Upload
others
View
78
Download
11
Embed Size (px)
Citation preview
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Electrical Machines - I
Lab Manual
ELECTRICAL AND ELECTRONICS ENGINEERING
ANURAG COLLEGE OF ENGINEERING
Aushapur (V), Ghatkesar (M) - 501301
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
INDEX
S. No. List of Experiments
1 Identifying the terminals of DC Motors
2 To study the parts of 3 Point, 4 Point Starter and Drum controller starter
3 Magnetization characteristic of DC shunt generator
4 Load test on DC shunt generator
5 Load test on DC series generator
6 Load test on DC compound generator
7 Hopkinson’s test on DC shunt machines
8 Field’s test on DC series machines
9 Speed control of DC shunt motor
10 Swinburne’s test on DC shunt motor
11 Brake test on DC compound motor
12 Brake test on DC shunt motor
13 Retardation test on DC shunt motor
14 Separation of core losses in DC shunt motor
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
IDENTIFY THE TERMINALS OF FOLLOWING DC MACHINES
(a) DC Shunt Wound Motor:
The shunt wound DC motor falls under the category of self-excited DC motors, where
the field windings are shunted to, or are connected in parallel to the armature winding of the
motor, as its name is suggestive of. And for this reason both the armature winding and the field
winding are exposed to the same supply voltage, though there are separate branches for the flow
of armature current and the field current as shown in the figure of DC shunt motor below.
Voltage and Current Equation of a Shunt Wound DC Motor
Let us now consider the voltage and current being supplied from the electrical terminal to the
motor be given by E and Itotal respectively. This supply current in case of the shunt wound DC
motor is split up into 2 parts. Ia, flowing through the armature winding of resistance Ra and Ish
flowing through the field winding of resistance Rsh. The voltage across both windings remains
the same. From there we can write
Thus we put this value of armature current Ia to get general voltage equation of a DC shunt
motor.
Now in general practice, when the motor is in its running condition, and supply voltage is
constant the shunt field current given by,
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
But we know Ish ∝ Φ i.e. field flux Φ is proportional to filed current Ish Thus the field flux
remains more or less constant and for this reason a shunt wound DC motor is called a constant
flux motor.
(b) Series Wound DC Motor or DC Series Motor:
A series wound DC motor like in the case of shunt wound DC motor or compound
wound DC motor falls under the category of self-excited DC motors, and it gets its name from
the fact that the field winding in this case is connected internally in series to the armature
winding. Thus the field winding is exposed to the entire armature current unlike in the case of a
shunt motor.
Construction of Series DC Motor:
Construction wise a motor is similar to any other types of DC motors in almost all aspects. It
consists of all the fundamental components like the stator housing the field winding or the rotor
carrying the armature conductors, and the other vital parts like the commutator or the brush
segments all attached in the proper sequence as in the case of a generic DC motor.
Voltage and Current Equation of Series DC Motor:
The electrical layout of a typical series wound DC motor is shown in the diagram below.
Let the supply voltage and current given to the electrical port of the motor be given by E and Itotal
respectively. Since the entire supply current flows through both the armature and field conductor.
Where, Ise is the series current in the field coil and Ia is the armature current.
Now form the basic voltage equation of the DC motor.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Where, Eb is the back emf. Rse is the series coil resistance and Ra is the armature resistance.
Since Ise = Ia, we can write,
This is the basic voltage equation of a series wound DC motor. Another interesting fact about the
DC series motor worth noting is that, the field flux like in the case of any other DC motor is
proportional to field current.
But since here and
i.e. the field flux is proportional to the entire armature current or the total supply current. And for
this reason, the flux produced in this motor is strong enough to produce sufficient torque, even
with the bare minimum number of turns it has in the field coil.
(c) Compound Wound DC Motor or DC Compound Motor:
A compound wound DC motor or rather a DC compound motor falls under the category
of self-excited motors, and is made up of both series the field coils S1 S2 and shunt field coils F1
F2 connected to the armature winding as shown in the figure below.
Both the field coils provide for the required amount of magnetic flux, that links with the
armature coil and brings about the torque necessary to facilitate rotation at desired speed.
As we can understand, a compound wound DC motor is basically formed by the amalgamation
of a shunt wound DC motor and series wound DC motor to achieve the better off properties of
both these types. Like a shunt wound DC motor is bestowed with an extremely efficient speed
regulation characteristic, whereas the DC series motor has high starting torque.
Types of Compound Wound DC Motor
The compound wound DC motor can further be subdivided into 2 major types on the basis of
its field winding connection with respect to the armature winding, and they are:
1. Long Shunt Compound Wound DC Motor
In case of long shunt compound wound DC motor, the shunt field winding is connected in
parallel across the series combination of both the armature and series field coil, as shown in the
diagram below.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Voltage and Current Equation of Long Shunt Compound Wound DC Motor
Let E and Itotal be the total supply voltage and current supplied to the input terminals of the
motor. And Ia, Ise , Ish be the values of current flowing through armature resistance Ra, series
winding resistance Rse and shunt winding resistance Rsh respectively. Now we know in shunt
motor, And in series motor
Therefore, the current equation of a compound wound DC motor is given by
and its voltage equation is,
2. Short Shunt Compound Wound DC Motor
In case of short shunt compound wound DC motor, the shunt field winding is connected in
parallel across the armature winding only. And series field coil is exposed to the entire supply
current, before being split up into armature and shunt field current as shown in the diagram
below.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Voltage and Current Equation of Short Shunt Compound Wound DC Motor:
Here also let, E and Itotal be the total supply voltage and current supplied to the input terminals of
the motor. And Ia, Ise, Ish be the values of current flowing through armature resistance Ra, series
winding resistance Rse and shunt winding resistance Rsh respectively. But from the diagram
above we can see,
Since the entire supply current flows through the series field winding. And like in the case of a
DC shunt motor,
Equation (2) and (3) gives the current equation of a short shunt compound wound DC motor.
