24
FG Wilson Control Systems www.FGWilson.com

FG Wilson Control Systems · 2013-12-06 · FG Wilson DCP-10 and DCP-20 The FG Wilson DCP range allows you to monitor and control your generator set with ease, providing important

  • Upload
    others

  • View
    101

  • Download
    9

Embed Size (px)

Citation preview

FG Wilson Control Systems

www.FGWilson.com

Contents

1002T Analogue Control Panel

FG Wilson DCP-10 and DCP-20 Digital Control Panels

PowerWizard 1.1, 1.1+ and 2.1 Digital Control Panels

PowerWizard Remote Monitoring Options

PowerWizard Remote Monitoring and Control Options

easYgen–2500SynchronisingControlPanel

easYgen–3200SynchronisingControlPanel

easYgenControlPanelOptions–NetBiterFGW200

easYgenControlpanelOptions–I/OExpansionModule

Load Transfer Panels

CTIPanelFeatures

ATIPanelFeatures

Features and Options

Putting You in Control

Whateveryourpowerrequirements,FGWilsoncanprovideacontrolsystemtosuityourneeds.Ourgeneratorsetexperts

designandvalidateFGWilsoncontrolsystemstooptimiseyourgeneratorsetperformanceandputyouincontrol.

AllFGWilsoncontrolpanelsarecompact,versatileandeasytouse.Ourcomprehensiverangeincludeskey-start

analoguecontrolpanelsforstraightforwardfunctionalityandreliability;digitalcontrolpanelssuitableforuseinmains

failureapplications,providingadvancedmetering,protectionanddiagnostics;andthenextgenerationofadvanced

synchronisingpanelswithintegratedloadmanagementcapability,suitableforsynchronisingupto32generatorsets.

Ourrangeofloadtransferpanelsaredesignedtoenhancetheoperationofyourstandbygeneratorsetinconjunctionwith

ourelectroniccontrolpanels,toprovideautomaticcontrolofyourstandbygeneratorsetintheeventofapoweroutage,

24hoursaday,365daysayear.

Formorechallengingpowerrequirements,ourPowerSolutionsTeamisdedicatedtothedesignandproductionof

bespokecontrolsystemstomeetyourindividualneeds,regardlessofcomplexity.

FG Wilson Control Systems

1002T

The1002TControlPanelisequippedwithallthenecessarygeneratorsetinstrumentationandprotectiondevices,whilstprovidingthestraightforwardfunctionalityandreliabilityofakey-startpanel.

1002TAnalogue Control Panel

• Simplifiedmonitoringofgeneratorsetconditionsata glance• Heavyduty,reliableindustrialpushbuttonsandswitches

• Visualindividualwarningandshutdownsthrough LED’s• Universalpictorialfaultlampindicators

Features• Analoguemetering:voltmeter,ammeter,hours-run counter,combinedfrequencyandtachometer• 7positionvoltmeterphaseselectorswitch• 4positionammeterphaseselectorswitch• Preheat(startaidactiveLEDindicator)• DCsupplyfromstartingbatteryprotectedbyMCB’s• Printedcircuitboardassemblies• Multi-pinplugandsocketconnectionsforeaseof servicing• Engineprotectionthroughcriticalshutdowns• ACinstrumentsare90°deflection,flushmounted• ACinstrumentsinaccordancewithIEC60051and 60529,DIN43700and43718,BSEN60051and 61010,UL94

Benefits

FG Wilson DCP-10 and DCP-20

TheFGWilsonDCPrangeallowsyoutomonitorandcontrolyourgeneratorsetwithease,providingimportantdiagnosticinformationwhilstensuringyourunitoperateswithinsafeparameters.

FGWilsonDCPdigitalcontrolpanels,providesimple, intuitivemenunavigationandcontrolofyourgenerator setoperations.KeyinformationisdisplayedviatheLCDscreenandLED’susinguniversallyrecognisedsymbols,eliminatingtheneedforcomplexinstructionsorlanguagesettings.

