18
Ferm ii ab TM - 1285 0102.000 WATER COOLING CONSIDERATIONS FOR THE SSC John O'Meara 11/2/84 The purpose of this note is to specify parameters for hypothetical SSC water cooling systems, in order that the comparative advantages of these system can be studied. The various methods of heat rejection considered include: 1. Cooling Towers 2. Cooling Ponds 3. "Ground Water Recharge System" 4. Water-to-air (dry) cooling towers 5. Use of tunnel "sump" water 5. Some combination of the above The SSC heat rejection needs occur at the east interaction area, the west interaction area and at ten major access areas. See Figure 1 for a diagram of these areas and their representative loads. Some devices are cooled directly by the pond water, others require a pond-water-to-LCW-water heat exchanger. Figure 2 contains a diagram of a typical LCW system. The "ground water recharge" method is described in the attached reprint authored by Robert Sasman 1 . This method requires the drilling supply wells and shallower return wells. The water is used in a "once-through" heat exchanger. This method may be practical for the ten major access areas but the huge pumping water required at the east and west areas probably preclude its use in these two locations. The ponds have been sized by Langhaar's2 weather conditions for July at ANL's 3 weather requiring 0.9 acres/for each MW rejected with conditions. We require an average depth "thermal inertia." method using the average station. This results in some reserve for peak of five feet to provide The cooling towers should be designed to meet the required temperature cooling range and delivery temperature under "worst" conditions, i.e. 99% of the time for the summer months. The design should be based upon "peak" conditions for flow water and heat loads. In addition the cost should assume the following requirements: 1. Prevailing industry standards apply including wind loads. 2. Windage and draft losses shall not exceed 1%. 3. Be suitable for winter use.

Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

Embed Size (px)

Citation preview

Page 1: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

Ferm ii ab TM - 1285 0102.000

WATER COOLING CONSIDERATIONS FOR THE SSC

John O'Meara 11/2/84

The purpose of this note is to specify parameters for hypothetical SSC water cooling systems, in order that the comparative advantages of these system can be studied. The various methods of heat rejection considered include:

1. Cooling Towers 2. Cooling Ponds 3. "Ground Water Recharge System" 4. Water-to-air (dry) cooling towers 5. Use of tunnel "sump" water 5. Some combination of the above

The SSC heat rejection needs occur at the east interaction area, the west interaction area and at ten major access areas. See Figure 1 for a diagram of these areas and their representative loads. Some devices are cooled directly by the pond water, others require a pond-water-to-LCW-water heat exchanger. Figure 2 contains a diagram of a typical LCW system.

The "ground water recharge" method is described in the attached reprint authored by Robert Sasman1 . This method requires the drilling supply wells and shallower return wells. The water is used in a "once-through" heat exchanger. This method may be practical for the ten major access areas but the huge pumping water required at the east and west areas probably preclude its use in these two locations.

The ponds have been sized by Langhaar's2 weather conditions for July at ANL's3 weather requiring 0.9 acres/for each MW rejected with conditions. We require an average depth "thermal inertia."

method using the average station. This results in

some reserve for peak of five feet to provide

The cooling towers should be designed to meet the required temperature cooling range and delivery temperature under "worst" conditions, i.e. 99% of the time for the summer months. The design should be based upon "peak" conditions for flow water and heat loads. In addition the cost should assume the following requirements:

1. Prevailing industry standards apply including wind loads. 2. Windage and draft losses shall not exceed 1%. 3. Be suitable for winter use.

Page 2: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

2

4. Limited degradation in performance due to winds. 5. vendor guarantees performance for a range of operating

conditions. In addition to "worst" condition point.

General Comments:

1. The cooling water temperature is likely to exceed the "max" tabulated temperature by 5 to 10 pF under worst load and weather conditions.

2. Heat rejected by Freon chillers is far greater than the horse power in. The rejection typically is 3 to 4 times as great.

3. Water quality is must be considered in determining the tendency to scale. This in turn determines blow down rate. Fermilab pond water is "good" in that typical analysis shows that is has little tendency to scale.

