Module 7 Introduction to 2009 PEC I Module 8 Grounded and Ungrounded System Module 9 - Fire Pumps
Jaime V. Mendoza, PEE, MTM Member Board of Electrical Engineering Chairman Distribution Management Committee, ERC
2
Module 7 Introduction to 2009 Philippine Electrical Code Part IIntroduction Purpose Basic Code rules, Important Definitions Why do Code rules changes? Requirements for Electrical Installations Working Space around Electrical Equipment Electrical Shock & Potential Difference
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
3
Safe Electrical Installations?
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
4
2009 Philippine Electrical CodeIt is NOT a textbook. It gives NO background, reasons, application or illustration of rules and regulations set down in the Code. The code is more of a catalogue of rules for an electrical installation. The Code definition of term is NOT the same as a definition for the same word in a standard dictionary.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
5
2009 Philippine Electrical CodeHistorical BackgroundThe first documented case of a Code as a requirement of rules was published on 16th Nov. 1881 entitled The Dangers of Electric Lighting. The first NEC was developed in 1897, eighteen after the invention of incandescent light bulb by Thomas A. Edison. Since 1911, the NFPA of Quincy, Massachussets, has been responsible for the maintenance and publication of the NEC. Regularly revised (every three years) to reflect the evolution of products, materials, and installation techniques. 21 Separate Committee, each consisting of 15-20 persons. Members of each committee meet several times, discuss proposed changes, accepting some and rejecting others, and rewrite (as required) the sections of the Code that were assigned to their committee. The 2009 PEC used the 2005 Edition of the National Electrical Code as referenced Code.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
6
2009 Philippine Electrical CodePurpose The primary objective of the code is to establish basic materials quality and electrical works standards for the safe use of electricity for light, heat, power, communications, signaling and for other purposes.Practical safeguarding of persons and property from hazards arising from the use of electricity COMPLIANCE TO THE PEC WILL ENSURE SAFETY AND PREVENT ELECTRICAL FIRESCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
7
2009 Philippine Electrical CodeIntentionNOT intended as a design specification or an instruction manual for untrained persons. The term untrained persons can be interpreted to mean anyone who does NOT have an understanding of electricity and electrical construction. It can also mean that the Code assumes a person reading or studying it knows and understands basic Ohm Law, Kirchoffs Law, the triangle of fire, etc.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
8
Qualified Person
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
9
2009 Philippine Electrical CodeThe PEC is a safety standard, NOT a design guide. Electrical designs must comply with the requirements of PEC to ensure safety. Energy management, maintenance, and power quality issues arent within the scope of the PEC. Consideration should be given for future expansion of electrical systems but this is not a Code requirement.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Standard - PEC
Electrical Safety Seminar for Jollibees Personnel
10
2009 Philippine Electrical CodeScopeCovered- the installation of electrical conductors, equipment, and raceways, monitoring, signaling, and communications conductors, equipment, and raceways; and optical fibers and raceways installed within or on, to from: Public and private buildings. Electric Gen. Plants Industrial plants Transformer stations Permanent & Temporary S/s Airfields Railways switchyard Yards, carnival, parks, parking and other lots Quarries and mines Watercraft Dockyards Trailers Mobile Homes and recreational vehicles Offshore facilities
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
11
2009 Philippine Electrical CodeNot coveredInstallations in railway rolling stock, aircraft, or automotive vehicles Installations of railways for generation, transformation, transmission, or distribution of power used exclusively for operation of transmission stock
InterpretationThe Board of Electrical Engineering shall render the final decision in the interpretation of any portion of the PEC, in case of controversy.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
12
2009 Philippine Electrical CodeClassification of Code Rules 1. Wiring Design Rules 2. Installation Rules 3. Manufacturing Rules
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
13
2009 Philippine Electrical CodeCLASSIFICATION OF CODE RULES Wiring design rules used to determine sizes and rating of circuit conductors and devices. Example:1. Branch circuit conductors supplying a single motor shall have an ampacity not less than 125% of the full-load current. Section 4.30.2.2 2. The disconnecting means for motor circuits shall have an ampere rating of at least 115% of the full-load current rating of the motor. Section 4.30.10.10(a)Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
14
2009 Philippine Electrical CodeCLASSIFICATION OF CODE RULES
Installation rules Example:1. A disconnecting means shall be located within sight from the motor controller. Section 4.30.102 2. In class II Division I Locations, motors, generators, and other rotating electric machinery shall be dust ignition proof or totally enclosed pipe ventilated and shall be approved for class II locations. Sections 5.02.8Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
15
2009 Philippine Electrical CodeCLASSIFICATION OF CODE RULESManufacturing rules Example: Section 4.30.1.7 A motor shall information: be marked with the following
1) Manufacturers Name 2) Rated Volts and Full-load Amperes 3) Rated Frequency and Number of Phases, if an alternating current motor, etc. 4) Rated full-load speedCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
16
2009 Philippine Electrical Code
Various Categories of the Code Rules which apply in a Motor and the CircuitsCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
17
Components that Create a Fire or Explosion
In the Installation Rules , one element of the Triangle of Fire is removed to make the installation safe.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
