FACTS are consisted of power electronics and other static components to increase controllability and power transfer capability of AC network. Representative systems are SVC and STATCOM.• Provide dynamic reactive power support and voltage control.• Suppression flicker by fluctuating load• Mitigate potential sub-synchronous resonance problems.• Improve system stability.
FACTS
SVC system are consisted of thyristor-controlled reactor (TCR) and the
thyristor switched capacitor (TSC) as well as harmonic filters.
SVC is the most widely employed FACTS device around the world.
SVC
Flexible AC Transmission System
Static Var Compensator
Like an SVC, the STATCOM(Static Synchronous Compensator) enhances the
stability of grid voltage by introducing the voltage sourced MMC(Modular
Multilevel Converter) technology. LSIS’ most advanced “SVC Compact”
provides high-performance in remarkably compact footprint.
PowerUtility companyIPP(Independent Power Plant)Wind and solar farm
Voltage controlStability improvePower factor improveReactive power controlPower loss reduce
SteelSteel companySmelting companySpecial steel company
Flicker, THD reducePower factor improveProductivity improveVoltage controlReactive power controlPower loss reduce
Mine, Gas & OilMining companyGas plantOil plant
Productivity improvePower factor improveFlicker, THD reduceVoltage controlReactive power control
STATCOMStatic Var Compensator Compact
FUTURING SMART ENERGY
FACTS applications and benefit
FACTS [Flexible AC Transmission System] 2 . 3
Electrical grid managementThe FACTS system can improve performance of transmission and disribution grid.Installing the FACTS suitable points in the grid can increase transfer capability andreduce losses while maintaining a voltage profile under different network conditions.The dynamic stability of the grid can also be improved, and active power oscillations mitigated.
Power
Time
Without FACTS
With FACTS
VoltageFault
Time(seconds)���
���
���
��!
� �� ��� ��� ���
Without FACTS
With FACTS
Power quality stabilizationIn industrial applications, the electronic rectifiers applied to the electrolysis power supply andmill machine requires large amount of reactive power.The use of arc furnace usually comes with voltage fluctuation and flicker and large harmonics.Large amount of reactive power demand and reactive power variation result in the voltagefluctuation and flicker, which also reduces the operation efficiency.The FACTS system can supply sufficient reactive power as well as eliminate the harmonicsgenerated by rectifiers and prevent the equipment from the voltage fluctuation.
Voltage
Time
Without FACTS
With FACTS
Arc-
furn
ace
P (p
,u)
Without FACTS
With FACTS
Arc-furnace A (p,u)
���
�
���
����
� ���
Harmonic filtersReactorsSVC valveCapacitor banksSVC control & protection system
SVC main components• SVC transformers• Circuit breaker• Thyristor valve
- Thyristor Controlled Reactors (TCR)- Thyristor Switched Capacitors (TSC)
• Cooling system• Harmonic filters• Control & protection
1 2
3 4 5
FUTURING SMART ENERGY
Control & protection
TCR TSC Harmonic filters
SVC control & protection systemStandard equipment for closed-loop and open loop control, commercially available and in use for multiple applications.Programming and customization of control functions are simplified by the use of a graphical programming interface.(LSIS' OPAS : Open Process Automation System)
• Multiple control modes can meet the requirements of different industry fields- Voltage control - Flicker compensation - Manual susceptance regulation- Unbalance contol - Reactive power control- Power factor control - Negative sequence control
• High accurate control angle(0.01°), large control range(95°-175°)• Full redundancy system(optional)• User optimized HMI(Human Man Interface)• Reliable protection scheme• Fast response time
SVC HMI (OWS)
SVC C&P panelSVC C&P System Configuration
C&P : Control and Protection EWS : Engineering Workstation DPC : Data Processing Center OWS : Operating Workstation
DPC AEWS/OWS
DI/DO/Field IO
DS PSCBTCR TSC
FieldPT
CT
PT
CT CB
TCRVBE
TSCVBE
DI/DO/Field IO
TCRFP
TCRFP
TSCFP
TSCFP
DPC BEWS/OWS
TFR
C&P A
AI/GPIO AI/GPIO
C&P B
GPS SCADA
C&P
StatusV&IV&I
Status
SCADA LAN
SVC Eng. tool (EWS)
Operation Panel VBE PanelC&P Panel(A/B)Field I/O Panel
Smart SVC Center in ulsan, Korea
Configuration of C&P system
FACTS [Flexible AC Transmission System] 4 . 5
Control and protection• Fully redundant system• Easy parallel operation• Remote control and monitoring• Self-diagnosis
AC yard(Reactor)• Harmonic filter(optional)• Small footprint reactor• Simple connection
Submodule and valve tower• Modular design• High speed bypass switch(Operating time 2ms)• Long life time• Easy maintenance
Valve cooling system• Easy user interface and maintenance• Low acoustic noise• Flexible layout of heat exchangers
(Roof or Ground)
FUTURING SMART ENERGY
Control & protection
STATCOM main components• STATCOM transformers• Circuit breaker• MMC valve• Cooling system• Control & protection
12m13.8m
20.25m
11.2
m
13.2
m
• Container type 50Mvar STATCOM • Container type 100Mvar STATCOM
FACTS [Flexible AC Transmission System] 6 . 7
STATCOM control & protection systemSTATCOM submodule and valve towerArm reactorsSTATCOM valve cooling system
1
3
4
2
TechnologyDue to the MMC(Modular Multilevel Converter) technology, the degree of harmonic generation emission is quite small.