Attached is a copy of a calculation for scaling tendency for Fermilab pond water. On the other hand, local well water has a strong tendency to scale at increasing temperatures.

We must bear in mind that the scaling will result in a larger heat exchangers, chemical treatment of the water, frequent cleaning of heat exchangers, and/or increased power consumption.

For this note we have assumed that we can tolerate two "cycle of concentrations" in determining blow down rates shown in Table 4. This may be optimistic for well water and conservative for run-off water.

1. Cooling ponds reject heat by evaporation, conduction to the air and radiation. (Heat conduction to the earth is nil). The evaporation rate is determined by the difference in the water vapor pressure in the pond and the water vapor pressure the air. Conduction and radiation rates are determined by the difference in pond surface temperature and air temperature. Attached are plots for pond performance for January, July and September based upon ANL weather data.

These charts show that the evaporation rates with a constant heat load vary considerably during the year. In addition the solar heat load varies with the seasons. Hence the blowdown requirements for ponds swing by about a factor of three.

Page 3: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

3

2. This note assumes that the cooling towers reject heat solely by evaporation.

3. Some conversion factors:

A) Evaporization conversion factors: 6.56 gpm/MW

B) Water flow rate for lpF rise and 1 MW = 6820 gpm for 20pF = 341 gpm.

Page 4: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

4

Footnotes:

1. Thermal Pollution of Ground Water by Artificial Robert T. Sasman, Water & Sewage Works, December 1972 pp52-55.

Recharge, Vol. 119

2. Cooling Pond Many Answer Your Water Cooling Problem, J.W.

3.

Langhaar,; Chemical Engineering, August, 1953, pp 194-199.

Fifteen-Year Climatological Harry Moses & Mary a Bogner.

Summary, ANL Report, 7084, September 1967.

4. Scaling Tendency Determined Using Ryzmar Method: A New Index for Determining Amount of Calcium Carbonate Scale Formed By a Water, John W. Ryznar; Journal of American Water Works Association, Vol. 39, November, 1947, pg 1090.

Page 5: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

H-40

WEST INTERACTION

AREA

F-40

K-40

D-40

M-40

EAST

INTERACTION

AREA

B-40

MAJOR HEAT REJECTION AREAS

2 INTERACTION AREAS

I 0 MAJOR ACCESS AREAS

FIGURE I

Page 6: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

COOLING LOOP

FOR L.C.W. &

DIRECTLY COOLED

LOADS

95°F

~ •105°F

L.c.w. ~

LOAD

)

• I 35°F

I 9 5 ° F I " D I R E c T'i I I I 5 ° F I I I 5 ° F ...,. _ LOAD _ t

-D~~~~~~~~~~~~~

NOTE: * OR COOLING TOWER

TEMPERATURES ARE FOR "WORST CASE" (9996) CONDITIONS

FIGURE 2

Page 7: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

~ ...

"d

b1 CJ

::E: 111 t9

'"d n1 0 ....:l

i:.i:: JJ::I

~ H CL> ~ 0 ..µ

-CL> tJ'I H n1

..c: u CL>

i:.i::

TABLE #1 HEAT REJECTION AT EACH MAJOR ACCESS AREA

Make-Up Water Req'd

t9 z H

(@ 2 cycles of concentration) gpm

::E: 111 CL> t9 Ul

·r-1 ( 1) ... i:.i:: Towers Ponds CL>

.µ ~ mo HO :;: '<:!' 0

r-1 CS!J ~

Power Supplies

LCW 250 0.733 105 30 375 188 9.6 8.8 & Elec (733 MW)

Refrig-era tor PONL il350 4 95 20 1350 675 52.5 48 Cool down Mode {4MW)

Normal Operating POND 675 2 95 2.0 675 338 26.2 24 Mode (2MW)

HVAC ( 30 OKW) POND 130 0.375 95 20 130 65 4.9 4.5

TOTP,..LS PEAK 5.1 1855 928 67 61. 3 NO~I 3.1 1180 591 40.7 37.7

(1) Make-Up water requirements for ponds is annual average. Rates vary from 6.06 to 18.25 gpm/MW see Table 4

(2) Ground water recharge system is a "Once Thru" system hence the cycles of concentration ~quals zero.

