Fibre optic technology-CG-S Network via Fibre Optic
A.Klepper – 01/04/11 Rev.A
3.2
A.Klepper – 01/04/11 Rev.A 2
Functionality of the fibre-optic cable:
Basic informtions about fibre optic technology
Electr./Optoconverter
Electr./Optoconverter
+-
Electr. signal
Fibre-optic cable with distance up to 100km+-
Electr. signal(one Fibre-optic cable for each direction !)
A.Klepper – 01/04/11 Rev.A 3
Structure of the fibre-optic cable: Types of fibre glass:
POF- fibre-optic cablePlastic Optical FiberUsed in:- cars - ambient lighting
HCS- fibre-optic cableHard polymer Cladded SilicaUsed in:- industry
Standard fibre-optic cableMaterial: Quartz glassUsed in:- standard telecommunication cable
Structure:
Core
Jacket
Primary coating
Secondary coating
Tertiary coating
Colour coating
Basic informtions about fibre optic technology
A.Klepper – 01/04/11 Rev.A 4
Typical Core diameter / Outer diameter: Used e.g. for:
9/125 μm Singlemode (Qualityclass OS1)
50 / 125 μm Multimode – Europa (Qualityclass OM2)
62,5 / 125 μm Multimode – USA (Qualityclass OM1)
100 / 140 μm other
Structure and Dimensions of the „core“:
Outer diameter Core diameter
Basic informtions about fibre optic technology
A.Klepper – 01/04/11 Rev.A 5
850 nm (near infrarot range) in Multimode
1310nm / 1550 nm in Singlemode
Typical wave length:
Duplex transmission:Two way communication (2 cores)
Multimode / Singlemode transmission:
Singlemode (used for telecommunication):
- Very high distances possible (5km up to 100km)
- lower bandwidth
Singlemode
Simplex / Duplex and wave length
Simplex transmission (Half-Duplex) :One way communication (1 core)
Multimode
Multimode :
- very high bandwidth (up to 10 Gigabit/sek.)
- lower distance (up to 2km...4km)
Basic informtions about fibre optic technology
A.Klepper – 01/04/11 Rev.A 6
Basic informtions about fibre optic technology
Fibre optic plug systems:
3. SC-Plug (4-square form with fast plug catch)
4. LC-Plug (4-square form, extremly compact, Plug of the future
5. E2000-Patchcabel
1. ST-Plug (Runde form with bayonet catch ) 2. MTRJ-Plug (AMP-plug)
A.Klepper – 01/04/11 Rev.A 7
Basic informtions about fibre optic technology
Fibre-optic cable versus copper cable
Advantage :
- Very high bandwidth
- High distances possible (up to 100 km)
- Very good transmission quality
- Undisturbed against lightnings, high currents
and voltage potential difference
- No cross talk, like copper applications
- Safety against explosion and fire (chemical industry)
- Safety against weathering
- Less weight
Disadvantage :
-Extrem sensible against pressure and drawing power
-Expensive in comparision with standard copper cable
(CAT 5)
- High bending radius !, easy breaking !!
A.Klepper – 01/04/11 Rev.A 8
Fibre Optic Media Converter to LAN (TCP/IP) :
Switch/fibre optic - Mediaconverter(LAN-Switch / fibre optic Converter)
CGVision with CG-S Bus Network via fibre optic
Switch/fibre optic – Mediaconverterfor DIN-rail mounting
(4 fold LAN-Switch / fibre optic Converter)
A.Klepper – 01/04/11 Rev.A 9
LONBus
1. With Switch/fibre optic mediaconverter
(LAN-Switch / fibre opt. converter)
Segment 1
CGVision
CG2000
ZB-S
USBInterface
ZB-S
CG2000
ZB-S
ZB-S
CG2000
ZB-S
Segment 2
Features:
Building 1 Segment 5
Building 3
Building 2ZB-S ZB-S
CG2000
CG2000
MC
MC
MC = Media ConverterSwitch/Fibre optic
• Recommended cable: JY(St)Y 2x2x0,8
• Up to 480 eml-devices CG2000 and ZB-S on CGVision
• All Topologies possible
• Line topology: max. 900m
