Equipment Grounding Conductor

Embed Size (px)

Citation preview

  • 7/29/2019 Equipment Grounding Conductor

    1/4

    NEC 250.122 Calculations

    Equipment Grounding Conductor

    By: Aisha Bajwa - Field Application Engineer, Alcan Cable

    Alcan CableThree Ravinia Drive, Suite 1600, Atlanta, GA 30346 | Tel (770) 394-9886 Toll Free (800) 347-0571 | www.cable.alcan.com | 2010 Alcan Cable.

    Executive Summary

    Observing proper grounding and bonding processes andemploying reliable materials are essential considerations thatcontribute to the safety of personnel and equipment over thelifetime of an electrical system.

    Properly following the general requirements for groundingand bonding articulated in Section 250.4 (A) of the NationalElectric Code (NEC) can prevent injuries by limiting the

    voltage imposed by incidents such as lightning strikes, linesurges, or unintentional contact with higher voltage lines.

    While the processes for grounding and bonding arestraightforward, well known, and commonly practiced,material selection for equipment grounding conductor (EGC)is not such a cut-and-dry aair. Where copper was formerlythe universally approved choice, the performance of aluminumalloy in EGC has earned the respect it deserves.

    Within the context provided by Section 250.122 of the NEC,this paper will examine the functionality, eectiveness, andpracticality of combining an aluminum alloy EGC withaluminum phase conductors.

    Types o Equipment Grounding Conductors

    Since the late 1960s, technology used in electrical componentshas improved tremendously. In particular, advancements inaluminum alloy manufacturing have resulted in more secureand reliable electrical systems at reduced material cost. In thelate 1970s, improved dual-rated (ALCU, AL7CU, and AL9CU)connectors that could be used with both aluminum and copperconductors became widely available. Simultaneously, the rangeof EGC options opened up considerably.

    NEC Section 250.118 provides a list of possible EGC options.In many cases, the requirements in this list articulate a needfor the EGC to run with or enclosing the circuit conductors.Acceptable EGCs shall consist of any of the following:

    A copper, aluminum, or copper-clad aluminumconductor. Tis conductor shall be solid or stranded;insulated, covered, or bare; and in the form of a wire or abusbar of any shape.

    Rigid metal conduit (RMC) Intermediate metal conduit(IMC)

    Electrical metallic tubing (EM) Listed exible metal conduit (FMC) Flexible metal tubing (FM) ype AC cable (BX) Listed liquidtight exible metal conduit (LFC) Mineral insulated sheathed cable (MI) ype MC Cable Cable trays Cablebus framework Other listed electrically continuous metal raceways Surface metal raceways listed for grounding

    Notable in this list is the opportunity represented by the

    inclusion of aluminum alloy EGCs. Indeed, the advances inthe 1960s and 1970s enabled a more harmonized system usingsimilar metals for both the conductor and connector. Teconnector body itself is made of aluminum alloy with atinplating to mitigate galvanic corrosion when copperconductor terminations are made on aluminum alloyconnectors.

    Te NEC acknowledges these advancements and recognizesthe use of aluminum alloy conductors such as SABILOYAA-8030 conductors. Section 310.106(B) in the 2011 NEC,states that solid aluminum conductors size 8 AWG, 10 AWG,and 12 AWG shall be made of an AA-8000 series electrical-

    grade aluminum alloy conductor material, and strandedaluminum conductors 8 AWG through 1000 kcmil shall bemade of AA-8000 series electrical-grade aluminum alloyconductor material for most insulation types.

    It is clear in the NEC that aluminum alloy conductors arean acceptable and equal choice for equipment groundingconductors. able 250.122 includes both copper and aluminumconductor sizing for equipment grounding conductors.

    Despite this armation by the NEC, and the fact that theAA-8000 series aluminum alloy has been in use for more than40 years, a tendency toward choosing copper EGCs for use

    with aluminum phase conductors persists within the industry.However, it is likely that the perception of copper as the defaultchoice for EGCs will continue to fade over time as awarenessof the NEC compliance of aluminum alloy EGCs and theeconomic benets of choosing aluminum alloy become betterknown. Tere is no engineering benet to using a copperEGC with aluminum phase conductors, and it simply adds costwithout benet.

