12
Fan coil units

Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

Embed Size (px)

Citation preview

Page 1: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

Fan coil units

MOV99091_EPCEN07-401 Page 1 14-MAR-07

Cyan Magenta Yellow Black

Page 2: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

2

3

PictogrammesManual cool/heat changeover.

Automatic cool/heat changeover based on water temperature.

Automatic cool/heat changeover based on air temperature.

Control of the 3-way/4-port ON/OFF valve. The water valve shut-off once the desiredtemperature is reached.

The controller controls the electric heater as integration or replacement of the hot waterheating system. When the operating mode selector witch is turned on “electric heater” and theelectric heater is turned on, the fan runs continuously at medium speed.

The fan speed can be set at one of the 3 speeds (low, medium or maximun) by turning theoperation mode selector.

The fan speed is switched automatically based on the difference between the temperature seton the thermostat and the room temperature.

Optimised comfort cooling. When the fan coil has reached the desired setpoint, the fan willoperate at medium speed and at regular intervals to ensure constant room temperature andlower sound.

The controller prevents the fan coil unit from operating in one mode, if the required watertemperature is not achieved to operate in the selected mode.

The dead zone is a temperature interval close to the set temperature. When the air is warmer/cooler than the top/lower limit of the neutral zone, the cooling/ heating mode is selected.

MOV99091_EPCEN07-401 Page 2 14-MAR-07

Cyan Magenta Yellow Black

Page 3: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

3

FWV

FWL

FWM

0 1 2 3 4 5 6 7 8 9 10 11 kW

FWD

2 4 6 8 10 12 14 16 18 20 22 24kW

FWB

2 4 6 8 10 12 14 16 18 20 22 24kW

2-pipe

4-pipe

Product portfolio

Fan Coil Reference

2-pipe

4-pipe

CoolingHeating

Fan Coil Reference

2-pipe

4-pipe

Daikin fan coil units deliver quiet, reliable, controllablecomfort of air conditioning without all the noise of othercentral systems.

Fan coil units are a highly efficient means of turning awater chiller or hot water boiler into an efficient, quietair conditioning system.

The units are super quiet because the only moving part isthe fan; making them ideal for use in offices, hotels andthe home.

The new range of fan coil units offers 5 models, of which3 in flexible application. A wide range of accessories isavailable.

For the ultimate in quiet, controllable air conditioningwith all the comfort but none of the bulk or noise, theclear choice is Daikin.

Fan Coil Reference

MOV99091_EPCEN07-401 Page 3 14-MAR-07

Cyan Magenta Yellow Black

Page 4: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

4

FWV, FWL, FWMEasy to installFast and easy field set up, ready for use!

KEY HOLE SYSTEM / LEVELLING

• quick fixing system for wall/ceiling mountingadvantage : no need to unscrew the nut

• units just need to be perfectly leveledadvantage : no need to calculate the condensate drainage

WATER CONNECTION

• pre-assembled 3-way/4-port ON/OFF valves are available• valve packages are insulated, no extra drain pan required• valve packages contain balancing valves and sensor pocket• valve packages can be factory-mounted and are leak tested• same valve package can be installed vertically and horizontally, on the

right or on the left side of the unit without changeadvantage : easy to connect even when space is limited

CONDENSATE DRAINAGE

• condensate drain pan features slopes to reduce water accumulation• supplied with flexible rubber hose pipe for easy connection

advantage : eliminates the need to align drain pan outlet withcustomer pipingadvantage : no need for collar if pipe diameter is compatible

QUICK ELECTRICAL CONNECTIONS

• fast-on connections for electrical options : no tools needed• controls are already factory-wired and tested

advantage : control panel no longer needs to be opened(external customer connections)

• wiring diagram on the cover of the electrical box

MOV99091_EPCEN07-401 Page 4 14-MAR-07

Cyan Magenta Yellow Black

Page 5: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

5

FWV, FWL, FWMEasy to maintainLow maintenance and high effeciency

FAN MOTOR/CONTROL PANEL ACCESSIBILITY

• 4 screws to access to the fan motor• fan board is removable without bringing the unit down• motor is life-lubricated and has a life span of 40,000 hours• control panel removable by a single screw• can be unfolded for a better component access• removable grilles• easy access to control valves

