Page 1 of 49 Partial Discharge Testing Of Aerospace Electrical Systems Faisal Alrumayan, Student Member, IEEE, Ian Cotton, Senior Member, IEEE and Andrew Nelms, Student Member, IEEE Abstract Modern aircraft are using more electrical equipment and are therefore using higher voltages. These higher voltage systems will become increasingly common in the future. The forms of system that are being used operate under frequencies/waveshapes different to those normally used on ground based electrical power systems and the testing regimes are relatively undeveloped in comparison to the other standardized tests available for aerospace components. This paper firstly introduces the reasons why higher voltage systems in aircraft may be susceptible to partial discharge. It then introduces two electrical test techniques that can be used to measure partial discharge activity. One of these, the balanced technique, is used to examine the partial discharge performance of four test objects that are stressed with high voltages at varying frequencies of both sine and square waveforms. The results that are presented show that while the level of damage that can be attributed to partial discharges can be significantly increased as frequency rises, the inception voltage of such discharges does not significantly vary. Index Terms— Aircraft power systems, Aircraft testing, High-voltage techniques, Partial discharges, Insulation testing, Insulation

Faisal Alrumayan, Student Member, IEEE Senior Member, …

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 1 of 49

Partial Discharge Testing Of Aerospace Electrical Systems

Faisal Alrumayan, Student Member, IEEE, Ian Cotton, Senior Member, IEEE and

Andrew Nelms, Student Member, IEEE

Abstract

Modern aircraft are using more electrical equipment and are therefore using higher

voltages. These higher voltage systems will become increasingly common in the future.

The forms of system that are being used operate under frequencies/waveshapes different

to those normally used on ground based electrical power systems and the testing regimes

are relatively undeveloped in comparison to the other standardized tests available for

aerospace components. This paper firstly introduces the reasons why higher voltage

systems in aircraft may be susceptible to partial discharge. It then introduces two

electrical test techniques that can be used to measure partial discharge activity. One of

these, the balanced technique, is used to examine the partial discharge performance of

four test objects that are stressed with high voltages at varying frequencies of both sine

and square waveforms. The results that are presented show that while the level of damage

that can be attributed to partial discharges can be significantly increased as frequency

rises, the inception voltage of such discharges does not significantly vary.

Index Terms— Aircraft power systems, Aircraft testing, High-voltage techniques, Partial

discharges, Insulation testing, Insulation

Page 2: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 2 of 49

I. INTRODUCTION

Electrical systems in the generation of aircraft currently in use tend to be a mix of AC and

DC. DC systems are typically operated at 28 V while the AC system operates at 115 V

rms (equivalent to 163 V peak phase to earth or 282 V peak phase to phase). The use of

these voltages has historically provided a safe and reliable means of energy transport with

the main risk being from electrical tracking. With the advent of technology such as the

More-Electric-Aircraft, there are increased electrical power demands on the engines and

this power must be transmitted across the airframe [1]. The increase in electrical power

demand is due to the desire to eliminate heavy mechanical systems such as air-starter

pipework and hot-air anti-ice systems. The replacement of such systems with electrical

alternatives will provide significant aircraft efficiency benefits resulting in better

environmental performance due to reduced fuel consumption. Boeing quote that the

advantage of the new electrical architecture used on the 787 will lead to a 35 % power

reduction as a result of using electrical power to displace pneumatic air demands on the

engine (such bleed air having largely being used for the environmental control system)

[2]. Some authors suggest that hybrid AC/DC systems will be used in the future with both

of these operating at higher voltages [3].

The significant levels of electrical power that will need to be transmitted between systems

on these More-Electric-Aircraft cannot, however, be efficiently transported at current

voltage levels. The continued use of low voltages to transmit the required power is

unsustainable as voltage drop becomes an increasing problem as does the conductor size /

weight which would increase. An increase to higher voltages would help solve these

Page 3: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 3 of 49

problems but would introduce others, namely the increased probability of electrical

discharge. The use of modern power electronic systems and generators driven directly at

variable speeds from the engines will also result in the existence of these higher voltages

at varying frequencies in the form of both sine wave and variable duty cycle square wave

forms.

In a system with a peak voltage below approximately 327 V, there is no possibility of

electrical discharge across an air gap during normal operating conditions. This statement

is based on the well established Paschen’s law that is illustrated graphically as shown in

Figure 1.

Page 4: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 4 of 49

Fig. 1. – Paschen’s curve (breakdown voltage of a gap against pressure x distance

product) in air for uniform field gaps

The figure shows that the breakdown strength of air varies according to the product of the

gap size and the gas pressure. The shape of the curve is defined by the processes

governing ionization of particles by electrons being accelerated by the electric field

within the air gap. Importantly, the figure shows that no breakdown is possible in an air

gap when a voltage of less than 327 V (231Vrms) [4] is applied to it (this figure being

Paschen’s minimum and changing slightly depending on the electrode material). The

exact shape of the curve, particularly the ascending portion on the right hand side, will

also depend on electrode geometry.

Page 5: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 5 of 49

As the voltage levels used in most previous generations of aircraft have been lower than

327 V peak, they have effectively been designed with electrical systems that cannot be

subject to an electrical discharge across air gaps during normal conditions (transients

from events such as lightning could, however, always cause a discharge event). This is

clearly desirable from a safety perspective. Raising the operating voltage of future aircraft

introduces the prospect of breakdown taking place in the electrical system should the 327

V threshold be passed (as would be the case in the modern aircraft systems that are

intended to operate at either 230Vrms phase to earth or +/-270DC).

The electrical discharges that could occur in the aircraft operating at higher voltages can

be subdivided into two types; partial discharges (PD) and disruptive discharges. The first

of these, the partial discharge is the formation of an electrical discharge that does not

completely bridge the gap between two conductors. It is often described as corona but this

is just one form of partial discharge. A partial discharge is characterized by a small flow

of charge, often in the region of 10-1000 pC, the production of light/sound and the

degradation of surrounding insulation (thermally, by chemical attack from resulting

ozone, by electrical discharge machining or by the impact of UV light). The duration of a

partial discharge varies between a few nanoseconds and a few microseconds.

A disruptive discharge, otherwise known as an electrical breakdown, occurs when the gap

between two conductors is fully bridged by a discharge. A disruptive discharge will result

in the flow of fault current and would normally require the operation of a protective

Page 6: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 6 of 49

device such as a fuse or circuit breaker to end the flow of current. This paper does not

discuss the testing of electrical systems with respect to disruptive discharges as this is

normally achieved by a simple high voltage (flash/HIPOT) test.

