Upload
amin-mohamed
View
228
Download
0
Embed Size (px)
Citation preview
8/3/2019 Fire 11
1/63
Chapter 1: Water at Rest and In
Motion
Six Principles of Fluid Pressure
1) Fluid pressure is perpendicular to any surface on which it acts.
2) Beneath the surface of a liquid at rest, the pressure is the same in all
directions (upward, sideward, downward).
3) Pressure applied to a confined fluid from without is transmitted equally in
all directions.
4) The pressure of a liquid in an open vessel is proportional to its depth.
5) The pressure of a liquid in an open vessel is proportional to the density of
the liquid.
6) Liquid pressure at the bottom of a vessel is unaffected by the size and
shape of the vessel as long as the height of water remains the same.
Pressure Height Density Relationship
Formulas
a. Pressure (P) = .434 X Height or P = .434H
b. Height / Head (H) = 2.31 X Pressure or H = 2.31P
Work Problems: Using the formulas above, solve the
following:
a. Find the pressure at the bottom of a standpipe filled with
water 100 feet high.
P = .434H
P = .434 (100)
P = 43.4 psi
* The pressure in this formula is often referred to as back
pressure (BP) in pumping operations. This back-pressure
8/3/2019 Fire 11
2/63
may be encountered during high-rise operations, while using
dry standpipes, or pumping up or down hills. BP = .434H
b. The static pressure in a fire hose connected to a standpipe
is 150 psi. How high will that static pressure raise the
water in the standpipe?
H = 2.31P
H = 2.31 (150)
H = 346.5 ft
Back Pressure
1) Multi-Story Buildings
The average height per story is 10-12 feet
BP = .434H
Therefore, BP per story is .434 (12) or 5.2 psi per story
As a rule of thumb, 5 psi per story above the first floor is used for
calculating BP in high-rise buildings.
Work Problems: Using the rule of thumb, find the BP for the following:
a. Fire on the 10th floor level of a 20-story office building
BP = 5 X 9
BP = 45 psi
note: the fire is only 9 floors above ground level (this can be
tricky)
b. Fire on the roof top of a 20-story office building
BP = 5 X 20
BP = 100 psi
Note: in this case, the fire is actually 20 floors above the ground
floor
Because it is on the roof and not the floor level. (Tricky
too)
8/3/2019 Fire 11
3/63
2) Uphill vs. Downhill
A. Uphill:
When pumping on a grade, either uphill or downhill, pump operators
must take into consideration the pressure loss or gain caused by BP.
When pumping uphill, the pump has to work harder to get the water to
the desired location because gravity is acting on the water and holding
it back. The pump pressure must be increased to overcome the back
pressure.
Example: A fire engine is pumping water uphill through a hoseline
that is
80ft above the firetruck.
BP = .434H
.434 (80)
34.7 psi
The pump operator will have to increase the pump pressure by 34.7 psi
to make up the difference in back pressure.
B. Downhill
When pumping downhill, the pump does not have to work as hard
because gravity is acting on the water, helping to move it through the
fire hose. This means that the BP gained will be in addition to the
pump pressure reading. You wont see the pressure increase on your
pump gauge, but the hoseman will feel it on the hoseline.
Example: A fire engine is pumping water downhill through a hoseline
that
is 60ft below the firetruck.
BP = .434H
.434 (60)
26.04 psi
The pump operator will have to decrease the pump pressure by 26.04 psi
To negate the pressure increase caused by back pressure.
8/3/2019 Fire 11
4/63
3) Types of Pressure
a. Static Pressure - Pressure of water at rest
b. Flow Pressure - Pressure of water flowing from nozzle
c. Residual Pressure Pressure remaining in water main or inlet side
of
Fire pump after water is flowing
Chapter 2: Velocity and DischargeDrafting Operations
1) Theory
Drafting is a way in which a fire pump uses atmospheric pressure to draw
water into the fire pump from a static water source (see figure 2.1).
Atmospheric pressure, at sea level, is 14.7 psi. Fire pumps are capable of
expelling its air through use of a priming pump. If all the air within a
pump is displaced and a good seal is maintained (no leaks or loose
fittings), the fire pump can create a vacuum-like atmosphere within the fire
pump. Once this vacuum-like atmosphere is obtained, the atmospheric
pressure outside the pump will be greater than the pressure within the fire
pump, and water will be forced into the pump through the drafting hose.
This means that using the formula H = 2.31P, we can see how atmospheric
pressure will force water into the fire pump up to 33.9 feet high (H = 2.31
X 14.7 psi).
8/3/2019 Fire 11
5/63
Figure 2.1 Drafting Operations
The theoretical lift of 33.9 feet is nearly impossible to obtain. Since the
fire pump cannot produce an absolute vacuum (0 psi), and there is friction
loss in the drafting hose, a practical lift of 22-25 feet is more realistic.
2) Factors Affecting Priming Operations (trying to obtain a
vacuum)
a. Loose hose connections, loose covers, open gates, open valves, too
long or too small suction hose
b. Defective priming pump
c. Depth of water source
note: 1250 gpm pumpers should only take 30 seconds to prime
1500 gpm pumpers should only take 45 seconds to prime
3) Factors Affecting Lift
a. Altitude
b. Weather
c.