QUICK REMOVAL OF WASHABLE FILTER

• no tools needed• same system on vertical and horizontal units

advantage : very fast filter removal

ELECTRIC HEATER RESETTING

• no relay up to 2kW capacityadvantage : even quieter operation

• manual reset easily accessible• equipped with two overheat cut-out thermostats

(manual & automatic reset)advantage : anticipates the upcoming standards

MOV99091_EPCEN07-401 Page 5 14-MAR-07

Cyan Magenta Yellow Black

Page 6: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

6

FWB

STRUCTURE

• modular concept• height of the units only 240mm for all the sizes• cooling coil and fan module is made of:

- galvanised sheet steel- internally insulated (with 3mm close-cell polyurethane)

• key-hole system for fast mounting• rubber anti-vibration damper to isolate the unit from supporting structure• straight duct connector is mounted to both suction and discharge side (width 30mm)• a template is available in the carton box for easy connection to the ceiling

HEAT EXCHANGER

• 3, 4 or 6 stage row cooling coil• standard left handed water connections + air-purge

(water connections can easily be turned)• drain pan can to collect the condensate from:

- heat exchanger- regulating valves

FAN MOTOR ASSEMBLY

• 1, 2 or 3 centrifugal fans with forward profile blades, dynamically andstatically balanced

• 7-speed electrical motors (with thermal protection on windings)• all 7 speeds pre-wired in the factory in the terminal block of the switch box• to reduce the requested installation space is the terminal block located on

the same side as the water connections

AIR FILTER

• located in the air inlet• removable from the bottom• made of acrylic fiber, filter class EU2

MOV99091_EPCEN07-401 Page 6 14-MAR-07

Cyan Magenta Yellow Black

Page 7: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

7

FWD

FAN MOTOR ASSEMBLY

• dual intake centrifugal fans made of aluminum, dynamically and statically balanced• 3-speed electric motor, installed on vibration damping supports

(with thermal protection on windings)

AIR FILTER

• air-intake module + Filter is standard delivered with each unit• removable filter from the bottom• made of acrylic fiber, filter class EU2

STRUCTURE

• possibility of installation both in horizontal and vertical position• reduced height 280mm up to model 10• the unit is made of:

- galvanised sheet steel- insulated with noise-proof/anti-condensing material(self-extinguishing in Class 1, with a thickness of 10mm)

• key-hole system for fast mounting• straight duct connector is mounted to discharge side

(width 30mm)

HEAT EXCHANGER

• 1 or 2 stage row cooling coil• standard left handed water connections + air-purge• system for collecting and discharging condensate setup either for ceiling or wall

mounting

MOV99091_EPCEN07-401 Page 7 14-MAR-07

Cyan Magenta Yellow Black

Page 8: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

8

01 02 03 04 05 06 07 08 09 10 12 16 18

FWV/L/M

FWB / / /

FWD / / /

••••

••

••

••

••••

••

••

•••

• • ••

••

••

••

••••

••

••••

••

••

••

••

•••

ECFWMB6

3

3

ECFWER6ECFWEB6

EPIMSA6EPIA6

/

Easy to control !The new fan coil units can be operated by 3 differentcontrollers:• electronic control built-in (ECFWEB6)• electronic control remote (ECFWER6)• electromechanical control built-in (ECFWMB6)

The electronic control consists of:• operating mode selector, to turn the fan coil on and off,

to choose the type of operating mode (automatic or atfixed speed) and to control the electric heating

• cooling / heating selector• operational LEDs that indicates the current operation mode• thermostat to control the room temperature• free contacts for external enabling signal that may switch

on or off the unit.• free contacts for centralized cool/heat changeover• water temperature probe• air temperature probe

Several configurations are possible by changing dip switches.

The electromechanical controller includes a fan speedselector (3 speeds + stop) and manual cool/heat changeover.In case of the on/off valves, control can also be donethrough this controller.

Power interface / master slave interfaceAn additional interface is required for units with acurrent greater than 1,12A.Master slave interface (EPIMSA6: 4x3A)For remote control of up to 4 fan coil units, an optionalmaster/slave interface can be installed. Up to 3 EPIMSA6can be connected in parallel (--> max. 12 fan coils).Power interface (EPIA6: 1x16A)This is absolutely required for connection of ECFWER6 toFWD12 to18. It can be used as an alternative for EPIMSA6for all other fan coils.

master slave interface is only needed in case of remote control ofmultiple fan coil units

obigation to use master slave interface or power interface

obligation to use power interface

Control featuresBasic control

functionsOptionsCooling/heating

changeover

2-p

ipe

4-p

ipe

MOV99091_EPCEN07-401 Page 8 14-MAR-07

Cyan Magenta Yellow Black

Page 9: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

**=

TN(2-

pipe,

witho

utval

ves),T

V(2-

pipe,

withv

alves)