(3) Dry Towers require annual "winterizing" with 50% ethyelene glycol/water mixture.

Ground Water(2) Recharge

0

0

0

0

0

0

Dry Towers Water to Air

0

0

0

0

0

0 I

Page 8: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

NiASP 3 I. R. 2 Refrig. Misc.

Injection Power Supplies R.F.

t:l

or ~ ~ li:i E-1

~· .. ~ 0 H

~

~ ~ li:i 8

~ s: 0 H fr-I

~·1025( !o,

PONDr rn

~ 5BOO. 1£ .!<: cO QJ4640-

'1-1

LCW cO

~ .. ~

~ ~ t!> z

S::H OH ·r-10 .j..)O (.) CJ Q) ·ri i::t: Q) H ~ :> .µ Q) rd .µ Q) rd ::r::~

30

17

13.6

~ r.::i 81i.t

0 8 r.::i ... ...:! Cl z i::t: HO

H ::< ~~

95

95

105

Ii< 0

... r.::i Cl ti) i::t: HO ~H

~~ r.::i ::r:: 88

=20

20

30

-I-I C) ~ 0 .µ

H o~

-'1.1 Cl t!> z r.::i 0 ... ti) '1.iri!H 8~

g~ fr-I H 0 H S:o OON OH CJ fr-I C!1J

10,250

5L00

6960

r.::i

~ ~ CJ

~ ~~ r.::i '1-1 8 t!> r.::i ~ ti) S: "'H

r.::i ~ Cl 8 z ~fr-I p 0 0 s: 0 ~0"'21 t!> H = fr-I C!1J

5125

2900

3480

TABLE #2 EAST AREA

Make-Up Water Req'd (@ 2 cycles of concentration)

gpm

GROUND "DRY"TOWERS I (1) WATER(2) WATER TO

Towers Ponds RECHARGE AIR

394 360 0 0

223 204 0 0

178 163 0 0

--

Misc. P.S. ~ 3750 11 105 30 5625 2813 144 132 0 0

TO'i'ALS

0 z

Peak 43.6 17,210 8605 572 523 I

Normal . 28 11,425 -. 5713 367 336 I

(1) Make-Up water requirements for ponds is annual average. Rates vary from 6. 06 to 18. 25 gpm/MW see Table 4.

(2) Ground water recharge system is a "Once Thru" system hence the cycles of concentration equals zero.

(3) Peak Loads are estimated @ 80% of installed electrical power.

- 0 0

0 0-

,___

Page 9: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

NiASP 3 I. R. 2 Refrig. Misc.

Power Supplies

TOTALS

Cl

QI

~ 111 t9

..

~ ..

p:; µ:i 8

~

1-1 Q)

:3: 0 ..µ

~ "1:! ::r: u

TABLE #3 HEAT REJECTION

AT WES1' AURORA

Make-Up Water Req'd ~ ~ µ:i E-1

0 "1:! 0 i----:1

~

t9 z

S:: H OH ·.-lO ..µ 0

~ ~ &

1-1 O:E:

- 111 0 t9 z µ:i

~ p:; :E: r..:I 111

(@ 2 cycles of concentration) gpm

i----:1 :r: 8 t9 r..:I

Towers PONDS

'

..I<: rO 11050 32.4 95 20 11050 <I) 5525 425 389 111

POND

.-I rO 7502 22 95 20 El 7502 3751 289 264 1-1

~ ..I<: rO <I) 2182 6.4 95 30 3275 1638 84 77 111

LCW .-I rO El 955 2.8 95 30 1433 717 38 34 1-1 0 z

PEAK 13232 38.8 14325 7163 509 466

NORMAL 8457 24.8 8935 446',8 327 298 _,_ ...... _

(1) Make-Up water requiP.ments for ponds is annual average. Rates vary from 6.06 to 18.25 gpm/MW see Table 4.

(2) Ground water recharge system is a "Once Thru" system hence the cycles of concentration equals zero.