• Automaticstartcontrolmodule

• Integratedmetering&controls

• Monitoring,protection,operationalstatus,fault conditionsandmeteringdisplayedviaLCD&LED’s

• Configurationofparametersvialicencefreesoftware

• Robustelectronicspackage

• Symbolsforsimple,intuitivecontrol

Features• Configurationofparametersbyfrontpanelpush buttonsorbyPCviaminiUSBinterface(DCP-10)or communicationsoftware(DCP-20)• TrueRMSVoltageSensing• Engine&ACmonitoring• Run/AutokeyswithLEDindicators• Under/Overvoltageprotection• Larger128×64graphicLCD(DCP-20only)• RS485,RS232orUSBportforremotecommunication (DCP-20only)• Powermetering(DCP-20only)

Benefits

FG Wilson DCPDigital Control Panels

FG Wilson DCP-10 is standard on 5.5 – 220 kVA range

PowerWizardPowerWizard – Providing safe control of your generator setTheFGWilsonPowerWizardrangeofdigitalcontrolpanels,combinestraightforwardmenunavigationwith advanced metering and protection technology. They are used in automatic mains failureapplicationsinconjunctionwithtransferpanels.

OurPowerWizardrangeallowsyoutomonitorandcontrolyourgeneratorsetwithease,whilstensuringyourunitoperateswithinsafeparametersandprovidesimportantdiagnosticinformationwhenneeded.

Digital Control Panels

PowerWizard 1.1, 1.1+ and 2.1

• Robustelectronicspackageforindustryleadingreliability• Singlemenulayoutforeaseofnavigationandmonitoringwithshortcutkeysforimmediateaccesstoengine or AC metering

• 10.5-32VDCprovidingasinglemoduletocoverthe wholeFGWilsongeneratorsetrange• Comprehensiverangeofstandardfeaturesandoptions toensurethemostappropriateconfigurationforyour needs• ServicedusingstandardEST

Features• TrueRMSVoltageSensing• CAN1DataLinkforcommunicationtoelectronic engines,CAN2(2.1only)AccessoryDataLinkfor additional modules• 40uniqueeventslogconfigurationincludingfirst,last andnumberofoccurancesandrealtimeclock• EngineandACMonitoring• Twodisplaylanguages(CustomerLanguage& TechnicianLanguage)• Upto5sparefaultchannels• Configurablesenderinput• Dedicatedkeytoresetallfaultsandmainmenushort cutkey• Run/Auto/StopkeyswithLEDindicators• Integratedmeteringandcontrolsreducingcomponents andwiring,aidingreliabilityandeaseofservice• Generatorsetvoltageandover/underfrequency protection(1.1+and2.1only)• MODBUSconnectiontobuildingmanagementsystem viaRS485(2.1only)• Powermetering(2.1only)

Benefits

PowerWizard 1.1+ is standard on 275 – 2500 kVA range

PowerWizardRemote Monitoring Options

Remote MonitoringThePowerWizardAnnunciatorisa16-channneldisplayunitforremotelymonitoringthestatusofFGWilsongeneratorsetsatadistanceofupto240metres.TheAnnunciatorcommunicatesviatheCAN2datalinkwhichcomesasstandardongeneratorsetsfittedwiththePowerWizard 2.1 Control Panel. Eachofthe16channelsontheAnnunciatorhastwoLEDstodisplaystatusandalarmsignalsdirectlyfromthePowerWizard2.1ControlPanelonthegeneratorset.Thepre-setchannelslinkedtoeachLEDdisplaycanbeindividuallyconfiguredusingtheElectronicServiceTool(EST).ThisallowsOperatorstomonitordifferentgeneratorsetstatusandalarmsignalstosuitsite-specificrequirements.InadditiontotheLEDdisplay,theAnnunciatorincludesanaudiblealarm,analarmacknowledgepushbuttonandalamptestpushbutton.

PW Panel Option Codes Annunciator Dimensions

A mm (in) B mm (in) C mm (in)

PW 2.1 ANN16 158(6.22) 130(5.12) 288(11.34)

AB

C

AB

C

The FG Wilson Communications Interface Module andSoftwarePackageallowsoperatorstomonitorandcontrolallgeneratorsetfunctionsfromavirtualcontrolpanelontheirPC.

Dependingontheoperator’sdistancefromthegeneratorset and the type of connection available to link to thegenerator set, two options are offered:

• Fordistancesupto1,000metres,whereitisconvenienttohaveahard-wiredconnection,ageneratorsetcanbe monitored using the Communications InterfaceModuleandSoftwarePackageontheoperator’sPCor laptop.