Two main issues are investigated in this paper in order to further understand the behavior

of partial discharges in an aerospace environment. Firstly, the dependence of partial

discharge behavior on the type of voltage waveform stressing the insulation is an

important factor to understand when designing insulation systems. Systems could operate

under DC, variable frequency AC or pulse width modulated (squarewave) voltage and the

partial discharge behavior of the insulation system will not necessarily be the same for

each of these. Secondly, testing of insulation systems using voltages that are ‘non-

standard’, i.e. not 50 Hz/60 Hz is difficult for reasons that will be explained. The paper

therefore ascertains the suitability of standard 50 Hz/60 Hz test methods in determining

the partial discharge inception voltages of insulation systems operating at other

frequencies / under non-sinusoidal waveshapes.

Before the experimental testing that was performed as part of this work is described, it is

appropriate to discuss the significant work that has been reported by other authors in

relation to the development of higher voltage systems in low pressure environments.

Much of this work has been related to space applications with the remainder mainly

examining the application of higher voltages to military systems. Bilodeau, Dunbar and

Sarjeant in a paper from nearly twenty years ago discussed the increased demand for

higher voltage usage in space power systems owing to the need to reduce the weight that

Page 7: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 7 of 49

would result from the use of lower voltage systems [5]. The paper discussed different

ways in which components could be tested and proposed an adjustment in the partial

discharge test voltage at 50/60Hz to account for reduced partial discharge inception

voltages at higher frequencies.

Many other papers examine some of the basic issues relating to the operation / testing of

higher voltage systems in a low pressure environment. An experiment was conducted by

Dunbar et al [6] in which a wire was stressed with high voltage to determine the effect of

high frequency at high altitudes. His results indicate a reduction in the partial discharge

inception voltage of around 15% at frequencies above 40 kHz for an altitude of 33000 ft.

This is compared with other authors work and is found to match with other results.

Dunbar suggests in another paper [7] that partial discharge can cause significant numbers

of failures in high voltage systems. In [8], along with Dobbs and Tarvin, Dunbar

describes a high voltage design guide that was developed for the US Air Force Materials

Lab and that gives guidelines on electric fields, material and processing choices,

packaging, manufacturing and testing. One of the issues discussed is that encapsulation

that can be sometimes be used to try and prevent high voltage problems can actually be a

source of them through the introduction of void discharge. Another general paper is that

by Brockschmidt [9] who discusses the problems associated with the operation of higher

voltage systems in a low pressure environment and discusses the fact that the voltage

required to sustain partial discharge can be lower than that required to initiate it. Karady

et al [10] examined the corona inception voltage of simple electrode geometries including

ones that involved thin layers of electrical insulation. The authors show that for certain

Page 8: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 8 of 49

experimental arrangements, corona inception can take place at voltages lower than

Paschen’s minimum.

In 1994, Hammoud and Stavnes [11] conducted a breakdown test on different types of

cables. A reduction in the breakdown voltage of 20% occurred when using a testing

frequency of 400 Hz at 200oC. In this case, the reduction in breakdown strength was

attributed to an increased dielectric loss at the higher frequency (this being a solid test

object and not a gas). A study was conducted on polypropylene cable by [12] at different

frequencies, ranging from 50 to 400 Hz. The results of these tests correlated with [11] in

that breakdown voltages of such insulation could fall as a function of frequency. This

paper also examined the corona initiation voltage of wires coated with this insulation and

found the impact of frequency was not as severe as that seen on the breakdown voltage.

Many other pieces of literature exist that examine the impact of voltage frequency on

breakdown and partial discharge inception at sea level. A number of these are useful in

further understanding of the topics discussed within this paper. Kurihara et al [13] discuss

the effect of a higher frequency voltage (created by superimposing a higher frequency

signal onto a lower frequency fundamental) on an air filled void. As the frequency of the

higher frequency component increased, the partial discharge inception voltage fell. In

contrast, they reported little change in the inception voltage of partial discharge within an

air filled void for a fundamental frequency between 6Hz and 1kHz. A dramatic increase

in the number of partial discharge pulses per second did however occur. Cavallini [14]

provides a theoretical analysis of the impact of frequency on partial discharges taking

Page 9: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 9 of 49

place within voids of solid insulation. These are then contrasted with test results that

show a significant effect of frequency on the phase distribution of partial discharge

pulses. The main conclusion of the work was that systems operating at lower frequencies

may be subject to lower numbers of partial discharges but that these would be larger in

magnitude.

Not all authors agree on the variation of inception voltage and/or discharge magnitude as

a function of frequency (although generally test objects vary). Plessow and Pfeiffer [15]

have carried out work examining the impact of frequency on the partial discharge

inception voltage of various materials including a ceramic, a polyester and a phenolic

resin. They report increases in partial discharge inception voltages as a function of

frequency. They also report higher discharge magnitudes as a function of frequency [15].

Meanwhile, work by Wilder and Hebner states that no variation in inception voltage is

reported as a function of frequency [16]. They also showed a different in behavior

between samples that had been previously exposed to high voltage and those tested as

new.

A number of authors have examined the impact of squarewave voltages on partial

discharge but such work has usually been focused on enameled wire [17],[18]. One

exception is [16] that looked at material samples of PVC and PE. Discharge inception

voltages are shown to reduce with temperature in [17] but there is no comparison with

standard test frequencies within this work. An analysis of the impact of space charge on

partial discharge in enameled wires is presented in [18]. The work shows a difference in

Page 10: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 10 of 49

partial discharge inception voltages depending on whether a bipolar or monopolar

waveform is applied, the difference being a result of space charge accumulation. The

work suggests that the partial discharge inception voltage is largely unchanged as a

function of frequency. An increase in the partial discharge inception voltage of PVC

samples was attributed to a decline in permittivity as frequency increases in the tests

carried out in [19].

II. EXPERIMENTAL ARRANGEMENTS

A. Test Objects

Within this paper, four specific types of partial discharge are produced in experiments.

They are corona discharge, void discharge, surface discharge and discharge in an air gap

formed by an insulated wire and a plane.. The test objects will now be described in more

detail. Reference should be made to Figure 2 which details the design of the different test

objects and Table 1 which describes the environmental conditions during the test. It

should be noted that the tests for corona discharge and surface discharge were carried out

at atmospheric pressure so the magnitudes of voltages reported for these cases should not

be directly applied to the aerospace environment.

Corona discharge occurs when the highest electric field in a gap with a non-uniform field

distribution exceeds a threshold value. Local ionisation takes place without breakdown as

the field is too low in other parts of the gap for the discharge to propagate between the

two electrodes. For these experiments, the non-uniform field required was produced using

a (sharp) needle to plane electrode geometry where the needle was connected to the high

Page 11: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 11 of 49

voltage test supply and the plane was earthed. A separation distance of 2 mm was

maintained between the two electrodes and the specific details of the needle type are

contained in [20]. In an aircraft, corona discharge could take place where sharp edges are

found whether these be created inadvertently or by design. A loose wire strand would be a

typical source of corona discharge.

Void discharge occurs in inhomogeneous areas of bulk insulation formed by gas bubbles.