(1) -pp::i'f<'- T.n;:ir1c:; ")rp pc:;t-inv=1t-Pr1 (cl 8051; of instnlled electrical power.

Ground 'lDRY"Tower Water(2) Water-to-Recharge Air

0 p

0 0

0 Q

0 0

0 0

0 0 ----'-'

Page 10: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

Winter

Summer

Annual Average

ESTIMATED WATER CONSUMPTION PER MEGA~vATT

TOWERS PONDS

Bleedof f +

Evap rate Makeup Windage Evap rate Makeup

6.56 13.12 13.12 3.03 6.06

6.56 13.12 13.12 9.25 18.25

6.56 13.12 13.12 6.00 12.0

TABLE 4 ESTIMATED WATER CONSUMPTION PER MEGAWATT

Bleedoff

3.03

9.25

6.0

Page 11: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

I I o I 35

l ( 1tJul/1J4 PcAJ D nL.J7, . ..;--r- c.n;? K.,(I !.:'.'.- ~ , v,-....

I ''\--+- 360 II FH7' l3:£JC't7 I DJ I

/JIVL lll/t!'.t21~t;,c;:- JAAJU!lf2)/ I l C.'t;/JO!Tl~AJS - \ I ~it .______________ _ ___________ ) I ~ ~

S!J

Av~t?A4e_ pRr eo~B

A-v e:1211 c: 1:::. f?t::t<.J P~ /JIJ r /i- U tr f3. l'-i 4 €:.. 1;U I IV D ti C:.L

2 4- Ill.:: A f/E, s ()!...P £ I AJPOT

-----------~----- .. -.

ZI/);::

17 t>F (. 0&&84-3 ~Hy

/3'13 mPll ~ /Sarr 3~ . g7?) /HZ-- JCT~

Page 12: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

_ _L_ ____ ·------'-------

! 300+­

I \ I

I i ! ;

0-, ---!

-----Avt:f?A-u €. ])Rt.( BULB

;/ u £ v ,~ ~:1· t:. 0!£w P6; ,IJ T

A- ll ;z:_;e/~ c, c;. WI /..1 D V 1£ L

)!- /-/£: /ft)(£. ScJL-Af:/ llJPU T

i

-~oo:J I \-...

f

/

ti \

)

l lie. +- fl ,e

/t£:;1'; p )

7 I "i=

t/tJ, ~ ~ ~ (, 5'310 3 ~ ;!-?)

q,~ MPH (@15'0Fr)

/I 0 B-ru /1-1-e- FT:..

I ~

\ti ' \ ..... I ~ I ~ I -=< I ~

--l./()O ~ ~ ~ ~~

\,

~ ·~

·0 _\-... I \t.\

~

It?~ i.

Page 13: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

···---··---------

' i , L I '3·C:0 I

,\ !

? \l..

J

I

I~~

./

/

D-

'1;0 g'5' 9~ 95' /<J-d I ~

?tJ/1) j) Wlf !IC/? 7£111? tC/ll/. 7cJ.t?6S I;:::-

!/tl!f;21/CC ORF .&Ot-f3

/J // C:1t' (/ t £.. /J~v) !'::a I IJ r II v rt1!1l·tte:.. w 11JO I/ CL SOt..fl</2 I IJPcJT 24- /.f-!2 A-UC..

t3 °F' sz °F( 3902Y~~) / 3,./3 mPH (@I 5CJ FT

q tJ /3 /U /f!2 ~- Fiz_

Page 14: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

/ (, ..

CHAPTER 2. SCALE AND DEro£ CONTROL

?/~I-_ ~I~ I l ' CHART 5-LANGELIER SATURATION INDEX

'• ,-- ._.J •. < ~--:-, ,. I J ,-.., C I ~ ::.; ~- ~-· : · _..1 ~ -.-"

0 2'

:') ;./

--

5.0

4.5

4.0

3.5

30 -

.. -3' 2.5 ..J c(

CL

2.0

1.5

l;O

TOTAL SOLIDS

OON~ANT\

EXAMPLE TEMP•l20°F pH• 8.0 Ca. HARDNESS •120PPM M ALKALINITY•IOOPPM TOTAL SOLIOS•210PPM

• pCa. • 2.92 PALK.• 2.70

CAT 120° • .!..:Z.Q. SUM •pH • 7.32·

ACTUAL pH • 8.00

DIFFERENCE = +.68 •SATURATION INDEX

'""""I .l Ca. HARDNESS ~ fAS Ca.C03

~4~ I' .,

PALK,-, ,, I 1

I

I ..... -- M ALK. - AS Ca.C03 -

--

-

-... I'

-

---

I 5 10

I

:

: I.