• Alternatively, when laying a hard-wired connectionis not convenient, the samemonitoring and controlfunctionalityisavailable,butcommunicationbetweentheoperator’sPCorlaptopandtheControlPanelismadethroughamodemandthetelephonenetwork.Dependingontheoperator’sdistancefromthegeneratorsetandthetypeofconnectionavailabletolinktothe generator set, two options are offered:

Remote Monitoring and Control

Additional remote monitoring and control options,via the internet, GSM and GPRS are available withPowerWizard2.1ControlPanels.Pleasecontactyourlocal FGWilsonDealerforfurtherinformation.

Operator laptopor PC

Using Telephone Network

TelephoneNetwork

Modem

Using Hard-wired Connection

Generator set withPowerWizard 2.1

Control Panel

CommunicationsInterfaceModule

CommunicationsInterfaceModule

Generator set withPowerWizard 2.1

Control Panel

Connection Via Panel Option Codes

PW2.1

Hand-wiredConnection(Upto1,000m) REM1

TelephoneNetwork REM2*

*Modemtolinktheoperator’sPCorlaptopwiththetelephonenetworkisnotincluded.Note:PCorlaptopisnotincludedinanyoftheaboveoptions.

PowerWizardRemote Monitoring and Control Options

easYgen–2500Synchronising Control Panel

easYgen–2500

• Capableofset-to-setsynchronisingforupto16generator sets

• Userfriendlyinterface• Easysystemnavigationviaprogrammablesoftkeys• MultiplecommunicationprotocolsforcommunicationwithEngineControlUnits(ECUs),externalI/Oboards,PLCs and modems

• Multilingualcapability:English,Chinese,French,German,Italian,Japanese,Polish,Portuguese,Russian,SpanishandTurkish

• Capableofworkingwithallcommonindustrialinterfaces

Features

• Powerandreactivepowerloadsharingupto16unitsincludingload-dependentstart/stop

• Enginestart/stopandgeneratorsetmeasuringandprotection

• Runninghoursbalancing• Breakercontrol:synchronization,open-closecontrol, only-opencontrol,breakermonitoring• Deadbusclosurenegotiation• PLC-likeprogrammingwithLogicsManager• 300-entry,timeanddatestamplog• Operatinghours/start/maintenancecounters• Configurabletriplevels/delays/alarmclasses• Fieldconfigurableapplicationsettings• Multi-levelpasswordprotection

Benefits

The easYgen-2500 offers industry leading power management and control

TheeasYgen-2500isageneratorset-to-setcontrollerforparallelingandloadsharingapplicationsofupto16generatorsets.AspecialfeatureoftheeasYgen-2500istheenhancedloadsharingsystem.Thisprovidesadvancedgeneratorloaddependentstart/stopfunctionalitywithautomaticgeneratorsetselectiontoensureoptimalsystemefficiency.

Generator Set• Over/undervoltage• Over/underfrequency• Deadbusdetection• Overload• Reverse/reducedpower• Timeovercurrent• Instantaneousovercurrent• Inversetimeovercurrent• Phaserotation• Unbalancedload• Powerfactor

Engine• Over/underspeed• Batteryover/undervoltage• Speed/frequencymismatch

Inputs / Outputs (I/O)

• 3phasetruer.m.s.generatorsetcurrent/power• 1speedinput(magnetic/switching)• 10configurablediscretealarminputs• Fiveconfigurableanalogueinputs• Fourconfigurableanalogueoutputs (+/–10V,+/–20mA,PWM;configurable)

• TwoCANbusinterface(loadshare,Toolkit)• 11RelayOutputsIsolated• RS485Modbusinterface• ServicePort (RS232–WoodwardDPCcablerequired)

ProtectionService / Configuration

Loadshare Line57/58

CAN 1

CAN BusEngine Level

MPU

Measuring

FrequencyBiasing

VoltageBiasing

10 Digital Inputs

11 Digital Outputs

5 Analogue Inputs

ECU

2 x I / OExpansion

board

USB toCAN

DPCCable

SCADA

87/90

CAN 22 Analogue Outputs

Service Port RJ45

55/56

USB

• J 1939

• 16 Digital Inputs• 16 Digital Outputs

easYgen–2500

easYgen–3200†

Synchronising Control Panel

easYgen–3200

• Capableofgeneratorset-to-set,set-to-mainsandmultiple set-to-mainssynchronisationforupto32generatorsets• Enhancedsystemflexibilitymeetsdemandingcustomer specifications• Userfriendlyinterfacevia320x240pixelgraphical interactive5.7”LCD• Easysystemnavigationviaprogrammablesoftkeys• Multilingualcapability:English,Chinese,French, German,Italian,Japanese,Polish,Portuguese, Russian,Spanish,TurkishandFinnish• Multiplecommunicationprotocolsforcommunication withEngineControlUnits(ECUs),externalI/Oboards, PLCs and modems

