Page 1: FILLING CHECK VERSION WITH FLOWMETER

Software rel. 2.3.x

FILLING CHECK VERSION WITH FLOWMETER

Page 2: FILLING CHECK VERSION WITH FLOWMETER

2

CONTENTS

● Legendofsymbols.....................................................................................................3INTRODUCTION ............................................................................................................4

Productdescription....................................................................................................4INTENDED USE .............................................................................................................4CONTENT OF THE PACKAGE .....................................................................................4PRECAUTIONS .............................................................................................................4RISKS AND PROTECTIONS BEFORE ASSEMBLY ....................................................5

Positioning..................................................................................................................5Powersupplyandsensorconnection........................................................................5

ASSEMBLY DIAGRAMS ...............................................................................................6CONTROLS IN THE MENU ...........................................................................................7

Firstswitchingon.......................................................................................................7Controlsinthemenu..................................................................................................8Workparameters........................................................................................................9

MENU STRUCTURE ....................................................................................................10PRELIMINARY SETUP FOR USE ............................................................................... 11

Flowratealarms........................................................................................................ 11Sensors....................................................................................................................12Flowmetercalibration...............................................................................................13Language.................................................................................................................15Unitsofmeasurement..............................................................................................16Displaycontrast........................................................................................................17Alarmtones..............................................................................................................18Keytones..................................................................................................................18Valveactivationtime................................................................................................19CANcommunication................................................................................................20Operatingmode.......................................................................................................21Setupmanagement..................................................................................................22Testmenu.................................................................................................................24

USE ..............................................................................................................................27MAINTENANCE / DIAGNOSTICS / REPAIRS ............................................................29

Troubleshooting........................................................................................................29END OF LIFE DISPOSAL ............................................................................................29TECHNICAL DATA ......................................................................................................30

Devicetechnicaldata...............................................................................................30Setupmenu..............................................................................................................31

GUARANTEE TERMS .................................................................................................32

Page 3: FILLING CHECK VERSION WITH FLOWMETER

3

● Legendofsymbols

= Genericdanger

= Warning

This manual is an integral part of the equipment to which it refers and must accompany the equipment in case of sale or change of ownership. Keep it for any future reference; ARAG reserves the right to modify product specifications and instructions at any moment and without notice.

Page 4: FILLING CHECK VERSION WITH FLOWMETER

4

INTRODUCTION

Productdescription

VISIOisaverycompactandaccuratetop-notchmultifunctiondisplay,abletodisplayanykindofinformationconcerningagriculturaltreatments.Operatorcanselecttherequiredfunctionviasoftware.Itcandisplayseveraltypesofvalues,whichchangeaccordingtosetoperatingmodeandtypeofconnectedsensors.

INTENDED USE

This device is designed towork onagriculturalmachinery for spraying and cropsprayingapplications.ThemachineisdesignedandbuiltincompliancewithENISO14982standard(Electromagneticcompatibility-Forestryandfarmingmachines),harmonizedwith2014/30/UEDirective.

CONTENT OF THE PACKAGE

ThetablebelowindicatesthecomponentsthatyouwillfindintheVISIOpackage:

Legend:

1 VISIO2 Fixingkit3 Instructionmanual (onCD-ROM)4 Installationsheet

PRECAUTIONS

•Donotaimwaterjetsattheequipment.•Donotusesolventsorfueltocleanthecaseoutersurface.•Donotcleanequipmentwithdirectwaterjets.•Complywiththespecifiedpowervoltage(12VDC).•Incaseofvoltaicarcwelding,removeconnectorsfromVISIOanddisconnectthepowercables.•OnlyuseARAGgenuinesparepartsandaccessories.

P o w e r c a b l e ,s e n s o r s a n dconnection cablesto be connectedto VISIO must beorderedseparately.

Page 5: FILLING CHECK VERSION WITH FLOWMETER

5

RISKS AND PROTECTIONS BEFORE ASSEMBLY

Allinstallationworksmustbedonewithbatterydisconnected,usingsuitabletoolsandanyindividualprotectionequipmentdeemednecessary.