• Free Topologie: max. 320 m - between 2 nodes (je Segment) max. 500 m – total cable distance (je Segment)
• Mixed bus mode possible
• Up to 64 eml-devices CG2000 and ZB-S (each Segment)
• Max. 30 media converter
• Max. fibre optic distance: 2km - 5km
• No Lightning-/Over voltage protection necessary
Re =Repeater
Re
Ro
Ro =Router
ZB-S
Segment 4
CG2000
ZB-S
Segment 3
ZB-S
Konfigurationsserver
Client 1
Client 2
Duplexmode
MC
CGVision with CG-S Bus Network via fibre optic
A.Klepper – 01/04/11 Rev.A 10
- Nuclear power plant - Olkiluoto 3- BP crude refinery - Gelsenkirchen- Airport Düsseldorf – Carpark 8- Airport Düsseldorf – Carpark 5- Pulp Mill Stendal - PTB-Braunschweig - University of cologne- Airport Cologne/Bonn – Carpark 3- Airport Frankfurt (Fraport)- Messe Frankfurt (Exhibition halls)- University Bochum
Actual Projects:
CGVision with CG-S Bus Network via fibre optic
A.Klepper – 01/04/11 Rev.A 11
CGVision with CG-S Bus Network via fibre optic
BP-Crude Refinery „Horst“ in Gelsenkirchen
Project data:- Employees: approx. 2.500- Crude Destillation capacity: 12.5 million tons/year- Fuel production: 112.600 barrel/day
Example of CEAG CGVision networks with fibre optic:
Company logo
CEAG Technic:CGVision via fibre optic
Project value:~ 150.000€
A.Klepper – 01/04/11 Rev.A 12
CGVision with CG-S Bus Network via fibre optic
LWL Duplex
Client 1
ZB-S
LAN (CAT5)
ZB-S ZB-S
USB LAN (RJ45)
LAN-Dose2x RJ45
CG-S/IP-Router
Config.server
GVL
EGA
Bus
MC MC MCMC
GVL
EGA/RS232
COM-Server
MC1
MC2
MC3
MC4
Res. Res.Res. Res. Res.MC5
MC6
MK +8-fachSwitch
12345678
Client 2 Client 3
LWL Duplex
Client 4
IP-Interface
WARTE - Bau 402
LAN (RJ45)
CG-S Bus (LON) 2-Draht
LWL – Duplex (max.2km)
EGA-Bus 3-Draht
CG-S Bus (LON) 2-wire
MK = Medienkonvertermit ST-Anschluss
NID: NID: NID:
EGA Bus
ZB96200 SK
COM-Server
EGA/RS232
MC
Bau 18 Bau 415 Bau 275
ZB-S
NID:
Bau 402Res.
Bau 431
ZB96
Bau 66
ZB96
Bau 349
700m
Bau 83 Bau 30
GVL
Bau 88
Montage im separatenKlemmen-schrank
CG-S Bus
(CAT5)
Bau 1Schaltbau - Raum 1
Bau 1
Raum 110
16-fach Switch
BP-Crude Refinery „Horst“ in Gelsenkirchen
Fibre optic
19“-rack
A.Klepper – 01/04/11 Rev.A 13
Nuclear power station - Olkiluoto 3 in FinlandProject data:
Reactor in production 1720 Megawatt
Example of CEAG CGVision networks
CEAG Technic:
~4.000 self contained lum.
on CGVision via fibre optic
Project value:
~ 750.000€
A.Klepper – 01/04/11 Rev.A
14
...X X X X1 2 3 ... 100
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
X
...X X X X1 2 3 ... 100
...X X X X
...X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
...X X X X
MC +
4-fold
switch
1234
19“-Built in PC -1 19“-Built in PC -2 19“-Built in PC -3 19“-Built in PC -4
8-fold PC-switch
Spare
To other areas
Fibre optic
Duplex
LAN (RJ45)
Fibre optic – Duplex (max.2km)
Monitor/Keyboaed/Mouse
cable
MC = Media Converter
with ST-connector
X CGLine luminiare
BMS
RJ 45
F3-
Interface 4
Fault
indicator
contact
LAN
LAN
F3-
Interface 3
Fault
indicator
contact
F3-
Interface 2
Fault
indicator
contact
F3-
Interface 1
Fault
indicator
contact
MC +
4-fold
switch
1234
MC +
4-fold
switch
1234
MC +
4-fold
switch
1234
MC +
4-fold
switch
1234
MC +
4-fold
switch
1234
MC +
4-fold
switch
1234
MC +
4-fold
switch
1234
1234567891
0
1
1
1
2
1
3
1
4
1
5
1
6
24-Port Switch
19“-MC
module
OL3 – schemes of eml monitoring
19“-Built in PC -5 Spare
CGLine
PC-Interface
CGLine
PC-Interface
CGLine
PC-Interface
CGLine
PC-Interface
CGLine
PC-Interface
CGLine
PC-Interface
CGLine
PC-Interface
CGLine
PC-Interface