. '

'

.... ~

"

:

l -I

20

I

I -.... I

i

! I

I

I J

_, ; - ! I

JI

' ~ - I.I - t I

'' I

~ - I I - -, I

I I I I

I 'I J

I I I

I I - ' - : I I 1 i I. t

'i i I'

I I I I

I .-. I ·-~ 11

·- 11'

J

I ~. -I

I

I - .... I I

I

I -I -

~ --, .. ...

' -..- -I

r-... _

I

I - ...... "'

" -

30 50 ICb i 200 300' 500 1000 PARTS PER MILLION

• 00

(

~2· I J

I I I I 40°

.1.0· I I

_I

60'

70°

I

80'

I I I I

90°

100'

I I l 110°

l I I I

120•

_I

I

130' _J L I I I

140'

I

150'

160° I I

I

170° I

180' -I I

190° -I I

l?OO'

' ....

5000

2.9

2.8

2.7

2.6

2.5

2.4

2.3

2.2

2.1

2.0

1.9

1.8

1.7

1.6

-1.5

1.4

1.3

1.2

" I.I

l&I _, c( ..., I/) . 0 .

! -~ .. !.-: From Waler Condi1ioning For lndu.iry, b)· Sheppard T. Powell. !\lcGraw·Hill Book Co. to~ .. 1954. Used by pcrmiuion.

I . · __ i1

I · ; . i •• t-

5-13

Page 15: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

0

.... __.

.... 0 :>

IJ'\ .. "'" t.'l I .-..: C2 s.. 1;""\

-0 c. !--"'

C> ':'l t·f c-­<1 r:r­:.1: ...... CJ ,, .

:.. e8 11

~(_)

!... c. 1!1 '\) .... 0 .:::; ~)

i:--~ A

REPRINT SERIES

llC $TATE WA ER SURVEr

·::a;~:-,~.•'~~~{~~;~-~/_ 5:,~..tt ... ~'_iJ.:h.:~.·;,-_:_.,?\L, --·:"" ·~,,..-~··"': ,'''=<'/( - . "" ' - ~ • .

,;i:.~·;~~};\~~·;._:~~?_.",~:~·t:..".:.J.?!:~'l:t~~:·~":~---·\~:.

,~ ... -.

F4 45.5.

''· '·,

Figure 1. Well locations and ground water temperature in area of recharge operation.

Thermal pollution of ground water by artificial recharge

By Robert T. Sasman*

P rojected large increases in municipal and in­dustrial ground water pumpage in northeastern Illinois indicate ground water demands will ex­

ceed ground water availability in some areas in 1990. The total ground water pumpage has increased stead­ily at an accelerating rate since the first high ca­pacity well was drilled in 1864. Pumpage has in­creased at an average rate of 8.3 million gallons per day (mgd) every year since 1960 and was 260 mgd of 1970 (Table l). Projections of ground water pump­age to the year 2020 made by Schicht and Moench, indicate a demand of 314 mgd by 1980 and 923 mgd by 2020.1 In 1970 more than 53 percent of the total pumpage was obtained from wells finished in deep sandstone formations. This is expected to in­crease to about 60 percent of the total pumpage by 2020, or 556 mgd.

But as pumpage from deep sandstone wells has in­creased, water levels in these wells have drastically

*Hydrologist, Illinois State Water Survey, Warrenville, Illinois.

declined, approaching 800 ft in the areas of heaviest pumpoge. Long term water level declines have aver­aged 7-8 ft/yr. The overage decline for the period 1958-1966 was Rearly 14 ft /yr. Schicht and Moench1

predict that the water level will decline an additional 500 feet in some areas within the next 20 years.