Water temperature
8/3/2019 Fire 11
6/63
d. Too long or too small suction hose
Velocity
1) Formulas
For velocity, you will be given either the height of the water or the
pressure. Therefore, two formulas for velocity will be discussed.
a. Velocity = 8 X Height of water or V = 8Hb. Velocity = 12.1 X Pressure of nozzle or V = 12.1P
Work Problems:
What is the velocity of water flow is the nozzle pressure is 60
psi?
V = 12.1 P
V = 12.1 60
V = 12.1 (7.75)
V = 93.78 fps
What is the velocity of water flow from a water tank 50 ft high?
V = 8 H
V = 8 50
V = 8 (7.07)
V = 56.56 fps
Flow Velocities
The velocity of water varies inversely with the cross section of the hoseline
and nozzle tip. What does this mean??
With the same nozzle pressure:
Changing to a smaller nozzle tip will increase nozzle velocity /
pressure
8/3/2019 Fire 11
7/63
Changing to a larger nozzle tip will decrease nozzle velocity / pressure
The inverse relationship between velocity and nozzle size simply means that
when one increases, the other decreases and vice versa.
Nozzle Discharge Gallons per Minute (GPM)
1) Discharge Formulas
a. With Nozzle
Discharge (GPM) = 30 X Diameter of Nozzle2 X Nozzle Pressure
GPM = 30d2PWork Problem: How many GPMs are flowing through a 2 hoselinewith a
1 1/8 nozzle tip with a nozzle pressure of 50 psi?
GPM = 30d2P
GPM = 30 (1.125)250 (nozzle size converted into adecimal)
GPM = 30 (1.27) (7.07)
GPM = 269.37
b. Without Nozzle (open butt)
To find the discharge pressure of a hoseline without a nozzle,
simply use 90% of the original discharge formula. The hose
diameter will substitute as the nozzle size in this case.
GPM (open butt) = 90% X 30 X Hose Diameter2 X Pressure
GPM (open butt) = 27d2 PWork Problem: How many GPMs are flowing through a 2 hoseline
without a nozzle attached to it at 50 psi?
GPM (open butt) = 27d2P
GPM = 27 (2.5)250
8/3/2019 Fire 11
8/63
GPM = 27 (6.25) (7.07)
GPM = 1193.06
Nozzle Reaction
1) Formula
Nozzle Reaction (NR) = 1.57 X Nozzle Diameter2 X Nozzle Pressure
NR = 1.57d2 P
note: In theory, the nozzle reaction will always be greater than the actual
nozzle reaction felt by the firefighter because:
a. The hoseline is in contact with the ground, and this
absorbs
some of the nozzle reaction.
b. Bends in the hoseline as it is laid out will help to absorb
some
of the nozzle reaction.
Work Problem: What is the nozzle reaction of a 2 hoseline with a
1 1/8 nozzle tip flowing 50 psi?
NR = 1.57 d2 P
NR = 1.57 (1.125)2 (50) (nozzle size converted to a decimal)
NR = 1.57 (1.27) (50)
NR = 99.70 lbs
2) Safety Factors to Consider
a. Handling Hose Lines
i. Bends near the nozzle tend to straighten out. The
hoseline should be straight at least 10 feet back of the
nozzle
ii. Nozzle reaction from fog streams is less than straight
streams
8/3/2019 Fire 11
9/63
iii. Open and close nozzle slowly because:
1. Initial nozzle reaction is greater than the nozzle
reaction when water is flowing
2. Sudden closing of nozzle sends pressure surgesbackwards. This is called a water hammer. A
water hammer can break the hoseline, fire pump,
and/or water main.
iv. When using handlines on ladders, the nozzle reaction
could cause the ladder to lift-off and fall away from the
building. To help avoid this dangerous situation from
occurring firefighters should:
1. Fasten the ladder to the window sill
2. Set the base of the ladder further away from the
building
b. Ladder Truck Operations
i. If the hose should burst, the ladder / boom will whip
violently
ii. Always try and shoot the fire stream in-line with the
ladder. Never turn the nozzle more than 15 degrees
fromthe center of the ladder.
Work Problem: What is the nozzle reaction of a ladder pipe
operation flowing 80 psi from a 2 nozzle
tip?
NR = 1.57 d2 P
NR = 1.57 (2)2(80)
NR = 1.57 (4) (80)
NR = 502.4 lbs (force)
Friction Loss
1) Effect of Flow Pattern
a. Laminar Flow Low Flow Velocities
b. Turbulent Flow High Flow Velocities
8/3/2019 Fire 11
10/63
i. Friction loss in hose affected by:
1. Inner lining of hose
2. Age of hose
3. Thickness of hose lining
4. Type of hose jacked weave (will it expand or not)
2) Friction Loss in Hoses
a. Friction loss varies with quality of hose
b. Friction loss varies directly with length of hose line (the longer the
hoseline, the greater the friction loss).
c. Friction loss varies approximately as the square of the velocity of
flow (the faster the flow velocity, the greater the friction loss)
Example:
If the flow velocity is doubled Friction loss is 4 times
greater (2)2 = 4
If the flow velocity is tripled Friction loss is 9 times
greater (3)2 = 9
d. For a given velocity, friction loss varies inversely as the fifth
power of the hose diameter (the bigger the hose diameter, the less
the friction loss)
Example:
If the hose size was doubled from 1 to 3
We see how 1 X 2 = 3
Inverting the 2 we get
Now we take the and multiply it to the fifth power
5 = X X X X = 1/32
We can now conclude that if the hose size is doubled,
the
8/3/2019 Fire 11
11/63
New friction loss is only 1/32 as much as the original
figure.
e. For a given velocity of flow, friction loss is nearly independent of
pressure. In other words, he velocity of flow, and not the pressure,
is the determining factor in friction loss.