18
2009 Philippine Electrical CodeWhy do Code Rules Change?
Existing provisions became unsafe New technologies New products New methods or techniques(needs for CPE)Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
19
2009 Philippine Electrical CodeWhy do Code Rules Changes?
Existing provisions became unsafe
w/ Adaptor
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
20
2009 Philippine Electrical CodeWhy do Code Rules Changes?
Existing provisions became unsafe
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
21
2009 Philippine Electrical CodeWhy do Code Rules Changes?
New technologies PVC Polyvinyl Chloride Conduit Non-metallic Conduit equipment grounding conductors
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
22
2009 Philippine Electrical CodeWhy do Code Rules Changes?
New productsGFCI and AFCIa) Dwelling Units (GFCI) 1. Bathrooms 2. Garages 3. Outdoors 4. Crawl spaces at or below grade level 5. Unfinished basements 6. Kitchens for countertop appliances 7. Wet bar sinks
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
23
2009 Philippine Electrical CodeWhy do Code Rules Changes?
New methods or techniquesPlywood
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
24
2009 Philippine Electrical CodeType of Changes 1. New Provision/Definition 2. Revision 3. Relocated 4. Reorganization 5. Universal Change 6. Deletion (310.5)
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
25
2009 Philippine Electrical CodeNew DefinitionsAHJ Authority Having Jurisdiction Bonding Jumper, System Coordination (Selective) Guest Rooms Guest Suite Handhole EnclosureCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
26
2009 Philippine Electrical CodeNew Provision2.10.1.8(b)(2) GFCI Protection Other than Dwelling Commercial and institutional kitchens for the purposes of this section, a kitchen is an area with a sink and permanent facilities for food preparation and cooking. (Culinary Schools)
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
27
2009 Philippine Electrical CodeNew Provision2.10.1.8(b)(5) GFCI Protection Other than Dwelling (5)Outdoor , where installed to comply with 2.10.3.14 Heating, Airconditioning, and Refrigeration Outlet
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
28
2009 Philippine Electrical CodeRevised -definitionDwelling Unit one or more rooms for the use of one or more persons as a housekeeping unit with space for eating, living, sleeping, and permanent provisions for cooking and sanitation. PEC 2000 Dwelling Unit a single unit, providing complete and independent living facilities for one or more persons, including permanent provisions for living, sleeping, cooking, and sanitation. (PEC 2009)
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
29
2009 Philippine Electrical CodeRevised2.10.1.8(a)(8) GCFI Protection Laundry, utility, and wet bar sinks where the receptacles are installed to serve the countertop surfaces and are located within 1.8 m (6 ft) of the outside edge of the sink. Laundry, utility, and wet bar sinks where the receptacles are installed within 1.8 m (6 ft) of the outside edge of the sink.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
30
2009 Philippine Electrical CodeRelocatedSolidly Grounded PEC 2000 Grounded, Solidly PEC 2009
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
31
Reorganization Article 2.20 Branch-Circuit, Feeder, and Service Calculations2000 Article 2.20 Part I. General II. Feeders and Services Sections 2.20.1.1- 4 2.20.2.1 - 14 2009 Article 2.20 Part I. General Sections 2.20.1.1 -5
II. Branch Circuit 2.20.2.1 - 7 Load Calculations III. Feeder and Service Load Calculations 2.20.3.1 - 23
III. Optional 2.20.3.1 - 7 Calculations for Computing Feeder and Service Loads IV. Method for 2.20.4.1 - 2 Computing Farm Loads
IV. Optional Feeder2.20.4.1 - 9 And Service Load Calculations V. Farm Calculation 2.20.5.1- 4
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
32
2009 Philippine Electrical CodeUniversal Change A universal change throughout the Code is the replacement of computed load and demand load with calculated load. For example, the term demand load is being replaced with calculated load to improve clarity and to reduce confusion, especially when related to calculated load and demand factor. The term calculated load includes demand factor, the concepts of diversity, and historical data.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
33
ReceptaclesA.
