Fire 11

Embed Size (px)

Citation preview

  • 8/3/2019 Fire 11

    1/63

    Chapter 1: Water at Rest and In

    Motion

    Six Principles of Fluid Pressure

    1) Fluid pressure is perpendicular to any surface on which it acts.

    2) Beneath the surface of a liquid at rest, the pressure is the same in all

    directions (upward, sideward, downward).

    3) Pressure applied to a confined fluid from without is transmitted equally in

    all directions.

    4) The pressure of a liquid in an open vessel is proportional to its depth.

    5) The pressure of a liquid in an open vessel is proportional to the density of

    the liquid.

    6) Liquid pressure at the bottom of a vessel is unaffected by the size and

    shape of the vessel as long as the height of water remains the same.

    Pressure Height Density Relationship

    Formulas

    a. Pressure (P) = .434 X Height or P = .434H

    b. Height / Head (H) = 2.31 X Pressure or H = 2.31P

    Work Problems: Using the formulas above, solve the

    following:

    a. Find the pressure at the bottom of a standpipe filled with

    water 100 feet high.

    P = .434H

    P = .434 (100)

    P = 43.4 psi

    * The pressure in this formula is often referred to as back

    pressure (BP) in pumping operations. This back-pressure

  • 8/3/2019 Fire 11

    2/63

    may be encountered during high-rise operations, while using

    dry standpipes, or pumping up or down hills. BP = .434H

    b. The static pressure in a fire hose connected to a standpipe

    is 150 psi. How high will that static pressure raise the

    water in the standpipe?

    H = 2.31P

    H = 2.31 (150)

    H = 346.5 ft

    Back Pressure

    1) Multi-Story Buildings

    The average height per story is 10-12 feet

    BP = .434H

    Therefore, BP per story is .434 (12) or 5.2 psi per story

    As a rule of thumb, 5 psi per story above the first floor is used for

    calculating BP in high-rise buildings.

    Work Problems: Using the rule of thumb, find the BP for the following:

    a. Fire on the 10th floor level of a 20-story office building

    BP = 5 X 9

    BP = 45 psi

    note: the fire is only 9 floors above ground level (this can be

    tricky)

    b. Fire on the roof top of a 20-story office building

    BP = 5 X 20

    BP = 100 psi

    Note: in this case, the fire is actually 20 floors above the ground

    floor

    Because it is on the roof and not the floor level. (Tricky

    too)

  • 8/3/2019 Fire 11

    3/63

    2) Uphill vs. Downhill

    A. Uphill:

    When pumping on a grade, either uphill or downhill, pump operators

    must take into consideration the pressure loss or gain caused by BP.

    When pumping uphill, the pump has to work harder to get the water to

    the desired location because gravity is acting on the water and holding

    it back. The pump pressure must be increased to overcome the back

    pressure.

    Example: A fire engine is pumping water uphill through a hoseline

    that is

    80ft above the firetruck.

    BP = .434H

    .434 (80)

    34.7 psi

    The pump operator will have to increase the pump pressure by 34.7 psi

    to make up the difference in back pressure.

    B. Downhill

    When pumping downhill, the pump does not have to work as hard

    because gravity is acting on the water, helping to move it through the

    fire hose. This means that the BP gained will be in addition to the

    pump pressure reading. You wont see the pressure increase on your

    pump gauge, but the hoseman will feel it on the hoseline.

    Example: A fire engine is pumping water downhill through a hoseline

    that

    is 60ft below the firetruck.

    BP = .434H

    .434 (60)

    26.04 psi

    The pump operator will have to decrease the pump pressure by 26.04 psi

    To negate the pressure increase caused by back pressure.

  • 8/3/2019 Fire 11

    4/63

    3) Types of Pressure

    a. Static Pressure - Pressure of water at rest

    b. Flow Pressure - Pressure of water flowing from nozzle

    c. Residual Pressure Pressure remaining in water main or inlet side

    of

    Fire pump after water is flowing

    Chapter 2: Velocity and DischargeDrafting Operations

    1) Theory

    Drafting is a way in which a fire pump uses atmospheric pressure to draw

    water into the fire pump from a static water source (see figure 2.1).

    Atmospheric pressure, at sea level, is 14.7 psi. Fire pumps are capable of

    expelling its air through use of a priming pump. If all the air within a

    pump is displaced and a good seal is maintained (no leaks or loose

    fittings), the fire pump can create a vacuum-like atmosphere within the fire

    pump. Once this vacuum-like atmosphere is obtained, the atmospheric

    pressure outside the pump will be greater than the pressure within the fire

    pump, and water will be forced into the pump through the drafting hose.

    This means that using the formula H = 2.31P, we can see how atmospheric

    pressure will force water into the fire pump up to 33.9 feet high (H = 2.31

    X 14.7 psi).

  • 8/3/2019 Fire 11

    5/63

    Figure 2.1 Drafting Operations

    The theoretical lift of 33.9 feet is nearly impossible to obtain. Since the

    fire pump cannot produce an absolute vacuum (0 psi), and there is friction

    loss in the drafting hose, a practical lift of 22-25 feet is more realistic.

    2) Factors Affecting Priming Operations (trying to obtain a

    vacuum)

    a. Loose hose connections, loose covers, open gates, open valves, too

    long or too small suction hose

    b. Defective priming pump

    c. Depth of water source

    note: 1250 gpm pumpers should only take 30 seconds to prime

    1500 gpm pumpers should only take 45 seconds to prime

    3) Factors Affecting Lift

    a. Altitude

    b. Weather

    c.

    Water temperature

  • 8/3/2019 Fire 11

    6/63

    d. Too long or too small suction hose

    Velocity

    1) Formulas

    For velocity, you will be given either the height of the water or the

    pressure. Therefore, two formulas for velocity will be discussed.

    a. Velocity = 8 X Height of water or V = 8Hb. Velocity = 12.1 X Pressure of nozzle or V = 12.1P

    Work Problems:

    What is the velocity of water flow is the nozzle pressure is 60

    psi?

    V = 12.1 P

    V = 12.1 60

    V = 12.1 (7.75)

    V = 93.78 fps

    What is the velocity of water flow from a water tank 50 ft high?

    V = 8 H

    V = 8 50

    V = 8 (7.07)

    V = 56.56 fps

    Flow Velocities

    The velocity of water varies inversely with the cross section of the hoseline

    and nozzle tip. What does this mean??

    With the same nozzle pressure:

    Changing to a smaller nozzle tip will increase nozzle velocity /

    pressure

  • 8/3/2019 Fire 11

    7/63

    Changing to a larger nozzle tip will decrease nozzle velocity / pressure

    The inverse relationship between velocity and nozzle size simply means that

    when one increases, the other decreases and vice versa.

    Nozzle Discharge Gallons per Minute (GPM)

    1) Discharge Formulas

    a. With Nozzle

    Discharge (GPM) = 30 X Diameter of Nozzle2 X Nozzle Pressure

    GPM = 30d2PWork Problem: How many GPMs are flowing through a 2 hoselinewith a

    1 1/8 nozzle tip with a nozzle pressure of 50 psi?

    GPM = 30d2P

    GPM = 30 (1.125)250 (nozzle size converted into adecimal)

    GPM = 30 (1.27) (7.07)

    GPM = 269.37

    b. Without Nozzle (open butt)

    To find the discharge pressure of a hoseline without a nozzle,

    simply use 90% of the original discharge formula. The hose

    diameter will substitute as the nozzle size in this case.

    GPM (open butt) = 90% X 30 X Hose Diameter2 X Pressure

    GPM (open butt) = 27d2 PWork Problem: How many GPMs are flowing through a 2 hoseline

    without a nozzle attached to it at 50 psi?

    GPM (open butt) = 27d2P

    GPM = 27 (2.5)250

  • 8/3/2019 Fire 11

    8/63

    GPM = 27 (6.25) (7.07)

    GPM = 1193.06

    Nozzle Reaction

    1) Formula

    Nozzle Reaction (NR) = 1.57 X Nozzle Diameter2 X Nozzle Pressure

    NR = 1.57d2 P

    note: In theory, the nozzle reaction will always be greater than the actual

    nozzle reaction felt by the firefighter because:

    a. The hoseline is in contact with the ground, and this

    absorbs

    some of the nozzle reaction.

    b. Bends in the hoseline as it is laid out will help to absorb

    some

    of the nozzle reaction.

    Work Problem: What is the nozzle reaction of a 2 hoseline with a

    1 1/8 nozzle tip flowing 50 psi?

    NR = 1.57 d2 P

    NR = 1.57 (1.125)2 (50) (nozzle size converted to a decimal)

    NR = 1.57 (1.27) (50)

    NR = 99.70 lbs

    2) Safety Factors to Consider

    a. Handling Hose Lines

    i. Bends near the nozzle tend to straighten out. The

    hoseline should be straight at least 10 feet back of the

    nozzle

    ii. Nozzle reaction from fog streams is less than straight

    streams

  • 8/3/2019 Fire 11

    9/63

    iii. Open and close nozzle slowly because:

    1. Initial nozzle reaction is greater than the nozzle

    reaction when water is flowing

    2. Sudden closing of nozzle sends pressure surgesbackwards. This is called a water hammer. A

    water hammer can break the hoseline, fire pump,

    and/or water main.

    iv. When using handlines on ladders, the nozzle reaction

    could cause the ladder to lift-off and fall away from the

    building. To help avoid this dangerous situation from

    occurring firefighters should:

    1. Fasten the ladder to the window sill

    2. Set the base of the ladder further away from the

    building

    b. Ladder Truck Operations

    i. If the hose should burst, the ladder / boom will whip

    violently

    ii. Always try and shoot the fire stream in-line with the

    ladder. Never turn the nozzle more than 15 degrees

    fromthe center of the ladder.