3) Formulas (more details in Chapter 5)
a. Friction Loss = 2 X Q2 + Q
FL = 2Q2 + Q Q = GPM 100note: This formula is only for 2 diameter hoselines.
The friction loss figure represents friction loss per 100 ft of 2
hose.
i.e. If the hoseline is 600 ft, the friction loss figure must be
Multiplied by 6 to get the total friction loss in that hoseline.
Work Problem: Find the friction loss in a 2 hoseline 100 ft in length
Flowing 300 gpm.
FL = 2Q2 + Q Q = GPM 100
FL = 2 (3)2 + 3 Q = 300 100
FL = 2 (9) + 3 Q = 3
FL = 21 # per 100 ft length
FL = 21# (since there is only 100 ft of hoseline)
c. Engine Pressure = Friction Loss + Nozzle Pressure
EP = FL + NP
Work Problem: An engine is pumping through 600 ft of 2 hoseline to a nozzle
that is flowing 200 gpm at 100 psi nozzle pressure. Find the engine pressure.
EP = FL + NP FL = 2Q2 + Q Q = GPM 100
EP = FL + 100 FL = 2(2)2 + 2 Q = 200 100
EP = 60 + 100 FL = 2(4) +2 Q = 2
8/3/2019 Fire 11
12/63
EP = 160 psi FL = 10 per 100ft hoseline
FL = 10 X 6 (# of hundreds of feet of
hose)
FL = 60
d. Engine Pressure = Friction Loss + Nozzle Pressure + Back
Pressure
EP = FL + NP + BP
Work Problem: An engine is pumping through 300 ft of 2
hoseline
to a nozzle that is flowing 200 gpm at 100 psi
nozzle
Pressure. The nozzle is on a hill that is 60 ft higher
Than the fire pump. Find the engine pressure.
EP = FL + NP + BP
FL = 2Q2 + Q Q = GPM 100 BP = .434H
FL = 2 (2)2 + 2 Q = 200 100 BP = .434(60)
FL = 2 (4) + 2 Q = 2 BP =
26.04
FL = 10 per 100 ft hoseline
FL = 10 X 3 ( # of hundreds of feet of hose)
FL = 30
EP = FL + NP + BP
EP = 30 + 100 + 26
8/3/2019 Fire 11
13/63
EP = 156 psi
Note: If the nozzle was below the fire pump (downhill or in a
Basement), the BP would have to be subtracted from the EP.
Remember that the gravity would cause the pressure to
increase, thus giving the firefighter on the hoseline too much
pressure.
Chapter 3: Water Distribution System
General Remarks
1) Public Water Systems are designed to perform two
functions.
a. Provide water for domestic, commercial and industrial use
b. Provide water for fire protection
i.
Combination systems use same water source for bothfunctions
ii. Separate systems use potable water for domestic use
and use brackish, salt or treated sewage water for
firefighting.
2) Fire hydrants must be installed and maintained in
accordance to standards set forth by the American Water
Works Association.
3) The term Fire Plug originated from the old days when
pipes were made from hollowed out wood and buried
underground. These pipes were gravity fed from water sources
located in the area. If there were a need for water, the fire
department would expose the pipe by digging up the ground.
Once exposed, a hole was drilled into the wooden pipe. Water
would then flow out of the hole by means of gravity. When the
fire was out, a tapered wooden plug was inserted into the hole
and the pipe would be re-buried.
8/3/2019 Fire 11
14/63
Fire Hydrants
1) Dry Barrel Hydrants (see figure 3.1)
a. Dry barrel hydrants do not have water stored in the fire hydrantitself. Instead, the water is stored in the piping below the hydrant.
When the operating stem is opened, water will begin to fill the
hydrant. This type of hydrant is used in areas where freezing can
occur. If the water is stored in the hydrant, it could freeze and that
hydrant would be useless in a fire situation. Because the water in
the piping below the hydrant is constantly moving, it usually does
not freeze.
b. Main Parts:
i. Dry Barrel
ii. Footpiece
iii. Bonnet
iv. Operating Stem
v. Main Valve
vi. Drain
2) Wet Barrel Hydrants (see figure 3.2)
a. Unlike the dry barrel hydrant, the wet barrel hydrant has water in
the hydrant right up to the discharge outlet. These hydrants should
not be used in areas where freezing could occur. These are the
types of hydrants commonly used in Hawai`i. However, there are
some dry barrel hydrants in use today in Hawai`i.
b. Wet barrel hydrants have fewer parts than dry barrel hydrants.
c. Each outlet has an independent valve on a threaded stem with
operating nut on opposite side of barrel.
8/3/2019 Fire 11
15/63
Figure 3.1 Dry Barrel Hydrant
Figure 3.2 Wet Barrel Hydrant
3) Other Information
d. Hydrant Outlets
i. Every hydrant must have at least two outlets.