Tamper-Resistant Receptacles in Dwellings Unit (NEC 2008 - 406.11)Why do you think it is a tamperresistant receptacle?
..To increase safety for children.
..maybe that your son, daughter, or grandchildren that you will save
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
34
Tamper-Resistant Receptacles
Insertion of an object in any one side does not open the shutter (left), but a two-bladed plug or grounding plug compresses the Spring and simultaneously opens both shutters (right)Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
35
Accessible, ReadilyAccessible, Readily
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
36
Accessible, Readily
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
37
Not Located in Bathrooms
Overcurrent protection devices must not be located in the bathrooms of dwelling units, or in guest rooms or guest suites of hotels or motels.(2.40.2.5Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
38
Vertical Position
Enclosures for overcurrent devices must be mounted In a vertical position, unless this isnt practical. (2.40.3.3)Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
39
Accessible
Accessible (as applied to equipment) Admitting close approach; not guarded by locked doors, elevation, or other effective means.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
40
Within Sight
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
41
Overcurrent
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
42
Wiring Methods
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
43
Wiring Methods
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
44
Wiring Methods
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
45
ReceptaclesGeneral Receptacle Placement 210.52(A)
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
46
ReceptaclesMaximum Distance to a Receptacle210.52(A)(1)
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
47
ReceptaclesWall Spaces 600 mm (2 ft) in Width210.52(A)(2)(1)
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
48
ReceptaclesReceptacle placement in a kitchen
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
49
Extension Cords
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
50
Clothes Closes Luminaires
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
51
Clothes Closes Luminaires
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
52
Luminaire as Raceway
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
53
Decorative Lightings
Faulty or inadequate decorative lighting causes the majority of Christmas tree fires. ( Do not used indoor Christmas lights for outside or outdoor decorative lightings.)Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
54
Faulty Wirings?
BUNDLED NON-CONDUITED NONWIRES ON A STEEL TRUSSCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
55
Faulty Wirings?
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
56
1.10 Requirement for Electrical Installations1.10.1.2 Approval of Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
57
Electrical Installation
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
58
1.10.1.10 Circuit Impedance
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
59
Short-Circuit Current Rating
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
60
Short-Circuit Current Rating
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
61
1.10.1.11 Deteriorating Agents
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
62
1.10.1.12 Mechanical Execution of Worka) b)
Unused Openings Subsurface EnclosuresConductors must be racked to provide ready and safe access in underground and subsurface enclosures into which persons enter for installation and maintenance.