    Work Problem: What is the nozzle reaction of a ladder pipe

    operation flowing 80 psi from a 2 nozzle

    tip?

    NR = 1.57 d2 P

    NR = 1.57 (2)2(80)

    NR = 1.57 (4) (80)

    NR = 502.4 lbs (force)

    Friction Loss

    1) Effect of Flow Pattern

    a. Laminar Flow Low Flow Velocities

    b. Turbulent Flow High Flow Velocities

  • 8/3/2019 Fire 11

    10/63

    i. Friction loss in hose affected by:

    1. Inner lining of hose

    2. Age of hose

    3. Thickness of hose lining

    4. Type of hose jacked weave (will it expand or not)

    2) Friction Loss in Hoses

    a. Friction loss varies with quality of hose

    b. Friction loss varies directly with length of hose line (the longer the

    hoseline, the greater the friction loss).

    c. Friction loss varies approximately as the square of the velocity of

    flow (the faster the flow velocity, the greater the friction loss)

    Example:

    If the flow velocity is doubled Friction loss is 4 times

    greater (2)2 = 4

    If the flow velocity is tripled Friction loss is 9 times

    greater (3)2 = 9

    d. For a given velocity, friction loss varies inversely as the fifth

    power of the hose diameter (the bigger the hose diameter, the less

    the friction loss)

    Example:

    If the hose size was doubled from 1 to 3

    We see how 1 X 2 = 3

    Inverting the 2 we get

    Now we take the and multiply it to the fifth power

    5 = X X X X = 1/32

    We can now conclude that if the hose size is doubled,

    the

  • 8/3/2019 Fire 11

    11/63

    New friction loss is only 1/32 as much as the original

    figure.

    e. For a given velocity of flow, friction loss is nearly independent of

    pressure. In other words, he velocity of flow, and not the pressure,

    is the determining factor in friction loss.

    3) Formulas (more details in Chapter 5)

    a. Friction Loss = 2 X Q2 + Q

    FL = 2Q2 + Q Q = GPM 100note: This formula is only for 2 diameter hoselines.

    The friction loss figure represents friction loss per 100 ft of 2

    hose.

    i.e. If the hoseline is 600 ft, the friction loss figure must be

    Multiplied by 6 to get the total friction loss in that hoseline.

    Work Problem: Find the friction loss in a 2 hoseline 100 ft in length

    Flowing 300 gpm.

    FL = 2Q2 + Q Q = GPM 100

    FL = 2 (3)2 + 3 Q = 300 100

    FL = 2 (9) + 3 Q = 3

    FL = 21 # per 100 ft length

    FL = 21# (since there is only 100 ft of hoseline)

    c. Engine Pressure = Friction Loss + Nozzle Pressure

    EP = FL + NP

    Work Problem: An engine is pumping through 600 ft of 2 hoseline to a nozzle

    that is flowing 200 gpm at 100 psi nozzle pressure. Find the engine pressure.

    EP = FL + NP FL = 2Q2 + Q Q = GPM 100

    EP = FL + 100 FL = 2(2)2 + 2 Q = 200 100

    EP = 60 + 100 FL = 2(4) +2 Q = 2

  • 8/3/2019 Fire 11

    12/63

    EP = 160 psi FL = 10 per 100ft hoseline

    FL = 10 X 6 (# of hundreds of feet of

    hose)

    FL = 60

    d. Engine Pressure = Friction Loss + Nozzle Pressure + Back

    Pressure

    EP = FL + NP + BP

    Work Problem: An engine is pumping through 300 ft of 2

    hoseline

    to a nozzle that is flowing 200 gpm at 100 psi

    nozzle

    Pressure. The nozzle is on a hill that is 60 ft higher

    Than the fire pump. Find the engine pressure.

    EP = FL + NP + BP

    FL = 2Q2 + Q Q = GPM 100 BP = .434H

    FL = 2 (2)2 + 2 Q = 200 100 BP = .434(60)

    FL = 2 (4) + 2 Q = 2 BP =

    26.04

    FL = 10 per 100 ft hoseline

    FL = 10 X 3 ( # of hundreds of feet of hose)

    FL = 30

    EP = FL + NP + BP

    EP = 30 + 100 + 26

  • 8/3/2019 Fire 11

    13/63

    EP = 156 psi

    Note: If the nozzle was below the fire pump (downhill or in a

    Basement), the BP would have to be subtracted from the EP.

    Remember that the gravity would cause the pressure to

    increase, thus giving the firefighter on the hoseline too much

    pressure.

    Chapter 3: Water Distribution System

    General Remarks

    1) Public Water Systems are designed to perform two

    functions.

    a. Provide water for domestic, commercial and industrial use

    b. Provide water for fire protection

    i.

    Combination systems use same water source for bothfunctions

    ii. Separate systems use potable water for domestic use

    and use brackish, salt or treated sewage water for

    firefighting.

    2) Fire hydrants must be installed and maintained in

    accordance to standards set forth by the American Water

    Works Association.

    3) The term Fire Plug originated from the old days when

    pipes were made from hollowed out wood and buried

    underground. These pipes were gravity fed from water sources

    located in the area. If there were a need for water, the fire

    department would expose the pipe by digging up the ground.

    Once exposed, a hole was drilled into the wooden pipe. Water

    would then flow out of the hole by means of gravity. When the

    fire was out, a tapered wooden plug was inserted into the hole

    and the pipe would be re-buried.

  • 8/3/2019 Fire 11

    14/63

    Fire Hydrants

    1) Dry Barrel Hydrants (see figure 3.1)

    a. Dry barrel hydrants do not have water stored in the fire hydrantitself. Instead, the water is stored in the piping below the hydrant.

    When the operating stem is opened, water will begin to fill the

    hydrant. This type of hydrant is used in areas where freezing can

    occur. If the water is stored in the hydrant, it could freeze and that

    hydrant would be useless in a fire situation. Because the water in

    the piping below the hydrant is constantly moving, it usually does

    not freeze.

    b. Main Parts:

    i. Dry Barrel

    ii. Footpiece

    iii. Bonnet

    iv. Operating Stem

    v. Main Valve

    vi. Drain

    2) Wet Barrel Hydrants (see figure 3.2)

    a. Unlike the dry barrel hydrant, the wet barrel hydrant has water in

    the hydrant right up to the discharge outlet. These hydrants should

    not be used in areas where freezing could occur. These are the

    types of hydrants commonly used in Hawai`i. However, there are

    some dry barrel hydrants in use today in Hawai`i.

    b. Wet barrel hydrants have fewer parts than dry barrel hydrants.

    c. Each outlet has an independent valve on a threaded stem with

    operating nut on opposite side of barrel.

  • 8/3/2019 Fire 11

    15/63

    Figure 3.1 Dry Barrel Hydrant

    Figure 3.2 Wet Barrel Hydrant

    3) Other Information

    d. Hydrant Outlets

    i. Every hydrant must have at least two outlets.

  • 8/3/2019 Fire 11

    16/63

    1. One pumper suction hose outlet (usually 4)

    2. One regular hose outlet (usually 2 )

    ii. Outlets must not be less than 18 inches from the

    ground level.

    iii. Outlets must have a cap and chain.

    e. Hydrant Spacing

    i. Hydrants should not be spaced more than 250 ft apart

    in commercial / industrial areas and should have a

    minimum flow of 1000 gpm.

    ii. Hydrants should not be spaced more than 350 ft apart

    in residential areas and should have a minimum flow of1000 gpm.

    iii. Hydrants should not be spaced more than 700 ft apart

    in rural areas and should have a minimum flow of 1000

    gpm.

    f. Branch Connection

    i. The minimum size water main supplying fire hydrants

    in Honolulu is 8 inches. Main sizes smaller than 6 inchesare not suitable for providing fire protection.

    ii. Each wet barrel hydrant has its own gate valve. This

    gate valve is located somewhere near the hydrant, and its

    location is indicated on the fire hydrant. In case the hydrant

    should be damaged (if a car knocks one over) the gate valve

    can be used to stop the flow of water to that one hydrant

    without interrupting the flow to other hydrants on that same

    water main.

    4) Estimating Available Flow From Fire Hydrants

    a. In order to estimate the amount of flow we have available in a

    hydrant, we must first find the percentage of drop in pressure

    between static and residual pressure.

    i. Open hydrant with suction hose connected to fire

    truck. At this time take note as to what your intake

    (suction) pressure gauge is reading. This is the hydrants

    static pressure.

    ii. Open a discharge gate for one hoseline. Again look atyour suction gauge. The pressure will be lower because

  • 8/3/2019 Fire 11

    17/63

    some of the static pressure will have been used for the first

    firefighting line. This is the hydrants residual pressure.

    iii. Subtract the residual pressure from the static pressure

    and convert that number into a percentage. This is the

    percentage of drop in pressure between static and residual.

    Work Problem: A hydrant is connected to your fire truck with no

    Firefighting lines flowing. Your suction gauge reads

    60

    psi. After opening one firefighting line, your suction

    Gauge now reads 55 psi. What is the percentage of

    drop in pressure?