Features

• Powerandreactivepowerloadsharingupto32unitsincludingload-dependentstart/stop

• Enginestart/stopandgeneratorsetmeasuringandprotection

• Automaticbaseloading• Runninghoursbalancing• Import/exportcontrol• Deadbusclosurenegotiation• ECUmonitoringandalarmmanagementaswellas remotestart/stopandcontrolcommands• PLC-likeprogrammingwithLogicsManager• 300-entry,timeanddatestamplog• Operatinghours/start/maintenancecounters• Configurabletriplevels/delays/alarmclasses• Fieldconfigurableapplicationsettings• Multi-levelpasswordprotection• RP3000remotedisplaypanelavailablefor managementandcontrolfromadjacentplantroom

Benefits

The easYgen-3200 offers industry leading power management and control

The easYgen-3200 is a versatile control unit, incorporating all the features of the easYgen-2500includingenhancedloadsharing,andisadaptabletoeveryapplication.Typicalapplicationsinclude co-generation, standby,AMF,peak shaving, import / exportordistributedgeneration. This controlpanelissuitableforsynchronisingupto32generatorsetsrunninginislandmode,mainsparallelandmultiple unit mains parallel operations.

† Available through Power Solutions

Generator Set• Over/undervoltageandfrequency• Deadbusdetection• Overload• Unbalancedload• Reverse/reducedpower• Timeovercurrent• Instantaneousovercurrent• Measured ground fault• Phaserotation• Powerfactor

Engine• Over/underspeed• Batteryover/undervoltage• Auxiliaryexcitation• Speed/frequencymismatch

Mains• Over/undervoltageandfrequency• Phaseshift• Rotation field

Inputs / Outputs (I/O)

• Twoseparatesetsof3-phasetruer.m.s.voltage measuringinputsforthegeneratorsetand mains,and2-phasebusbarvoltage• 3-phasetruer.m.s.generatorsetcurrent/power• 1-phasetruer.m.s.currentinputfreelyconfigurable• 1speedinput(magnetic/switching)• 10configurablediscretealarminputs

Protection Service / Configuration

Guidance / LoadShare Level

RS232

CAN 1

RS485 1

CAN Bus Engine Level

CA

N 2

MPU

FrequencyBiasing

VoltageBiasing

10 Digital Inputs

12 Digital Outputs

3 Analogue Inputs

AC Measurement:• 4 x U Gen, 3 x l Gen• 2 x U Bus• 4 x U Mains, 1 x l Mains

MCB GCB

• J 1939 including 100 SPN text events

• 16 Digital Inputs• 16 Digital Outputs

ECU

2 x I/OExpansion

board

PLC /SCADA

• Upto12programmablediscreteoutputs• Threeconfigurableanalogueinputs• Twoconfigurableanalogueoutputs• TwoCANbuscommunicationnetworks(upto 32participants,isolated)• TwoserialportssupportingModbusRTU Protocol,RS-485andRS-232(isolated)

easYgen–3200

easYgen Control Panel OptionsNetBiter® FGW200Remote management for new and existing generator set installations

With softwaredesignedexclusively forFGWilson, theFGW200offersnewopportunities for remote accessovertheinternetandmobilephone.TheNetBiterunitissuitableforuseinnewandexistinginstallationsduetocontrolpanelAutoDetectsoftwarewhichoffersplugandplaycapability.

Remote management that takes customer service to a new level by:

Features

• NewAutoDetectsoftwareallowsretrofittoPowerWizard2.1,easYgen-2500, easYgen-3200controlpanelsandATItransferpanels

• Builtinwebinterfacefordatamonitoring• BuiltinalarmmanagerforSMS,emailandSNMP• Builtindataloggerofhistoricaltrends• GSM/GPRSmodemincluded• Allsoftwareincluded,easilyupgradedremotelyandprovidedwithnolicensingcost

• Reducingtheneedtotraveltoremotesitesfor maintenancepurposes• Minimisingdowntimewithinstantinformationabout equipmenthealth• Theftpreventionthroughgeneratorsettracking• Fuellevelmonitoringtooptimisefuelinventory• Startuploggingtohelppreventgeneratorsetmisuse• AllowingmultipleprojectanddevicemanagementthroughNetBiter.net

I/O Expansion Module†

Connection to and from external system devices enabling more flexibility to meet your specfic power requirements.