There are several alternative programs that can be considered in attempts to balance supply and de­mand. These include artificial ground water recharge, industrial water recirculation, reuse of treated sew­age plant effluent, importation of either ground wa­ter or surface water from sources outside the metro­politan area, restrictions on use and increased diver­sion from Lake Michigan.

In spite of declining water levels and associated deeper pump settings and larger pumps, numerous municipalities and industries continue to develop additional water supplies from the deep sand­stone aquifers. One of the major reasons for this Is that these aquifers con still provide uniformly moder­ate to high yields to wells throughout the region. Artl-

Page 16: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

800 '3'1 R

600

, .. , .. "'· ~ ·. . .

S3 F1 F2

~· ,• .. -·. "•. ' . .. . . , '. ~· • : • DRIFT . . .

F3 F4 Fs

CASING

":.•."• ,. •.,· _:_ _:_ J...".:....: , - - - - -•':' .; , .. --!..---? . .. . . . . . .

-J w > w 400

: : : •• : :. •.· .. :·.::·SANDSTONE : .. • • • • • • • l •

. . ..... . . OPEN HOLE

I I I I I I -J . . . .. . . . . . . . . . . .

ex: LLJ Cl)

. . . . . . . . . : .. ;.;..~·+4·.~rin:~v.a.:..-.. n:cHERT 1.

z 200 ex: . : •• • ·• : . : : ·. ·: : :-:·:.·.:SANDSTONE

•· : . . . . . . .. ·,: .. ..... . LLJ :E:

-400

. __,_ . . .

0 8 16 24 32 DISTANCE FROM RECHARGE WELL, IN HUNDREDS OF FEET

Figure 2. Generalized geologic profile in area of recharge operation.

ficiol recharge of the deep sandstonas is one method by which the high productivity can be maintained. The great decrease in the water levels will permit re­charge with gravity injection.

Recharge Water One source of recharge water is water usad for

cooling purposes in various industrial processes. Ac­cording to McDonald and Sasman, there are five in­dustries in northeastern Illinois recharging cooling water at rotas of '.25,000-395,000 gpd.2 This water flows through closed circulation systems and its min­eral character is not changed. It does undergo an increase in temperature, however. Since water quality requirements of many industrial processes are par­ticularly vulnerable to increases in temperature, re­charging high temperature cooling water may ulti­mately increase well water temperatures and serious­ly affect the industrial operations. This article de­scribes the effect on well water temperaturas of one

industry recharging high temperature cooling water effluent.

The water for this industry is, primarily, obtained from a 1348-ft daep well (well No. 1 in this article) and a 1353-ft deep well (well No. 2 in this article) both finished in the Ironton-Galesville Sandstone. These wells are cased and cemented to dapths of 63'.2 and 639 ft, respectively. They are approximately 450 ft apart. The water is used primarily for cooling air conditioning condensars and, intermittently, for cooling emergency engine alternators. Water cir­culates through a closed piping system and is re­turned to the ground through a recharge well 608 ft deap, cased to a depth of 244 ft. The recharge well is SO ft from supply well No. I and approximately 435 ft from supply well No. 2. Recharge occurred at a continuous rate of 500-600 gpm during the first five years of plant operation. During the past four years, the recharge rote hos baen about 200-300 gpm. A third supply well at the site has a depth of 373 ft

Page 17: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

T abfe 1. Groundwater pumpage trends and demand projections*

Date 1900 1940 1960 1970 1980 2020

Pumpage (mgd) 31 85

177 260 314 (projected) 923 (projected)

*Includes Cook, DuPage, Kone, Lake, McHenry, and Will Counties

Table 2. Generalized stratigraphy and water-yielding properties of rocks in northeastern Illinois.