c)
Integrity of Electrical Equipment and Connections
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
63
1.10.1.12 Mechanical Execution of Work(a) Unused Openings
Unused cable or raceway openings must be closed with a fitting that provides equivalent protection.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
64
1.10.1.12 Mechanical Execution of Work(a) Unused Openings
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
65
1.10.1.12 Mechanical Execution of Work1.10.1.12(c) Integrity of Electrical Equipment and Connections
Internal parts of electrical equipment must be covered to avoid damage from paint or other substances.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
66
1.10.1.12 Mechanical Execution of Work1.10.1.12(c) Integrity of Electrical Equipment and ConnectionsIntegrity of Electrical Equipment Section 1.10.1.12 ( C )
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
67
1.10.1.14 Conductor Termination
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
68
1.10.1.14 Conductor Termination
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
69
1.10.1.14 Conductor Termination
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
70
1.10.1.14 Conductor Termination
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
71
1.10.1.14 Conductor Termination
Conductors must be spliced by a listing splicing device and they are NOT required to be twisted together prior to the installation of a twist-on wire connector.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
72
1.10.1.14 Conductor Termination
Twist-on Connectors
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
73
1.10.1.22 Identification of Disconnecting Means
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
74
1.10.2.1 Spaces about Electrical Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
75
1.10.2.1(a) Spaces about Electrical Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
76
1.10.2.1(a) Spaces about Electrical Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
77
1.10.2.1 Spaces about Electrical Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
78
1.10.2.1(a) Spaces about Electrical Equipment
Example of the 30 inch minimum working space at the rear of equipment to allow work on nonelectrical parts, such as the replacement of an air filter,Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
79
1.10.2.1(a) Spaces about Electrical Equipment
Permitted reduction from a Cond. 3 to a Cond. 2 Clearance according to 1.10.2.1(a)Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
80
1.10.2.1(a) Spaces about Electrical Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
81
1.10.2.1 Spaces about Electrical Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
82
1.10.2.1 Spaces about Electrical Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
83
1.10.2.1 Spaces about Electrical Equipment
Unacceptable arrangement of a large switchboard. A person could be trapped behind arcing electrical equipment.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
84
1.10.2.1 Spaces about Electrical Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
85
1.10.2.1 Spaces about Electrical Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
86
1.10.2.1(d) Illumination
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
87
1.10.2.1(f) Dedicated Equipment Space
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
88
1.10.2.1(f) Dedicated Equipment Space
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
89
1.10.2.1(f) Dedicated Equipment Space
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
90
1.10.2.2(b) Prevention of Physical Damage
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
91
1.10.2.1(f) Dedicated Equipment Space
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
92
Electric Shock
Electric shock is the physical simulation or trauma that occurs as a result of electric current passing through the body.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
93
Electric Shock
Human completing the path for current the earthCarmelray Industrial Park I Canlubang, Calamba, Laguna
Human in parallel with equipment grounding conductor during ground fault
Electrical Safety Seminar for Jollibees Personnel
94
Electric ShockElectric Shock Severity1.
Path of Current through Body Length of Time Current Flows Amount of Current through Body
2.
3.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
95
Electric ShockCurrent flow through body tissues delivers energy in the form of heat. The magnitude of energy may be approximated by
J = I2Rtwhere J = energy, joules I = current, amperes R = resistance of the current path through the body, ohms t = time of current flow, seconds
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
96
Effects of AC Electric Shock
ELCB!!!
Level (in milliamperes) of current through the bodyCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
97
Potential Difference
Potential difference between a grounded Water pipe and an ungrounded motor.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
98
Potential Difference
Motor ground-fault. A hazard now exists.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
99
Potential Difference
The hazard results in an electric shock.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
100
Potential Difference
Another shock hazard exists.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
101
Potential Difference
Shock hazard eliminated by installing a bonding jumper.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
102
Module 8 Grounded and Ungrounded SystemA.
Grounded Systems1) 2) 3) 4) Electrical System Grounding Grounding of Electrical Equipment Bonding of Electrical Equipment Bonding of Electrically Conductive Materials and Other Equipment 5) Effective Ground-Fault Current Path
B.
Ungrounded Systems1) Grounding of Electrical Equipment 2) Bonding of Electrical Equipment 3) Bonding of Electrically Conductive Materials and Other Equipment 4) Path for Fault CurrentCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
103
Grounded and Ungrounded SystemSec. 250.1.4 is divided into two parts
Part A Grounded SystemCarmelray Industrial Park I Canlubang, Calamba, Laguna
Part B Ungrounded SystemElectrical Safety Seminar for Jollibees Personnel
104
2.50.2.7 Conductor to be Grounded AC Systems
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
105
2.50.1.4 General Requirements for Grounding & Bonding
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
106
2.50.1.4 General Requirements for Grounding & BondingA.1.
Grounded SystemsElectrical System GroundingElectrical systems that are grounded shall be connected to earth in a manner that will limit the voltage imposed by lightning, line surges, or unintentional contact with higher voltage lines and that will stabilize the voltage to earth during normal operation.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