These gas bubbles enhance the electric field owing to a difference in permittivity between

the gas and the surrounding bulk insulation. The shape of the void can therefore

contribute to field enhancement within the void. If the electric field in the void becomes

high enough, a partial discharge will take place within that void. As long as enough bulk

insulation remains, a disruptive discharge will not take place but cumulative damage over

time could lead to this situation. To produce this test object, an insulated wire had silver

paint applied to it to ensure that the electric field was contained within the insulation. A

semiconducting varnish was then used to paint the two extreme ends to provide local

electric field control and ensure that only void discharge would take place in this test

object. In an aircraft, this form of electrical discharge could take place in any wiring

system irrelevant of whether screening was present on the outside of such wires.

Surface discharge occurs when the electric field on the surface of a material exceeds the

electric strength of that interface, the discharge typically propagating in the air across the

surface. For these tests, a brass disk with a 12.75 mm diameter was attached to a square

sheet of Teflon (PTFE) material that was 400 mm2 in area and 2 mm thick. This sheet

Page 12: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 12 of 49

was then placed onto a copper ground plane. In an aircraft, surface discharge could take

place on surfaces of connectors, the outside of power electronic modules, across circuit

boards and other similar locations. Other materials other than PTFE have been tested and

some photographs of the type of damage that occurs to these is presented later in this

paper.

Wire to plane discharge can occur when a large enough insulation thickness is not defined

in an aerospace system. In any small air gaps formed between the wire insulation and

another grounded electrode, the electric field can exceed that required to a partial

discharge. A disruptive discharge will not occur as long as the bulk insulation of the wire

remains sound. For these experiments, a wire with an insulation thickness of 0.3 mm and

a conductor radius of 0.3 mm was placed above a plane electrode. This wire is a type that

is designed for use in modern aircraft power systems. The wire was in contact with the

plane electrode for an approximate distance of 5 cm, the ends of the wires then rose off

the plane. Discharge was expected in the region where the wire lifted off the plane. In an

aircraft this form of discharge could take place between two wires, where a wire moves

against a grounded object (a ground plane or a duct) or when wires move into a

connector.

Page 13: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 13 of 49

Fig. 2. Block diagram of the four test objects. (a) Corona (b) Void (c) Surface (d) Wire To

Plane

Test Object Temperature(°C) Pressure(bar) Relative

Humidity (%)

Corona 20 ±2 1 N/A

Void 20 ±2 0.1 N/A

Surface 20 ±2 1 25%

Wire To Plane 20 ±2 0.1 N/A

Page 14: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 14 of 49

Table 1: Environmental Conditions During HV Tests

B. Test Circuits

Many methods exist for partial discharge detection exist. Historically, most

measurements have used electrical systems to detect partial discharge. These systems will

be discussed in more detail below as they are the ones that have been used within this

paper. However, alternatives do exist and these are summarized in detail in [21]. A brief

discussion of possible alternative measurement techniques is, however, presented.

• Electromagnetic Radiation (RF): When a PD pulse takes place, it is

accompanied by the emission of electromagnetic radiation. The measurement systems

used to detect discharge in this way tend to focus on the frequency range from 5 to

100MHz. While RF measurements may not always be as sensitive as electrical

measurements, according to [22] they are able to measure discharge as low as tens of

pico-coloumbs and have the added benefit that they can distinguish between more than

one discharge site. They are not, however, able to give a measurement of partial discharge

that can be directly correlated with the typical measurements given by electrical detectors.

• Acoustic method: This method is based on detecting the pressure waves that are

Page 15: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 15 of 49

associated with a discharge in the test object. The higher the energy on the PD pulse, the

higher the intensity emitted of the acoustic waves [23]. The detected signal measured by

acoustic sensor significantly depends on the characteristic of the test object (in terms of

the acoustic propagation path from source to sensor), the location of the discharge and the

sensor itself. A sensitivity of around 10pC at best is claimed in the referenced paper.

• Optical techniques: The final method used for partial discharge detection

measures light emission from PD sites. Some types of partial discharge, especially

corona, produce light with a magnitude proportional to the PD pulse energy [21]. The

spectrum of the emitted light depends on the surrounding dielectric material [24]. A

sensitivity as low as 0.3pc is claimed in [25] when a photomultiplier is used. However, a

clear disadvantage of this technique is that it cannot detect internal forms of discharge.

The advantage of all of these methods is their immunity to interference, their ability to

detect PD no matter what waveform is used to energise the test object and their ability to

not be subject to electrical noise from surge voltages any other lower frequency signals

that are conducted through the electrical circuit. However, owing to the relatively low

sensitivity of the RF/Acoustic techniques, the inability to directly measure charge values

with any method and the inability of the optical technique to see internal discharges,

electrical techniques have been used for this study.

1) Unbalanced Detection Method

The basic PD detection circuit used by many laboratories is the unbalanced (or straight)

detection circuit as shown in Figure 3 and described by IEC 60270 [26]. The current

Page 16: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 16 of 49

generated by the test object (TO) as a result of a partial discharge is very fast with a

maximum time duration in the order of tens to hundreds of nanoseconds seconds. This

pulse current flows through the measuring impedance (MI) and then through the coupling

capacitor (CC) which is provided to form a low impedance loop for the PD current. A

resistive impedance is often included between the test object and the voltage source to

limit current flow in the event of test object failure.

Fig. 3. – Block diagram of straight detection circuit (unbalanced detector)

The measurement impedance can also be connected between the coupling capacitor and

the ground. In this case, the circuit would not have the disadvantage of significant levels

of current flowing through the measurement impedance should the test object fail.

Page 17: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 17 of 49

However, any PD signal is split between the coupling capacitor and any circuit stray

capacitance reducing the sensitivity of the circuit. In this configuration it would be

normal to maximize the value of the coupling capacitance to reduce the effect of any stray

capacitance.

In either case, the PD current passes through the measurement impedance along with any

current flowing as a result of the voltage used to energize the circuit [27]. It is the current

that flows from the power supply and through the measurement impedance that means

that there is an inherent difficulty in carrying out measurements at high frequency. The

reasons for this stem from the characteristics of the measurement impedance.

The wide band system used in most commercial PD detectors requires a measurement

impedance that is effectively a bandpass filter with a pass band magnitude of between

100kHz and 400kHZ. The filter has a high pass cut-off frequency between 30kHz and

100kHz and a low pass cut-off frequency of less than 500kHz. All of these values are

taken from the IEC standard on partial discharge measurement [26]. Other commercial

systems do exist that do not use these exact filter values. The use of this filtering

arrangement means that the output of the circuit is a voltage pulse whose pulse height is

proportional to the integral of the current, i.e. the pulse height is proportional to charge.

As partial discharges are normally quantified in terms of charge, this is a useful

experimental arrangement. The use of a band-pass filter also means that the narrow

partial discharge pulses are widened as the high frequency components are removed. This

means the system has a prescribed pulse resolution time. This is typically in the range of 2

Page 18: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 18 of 49

µs to 10 µs and means that partial discharges occurring more frequently than this will

appear overlapped on the recording instrument.