Geologic Units

Glacial drift

Siiurian dolomite

Maquoketa shale

Galena-Platteville dolomite*

Glenwood-St. Peter sandstone*

New Richmond, One-ota, Potosi, and Franconia Forma-tions*

I ronton-Galesvi lie sandstone*

Eau Claire shale

Eau Claire and Mt. Simon sandstones

Thickness (ft)

0-400+

o.-100+

0-250

150-350

75-650

45-750

103-275

235--450

2000±

Water Yielding Properties

Yields of wells variable, some well yields greater than l 000 gpm Yields of wells variable, some well yields greater than 1000 gpm Generally not water yielding, acts as barrier between shallow and deep aquifers Water yielding where not capped by shales Estimated transmissivity 15 percent that of Cambrian-Ordovician aquifer Estimated transmissivity 35 percent that of Cambrian-Ordovician aquifer

Estimated transmissivlty 50 percent that of Cambrian-Ordovician aquifer Generally not water yielding, ads as barrier between Ironton-Galesville and Mt. Simon Moderate amounts of water, per. meability between that of Glen­wood-St. Peter and Ironton-Galesville, water quality problem with depth

*Collectively referred to os Cambrian-Ordovician aquifer

Table 3. Groundwater temperature at measured distances from recharge well.

Well No.

Supply Well l Supply Well 3 Farm Well 1 Farm Well 2 Farm Well 3 Form Well 4 Farm Well 5

Depth (ft)

1348 373 330 275 241 302

?

Distance from Re­charge Well (ft)

50 450 525

1000 2000 2000 3200

Water Temp. (o F)

57.9 78.8 64.5 54.0 51.0 45.5 49.7

and a capacity ot about 200 gpm. During recent years it has been used in the winter instead of wells 1 and 2 when a smaller capacity is required.

The structure and general characteristics of the rocks beneath northeastern Illinois are shown in Table 2. Available records indicate that the glacial drift is 225-250 ft thick in the general vicinity of the recharge installation and overlies the St. Peter Sand­stone, the top bedrock formation. This formation is 250 ft thick and is composed primarily of fine to coarse groined sandstone. Underlying the St. Peter Sandstone are nearly 100 feet of New Richmond Sandstone. This is followed by more than 500 ft of dolomite of the Oneota, Potosi and Franconia Forma­tions. The Ironton-Galesville Sandstone, below the Franconia Formation, is 207 feet thick and pene­trated by the two deep supply wells.

Upon completion, the recharge well had a specific capacity of 11.8 gpm/ft of drawdown. Initial iniec­tion tests were conducted with supply well No. 1 pumping 1620 gpm.

Warmer Water The temperature of the water entering the re­

charge well varies from about 85-110 °F, deRending in part on the volume of water used for cooling, the supply well being used and the season of the year. No significant mechanical problems have occurred with the recharge operation. However, in April, 1970, a farmer on property adioining the installation noticed that water from his well was warmer than normal. A subsequent investigation revealed a mark­ed increase in ground water temperature for a dis­tance of at least 525 ft from the recharge well.

Water temperatures were measured in the re­charge well, the supply well in operation (No. 1), the shallow supply well and five farm wells in the area during a 4-hr period on one day (Table 3). Water was entering the recharge well at a temperature of 86.5 °F and water from supply well No. 1 was 57.9 °F. Previously recorded temperatures for water from the two deep supply wells had been 57.5 °F and 60 °F. The recharge rate during the investigation was 320 gpm.

Supply well No. 3, the shallow supply well, had not been in operation for some time prior to the in­vestigation. When the pump was turned on, the water temperature rose rapidly from 50 °F to 78.8 °F, and then remoined constant. One farm well was in op­eration at the time of the investigation. The tempera­ture of the water at other farm wells varied only slightly during pumping periods of 15-30 min. The farm wells are usually not pumped continuously for extended periods.

The five farm wells studied are located less than a mile from the recharge installation (Fig. 1 ). The wells range in depth from 241-330 ft and penetrate the St. Peter Sandstone (Fig. 2). The recharge well is open to

Page 18: Ferm ii ablss.fnal.gov/archive/test-tm/1000/fermilab-tm-1285.pdf · Ferm ii ab TM - 1285 ... Cooling ponds reject heat by evaporation, ... Ground 'lDRY"Tower Water(2) Water-to-Recharge

both the St. Peter and New Richmond Sandstones. The. deep supply wells are cased into the Oneota Dolomite below the New Richmond Sandstone.