Positioning

1) Set mounting rail in cabin and fasten it with the relevant screws (1), in a position where VISIO can be easily seen and at hands' reach, but away from any moving organs.2) Secure VISIO to rail and push down until locked in place.3) Fasten wiring so that it does not interfere with any moving parts.

Powersupplyandsensorconnection

Sensorsandpowersupplymustbeinstalledandconnectedbyqualifiedpersonnel.VISIOmustbeexclusivelyconnectedtoARAGequipment.WHENARCWELDINGISREQUIRED,MAKESURETHATEQUIPMENTPOWER IS SWITCHED OFF; DISCONNECT POWER CABLES IF NEEDED.ARAGisnotliablefordamagetothesystem,persons,animalsorpropertycausedbyVISIOwrongorunsuitableassembly.Failuretoobservetheaboveinstructionsautomaticallyvoidsthewarranty.

Wirecolor (powercable) Connectionof

red positive

black negative

green countingabort-groundconnection

yellow countingabort-connection+12VDC

power supplysensors

Page 6: FILLING CHECK VERSION WITH FLOWMETER

6

ASSEMBLY DIAGRAMS

+12Vdc

GND

3

1

2

Counting abortGround

connection(green wire)

Counting abortConnection

+12VDC

(yellow wire)

Legend:

1)Powercable2)Pumpstopkit3)Flowmeter4)Powercable-ConnectioncableforBravo300S/400S

STANDARD SYSTEM

SYSTEM WITH RCU

Page 7: FILLING CHECK VERSION WITH FLOWMETER

7

CONTROLS IN THE MENU

Firstswitchingon

Atfirstswitchingon,VISIOwillrunaguidedprocedureallowingusertosetthedevice'sbasicsettings.

Press toscrollthroughitems,OKtosaveandmoveontonextsetting,orESCtogobacktoprevioussetting.

WARNING:Beforechangingoperatingmode,makesurethatallsensors/flowmetersareDISCONNECTEDfromthedevice.

Page 8: FILLING CHECK VERSION WITH FLOWMETER

8

Controlsinthemenu

Inthefollowingpages,accordingtothesetoperatingmode,somemenuitemscouldslightlydifferfromtheshownones.

SWITCHING ONAPressfor1second;BPressthekeytoviewthevariousvaluesinextendedmode,inasequence(ondisplaycentralpart).Everytimethedeviceisswitchedon,itwillshortlyshowapagewiththenameofdeviceandsoftwareversion.

SWITCHING OFFAPressfor2seconds.

ACCESS TO SETUP MENUFromthemainpage,presskeysatthesametimefor2secondstoopentheSetupMenu.

SELECTION AND ACCESS TO MENU ITEMS

APressafewtimestoscrollthroughitems(selecteditemisindicatedbyablackline);BPresstoopentheselectedmenuitem.

Thethreedotsunderanitemindicatepresenceofanothersetupmenu.

Page 9: FILLING CHECK VERSION WITH FLOWMETER

9

EDITING A VALUEAPresstomovethroughdigits;BPressafewtimestoeditthehighlighteddigit;CPresstoconfirm.Thedisplaygoesbacktopreviouspage;DPresstoexitpagewithoutconfirmingmodification.

Editedvaluemustfallwithintherangeshown.

Workparameters

Start ¬

¬

1000.0o

Quantity ¬

¬

Fromthemainpage,presskeyfortwosecondstoopenWorkParametersmenu,andsetvaluesforFlowcorrection.

Page 10: FILLING CHECK VERSION WITH FLOWMETER

10

MENU STRUCTURE

Alarms

Min flowrateMax flowrate

Sensors

FlowmeterMan. calibrationAuto calibration

Options

Language

Units of measurem.

Flowrate

VolumelGalm

3

Display contrast

Alarm tones

Keytones

Valve activ. time

l/minGPMm

3/h

Operating mode

Setup management

Save setupLoad setup

Test

CAN communication

Start

Quantity

¬

¬

¬

¬

1000.0o

Firmware versionBattery voltageDisplayKeysSensorsCAN communication *

Fill control (F)

* Menu item active only if CAN communication is active.