Features

easYgen Control Panel Options

• 8configurablediscretealarminputs• 8configurablerelayoutputs• ConnectiontoeasYgencontrolpanelviaCANbus• InputandoutputconfigurationviaonboardeasYgenrelaymanager

• RemotecontrolofoutputrelaysviaCANbus• TheI/OExpansionModulecanbeusedwithothermanufacturer’scontrols.ConsultWoodwardproductmanual37135forinformationregardingtheaddressassignmentsoftheCANbusinterface

† Available through Power Solutions

Load Transfer Panels24 Hour Power Protection 365 days a year...

Load Transfer Panel Range

• Fullyautomaticmainsfailuresensingandgeneratorsetstart signal

• Pre-programmedenablingthepaneltorunoninstallationwiththeabilitytocustomiseifnecessary

• Fastactingswitchesreducetransfertimesbetweensetandutilitypower

• Availablefrom63–3200A• SeamlessintegrationwithFGWilsondigitalcontrol

panels

Benefits

FG Wilson’s range of intelligent Load Transfer Panels offer you peace of mind.

TheFGWilsonLoadTransferPanelrangeoffersanelectronicallycontrolledresponsetopoweroutages. Withflexible,upgradeableoptionsandahighleveloffunctionalityFGWilsontransferpanelsprovide24-hourautomaticcontrolofstandbygeneratorsets,365daysayear.

• Automaticandmanualoperation• Automaticallyprovidesgeneratorsetstartsignalupon detectionofmainsfailure,overvoltageorlossofphase• Automaticmainsre-transferfunction• Flexible,upgradeableoptions• Testoperationsandsequencesaccessiblefrompanelorremotely

• Manualswitchoperationpossibleviaexternalhandle• LEDfunctionsdisplayshowinggeneratorset/mains availabilityandswitchposition• LCDdisplayforvoltageandtimers• LoadtransferpanelrangemeetsATSIEC60947-6-1 standard

Features

Model Rating ATI Transfer Dimensions Weight

A mm (in) B mm (in) C mm (in) kg (Ib)

ATI250 250A 900(35.4) 600(23.6) 323(12.7) 39(86.0)

ATI400 400A 900(35.4) 600(23.6) 323(12.7) 44(97.0)

ATI630* 630A 1100(43.3)† 600(23.6) 398(15.7) 66(145.5)

ATI800* 800A 1375(54.1) 775(30.5) 600(23.6) 125(275.6)

ATI1000* 1000A 1375(54.1) 775(30.5) 600(23.6) 130(286.6)

ATI1250* 1250A 1800(70.8) 1005(39.6) 775(30.5) 230(507.1)

ATI1600* 1600A 1800(70.8) 1005(39.6) 775(30.5) 330(727.7)

ATI2000* 2000A 2200(86.6) 1000(39.4) 1000(39.4) 400(881.8)

ATI2500* 2500A 2200(86.6) 1000(39.4) 1000(39.4) 400(881.8)

ATI3200* 3200A 2200(86.6) 1000(39.4) 1000(39.4) 400(881.8)

Model Rating ATI Transfer Dimensions Weight

A mm (in) B mm (in) C mm (in) kg (Ib)

CTI63 63A 600(23.6) 400(15.7) 200(7.9) 19(41.8)

CTI100 100A 600(23.6) 400(15.7) 200(7.9) 19(41.8)

CTI125 125A 600(23.6) 400(15.7) 200(7.9) 19(41.8)

CTI160 160A 600(23.6) 400(15.7) 200(7.9) 19(41.8)

*Floorstanding.†DimensionAforthetopcableentrymodelwillchangeto1350mm(53.1in)

ATI wall mountedCTI wall mounted Floor standing (ATI only)

Load Transfer Panels

CTI Panel Features

CTI Load Transfer Panel – Ratings 63 – 160 AmpsKey: – Standard Feature – Optional Feature

Programmable Countdown Timers

Setroutinetimesfordelayonstarts,delayontransfer,delay

on re-transfer and run on timer.

Manual HandleFullyintegratedhandleformanual operation.