Now for equating the voltage equation, we apply Kirchhoff’s law to the circuit and get,
But since
Thus the final voltage equation can be written as,
Apart from the above mentioned classification, a compound wound DC motor can further be sub
divided into 2 types depending upon excitation or the nature of compounding. i.e.
Cumulative Compounding of DC Motor:
A compound wound DC motor is said to be cumulatively compounded when the shunt field flux
produced by the shunt winding assists or enhances the effect of main field flux, produced by the
series winding.
Differential Compounding of DC Motor:
Similarly a compound wound DC motor is said to be deferentially compounded when the flux
due to the shunt field winding diminishes the effect of the main series winding. This particular
trait is not really desirable, and hence does not find much of a practical application.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
The net flux produced in this case is lesser than the original flux and hence does not find much of
a practical application. The compounding characteristic of the self excited DC motor is shown in
the figure below.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
DC 3-POINT STARTER
A 3 point starter in simple words is a device that helps in the starting and running of a
shunt wound DC motor or compound wound DC motor. Now the question is why these types of
DC motors require the assistance of the starter in the first case. The only explanation to that is
given by the presence of back emf Eb, which plays a critical role in governing the operation of
the motor. The back emf, develops as the motor armature starts to rotate in presence of the
magnetic field, by generating action and counters the supply voltage. This also essentially means
that the back emf at the starting is zero, and develops gradually as the motor gathers speed.
The general motor emf equation at starting is modified to E =
Ia.Ra as at starting Eb = 0. Thus we can well understand from the above equation
that the current will be dangerously high at starting (as armature resistance Ra is small) and
hence its important that we make use of a device like the 3 point starter to limit the starting
current to an allowable lower value. Let us now look into the construction and working of three
point starter to understand how the starting current is restricted to the desired value. For that
let’s consider the diagram given below showing all essential parts of the three point starter.
Construction of 3 Point Starter
Construction wise a starter is a variable resistance, integrated into number of sections as
shown in the figure beside. The contact points of these sections are called studs and are shown
separately as OFF, 1, 2, 3, 4, 5, RUN. Other than that there are 3 main points, referred to as
1. 'L' Line terminal. (Connected to positive of supply.)
2. 'A' Armature terminal. (Connected to the armature winding.)
3. 'F' Field terminal. (Connected to the field winding.)
And from there it gets the name 3 point starter. Now studying the construction of 3 point
starter in further details reveals that, the point 'L' is connected to an electromagnet called
overload release (OLR) as shown in the figure. The other end of OLR is connected to the lower
end of conducting lever of starter handle where a spring is also attached with it and the starter
handle contains also a soft iron piece housed on it. This handle is free to move to the other side
RUN against the force of the spring. This spring brings back the handle to its original OFF
position under the influence of its own force. Another parallel path is derived from the stud '1',
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
given to another electromagnet called No Volt Coil (NVC) which is further connected to
terminal 'F'. The starting resistance at starting is entirely in series with the armature. The OLR
and NVC acts as the two protecting devices of the starter.
Working of Three Point Starter
Having studied its construction, let us now go into the working of the 3 point starter.
To start with the handle is in the OFF position when the supply to the DC motor is switched on.
Then handle is slowly moved against the spring force to make a contact with stud No. 1. At this
point, field winding of the shunt or the compound motor gets supply through the parallel path
provided to starting resistance, through No Voltage Coil. While entire starting resistance comes
in series with the armature. The high starting armature current thus gets limited as the current
equation at this stage becomes As the handle is moved further, it goes on
making contact with studs 2, 3, 4 etc., thus gradually cutting off the series resistance from the
armature circuit as the motor gathers speed. Finally when the starter handle is in 'RUN' position,
the entire starting resistance is eliminated and the motor runs with normal speed. This is because
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
back emf is developed consequently with speed to counter the supply voltage and reduce the
armature current.
So the external electrical resistance is not required anymore, and is removed for optimum
operation. The handle is moved manually from OFF to the RUN position with development of
speed. Now the obvious question is once the handle is taken to the RUN position how is it
supposed to stay there, as long as motor is running? To find the answer to this question let us
look into the working of No Voltage Coil.
Working of No Voltage Coil of 3 Point Starter
The supply to the field winding is derived through no voltage coil. So when field current
flows, the NVC is magnetized. Now when the handle is in the 'RUN' position, soft iron piece
connected to the handle and gets attracted by the magnetic force produced by NVC, because of
flow of current through it. The NVC is designed in such a way that it holds the handle in 'RUN'
position against the force of the spring as long as supply is given to the motor. Thus NVC holds
the handle in the 'RUN' position and hence also called hold on coil.
Now when there is any kind of supply failure, the current flow through NVC is affected
and it immediately looses its magnetic property and is unable to keep the soft iron piece on the
handle, attracted. At this point under the action of the spring force, the handle comes back to
OFF position, opening the circuit and thus switching off the motor. So due to the combination of
NVC and the spring, the starter handle always comes back to OFF position whenever there is any
supply problems. Thus it also acts as a protective device safeguarding the motor from any kind
of abnormality.
Drawbacks of a Three Point Starter
The 3 point starter suffers from a serious drawback for motors with large variation of
speed by adjustment of the field rheostat. To increase the speed of the motor field resistance can
be increased. Therefore current through shunt field is reduced. Field current becomes very low
which results in holding electromagnet too weak to overcome the force exerted by the spring.