Page 11: FILLING CHECK VERSION WITH FLOWMETER

11

PRELIMINARY SETUP FOR USE

Flowratealarms

Setminimumandmaximumflowratethresholdsforalarmmessage.

1)OpenAlarmmenu(Setupmenu>Alarms).

Minimumandmaximumflowratealarmsaresetinthesameway.

Thedisplaywillshowthecurrentsettingbelowtheselecteditem.Press OK toedittheselectedmenuitem.

2)Toactivatethealarm,press and

atthesametimeuntilmessage OFF

goesoffandratealarmvalueisdisplayedinstead.Carryoutthesameproceduretodisablealarmagain.3)Setalarmvalue:A)Presstomovethroughdigits.B)Pressafewtimestoeditthehighlighteddigit.C)Presstosavechanges,orD)Presstoquitthepagewithoutconfirmingchanges.

Page 12: FILLING CHECK VERSION WITH FLOWMETER

12

Sensors

1)OpenSensorsmenu(Setupmenu>Sensors).

Themenuitemsdisplayedbelowchangeaccordingtothesetoperationmode:whenmoreitemsareavailable,selectthedesiredoneandpressOKtoeditit.

Page 13: FILLING CHECK VERSION WITH FLOWMETER

13

Flowmetercalibration

Duetothedifferentsystemconfigurations(tubes,valves,etc.)ratereadingcouldnotbecorrect.Itisthereforerecommendedtoperformasprayingtest.Ifmeasuredvalueisdifferentfromactualvalue,changetherateconstantthroughanautomaticcalibrationprocedureormanuallycalculatetheconstant.

Automatic calibration

Letapreviouslymeasuredquantityoffluidgothroughthesystemoraquantitythatcouldbemeasuredthroughanothersystem.Thehigherthequantityoffluidusedtoperformthecalibrationprocedure,themoreaccuratethecalibration.

1)Openautomaticcalibrationmenu(Setupmenu>Sensors>Flowmeter>AutoCalibration).Assoonasmenuisopen,theequipmentisreadytostartmeasuringwithnofurthercontrolsbeingrequired.2)Startliquidflowinthesystem.Thedisplaywillstartshowingtheincreasingvalueofthemeasuredfluidquantity.Assoonasfluidflowisover,thedisplayedcounterwillstop.

3)NowpressOK.AtthebottomofthedisplayStabilization,messagewillturnonandequipmentwillthenshowthepageontheside.4)Enterpreviouslymeasuredquantityoffluid:A)Presstomovethroughdigits.B)Pressafewtimestoeditthehighlighteddigit.C)Presstocompletethecalibrationprocedure,orD)Pressfor1secondtocancelthecalibrationprocedure.

1 Setting the fluid quantity actually passed through flowmeter during the calibrationprocedure.2 Viewingthefluidquantityreadbyflowmeterduringthecalibrationprocedure.

Page 14: FILLING CHECK VERSION WITH FLOWMETER

14

Ifequipmentdoesnotdetectanyflowaftercalibrationisstarted(anddisplayedvalueremains0),pressOKtoquitthecalibrationprocedurewithoutsaving.IfthedevicecontinuestodetectflowafterOKwaspressed,theerrormessageStop flow!.willbedisplayedafterafewseconds.Assoonasflowisstopped,readingwillstabilize,asperstandardprocedure.IncaseVISIOcalculatesavalueoutoftherangethatcanbesetbymeansofthemanualcalibration,thecalculatedvaluewillnotbeset.

Manual calibration

Inordertomanuallysetrateconstant,calculateandsetsuitableconstantusingthefollowingformula:

1)Openmanualcalibrationmenu(Setupmenu>Sensors>Flowmeter>Man.calibration).UnderCalibrationmenu,selectMan.calibration,toviewcurrentlysetconstantvaluebelowtheitem.PressOKtoeditthevalue.

Forflowmeterconstantvalue,refertothecorrespondingmanual.