,FN

(4-pip

e,wit

hout

valves

)*C

anbe

ordere

dfact

orymo

unted

**fac

torym

ounte

donr

eque

st

Measuring conditions (at nominal air flow and ESP) : COOLING • air temperature entering the unit: 27°C/19°C • water temperature entering the unit 7°C • water temperature rise 5 KHEATING • room air temperature 20°C • for 2 pipe units : water temperature entering 50°C - water flow rate same as for the cooling test • for 4 pipe units : - water temperature entering 70°C - water temperature leaving 60°

FWV/FWL/FWM01-10C** 01 02 03 04 06 08 10

2-pi

pe(*

*=TN

orTV

)

COOLING

total capacity (H) kW 1.54 2.09 2.93 4.33 4.77 6.71 8.02sensible capacity (H) kW 1.20 1.51 2.11 3.15 3.65 4.91 5.96water flow l/h 265 359 504 745 820 1,154 1,343pressure drop kPa 13 13 11 12 14 12 19

HEATINGheating capacity (H) kW 2.14 2.57 3.81 5.63 6.36 7.83 10.03water flow l/h 265 359 504 745 820 1,154 1,343pressure drop kPa 9 11 9 9 10 9 16

Power input H W 37 53 56 98 98 182 244Coil water volume l 0.5 0.7 1 1.4 1.4 2.1 2.1Air flow H/M/L m3/h 319/233/178 344/271/211 442/341/241 706/497/361 785/605/470 1,011/771/570 1,393/1,022/642Sound power level H/M/L dBA 45/39/33 50/44/38 47/41/33 52/43/35 56/49/43 61/54/47 66/59/49

WeightFWV kg 19 20 25 30 31 41 41FWL kg 20 21 27 32 33 44 44FWM kg 14 15 19 23 23 32 32

4-pi

pe(*

*=FN

)

COOLING

total capacity (H) kW 1.46 1.90 2.87 4.33 4.67 6.64 7.88sensible capacity (H) kW 1.14 1.51 2.07 3.15 3.57 4.85 5.85water flow l/h 251 327 494 745 803 1,142 1,355pressure drop kPa 13 13 11 12 14 12 19cooling coil water volume l 0.5 0.7 1 1.4 1.4 2.1 2.1

HEATING

heating capacity (H) kW 1.90 2.10 3.08 5.05 5.30 7.91 9.30water flow l/h 196 182 286 396 465 694 816pressure drop kPa 7 8 5 10 10 8 9heating coil water volume l 0.2 0.2 0.3 0.4 0.4 0.6 0.6

Power input H W 37 53 56 98 98 182 244Air flow H/M/L m3/h 307/225/174 327/261/205 431/332/238 690/490/356 763/593/460 998/765/565 1,362/1,007/636Sound power level H/M/L dBA 45/39/33 50/44/38 47/41/33 52/43/35 56/49/43 61/54/47 66/59/49

WeightFWV kg 20 21 26 32 33 44 44FWL kg 21 22 28 34 35 46 46FWM kg 15 16 20 25 25 34 34

2pi

pe/4

-pip

e Water connections inch 1/2” 1/2” 1/2” 1/2” 1/2” 3/4” 3/4”Max. absorbed current W 0.17 0.24 0.25 0.44 0.43 0.80 1.12

DimensionsFWV/FWL mm 564x774x226 564x984x226 564x1,194x226FWM mm 535x584x224 535x794x224 535x1,004x224

Power supply V/~/Hz 230/1/50

Option description 01 02 03 04 06 08 10 FWV FWL FWM

Additional single row heat exchanger* ESRH02A6 ESRH03A6 ESRH06A6 ESRH10A6 x x x

Electric heater** EEH01A6 EEH02A6 EEH03A6 EEH06A6 EEH10A6 x x x

2-pipe ON-OFF 3-way motor driven valveE2MV03A6 E2MV06A6 E2MV10A6 x x x

with complete mounting kit*4-pipe ON-OFF 3-way motor driven valve E4MV03A6 E4MV06A6 E4MV10A6 x x x

with complete mounting kit*(**)Fan stop thermostat** YFSTA6 x x x

(only for ECFWMB6)Air intake & discharge grille + EAIDF02A6 EAIDF03A6 EAIDF06A6 EAIDF10A6 - - x

front filter fixing kit for concealed modelsSupporting feet ESFV06A6 ESFV10A6 x - x

(= supporting brackets + covers)Supporting feet + grille ESFVG02A6 ESFVG03A6 ESFVG06A6 ESFVG10A6 x - -