  • 7/29/2019 Equipment Grounding Conductor

    2/4

    Sizing o Equipment Grounding Conductors

    Te purpose of EGCs is to provide a low-impedance, ground-fault current path that reduces equipment to as close to zeropotential as possible. NEC able 250.122 relates the selectionof size-appropriate EGC to the size of the over-current deviceahead of the conductor. Section 250.122 (A) clearly states thataluminum and copper EGCs shall not be smaller than the

    values presented in this table, but also states that they are not

    required to be larger than the circuit conductors supplying theequipment.

    As a rule-of-thumb (using calculations for verication), EGCsshould not be less than 25 percent of the capacity of the phaseconductors or the over-current device.

    Note: Where necessary to comply with 250.4(A)(5) or (B)(4), the equipmentgrounding conductor shall be sized larger than given in this table.*See installation restrictions in 250.120.

    Example 1 shows an EGCs minimum size based on the over-current protection device (OCPD).

    Identifcation o Equipment Grounding Conductors

    Being able to visually isolate and identify EGCs is a veryimportant safety consideration, and is key to prevention ofelectrical accidents. Section 250.119 of the NEC explainsthe identication of EGCs for use with conductors larger than6 AWG (250.119 (A)), multi-conductor cable (250.119 (B)),and exible cords (250.119 (C)). According to the NEC, EGCscan be bare, insulated, or covered, unless stipulated otherwise

    elsewhere in the NEC. Individually covered or insulated EGCsshould have a continuous outer nish that is either green orgreen with one or more yellow stripes and to accentuatedierentiation this color scheme is not permitted forungrounded or grounded circuit conductors.

    EGCs larger than 6 AWG, whether aluminum or copper, thatare insulated or covered, shall be color-coded at each end andat every point where the conductor is accessible.

    Installation o Equipment Grounding Conductors

    Optimal location is a crucial factor in achieving minimal

    impedance in an AC grounding system. Even if a sucientlysized EGC is used, electrical hazard can manifest if it is notproperly located and installed. o this end, Section 250.134(B) requires that EGCs be installed in the same raceway, cableor cord as the circuit conductors. Tis requirement, in similarform, is again reiterated in Section 300.3 (B), which expressesthe need for EGCs to be installed in the same raceway, cable,trench, etc. with the other circuit conductors.

    Te purpose of the EGC is to bond non-current carryingparts of the electrical system and provide a low impedancepath for ground fault current, allowing for eective clearing ofground faults. Routing the EGC with the circuit conductors is

    required by the NEC in most cases.

    EGCs should be installed in accordance with Section 250.120(A), (B), and (C). Tese NEC entries require that installationwithin a raceway, cable tray, cable armor, cablebus framework,or cable sheath be installed with applicable code provisions,and that all terminations and joints be listed, approved, andtightly secured with appropriate tools.

    While both bare and insulated aluminum or copper-cladaluminum EGCs are permitted, Section 250.120(B), requiresthat bare conductors not come into direct contact withmasonry, earth or any region where they may be subjectedto corrosive conditions. Further, aluminum or copper-cladaluminum should not be terminated within 18 inches of theearths surface the intention of this restriction is to avoidcorrosion of the aluminum by contact with certain types of soil(for example, soils that contain certain salts and/or alkaline pHlevels).

    Alcan CableThree Ravinia Drive, Suite 1600, Atlanta, GA 30346 | Tel (770) 394-9886 Toll Free (800) 347-0571 | www.cable.alcan.com

    Table 250.122 Minimum Size Equipment GroundingConductors for Grounding Raceway and Equipment

    Rating or Setting ofAutomatic Overcurrent

    Device in Circuit Ahead ofEquipment, Conduit, etc.,

    Not Exceeding (Amperes)

    Size (AWG or kcmil)

    CopperAluminum orCopper-Clad

    Aluminum*15 14 12

    20 12 10

    60 10 8

    100 8 6

    200 6 4

    300 4 2

    400 3 1

    500 2 1/0

    600 1 2/0

    800 1/0 3/01000 2/0 4/0

    1200 3/0 250

    1600 4/0 350

    2000 250 400

    2500 350 600

    3000 400 600

    4000 500 750

    5000 700 1200

    6000 800 1200

  • 7/29/2019 Equipment Grounding Conductor

    3/4

    Step3: CalculatewhichnewEGCistobeusedbytaking

    intoaccountthesizeincreaseofthephase

    conductors.