2)Setflowmeterconstantvalue:A)Presstomovethroughdigits.B)Pressafewtimestoeditthehighlighteddigit.C)Presstosavechanges,orD)Presstoquitthepagewithoutconfirmingchanges.

[quantity measured by equipment]

[actually sprayed quantity]x [constant indicated on flowmeter body]

Page 15: FILLING CHECK VERSION WITH FLOWMETER

15

Language

Setthedesiredlanguage.

Options

Language

English

Units of measurem.Display contrast

Openlanguagesettingmenu(Setupmenu>Options>Language).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.

PressOK toeditlanguage.

2 1

2

Language

English

ČeskDeutsch

Español

1)Selectalanguagethrough .

2)PressOK tosave,orESC toquitwithoutsaving.

Page 16: FILLING CHECK VERSION WITH FLOWMETER

16

Unitsofmeasurement

Setunitofmeasurementforthevaluesdetectedbythedevice.

Flowrate units of measurement

1)Openinstantrateunitofmeasurementsettingmenu(Setupmenu>Options>Unitsofmeasurem.>Flowrate).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.Press OK toselectflowrateunitofmeasurement.

1)Selectaunitthrough .

2) Press OK tosave,orESC toquitwithoutsaving.

Volume units of measurement

1)Openvolumeunitofmeasurementsettingmenu(Setupmenu>Options>Unitsofmeasurem.>Volume).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.Press OK toselectvolumeunitofmeasurement.

1)Selectaunitthrough .

2) Press OK tosave,orESC toquitwithoutsaving.

Page 17: FILLING CHECK VERSION WITH FLOWMETER

17

Displaycontrast

Setdisplaycontrast.

Opendisplaycontrastmenu(Setupmenu>Options>Displaycontrast).

Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOK toedittheselectedmenuitem.

1)Setavaluethrough .Everytime

youpressit,valuewillincreaseby5%up

to100%.Usekey todecreasevalue

by5%.2) PressOK tosave,orESC toquitwithoutsaving.

Page 18: FILLING CHECK VERSION WITH FLOWMETER

18

Alarmtones

Enable/disablethealarmtones.

Openalarmtonesmenu(Setupmenu>Options>Alarmtones).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOK toedittheselectedmenuitem.

1)Setstatusthrough .

2)PressOK tosave,orESC toquitwithoutsaving.

Keytones

Enable/disablekeytones.

1)Openkeytonesmenu(Setupmenu>Options>Keytones).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOK toedittheselectedmenuitem.

1)Setstatusthrough .

2)PressOK tosave,orESC toquitwithoutsaving.

Page 19: FILLING CHECK VERSION WITH FLOWMETER

19

Valveactivationtime

Itispossibletosetfillingvalvetriptime,i.e.thetimefromwhenvalveclosingsignalisoutputandtheactualvalveclosing,sothatVISIOcanaccuratelycalculatetheexactsignaloutputmomentforamoreaccuratefilling.Thevaluetobeenteredisindicatedonthetechnicaldatasheetofthefillingvalveofthesystem.

1)Openvalveactivationtimemenu(Setupmenu>Options>Valveactiv.time).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.Press OK toedittheselectedmenuitem.

2)Setvalveactivationtime:A)Presstomovethroughdigits.B)Pressafewtimestoeditthehighlighteddigit.C)Presstosavechanges,orD)Presstoquitthepagewithoutconfirmingchanges.

Page 20: FILLING CHECK VERSION WITH FLOWMETER

20

CANcommunication

FlowrateorlevelvaluescanalsobemeasuredbyconnectingVISIOtoacomputeroftheBravo300SRCUorBravo400Sseries(ASSEMBLYDIAGRAMS).InthiscasedataaresenttoVISIOdirectlybythecomputerRCUthroughtheCANbusconnection.Activatethefunctionasfollows:

Valve activ. time

1)OpenCANcommunicationmenu(Setupmenu>Options>CANcommunication).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.Press OK toedittheselectedmenuitem.

1)Setstatusthrough .