    Static Pressure = 60 psi

    Residual Pressure = 55 psi

    Pressure Difference = 5 psi

    To find the drop in a %, simply divide the difference in

    pressure by the static pressure.

    5 psi 60 psi = .083 or 8.3%

    b. Applying percentage of drop in pressure to practical situations.

    i. Once the percentage of drop between static and

    residual pressure is found, that number can be used to help

    estimate the number of additional hoselines the hydrant can

    supply. The estimates are based on hoselines of the same

    diameter utilizing nozzles of the same diameter also. The

    following chart shows the general rule of thumb regarding

    additional hoselines:

    10% or less 3 more hoselines

    11-15% 2 more hoselines

    16-25% 1 more hoseline

    more than 25% no more hoselines

  • 8/3/2019 Fire 11

    18/63

    Chapter 4: Fire Service Pumps

    Introduction

    1) Three Basic Types of Fire Pumps

    a. Piston Type Fire Pump

    b. Rotary Type Fire Pump

    c. Centrifugal Type Fire Pump

    2) Pump Mounting on Apparatus

    a. Mid-ship (middle) 2 ways

    i. Between road transmission and rear axle in line with

    drive shaft (most common)

    ii. Ahead of clutch and transmission with flywheel and

    power take off. This type allows for direct engine power to

    pump transmission connection. It allows for driving and

    pumping simultaneously.

    b. Front Mounting

    i. From front of engine crankshaft connected to pump

    transmission. This type also allows for driving and

    pumping simultaneously.

    3) Pump Ratings

    a. Standard pumper capacity ratings start from 500 gpm and increase

    in 250 gpm increments (NFPA 19 Specification) up to 2000 gpm.

    i. 500 gpm, 750 gpm, 1000 gpm, 1250 gpm, 1500 gpm,1750 gpm, 2000 gpm

    ii. Pumpers must have one 2 gated outlet per 250 gpm

    rated capacity.

    b. Fire pumps are designed to perform as follows:

    100% of rated capacity at 150 psi net pumps pressure

    70% of rated capacity at 200 psi net pumps pressure

    50% of rated capacity at 250 psi net pumps pressure

  • 8/3/2019 Fire 11

    19/63

    Net pump pressure is found by subtracting suction or inlet pressure

    from the discharge pressure.

    Work Problem: A fire pump is discharging 200 psi through a 2

    Hoseline and is receiving 50 psi from a fire

    Hydrant. What is the net pump pressure?

    Net Pump Pressure = Discharge Pressure Intake

    Pressure

    Net Pump Pressure = 200 psi 50 psi

    Net Pump Pressure = 150 psi

    Work Problem: A pumper has a capacity rating of 1000 gpm.

    Using net pump pressure finds the efficiency

    of the pump:

    At 150 psi net pump pressure _______gpm

    At 200 psi net pump pressure _______gpm

    At 250 psi net pump pressure _______gpm

    The answers are 1000 gpm (1000 gpm X 100%), 700

    gpm

    (1000 gpm X 70%) and 500 gpm (1000 gpm X 50%).

    note: Fire pumps are most efficient at 150 psi or less.

    4) Cavitation

    a. Causes of cavitation

    i. Lift too high for volume and pressure discharged

    ii. Suction hose too small for volume and pressure

    discharged

    iii. Suction strainer or hose clogged

    iv. Partial collapse of hose lining

  • 8/3/2019 Fire 11

    20/63

    v. Temperature of water too high

    b. Signs of cavitation

    i. Pump vibrations with loud pinging noises. This is

    caused by air bubbles that form in the pump that collapseviolently when they enter the impeller.

    ii. Pump running away This happens when the pump is

    pumping air or steam instead of water. The pump speed

    will increase with no increase in discharge pressure or

    volume. The pump operator will hear the engine revving

    and running away. If this should occur, shut down

    pumping operations immediately.

    Centrifugal Fire Pumps1) General Information

    a. Water enters the centrifugal pump through the eye and is delivered

    to the impeller through the vanes. The impeller increases the speed of

    the water and discharges it through the volute. (see figure 4.1)

    figure 4.1 Centrifugal Fire Pump

    c. Centrifugal pumps may be connected in stages to each other.

    Centrifugal pumps can have 1 4 stages. Each impeller and volute

    is one stage in a multi-stage centrifugal pump.

    2) Capabilities and Limitations

    a. Volume (gpm) varies directly as the pump speed. The faster the

    pump speed, the greater the volume.

    b. Pressure (psi) varies as the square of the pump speed. If you

    double the pump speed, the pressure increases 4 times (22 = 4)

    c. Centrifugal pumps are not self-priming. A separate rotary vanepriming pump unit is used to prime centrifugal pumps.

  • 8/3/2019 Fire 11

    21/63

    3) Single-Stage Centrifugal Fire Pumps

    a. Basic Designs

    i. Single suction impeller

    1. Limited up to 750 gpm pumpers

    ii. Double suction impeller

    1. 1000 1500 gpm pumpers

    iii. Double Volute design

    1. Limited to single stage pumps

    2. High efficiency at rated capacity

    b. In general, single stage pumps have a high efficiency rating (about

    70%), which is generally slightly higher than multi-stage pumps.

    4) Two-Stage Centrifugal Fire Pumps

    a. Basic design

    i. Two impellers with separate volute chambers for each

    impeller

    b. Limited use in fire service

    i. Pumps may be front mounted for smaller trucks

    1. Provides vehicle movement while pumping

    2. Able to provide high-pressure for operations (300-

    400 psi).

    5) Parallel Series Two-Stage Centrifugal Pumps

    a. Basic design

    i. Two impellers with separate volutes

    ii. Addition of transfer or changeover valve for parallel or

    series pumping operations

    iii. The efficiency of parallel series two-stage pumps is

    around 65-70%. This is slightly less than a single stagepump.

  • 8/3/2019 Fire 11

    22/63

    b. Parallel (Volume) Operations (see figure 4.2)

    i. When a pump is placed in the parallel position, water

    enters both stages of the pump simultaneously from the

    suction side. This means that the pump will be able to

    deliver twice the volume at half of the pressure.

    ii. An example of this is: A 1000 gpm rated capacity

    pumper operating at 150 psi net pump pressure. In the

    parallel position, each impeller will deliver 500 gpm at 150

    psi. Note that the pump will double the volume of water,

    but at half the speed.

    figure 4.2 Parallel Series pump in parallel position

    c. Series (Pressure) Operations (see figure 4.3)

    i. When a pump is placed in the series position, water

    enters one stage of the pump from the suction side. The

    water is then delivered to the second stage via the first stage

    of the pump. This means that the pump will be able to

    deliver half the volume at twice the pressure.

    ii. An example of this is: A 1000 gpm rated capacity

    pumper operating at 150 psi net pump pressure. In theseries position, the first impeller will deliver 500 gpm at

    150 psi to the second stage. The second impeller will

    discharge the 500 gpm, but it will double the pressure. In

    the series position, this pump will deliver 500 gpm at 300

    psi. Note that the pump will double the pressure, but at half

    the volume.

  • 8/3/2019 Fire 11

    23/63

    figure 4.3 Parallel Series pump in series position

    d. Transfer Valve

    i. A transfer valve is the device that is used to change a

    pump from series to parallel or vice versa. The pump

    operator must decide which position would best meet the

    needs of a given situation.

    ii. Transfer valves may be either powered or manual

    iii. Transfer valves may be disk type or cylinder type

    iv. Transfer valves are normally left in the series position

    for normal day-to-day operations.

    v. As a general rule, the transfer valve should be kept in

    the series position when pumping up to 70% of the pumps

    capacity. The transfer valve should be switched to the

    parallel position when evolutions or circumstances require a

    pump to deliver more than 70% of its rated capacity.

    vi. When switching the transfer valve from one position

    to another, the pump pressure should be lowered to below

    60 psi. This is especially crucial when switching from

    parallel to series because the pressure will immediately

    double. This sudden increase in pressure could damage the

    pump, hoses, or seriously injure the firefighters on the

    hoselines.

    6) Piston Pumps

    a. General Remarks

    i. Piston pumps were the first pumps developed for

    firefighting.

  • 8/3/2019 Fire 11

    24/63

    ii. Piston pumps are preferred by fire departments that get

    their water supply mostly by drafting operations.

    iii. Piston pumps have a high efficiency (around 75-80%)

    b. Basic Design

    i. Use of piston to displace water

    1. Single action (water gets moved on pistons up

    stroke)

    2. Double action (water gets moved on up stroke and

    down stroke)

    ii. Piston pumps are positive displacement pumps. This

    means that they are self-priming

    iii. Different gear ratios between engine and pump are

    needed to obtain higher pressure.

    7) Rotary Fire Pumps

    a. General Remarks

    i. Rotary fire pumps were first used by the fire service

    around the 1600s. In the 1900s they were adapted towork with the steam engines.

    ii. Rotary pumps are preferred where all pumping

    operations involve drafting, high lift conditions, or long

    suction hoses.

    Chapter 5: Friction Loss Calculations

    Basic 2 Hoselines

    As discussed earlier, the formula for finding friction loss in a 2 fire hose

    is:

    FL= 2Q2 + Q; where Q= GPM 100.This formula only applies to:

    a. 2 diameter fire hose per 100 ft length

  • 8/3/2019 Fire 11

    25/63

    b. 2 diameter fire hose flowing 100 gpm or greater

    The formula for finding friction loss in a 2 fire hose flowing less than

    100

    gpm is:

    FL = 2Q2 + Q; where Q = GPM 100Work Problems:

    Find the friction loss in a 500 ft length of 2 fire hose flowing 200

    gpm.

