THIS DOCUMENT CONTAINS PROPRIETARYINFORMATION OF "FREE HOT WATER", AND ITS
POSSESSION DOES NOT CONSTITUTE ANYRIGHTS TO REPRODUCE, DISCLOSE ITS
CONTENTS, OR TO MANUFACTURE, UTILIZE, ORSELL ANYTHING IT MAY DESCRIBE.
REPRODUCTION, DISCLOSURE OR USEWITHOUT EXPRESSED WRITTEN PERMISSION
OF "FREE HOT WATER" IS FORBIDDEN.
ENER
GY
408-
859-
5415
AREA OFWORK
THIS DOCUMENT CONTAINS PROPRIETARYINFORMATION OF "FREE HOT WATER", AND ITS
POSSESSION DOES NOT CONSTITUTE ANYRIGHTS TO REPRODUCE, DISCLOSE ITS
CONTENTS, OR TO MANUFACTURE, UTILIZE, ORSELL ANYTHING IT MAY DESCRIBE.
REPRODUCTION, DISCLOSURE OR USEWITHOUT EXPRESSED WRITTEN PERMISSION
OF "FREE HOT WATER" IS FORBIDDEN.
ENER
GY
408-
859-
5415
Salt Controller &Sensor
Chlorking & CO-2 controlled bychemical controller
Chlorking Chlor-25SM Controllers
3 x Chlorking Cells,25 lb per day each
pH 7.4 On 7.4
ORP 750 Off 752
Flow Switch On
Temperaure: 81
ControllerSample Stream
CO-2Supply
THIS DOCUMENT CONTAINS PROPRIETARYINFORMATION OF "FREE HOT WATER", AND ITS
POSSESSION DOES NOT CONSTITUTE ANYRIGHTS TO REPRODUCE, DISCLOSE ITS
CONTENTS, OR TO MANUFACTURE, UTILIZE, ORSELL ANYTHING IT MAY DESCRIBE.
REPRODUCTION, DISCLOSURE OR USEWITHOUT EXPRESSED WRITTEN PERMISSION
OF "FREE HOT WATER" IS FORBIDDEN.
ENER
GY
408-
859-
5415
pH 7.4 On 7.4
ORP 750 Off 752
Flow Switch On
Temperaure: 81
ControllerSample StreamSalt Controller &
Sensor
Chlorking & CO-2 controlled bychemical controller
CO-2Supply
Chlorking Chlor-25 Controller
Chlorking Cell,25 lb per day
THIS DOCUMENT CONTAINS PROPRIETARYINFORMATION OF "FREE HOT WATER", AND ITS
POSSESSION DOES NOT CONSTITUTE ANYRIGHTS TO REPRODUCE, DISCLOSE ITS
CONTENTS, OR TO MANUFACTURE, UTILIZE, ORSELL ANYTHING IT MAY DESCRIBE.
REPRODUCTION, DISCLOSURE OR USEWITHOUT EXPRESSED WRITTEN PERMISSION
OF "FREE HOT WATER" IS FORBIDDEN.
ENER
GY
408-
859-
5415
THIS DOCUMENT CONTAINS PROPRIETARYINFORMATION OF "FREE HOT WATER", AND ITS
POSSESSION DOES NOT CONSTITUTE ANYRIGHTS TO REPRODUCE, DISCLOSE ITS
CONTENTS, OR TO MANUFACTURE, UTILIZE, ORSELL ANYTHING IT MAY DESCRIBE.
REPRODUCTION, DISCLOSURE OR USEWITHOUT EXPRESSED WRITTEN PERMISSION
OF "FREE HOT WATER" IS FORBIDDEN.