2) Press OK tosave,orESC toquitwithoutsaving.

IfCANcommunicationisactive,thecorrespondingitemwillalsobedisplayedunderthe"Test"Menu.

Page 21: FILLING CHECK VERSION WITH FLOWMETER

21

Operatingmode

Setrequiredoperatingmode.

Openoperatingmodemenu(Setupmenu>Options>Operatingmode).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOK tochangetheoperatingmode.

1)Selecttherequiredoperatingmode

through .

2)PressOK tosave,orESC toquitwithoutsaving.

WARNING:OnceOKispressed,thepageontwhesidewillbedisplayed.Beforechangingoperatingmode,makesurethatallsensorsareDISCONNECTEDfromthedevice.PressOKtoconfirmchanges.ConnectthesensorsREQUIREDFORTHE SET OPERATING MODE.

Page 22: FILLING CHECK VERSION WITH FLOWMETER

22

Setupmanagement

VISIOsettingscanbeloadedfromorsavedonaUSBpendriveinordertoreconfigureit ifrequired,fixproblemsorsetanotherVISIOwithnoneedtorepeatallmanualoperations.Onceinstallationiscompleted,andVISIOoperationhasbeenchecked,werecommendtosaveallsettingsontoaUSBpendrive.TobeabletousethefollowingfunctionsitisnecessarytoinsertaUSBpendriveintherelevantportatthebottomofVISIO.

1)OpenSetupmanagementmenu(Setupmenu>Setupmanagement).

PressOK toedittheselectedmenuitem.

Load setupAllowstoselectaconfigurationfilesavedintheUSBpendriveandtosetVISIOagain.WARNING:ByloadingtheSETUP.BIN filecontainedintheUSBpendriveontotheVISIO,allcurrentsettingswillbelost.

1)Selectthedesiredcontrolthrough key.2)PressOK toconfirmloading,orESC toquitwithoutsaving.

TheSETUP.BINfilecanbeloadedonlyifitissavedintheUSBpendriverootdirectory.Ifsetupdownloadinvolveschangingoperatingmodeandusingdifferentsensorsthantheonesinuse,makesurethatallsensorsareDISCONNECTEDfromthedevice.PressOKtoconfirmloading.Reconnectsensors.

Page 23: FILLING CHECK VERSION WITH FLOWMETER

23

Save setupAllowssavingVISIOconfigurationfileontheUSBpendrive:itwillbepossibletoloaditagainanytimethesamesettingsneedtoberetrieved.

1)Selectthedesiredcontrolthrough

key.2)PressOK toconfirmsaving,orESC toquitwithoutsaving.

IfaSETUP.BINfileisalreadypresentintheUSBpendriverootdirectory,thefilewillbeoverwritten.

Page 24: FILLING CHECK VERSION WITH FLOWMETER

24

Testmenu

ThismenuallowsusertoviewsomedataandcarryoutanoperationtestofVISIO:-Firmwareversion:thedisplayshowsthefirmwareversioninstalled.-Batteryvoltage:thedisplayshowsthepowervoltageofthedevice.

Display test

Displaytestchecksthedevicedisplaycorrectoperation.

1)Opendisplaytestmenu(Setupmenu>Test>Display).Press OK toperformthetest.

Allpixelsondisplayareturnedon.PressESCtogobacktopreviouspage.

Keys test

Keystestchecksthedevicekeyscorrectoperation.

Openkeystestmenu(Setupmenu>Test>Keys).

Press OK toperformthetest.

1)Pressanykeyandthecorrespondingdisplayareawillturnon.PressESC toquit:assoonasyouacknowledgetheswitch-ononofthecorrespondingareaonthedisplay,devicewillgobacktopreviouspage.

Page 25: FILLING CHECK VERSION WITH FLOWMETER

25

Sensors test

Sensorstestcheckscorrectoperationofthesensorsconnectedtothedevice.

Opensensorstestmenu(Setupmenu>Test>Sensors).

Press OK toperformthetest.