107
Lightning Theory
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
108
2.50.1.4 General Requirements for Grounding & BondingA.2.
Grounded SystemsGrounding of Electrical Equipment Normally non-currentcarrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected to earth so as to limit the voltage to ground on these materials.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
109
2.50.1.4 General Requirements for Grounding & BondingA.3.
Grounded SystemsBonding of Electrical Equipment Normally non-currentcarrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected together and to the electrical supply source in a manner that establishes an effective ground-fault current path.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
110
2.50.1.4 General Requirements for Grounding & BondingA. Grounded Systems4. Bonding of Electrically Conductive Materials and Other Equipment Normally non-currentcarrying conductive materials that are likely to become energized shall be connected together and to the electrical supply source in a manner that establishes an effective ground-fault current path.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
111
2.50.1.4 General Requirements for Grounding & BondingA.
Grounded Systems5. Effective Ground-Fault Current Path Electrical equipment, wiring, and other electrically conductive material likely to become energized shall be installed in a manner that creates a low-impedance circuit facilitating the operation of the overcurrent device or ground detector for high impedance grounded systems. It shall be capable of safely carrying the maximum groundfault current likely to be imposed on it from any point on the wiring system where a ground fault may occur to the eletrical supply source. The earth shall NOT be considered as an effective ground fault current path.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
112
2.50.1.4 General Requirements for Grounding & Bonding
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
113
Earth is Not an Effective Ground-Fault Current Path
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
114
2.50.1.4 General Requirements for Grounding & BondingB.
Ungrounded Systems1. Grounding of Electrical Equipment Normally non-current-carrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected to earth in a manner that will limit the voltage imposed by lightning or unintentional contact with higher voltage lines and limit the voltage to ground on these materials. Bonding of Electrical Equipment Normally non-current-carrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected together and to the supply system grounded equipment in a manner that creates a lowimpedance path for ground-fault current that is capable of carrying the maximum fault current likely to be imposed on it.
2.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
115
2.50.1.4 General Requirements for Grounding & BondingB.
Ungrounded Systems2. Bonding of Electrical Equipment
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
116
2.50.1.4 General Requirements for Grounding & BondingB.
Ungrounded Systems3. Bonding of Electrically Conductive Materials and Other EquipmentElectrically conductive materials that are likely to become energized shall be connected together and to the supply system grounded equipment in a manner that creates a lowimpedance path for ground-fault current that is capable of carrying the maximum fault current likely to be imposed on it.
4. Path for Fault CurrentElectrical equipment, wiring, and other electrically conductive material likely to become energized shall be installed in a manner that creates a low-impedance circuit facilitating the operation of the overcurrent device or ground detector for high impedance grounded systems. It shall be capable of safely carrying the maximum ground-fault current likely to be imposed on it from any point on the wiring system where a ground fault may occur to the electrical supply source. The earth shall not be considered as an effective ground fault current path.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
117
2.50.1.6 Objectionable Current Over Grounding ConductorsA.
Arrangement to Prevent Objectionable Current The grounding of electrical systems, circuit conductors, surge arresters, surge protective devices, and conductive normally non-current-carrying metal parts of equipment shall be installed and arranged in a manner that will prevent objectionable current over the grounding conductors or grounding paths.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
118
2.50.1.6 Objectionable Current Over Grounding ConductorsA.
Preventing Objectionable Current To prevent a fire, electric shock, or improper operation of circuitprotection devices or sensitive equipment, electrical systems and equipment must be installed in a manner that prevents objectionable current from flowing on conductive materials, electrical equipment, or grounding and bonding paths.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