8/3/2019 Fire 11
16/63
1. One pumper suction hose outlet (usually 4)
2. One regular hose outlet (usually 2 )
ii. Outlets must not be less than 18 inches from the
ground level.
iii. Outlets must have a cap and chain.
e. Hydrant Spacing
i. Hydrants should not be spaced more than 250 ft apart
in commercial / industrial areas and should have a
minimum flow of 1000 gpm.
ii. Hydrants should not be spaced more than 350 ft apart
in residential areas and should have a minimum flow of1000 gpm.
iii. Hydrants should not be spaced more than 700 ft apart
in rural areas and should have a minimum flow of 1000
gpm.
f. Branch Connection
i. The minimum size water main supplying fire hydrants
in Honolulu is 8 inches. Main sizes smaller than 6 inchesare not suitable for providing fire protection.
ii. Each wet barrel hydrant has its own gate valve. This
gate valve is located somewhere near the hydrant, and its
location is indicated on the fire hydrant. In case the hydrant
should be damaged (if a car knocks one over) the gate valve
can be used to stop the flow of water to that one hydrant
without interrupting the flow to other hydrants on that same
water main.
4) Estimating Available Flow From Fire Hydrants
a. In order to estimate the amount of flow we have available in a
hydrant, we must first find the percentage of drop in pressure
between static and residual pressure.
i. Open hydrant with suction hose connected to fire
truck. At this time take note as to what your intake
(suction) pressure gauge is reading. This is the hydrants
static pressure.
ii. Open a discharge gate for one hoseline. Again look atyour suction gauge. The pressure will be lower because
8/3/2019 Fire 11
17/63
some of the static pressure will have been used for the first
firefighting line. This is the hydrants residual pressure.
iii. Subtract the residual pressure from the static pressure
and convert that number into a percentage. This is the
percentage of drop in pressure between static and residual.
Work Problem: A hydrant is connected to your fire truck with no
Firefighting lines flowing. Your suction gauge reads
60
psi. After opening one firefighting line, your suction
Gauge now reads 55 psi. What is the percentage of
drop in pressure?
Static Pressure = 60 psi
Residual Pressure = 55 psi
Pressure Difference = 5 psi
To find the drop in a %, simply divide the difference in
pressure by the static pressure.
5 psi 60 psi = .083 or 8.3%
b. Applying percentage of drop in pressure to practical situations.
i. Once the percentage of drop between static and
residual pressure is found, that number can be used to help
estimate the number of additional hoselines the hydrant can
supply. The estimates are based on hoselines of the same
diameter utilizing nozzles of the same diameter also. The
following chart shows the general rule of thumb regarding
additional hoselines:
10% or less 3 more hoselines
11-15% 2 more hoselines
16-25% 1 more hoseline
more than 25% no more hoselines
8/3/2019 Fire 11
18/63
Chapter 4: Fire Service Pumps
Introduction
1) Three Basic Types of Fire Pumps
a. Piston Type Fire Pump
b. Rotary Type Fire Pump
c. Centrifugal Type Fire Pump
2) Pump Mounting on Apparatus
a. Mid-ship (middle) 2 ways
i. Between road transmission and rear axle in line with
drive shaft (most common)
ii. Ahead of clutch and transmission with flywheel and
power take off. This type allows for direct engine power to
pump transmission connection. It allows for driving and
pumping simultaneously.
b. Front Mounting
i. From front of engine crankshaft connected to pump
transmission. This type also allows for driving and
pumping simultaneously.
3) Pump Ratings
a. Standard pumper capacity ratings start from 500 gpm and increase
in 250 gpm increments (NFPA 19 Specification) up to 2000 gpm.
i. 500 gpm, 750 gpm, 1000 gpm, 1250 gpm, 1500 gpm,1750 gpm, 2000 gpm
ii. Pumpers must have one 2 gated outlet per 250 gpm
rated capacity.
b. Fire pumps are designed to perform as follows:
100% of rated capacity at 150 psi net pumps pressure
70% of rated capacity at 200 psi net pumps pressure
50% of rated capacity at 250 psi net pumps pressure
8/3/2019 Fire 11
19/63
Net pump pressure is found by subtracting suction or inlet pressure
from the discharge pressure.
Work Problem: A fire pump is discharging 200 psi through a 2
Hoseline and is receiving 50 psi from a fire
Hydrant. What is the net pump pressure?
Net Pump Pressure = Discharge Pressure Intake
Pressure
Net Pump Pressure = 200 psi 50 psi
Net Pump Pressure = 150 psi
Work Problem: A pumper has a capacity rating of 1000 gpm.
Using net pump pressure finds the efficiency
of the pump:
At 150 psi net pump pressure _______gpm
At 200 psi net pump pressure _______gpm
At 250 psi net pump pressure _______gpm
The answers are 1000 gpm (1000 gpm X 100%), 700
gpm
(1000 gpm X 70%) and 500 gpm (1000 gpm X 50%).
note: Fire pumps are most efficient at 150 psi or less.
4) Cavitation
a. Causes of cavitation
i. Lift too high for volume and pressure discharged
ii. Suction hose too small for volume and pressure
discharged
iii. Suction strainer or hose clogged
iv. Partial collapse of hose lining
8/3/2019 Fire 11
20/63
v. Temperature of water too high
b. Signs of cavitation
i. Pump vibrations with loud pinging noises. This is
caused by air bubbles that form in the pump that collapseviolently when they enter the impeller.
ii. Pump running away This happens when the pump is
pumping air or steam instead of water. The pump speed
will increase with no increase in discharge pressure or
volume. The pump operator will hear the engine revving
and running away. If this should occur, shut down
pumping operations immediately.