    FL = 2Q2 + Q Q = GPM 100

    FL = 2 (2)2 + 2 Q = 200 100

    FL = 2 (4) + 2 Q = 2

    FL = 10 per 100 length

    FL = 10 x 5 (500 ft 100)

    FL = 50 psi

    Find the friction loss in a 800 ft length of 2 fire hose flowing 250gpm.

    FL = 2Q2 + Q Q = GPM 100

    FL = 2 (2.5)2 + 2.5 Q = 250 100

    FL = 2 (6.25) + 2.5 Q = 2.5

    FL = 15 per 100 length

    FL = 15 x 8 (800 ft 100)

    FL = 120 psi

    Find the friction loss in 400 ft of 2 fire hose flowing 80 gpm.

    FL = 2Q2 + 1/2 Q Q = GPM 100

    FL = 2 (.8)2 + (.8) Q = 80 100

    FL = 2 (.64) + .32 Q = .8

  • 8/3/2019 Fire 11

    26/63

    FL = 1.6 per 100 length

    FL = 1.6 x 4 (400 ft 100)

    FL = 6.4 psi

    Finding friction loss for hoses other than 2 diameters.

    1) Finding Equivalent Lengths

    Before we can use the friction loss formula on hoses other than 2 in

    diameter, we must first find the equivalent length. In other words, we will

    be converting the hose to reflect the length in a 2 diameter.

    This is like converting feet to inches. Suppose we wanted to convert 5 feet

    into inches; it is understood that we must multiply the number of feet by

    12 (the number of inches in a foot). 5 feet converted to inches would be: 5

    x 12 = 60 inches.

    Keeping that principle in mind, we only have a friction loss formula for 2

    hoselines. We will need to convert hoses of all other diameters to a 2

    length. This is called finding the equivalent length. It is easier to

    find the equivalent length, than it is to learn a new friction loss formula for

    each possible hose diameter.

    There are two methods in which we can find an equivalent length.

    a. Using Rule of Thumb

    To find the equivalent length of a fire hose using the rule of

    thumb,

    simply multiply the total length of hose by the rule of thumb

    factor. These factors are listed below and will be provided for

    you on the exam. You are not required to memorize the

    factors.

    Diameter of Hose Rule of Thumb Factor

    1 91

    1 13

    1 7.76

    3 .4

  • 8/3/2019 Fire 11

    27/63

    3 .17

    4 .09

    Work Problem: Using the rule of thumb factor, convert the

    following to an equivalent 2 length:

    100 ft of 1 hose = 100 x 91 or 9100 ft of 2

    100 ft of 1 hose = 100 x 13 or 1300 ft of 2

    100 ft of 4 hose = 100 x .09 or 9 ft of 2

    b. Using Conversion Factor

    To find the equivalent length of a fire hose using conversion

    factor,

    divide the total length of hose by the conversion factor. These

    factors are listed below and will be provided for you on the

    exam. You are not required to memorize the factors.

    Diameter of Hose Conversion Factor

    1 .011

    1 .074

    1 .129

    3 2.5

    3 5.8

    4 11.0

    Work Problem: Using the conversion factor, convert the

    following to an equivalent 2 length:

    100 ft of 1 hose = 100 .011 or 9090 ft of 2

    100 ft of 1 hose = 100 .074 or 1351 ft of 2

    100 ft of 4 hose = 100

    11 or 9 ft of 2

  • 8/3/2019 Fire 11

    28/63

    2) Finding friction loss using equivalent length

    Using either equivalent length method (rule of thumb or conversion

    factor), we can now find the friction loss for hoses other than 2 .

    Work Problem: Find the friction loss in a 1 diameter hoseline 200ft in

    Length flowing 100 gpm.

    Step 1: Find equivalent length

    200 x 13 = 2600 ft or 200 .074 = 2700 ft

    (for this example we will use 2600 ft)

    Step 2: Find friction loss

    FL = 2Q2 + Q Q = GPM 100

    FL = 2 (1)2 + 1 Q = 100 100

    FL = 2 (1) + 1 Q = 1

    FL = 3 (per 100 ft of hose)

    FL = 3 x 26 (2600 ft 100)

    FL = 78

    Work Problem: Find the total friction loss in a 1 diameter hoseline

    200 ft in length, connected to a 1 diameter hoseline 200 ft. in length flowing 40

    gpm.

    Step 1: Find equivalent length of 1 hose

    200 x 13 = 2600 ft or 200 .074 = 2700 ft (forthis example we will use 2600 ft)

    Step 2: Find equivalent length of 1 hose

    200 x 91 = 18,200 ft or 200 .011 = 18,182 ft

    (for this example we will use 18,200 ft.)

    Step 3: Find total equivalent length of evolution (1 + 1)

    2600 ft + 18,200 ft = 20, 800 ft

  • 8/3/2019 Fire 11

    29/63

    Step 4: Find Friction loss

    FL = 2Q2 + Q Q = GPM 100

    FL = 2 (.4)2 + (.4) Q = 40 100

    FL = 2 (.16) + .2 Q = .4

    FL = .52 (per 100 ft of hose)

    FL = .52 x 208 (20800 ft 100)

    FL = 108.16

    3) Finding Friction Loss in Siamese Hose Lays

    Some hose evolutions involve the use of siamesed hoselines. This means

    that two or more hoses are running parallel to each other and are supplying

    water to the same discharge. This discharge can be either a deluge or

    another hoseline. In order to find friction loss in this type of evolution, we

    must first convert all siamesed lines into an equivalent length of 2

    hose.

    a. Converting Siamesed Hoselines to Equivalent 2 Lengths

    To convert siamesed lines to an equivalent 2 length, we must

    first find the average length of the siamesed hoses. This is done by

    taking the total length of all siamesed hoses and dividing this figure

    by the number of hoses being siamesed.

    The example above shows a typical siamese operation. To find the

    average length of siamesed hose:

    Step 1: Find total length of siamesed hose

    600 ft + 600 ft = 1200 ft

    Step 2: Divide the total length of siamesed hose by the number

    of

    siamesed hoses.

  • 8/3/2019 Fire 11

    30/63

    1200 ft 2 = 600 ft

    b. Using rule of thumb factors to find equivalent length

    To find the equivalent length of siamesed hoses, we will need

    to multiply the average length of the siamesed hoses by the ruleof thumb factor. These factors are listed below and will be

    provided for you on the exam. You are not required to

    memorize the factors.

    Number of Siamesed Hoses Rule of Thumb Factor

    2 1 hoses 3.75

    2 2 hoses .28

    3 2 hoses .13

    4 2 hoses .08

    Work Problem: Find the friction loss for the evolution shown

    below.

    Step 1: Find the average length of siamesed hoses

    600 ft + 600 ft = 1200 ft

    1200 ft 2 = 600 ft

    Step 2: Find equivalent length of siamesed hoses (this

    is the average length multiplied by the factor)

    600 ft x .28 = 168 ft

    Step 3: Find friction loss

    FL = 2Q2 + Q Q = GPM 100

    FL = 2 (5)2 + 5 Q = 500 100

    FL = 2 (25) + 5 Q = 5

    FL = 55 (per 100 ft of hose)

  • 8/3/2019 Fire 11

    31/63

    FL = 55 x 1.68 (168 ft 100)

    FL = 92.4 psi

    Work Problem: Find the friction loss for the evolution shown

    below.

    Step 1: Find the average length of siamesed hoses

    600 ft + 600 ft = 1200 ft

    1200 ft 2 = 600 ft

    Step 2: Find equivalent length of siamesed hoses (this

    is the average length multiplied by the factor)

    600 ft x .28 = 168 ft

    Step 3: Find total equivalent length of evolution

    (equivalent length of siamesed hose + single 2 hose)

    168 ft + 300 ft = 468 ft

    Step 4: Find Friction loss

    FL = 2Q2 + Q Q = GPM 100

    FL = 2 (2.5)2 + 2.5 Q = 250 100

    FL = 2 (6.25) + 2.5 Q = 2.5

    FL = 15 (per 100 ft of hose)

    FL = 15 x 4.68 (468 ft 100)

    FL = 70.2 psi

    Work Problem: The fire engine below is supplying three 2

    hoselines to a portable deluge flowing 600 gpm.

    Find the friction loss of the hoses.

  • 8/3/2019 Fire 11

    32/63

    Step 1: Find the average length of siamesed hoses

    400 ft + 350 ft + 450 ft = 1200 ft

    1200 ft 3 = 400 ft

    Step 2: Find equivalent length of siamesed hoses (this

    is the average length multiplied by the factor)

    400 ft x .13 = 52 ft

    Step 3: Find friction loss

    FL = 2Q2 + Q Q = GPM 100

    FL = 2 (6)2 + 6 Q = 600 100

    FL = 2 (36) + 6 Q = 6

    FL = 78 (per 100 ft of hose)

    FL = 78 x .52 (52 ft 100)

    FL = 40.56 psi

    4) Finding Friction Loss in Wyed Hose Lays

    Some hose evolutions involve the use of wyed hose lays. This means that

    one hose is split into two or more hoselines by use of a wye or water thief

    appliance. In order to find friction loss in this type of evolution, we must

    first convert all wyed hoselines into an equivalent length of 2 .

    a. Converting Wyed Hoselines to Equivalent 2 Lengths

    To convert wyed hoselines to an equivalent 2 length, we must

    first find the average length of the wyed hoses. This is done by

    taking the total length of all wyed hoselines and dividing this figure

    by the number of hoses being wyed.