ENER
GY
408-
859-
5415
1/16" = 1'-0"GRAPHIC SCALES:
5'0 50' 0 5'
1/8" = 1'-0" 1/4" = 1'-0"
25' 0 1' 12'
1/2" = 1'-0"
0 1' 6' 0
1" = 1'-0"3/4" = 1'-0"
4' 0 1' 3'
A REDUCED PRINT SCALE ACCORDINGLY
IF THIS SHEET IS NOT 24"x36" , IT IS
Facility
Project
Sheet Title
Permit No.:
Sheet
Drawn By:
Checked By:
Issue Date:
Scale: AS NOTED
07/15/2016
NWB
NWB
LANEY COLLEGE900 FALLON STREETOAKLAND, CA 94607
Whittington
Electric, Inc.Engineering / Commercial / Industrial
1940 Industrial Drive • Auburn, CA 95603
Office (530) 823-3055 • Fax (530) 823-3066
WEI Project#: 215-095
LANEY COLLEGE POOLBOILER REPLACEMENT
REVIEW SET - NOT FOR CONSTRUCTION
E0
ELECTRICAL SHEET INDEX,
SYMBOL LIST, ABBREVIATIONS,
PANEL SCHEDULES, LOAD
CALCULATION, ONE-LINE DIAGRAM,
AND CONNECTION SCHEDULE
Panel: Panel "EPH"Location: Lower Mechanical Area Volts: 277/480V Wye Mains: 100A Main Breaker
Supply From: 0 Phases: 3 Bus Rating: 100A
Mounting: Surface Wires: 4 AIC Rating: -
Load DescriptionLoad (VA) Circuit Breaker Ckt
#Ckt#
Circuit Breaker Load (VA)Load Description
A B C Amp Pole Amps Poles A B C
(R) ChlorTec 0 20 3 1 2 15 3 0 (E) Spare
- 0 - - 3 4 - - 0 -
- 0 - - 5 6 - - 0 -
(E) Spare 0 15 3 7 8 15 3 0 (E) Spare
- 0 - - 9 10 - - 0 -
- 0 - - 11 12 - - 0 -
(E) 5HP Dive Pool Pump 2100 15 3 13 14 70 3 9350 (E) 20HP Lap Pool Pump
- 2100 - - 15 16 - - 9350 -
- 2100 - - 17 18 - - 9350 -
Space - 1 19 20 - 1 Space
Space - 1 21 22 - 1 Space
Space - 1 23 24 - 1 Space
Space - 1 25 26 - 1 Space
Space - 1 27 28 - 1 Space
Space - 1 29 30 - 1 Space
Notes:1.
Totals
kVA Amps
Phase A 11.5 31.79
Phase B 11.5 31.79
Phase C 11.5 31.79
Total 34.4 41.32
EXISTING ELECTRICAL BRANCH CIRCUIT PANEL - SURFACE MOUNTED
NON-FUSED SAFETY SWITCH DISCONNECT. SIZE AS NOTED.
NEW CONDUIT WITH WIRING AS NOTED ON PLANS.
EXISTING CONDUIT WITH WIRING TO BE REMOVED.
NUMBERED SHEET NOTE TAG. REFER TO MATCHING NUMBERED
SHEET NOTE ON SAME SHEET.
ELECTRICAL MOTOR - SIZED IN AS NOTED (EXAMPLE 5HP).
SYMBOL LIST
E0 ELECTRICAL SHEET INDEX, SYMBOL LIST, ABBREVIATIONS, PANEL
SCHEDULES, LOAD CALCULATIONS, ONE-LINE DIAGRAM AND CONNECTION
SCHEDULE
E1 MECHANICAL AREA - UPPER LEVEL - ELECTRICAL
E2 MECHANICAL AREA - LOWER LEVEL - ELECTRICAL
E3 ELECTRICAL SPECIFICATIONS
SHEET INDEX
ABBREVIATIONS
A AMPERE
AFF ABOVE FINISHED FLOOR
C CONDUIT
CKT CIRCUIT
CB CIRCUIT BREAKER
DIA DIAMETER
(E) EXISTING
FLA FULL LOAD AMPERES
(F) FUTURE
GALV GALVANIZED
GFCI GROUND-FAULT CIRCUIT
INTERRUPTER
HZ HERTZ
JB JUNCTION BOX
KVA KILOVOLT AMPERE
KW KILOWATT
LT LIGHT
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.S. NURSE STATION
NTS NOT TO SCALE
OC ON CENTER
PNL PANEL
PH PHASE
(R) REMOVE
RCPT RECEPTACLE
SM SHEET METAL
SMS SHEET METAL SCREW
SWBD SWITCHBOARD
TYP. TYPICAL
V VOLT
VA VOLT AMPERE
W WATT
WP WEATHERPROOF
1
5
1PARTIAL ONE-LINE POWER DIAGRAMSCALE: NONE
(E)
70/3
(E) PANEL "EPH"
100A, 480Y/277V, 3ɸ, 4W
(E)
100/3
(E) FEEDER
(E)
15/3
(N)
70/3
(N) 1" C.,
(3) #4, AND
(1) #8 GND.