However, in the context of this paper, the response of this LCR impedance to higher

frequency or non-sinusoid voltages is a fundamental consideration. For a circuit supplied

by sinusoidal voltages, the amount of current flowing through the measurement

impedance increases with frequency as the reactance of the test object falls. This therefore

reduces the detection sensitivity in the circuit as a larger PD pulse is required for it to be

seen over the ‘noise’ produced by the flow of power frequency current. In addition, as the

frequency of the noise moves further into the pass-band of the filter, the measurement

impedance does not filter this as significantly as it would lower frequencies. The result is

a dramatic reduction in the detection threshold when using the circuit at higher

frequencies. Experience has shown this circuit adequate to frequencies of a few hundred

hertz. The response of the circuit to a squarewave source of the form produced by a PWM

voltage supply gives more significant difficulties. The application of a squarewave

voltage across the circuit will cause a large current to flow through the test object and the

coupling capacitances during the rising and falling edges. This significant level of current

will swamp any signals produced by PD pulses taking place during this transition period.

Figure 4 shows the noise levels measured in an unbalanced test circuit for sinewave

energisation with a test object capacitance of 750 pF, a coupling capacitance of 1 nF and

a test voltage of 1kV pk-pk. The 10 pC threshold that is often taken to be acceptable for

measurement is passed for frequencies above 400 Hz. The noise during the squarewave

Page 19: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 19 of 49

voltage energisation is constant as a function of frequency as it is based on the rise time

of the voltage pulse that in this work was fixed at around 40µs. A noise level of 10,000pC

was measured in this case using an unbalanced test circuit for a 1kVpk-pk waveform, a

value well in excess of the partial discharge levels that need to be measured in a circuit.

1

10

100

1000

0 500 1000 1500 2000

Frequency (Hz)

No

ise level (p

C)

Fig. 4. Noise level measured in a test at varying frequencies using a straight detection

method

Several techniques are mentioned in literature that could allow these noise problems to be

overcome. These methods include Fast Fourier transform-based techniques (FFT),

wavelet transform techniques (WT) and digital filter techniques [28]-[31]. In FFT-based

methods, the time domain signal is transformed into the frequency domain before being

Page 20: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 20 of 49

manipulated to eliminate unwanted noise. The de-noised signal is then converted back

into the time domain by using an inverse Fourier Transform (IFT). In contrast, while

Fourier transforms decompose the PD signal into sine-waves of various frequencies,

wavelet transforms involve multi-resolution decomposition techniques that owing to the

non-periodical and broadband nature of PD signal means that they have an enhanced

ability to extract information from a noisy signal [28],[32]. Digital filters can be classified

into two types: Finite impulse response (FIR) and Infinite impulse response (IIR). In such

methods the input signal is transformed into a digital form using digital signal processing

techniques. Filter coefficients of theses approaches can then be implemented either in

hardware (Digital Signal Processors) or software. While these two filters work well with

noise of a specific frequency spectrum (i.e. narrowband), they may become inefficient

with broadband noise signals.

All of these methods have been able to reduce noise in partial discharge measurement

circuits to acceptable levels. However, they all rely on post-processing and the input

signal has to firstly be captured. If the magnitude of the noise produced in the circuit is

significantly higher than the signal itself, no post-processing of that signal will be able to

denoise it should the resolution of the measurement system be unacceptably low. For this

reason, an alternative means of reducing the noise level was used that also complies with

the requirements of IEC 60270.

2) Balanced Detection Method

The alternative PD detection circuit that can be used for measurements is a balanced

Page 21: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 21 of 49

circuit where two test objects are tested, each one acting as the coupling capacitor for the

other. If the test object impedances are perfectly matched, the equal flow of power supply

current through each test object can be removed using an LCR impedance made up of

differential windings. This will significantly reduce noise levels if operated properly.

However, the test objects need to be clearly matched or additional tuning impedances

need to be provided in the circuit and this is not always straightforward.

Fig. 5. Block diagram of balanced circuit

The balanced circuit shown in Figure 5 can be practically realized by forming L1, L2 and

L3 from a three winding transformer with 1:1:1 turn ratios. The transformer should be

wound so that L3 gives the output of the signal through L1 minus that of L2. The

transformer windings can be designed to provide a given inductance and extra

Page 22: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 22 of 49

resistance/capacitance can be placed in parallel to achieve the bandpass characteristic

desired.

This type of experimental arrangement was used in the testing described to minimise

noise levels. It would not normally be required if tests were to be carried out with 50

Hz/60 Hz only. The maximum noise level in the testing carried out was 12 pC. This was

achieved even under squarewave voltage energisation.

III. EXPERIMENTAL TEST RESULTS

A. Experimental Apparatus

The circuit diagram of the test arrangement is shown in Figure 6. A Trek power amplifier

rated at 2.5 kW and 20 kV peak supplied the test voltage. It was controlled using a 20 V

pk-pk signal generator. Experimental data was collected using a fast oscilloscope with

results then being processed by Matlab. A commercial PD detector was not used as while

they are available from various manufacturers, they only work for sinewave and generally

not for frequencies above 400 Hz. However, the filtering characteristics of the circuit

used matched the requirements of IEC 60270. When testing with a squarewave, the rise

time of the voltage pulses was approximately 40 µs. The duty cycle of the waveform was

50 %. When the frequency is reported in the following sections, this frequency refers to

the inverse of the time between two rising edges (the rise time always being around 40us).

The experiments were carried out at room temperature.

Page 23: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 23 of 49

Filter

Out

V1

A1

A2

R1

R2 R3C3 C4

L1 L2

L3

Cto1 Cto2

A1 is High Voltage Amplifier

A2 is PD Amplifier

Fig. 6. Circuit diagram as used in experiments

In all of the experiments, the partial discharge inception and extinction voltages were first

measured over a frequency range of 50 Hz to 1 kHz. The inception voltage is the voltage

at which continuous PD activity is first recorded, the extinction voltage is the voltage at

which it stops. At each frequency, partial discharge data was then collected by applying a

voltage 10 % above the inception voltage. An average of 100 cycles of data was collected

for each frequency measurement.

B. Test Results

The test results for each sample are discussed in detail in the sections below.

Page 24: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 24 of 49

1) Corona Discharge

Corona discharge occurs when the electric field in an area of air is elevated to a value that

allows local ionisation to occur. The exact discharge processes are different for

positive/negative polarities and are discussed in detail in [4]. For negative corona, the

mode produced in the experimental arrangement used to produce the results for this

paper, partial discharges are seen at regular intervals whenever the electric field in the gap

remains high enough. In practice, this means that corona discharge only depends on the

voltage exceeding a given threshold. The form of discharge seen when applying a 200 Hz

sinewave or squarewave is observed in Figure 7. The y-axis in these figures corresponds

only to the magnitude of the signal coming into the PD detector and not to the

energisation voltage. This has not been converted to a level of apparent charge, this

information is presented in Figures 8 & 9.