  • 8/3/2019 Fire 11

    33/63

    The example above shows a typical wyed operation. To find the

    average length of wyed hose:

    Step 1: Find total length of wyed hose

    200 ft + 200 ft = 400 ft

    Step 2: Divide the total length of siamesed hose by the number

    of

    siamesed hoses.

    400 ft 2 = 200 ft

    b. Using rule of thumb factors to find equivalent length

    To find the equivalent length of wyed hoses, we will need to

    multiply the average length of the wyed hoses by the rule of

    thumb factor. These factors are listed below and will be

    provided for you on the exam. You are not required to

    memorize the factors.

    Number of Wyed Hoses Rule of Thumb Factor

    2 1 hoses 3.75

    2 2 hoses .28

    3 2 hoses .13

    4 2 hoses .08

    Work Problem: Find the friction loss for the evolution shown

    below.

    Step 1: Find the average length of the wyed hoses

    200 ft + 200 ft = 400 ft

    400 ft 2 = 200 ft

    Step 2: Find equivalent length of wyed hoses (this is

    the average length multiplied by the factor)

    200 ft x 3.75 = 750 ft

  • 8/3/2019 Fire 11

    34/63

    Step 3: Find total equivalent length of evolution

    (equivalent length of siamesed hose + single 2 hose)

    750 ft + 400 ft = 1150 ft

    Step 4: Find total GPM flowing from all hoses

    Total GPM is calculated by adding the GPMs

    flowing from each hoseline or discharge.

    1 hose #1 = 100 GPM 1 hose #2 = 100

    GPM

    100 GPM + 100 GPM = 200 GPM

    GPM = 200 (this figure will be used to find Q)

    Step 5: Find Friction loss

    FL = 2Q2 + Q Q = GPM 100

    FL = 2 (2)2 + 2 Q = 200 100

    FL = 2 (4) + 2 Q = 2

    FL = 10 (per 100 ft of hose)

    FL = 10 x 11.5 (1150 ft 100)

    FL = 115 psi

    Note: Finding friction loss for siamesed and wyed lines

    are very similar. The rule of thumb figures are the same when finding equivalent

    length

    The only difference is when finding friction

    loss in wyed lines, the total gpm must be found by

    adding the gpm of each individual line that isdischarging water.

    Work Problem: Find the friction loss for the evolution shown

    below. A fire truck is pumping through 400 ft of 2 hose that is wyed to

    two 2 hoselines each flowing 200 gpm.

    Step 1: Find the average length of the wyed hoses

    200 ft + 300 ft = 500 ft

  • 8/3/2019 Fire 11

    35/63

    500 ft 2 = 250 ft

    Step 2: Find equivalent length of wyed hoses (this is

    the average length multiplied by the factor)

    250 ft x .28 = 70 ft

    Step 3: Find total equivalent length of evolution

    (equivalent length of siamesed hose + single 2 hose)

    70 ft + 200 ft = 270 ft

    Step 4: Find total GPM flowing from all hoses

    Total GPM is calculated by adding the GPMs

    flowing from each hoseline or discharge.

    2 hose #1 = 200 GPM 2 hose #2 = 200

    GPM

    200 GPM + 200 GPM = 400 GPM

    GPM = 400 (this figure will be used to find Q)

    Step 5: Find Friction loss

    FL = 2Q2

    + Q Q = GPM 100

    FL = 2 (4)2 + 4 Q = 400 100

    FL = 2 (16) + 4 Q = 4

    FL = 36 (per 100 ft of hose)

    FL = 36 x 2.7 (270 ft 100)

    FL = 97.2 psi

    Chapter 6: Fire Ground (Field)

    Calculations

    General Information

  • 8/3/2019 Fire 11

    36/63

    In the previous chapter we discussed how engine pressure was found using

    various formulas and conversion factors. If youre sitting in a classroom

    taking an exam, these methods for finding the proper engine pressure is

    adequate. But, as you all know, finding the proper engine pressure is most

    critical and valuable at the fire scene. Pump operators do not have the luxury

    of booting up their laptop computers or pulling out a calculator during anincident. Operators need to have some sort of pre-determined method to

    quickly deliver water to the hoselines with the proper pressure. This method is

    termed Fire Ground Calculations or Field Calculations. These

    calculations are not designed to be exact, but rather to be quick and close.

    Field Calculations also require the operator to memorize certain constants

    such as nozzle pressures, appliance losses, and even memorizing the friction

    loss in commonly used hoselines. Below is an outline of Field Calculation

    constants that will need to be memorized.

    1) Basic Formula

    The basic formula for Engine Pressure (EP) is:

    EP= Nozzle Pressure + Friction Loss (hose) + Back Pressure + Appliance

    Loss

    EP = NP + FL + BP + APP

    The components (NP, FL, BP, and APP) of this formula will be explainedbelow.

    2) Appliance Loss Figures (APP)

    Appliance Friction Loss Figure

    Deluge (Turret or Deluge) 25 psi

    Dry Standpipe connection 25 psi + BP

    Wye or Siamese connection 5 psi

    Ladderpipe 80 psi

    Sprinkler System (no fire) 100 psi + BP

    Sprinkler System (with fire) 150 psi + BP

    3) Nozzle Pressures (NP)

    Handlines Master Streams

    Barrel Tip (solid stream) 50 psi 80 psi

  • 8/3/2019 Fire 11

    37/63

    Fog Nozzle (fog or straight stream) 80 psi 100 psi

    These nozzle pressure figures are to be used for work problems where

    nozzle type, and not pressure, is given.

    4) Back Pressure

    The field calculation for back pressure is 5 psi per 10 of grade or5 psi

    per story above the first floor.

    5) Friction Loss in Hoselines

    You will be required to memorize the boldface friction loss figures in the

    chart below. The calculated figure is next to the field calculation figure to

    show how the field calculation figure is obtained.

    Nozzle Size Hose Size GPM Friction Loss per 100

    feet

    Desktop Field

    Calculation

    Calculation

    1/2 - 5/8 1 30 30 30

    40 47.3 45

    50 68.2 70

    3/4" 1 1/2 100 39 35

    3/4" 1 3/4 125 34 35

    150 46.6 45

    200 77 75

    1 2 1/2" 200 10 10

    1 1/8 2 1/2" 250 15 15

    1 1/4" 2 1/2" 300 21 21

    1 3/8 4 500 4.95 5

    1 1/2" 600 7 7

    1 3/4" 800 12.2 10

  • 8/3/2019 Fire 11

    38/63

    2 1000 18.9 20

    Notes: 4 hoseline used as a supply line for master streams (ladder

    pipe, deluge, and snorkel) and relays. Friction loss figures are for each 100length of hose Items in bold to be memorized for final

    Work Problems:

    Using Fire Ground calculations, find the proper EP for the following:

    a) 200 of 1 hose flowing 30 gpm at 60 psi

    EP= NP + FL + BP + APP

    EP = 60 + (30 X 2) + 0 + 0

    EP = 60 + 60

    EP = 120 psi

    Note: FL figures must be multiplied by the number of 100 of

    hose

    When there are no figures for BP or APP, use 0

    b) 200 of 1 handline with a fog tip nozzle flowing 100 gpm

    EP = NP + FL + BP + APP

    EP = 80 + (35 X 2) + 0 + 0

    EP = 80 + 70

    EP = 150 psi

    b) 400 of 2 handline with a barrel tip nozzle flowing 250 gpm on

    a

    hill 50 above the fire truck

    EP = NP + FL + BP + APP

    EP = 50 + (15 X 4) + (5 X 5) + 0

    EP = 50 + 60 + 25 + 0

  • 8/3/2019 Fire 11

    39/63

    EP = 135 psi

    6) Siamesed Hoselines

    When two or more hoselines are used to supply water to a desired point or

    appliance, calculations are simplified by calculating the friction loss in theaverage length of the siamesed hoselines. Each hoseline will deliver its

    equal share of water because the pressure applied by the fire pump will

    equalize in the hoselines. The discharge rate (GPM) will be divided by the

    number of siamesed hoselines when determining gpm for each hoseline.

    The average length of the siamesed hoses is 600

    total length number of hoses

    (600 + 600) 2 = 600

    The average flow of the hoses is 250 gpm

    Total gpm number of hoses

    500 gpm 2 = 250

    Using fire ground calculations, we know that each 100 length

    of 2 hose flowing 250 gpm has a friction loss of 15 psi.

    600 100 = 6

    6 X 15 = 90psi

    The total friction loss in the siamesed hoses is 90 psi.

    Work Problem: Using Fire Ground Calculations, find the EP of the

    following evolution.