119
2.50.1.6(A) Objectionable Current Over Grounding Conductors
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
120
2.50.1.6(A) Objectionable Current Over Grounding Conductors
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
121
2.50.1.6(A) Objectionable Current Over Grounding Conductors
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
122
2.50.1.6(A) Objectionable Current Over Grounding Conductors
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
123
2.50.1.6(A) Objectionable Current Over Grounding Conductors
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
124
2.50.1.6(A) Objectionable Current Over Grounding Conductors
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
125
2.50.1.6(A) Objectionable Current Over Grounding Conductors
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
126
2.50.1.6 Objectionable Current Over Grounding ConductorsC.
Temporary Currents Not Classified as Objectionable CurrentTemporary current resulting from accidental conditions, such as ground faults, shall not be classified as objectionable current for the purposes specified in 250.6(A) and (B).Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
127
2.50.1.6 Objectionable Current Over Grounding Conductors
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
128
2.50.1.6 Objectionable Current Over Grounding ConductorsD.
Limitations to Permissible Alterations The provision of this section shall not be considered as permitting electronic equipment for being operated on AC systems or branch circuits that are not connected to an equipment grounding conductor as required by this article. Currents that introduce noise or data errors in electronic equipment shall NOT be considered the objectionable currents addressed in this section.Section 2.50.1.6(d)
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
129
2.50.1.6 Objectionable Current Over Grounding ConductorsD.
Limitations to Permissible Alterations The provision of this section shall not be considered as permitting electronic equipment for being operated on AC systems or branch circuits that are not connected to an equipment grounding conductor as required by this article. Currents that introduce noise or data errors in electronic equipment shall not be considered the objectionable currents addressed in this section.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
130
Types of GroundingSystem Grounding Equipment Grounding These two are kept separate except at the point where they receive their source of power, such as at the service equipment or at a separately derived system!!!
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
131
2.50.2 System Grounding2.50.2.1 AC Systems to be GroundedA.250 V
AC System of Less than 50 Volts shall be grounded under any of the ff. conditions where:1) Supplied by transformers, if the transformer supply exceeds 250 V to ground Supplied by transformers, if the transformer supply is ungrounded Installed outside as overheads
2)
3)
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
132
2.50.2 System Grounding2.50.2.1 AC Systems to be GroundedB.
AC systems of 50 V to 1000 V that supply premises wiring and premises wiring systems shall be grounded under any of the ff conditions, where the system:1) Can be grounded so that the maximum voltage to ground on the ungrounded conductors does not exceed 250 V: 240 V 1 phase, 120/240 V -1-phase, 3 wire and 208/120 V, 3-phase, 4-wire 2) Is 3-phase, 4-wire, wye-connected in which the neutral conductor is used as a circuit conductor: 208/120 V, 3phase, 4-wire, and 480/277 V, 3-phase, 4-wire 3) Is 3-phase, 4-wire, delta-connected in which the midpoint of one phase winding is used as a circuit conductor: 120/240 V, 3-phase, 4-wire, and 240/480 V, 3-phase, 4-wireCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
133
2.50.2.1(B) Systems rated 50 to 1000 V that are required to be grounded
25 0V
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
134
2.50.2.1(B) Systems rated 50 to 1000 V that are required to be grounded
250 V
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
135
2.50.2.1(c) AC Systems of 1 kV & OverAC systems supplying mobile or portable equipment shall be grounded as specified in 2.50.10.9. Where supplying other than mobile or portable equipment, such systems shall be permitted to be grounded.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
136
2.50.2.1(D) Separately Derived Systems
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
137
2.50.2.1(d) Separately Derived Systems
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
138
2.50.2.1(e) Impedance Grounded Neutral Systems Impedance grounded neutral systems shall be grounded in accordance with 2.50.2.17 or 2.50.10.7
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
139
2.50.2.2 AC Systems of 50 to 1000 V NOT required to be Grounded
2.50.2.1(b)
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
140
2.50.2.2 Ground DetectorsUngrounded AC systems as permitted in 2.50.2.2(1) to ((4) operating at Not less than 120 V and Not exceeding 1000 V shall have ground detectors installed on the system.Ground Detectors (lights)
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
141
2.50.2.2 Ground Detectors
All relays and alarm Circuitry not shownGround detection is required on ungrounded systemsCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
142
2.50.2.5 Grounding ServiceSupplied AC Systems250.24(A) System Grounding Connections A premises wiring system supplied by a grounded AC service is required to have a grounding electrode conductor connected to the grounded service conductor , at each service, in accordance with 250.24(a)(1) through (A)(5).