Manual fresh air intake louver EFA02A6 EFA03A6 EFA06A6 EFA10A6 x x x

Rear panel for vertically installed units ERPV02A6 ERPV03A6 ERPV06A6 ERPV06A6 x x -

Controller - electromechanical built-in** ECFWMB6 x x -

Controller - electronic built-in + water probe** ECFWEB6 x x -

Controller - electronic remote + water probe ECFWER6 x x x

Power interface for connection of up to 4 FCU EPIMSA6 x x x

to a single control panelVertical drain pan EDPVA6 x x x

Horizontal drain pan EDPHA6 - x x

MOV99091_EPCEN07-401 Page 9 14-MAR-07

Cyan Magenta Yellow Black

Page 10: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

10

FWB

Measuring conditions (at nominal airflow and ESP):COOLING • air temperature entering the unit : 27°C/19°C • water temperature entering the unit 7°C • leaving the unit 12°CHEATING • room air temperature 20°C • for 2 pipe units : water temperature entering 70°C - water temperature leaving 60°C

FWB02-10AT 02 03 04 05 06 07 08 09 10

2-pi

pe

COOLING

total capacity (H) kW 2.61 3.14 3.49 5.08 5.45 6.47 7.57 8.67 10.34sensible capacity (H) kW 1.88 2.16 2.34 3.6 3.87 4.4 5.23 5.96 6.9water flow l/h 448 539 598 873 936 1,111 1,299 1,488 1,774pressure drop kPa 8 14 11 15 8 14 21 21 26

HEATINGheating capacity (H) kW 5.47 6.01 6.47 10.31 11.39 12.28 15.05 16.85 18.78water flow l/h 480 527 567 904 999 1,077 1,319 1,479 1,647pressure drop kPa 7 10 8 12 7 10 16 15 18

Machine weight kg 23 24 26 31 33 35 43 45 48Dimensions (HxWxD) mm 239X1,039X609 239x1,389x609 239x1,739x609

Add.

Heat

exch

ange

r

HEATINGheating capacity (H) kW 3.14 5.99 12.8water flow l/h 275 526 1,123pressure drop kPa 3 5 8

2-pip

e/4-p

ipe

Air flow rate m3/h 400 800 1,200Power input (H) W 106 192 294Max. absorbed current A 0.51 0.94 1.28Available static pressure Pa 71 65 59Sound power level (H) dBA 58 60 69Power supply 230V/1 ~/50Hz

Option description 02 03 04 05 06 07 08 09 10

Additional heat exchanger EAH04A6 EAH07A6 EAH10A6

3-way valve add. h/e E2MV307A6 E2MV310A6

2-way valve add. h/e E2MV207A6 E2MV210A6

Fan stop thermostat YFSTA6

Power interfaces (*) -- EPIA6

Master slave interface (*) EPIMSA6

Controller electronic - remote ECFWER6

(*) In combination with ECFWER6, EPIMSA6 or EPIA6 must be installed for FWB08-10

MOV99091_EPCEN07-401 Page 10 14-MAR-07

Cyan Magenta Yellow Black

Page 11: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

11

Measuring conditions (at nominal air flow and ESP) : COOLING • air temperature entering the unit: 27°C/19°C • water temperature entering the unit 7°C • leaving the unit 12°CHEATING • room air temperature 20°C • for 2 pipe units : water temperature entering 50°C - water flow rate same as for the cooling test • for 4 pipe units : water temperature entering 70°C - water temperature leaving 60°C

FWD

FWD04-18A* 04 06 08 10 12 16 18

2-pi

pe(*

=T)

COOLING

total capacity kW 3.90 6.20 7.80 8.82 11.90 16.4 18.3sensible capacity kW 3.08 4.65 6.52 7.16 9.36 12.8 14.1water flow (H) l/h 674 1,064 1,339 1,514 2,056 2,833 3,140pressure drop (H) kPa 17 24 24 16 26 34 45

HEATINGheating capacity kW 4.05 7.71 9.43 10.79 14.45 19.81 21.92water flow (H) l/h 674 1,064 1,339 1,514 2,056 2,833 3,140pressure drop (H) kPa 14 20 20 13 21 28 37

Available static pressure Pa 66 58 68 64 97 145 134Weight kg 33 41 47 49 65 77 80

4-pi

pe(*

=F)

COOLING

total capacity kW 3.90 6.20 7.80 8.82 11.90 16.4 18.3sensible capacity l/h 3.08 4.65 6.52 7.16 9.36 12.8 14.1water flow (H) kPa 674 1,064 1,339 1,514 2,056 2,833 3,140pressure drop (H) kPa 17 24 24 16 26 34 45