    EP = NP + FL + BP + APP

  • 8/3/2019 Fire 11

    40/63

    Step 1: Find NP

    The NP for a master stream using a fog nozzle is 100

    NP = 100 psi

    Step 2: Find FL

    The average length of siamesed hoses is 400:

    (400 + 350 + 450) 3

    1200 3 = 400

    The average flow of the siamesed hoses is 200 GPM

    600 GPM 3 = 200

    FL = 10 psi for every 100 of 2 hose flowing 200 GPM

    FL = 10 X 4

    FL = 40 psi

    Step 3: Find BP

    There is no BP for this problem

    BP = 0

    Step 4: Find APP

    The appliance loss figure for a Deluge is 25 psi

    APP = 25 psi

    Step 5: Plug all the figures into the formula

    EP = NP + FL + BP + APP

    EP = 100 + 40 + 0 + 25

    EP = 165 psi

    7) Wyed Hoselines

  • 8/3/2019 Fire 11

    41/63

    For wyed lines of equal diameter with nozzles of the same size, the friction

    loss for the average length of wyed lines will be considered. Find the

    average length and treat as one line. This means that the nozzle pressure

    of only one hose will be added to the NP portion of the EP formula. The

    hoseline supplying the wyed lines (before the wye) must provide the total

    amount of GPM to all the wyed lines. The total GPM will be used for allfriction loss calculations behind (pump side) the wye. For all calculations

    in front of the wye (nozzle side of wye), use the discharge of only one

    hoseline. The following example should make this a little clearer.

    Work Problem: Using Fire Ground Calculations, find the EP of the

    following evolution.

    EP = NP + FL + BP + APP

    Step 1: Find NP

    Find the nozzle pressure of only one nozzle

    The NP for a handline using a fog nozzle is 80 psi

    NP = 80 psi

    Step 2: Find FL in the wyed hoselines

    The average length of wyed hoses is 200:

    (150 + 250) 2

    400 2 = 200

    The flow of one of the wyed hoses is 100 GPM

    FL = 35 psi for every 100 of 1 hose flowing 100 GPM

    FL = 10 X 2

    FL = 70 psi

  • 8/3/2019 Fire 11

    42/63

    Step 3: Find FL in the 2 hoseline before the wye

    Find the total GPM in the 2 hoseline (total of all discharge)

    The total flow of all the wyed hoses is 200 GPM

    100 GPM + 100 GPM = 200 GPM

    The length of the 2 hose is 200

    FL = 10 psi for every 100 of 2 hose flowing 200 GPM

    FL = 10 X 2

    FL = 20 psi

    Step 4: Find the total Friction loss by all hoses

    Total the friction loss in the wyed lines and the 2 line

    Add the results from steps 2 and 3

    70 + 20 = 90

    FL = 90 psi

    Step 5: Find BP

    There is no BP for this problem

    BP = 0

    Step 4: Find APP

    The appliance loss figure for a Wye is 5 psi

    APP = 5 psi

    Step 5: Plug all the figures into the formula

    EP = NP + FL + BP + APP

    EP = 80 + 90 + 0 + 5

    EP = 175 psi

  • 8/3/2019 Fire 11

    43/63

    Do problems on worksheet provided for extra practice. Contact the

    instructor if you need a worksheet or have any questions.

    Remember: If you encounter a work problem that has a GPM value

    not covered in the Field Calculation Chart, or if you forget a FL of a

    hose, you can always find it by using 2Q2 + Q. But remember, thisformula is only for every 100 of 2 hose. Hoses of all other

    diameters need to be converted to an equivalent length.

    8) Supplying Multiple Hoselines

    Some incidents require that hoselines of different lengths and diameters be

    used simultaneously from the same fire truck. The pump operator must be

    able to quickly determine the proper pump pressure for each of the

    different lines. Below is an example of a common hose evolution

    involving different hose diameters and lengths

    The EP for each of the 1 hoselines is 150 psi

    The EP for the 2 hoseline is 95 psi

    What engine pressure should the operator pump?

    Modern fire trucks have multiple discharge outlets, each equipped with

    individual gates and pressure gauges. The pump operator would have

    to set the pump speed at the pressure of the highest discharge pressure.

    In the above example, the pump pressure would have to be set at 150

    psi. This would give the 1 hoselines the proper pressure. As forthe 2 hoseline, the operator would have to choke down or only

    partially open the gate valve to obtain the desired pressure of 95 psi. If

    the 2 gate valve was fully opened, the pressure would be too high

    for the hoseline, and if the pump speed was lowered to 95 psi, the

    pressure would be insufficient for the 1 hoselines.

    Some older fire trucks have multiple discharges, but only one pressure

    gauge. This makes it very difficult when pumping multiple hoselines

    requiring different pressures. One method of pumping these types of

    evolutions is to take the average pressure of all hoselines and set the

    pump pressure to that average. This only works if the different

    pressures are moderately close. The old timers used to set the pump to

  • 8/3/2019 Fire 11

    44/63

    the highest hose pressure and choke down on the other lines that

    require lower pressures. They would check the pressure by stepping

    on the hose and feeling for the perfect hardness.

    9) Aerial Streams (Ladderpipe and Platform Operations)

    Aerial streams are master stream nozzles that are elevated to heights up to

    100 through use of an aerial ladder or an aerial platform. These ladders or

    platforms are mounted directly onto an apparatus called a Ladder Truck or

    Snorkel. Ladder trucks or Snorkel trucks are not required to have their

    own pumps, although some models do. Usually, in an aerial stream

    operation, the truck providing the aerial stream will set up operations in a

    way that best utilizes their aerial stream. Once the aerial is in place, a fire

    truck with a pump will provide water to the aerial truck. It is important for

    the pumper truck to deliver the proper pressure so that an effective fire

    stream is delivered.

    As noted earlier in this chapter, the APP loss for a ladderpipe operation is

    80 psi. This figure is only for the friction loss of components after the

    supply lines and before the nozzle (siamese, hose, BP of elevation). This

    means that operators will have to find the friction loss in the supply lines

    (method for finding FL in siamesed lines) and find the appropriate FL for

    the nozzle used. These figures will be added to the constant APP loss of

    80 psi to get the engine pressure.

    Work Problem: Find the EP of the above ladderpipe operation.

    EP = NP + FL + BP + APP

    Step 1: Find NP

    The NP for a master stream using a fog nozzle is 100 psi

    (given)

    NP = 100 psi

  • 8/3/2019 Fire 11

    45/63

    Step 2: Find FL in the supply hoselines

    The average length of wyed hoses is 200:

    (200 + 200) 2

    400 2 = 200

    The average flow of the hoses is 300 gpm

    Total gpm number of hoses

    600 gpm 2 = 300

    Using fire ground calculations, we know that each 100 length

    of 2 hose flowing 300 gpm has a friction loss of 21 psi.

    200 100 = 2

    2 X 21 = 42 psi

    FL = 42 psi

    Step 3: Find BP

    The BP for ladderpipe operations is included in the APP loss

    BP = 0

    Step 4: Find APP

    The appliance loss figure for a ladderpipe operation is 80 psi

    APP = 80 psi

    Step 5: Plug all the figures into the formula

    EP = NP + FL + BP + APP

    EP = 100 + 42 + 0 + 80

    EP = 222 psi

    10) Relay Pumping

    Relay pumping is used when the distance from the water supply (firehydrant) to the incident is longer than the supply lines carried by a single

  • 8/3/2019 Fire 11

    46/63

    fire truck. A relay operation consists of two or more fire trucks, in

    concession, providing water to the next fire truck.

    Each fire truck, except for the truck pumping the firefighting lines, should

    provide 20 psi residual pressure to the next fire truck. To accomplish this,

    pump operators must pump 20 psi above the friction loss of the relay

    hose. If the 20 psi is not added, the receiving truck will have 0 psi coming

    in and will not be able to deliver any water to the next fire truck. The gpm

    used for finding the friction loss is determined by the amount of water

    flowing through the firefighting lines.

    Engine #1: EP = FL + 20 psi

    Pumping 250 gpm through 1500 of 2

    FL for 2 flowing 250 gpm = 15 per 100

    1500 100 = 15

    FL = 15 X 15

    FL = 225

    Add 20 psi residual pressure

    EP = 225 + 20

    EP = 245 psi

    Engine #2: EP = FL + 20 psi

    Pumping 250 gpm through 1000 of 2

    FL for 2 flowing 250 gpm = 15 per 100

    1000 100 = 10

    FL = 15 X 10

    FL = 150

    Add 20 psi residual pressure

    EP = 150 + 20

  • 8/3/2019 Fire 11

    47/63

    EP = 170 psi

    Engine #3: EP = NP + FL + BP + APP

    NP = 80 psi

    FL = 60 psi (400 2 flowing 250 = 4 X 15)

    BP = 0

    APP = 0

    EP = 80 + 60 + 0 + 0

    EP = 140 psi

    The quickest method in setting up a relay operation is to pump all relaying fire

    trucks at the same pressure (except truck pumping firefighting lines). The pressure

    used should be that of the truck with the longest hose lay. This will ensure

    adequate pressure to all trucks in the relay operation. Once the relay operation is

    set up, adjustments can be made to the pressure. In a relay operation it is difficult

    to tell exactly how much hose is initially laid out, especially if the fire truck did not

    lay out its entire compliment of hose. After water is flowing, there will be time to

    fine- tune the operation.