Centrifugal Fire Pumps1) General Information
a. Water enters the centrifugal pump through the eye and is delivered
to the impeller through the vanes. The impeller increases the speed of
the water and discharges it through the volute. (see figure 4.1)
figure 4.1 Centrifugal Fire Pump
c. Centrifugal pumps may be connected in stages to each other.
Centrifugal pumps can have 1 4 stages. Each impeller and volute
is one stage in a multi-stage centrifugal pump.
2) Capabilities and Limitations
a. Volume (gpm) varies directly as the pump speed. The faster the
pump speed, the greater the volume.
b. Pressure (psi) varies as the square of the pump speed. If you
double the pump speed, the pressure increases 4 times (22 = 4)
c. Centrifugal pumps are not self-priming. A separate rotary vanepriming pump unit is used to prime centrifugal pumps.
8/3/2019 Fire 11
21/63
3) Single-Stage Centrifugal Fire Pumps
a. Basic Designs
i. Single suction impeller
1. Limited up to 750 gpm pumpers
ii. Double suction impeller
1. 1000 1500 gpm pumpers
iii. Double Volute design
1. Limited to single stage pumps
2. High efficiency at rated capacity
b. In general, single stage pumps have a high efficiency rating (about
70%), which is generally slightly higher than multi-stage pumps.
4) Two-Stage Centrifugal Fire Pumps
a. Basic design
i. Two impellers with separate volute chambers for each
impeller
b. Limited use in fire service
i. Pumps may be front mounted for smaller trucks
1. Provides vehicle movement while pumping
2. Able to provide high-pressure for operations (300-
400 psi).
5) Parallel Series Two-Stage Centrifugal Pumps
a. Basic design
i. Two impellers with separate volutes
ii. Addition of transfer or changeover valve for parallel or
series pumping operations
iii. The efficiency of parallel series two-stage pumps is
around 65-70%. This is slightly less than a single stagepump.
8/3/2019 Fire 11
22/63
b. Parallel (Volume) Operations (see figure 4.2)
i. When a pump is placed in the parallel position, water
enters both stages of the pump simultaneously from the
suction side. This means that the pump will be able to
deliver twice the volume at half of the pressure.
ii. An example of this is: A 1000 gpm rated capacity
pumper operating at 150 psi net pump pressure. In the
parallel position, each impeller will deliver 500 gpm at 150
psi. Note that the pump will double the volume of water,
but at half the speed.
figure 4.2 Parallel Series pump in parallel position
c. Series (Pressure) Operations (see figure 4.3)
i. When a pump is placed in the series position, water
enters one stage of the pump from the suction side. The
water is then delivered to the second stage via the first stage
of the pump. This means that the pump will be able to
deliver half the volume at twice the pressure.
ii. An example of this is: A 1000 gpm rated capacity
pumper operating at 150 psi net pump pressure. In theseries position, the first impeller will deliver 500 gpm at
150 psi to the second stage. The second impeller will
discharge the 500 gpm, but it will double the pressure. In
the series position, this pump will deliver 500 gpm at 300
psi. Note that the pump will double the pressure, but at half
the volume.
8/3/2019 Fire 11
23/63
figure 4.3 Parallel Series pump in series position
d. Transfer Valve
i. A transfer valve is the device that is used to change a
pump from series to parallel or vice versa. The pump
operator must decide which position would best meet the
needs of a given situation.
ii. Transfer valves may be either powered or manual
iii. Transfer valves may be disk type or cylinder type
iv. Transfer valves are normally left in the series position
for normal day-to-day operations.
v. As a general rule, the transfer valve should be kept in
the series position when pumping up to 70% of the pumps
capacity. The transfer valve should be switched to the
parallel position when evolutions or circumstances require a
pump to deliver more than 70% of its rated capacity.
vi. When switching the transfer valve from one position
to another, the pump pressure should be lowered to below
60 psi. This is especially crucial when switching from
parallel to series because the pressure will immediately
double. This sudden increase in pressure could damage the
pump, hoses, or seriously injure the firefighters on the
hoselines.
6) Piston Pumps
a. General Remarks
i. Piston pumps were the first pumps developed for
firefighting.
8/3/2019 Fire 11
24/63
ii. Piston pumps are preferred by fire departments that get
their water supply mostly by drafting operations.
iii. Piston pumps have a high efficiency (around 75-80%)
b. Basic Design
i. Use of piston to displace water
1. Single action (water gets moved on pistons up
stroke)
2. Double action (water gets moved on up stroke and
down stroke)
ii. Piston pumps are positive displacement pumps. This
means that they are self-priming
iii. Different gear ratios between engine and pump are
needed to obtain higher pressure.
7) Rotary Fire Pumps
a. General Remarks
i. Rotary fire pumps were first used by the fire service
around the 1600s. In the 1900s they were adapted towork with the steam engines.
ii. Rotary pumps are preferred where all pumping
operations involve drafting, high lift conditions, or long
suction hoses.