Thedisplaywillshowthecurrentsensorreadingbelowtheselecteditem.1)Severalsensorscouldbedisplayed,dependingonthesetoperatingmode.Inthiscase,selectrequiredsensor

through .

2)PressESCtoquit.

Page 26: FILLING CHECK VERSION WITH FLOWMETER

26

CANcommunicationtest

OpenCANcommunicationtest(Setupmenu>Test>CANcommunication).ThedisplayshowsCANcommunicationstatus.

TheCANdeviceshownisonlyanexample.

Page 27: FILLING CHECK VERSION WITH FLOWMETER

27

USE

Themainpageshowsthedisplaydividedintothreehorizontalparts:

-toppart:itemStartreferstothekeyonthesidewhichallowsusertostarttheprocedure

( key).

-centralpart:the value is the set filling quantity (in liters).On the side, the symbolois displayed.-bottompart:itemQuantityreferstothekeyonthesidewhichallowsusertosettankfilling

value( key).

1)Press keyfortwosecondstoopen

themenuforsettingthefillingquantity.

2)Setfillingquantity:A)Presstomovethroughdigits.B)Pressafewtimestoeditthehighlighteddigit.C)Presstosavechanges,orD)Presstoquitthepagewithoutconfirmingchanges.

3)Keep keypressedfortwoseconds.Fillingstarts.

Page 28: FILLING CHECK VERSION WITH FLOWMETER

28

Thedisplayshowsthefollowingdata:-toppart:setfillingquantity;-centralpart:partialtotalizer;-bottompart:instantflowrate.

Press keyseveraltimestoviewa

valueinextendedmodeuntilrequiredvalueisondisplaycentralpart.

Displayedvaluescannotbeedited.

TankfillingcanbeinterruptedatanytimebypressingESC.Pausemessagewillbeshownatthebottomofthedisplay.PressOKtoresumefilling;pressESCtofinallystopfillinganddisplaywillgobacktoinitialpage.

Whensetquantityisreached,fillingstopsautomatically.Completedmessagewillbeshownatthebottomofthedisplay.

Page 29: FILLING CHECK VERSION WITH FLOWMETER

29

MAINTENANCE / DIAGNOSTICS / REPAIRS

•Cleanonlywithasoftwetcloth.•Donotuseaggressivedetergentsorproducts.•Donotcleanequipmentwithdirectwaterjets.

Troubleshooting

FAULT CAUSE REMEDY

VISIOisoffordoesnotswitchon

Nopowersupply Checkpowercableconnections

DeviceisOFF PresstheONkey

VISIOshowswrongdata

Wrongsetup Checkdisplayeddatasetup

Sensorfault ContactthenearestAssistanceCenterVISIOfault

Fillingpump(ifany)doesnotstart

PumpStopModulenotpowered

Checkpowersupplyconnection

END OF LIFE DISPOSAL

Disposeofthesystemincompliancewiththeestablishedlegislationinthecountryofuse.

Page 30: FILLING CHECK VERSION WITH FLOWMETER

30

TECHNICAL DATA

Devicetechnicaldata

Description VISIO

Display GraphicLCD,128x64pixels,back-lighting

Powersupplyvoltage 9÷16Vdc

Protectionagainstshort-circuit •

Protectionagainstpolarityinversion •

Max.frequency 1.2KHz

Analoginputs 4÷20mA

Digitaloutput-Maxcurrent 100mA

Maximumpowerinput(withnosensorsconnected) 160mA

Operatingtemperature -20°C÷70°C-4°F÷+158°F

Storagetemperature -30°C÷80°C-22°F÷+176°F

Size 126x79x66mm

Weight 245g

Page 31: FILLING CHECK VERSION WITH FLOWMETER

31

Setupmenu

Data Min. Max. Default UoM Notes

Flowmeter Calibration 1 10000 OFF pls/l --

Alarms

Min.flowrate 0.1 1000 OFF l/min. Alarmcanbedisabledbysettingvalueto"OFF"

Max.flowrate 0.1 1000 OFF l/min. Alarmcanbedisabledbysettingvalueto"OFF"

Display Contrast 0 100 50 % --

Options

Language - - English -

Availablelanguages:Italiano,English,Español,Português,Français,Deutsch,Cesky,Polski,Русский,Magyar,ニホン .