HEATINGheating capacity kW 4.49 6.62 9.21 9.21 15.86 21.15 21.15water flow (H) l/h 349 581 808 808 1,392 1,856 1,856pressure drop (H) kPa 9 15 13 13 12 16 16

Available static pressure Pa 63 53 63 59 92 138 128Weight kg 35 43 50 52 71 83 86

2-pi

pe/

4-pi

pe

Air flow rate m3/h 800 1,250 1,600 1,600 2,200 3,000 3,000Power input (H) W 234 349 443 443 714 1197 1197Water connections inch 3/4 3/4 3/4 3/4 1 1 1Max. absorbed current A 0.95 1.58 1.97 1.97 3.21 5.37 5.37Dimensions mm 280x754x559 280x964x559 280x1,174x559 352x1,174x718 352x1,384x718Sound power level (H) dBA 66 69 72 72 74 78 78Power supply V/~/Hz 230/1/50

Notes:1. The valves for FWD12-16-18 do not contain piping nor drain pan.2. Requires electronic control.3. Neglecting the absolute requirement to install an additional interface (EPIA6 or EPIMSA6) to FWD06 -->18 may cause fire or other damage to the equipment.4. In combination with ECFWER6, EPIMSA6 or EPIA6 must be installed for FWD06-10.5. In combination with ECFWER6, EPIA6 must be installed for FWD12-18.

Option description 04 06 08 10 12 16 18

Electric heater: small (2) EDEH04A6 EDEHS06A6 EDEHS10A6 EDEHS12A6 EDEHS18A6

Electric heater: big (2) EDEH04A6 EDEHB06A6 EDEHB10A6 EDEHB12A6 EDEHB18A6

2-pipe 3-way valve (1) ED2MV04A6 ED2MV10A6 ED2MV12A6 ED2MV18A6

4-pipe 3-way valve (1) ED4MV04A6 ED4MV10A6 2 x ED2MV12A6 2 x ED2MV18A6

Vertical drain pan EDDPV10A6 EDDPV18A6

Horizontal drain pan EDDPH10A6 EDDPH18A6

Fan stop thermostat YFSTA6

Fresh air intake louvers (motorised) EDMFA04A6 EDMFA06A6 EDMFA10A6 EDMFA12A6 EDMFA18A6

Controller - electronic remote + water probe (3) ECFWER6

Master / Slave Interface (4) EPIMSA6 - - -

Power interface (5) - EPIA6

MOV99091_EPCEN07-401 Page 11 14-MAR-07

Cyan Magenta Yellow Black

Page 12: Fan coil units - UK | Daikin coil units are a highly efficient means of turning a ... 3 in flexible application. A wide range of accessories is ... FWB STRUCTURE • modular concept

Daikin products are distributed by:

The present publication is drawn up by way of information onlyand does not constitute an offer binding upon Daikin EuropeN.V.. Daikin Europe N.V. has compiled the content of thispublication to the best of its knowledge. No express or impliedwarranty is given for the completeness, accuracy, reliability orfitness for particular purpose of its content and the products andservices presented therein. Specifications are subject to changewithout prior notice. Daikin Europe N.V. explicitly rejects anyliability for any direct or indirect damage, in the broadest sense,arising from or related to the use and/or interpretation of thispublication. All content is copyrighted by Daikin Europe N.V.

Daikin Europe N.V. is approved by LRQA for its QualityManagement System in accordance with the ISO9001standard. ISO9001 pertains to quality assuranceregarding design, development, manufacturing aswell as to services related to the product.

ISO14001 assures an effective environmentalmanagement system in order to help protecthuman health and the environment from thepotential impact of our activities, products andservices and to assist in maintaining and improvingthe quality of the environment.

Daikin units comply with the European regulationsthat guarantee the safety of the product.

Daikin Europe NV participates in the EuroventCertification Programme for Air Conditioners (AC),Liquid Chilling Packages (LCP) and Fan Coil Units(FC); the certified data of certified models are listedin the Eurovent Directory.

Daikin’s unique position as a manufacturer ofair conditioning equipment, compressors andrefrigerants has led to its close involvement inenvironmental issues. For several years Daikinhas had the intention to become a leaderin the provision of environmental friendlyproducts. This challenge demands the ecodesign and development of a wide rangeof products and an energy managementsystem; which involves energy conservationand reduction of waste.

EPCE

N07-

401

/500

/02/

07/L

aM

ovid

aTh

epr

esen

tpub

licat

ion

supe

rsed

esEP

LE04

-25B