    Ratio=Selectedconductorarea(CM) Requiredconductorarea(CM)

    Ratio=105,600/83,690=1.262

    Newequipmentgroundingconductor= ConductorareaoforiginalEGC*Ratio

    =26240*1.262 =33,115CM

    NECTable8inChapter9showsusthecircularmil areaofthesmallestconductorthatislargerthanthe

    calculatedvalueisa4AWGaluminumat41,740CM. So,thesizeofthenewEGCis4AWGaluminum.

    Multiple Circuits

    Section 250.122 (C) mentions that when a single EGC is runwithin a raceway with multiple circuits, it should be sized forthe largest over-current device present.

    Example3:

    FindtheEGCforaconduitthatcontainsmultiplecircu

    withover-currentprotectionsratingsof20A,30A,40A, and50A.

    Solution:

    OCPDare20A,30A,40A,and50A.Per250.122(C)th sizeoftheEGCshouldbeforthelargestover-current

    device.

    InthisexamplethelargestOCPDaheadofthecircuit is50A.Sincea50Adesignationisnotprovidedin

    Table250.122,wereferencethenextlargersize,which 60A.MinimumaluminumEGCis8AWG.

    Conductors in Parallel

    When using EGCs for conductors in parallel runs, Section250.122 (F) is our point of reference. Whether or not toinstall parallel conductors is largely determined by design aneconomic considerations. Ampacities for aluminum andcopper conductors are given in able 310.15(B)(16). Noticethat they do not increase in direct proportion to the size of thconductors. Te general requirements of parallel conductorinstallations are given in Section 310.10(H) of the NEC, wheit is required that each set of conductors must be comprisedof the same conductor material and insulation type, must be

    Example1:

    Whatsizealuminumequipmentgroundingconductoris

    neededfora400Acircuitbreakerprotectingthefeeder circuit?

    Solution:

    ReferencingNECTable250.122,listingofminimum sizesofEGCsbasedontheover-currentdevicerating,we

    seeundertheover-currentdevicecolumn,thata1AWG aluminumEGCmeetstheminimumrequirementfora

    400Acircuitbreaker.

    Size Increase Requirements

    Sometimes higher voltage drop or other adjustments orcorrection factors require that phase conductors be increasedin size. Under these circumstances, Section 250.122 (B)requires a proportional increase in the size of the EGC. TeNational Electrical Code Chapter 9, able 8 contains

    information that can be used to determine the appropriatesize EGCs based on the circular mil area of the ungroundedconductors.

    Example2:

    Fora100Aload,whatsizeofaluminumEGCshould beusedwhenthephaseconductorsareincreasedinsize

    tocompensateforahighervoltagedrop?

    Solution:

    Step1: Consideringavoltagedrop,selectphase

    conductorfromTable310.15(B)(16)fora100A load.

    AsperTable250.122,a100AOCPDrequiresa6

    AWGaluminumconductor.FromTable310.5(B) (16),a100Aloadwillneed1AWGaluminum

    conductors.Tocompensateforavoltagedrop,the conductorsizeisincreasedto1/0AWGaluminum.

    Step2: FindcircularmilsofconductorsfromTable8 inChapter9.

    Requiredconductorarea(CM)=originalwire

    sizewithoutVD=1AWGAl=83,690CM

    Selectedconductorarea(CM)=increased wiresizewithVD=1/0AWGAl=105,600CM

    MinimumEGCwiresize=6AWGAl= 26,240CM

    Alcan CableThree Ravinia Drive, Suite 1600, Atlanta, GA 30346 | Tel (770) 394-9886 Toll Free (800) 347-0571 | www.cable.alcan.com

  • 7/29/2019 Equipment Grounding Conductor

    4/4

    should be permanent; it should be electrically continuous; andit should facilitate the lowest possible impedance.