The holding magnet may release the arm of the starter during the normal operation of the motor
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
and thus disconnect the motor from the line. This is not desirable. A four point starter is thus
used.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
DC 4-POINTER STARTER
The 4 point starter like in the case of a 3 point starter also acts as a protective device
that helps in safeguarding the armature of the shunt or compound excited DC motor against the
high starting current produced in the absence of back emf at starting.
The 4 point starter has a lot of constructional and functional similarity to a three point starter, but
this special device has an additional point and a coil in its construction. This naturally brings
about some difference in its functionality, though the basic operational characteristic remains the
same. The basic difference in circuit of 4 point starter as compared to 3 point starter is that the
holding coil is removed from the shunt field current and is connected directly across the line with
current limiting resistance in series. Now to go into the details of operation of 4 point starter,
let’s have a look at its constructional diagram, and figure out its point of difference with a 3 point
starter.
Construction and Operation of Four Point Starter
A 4 point starter as the name suggests has 4 main operational points, namely
1. 'L' Line terminal. (Connected to positive of supply.)
2. 'A' Armature terminal. (Connected to the armature winding.)
3. 'F' Field terminal. (Connected to the field winding.)
4. Like in the case of the 3 point starter, and in addition to it there is, A 4th point N. (Connected
to the No Voltage Coil NVC)
The remarkable difference in case of a 4 point starter is that the No Voltage Coil is
connected independently across the supply through the fourth terminal called 'N' in addition to
the 'L', 'F' and 'A'. As a direct consequence of that, any change in the field supply current does
not bring about any difference in the performance of the NVC. Thus it must be ensured that no
voltage coil always produce a force which is strong enough to hold the handle in its 'RUN'
position, against force of the spring, under all the operational conditions. Such a current is
adjusted through No Voltage Coil with the help of fixed resistance R connected in series with the
NVC using fourth point 'N' as shown in the figure above.
Apart from this above mentioned fact, the 4 point and 3 point starters are similar in all
other ways like possessing is a variable resistance, integrated into number of sections as shown
in the figure above. The contact points of these sections are called studs and are shown
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
separately as OFF, 1, 2, 3, 4, 5, RUN, over which the handle is free to be maneuvered manually
to regulate the starting current with gathering speed.
Now to understand its way of operating lets have a closer look at the diagram given
above. Considering that supply is given and the handle is taken stud No.1, then the circuit is
complete and line current that starts flowing through the starter. In this situation we can see that
the current will be divided into 3 parts, flowing through 3 different points.
1. 1 part flows through the starting resistance (R1+ R2+ R3…..) and then to the armature.
2. A 2nd part flowing through the field winding F.
3. And a 3rd part flowing through the no voltage coil in series with the protective resistance R.
So the point to be noted here is that with this particular arrangement any change in the
shunt field circuit does not bring about any change in the no voltage coil as the two circuits are
independent of each other. This essentially means that the electromagnet pull subjected upon the
soft iron bar of the handle by the no voltage coil at all points of time should be high enough to
keep the handle at its RUN position, or rather prevent the spring force from restoring the handle
at its original OFF position, irrespective of how the field rheostat is adjusted.
This marks the operational difference between a 4 point starter and a 3 point starter. As
otherwise both are almost similar and are used for limiting the starting current to a shunt wound
DC motor or compound wound DC motor, and thus act as a protective device.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Working principle of 4-point starter:
The 4-point starter like in the case of a 3-point starter also acts as a protective device that
helps in safeguarding the armature of the shunt or compound excited DC motor against the high
starting current produced in the absence of back emf as starting. The 4-point starter has a lot of
constructional and functional similarity to a three point starter, but this special device has an
additional point and a coil in its construction. This naturally brings about some difference in its
functionality, though the basic operational characteristic remains the same. The basic difference
in circuit of 4-point starter as compared to 3-point starter is that the holding coil is removed from
the shunt field current and is connected directly across the line with current limiting resistance in
series. Now to go into the details of operation of 4-point starter, have a view of constructional
diagram and figure out its point of difference with a 3-point starter.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
DRUM CONTROLLER STARTER
For winch and crane motors where frequent starting, stopping, reversing and speed
variations are necessary, drum type controllers are used. They are called controllers because they
can be left in the circuit for any length of time. In addition to serving their normal function of
starters, they also used as speed controllers.
Series and cumulative compound motors are often used on cranes, elevators, machine tools, and
other devices where the motor is under the direct control of an operator and where frequent
starting, varying speed, stopping, and reversing are necessary. A manually operated controller
that is more rugged than a starting rheostat is used in these applications. This starting rheostat is
called a drum controller.
A typical drum controller is illustrated in Figure 22–10. Inside the switch is a series of contacts
mounted on a movable cylinder. These contacts, insulated from the cylinder and from each other,
are the movable contacts. There is another series of contacts, located inside the controller, called
stationary contacts. These contacts are arranged to make contact with the movable contacts as the
cylinder is rotated. On top of the drum controller is a handle that is keyed to the shaft for the
movable cylinder and contacts. This handle can be moved in either a clockwise or a
counterclockwise direction, providing a range of speed control in either direction or rotation.
Once set, a roller and notched- wheel arrangement keeps the cylinder and movable contacts
stationary until the handle is turned by the operator.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
A schematic of a drum controller having two steps of resistance is shown in Figure 22–11. In this
wiring diagram, the contacts are shown in a flat position to make it easier to trace connections.