Chapter 5: Friction Loss Calculations
Basic 2 Hoselines
As discussed earlier, the formula for finding friction loss in a 2 fire hose
is:
FL= 2Q2 + Q; where Q= GPM 100.This formula only applies to:
a. 2 diameter fire hose per 100 ft length
8/3/2019 Fire 11
25/63
b. 2 diameter fire hose flowing 100 gpm or greater
The formula for finding friction loss in a 2 fire hose flowing less than
100
gpm is:
FL = 2Q2 + Q; where Q = GPM 100Work Problems:
Find the friction loss in a 500 ft length of 2 fire hose flowing 200
gpm.
FL = 2Q2 + Q Q = GPM 100
FL = 2 (2)2 + 2 Q = 200 100
FL = 2 (4) + 2 Q = 2
FL = 10 per 100 length
FL = 10 x 5 (500 ft 100)
FL = 50 psi
Find the friction loss in a 800 ft length of 2 fire hose flowing 250gpm.
FL = 2Q2 + Q Q = GPM 100
FL = 2 (2.5)2 + 2.5 Q = 250 100
FL = 2 (6.25) + 2.5 Q = 2.5
FL = 15 per 100 length
FL = 15 x 8 (800 ft 100)
FL = 120 psi
Find the friction loss in 400 ft of 2 fire hose flowing 80 gpm.
FL = 2Q2 + 1/2 Q Q = GPM 100
FL = 2 (.8)2 + (.8) Q = 80 100
FL = 2 (.64) + .32 Q = .8
8/3/2019 Fire 11
26/63
FL = 1.6 per 100 length
FL = 1.6 x 4 (400 ft 100)
FL = 6.4 psi
Finding friction loss for hoses other than 2 diameters.
1) Finding Equivalent Lengths
Before we can use the friction loss formula on hoses other than 2 in
diameter, we must first find the equivalent length. In other words, we will
be converting the hose to reflect the length in a 2 diameter.
This is like converting feet to inches. Suppose we wanted to convert 5 feet
into inches; it is understood that we must multiply the number of feet by
12 (the number of inches in a foot). 5 feet converted to inches would be: 5
x 12 = 60 inches.
Keeping that principle in mind, we only have a friction loss formula for 2
hoselines. We will need to convert hoses of all other diameters to a 2
length. This is called finding the equivalent length. It is easier to
find the equivalent length, than it is to learn a new friction loss formula for
each possible hose diameter.
There are two methods in which we can find an equivalent length.
a. Using Rule of Thumb
To find the equivalent length of a fire hose using the rule of
thumb,
simply multiply the total length of hose by the rule of thumb
factor. These factors are listed below and will be provided for
you on the exam. You are not required to memorize the
factors.
Diameter of Hose Rule of Thumb Factor
1 91
1 13
1 7.76
3 .4
8/3/2019 Fire 11
27/63
3 .17
4 .09
Work Problem: Using the rule of thumb factor, convert the
following to an equivalent 2 length:
100 ft of 1 hose = 100 x 91 or 9100 ft of 2
100 ft of 1 hose = 100 x 13 or 1300 ft of 2
100 ft of 4 hose = 100 x .09 or 9 ft of 2
b. Using Conversion Factor
To find the equivalent length of a fire hose using conversion
factor,
divide the total length of hose by the conversion factor. These
factors are listed below and will be provided for you on the
exam. You are not required to memorize the factors.
Diameter of Hose Conversion Factor
1 .011
1 .074
1 .129
3 2.5
3 5.8
4 11.0
Work Problem: Using the conversion factor, convert the
following to an equivalent 2 length:
100 ft of 1 hose = 100 .011 or 9090 ft of 2
100 ft of 1 hose = 100 .074 or 1351 ft of 2
100 ft of 4 hose = 100
11 or 9 ft of 2
8/3/2019 Fire 11
28/63
2) Finding friction loss using equivalent length
Using either equivalent length method (rule of thumb or conversion
factor), we can now find the friction loss for hoses other than 2 .
Work Problem: Find the friction loss in a 1 diameter hoseline 200ft in
Length flowing 100 gpm.
Step 1: Find equivalent length
200 x 13 = 2600 ft or 200 .074 = 2700 ft
(for this example we will use 2600 ft)
Step 2: Find friction loss
FL = 2Q2 + Q Q = GPM 100
FL = 2 (1)2 + 1 Q = 100 100
FL = 2 (1) + 1 Q = 1
FL = 3 (per 100 ft of hose)
FL = 3 x 26 (2600 ft 100)
FL = 78
Work Problem: Find the total friction loss in a 1 diameter hoseline
200 ft in length, connected to a 1 diameter hoseline 200 ft. in length flowing 40
gpm.
Step 1: Find equivalent length of 1 hose
200 x 13 = 2600 ft or 200 .074 = 2700 ft (forthis example we will use 2600 ft)
Step 2: Find equivalent length of 1 hose
200 x 91 = 18,200 ft or 200 .011 = 18,182 ft
(for this example we will use 18,200 ft.)