    Chapter 7: Fire Streams

    1) General Information

    A good fire stream will extinguish a fire in the shortest period of time with a

    minimum amount of water. A good fire stream must have a sufficient amount

    of volume and reach to get to the seat of the fire and cool burning materials

    below their ignition temperature. Some characteristics of a good fire stream

    are as follows:

    a. Does not break up before reaching the fire

    b. Compact enough to reach the height or distance needed

  • 8/3/2019 Fire 11

    48/63

    c. Compact enough so that:

    I. 90% of its volume fits within a 15-inch circle

    OR

    ii. 75% of its volume fits within a 10-inch circle

    b. With no wind, a good fire stream should be able to enter a room

    through a window and strike the ceiling with enough force to

    splatter well enough to extinguish a fire (indirect attack)

    There are several factors that affect a fire stream:

    a. Air resistance (friction of fire stream traveling through air)

    b. Gravity

    c. Wind Conditions

    1. Moderate tail winds will increase the horizontal reach but

    will decrease the vertical reach

    2. Head winds will raise the vertical reach but will shorten

    horizontal reach

    d. Condition of nozzle

    2) Nozzle Size and Pressure

    Each nozzle tip has an optimal nozzle pressure. If the pressure is

    substantially lower or higher than the rated (recommended) nozzle

    pressure, the fire stream produced by that nozzle will be inefficient or

    ineffective. In other words, if a pump operator does not provide the proper

    nozzle pressure, the fire stream produced will break up before reaching the

    fire. As a general rule of thumb, nozzle pressure recommendations are as

    follows:

    Handlines Master Streams

    Barrel Tip (solid stream) 50 psi 80 psi

    Fog Nozzle (fog or straight stream) 80 psi 100 psi

    note: For safety reasons handlines and master stream devices (deluge,

    turret, ladder pipe) should not be pumped from the same pumper

    at

    the same time. If a master stream device should suddenly shut

  • 8/3/2019 Fire 11

    49/63

    down, the pressure being used for the master stream device

    could be

    absorbed by the handlines causing them to burst or injuring the

    firefighters on those handlines. Separate fire trucks should beused

    for incidents requiring the simultaneous use of handlines and

    master stream devices

    The nozzle size must also be suited for the diameter of hoseline that is

    being used. As a general rule, the diameter of the nozzle should not

    exceed of the hose diameter. This means that a 1 hoseline should not

    use a nozzle with a diameter of greater than .

    3) Horizontal Reach

    Firefighters may encounter situations requiring the use of long-range fire

    streams. Some examples are:

    a. Fires producing extreme heat

    b. Unusual structural conditions

    c. Dangerous fires

    i. Flammable tanks

    ii. Gas tanks

    iii. Reactive materials

    d. Limited access

    i. Junk yards

    ii. Lumber yards

    iii. Brush fires

    In theory, a fire stream angled at 45will produce the greatest horizontalreach. However for firefighting purposes, the maximum effective horizontal range of

    a fire stream can be obtained from a fire stream angled between 30-34

  • 8/3/2019 Fire 11

    50/63

    The formula for finding the horizontal reach of a fire stream is:

    Horizontal Reach = x Nozzle Pressure + 26 feet

    HR = NP + 26

    This formula is based on a nozzle size of . For every 1/8

    over

    , 5 feet must be added to the 26.

    Work Problem: What is the horizontal reach of a fire stream flowing

    50

    psi through a 1 tip (nozzle)?

    HR = NP + 26 (+5 for every 1/8 over )

    Step 1: Find difference in eighths between 1 and

    1 (8/8) minus (6/8) = 2/8

    1 is 2 eighths over

    Step 2: Multiply 5 by the total number of eighths over

    5 x 2 = 10

    Step 3: Add the figure in step two into the formula

    HR = NP + 26 + 10

    Step 4: Solve problem (using adjusted formula in step 3)

    HR = NP + 26 + 10

    HR = (50) + 26 + 10

    HR = 25 + 26 + 10

    HR = 61 feet

  • 8/3/2019 Fire 11

    51/63

    Work Problem: What is the horizontal reach of a fire stream flowing

    60

    psi through a 1 1/8 tip (nozzle)?

    HR = NP + 26 (+5 for every 1/8 over )

    Step 1: Find difference in eighths between 1 1/8 and

    1 1/8 (9/8) minus (6/8) = 3/8

    1 1/8 is 3 eighths over

    Step 2: Multiply 5 by the total number of eighths over

    5 x 3 = 15

    Step 3: Add the figure in step two into the formula

    HR = NP + 26 + 15

    Step 4: Solve problem (using adjusted formula in step 3)

    HR = NP + 26 + 15

    HR = (60) + 26 + 15

    HR = 30 + 26 + 15

    HR = 71 feet

    4) Vertical Reach

    Firefighters may encounter situations requiring the use of long vertical fire

    streams. Some examples are:

    a. Multi-storied buildings

    b. Hillside fires

    c. Use of fire streams to disperse contaminants or smoke

    In theory, a fire stream angled at 90will produce the greatest vertical

    reach. However for firefighting purposes, the maximum effective vertical

    range of a fire stream can be obtained from a fire stream angled between

    60-75

  • 8/3/2019 Fire 11

    52/63

    When using a vertical fire stream on a multi-story building, firefighters

    should consider the following factors:

    a. The third floor is considered the highest story that a fire stream may

    be

    applied effectively from the street level.

    a. The fire stream should not be angled greater than 50. This isbecause

    an angle is needed so that the stream may enter the building and

    deflect off the ceiling towards the fire. If the angle is too steep, the

    stream will not reach the fire within the structure, but rather hit the

    ceiling and fall straight down.

    b. If using a deluge or deck gun (turret), park the apparatus on the

    opposite side of street from the fire to help achieve the effective

    angle of discharge (50).

    The formula for finding the vertical reach of a fire stream is:

    Vertical Reach = 5/8 x Nozzle Pressure + 26 feet

    VR = 5/8 NP + 26

    This formula is based on a nozzle size of . For every 1/8

    over

    , 5 feet must be added to the 26.

    Work Problem: What is the vertical reach of a fire stream flowing 40

  • 8/3/2019 Fire 11

    53/63

    psi through a 1 tip (nozzle)?

    VR = 5/8 NP + 26 (+5 for every 1/8 over )

    Step 1: Find difference in eighths between 1 and

    1 (8/8) minus (6/8) = 2/8

    1 is 2 eighths over

    Step 2: Multiply 5 by the total number of eighths over

    5 x 2 = 10

    Step 3: Add the figure in step two into the formula

    VR = 5/8 NP + 26 + 10

    Step 4: Solve problem (using adjusted formula in step 3)

    VR = 5/8 NP + 26 + 10

    HR = 5/8 (40) + 26 + 10 (convert 5/8 to decimal on

    calc.)

    HR = 25 + 26 + 10

    HR = 61 feet

    Work Problem: What is the vertical reach of a fire stream flowing 80

    psi through a 1 1/8 tip (nozzle)?

    VR = 5/8 NP + 26 (+5 for every 1/8 over )

    Step 1: Find difference in eighths between 1 1/8 and

    1 1/8 (9/8) minus (6/8) = 3/8

    1 1/8 is 3 eighths over

    Step 2: Multiply 5 by the total number of eighths over

    5 x 3 = 15

    Step 3: Add the figure in step two into the formula

    VR = 5/8 NP + 26 + 15

    Step 4: Solve problem (using adjusted formula in step 3)

  • 8/3/2019 Fire 11

    54/63

    VR = 5/8 NP + 26 + 15

    HR = 5/8 (80) + 26 + 15 (convert 5/8 to decimal on

    calc.)

    HR = 50 + 26 + 15

    HR = 91 feet

    Note: to increase horizontal or vertical range, increase pressure

    by 1 psi for every foot needed. (i.e. if 10 more feet of reach is needed, increasing the

    nozzle pressure by 10 psi would get the approximate distance needed)

    Chapter 8: Standpipe Systems

    General Remarks

    1) Where required

    a. Tall Buildings

    b. Large Buildings

    c. Special Occupancies

    2) Enforcement in Hawai`i

    a. Building Department Uniform Building Code

    b. Fire Department Uniform Fire Code

    Types of Standpipe Systems in Hawai`i

    1) Dry Standpipe System (designed for Fire Department

    use)

    Dry standpipe systems are required in certain types of occupancies and are

    installed to help provide a water supply throughout the occupancy. A dry

    standpipe system provides 2 hose outlets to each floor of a building.

    These outlets are connected to a pipe, called a riser, which is connected to

    a siamese connection located on the street level at the front of the

    building. When firefighters need water, a fire truck will have to connect toa fire hydrant (intake side of pump) and supply lines to the siamese

  • 8/3/2019 Fire 11

    55/63

    connection (discharge side of pump). Once the fire truck begins

    discharging water to the siamese connection, water will fill the risers and

    will be distributed to all the 2 outlets. Each outlet has an individual

    shut-off, and firefighters can connect their firefighting lines to the desired

    outlet. Once the hoselines are connected and in place, firefighters can then

    open the 2 outlets to allow water to flow through their hoselines.

    The following are guidelines for dry standpipe systems:

    a. Required in buildings 4 or more stories

    b. Riser Size (pipe) 4 6 inches (found within stairwells)

    c. Fire Department Siamese Connection

    i. Located on street front of building

    ii. 2 or 4 way connection for Fire Department use

    d. 2 hose outlets for each riser

    i. 1 per floor level (optional for 1st floor)

    ii. Roof outlet requires a two-way 2 connection

    2) Wet Standpipe System (designed for occupant / tenant

    use)

    Wet standpipe systems are similar to the dry standpipe system, but there

    are a few differences. Wet standpipes have hose cabinets on each floor.