For operating in the forward direction, the movable contacts on the right connect with the center
stationary contacts. For operation in the reverse direction, the movable contacts on the left touch
the stationary contacts in the center.
There are three forward positions and three reverse positions in which the controller handle can
be set. In the first forward position, all resistance is in series with the armature. The circuit for
the first forward position is traced as follows:
1. Movable fingers A, B, C, and D contact the stationary contacts 7, 5, 4, and 3.
2. The current path is from 7 to A, from A to B, from B to 5, and then to armature terminal A1.
3. From A1, the current path is through the armature winding to terminal A2, then to stationary
contact 6, and then to stationary contact 4.
4. From contact 4, the current path is to contact C, to D, and then to 3.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
5. From 3, the current path is through the entire armature resistor, through the series field, and
then back to the line.
In the second forward position, part of the resistance is cut out by the connection from D to E.
The third forward position bypasses all resistance and puts the armature circuit directly across
the source voltage.
In the first reverse position, all resistance is again inserted in series with the armature. Figure 22–
12 illustrates the first position of the controller for the reverse direction.
The current in the armature circuit is reversed. However, the current direction in the shunt and
series fields is the same as for the forward direction. As shown earlier, changing the direction of
the current in only the armature changes the direction of rotation. In the second position, part of
the resistance circuit is cut out. The third reverse position cuts out all resistance and puts the
armature circuit directly across line voltage.
There are more elaborate drum controllers with more positions and a greater control of speed.
However, they all use practically the same circuit arrangement.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
MAGNETIZATION CHARACTERISTICS OF DC SHUNT GENERATOR
Aim:
To draw the magnetization characteristics or open circuit characteristics curve of a dc
shunt generator and to determine its critical field resistance.
Name plate details:
Details Motor Generator
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-1/2 A MC 02
2. Voltmeter 0-300 V MC 01
3. Rheostat 0-350 Ohms / 2A WW 02
4. Tachometer 0-1000 rpm Digital 01
5. SPST - - 01
6. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram
2. Initially keep the motor field rheostat in minimum position and generator field rheostat in
maximum position
3. Close the DPST switch and start motor slowly with the help of starter.
4. Adjust the motor field rheostat till rated speed of motor is obtained.
5. Note down the voltmeter and ammeter reading and close the SPST.
6. Now decrease generator field resistance in steps of field current and note down the
corresponding voltmeter reading till the generated emf is 120% of rated value.
7. Increase the generator field resistance in steps of field current and note down the
corresponding voltmeter reading till the field current zero.
8. Bring back rheostats to their initial position and open DPST.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Circuit Diagram:
Tabular column:
S. NO Field current
If (Amperes)
Generated EMF in Volts
Average Eg
in Volts
(If Increasing) (If Decreasing)
Model Graph:
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Precautions:
1. Before opening the DPST switch ensure that rheostats are in their original position.
2. Loose connections are to be avoided.
3. Avoid parallax error.
Result:
Conclusion:
Viva questions:
1. Define critical field resistance.
2. How do you get the maximum voltage to which the generator builds up from OCC?
3. What does the flat portion of OCC indicate?
4. Why OCC does not start from origin?
5. Why is Rf > Ra in dc shunt machine?
6. How do you create residual magnetism if it is wiped out?
7. Why does the OCC differ for decreasing and increasing values of field current?
8. Under what conditions does the DC shunt generator fail to self - excite?
9. OCC is also known as magnetization characteristic, why?
10. How do you check the continuity of field winding and armature winding?
11. How do you make out that the generator is DC generator without observing the name plate?
12. Does the OCC change with speed?
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
LOAD TEST ON DC SHUNT GENERATOR
Aim:
To perform on load test on DC Shunt generator and to draw its performance
characteristics
Name plate details:
Details Motor Generator
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-10/20 A, 0-1/2 A MC 02
2. Voltmeter 0-300 V MC 01
3. Rheostat 0-350 Ohms / 2A WW 02
4. Tachometer 0-1000 rpm Digital 01
5. Load rheostat 4 KW - 01
6. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram
2. Initially keep the motor field rheostat in minimum position and generator field
rheostat in maximum position
3. Close the DPST switch and start motor slowly with the help of starter.
4. Adjust the motor field rheostat till rated speed of motor is obtained.
5. Now decrease generator field resistance till voltmeter decreases rated EMF.
6. Note down readings of meters at no load.
7. Increase load in steps and note down voltmeter and ammeter readings till generator
generates rated current.
8. Switch off load bring back rheostats to their initial position and open DPST.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Circuit Diagram:
Tabular column:
S. No. Voltage V in
volts
Load current
IL in Amps
Field current
ISH in Amps
Armature
current IA in
Amps
Generated
EMF EG in
volts
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Model Graph:
Precautions:
1. Before opening the DPST switch ensure that rheostats are in their original position.
2. Loose connections are to be avoided.
3. Avoid parallax error.
Result:
Conclusion:
Viva questions:
1. Specify the applications of DC shunt generators.
2. Differentiate between DC shunt Motor and DC shunt generator.
3. Which method is suitable for testing of high rating DC generator?
4. Why the terminal voltage decreases when load is increased on the generator?
5. Why is the generated EMF not constant even though the field circuit resistance is kept
unaltered?