PadlockableSwitchcanbepadlockedinallthreepositionsforaddedsecurityandsafety.Onlypossibleinmanualoperationmode.

Wall Mounting KitPanelcanbewallmounted

forgreaterflexibilityinpositioning.

Auto/Manual/Test Mode Status IndicationAllowson/offloadtestsatroutineservicechecks.

LCD DisplayShowsdetailedstatusofsystematalltimesfor

greater awareness and control.

Control TerminalsGenerator set remote start signal and terminals for remotelymonitoringthesystem.

System Status Indicators

Showsstatusofutilitypower,generatorsetandswitchat

all times.

Voltage Sensing Tap

Allows for pole voltagesensing.

KeypadForstraightforwardprogramming and testing. Passwordprotectionisincluded.

Terminal shroudForaddedprotection.

Auxiliary ContactsAuxiliary/voltfreecontactsforremotelymonitoringtheswitchposition.

Solid Neutral KitAllowstheconnectionofneutralcablesfromutilitypower, generator set and loadwithouthavingthe

neutralbrokenbytheswitchduring transfer operations.

Auxiliary ControlsAuxiliaryinputsforautomaticcontrol,remotetestonloadandmanual re-transfer.

Top and Bottom Cable Entry Aids ease of installation

Lightning Protection Ensuringsystemsafety

Load Terminal Extensions Improvingeaseofinstallation

Ingress Protection IP54 Protectionforthecontrolpanel

Load Transfer Panels

ATI series

ATI Load Transfer Panel – Ratings 250 – 1600 Amps

RS485 Communications ModuleEnablesaccesstothesystemremotelythrough

telephoneorPCviamodem.

LCD DisplayShowsdetailedstatusofsystematalltimesforgreater awareness and control.

Programmable Countdown TimersSetroutinetimesfordelayonstarts,delayontransfer,delayonre-transferandrunon timer.

Wall Mounting KitPanelcanbewallmounted

forgreaterflexibilityinpositioning(ATI250and

400).

Power MeteringTomeasureloadcurrent,kW,kVAr,kVA,powerfactor.

Manual HandleFullyintegratedhandlefor

manual operation.

PadlockableSwitchcanbepadlockedinallthreepositionsforadded

securityandsafety.

Solid NeutralAllowstheconnectionofneutralcablesfromutilitypower, generator set and loadwithouthavingthe

neutralbrokenbytheswitchduring transfer operations.

Auto/Manual/Test Mode Status IndicationAllowson/offloadtestsatroutineservicechecks.

Auxiliary ContactsAuxiliary/voltfreecontactsforremotelymonitoringsystem;switchposition,padlockandautomaticormanualoperation.

Volt Free ContactsForpoweravailableandgeneratoravailable.

Lightning ProtectionEnsuresthesafetyofsystemduringlightningstorms(includesvoltfreecontactsforutilitypowerandgeneratorset).

System Status Indication

Showsstatusofutilitypower,generatorsetandswitchat

all times.

KeypadForstraightforwardprogramming and testing. Passwordprotectionisincluded.

Two Wire Start Signal

Simpletwowireconnectionforautomaticcontrol.

Bottom Gland PlateRemovableglandplateproviding

increasedaccessibilitywithasizeableareaforutilitypowerandgeneratorsetcablestobe

connected.

Installation Typicalinstallationsetup

Ingress Protection IP54Protectionforthecontrolpanel

Wall Mounting PanelsWallmountwithease–includesfittings

Top Cable Entry Aids eased installation

Key: – Standard Feature – Optional Feature

ATI Panel Features

ATI series

ATI Load Transfer Panel – Ratings 2000 – 3200 Amps

RS485 Communications ModuleEnablesaccesstothesystemremotelythrough

telephoneorPCviamodem.

LCD DisplayShowsdetailedstatusofsystematalltimesforgreater awareness and control.

Programmable Countdown TimersSetroutinetimesfordelayonstarts,delayontransfer,delayonre-transferandrunon timer.

Manual HandleFullyintegratedhandlefor

manual operation.

PadlockableSwitchcanbepadlockedinallthreepositionsforadded

securityandsafety.

Auto/Manual/Test Mode Status IndicationAllowson/offloadtestsatroutineservicechecks.

Auxiliary ContactsAuxiliary/voltfreecontactsforremotelymonitoringsystem;switchposition,padlockandautomaticormanualoperation.