(N) PANEL "EPL2"
100A, 208Y/120V, 3ɸ, 4W
(N) XFMR "TEPL2"
30 KVA, 480-208Y/120V, 3ɸ, 4W
(N) 1-1/4" C.,
(4) #2, AND
(1) #8 GND.
(N)
100/3
(N)
60/2
(N)
60/2
(N)
30/2
(N)
45/2
(N)
20/2
(N)
20/2
(N)
20/2
(N)
20/1
20 5
(E) FEEDER
(E) FEEDER (E) FEEDER
(E) VFD (E) VFD
(E) LAP POOL PUMP (E) DIVE POOL PUMP
TO BE REPLACED
IN KIND
1 1 13
P
3
P
1
P
2
P
4
JJJJ
SEE MECHANICAL
EQUIPMENT CONNECTION
SCHEDULE FOR CONDUIT
AND CONDUCTOR SIZING
DISCONNECT PER
MECHANICAL EQUIPMENT
CONNECTION SCHEDULE,
TYPICAL OF (7)
SM
-1
CH
LO
R 4
0 #
1
CH
LO
R 4
0 #
2
CH
LO
R 2
5S
M
(E)
(E) FEEDER
Panel: Panel "EPL2"Location: Lower Mechanical Area Volts: 120/208V Wye Mains: 100A Main Breaker
Supply From: Panel "EPH" via Xfmr"TEPL2"
Phases: 3 Bus Rating: 100A
Mounting: Surface Wires: 4 AIC Rating: Match existing AIC
Load DescriptionLoad (VA) Circuit Breaker Ckt
#Ckt#
Circuit Breaker Load (VA)Load Description
A B C Amp Pole Amps Poles A B C
CHLOR 40 #1 [1] 3328 60 2 1 2 916 Pump P-1
- 3328 - - 3 4 916 -
CHLOR 40 #2[1] 3328 60 2 5 6 916 Pump P-2
- 3328 - - 7 8 916 -
CHLOR 25SM [1] 1560 30 2 9 10 1945 Pump P-3
- 1560 - - 11 12 1945 -
Space - 1 13 14 - 1 916 Pump P-4
Space - 1 15 16 - 1 916 -
Space - 1 17 18 - 1 1320 SM-1
Space - 1 19 20 - 1
Space - 1 21 22 -
Notes:1. Provide new GFCI circuit breaker with rating indicated matching existingbreaker type and AIC ratings.
Totals
kVA Amps
Phase A 9.4 26.11
Phase B 8.7 24.06
Phase C 9.1 25.18
Total 27.1 75.34
ELECTRICAL LOAD CALCULATION FOR PANEL EPH
Phase
A B C A+B+C
20 HP Lap Pool Pump 9.35 kVA 9.35 kVA 9.35 kVA 28.05 kVA
+25% Largest Motor Load 2.34 kVA 2.34 kVA 2.34 kVA 7.01 kVA
5 HP Dive Pool Pump 2.10 kVA 2.10 kVA 2.10 kVA 6.30 kVA
(N) CHLOR 25SM 0.00 kVA 1.56 kVA 1.56 kVA 3.12 kVA
(N) CHLOR 40 3.30 kVA 3.30 kVA 0.00 kVA 6.60 kVA
(N) CHLOR 40 3.30 kVA 0.00 kVA 3.30 kVA 6.60 kVA
(N) P-1 0.90 kVA 0.90 kVA 0.00 kVA 1.80 kVA
(N) P-2 0.90 kVA 0.00 kVA 0.90 kVA 1.80 kVA
(N) P-3 0.00 kVA 1.95 kVA 1.95 kVA 3.90 kVA
(N) P-4 0.90 kVA 0.90 kVA 0.00 kVA 1.80 kVA
(N) SM-1 0.00 kVA 0.00 kVA 1.32 kVA 1.32 kVA
Total Load kVA ( Existing and New) 23.09 kVA 22.40 kVA 22.82 kVA 68.30 kVA
Total Load Amps ( Existing and New) 192.40 A 186.65 A 190.15 A 82.16 A
Therefore 100A Panel, Breaker, and Feeder have capacity for the added load.
Notes:1. Existing loads calculated per 2013 CEC 430.2.