6. Find out the voltage drop due to full load armature reaction?
7. State the conditions required to put the DC shunt generator on load.
8. How do you compensate for the armature reaction?
9. What happens if shunt field connections is reversed in the generator?
10. The EMF induced in armature conductors of DC shut generator is AC or DC?
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
LOAD TEST ON DC SERIES GENERATOR
Aim:
To perform on load test on DC Series generator and to draw its performance
characteristics
Name plate details:
Details Motor Generator
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-10/20 A MC 01
2. Voltmeter 0-300 V MC 01
3. Rheostat 0-350 Ohms / 2A WW 01
4. Tachometer 0-1000 rpm Digital 01
5. Load rheostat 4 KW - 01
6. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram
2. Initially keep the motor field rheostat in minimum position and switch on load and
apply minimum load on generator
3. Close the DPST switch and start motor slowly with the help of starter.
4. Adjust the motor field rheostat till rated speed of motor is obtained.
5. Note down readings of volt meter and ammeter.
6. Increase load in steps and note down voltmeter and ammeter readings till rated
current.
7. Reduce the load to initial position, bring back the rheostats to their initial position and
open DPST.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Circuit Diagram:
Tabular column:
S. No. Voltage V in
volts
Load current
IL in Amps
Generated
EMF EG in
volts
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Model Graph:
Precautions:
1. Minimum load should be applied generator before switching ON OFF the supply
2. Before opening the DPST switch ensure that rheostats are in their original position.
3. Loose connections are to be avoided.
4. Avoid parallax error.
Result:
Conclusion:
Viva questions:
1. In what way does the series generator differ fundamentally from shunt generator?
2. Why does a series generator have rising characteristics?
3. Why the series generators will only built up when load switch is on?
4. Why the series generator used as voltage booster in transmission system? 5. What are the applications of DC series generator?
6. To conduct the test on DC series generator, can we use any other prime mover other than DC
shunt motor?
7. Why DC series motor should not start without any load?
8. State the applications of the series generator.
9. State voltage builds up conditions of a series generator.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
LOAD TEST ON DC COMPOUND GENERATOR
Aim:
To perform on load test on DC compound generator and to draw its performance
characteristics
Name plate details:
Details Motor Generator
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-10/20 A, 0-1/2 A MC 02
2. Voltmeter 0-300 V MC 01
3. Rheostat 0-350 Ohms / 2A WW 02
4. Tachometer 0-1000 rpm Digital 01
5. Load rheostat 4 KW - 01
6. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram
2. Initially keep the motor field rheostat in minimum position and generator field
rheostat in maximum position
3. Close the DPST switch and start motor slowly with the help of starter.
4. Adjust the motor field rheostat till rated speed of motor is obtained.
5. Now decrease generator field resistance till voltmeter decreases rated emf.
6. Note down readings of meters at no load.
7. Increase load in steps and note down voltmeter and ammeter readings till generator
generates rated current.
8. Switch off load bring back rheostats to their initial position and open DPST.
9. Connect the generator for differential compounding by interchanging the series field
terminals and repeat the above procedure.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Circuit Diagram:
Tabular column:
S. No. Voltage V in
volts
Load current
IL in Amps
Field current
ISH in Amps
Armature
current IA in
Amps
Generated
EMF EG in
volts
Model Graph:
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Precautions:
1. Before opening the DPST switch ensure that rheostats are in their original position.
2. Loose connections are to be avoided.
3. Avoid parallax error.
Result:
Conclusion:
Viva questions:
1. What do you understand from load curves?
2. Which causes the drop between internal & external characteristics?
3. A cumulative compound generator is generating full load, what will happen if its series field
winding gets short – circuited?
4. Explain the difference between cumulative and differential compound generators. 5. Where you can use DC Compound Generator?
6. Comment on the shape of load current Vs speed curve of the differential compounded generator.
7. How do you reverse the terminal voltage of an over compounded short shunt generator without effecting the over compounding?
8. Mention the applications of differential compound generator.
9. Mention the applications of over compound generator.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
HOPKINSON’S TEST ON DC SHUNT MACHINES
Aim:
To perform on Hopkinson’s test on dc shunt generator and to determine the efficiency of
both motor and generator.
Name plate details:
Details Motor Generator
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-10/20 A, 0-1/2 A MC 04
2. Voltmeter 0-300 V MC 03
3. Rheostat 0-350 Ohms / 2A WW 02
4. Tachometer 0-1000 rpm Digital 01
5. Load rheostat 4 KW - 01
6. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram
2. Initially keep the motor field rheostat in minimum position and generator field
rheostat in maximum position
3. Close the DPST switch and start motor slowly with the help of starter.
4. Adjust the motor field rheostat till rated speed of motor is obtained.
5. Now decrease generator field resistance till voltmeter decreases rated emf.
6. If the voltmeter reads zero then close parallel switch
7. Load the generator in steps of load current either by decreasing field resistance of
generator or by increasing field resistance of motor
8. Note down the reading of meters for each load and measure the corresponding speed
9. Reduce the excitation of generator by increasing the field resistance of generator and
open switch
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
10. Bring back the rheostat to its initial position and open the DPST switch
Armature field resistance / field resistance
i. Connect the circuit as shown
ii. Note down the readings of voltmeter and ammeter by varying
resistance.
Circuit Diagram:
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Tabular column: G
ener
ato
r
effi
cien
cy
Mo
tor
Eff
icie
ncy
Str
ay l
oad
loss
es W
Gen
erat
or
fiel
d
curr
ent
If
Gen
erat
or
curr
ent
Ig
Gen
erat
or
Vo
ltag
e V
Mo
tor
fiel
d
curr
ent
Ish
m
Mo
tor
curr
ent
Ia
Vo
ltag
e V
S.
No
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Model Graph:
Precautions:
1. Before opening the DPST switch ensure that rheostats are in their original position.
2. Take excessive care while closing the parallel switch the voltmeter must read zero for
switch to be closed.