Volt Free ContactsForpoweravailableandgeneratoravailable.

Lightning ProtectionEnsuresthesafetyofsystemduringlightningstorms(includesvoltfreecontactsforutilitypowerandgeneratorset).

System Status Indication

Showsstatusofutilitypower,generatorsetandswitchat

all times.

KeypadForstraightforwardprogramming and testing. Passwordprotectionisincluded.

Two Wire Start Signal

Simpletwowireconnectionforautomaticcontrol.

Bottom Gland PlateRemovableglandplateproviding

increasedaccessibilitywithasizeableareaforutilitypowerandgeneratorsetcablestobe

connected.

Installation Typicalinstallationsetup

Ingress Protection IP54Protectionforthecontrolpanel

Key: – Standard Feature – Optional Feature

ATI Panel Features

Features and Options1002T DCP-10 DCP-20 PW 1.1 PW 1.1+ PW 2.1 easYgen

2500easYgen3200+

Instrumentation

LCDDisplaywithAutoPowerff – – –

BatteryTrickleChargeAmmeter – – –

AudibleAlarm –

RemoteAnnunciator – – – – –

AC

Met

erin

g

Voltmeter3-phase(L-L&L-N)

Amps(perphaseandaverage)

Frequency

kW(total&perphase) – – – –

kVA(total&perphase) – – – –

kVAr(total&perphase) – – – –

PowerFactor(overallandperphase) – – – –

kWHours – – – –

kVArHours – – – –

DC

Met

erin

g

BatteryVoltmeter –

EngineHoursRun

EngineJacketWaterTemperature(in°Cor°F) –

LubeOilPressure(inPsi,kPAorbar) –

EngineSpeed(rpm) – –

CrankAttemptCounter – – – –

StartCounter – – – –

Protection

FailtoStart –

Low Oil Pressure

HighEngineTemperature

Underspeed,Overspeed –

LossofEngineSpeedDetection – – –

Low/HighBatteryVoltage –

BatteryChargerFailure(ifBatteryChargerfitted) – – –

UnderVolts,OverVolts – –

UnderFrequency,OverFrequency – – – –

Overcurrent – – – – –

ConfigurableSenderInput (for'OilTemperature'or'FuelLevel'optionsonly) – – – –

EarthLeakageProtection – – –

EarthFault Protection – – –

Low Fuel LevelAlarm –

Low Fuel LevelShutdown – – –

HighFuel LevelAlarm – – –

FuelTransferSystemControl – –

Low CoolantLevelShutdown – – –

Low Coolant Temperature Alarm –

HighLubeOilTemperatureShutdown – – –

OverloadviaAlarmSwitchonBreaker – – – –

OverloadviaOverCurrentRelay – – – – –

Low Gas Pressure – – – – – – –

HighGasPressure – – – – – – –

HighExhaustTemperatureAlarm – – –

1002T DCP-10 DCP-20 PW 1.1 PW 1.1+ PW 2.1 easYgen 2500

easYgen3200+

Protection Monitoring

NameofEachEvent – – –

EngineHoursatFirstOccurrenceofEvent – – –

TimeandDateofFirstOccurrenceofEvent – – – – –

EngineHoursatLastOccurrenceofEvent – – –

NumberofOccurrencesofEvent – – –

Instrumentation

SpareFaultChannels

NumberofChannelsAvailable 0 0 4 3 5 5 5 6

Exceptions:

OnmodelsP730P1–P1100E1 – – – – 3 3 4 5

OnmodelsP1250–P2500-1 – – – – 2 2 3 4

Controls

2LEDStatusIndicators(1redshutdown,1amberwarning) – –

Runkey,AutoKeyandStopKeywithLEDindicators –

Lamp Test

AlarmAcknowledgeKey –

MenuNavigationKeys –

DedicatedKeytoresetallevents – – – – –

EngineandACMeteringShortCutKeys – – – – –

MainMenuandEventLogShortCutKeys – – –

ControlModuleKeyswithTactileFeedback – – –

CAN1DataLink-J1939forcommunicatingwith electronicenginecontrolmodules – – –

CAN2AccessoryDataLink-foradditionalmodulesremoteannuncia-tor,digitalinput/outputmodule – – – – –