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
EQUIPMENT DATA POWER SUPPLY CONDUIT & WIRE DISCONNECT SWITCH
NO
TE
S
DESIGNATION LOCATION
HP
OR
KW
FLA
MC
A
MO
CP
PH
AS
E
VO
LT
S
BR
EA
KE
R
PO
LE
S
PANELBOARD
OR MCCCKT # QUANTITIES AND SIZE
TYPE LOCATION SIZE
FU
SE
D (
F)
OR
NO
N-F
US
ED
(NF
)
AT
UN
IT
INT
EG
RA
L
FU
SE
SIZ
E
NE
MA
EN
CL.
RA
TIN
G
SM-1 LOWER LEVEL - 1.0 A - - 1 120 V 20 A 1 EPL2 18 (N) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 1
P1 UPPER LEVEL 1 HP 8.8 A 11.0 A 20.0 A 1 208 V 20 A 2 EPL2 2,4 (N) 1/2"C, (2) #12 & (1) #12 GND F X - 20 A 3R 30A/2P 3
P2 UPPER LEVEL 1 HP 8.8 A 11.0 A 20.0 A 1 208 V 20 A 2 EPL2 6,8 (N) 1/2"C, (2) #12 & (1) #12 GND F X - 20 A 3R 30A/2P 3
P3 UPPER LEVEL 3 HP 18.7 A 24.0 A 45.0 A 1 208 V 45 A 2 EPL2 10,12 (N) 1/2"C, (2) #8 & (1) #10 GND F X - 45 A 3R 60A/2P 3
P4 UPPER LEVEL 1 HP 8.8 A 11.0 A 20.0 A 1 208 V 20 A 2 EPL2 14,16 (N) 1/2"C, (2) #12 & (1) #12 GND F X - 20 A 3R 30A/2P 3
CHLOR 25 UPPER LEVEL - 15.0 A - - 1 208 V 30 A 2 EPL2 9,11 (N) 1/2"C, (2) #10 & (1) #10 GND NF X - - 3R 30A/2P 3
CHLOR 40-1 UPPER LEVEL - 32.0 A - - 1 208 V 60 A 2 EPL2 1,3 (N) 3/4"C, (2) #6 & (1) #10 GND NF X - - 3R 60A/2P 3
CHLOR 40-2 UPPER LEVEL - 32.0 A - - 1 208 V 60 A 2 EPL2 5,7 (N) 3/4"C, (2) #6 & (1) #10 GND NF X - - 3R 60A/2P 3
BLR-1 LOWER LEVEL - 5.0 A - - 1 120 V 20 A 1 - - (E) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 2
BLR-2 LOWER LEVEL - 5.0 A - - 1 120 V 20 A 1 - - (E) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 2
BLR-3 LOWER LEVEL - 5.0 A - - 1 120 V 20 A 1 - - (E) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 2
BLR-4 LOWER LEVEL - 5.0 A - - 1 120 V 20 A 1 - - (E) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 2
BLR-5 LOWER LEVEL - 5.0 A - - 1 120 V 20 A 1 - - (E) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 2
Notes:
1. Mechanical to provide (1) SM-1 per sensor. See mechanical drawings.
2. Re-use existing circuits. Replacement in kind. No load chance.
3. Coordinate location with mechanical. See mechanical drawings.
LOCATION OF NEW CHLORINATOR EQUIPMENT, COORDINATE WITH MECHANICAL
(R) CHLORINATION EQUIPMENT(R) DISCONNECT, EPH-1,3,5 1 1
1/16" = 1'-0"GRAPHIC SCALES:
5'0 50' 0 5'
1/8" = 1'-0" 1/4" = 1'-0"
25' 0 1' 12'
1/2" = 1'-0"
0 1' 6' 0
1" = 1'-0"3/4" = 1'-0"
4' 0 1' 3'
A REDUCED PRINT SCALE ACCORDINGLY
IF THIS SHEET IS NOT 24"x36" , IT IS
Facility
Project
Sheet Title
Permit No.:
Sheet
Drawn By:
Checked By:
Issue Date:
Scale: AS NOTED
07/15/2016
NWB
NWB
LANEY COLLEGE900 FALLON STREETOAKLAND, CA 94607
Whittington
Electric, Inc.Engineering / Commercial / Industrial
1940 Industrial Drive • Auburn, CA 95603
Office (530) 823-3055 • Fax (530) 823-3066
WEI Project#: 215-095
LANEY COLLEGE POOLBOILER REPLACEMENT
REVIEW SET - NOT FOR CONSTRUCTION
1MECHANICAL AREA - UPPER LEVEL - NEW ELECTRICALSCALE: 3/4" = 1'-0"
E1
MECHANICAL AREA FLOOR
PLAN - UPPER LEVEL -
ELECTRICAL
REMOVE EXISTING DISCONNECT, CONDUIT AND CONDUCTORS TO EXISTING
CHLORINATION EQUIPMENT.