3. Loose connections are to be avoided.
4. Avoid parallax error.
Result:
Conclusion:
Viva questions:
1. Hopkinson’s test is a ………..test.
2. What are the disadvantages of this test?
3. What are heat run tests? 4. What are the advantages of the test?
5. Can you explain this test be applied to compound machines?
6. When two DC machines are paralleled as is done in this test, which machine acts as generator and
which machine acts as motor?
7. Hopkinson’s test on DC machines is conducted at ….load.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
FIELD TEST ON DC SERIES MACHINES
Aim:
To determine the efficiency of two given dc series machines which are mechanically
coupled.
Name plate details:
Details Motor Generator
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-10/20 A MC 02
2. Voltmeter 0-300 V MC 02
3. Tachometer 0-1000 rpm Digital 01
4. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram.
2. Apply minimum load on generator
3. Close DPST switch and start motor slowly with the help of starter.
4. Increase load in steps and note down corresponding voltmeter and ammeter reading
till rated current.
5. Decrease load in steps put minimum load on generator and open DPST.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Circuit Diagram:
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Tabular column: M
ote
r
effi
ecie
n
y
Ou
tpu
t
po
wer
Inp
ut
po
wer
Gen
erat
or
effi
ecie
nc
y
Ou
tpu
t
po
wer
Inp
ut
po
wer
Co
nst
ant
loss
es
Lo
ad
curr
ent
IL
Lo
ad
vo
ltag
e
VL
Cu
rren
t
I1
Vo
ltag
e
V1
S.
No
.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Model Graph:
Precautions:
4. Minimum load should be applied on generator before switching ON/OFF the supply.
5. Loose connections are to be avoided.
6. Avoid parallax error.
Result:
Conclusion:
Viva questions:
1. Why the field of generator connected to motor?
2. What are the applications of D.C series generator?
3. Why the series generator used as voltage booster in transmission system? 4. Why Series motor should not start at no load?
5. What is the main advantage of this test?
6. Is it possible to conduct Field test on any another DC machine
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
SPEED CONTROL OF DC SHUNT MOTOR
Aim:
To draw the speed characteristics of dc shunt motor by field control method and armature
control.
Name plate details:
Details Motor
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-1/2 A MC 02
2. Voltmeter 0-300 V MC 01
3. Rheostat 0-350 Ohms / 2A WW 02
4. Tachometer 0-1000 rpm Digital 01
6. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram
2. Initially keep the motor field rheostat in minimum position.
3. Close the DPST switch and start motor slowly with the help of starter.
4. For the filed control method adjust the armature rheostat in position so that voltmeter
reads a selected value and keep it constant
5. Increase the field resistance thereby decreasing the field current in steps and note down
the readings of field current and speed for each step
6. For armature control method adjust field current at selected value keep it constant.
7. Decrease the armature resistance in steps of armature voltage and note down the
voltmeter reading and speed for each step
8. Bring back rheostat to its initial position and open DPST switch.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Circuit Diagram:
Tabular column:
Field control method
Eb
Eb
Field current (A) speed in rpm Field current speed in rpm
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Armature control method
If
If
Eb(V) N(rpm) Eb(V) N (rpm)
Model Graph:
Precautions:
1. Before opening the DPST switch ensure that rheostats are in their original position.
2. Loose connections are to be avoided.
3. Avoid parallax error.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Result:
Conclusion:
Viva questions:
1. Explain why the graph of armature speed control of motor is linear?
2. Comment on the efficiency calculated by this method.
3. Why do you need a starter in a dc motor?
4. What is meant by rated speed?
5. Can we start the dc shunt motor and series motor without load?
6. What is meant by speed regulation?
7. Can we operate a dc motor an ac supply?
8. What are the other methods of controlling the speed of dc shunt motor?
9. How do you change the direction of rotation of a D.C. motor?
10. What is the disadvantage of using armature control of speed on load?
11. What are the limitations of shunt field control?
12. Can we conduct continuity test on ac supply?
13. While running if the field winding gets disconnected, what will happen?
14. What is the shape of the curve of field control of method motor speed? Explain why is it so?
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
SWINBURNE’S TEST ON DC SHUNT MOTOR
Aim:
To perform on Swinburne’s test on a given DC Shunt machine and to predetermine its
efficiency at any desired load both as motor and generator.
Name plate details:
Details Motor
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-10/20 A, 0-1/2 A MC 02
2. Voltmeter 0-300 V MC 01
3. Rheostat 0-350 Ohms / 2A WW 01
4. Tachometer 0-1000 rpm Digital 01
6. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram
2. Initially keep the motor field rheostat in minimum position.
3. Close the DPST switch and start motor slowly with the help of starter.
4. Adjust the motor field rheostat till rated speed of motor is obtained.
5. Note down readings of meters at no load.
6. Bring back rheostat to its initial position and open DPST.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Circuit Diagram:
Tabular column:
S. No. Voltage V in
volts
Line current
IL in Amps
Field current
ISH in Amps
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Model Graph:
Precautions:
1. Before opening the DPST switch ensure that rheostats are in their original position.
2. Loose connections are to be avoided.
3. Avoid parallax error.
Result:
Conclusion:
Viva questions:
1. Will the values deduced from the Swinburne’s method exactly coincide with the values realized
by direct loading on the machine? Why?