Step 3: Find total equivalent length of evolution (1 + 1)
2600 ft + 18,200 ft = 20, 800 ft
8/3/2019 Fire 11
29/63
Step 4: Find Friction loss
FL = 2Q2 + Q Q = GPM 100
FL = 2 (.4)2 + (.4) Q = 40 100
FL = 2 (.16) + .2 Q = .4
FL = .52 (per 100 ft of hose)
FL = .52 x 208 (20800 ft 100)
FL = 108.16
3) Finding Friction Loss in Siamese Hose Lays
Some hose evolutions involve the use of siamesed hoselines. This means
that two or more hoses are running parallel to each other and are supplying
water to the same discharge. This discharge can be either a deluge or
another hoseline. In order to find friction loss in this type of evolution, we
must first convert all siamesed lines into an equivalent length of 2
hose.
a. Converting Siamesed Hoselines to Equivalent 2 Lengths
To convert siamesed lines to an equivalent 2 length, we must
first find the average length of the siamesed hoses. This is done by
taking the total length of all siamesed hoses and dividing this figure
by the number of hoses being siamesed.
The example above shows a typical siamese operation. To find the
average length of siamesed hose:
Step 1: Find total length of siamesed hose
600 ft + 600 ft = 1200 ft
Step 2: Divide the total length of siamesed hose by the number
of
siamesed hoses.
8/3/2019 Fire 11
30/63
1200 ft 2 = 600 ft
b. Using rule of thumb factors to find equivalent length
To find the equivalent length of siamesed hoses, we will need
to multiply the average length of the siamesed hoses by the ruleof thumb factor. These factors are listed below and will be
provided for you on the exam. You are not required to
memorize the factors.
Number of Siamesed Hoses Rule of Thumb Factor
2 1 hoses 3.75
2 2 hoses .28
3 2 hoses .13
4 2 hoses .08
Work Problem: Find the friction loss for the evolution shown
below.
Step 1: Find the average length of siamesed hoses
600 ft + 600 ft = 1200 ft
1200 ft 2 = 600 ft
Step 2: Find equivalent length of siamesed hoses (this
is the average length multiplied by the factor)
600 ft x .28 = 168 ft
Step 3: Find friction loss
FL = 2Q2 + Q Q = GPM 100
FL = 2 (5)2 + 5 Q = 500 100
FL = 2 (25) + 5 Q = 5
FL = 55 (per 100 ft of hose)
8/3/2019 Fire 11
31/63
FL = 55 x 1.68 (168 ft 100)
FL = 92.4 psi
Work Problem: Find the friction loss for the evolution shown
below.
Step 1: Find the average length of siamesed hoses
600 ft + 600 ft = 1200 ft
1200 ft 2 = 600 ft
Step 2: Find equivalent length of siamesed hoses (this
is the average length multiplied by the factor)
600 ft x .28 = 168 ft
Step 3: Find total equivalent length of evolution
(equivalent length of siamesed hose + single 2 hose)
168 ft + 300 ft = 468 ft
Step 4: Find Friction loss
FL = 2Q2 + Q Q = GPM 100
FL = 2 (2.5)2 + 2.5 Q = 250 100
FL = 2 (6.25) + 2.5 Q = 2.5
FL = 15 (per 100 ft of hose)
FL = 15 x 4.68 (468 ft 100)
FL = 70.2 psi
Work Problem: The fire engine below is supplying three 2
hoselines to a portable deluge flowing 600 gpm.
Find the friction loss of the hoses.
8/3/2019 Fire 11
32/63
Step 1: Find the average length of siamesed hoses
400 ft + 350 ft + 450 ft = 1200 ft
1200 ft 3 = 400 ft
Step 2: Find equivalent length of siamesed hoses (this
is the average length multiplied by the factor)
400 ft x .13 = 52 ft
Step 3: Find friction loss
FL = 2Q2 + Q Q = GPM 100
FL = 2 (6)2 + 6 Q = 600 100
FL = 2 (36) + 6 Q = 6
FL = 78 (per 100 ft of hose)
FL = 78 x .52 (52 ft 100)
FL = 40.56 psi
4) Finding Friction Loss in Wyed Hose Lays
Some hose evolutions involve the use of wyed hose lays. This means that
one hose is split into two or more hoselines by use of a wye or water thief
appliance. In order to find friction loss in this type of evolution, we must
first convert all wyed hoselines into an equivalent length of 2 .
a. Converting Wyed Hoselines to Equivalent 2 Lengths
To convert wyed hoselines to an equivalent 2 length, we must
first find the average length of the wyed hoses. This is done by
taking the total length of all wyed hoselines and dividing this figure
by the number of hoses being wyed.
8/3/2019 Fire 11
33/63
The example above shows a typical wyed operation. To find the
average length of wyed hose:
Step 1: Find total length of wyed hose
200 ft + 200 ft = 400 ft
Step 2: Divide the total length of siamesed hose by the number
of
siamesed hoses.
400 ft 2 = 200 ft
b. Using rule of thumb factors to find equivalent length
To find the equivalent length of wyed hoses, we will need to
multiply the average length of the wyed hoses by the rule of
thumb factor. These factors are listed below and will be
provided for you on the exam. You are not required to
memorize the factors.
Number of Wyed Hoses Rule of Thumb Factor
2 1 hoses 3.75
2 2 hoses .28
3 2 hoses .13
4 2 hoses .08
Work Problem: Find the friction loss for the evolution shown
below.
Step 1: Find the average length of the wyed hoses
200 ft + 200 ft = 400 ft
400 ft 2 = 200 ft
Step 2: Find equivalent length of wyed hoses (this is
the average length multiplied by the factor)
200 ft x 3.75 = 750 ft
8/3/2019 Fire 11
34/63
Step 3: Find total equivalent length of evolution
(equivalent length of siamesed hose + single 2 hose)
750 ft + 400 ft = 1150 ft
Step 4: Find total GPM flowing from all hoses
Total GPM is calculated by adding the GPMs
flowing from each hoseline or discharge.