50 100 150 200 250 300 350-2

-1.5

-1

-0.5

0

0.5

1

1.5

2

Phase

PD

Am

plit

ud

e (

V)

50 100 150 200 250 300 350-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

Phase

PD

Am

plit

ude (

V)

Fig. 7. Corona discharge patterns for squarewave and sinewave voltage energisation

In both cases, corona discharge can be seen to occur on the negative polarity waveform

and only when the voltage exceeds a given value. Corona would occur on the positive

half cycle if the voltage was increased further [33]. As the squarewave maintains the

Page 25: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 25 of 49

voltage at a constant value over the full half cycle, corona discharge can be seen for the

entire time of that half cycle. For the sinewave, the partial discharge only occurs in a

narrow window either side of the negative peak. This would imply that the expected

damage to insulation caused by corona discharge would be greater when produced by a

squarewave in comparison to a sinewave.

Figure 8 shows the inception and extinction voltages for corona discharge. For the

squarewave case, the peak to peak voltage given includes any overshoot (this is also the

case for graphs in future sections). The inception voltage required to cause corona

discharge was around 5 % higher with squarewave energisation in comparison to

sinewave. As there was around 10% overshoot on the squarewave voltage, it is likely that

the corona persisted for the full half cycle as the steady-state portion of the voltage was

above the extinction level. Both of the waveforms showed a reasonably consistent level

as a function of frequency. This is in contrast to Plessow’s finding in [15] in which an

increase in PDIV as function of frequency was noticed. An assessment of the damage that

could be caused by corona discharge has also been made by multiplying the average

charge of the corona discharge by the number of discharges per second.

Page 26: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 26 of 49

0.00E+00

5.00E+05

1.00E+06

1.50E+06

2.00E+06

2.50E+06

3.00E+06

3.50E+06

0 200 400 600 800 1000

Frequency (Hz)

Dam

ag

e (

pC

/s)

6

6.5

7

7.5

8

8.5

Ap

pli

ed

Vo

ltag

e (

kV

_p

k-p

k)

Damage_Sinewave Damage_Squarewave Ui_Sinewave

Ui_Squarewave Ue_Sinewave Ue_Squarewave

Fig. 8. Inception/extinction voltages and cumulative damage level for corona discharge

To understand why the damage that could be caused by corona does not vary

significantly, further information in the form of the number of discharges per unit time

and the average charge level are given as Figure 9.

Page 27: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 27 of 49

0

50

100

150

200

250

300

0 200 400 600 800 1000

Frequency (Hz)

Ch

arg

e (

pC

)

0.00E+00

2.00E+03

4.00E+03

6.00E+03

8.00E+03

1.00E+04

1.20E+04

1.40E+04

1.60E+04

N (

1/s

)

q_Sinewave q_Squarewave N_Sinewave N_Squarewave

Fig. 9. Corona discharge repetition rate of discharges (number per second) and average

charge as a function of frequency

As a function of frequency, the number of discharges in each cycle was seen to decrease.

This is to be expected as the time between negative corona discharge Trichel pulses is

driven by the degree of overvoltage applied to the gap [34]. In these experiments, a

constant level of overvoltage was applied to the gap so the time between pulses can be

expected to be constant. With a smaller half cycle time and a constant time between

discharges, fewer discharges could occur in a half cycle for higher frequency waveforms.

However, more cycles occur per second and it can be shown that this leads to an

effectively constant relationship between the number of partial discharges per second and

Page 28: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 28 of 49

the supply frequency. This is a simplistic analysis but broadly fits the weak increase in the

level of damage as a function of frequency that was observed in measurements.

The significant findings from these tests were the clear increase in level of damage caused

by squarewave voltages, the weak impact of supply frequency on either inception voltage

levels or damage and the fact that a test with a sinewave voltage would over-estimate the

inception voltage for a system energised with a squarewave.

2) Void Discharges

Void discharges take place within gas filled cavities in solid insulation. In most cases,

these voids will not be connected to an electrode and if discharged must be recharged by

the flow of current through surrounding insulation. For this to take place quickly, a

changing electric field is required. Models have been used by other authors to show the

variance of partial discharge within voids as a function of frequency and explain the

governing processes in more detail [35].

Figure 10 shows the partial discharge pulses and the voltage waveforms for both

sinewave and squarewave energisation. In the case of the squarewave, a single discharge

can be seen at the transition between half cycles. The absence of any change in voltage

between these transitions stops further discharges taking place in that half cycle. This is

due to the constant voltage between transitions allowing no charging through the

capacitance of the surrounding insulation but forcing them to recharge through the large

insulation resistance, a process that takes too long in comparison to the cycle time. In

Page 29: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 29 of 49

contrast, multiple pulses can be seen on the rising edges of the positive and negative half

cycles of the sinewave.

50 100 150 200 250 300 350-5

-4

-3

-2

-1

0

1

2

3

4

Phase

PD

Am

plit

ude (

V)

50 100 150 200 250 300 350-4

-3

-2

-1

0

1

2

3

4

Phase

PD

Am

plit

ud

e (

V)

Fig. 10. Void discharge patterns for squarewave and sinewave voltage energisation

Figure 11 shows the inception voltage and damage effect of void discharge as a function

of frequency. The inception voltage was highest for a squarewave, being around 13 %

above that of a sinewave when the supply frequency was low and around 6 % for higher

frequencies. Again, the peak to peak squarewave voltage is given. This now includes a

significant overshoot component (as can be seen in Figure 10).

Page 30: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 30 of 49

0.0E+00

1.0E+05

2.0E+05

3.0E+05

4.0E+05

5.0E+05

6.0E+05

0 200 400 600 800 1000Frequency (Hz)

Da

ma

ge (

pC

/s)

1.2

1.3

1.4

1.5

1.6

1.7

1.8

Ap

plie

d V

olt

ag

e (

kV

,pk

-pk

)

Damage_Sinewave Damage_squarewave Ui_Sinewave

Ui_Squarewave Ue_Sinewave Ue_Squarewave

Fig. 11. Inception/extinction voltages and cumulative damage level for void discharge

The damage caused by the discharge increased as a function of frequency in both cases.

This mainly due to an elevation in the number of partial discharge pulses as a function of

frequency as shown in Figure 12. The average charge of the discharges as a function of

frequency was fairly constant for both energisation types. Void discharges created by a

squarewave were of higher average charge. It is thought that this is a result of the

increased charge that can be deposited in the surrounding insulation during the steady

state period of the half cycle.

Considering damage done by partial discharge during squarewave energisation, with only

Page 31: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 31 of 49

one partial discharge per half cycle a linear relationship with frequency would therefore

be expected and this is what was found. The increase in damage as a function of

frequency for sinewaves is also due to an increase in the number of partial discharges per

second, this effect also being shown by Kurihara et al [13].

