRT(3) x IN x (Rcos + Xsin)

    JOINT VENTURECONSOLIDATED CONTRACTORS GROUP S.A.L. (CCC)

    TEYSEER CONTRACTING COMPANY (TCC)www.ccc.gr

    3- PH LV MOTOR FEEDERS - RUNLAID IN AIR - ON CABLE LADDER (INDOOR / OUTDOOR)

    From LV Switch Board to LV Motors.CABLE SELECTION CHART FOR

    CABLE SPECIFICATION: FREQUENCYMAXIMUM PERMISSIBLE VOLT DROP = % AT MOTOR F.L.CDERATING FACTOR =

    CABLE C.S.A in mm2CURRENT CARRYING CAPACITY (CCC) in AMPSSITE CABLE RATING *CONDUCTOR RESIST. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X)

    MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS***

    * SITE CABLE RATING = CCC x DERATING FACTOR ** IN (FLC) = (LOAD x 1000) (Vd%) x V x 1000 (SQRT 3 x P.F xVOLT)

  • APPENDIX : 27

    CLIENT: STATE OF QATAR - NEW PORT PROJECT STEERING COMMITTEE Document No.: DPCT-TCC-CAL-EL-00066

    CONTRAT NO: NPP/0026 Page 40 of 44

    PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS REV. No. 01415 V 3- PH MOTORS STARTING

    0.6/1 kV, CU/XLPE/SWA/PVC (THREE CORE CABLES - ARMOURED)50 Hz

    150.82

    3 X 4 3 X 6 3 X 10 3 X 16 3 X 25 3 X 35 3 X 50 3 X 70 3 X 95 3 X 120 3 X 150 3 X 185 3 X 24036.00 45.00 60.00 79.00 106.00 129.00 159.00 200 238 275 313 359 43029.52 36.90 49.20 64.78 86.92 105.78 130.38 164.00 195.16 225.50 256.66 294.38 352.605.8800 3.9300 2.3300 1.4666 0.9270 0.6686 0.4940 0.3425 0.2480 0.1970 0.1604 0.1290 0.09980.0933 0.0888 0.0856 0.0823 0.0817 0.0799 0.0750 0.0740 0.0720 0.0710 0.0710 0.0710 0.0710

    MOTOR RATING

    kW

    INLOAD F.L.C AMPS

    **

    MOTOR L.R.C AMPS

    ****

    COS SIN

    0.25 0.43 2.61 0.20 0.98 10870.95 15782.25 25056.81 36843.79 51904.45 64988.82 79972.28 97712.92 114677.81 126443.68 135549.52 144475.71 153900.270.37 0.64 3.86 0.20 0.98 7345.23 10663.68 16930.28 24894.45 35070.57 43911.37 54035.33 66022.24 77485.00 85434.92 91587.51 97618.73 103986.670.55 0.96 5.74 0.20 0.98 4941.34 7173.75 11389.46 16747.18 23592.93 29540.37 36351.04 44414.96 52126.28 57474.40 61613.42 65670.78 69954.670.75 1.30 7.83 0.20 0.98 3623.65 5260.75 8352.27 12281.26 17301.48 21662.94 26657.43 32570.97 38225.94 42147.89 45183.17 48158.57 51300.091.50 2.61 15.65 0.20 0.98 1811.82 2630.38 4176.13 6140.63 8650.74 10831.47 13328.71 16285.49 19112.97 21073.95 22591.59 24079.29 25650.052.20 3.83 22.95 0.20 0.98 1235.33 1793.44 2847.36 4186.79 5898.23 7385.09 9087.76 11103.74 13031.57 14368.60 15403.35 16417.69 17488.673.00 5.22 31.30 0.20 0.98 905.91 1315.19 2088.07 3070.32 4325.37 5415.74 6664.36 8142.74 9556.48 10536.97 11295.79 12039.64 12825.024.00 6.96 41.74 0.20 0.98 679.43 986.39 1566.05 2302.74 3244.03 4061.80 4998.27 6107.06 7167.36 7902.73 8471.85 9029.73 9618.775.50 9.56 57.39 0.20 0.98 494.13 717.38 1138.95 1674.72 2359.29 2954.04 3635.10 4441.50 5212.63 5747.44 6161.34 6567.08 6995.477.50 13.04 78.26 0.20 0.98 362.36 526.08 835.23 1228.13 1730.15 2166.29 2665.74 3257.10 3822.59 4214.79