2. Why are the constant losses calculated by this method less than the actual losses?
3. Can we conduct Swinburne’s test on dc series motor?
4. What are the drawbacks of Swinburne’s test?
5. Why Swinburne’s is used to find efficiency of high rating motors?
6. How you can say that the wattmeter reading in the experiment is constant losses?
7. Why constant losses are constant irrespective of load?
8. Advantage of this test.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
BRAKE TEST ON DC COMPOUND GENERATOR
Aim:
To perform brake test on DC compound motor and to draw its performance
characteristics
Name plate details:
Details Motor Generator
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-10/20 A MC 01
2. Voltmeter 0-300 V MC 01
3. Rheostat 0-350 Ohms / 2A WW 01
4. Tachometer 0-1000 rpm Digital 01
5. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram
2. Initially keep the motor field rheostat in minimum position.
3. Check whether the belt on pulley is free so that there is no load on the motor.
4. Close the DPST switch and start motor slowly with the help of starter.
5. Adjust the motor field rheostat till rated speed of motor is obtained.
6. Note down readings of ammeter, voltmeter and speed at no load
7. Apply the load on pulley gradually in steps of input current till the rated current of
motor by tightening the belt around it.
8. Note down the voltmeter, ammeter and spring balance readings and measure the
speed for each step.
9. Remove load bring back rheostat to its initial position and open DPST switch.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Circuit Diragram:
Tabular column:
S. No. Voltage V in
volts
Load current
IL in Amps
Field current
ISH in Amps
Armature
current IA in
Amps
Generated
EMF EG in
volts
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Model Graph:
Precautions:
1. Cool the pulley while the experiment is performed.
2. Before opening the DPST switch ensure that rheostats are in their original position.
3. While measuring radius of pulley, effective radius must be considered.
4. Loose connections are to be avoided.
5. Avoid parallax error.
Result:
Conclusion:
Viva questions:
1. Differentially compounded after reversal?
2. Mention the applications of the cumulative compounded motor?
3. Which type of DC starter is used to start the compound motor?
4. Why differentially compounded motors are not in common use?
5. What is the speed regulation of DC motor?
6. What is Difference between Shunt and compound motors?
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
BRAKE TEST ON DC SHUNT MOTOR
Aim:
To perform on brake test on DC Shunt motor and to draw its performance characteristics
Name plate details:
Details Motor Generator
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-10/20 A MC 01
2. Voltmeter 0-300 V MC 01
3. Rheostat 0-350 Ohms / 2A WW 01
4. Tachometer 0-1000 rpm Digital 01
6. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram
2. Initially keep the motor field rheostat in minimum position and generator field
rheostat in maximum position
3. Check whether the belt on pulley is free so that there is no load on the motor
4. Close the DPST switch and start motor slowly with the help of starter.
5. Adjust the motor field rheostat till rated speed of motor is obtained.
6. Note down readings of ammeter and voltmeter at no load.
7. Apply the load on pulley gradually in steps of input current till the rated current of
motor is obtained by tightening the belt around it
8. Note down the voltmeter, ammeter and spring balance readings and measure the
speed for each step.
9. Remove load bring back rheostat to its initial position and open DPST switch.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Circuit Diagram:
Tabular column:
Voltage
V
Current
IL
LOAD
S1 S2
SPEED
IN RPM
TORQUE INPUT
POWER
O/P POWER EFFICIEN
CY
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Model Graph:
Precautions:
1. Cool the pulley while the experiment is performed.
2. Before opening the DPST switch ensure that rheostats are in their original position.
3. Loose connections are to be avoided.
4. Avoid parallax error.
Result:
Conclusion:
Viva questions:
1. Why did you use a 3-point starter for starting DC shunt motor?
2. What is the efficiency range of DC motor?
3. Where can you use the DC shunt motor?
4. What is the starting torque?
5. If starter is not available, how can you start DC motor?
6. Why is it considered as a constant speed motor?
7. Why brake test is used to find the efficiency of DC motor?
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
RETARDATION TEST DC SHUNT MOTOR
Aim:
To separate the mechanical and iron losses of the given dc shunt machine.
Name plate details:
Details Motor Generator
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-10/20A, 0-1/2 A MC 02
2. Voltmeter 0-300 V MC 01
3. Rheostat 0-350 Ohms / 2A WW 02
4. Tachometer 0-1000 rpm Digital 01
5. SPST - - 01
6. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram.
2. Keep the switches SW1 and SW2 in ON position and keep switch SW3 in OFF
position.
3. Gradually raise the motor speed up to 100 rpm above the rated speed.
4. Switch OFF SW1 and press stop watch simultaneously. Note down the time taken
until the motor speed falls to 100 rpm below the rated speed.
5. Stop the motor.
6. Switch ON SW1 and SW2 switches and keep SW3 in OFF position.
7. Start the motor again and raise the speed up to 100 rpm above the rated speed.
8. Switch OFF SW2 switch and press stop watch simultaneously. Note down the time
taken till the motor speed falls to 100 rpm below the rated speed.
9. Stop the motor.
10. Switch on SW1 and SW2 switches and keep SW3 in OFF position.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
11. Start the motor again and raise the speed up to 100 rpm above the rated speed.
12. Note down Va and Ia readings
13. Switch off SW2 and switch on SW3 switch and press stop watch simultaneously.
14. Note down the time taken till the motor speed falls to 100 rpm below the rated speed.
15. Note down Va and Ia readings at both the speeds.
16. Stop the motor
Circuit Diagram:
Tabular column:
S1 CLOSE, S2 OPEN
S.NO V (VOLTS) If (A) TIME
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
S1 OPEN, S2 CLOSE
S.NO V (VOLTS) If (A) TIME
Precautions:
4. Before opening the DPST switch ensure that rheostats are in their original position.
5. Loose connections are to be avoided.
6. Avoid parallax error.
Result:
Conclusion:
Viva questions:
1. What is another name for Retardation test?
2. What is the difference between Retardation and Swinburne test?
3. The values obtained from this test are Pessimistic or Optimistic?
4. Is it possible to conduct Retardation test on DC series machines?
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
SEPERATION OF LOSSES IN DC SHUNT MOTOR
Aim:
To obtain separately hysteresis, eddy current, friction and windage losses of a given
motor.