Specifications & VI charicteristicTypical specifications of LSIS can be changedby requirements of customer, also can beoptimized according to condition.The STATCOM can be installed in a containeror building types, depending on the systemvoltage and capacity
FUTURING SMART ENERGY
Inductive operation Vcon V
Vcon V
V
V jXI
Vcon jXI
Vcon
Vcon = V
V
Vcon
V
Vcon
V
Vcon
VVcon
Capacitive operation
V
VCON
VCON V
I
I
I=0
I
I
No load operation
Busbar
20Mvar ~ 200Mvar
Up to 12kVL-Lrms (Without Transformer)
Above 13kVL-Lrms (With Transformer)
-connection
Less than 1.5%
Less than 16ms
Deionized water
Voltage regulationReactive power control
Voltage unbalance controlPower factor control
Flicker control
OV, UV, OC, SC, etc.
20 years
Container(45ft) / Building
Rated power
Rated voltage
Connection type
System loss
Response time
Cooling system
Control mode
Protection mode
Life time
Installation type
1.31.2
1.0
0.8
0.5
1.0 0.5 Iprim(p.u) 0.5 1.0
VI charicteristic & conrol performanceSystem voltage suppot and stabilization by smooth but fast( 16ms) control over a wide range of operating conditions.Contorl system maintain submodule capacitor voltage ripple lower than 10%.A dynamic response is follow the system contingencies.
FACTS [Flexible AC Transmission System] 8 . 9
STATCOM V-I characteristic
Capacitive Inductive
V prim(p.u)
Detailed waveform
System voltage [kV] Submodule capacitor voltage [kV]System, Arm, Cluster current [kA]
1. DC Dielectric Test2. Impulse test3. C&P test4. Synthetic test5. AC dielectric test
FUTURING SMART ENERGY
LSIS’ busan HVDC plant, established in 2011, is the first and only facility in Korea.HVDC & FACTS valve development, production and various DC tests includingC&P(Control & Protection) are available.
Busan HVDC/FACTS plant
1 2 3
5
4
1. Valve dielectric test2. Valve synthetic test
1 2
ProposalOptimum installation locationSystem capacityFeasibility study Detailed design
Configuration of control & protection designControl functionsSystem components detail design
System designHVDC/FACTS configurationHarmonics distortion limitEquipment ratingLoss and cost evaluation
ManufacturingValveTransformerControl & protection
Construction &commissioning
Maintenance
Condition analysis
FACTS [Flexible AC Transmission System] 10 . 11
Total solution provider
LSIS provides total HVDC & FACTS solution from systemdesign, equipment design, manufacture & tests,commissioning, and maintenance. Proposal is optimizedby customer’s needs, use condition and location.
General process
Seoul
Anyang
Dokdo
Ulleungdo
Cheongju
Busan
Ulsan
Jeju
Cheonan
Smart SVC center, Ulsan
Power TR plant, Busan
HVDC/FACTS plant, BusanHVDC smart center, Jeju
LS tower, Anyang
R&D campus, Anyang
Head OfficeLS Tower, LS-ro 127, Dongan-gu, Anyang-si, Gyeonggi-do, 14119, KoreaTel. 82-2-2034-4784, 4890, 4849 Fax. 82-2-2034-4755
R&D campusLSIS R&D Campus, LS-ro 116beongil 40, Dongan-gu, Anyang-si Gyeonggi-do 14118, KoreaTel. 82-31-8090-7787 Fax. 82-31-8090-7250
Busan HVDC/FACTS plantHwajeon-sandan2ro 9,Gangseo-gu, Busan, 46739, KoreaTel. 82-51-711-8040 Fax. 82-51-711-8089
Busan plant1-19 Block Hwajeon-dong, Gangseo-gu, Busan, 46735, KoreaTel. 82-51-795-6114 Fax. 82-51-795-6169
Cheong-ju plant1 Songjeong-dong, Cheongju-si, Chungbuk-do, 28439, KoreaTel. 82-43-261-6114 Fax. 82-43-261-6602
Overseas subsidiaries• LSIS Shanghai Office (China) Tel: 86-21-5237-9977 Fax: 86-21-5237-7189 E-Mail: [email protected]
• LSIS Beijing Office (China) Tel: 86-10-5761-3127 Fax: 86-10-5761-3128 E-Mail: [email protected]
• LSIS Guangzhou Office (China) Tel: 86-20-8326-6784 Fax: 86-20-8326-6287 E-Mail: [email protected]
• LSIS Qingdao Office (China) Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 E-Mail: [email protected]
• LSIS Chengdu Office (China) Tel: 86-28-8670-3200 Fax: 86-28-8670-3203 E-Mail: [email protected]
• LSIS ShenYang Office (China) Tel:86-24-2321-9050 Fax: 86-24-8386-7210 E-Mail: [email protected]
• LSIS Jinan Office (China) Tel: 86-531-8699-7826 Fax: 86-531-8697-7628 E-Mail: [email protected]
• LSIS Co., Ltd. Tokyo Office (Japan) Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: [email protected]
• LSIS Co., Ltd. Rep. Office (Vietnam) Tel: 84-8-3823-7890 E-Mail: [email protected]
• LSIS Moscow Office (Russia) Tel: 7-499 682 6130 E-Mail: [email protected]
• LSIS Jakarta Office (Indonesia) Tel: 62-21-293-7614 E-Mail: [email protected]
Specifications in this catalog are subject to change without notice due to continuousproduct development and improvement2018. 10 2016. 10 LSIS Co., Ltd. All Rights Reserved. / (03) 2018. 10 Hu man Power