RemoteMonitoringandControlDataLink(ModBus) – – – – –

RealTimeClock – – – – –

ServiceMaintenanceIntervalWarning – – – – –

Remote Monitoring and Control – – – – –

StaticBatteryCharger – – –

StaticBatteryChargerwithAutoBoost –

VoltFreecontactsfor:CommonAlarm&GeneratorSetRunning –

EngineCoolantHeaterControls – – –

Control Panel Heater – – – – –

VoltsAdjustPotentiometer – – –

SpeedAdjustPotentiometer – – –

SpeedAdjustSwitch – – –

OilTemperatureDisplay – – – –

Oil Temperature Gauge – – – – –

LubeOilTemeperaturedisplayedonLCDscreen – – –

FuelLevelSwitch – – – –

FuelLevelSender&Display – – –

PanelLockdownStopPushButtonwithsecuritykey – – – – –

NetbiterInternetMonitoringandControlUnit – – – – – –

MainsLoadSensingUnit – – – – – – –

Additional8inputsand8outputs – – – – – – –

Key: –Standard;–Optional

Panel Display languagesArabic*,Bulgarian*,Chinese,Czech*,Danish*,Dutch*,English,Estonian*,Finnish*,French,German,Greek*,Hungarian*,Icelandic*,Italian,Janpanese,Latvian*, Lithuanian*,Norwegian*,Polish,Portuguese,Romanian*,Russian,Slovak*,Slovene*,Spanish,Swedish*,Turkish.

*NotavailableforeasYgencontrolpanels.+AvailablethroughPowerSolutions.

Features and Options

CTI ATI < 1600A ATI > 2000AMotorised Mechanically Held Switch

Facilityformanualchangeover

Protection

Utlitypoweravailable

Utilitypoweronload

Generatoravailable/Generatoronload

Utilitypowerandgeneratoroffload

Manualmode/Automaticmode

Testonload/Testoffload

Manualre-transferforenabled/required

Power/Errorindication(LED)

Facia

Universalsymbolstoallowformultiplelanguages

Liquid Crystal Display

UtilityPowerL1-2,L1-3,L2-3voltage

UtilityPowerL1-N,L2-N,L3-Nvoltage

GeneratorSetL1-N,L2-N,L3-Nvoltage

GeneratorSetL1-2,L1-3,L2-3voltage

UtilityPowerFrequency/GeneratorSetFrequency

Numberoftimesswitchtransfersfrommainstogeneratorset

Timer settings

Standards

CompleteenclosuremeetsstandardIEC60947-6-1

SwithmeetsstandardAC31B

Controls

Under/Overfrequencyfailure

Under/Overfrequencyrestoration

Manual/Autore-transfer

Modeselectpushbutton

Under/OverVoltsFailure

Under/OverVoltsRestoration

DelayonStartTimer

DelayonTransfer

DelayonRe-Transfer

DeadBandTimer

Run On Timer

Auto/ManualControlKeyswitch

LampTestPushbutton

Padlockfacility

SelectionbetweenContactororSwitchMode – –

Cable entry

Top –

Bottom

Load Terminal Extensions

Improvingeaseofinstallation – –

Features and Options

CTI ATI < 1600A ATI > 2000AAuxiliary Contacts

Formonitoringofswitchposition(Includingpadlocking&auto/manual) –

Lightning Protection

Ensuringthesafetyofsystemduringlightningstorms

Ingress Protection IP54

Protectionforcontrolmodule

Power Metering

Tomeasureloadcurrent,kW,kVAr,kVA,Powerfactor –

Volt Free Cotacts

Forutilitypoweravailability&generatoravailable

Communication Module

PluginmodulethatusesJbus/modbusprotocoltoallowremotecommunicationofthechangeoversystem –

Voltage Sensing Tap

Allowingforpolevoltagesensing – –

Solid Neutral Kit

Toconnectneutralcablesfromthemains,generatorsetandload –

Terminal Shroud

Foraddedprotection – –

Key: –Standard;–Optional

Note:Optionsavailabledependsontheexactconfigurationofthegeneratorsetpackage.Notalloptionsareavailableonallpackages.PleasecontactyourlocalFGWilsonDealerformoreinformation

FG Wilson manufactures product in the following locations:Northern Ireland • Brazil • China • India • USAWith headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.To contact your local Sales Office please visit the FG Wilson website at www.FGWilson.com.

FG Wilson is a trading name of Caterpillar (NI) Limited.In line with our policy of continuous product development, we reserve the right to change specification without notice. ControlPanelRange/0513/GB