0

100

200

300

400

500

600

0 200 400 600 800 1000Frequency (Hz)

Ch

arg

e (

pC

)

0

1000

2000

3000

4000

5000

6000

7000

N (

1/s

)

q_Sinewave q_Squarewave N_Sinewave N_Squarewave

Fig. 12. Void discharge repetition rate of discharges and average charge as a function of

frequency

In summary, for void discharges high frequencies increase the level of damage to

insulation but do not significantly affect the inception voltage of partial discharge

measurements. Inception voltages measured with sinewaves were more conservative, i.e.

lower than those measured with squarewaves.

Page 32: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 32 of 49

3) Surface Discharge

Surface discharge takes place when the external electrical field strength exceeds the

dielectric field strength of the material. It is well known that this type of discharge is

highly influenced by charge accumulated on the surface, which will disappear or be

reduced when the field changes its polarity [36], [37]. The material used in these tests,

Teflon, is characterized by slow charge decay with time as it has a high surface resistivity

(low conductivity) [36]. Usually, surface discharge exhibits a higher charge magnitude (in

the order of nC) than other forms of discharge.

Figure 13 shows the PD pulses obtained from the two types of waveform. For

squarewaves, they appear at transitions between voltage polarities and they are very high

in terms of magnitude. For sinewaves, the partial discharges occur on the rising edges of

the positive and negative half cycles.

50 100 150 200 250 300 350

-3

-2

-1

0

1

2

3

Phase

PD

Am

plit

ude (

V)

50 100 150 200 250 300 350

-1.5

-1

-0.5

0

0.5

1

1.5

Phase

PD

Am

plit

ude (V

)

Fig.13. Surface discharge patterns for squarewave and sinewave voltage energisation

Figure 14 shows the inception voltage and damage caused to the PTFE. The maximum

Page 33: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 33 of 49

difference in inception voltages between the waveform types was less than 10 %,

squarewave inception voltages being the lower. Both the squarewave and the sinewave

cases show an increase in the level of damage as a function of frequency although this is

realized by different mechanisms.

0.0E+00

5.0E+05

1.0E+06

1.5E+06

2.0E+06

2.5E+06

3.0E+06

3.5E+06

4.0E+06

0 200 400 600 800 1000

Frequency(Hz)

Da

ma

ge

(p

C/s

)

6

7

8

9

10

11

12

13

14

Ap

pli

ed

Vo

lta

ge

(kV

_p

k-

pk

)

Damage_Square Wave Damage_Sine Wave Ui_Sine Wave

Ue_Sine Wave Ui_Square Wave Ue_Square Wave

Fig. 14. Inception/extinction voltages and cumulative damage level for surface discharge

For a sinewave, a roughly linear increase in damage as a function of frequency is

observed. As shown in Figure 15, the number of discharges per second increased as a

function of frequency while the average charge level remained the same. For a

squarewave, the number of discharges per second increases linearly (1 discharge per half

cycle) but the average charge level falls. However, as the average charge level falls

slower than the rate of increase number of discharges, the damage level still increases but

Page 34: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 34 of 49

at a slower rate. The fall in charge level as a function of frequency can be attributed to the

lower amount of charge deposition that can take place on the surface between discharges

as the frequency increases.

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

0 200 400 600 800 1000

Frequency (Hz)

Ch

arg

e (

pC

)

0

1000

2000

3000

4000

5000

6000

7000

N (

1/s

)

q_Sinewave q_Squarewave N_Sinewave N_Squarewave

Fig. 15. Surface discharge repetition rate of discharges and average charge as a function

of frequency

With surface discharge, it is easy to visually show the damage that can be caused to

materials. Figure 16 shows the severe damage done to acrylic and PVC material exposed

to a 50 Hz sinewave and a 1 kHz squarewave for a period of 24 hours. As dust can be

collected on this form of sample through electrostatic precipitation during testing, these

samples were cleaned before the photos were taken. The photos show very clearly that

those samples exposed to higher frequency voltages suffered more serious damage than

those exposed to 50 Hz. However, some materials are particularly resilient to such

Page 35: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 35 of 49

damage. One of these is PTFE, a material often used in aerospace applications. Figure 16

shows the damage done to PTFE material exposed to a 50 Hz sine wave (after 16 hours)

and a 1000 Hz squarewave. The amount of damage is not as severe as in the previous two

cases, partly owing to the high melting point of PTFE of around 327 degrees.

(a) Virgin Sample (Acrylic) (b) 50 Hz/Sinewave (C) 1 kHz/Squarewave

Page 36: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 36 of 49

(d) Virgin Sample (PVC) (e) 50 Hz/Sinewave (f) 1 kHz/Squarewave

Page 37: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 37 of 49

(g) Virgin Sample (PTFE) (h) 50 Hz/Sinewave (i)1 kHz/Squarewave

Fig. 16. Results from ageing tests of three different materials. Photos magnified by a

factor of 8.

In summary for surface discharge, high frequencies increase the level of damage to

insulation but do not significantly affect the inception voltage of partial discharge

measurements. Inception voltages measured with sinewaves were higher than those

measured with squarewave.

4) Wire To Plane Discharge

Wire to plane discharge occurs when the insulation thickness of a wire is not thick

enough and the electric field in the air surrounding the wire is high enough to cause a

discharge between the outside of the wire insulation and an earthed object such as a

ground plane. Figure 17 shows the form of discharge seen when applying the two

waveforms at 200 Hz.

Page 38: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 38 of 49

50 100 150 200 250 300 350-5

-4

-3

-2

-1

0

1

2

3

4

5

Phase

PD

Am

plit

ude (

V)

50 100 150 200 250 300 350-5

-4

-3

-2

-1

0

1

2

3

4

5

Phase

PD

Am

plit

ud

e (

V)

Fig.17. Wire to plane discharge patterns for squarewave and sinewave voltage

energisation

Figure 18 shows the inception, extinction voltage and damage to the wire as a function of

frequency. The inception voltage values for the two waveforms were very close and

tended to decrease slightly with increasing frequency. This is in contrast to [19] where

inception voltage was increased at high frequency.

Page 39: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 39 of 49

0.0E+00

2.0E+05

4.0E+05

6.0E+05

8.0E+05

1.0E+06

1.2E+06

1.4E+06

0 200 400 600 800 1000

Frequency (Hz)

Dam

ag

e (

pC

/s)

1

1.2

1.4

1.6

1.8

2

2.2

Damage_Sinewave Damage_Squarewave Ui_Squarewave

Ui_Sinewave Ue_Squarewave Ue_Sinewave

Fig.18. Inception/extinction voltages and cumulative damage level for wire to plane

Figure 19 shows the repetition rate and average charge used to calculate the expected

damage from wire to plane discharge. The level of damage seen by combining the

discharge rate with the average discharge magnitude increases as a function of frequency

for both the squarewave and the sinewave. The squarewave damage function is again

driven by the linear relationship between the number of pulses per cycle and frequency.