    Due to pervasive and persistent misunderstandings about thesuitability of aluminum alloy EGCs for use with aluminumphase conductors, many designers still unnecessarily specifythe use of copper EGCs. Section 250.118 clearly accepts theuse of aluminum EGCs and rearms it in able 250.122. Bothcopper and aluminum EGCs facilitate suciently low

    impedance path levels provided they are of the appropriatesize, which is determined by the over-current device ahead ofthe circuit.

    All aluminum alloy conductors, including EGCs, mustterminate on connectors listed for use with aluminum. Teseconnectors are typically dual-rated for both aluminum andcopper. In 1978, dual-rated (ALCU, AL7CU, and AL9CU)aluminum body lugs were introduced and tested in accordancewith UL 486B. Tese dual-rated connectors are suitable forboth copper and aluminum conductors and are made of analuminum alloy.

    Considering more than a century of withstanding naturesharshest conditions in electrical transmission line systems,decades of use for EGCs in buildings, and growing awarenessof the economic value it oers, aluminum nally appears to begetting the attention it deserves on the draing table and onthe job site.

    Reerences

    Simmons, Philip J., Electrical Grounding and Bonding, 2nd ed:199-227National Electrical Code NFPA: 2011 ed..

    [Soares]. Book on Grounding and Bonding, IAEI: 9th edition: 160-207Michael Johnston.,Equipment Grounding Conductors for ParallelRuns.

    Hunter, Christel. Aluminum Building Wire Installation andTerminations. IAEI News (January/February 2006)

    of the same dimensions in both circular mil area and length,and must be terminated in the same manner. Also, each runshould have separate EGCs in each conduit. Te reason for thisis to ensure that each EGC is adequately sized to facilitate lowimpedance values during a ground fault in order to preventdamage due to overloading. And remember, EGCs never haveto be larger than the phase conductors of the circuit accordingto Section 250.122(A).

    Te rationale behind the requirements in Section 310.10(H)is to keep equal current in parallel sets and avoid insulationdamage from severe current imbalances. Please notice again,referencing able 250.122, that there is no need to use copperEGCs if the phase conductors are aluminum. Te onlyrequirement here is that parallel EGCs must be of the samematerial.

    Cable assemblies, such as Metal Clad (MC) Cable, aremanufactured in standard conductor congurations, andwhile the EGCs in cable assemblies are sized for many circuitarrangements, it is not safe to assume that they are suitablefor all parallel circuit arrangements. It is very important to

    conrm that the EGC in each assembly is sized according toable 250.122 using the size of the over-current device as thedetermining factor.

    Example4:

    A2000Afeederisinstalledinparallelusing6MetalClad (MC)typecables.Eachsetcontainsfour600kcmil

    aluminumalloyconductors.Whatistheminimumsize EGCthatcanbeused?

    Solution:

    FromTable250.122,weseethata2000AOCPDrequires ataminimumthata400kcmilaluminumEGCbe

    installedineachMCCableassembly.

    Section 250.122 (G), which refers to the selection of EGC forfeeder taps, shows the EGC run with feeder taps shall notbe smaller than the values presented in able 250.122 thatreference the rating of the over-current device ahead of thefeeder. It also shows that they are not required to be larger thanthe tap conductor.

    Conclusion

    EGCs are an indispensable aspect of grounding and bondingsafeguards in electrical installation projects. Tey not onlyprotect circuits and equipment, but also help eliminate therisk of electrical shock. In order to achieve the desired levelof impedance, sizing of EGCs is very important and canbe accomplished using the details in Section 250.122 of theNEC. Ultimately, the proper grounding of electrical equipmentrequires adherence to three fundamentals: the grounding path

    Alcan Cable

    Three Ravinia Drive, Suite 1600, Atlanta, GA 30346 | Tel (770) 394-9886 Toll Free (800) 347-0571 | www.cable.alcan.com

    2011 Alcan Cable. STABILOY is a registered trademark of Alcan Cable, a division of Alcan Products Corporation. All rights reserved.