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
143
2.50.2.5 Grounding ServiceSupplied AC Systems250.24(a)(1) General The grounding electrode conductor connection is required to be made at any accessible point from the load end of the service drop or service lateral to and including the terminal bus to which the grounded service conductor is connected at the service disconnecting means.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
144
2.50.2.5(a)(1) General
Grounding electrode conductor connection at accessible location
Grounding electrode conductor connection in wireway
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
145
2.50.2.5 (a)(2) Outdoor TransformerWhere the transformer supplying the service is located outside the building, at least one additional grounding connection is required to be made from the grounded service conductor to a grounding electrode, either at the transformer or elsewhere outside the building.Carmelray Industrial Park I Canlubang, Calamba, Laguna
WHY?
Electrical Safety Seminar for Jollibees Personnel
146
Module 9- Fire PumpsThe general philosophy behind Code articles is that circuit protection will shut down equipment before letting the supply conductors melt from overload. Art. 6.95 Fire Pumps depart from this philosophy. The idea is that the fire pump motor must run, no matter what; it supplies water to facilitys fire protection piping, which in turn supplies water to the sprinkler system and fire hoses.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
147
6.95.1.1 Scopea)
Covered 1) Electric power sources and interconnecting circuits 2) Switching and control equipment dedicated to fire pump drivers
b) Not Covered 1) The performance, maintenance, and acceptance testing of the fire pump system, and the internal wiring of the components of the system 2) Pressure maintenance (jockey or makeup) pumps
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
148
6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumpsa)
Individual Source1) Electric Utility Service. A separate service from a connection located ahead of but not within the service disconnecting means. 2) On-Site Power. An on-site power supply, such as generator, located and protected to minimize damage by fire is permitted to supply a fire pump.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
149
6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumps
a) Electric-Utility Service ConnectionCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
150
6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumps
a) Electric-Utility Service ConnectionCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
151
6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumps
2) On-Site Power Production FacilityCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
152
6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumpsb)
Multiple Sources1) Generator Capacity. Shall have sufficient capacity to allow normal starting and running 0f the motor(s) driving the fire pump(s) while supplying other simultaneously operated load. 2) Feeder Sources. 3) Arrangement. The power sources shall be arranged so that a fire at one will not cause an interruption at the other source.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
153
6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumps
2) Feeder SourcesCarmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
154
6.95.1.5 TransformersDedicated transformer and overcurrent protection sizing can be broken down into three requirements.1. The transformer must be size to at least 125% of the sum of the loads. 2. The transformer primary overcurrent device must be at least a specified minimum size. 3. The transformer secondary must not contain any overcurrent device whatsoever.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
155
6.95.1.5 Transformers
The overcurrent device in the primary of a transformer supplying a fire pump installation. The device is required to be sized to carry the locked-rotor current motor(s) and associated fire pump accessory equipment indefinitely.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
156
6.95.1.6 Power Wiringa)
Service and Feeder Conductors. Supply conductors must be physically routed outside buildings and must be installed in accordance with Article 2.30. Where supply conductors cannot be routed outside buildings, they must be encased in 2 inches or 50 mm of concrete or brick.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
157
6.95.1.6 Power Wiringb) Circuit Conductors. Fire pump supply conductors on the load side of the final disconnecting means and overcurrent device(s) must be kept entirely independent of all other wiring. They can be routed through a building using one of the following methods:1) Be encased in a minimum 2 inches or 50 mm of concrete 2) Be within an enclosed construction dedicated to the fire pump circuit(s) and having a minimum of a 1-hour fireresistant rating 3) Be listed electrical circuit protective system with a minimum 1-hour fire rating.
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
158
6.95.1.6(c)(2) BC Conductor SizeFire Pump Motor Branch Circuit Conductor SizeFrom Table 4.30.14.5(b)
Branch circuit conductors to a single fire pump motor must have a rating not less than 125% of the motor FLC as listed in Table 4.30.14.2 or 4.30.14.4Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
159
6.95.1.7 Voltage Drop
The voltage drop at the line terminals of the controller when the motor starts (locked-rotor current), must not drop more than 15% below the controllers rated voltage.Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
160
6.95.1.7 Voltage DropFire Pump Motor Voltage Drop
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
161
6.95.1.7 Voltage DropFire Pump Conductor Size Voltage Drop
Carmelray Industrial Park I Canlubang, Calamba, Laguna
Electrical Safety Seminar for Jollibees Personnel
162
Thank You !!!!&