The sinewave damage rate is also determined by an increase in the number of partial

discharges as a function of frequency. In both cases the average charge seems to decrease

over the frequency range but more significantly in the case of the squarewave.

Page 40: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 40 of 49

0

200

400

600

800

1000

1200

1400

1600

1800

0 200 400 600 800 1000

Frequency (Hz)

Ch

arg

e (

pC

)

0.00E+00

1.00E+03

2.00E+03

3.00E+03

4.00E+03

5.00E+03

6.00E+03

N (

1/s

)

q_Sinewave q_Squarewave N_Sinewave N_Squarewave

Fig. 19. Wire To Plane repetition rate of discharges and average charge as a function of

frequency

In summary, for wire to plane discharge high frequencies increase the level of damage

to insulation but do not significantly affect the inception voltage of partial discharge

measurements. Inception voltages measured with sinewaves were higher than those

measured with squarewave.

IV. IMPLICATIONS OF TEST RESULTS FOR AEROSPACE SYSTEM TESTING

While scientifically interesting, the real benefit of the measurements presented is the

ability to use them to develop an understanding the behavior of higher voltage systems

Page 41: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 41 of 49

within an aerospace environment.

The first use of the results is to examine whether systems intended for use at higher

frequencies or those systems used squarewave voltages can be tested with a 50/60 Hz

sinewave system. In such a test being carried out for aerospace applications, the

importance would not be the magnitude of or the number of discharges. The inception

voltage would be the key measurement as you would not want a system to be discharging

in use.

The results show a contrast in behaviors of different test samples. Some show a higher

sinewave inception voltage, some show a higher squarewave inception voltage. The

magnitude of the difference varies but is no more than 20 %. This could partly be

explained by accuracies/tolerances of measurement equipment. As sinewave testing is

much easier, has lower noise levels and is very established as a laboratory technique, it

would seem prudent to recommend that testing was always carried out using this

technique. If necessary, a safety factor could be added to the inception voltage criteria to

account for operation of the insulation system under squarewaves. The testing showed a

bigger variation in the inception voltages according to whether a sinewave or a

squarewave was used in comparison to the frequency of the test. In this case, the

maximum variation in inception voltage was 15.6 % for sinewaves and 13.4 % for

squarewaves.

The results clearly showed that with the exception of corona, all the types of discharge

Page 42: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 42 of 49

exhibited a strong link between the level of damage that could be caused (measured

through the product of the average charge magnitude with the number of discharges per

second) and the frequency. The use of higher frequency systems in aircraft will mean that

partial discharges could have a severe impact on insulation. This was shown by tests on

PVC and acrylic materials. PTFE was also tested and was shown to be very resilient to

partial discharges.

V. CONCLUSIONS

The use of higher voltage systems in aircraft will lead to an increased likelihood of partial

discharge and the need for testing of equipment before it is used on an airframe will

therefore exist. The problems associated with standard partial discharge test circuits were

described, higher frequencies and squarewaves increasing the noise levels in the circuits.

This could be solved by the use of a balanced test circuit.

Inception voltages, average charges and repetition rates were measured for a range of

sample types of various frequencies for both a sinewave and a bipolar squarewave. The

inception voltages were shown to vary by no more than 20 % depending on the waveform

used within the measurements. The level of damage caused by partial discharge increased

significantly as a function of frequency in the majority of cases.

It is concluded that 50/60 Hz testing could be used for aerospace systems as long as a

safety margin is attached to the inception voltage criteria.

Page 43: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 43 of 49

REFERENCES

[1] Howse M, ‘All Electric Aircraft’, Power Engineer, Volume 17, Issue 4, Aug.-Sept.

2003, Page(s): 35 – 37

[2] www.boeing.com/commercial/787family/programfacts.html

[3] K. Emadi and M. Ehsani, "Aircraft power systems: technology, state of the art, and

future trends," Aerospace and Electronic Systems Magazine, IEEE, vol. 15, pp. 28-32,

2000.

[4] M. Abdel-Salam, H. Anis, A. El-Morshedy, R. Radwan, “High-Voltage Engineering,”

2nd ed, Marcel Dekker Inc. 2000.

[5] T. M. Bilodeau, W. G. Dunbar, and W. J. Sarjeant, "High-voltage and partial

discharge testing techniques for space power systems," Electrical Insulation Magazine,

IEEE, vol. 5, pp. 12, 1989.

[6] W. G. Dunbar, D. L. Schweickart, J. C. Horwath, and L. C. A. W. L. C. Walko, "High

frequency breakdown characteristics of various electrode geometries in air," presented at

Power Modulator Symposium, 1998. Conference Record of the 1998 Twenty-Third

International, 1998.

[7] W. Dunbar and J. A. Rugama, "Applying AVIP to high voltage power supply

designs," presented at Energy Conversion Engineering Conference, 1989. IECEC-89.,

Proceedings of the 24th Intersociety, 1989.

[8] B. Dobbs, W. G. Dunbar, and C. Tarvin, "High Voltage Design Guide summary,"

presented at Energy Conversion Engineering Conference, 1989. IECEC-89., Proceedings

of the 24th Intersociety, 1989.

Page 44: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 44 of 49

[9] A. Brockschmidt, "Electrical environments in aerospace applications," presented at

Electric Machines and Drives, 1999. International Conference IEMD '99, 1999.

[10] G. G. Karady, M. D. Sirkis, and L. Li, "Investigation of corona initiation voltage at

reduced pressures," Aerospace and Electronic Systems, IEEE Transactions on, vol. 30,

pp. 144-150, 1994.

[11] A. N. Hammoud, M. W. Stavnes, J. L. Suthar, W. A. K. W. Khachen, and J. R. A.

L. J. R. Leghari, "Testing of cable insulation for aerospace applications," presented at

Electrical Insulation, 1994., Conference Record of the 1994 IEEE International

Symposium on, 1994.

[12] W. Khachen and J. R. Laghari, "Polypropylene for high voltage high frequency

airborne applications," presented at Electrical Insulation, 1990., Conference Record of the

1990 IEEE International Symposium on, 1990.

[13] T. Kurihara, S. Tsuru, K. Imasaka, J. Suehiro, and M. Hara, "PD characteristics in

an air-filled void at room temperature under superimposed sinusoidal voltages,"

Dielectrics and Electrical Insulation, IEEE Transactions on [see also Electrical

Insulation, IEEE Transactions on], vol. 8, pp. 269, 2001.

[14] A. Cavallini and G. C. Montanari, "Effect of supply voltage frequency on testing of

insulation system," Dielectrics and Electrical Insulation, IEEE Transactions on [see also

Electrical Insulation, IEEE Transactions on], vol. 13, pp. 111, 2006.