The temperature of water from wells finished in glacial drift and upper bedrock formations varies somewnat with the time of year, the depth of the well, the depth and thickness of the water bearing formation, and the length of pumping time before the temperature is measured. Records are available for water temperatures from seven wells in the general area though these wells are several miles from the specific location (Table 4). The depths of these wells range from 183-500 ft and the recorded temperatures range from 52 °F to 57.6 °F. The aver­age temperature of the seven wells listed in Table 4 is 55.1 °F. Although this is a few degrees wormer than water from three of the farm wells, it is consid­erably colder than the two farm wells closest to the recharge injection wells.

A temperature gradient curve (Fig. 3) shows that high temperature recharge water has hod a signifi­cant effect on the groundwater temperature in the general vicinity, for a distance of at least 500 ft from th3 recharge well, and perhaps OS far OS ] 000 ft.

Another development hos caused additional con­cern regarding the continued operation of the re­charge system at the installation. After an idle per­iod of about three months, the temperature of water from supply well No. 1 (nearest the recharge well} was 88 °F. Within a few hours of operation, the temperature lowered to 60 °F, which is in the normal range for water from this well. Recent recharge water temperatures have ranged from 90 °F to 110 °F. Al­though the plant hos been in operation for nine years and the supply well previously had been idle for periods up to several weeks, this was the first time a high temperature water from the supply well hod been detected. In looking for a reason for the high temperature, a check valve in the system was dis­covered to be defective. With supply well No. 1 not operating, port of the normal flow of water was re­versed and heated water was entering the deep sandstone formation through the idle supply well. Re­pair of the check valve corrected this condition.

Conclusions No undesirable effects have been reported at

four of the five groundwater recharge installations in northeastern Illinois, other than some associated with the actual mechanics of the operation. Recharge rotes at these four installations reportedly range from ap­proximately 25,000-395,000 gpd. All of these facil­ities hove been in operation nine years or more.

Under certain conditions of geologic formation permeability, recharge rotes and water temperoure, it appears highly probable that the normal ground water temperature will be raised significantly for some distance from the recharge installation. As a re­sult of this study it seems desirable that additional

90 i 80

u.

• - 70 .... "" "' !;;:: :::l 60 0..

ffi ...

\

\ ~

\ :--.

' '~ r--__

ffi so ~

• ·=--! 40

o 3 0 4 8 12 16 20 24 28 32 36

OISTAllCE FROM RECHARGE WELL, IN HUNDREDS OF FEET

Figure 3. Ground waler temperature gradient in area of recharge operation.

Table .4. Selected well water temperatures in general re­gion of recharge operation.

Well Depth (ft) Water Temp. (° Fl Month Measured

183 54.0 Sept. 230 54.5 May 298 52.0 Oct. 402 57.5 Apr. 418 55.7 Apr. 451 54.9 May 500 57.6 Feb.

Average 55.1 Median 54.9

consideration should be given to this problem in fu­ture operations of this type. Monitoring the recharge injection rate, water levels, temperature and quality of the injection water and of the ground water at one or more observation sites at different distances from the injection site would be beneficial in attempts to determine long-range effects on ground water aqui­fers.•

References 1. Schicht, R. J. & Moench, A. Projected Groundwater Deficien­

cies in Northeastern Illinois, 1980-2020. llliqois State Water Survey Circular 101 (1971).

2. McDonald, C. K. & Sasman, R. T. Artificial Groundwater Re­charge in Northea~tern Illinois. Groundwater (April, 1967).

3. Sosman, R. T. Industrial Water Recirculation In Northeastern Illinois. American Water Works Association (May, 1970).

4. Csallany, S. C., Roberts, W. J. & Towery, N. G. Illinois P-260 State Water Resources Planning Project Progress Report. 1echnical Appendix to the Report on Priority and Planning Elentents for Developing Illinois Water Resources, Illinois De­pamnent of Business and Economic Development (1969).