NUMBERED SHEET NOTES1
2PARTIAL MECHANICAL AREA - UPPER LEVEL - DEMO ELECTRICALSCALE: 3/4" = 1'-0"
(5) BOILERS TO BE REPLACED IN KIND
5 20
(E) VFD, DIVE POOL PUMP
(E) VFD, LAP POOL PUMP
(N) 5HP DIVE POOL PUMP (E) 20HP LAP POOL PUMP
(E) PANEL "EPL"
(E) PANEL "EPH"
(E) ELECTRICAL GUTTER
(R) ABANDONED FUSED DISCONNECTS
8
7
6
54
2
3
1
(E) PANEL "EPL2" (E) XFMR "TEPL2"109
1/16" = 1'-0"GRAPHIC SCALES:
5'0 50' 0 5'
1/8" = 1'-0" 1/4" = 1'-0"
25' 0 1' 12'
1/2" = 1'-0"
0 1' 6' 0
1" = 1'-0"3/4" = 1'-0"
4' 0 1' 3'
A REDUCED PRINT SCALE ACCORDINGLY
IF THIS SHEET IS NOT 24"x36" , IT IS
Facility
Project
Sheet Title
Permit No.:
Sheet
Drawn By:
Checked By:
Issue Date:
Scale: AS NOTED
07/15/2016
NWB
NWB
LANEY COLLEGE900 FALLON STREETOAKLAND, CA 94607
Whittington
Electric, Inc.Engineering / Commercial / Industrial
1940 Industrial Drive • Auburn, CA 95603
Office (530) 823-3055 • Fax (530) 823-3066
WEI Project#: 215-095
LANEY COLLEGE POOLBOILER REPLACEMENT
REVIEW SET - NOT FOR CONSTRUCTION
1MECHANICAL AREA - LOWER LEVEL - ELECTRICALSCALE: 3/4" = 1'-0"
E2
MECHANICAL AREA FLOOR
PLAN - LOWER LEVEL -
ELECTRICAL
(R) ABANDONED CONDUIT
EXISTING BOILERS TO BE REPLACED IN KIND. NO CHANGE IN PANEL/CIRCUIT
LOADS.
EXISTING 480/277V, 3 PHASE, 4 WIRE PANEL. SEE PANEL SCHEDULE, SHEET
"E0".
EXISTING 208/120V, 3 PHASE, 4 WIRE PANEL.
EXISTING 5 HP DIVE POOL PUMP MOTOR TO BE REPLACE IN KIND. NO LOAD
CHANGE. PROVIDE MEGGER TEST ON PHASE CONDUCTORS TO VERIFY
CONDUCTOR INSULATION CONDITION. REPLACE CONDUCTORS IN KIND IF
NECESSARY.
EXISTING 20 HP LAP POOL PUMP MOTOR TO REMAIN. PROVIDE MEGGER TEST
ON PHASE CONDUCTORS TO VERIFY CONDUCTOR INSULATION CONDITION.
REPLACE CONDUCTORS IN KIND IF NECESSARY.
REMOVE EXISTING FUSED DISCONNECTS. CIRCUIT BREAKERS ARE WITHIN
LINE OF SITE AND OF SUITABLE RATING FOR SHORT-CIRCUIT AND GROUND
FAULT PROTECTION OF CONDUCTORS. RELOCATE CONDUCTOR SPLICES INTO
ELECTRICAL GUTTER ABOVE.
IDENTIFY AND PROVIDE LABELS FOR ALL CIRCUIT CONDUCTORS IN GUTTER.
REMOVE ABANDONED CONDUITS AND PROVIDE KNOCKOUT SEALS.
REMOVE ABANDONED CONDUIT. EXISTING CAT CABLE TO REMAIN, PROVIDE
NEW CABLE SUPPORTS ALONG CONCRETE WALL.
PROVIDE NEW BRANCH CIRCUIT PANEL. SEE ONE-LINE DIAGRAM AND PANEL
SCHEDULE, SHEET "E0".
PROVIDE NEW TRANSFORMER. SEE ONE-LINE DIAGRAM, SHEET "E0". EXTEND
HOUSE KEEPING PAD AS NECESSARY.
NUMBERED SHEET NOTES1
2
3
4
5
6
7
8
9
10