Flowrateunitsofmeasurement - - l/min. l/min. Availableunitsofmeasurement:

l/min,GPM,m3/h

Volumeunitsofmeasurement - - l liters Availableunitsofmeasurement:

l,gal,m3

Valveactivationtime 0.0 10 1 sec. --

- Fillingquantity 0.1 50000 1000 l --

Page 32: FILLING CHECK VERSION WITH FLOWMETER

32

GUARANTEE TERMS

1. ARAGs.r.l.guaranteesthisapparatusforaperiodof360days(1year)fromthedateofsaletotheclientuser(dateofthegoodsdeliverynote).Thecomponentsoftheapparatus,thatintheunappealableopinionofARAGarefaultyduetoanoriginaldefectinthematerialorproductionprocess,willberepairedorreplacedfreeofchargeatthenearestAssistanceCenteroperatingatthemomenttherequestforinterventionismade.Thefollowingcostsareexcluded:

- disassemblyandreassemblyoftheapparatusfromtheoriginalsystem;- transportoftheapparatustotheAssistanceCenter.2. Thefollowingarenotcoveredbytheguarantee:- damagecausedbytransport(scratches,dentsandsimilar);- damageduetoincorrectinstallationortofaultsoriginatingfrominsufficientor

inadequatecharacteristicsoftheelectricalsystem,ortoalterationsresultingfromenvironmental,climaticorotherconditions;

- damageduetotheuseofunsuitablechemicalproducts,forspraying,watering,weedkillingoranyothercroptreatment,thatmaydamagetheapparatus;

- malfunctioningcausedbynegligence,mishandling,lackofknowhow,repairsormodificationscarriedoutbyunauthorizedpersonnel;

- incorrectinstallationandregulation;- damageormalfunctioncausedbythelackofordinarymaintenance,suchascleaning

offilters,nozzles,etc.;- anythingthatcanbeconsideredtobenormalwearandtear.3. Repairingtheapparatuswillbecarriedoutwithintimelimitscompatiblewiththe

organizationalneedsoftheAssistanceCenter.Noguaranteeconditionswillberecognizedforthoseunitsorcomponentsthathavenotbeenpreviouslywashedandcleanedtoremoveresidueoftheproductsused;

4. Repairscarriedoutunderguaranteeareguaranteedforoneyear(360days)fromthereplacementorrepairdate.

5. ARAGwillnotrecognizeanyfurtherexpressedorintendedguarantees,apartfromthoselistedhere.NorepresentativeorretailerisauthorizedtotakeonanyotherresponsibilityrelativetoARAGproducts.Theperiodoftheguaranteesrecognizedbylaw,includingthecommercialguaranteesandallowancesforspecialpurposesarelimited,inlengthoftime,tothevaliditiesgivenhere.InnocasewillARAGrecognizelossofprofits,eitherdirect,indirect,specialorsubsequenttoanydamage.

6. ThepartsreplacedunderguaranteeremainthepropertyofARAG.7. Allsafetyinformationpresentinthesalesdocumentsregardinglimitsinuse,

performanceandproductcharacteristicsmustbetransferredtotheenduserasaresponsibilityofthepurchaser.

8. AnycontroversymustbepresentedtotheReggioEmiliaLawCourt.

Page 33: FILLING CHECK VERSION WITH FLOWMETER

CONFORMITY DECLARATION

The declaration of conformity is available at www.aragnet.com, in the relevant section.

Page 34: FILLING CHECK VERSION WITH FLOWMETER

42048 RUBIERA (Reggio Emilia) - ITALYVia Palladio, 5/ATel. +39 0522 622011Fax +39 0522 [email protected]

Only use genuine ARAG accessories or spare parts to make sure manufacturer guaranteed safety conditions are maintained in time. Always refer to the internet address www.aragnet.com

D20

287_

GB

-m04

03/2

017