[15] R. Plessow and W. Pfeiffer, "Influence of the frequency on the partial discharge

inception voltage," presented at Electrical Insulation and Dielectric Phenomena, 1994.

IEEE 1994 Annual Report., Conference on, 1994.

Page 45: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 45 of 49

[16] A. T. Wilder and R. Hebner, "Frequency dependence of partial discharge initiation

voltages with embedded electrodes," presented at Power Modulator Symposium, 2004

and 2004 High-Voltage Workshop. Conference Record of the Twenty-Sixth International,

2004.

[17] M. Kaufhold, G. Borner, M. Eberhardt, and J. Speck, "Failure mechanism of the

interturn insulation of low voltage electric machines fed by pulse-controlled inverters,"

Electrical Insulation Magazine, IEEE, vol. 12, pp. 9-16, 1996.

[18] D. Fabiani, G. C. Montanari, A. Cavallini, and G. Mazzanti, "Relation between

space charge accumulation and partial discharge activity in enameled wires under PWM-

like voltage waveforms," Dielectrics and Electrical Insulation, IEEE Transactions on

[see also Electrical Insulation, IEEE Transactions on], vol. 11, pp. 393, 2004.

[19] K. Wada, K. Tsuji, and H. Muto, "Partial discharge inception voltage for two

insulating materials (PVC and PE) under inverter surge voltage," presented at Properties

and Applications of Dielectric Materials, 2003. Proceedings of the 7th International

Conference on, 2003.

[20] BS EN ISO 7864 ”Sterile Hypodermic Needles For Single Use”1996

[21] G. C. Stone, "Partial discharge diagnostics and electrical equipment insulation

condition assessment," Dielectrics and Electrical Insulation, IEEE Transactions on [see

also Electrical Insulation, IEEE Transactions on], vol. 12, pp. 891, 2005.

[22] A. J. Reid, M. D. Judd, B. G. Stewart, D. M. A. H. D. M. Hepburn, and R. A. A. F.

R. A. Fouracre, "Identification of Multiple Defects in Solid Insulation Using Combined

RF and IEC60270 Measurement," presented at Solid Dielectrics, 2007. ICSD '07. IEEE

International Conference on, 2007.

Page 46: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 46 of 49

[23] L. E. Lundgaard, "Partial discharge. XIV. Acoustic partial discharge detection-

practical application," Electrical Insulation Magazine, IEEE, vol. 8, pp. 34, 1992.

[24] R. Schwarz, M. Muhr, and S. Pack, "Partial discharge detection in oil with optical

methods," presented at Dielectric Liquids, 2005. ICDL 2005. 2005 IEEE International

Conference on, 2005.

[25] F. H. Kreuger, P. H. F. Morshuis, and W. A. Sonneveld, "Optical detection of

surface discharges," Electrical Insulation, IEEE Transactions on [see also Dielectrics and

Electrical Insulation, IEEE Transactions on], vol. 23, pp. 447, 1988.

[26] IEC 60270, ” High Voltage Testing Techniques-Partial Discharge Measurement” ,

2001.

[27] J. P. Steiner, "Partial discharge. IV. Commercial PD testing," IEEE Electrical

Insulation Magazine, vol. 7, pp. 20, 1991.

[28] L. Satish and B. Nazneen, "Wavelet-based denoising of partial discharge signals

buried in excessive noise and interference," Dielectrics and Electrical Insulation, IEEE

Transactions on [see also Electrical Insulation, IEEE Transactions on], vol. 10, pp. 354,

2003.

[29] S. Sriram, S. Nitin, K. M. M. Prabhu, and M. J. A. B. M. J. Bastiaans, "Signal

denoising techniques for partial discharge measurements," Dielectrics and Electrical

Insulation, IEEE Transactions on [see also Electrical Insulation, IEEE Transactions on],

vol. 12, pp. 1182, 2005.

[30] U. Kopf and K. Feser, "Rejection of narrow-band noise and repetitive pulses in on-

site PD measurements [corrected version]," Dielectrics and Electrical Insulation, IEEE

Page 47: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 47 of 49

Transactions on [see also Electrical Insulation, IEEE Transactions on], vol. 2, pp. 1180,

1995.

[31] K. Feser, G. Konig, J. Ott, and P. A. S. P. Seitz, "An adaptive filter algorithm for

on-site partial discharge measurements," presented at Electrical Insulation, 1988.,

Conference Record of the 1988 IEEE International Symposium on, 1988.

[32] C. Petrarca and G. Lupo, "Wavelet Packet Denoising of Partial Discharge Data,"

presented at Electrical Insulation and Dielectric Phenomena, 2006 IEEE Conference on,

2006.

[33] G.G.Raju, Dielectrics in Electric Fields: Marcel Dekker, 2003,pp.448-449.

[34] C. C. Chang and Q. Su, "Memory propagation of negative point-to-plane corona

under AC voltage," Science, Measurement and Technology, IEE Proceedings-, vol. 149,

pp. 117, 2002.

[35] U. Gafvert, H. Edin, and C. Forssen, "Modelling of partial discharge spectra

measured with variable applied frequency," 2003.

[36] K. Kimura, S. Itaya, S. Ushirone, M. Hikita, and W. Bito, "Discharge condition and

surface charge distribution under repetitive bipolar impulses," 2003.

[37] A. Neves and H. J. A. Martins, "Surface charging and charge decay in solid

dielectrics," presented at Electrical Insulation, 1996., Conference Record of the 1996

IEEE International Symposium on, 1996.

BIOGRAPHIES

Page 48: Faisal Alrumayan, Student Member, IEEE Senior Member, …

Page 48 of 49

Faisal Alrumayan (M’08, Student Member'07) was born in Saudi Arabia. He

received his MSc and PhD from, respectively UMIST in 2004 and the

University of Manchester in 2008 respectively. He is currently a Postdoctoral Fellow at

Research Centre, King Faisal Specialist Hospital and Research Centre, Saudi Arabia. His

research interests include the use of higher voltage systems.

Ian Cotton (M’98, SM’07) received a Class I BEng (Hons) degree in Electrical

Engineering from the University of Sheffield in 1995 and a PhD in Electrical

Engineering from UMIST in 1998. He is currently a Senior Lecturer in the

Electrical Energy and Power Systems Group of the School Of Electrical and Electronic

Engineering at the University of Manchester. His research interests include power

systems transients, the use of higher voltage systems in aerospace applications and power

system induced corrosion. He is a Member of the Institution of Electrical Engineers and a

Chartered Engineer.

Andrew Nelms Andrew Nelms was born in the United Kingdom in 1980. He

received an MEng (Hons) degree from the University of Manchester Institute

of Science and Technology (UMIST) in Electrical and Electronic Engineering

in 2004 and a PhD in the Electrical Energy and Power Systems group of the School of

Electrical and Electronic Engineering at the University of Manchester in 2007. He

currently works for British Energy as an Operations Engineer.