Name plate details:
Details Motor Generator
Rating
Voltage
Current
Speed
Apparatus:
S. No Apparatus Range Type Quantity
1. Ammeter 0-10/20A, 0-1/2 A MC 02
2. Voltmeter 0-300 V MC 01
3. Rheostat 0-350 Ohms / 2A WW 02
4. Tachometer 0-1000 rpm Digital 01
6. Connecting wire - - required
Procedure:
1. Make the connections as per the circuit diagram.
2. Initially keep the motor field rheostat in minimum position.
3. Increase the armature voltage till the speed is about 200 rpm more than the rated
value
4. Now, gradually decrease the armature voltage, and note down the values of armature
voltage, armature current and speed.
5. Repeat the experiment at some other field current.
6. Measure the armature resistance separately, after disconnecting the circuit.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Circuit Diagram:
Tabular column:
Full excitation: Field Current=0.9A
S. No Armature
Voltage
Armature
current
Speed W=VIa-Ia2Ra
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Reduced excitation: Field Current=0.6A
S. No Armature
Voltage
Armature
current
Speed W=VIa-Ia2Ra
Model Graph:
Precautions:
7. Before opening the DPST switch ensure that rheostats are in their original position.
8. Loose connections are to be avoided.
9. Avoid parallax error.
Result:
Conclusion:
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Viva questions:
1. Where are eddy current losses occurring in a D.C. Machine?
2. How are the magnetic losses minimized?
3. How is brush contact resistance loss taken into consideration in practice?
4. Give the expression for hysteresis loss?
5. Differentiate MNA and GNA?
6. Which test gives us stray losses?
7. How Hysteresis losses occur in a D.C. Machine?
8. What is the effect of armature reaction?
9. How do you minimize cross magnetizing effect of armature reaction?
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
Viva questions
1. Why, the magnetic losses calculated by Swinburne’s test are different from the actual value?
2. Comment on the accuracy of Swinburne’s test over other methods.
3. What is the condition required for maximum efficiency?
4. State the applications of a D.C. shunt generator.
5. Explain the armature reaction.
6. Explain the principle of a D.C. motor.
7. For the same Ia, why the generator is having more efficiency than the motor?
8. Which winding has low resistance Shunt/Armature?
9. Give the reasons, why the voltage of D.C. generator drops as the load is applied?
10. Define the armature reaction. Explain its effect on the internal
11. What do you understand from the external characteristic of D.C. shunt generator?
12. How, the objectionable drooping characteristics of D.C. shunt generator can be improved?
13. If you take the demagnetizing effect of the armature reaction into consideration show the
effects of speed and degree of saturation on the characteristic of a D.C. shunt generator.
14. Shunt field plays the dominating role in a compound generator. Explain.
15. What are the differences between cumulative and differential compound generators?
16. Differentiate between the under-compound, flat-compound, and over-compounded
generators.
17. A cumulative compound generator is delivering at full load, if its shunt field gets opened,
what will happen? If its series field gets short circuited, what will happen?
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
18. Two D.C. generators (one cumulatively and other differentially compounded) are delivering
the same load ampere at same voltage level. How will the terminal voltage change when the
above loads are switched off?
19. What is the effect of speed on the degree of compounding; if the no load voltage is same in
each case?
20. What are the effects of commutating poles on the characteristic of both types of generators?
21. How, the number of turns for a desired degree of compounding may be determined
experimentally?
22. Discuss the performance of a D.C. compound generator (both cumulative and differential)
using one field winding at a time.
23. Why the speed falls as the load increases for a D.C. shunt motor?
24. When is the efficiency of the motor, maximum?
25. What will happen when a D.C. shunt motor is started with load?
26. What is back electro motive force in a D.C. motor?
27. What is the effect on speed, if part of the field winding is shorted?
28. When will the motor be able to draw maximum power?
29. Explain the process of commutation.
30. While running a D.C. shunt motor, if the field winding is disconnected, what will happen?
31. Why, the speed is maintained constant during the experiment on a generator?
32. What is residual magnetism?
33. Explain hysterisis phenomena.
34. Define coercive force.
35. Explain magnetization curve.
Electrical Machines-I lab manual
Anurag College of Engineering, Aushapur Department of EEE
36. Define critical field resistance.
37. Define critical speed.
38. Explain the buildup of voltage in a self excited D.C. shunt generator.
39. What are the conditions required to build up the voltage in a D.C. generator?
40. What will happen if the armature rheostat is set to zero (i.e., maximum Va) and field
circuit resistance kept at high (i.e., minimum If) at the time of starting?
41. What will happen if A.C. supply is given to a D.C. motor?
42. Why, a starter is used for starting a D.C. motor?
43. How do you change the direction of rotation of a D.C. shunt motor?
44. What would be the direction of rotation if both the field windings and armature connections
are reversed?
45. What are the limitations for shunt field control method?
46. Why, a series generator characteristic is called a raising characteristic?
47. List some applications of it applications.
48. Draw speed ~ torque characteristics of a series motor and hence try to co-relate with the load
characteristics of the generator.
49. How does the speed of a prime mover affect the generator characteristics?
50. Why, the retardation test is more appropriate for large machines?