    These hose cabinets contain 1 fire hose with a nozzle. In case of a fire,

    tenants can open the hose cabinet, pull out the hose and then open thevalve allowing water to flow through the hose. With this having been said,

  • 8/3/2019 Fire 11

    56/63

    this type of system requires that water be provided and pressurized up to

    each hose cabinet at all times. Buildings can either use county water

    pressure, or have some type of pressure booster, such as a pump.

    The following are guidelines for dry standpipe systems:

    a. Required in buildings 4 stories or more

    Note: Not required in buildings equipped with an automatic

    sprinkler system.

    b. Riser size (pipe) 2 2

    c. Outlet (Fire hose cabinet) on each floor level

    d. Building fire pumps may be needed to meet flow and pressure

    requirements (UL Underwriters Laboratory FM FactoryMutual)

    3) Combination / Combined Systems

    It is not uncommon to find occupancies having a combination of systems

    for fire protection. Examples of combination systems are:

    a. Combination System (Wet standpipe and Dry standpipe)

    b. Combined System (Dry standpipe and Automatic SprinklerSystem)

    Pumping Operations:

    The following is an example of a typical dry standpipe operation. Using fire

    ground calculations, figure out the engine pressure of a fire truck pumping this

    evolution.

  • 8/3/2019 Fire 11

    57/63

    EP= FL ( 2 hoses to siamese) 2 2-1/2 lines flowing 200 gpm 3 psi

    FL (2 hose on fire floor) 1 2-1/2 line flowing 200 gpm

    10 psi

    FL (1 firefighting lines) 1 1-1/2 line flowing 100

    gpm 35 psi

    FL (Appliance for siamese)

    25 psi

    FL (Wye on the fire floor) 5

    psi

    BP (Back pressure 11 floors)

    50 psi

    NP (Nozzle pressure) 80

    psi

    Engine Pressure =

    208 psi

    note: The way I like to figure this one out is to break up the evolution into 3

    parts.

    First, figure the friction loss for the evolution on the fire floor.

    Step 1: Find the friction loss in the wyed hoses

  • 8/3/2019 Fire 11

    58/63

    Find the average length of the wyed hoses

    100 ft + 100 ft = 200 ft

    200 ft 2 = 100 ft

    1 flowing 100 gpm = 35 psi / 100

    FL = 35 psi

    Step 2: Find friction loss in 2 hose

    Total flow = 200 gpm (both 1 hoses)

    2 hose flowing 200 gpm = 10 / 100

    FL = 10 psi

    Step 3: Find NP and Appliance loss

    NP = 80 psi

    Appliance Loss = 5 psi (2 to 1 wye)

    Total other losses = 85 psi

    Step 4: Combine figures for steps 1 - 3

    35 + 10 + 85

    130 psi

    Second, find friction loss for hoses supplying the siamese.

    Step 1: Find the friction loss in the siamesed hoses

    Find the average length of the wyed hoses

    100 ft + 100 ft = 200 ft

    200 ft 2 = 100 ft

    Find the flow for each 2 hose

    200 gpm (both 1 hoses)

    divided by 2 (number of siamesed hoses)

    Each hose is flowing 100 gpm

  • 8/3/2019 Fire 11

    59/63

    2 flowing 100 gpm = 3 psi / 100

    FL = 3 psi

    Step 2: Find Appliance loss

    Appliance Loss = 25 psi (siamese connection)

    Step 3: Combine figures for steps 1 - 2

    3 + 25

    28 psi

    Third, find back pressure and add this figure to the totals of the above

    steps.

    BP = 10 x 5 (fire on 11th floor = 10 floors above ground)

    BP = 50

    Now we can add all the figures from the 3 parts.

    Part 1 = 130

    Part 2 = 28

    Part 3 = 50

    Total = 208 psi

    Chapter 9: Automatic Sprinkler

    SystemsGeneral Information

    1) History

    Sprinkler systems were developed around the 1850s. These early systems

    were made up of perforated piping and were not automatic. In 1878, USA

    saw its first automatic sprinkler system and shortly afterward, Federick

    Grinnel began rapid commercial development of these automatic sprinkler

    systems. Nowadays, law requires automatic sprinkler systems in certain

  • 8/3/2019 Fire 11

    60/63

    occupancies. These requirements vary from local jurisdictions. Hawai`i

    law requires automatic sprinkler systems in the following occupancies:

    a. High Rise Buildings (required since 1972)

    b. Hotels

    c. Large Retail Stores

    d. Hospitals

    e. Large Assembly Buildings

    f. Basements

    g. Hazardous Storage Areas

    These modern sprinkler systems are very efficient, extinguishing

    approximately 96% of all fires before firefighters arrive at the scene.

    2) Design & Installation per Occupancy Classification

    Sprinkler systems are usually activated when a sprinkler head is exposed

    to extreme heat. Sprinkler heads have links or fuses that are designed to

    open at a pre-determined temperature. Once this temperature is reached,the link or fuse will break and water will begin to flow. Each sprinkler

    head has its own fuse or link, and only those exposed to the pre-

    determined temperature will flow water. In other words, if a fire starts in a

    corner of the room, only the sprinkler heads affected by the fire will

    activate. The heads in the opposite corner may not be exposed to enough

    heat to activate them.

    Light hazard occupancies (low combustibility) require sprinkler heads to

    open when exposed to temperatures around 135 - 150. Examples of theseoccupancies are:

    a. Churches

    b. Schools

    c. Office Buildings

    Ordinary hazard occupancies (moderate quantity of combustibles) require

    sprinkler heads to open when exposed to temperatures of 160and above.

    Examples of these occupancies are:

  • 8/3/2019 Fire 11

    61/63

    a. Warehouses

    b. Laundries

    c. Manufacturing Occupancies

    Extra (high) hazard occupancies require sprinkler heads to open when

    exposed to temperatures of 325and above. Examples of theseoccupancies are:

    a. Airplane Hangars

    b. Occupancies dealing with explosives

    c. Occupancies dealing with flammable liquids or gases

    Basic Types of Automatic Sprinkler Systems

    1) Wet-pipe System

    Wet-pipe sprinkler systems are the most common in use today. These

    systems contain water under pressure to each individual sprinkler head. When a head

    is exposed to a pre-determined temperature, the fuse or link will break and water will

    begin to flow.

    2) Dry-pipe System

    Dry-pipe systems are usually installed in occupancies where there is a

    chance of the water freezing in the lines. Dry-pipe systems have air or nitrogen under

    pressure to each sprinkler head. The pressure in these lines is slightly above the

    water pressure, and this pressure difference is what keeps the water out of the

    sprinkler lines. When a sprinkler head is activated, the air will begin to expel, and the

    air pressure will drop. As the air pressure drops, water will begin to advance

    throughout the lines and flow through the activated heads.

    3) Preaction System

    Pre-action systems are usually installed in areas or occupancies that are

    concerned about water damage from broken or faulty sprinkler lines or

    heads. Water is stopped at the feeders (in the walls before the pipes

    supplying the sprinkler heads) by a valve. This valve is electronically

    activated by a heat-detecting device within the area. Once the heat-

    detecting device detects heat, a signal is sent to the valve and the valve

    opens. Water will then flow to all heads, but will only discharge through

    the activated heads. If a forklift or some other type of equipment breaks a

    sprinkler line, water will not immediately discharge because the valve is

    holding back the water flow and not the sprinkler heads (unlike the wet-

    pipe or dry-pipe systems).

  • 8/3/2019 Fire 11

    62/63

    4) Deluge System

    Deluge systems are generally installed in hazardous areas requiring the

    immediate application of water. This system is very similar to the

    preaction system, except all sprinkler heads are open (no activating

    device). Once the heat-detecting device activates the valve, water willflow from all heads within the area.

    Pumping Operations

    Sprinkler systems are installed in accordance with building and fire codes, and

    therefore usually designed with adequate pressure to supply water. However,

    there may be circumstances when a fire pumper is needed to supplement the

    system. Examples are:

    a. City water main broken or out of order

    b. Building fire pump not working

    When pumping into sprinkler systems, fire pumps may attach hoses to the

    sprinkler systems siamese connection (similar to a standpipe connection). It

    is recommended that:

    a. Initial water pressure be 100 psi

    b. Minimum of 2 supply lines (2 )

    Most sprinkler heads have a discharge opening. Each head can cover

    approximately 100 (10 x 10) square feet. The discharge for sprinkler heads

    can be found using the following formula:

    Sprinkler Discharge = Pressure + 15

    Sprinkler Discharge = P + 15

    note: this formula is to find discharge per head (must multiply # of heads

    flowing)

    Work Problem: A sprinkler system has 8 sprinkler heads activated at

    40 psi. Find the total gpm (discharge)

    Discharge = P + 15

    Discharge = (40) + 15

    Discharge = 20 + 15

    Discharge = 35 (per head)

  • 8/3/2019 Fire 11

    63/63

    Total Discharge = 35 x 8 (# of heads flowing)

    Total Discharge = 280 gpm

    The pressure of a sprinkler head can be found using the following formula:

    Sprinkler Pressure = 2 x (Sprinkler Discharge 15)

    P = 2 (Dis 15)

    Work Problem: An activated sprinkler head is flowing 35

    gpm. What is the pressure of that sprinkler head?

    Pressure = 2 ( Dis 15)

    Pressure = 2 (35 15)

    Pressure = 2 (20)

    Pressure = 40 psi