1 hose #1 = 100 GPM 1 hose #2 = 100
GPM
100 GPM + 100 GPM = 200 GPM
GPM = 200 (this figure will be used to find Q)
Step 5: Find Friction loss
FL = 2Q2 + Q Q = GPM 100
FL = 2 (2)2 + 2 Q = 200 100
FL = 2 (4) + 2 Q = 2
FL = 10 (per 100 ft of hose)
FL = 10 x 11.5 (1150 ft 100)
FL = 115 psi
Note: Finding friction loss for siamesed and wyed lines
are very similar. The rule of thumb figures are the same when finding equivalent
length
The only difference is when finding friction
loss in wyed lines, the total gpm must be found by
adding the gpm of each individual line that isdischarging water.
Work Problem: Find the friction loss for the evolution shown
below. A fire truck is pumping through 400 ft of 2 hose that is wyed to
two 2 hoselines each flowing 200 gpm.
Step 1: Find the average length of the wyed hoses
200 ft + 300 ft = 500 ft
8/3/2019 Fire 11
35/63
500 ft 2 = 250 ft
Step 2: Find equivalent length of wyed hoses (this is
the average length multiplied by the factor)
250 ft x .28 = 70 ft
Step 3: Find total equivalent length of evolution
(equivalent length of siamesed hose + single 2 hose)
70 ft + 200 ft = 270 ft
Step 4: Find total GPM flowing from all hoses
Total GPM is calculated by adding the GPMs
flowing from each hoseline or discharge.
2 hose #1 = 200 GPM 2 hose #2 = 200
GPM
200 GPM + 200 GPM = 400 GPM
GPM = 400 (this figure will be used to find Q)
Step 5: Find Friction loss
FL = 2Q2
+ Q Q = GPM 100
FL = 2 (4)2 + 4 Q = 400 100
FL = 2 (16) + 4 Q = 4
FL = 36 (per 100 ft of hose)
FL = 36 x 2.7 (270 ft 100)
FL = 97.2 psi
Chapter 6: Fire Ground (Field)
Calculations
General Information
8/3/2019 Fire 11
36/63
In the previous chapter we discussed how engine pressure was found using
various formulas and conversion factors. If youre sitting in a classroom
taking an exam, these methods for finding the proper engine pressure is
adequate. But, as you all know, finding the proper engine pressure is most
critical and valuable at the fire scene. Pump operators do not have the luxury
of booting up their laptop computers or pulling out a calculator during anincident. Operators need to have some sort of pre-determined method to
quickly deliver water to the hoselines with the proper pressure. This method is
termed Fire Ground Calculations or Field Calculations. These
calculations are not designed to be exact, but rather to be quick and close.
Field Calculations also require the operator to memorize certain constants
such as nozzle pressures, appliance losses, and even memorizing the friction
loss in commonly used hoselines. Below is an outline of Field Calculation
constants that will need to be memorized.
1) Basic Formula
The basic formula for Engine Pressure (EP) is:
EP= Nozzle Pressure + Friction Loss (hose) + Back Pressure + Appliance
Loss
EP = NP + FL + BP + APP
The components (NP, FL, BP, and APP) of this formula will be explainedbelow.
2) Appliance Loss Figures (APP)
Appliance Friction Loss Figure
Deluge (Turret or Deluge) 25 psi
Dry Standpipe connection 25 psi + BP
Wye or Siamese connection 5 psi
Ladderpipe 80 psi
Sprinkler System (no fire) 100 psi + BP
Sprinkler System (with fire) 150 psi + BP
3) Nozzle Pressures (NP)
Handlines Master Streams
Barrel Tip (solid stream) 50 psi 80 psi
8/3/2019 Fire 11
37/63
Fog Nozzle (fog or straight stream) 80 psi 100 psi
These nozzle pressure figures are to be used for work problems where
nozzle type, and not pressure, is given.
4) Back Pressure
The field calculation for back pressure is 5 psi per 10 of grade or5 psi
per story above the first floor.
5) Friction Loss in Hoselines
You will be required to memorize the boldface friction loss figures in the
chart below. The calculated figure is next to the field calculation figure to
show how the field calculation figure is obtained.
Nozzle Size Hose Size GPM Friction Loss per 100
feet
Desktop Field
Calculation
Calculation
1/2 - 5/8 1 30 30 30
40 47.3 45
50 68.2 70
3/4" 1 1/2 100 39 35
3/4" 1 3/4 125 34 35
150 46.6 45
200 77 75
1 2 1/2" 200 10 10
1 1/8 2 1/2" 250 15 15
1 1/4" 2 1/2" 300 21 21
1 3/8 4 500 4.95 5
1 1/2" 600 7 7
1 3/4" 800 12.2 10
8/3/2019 Fire 11
38/63
2 1000 18.9 20
Notes: 4 hoseline used as a supply line for master streams (ladder
pipe, deluge, and snorkel) and relays. Friction loss figures are for each 100length of hose Items in bold to be memorized for final
Work Problems:
Using Fire Ground calculations, find the proper EP for the following:
a) 200 of 1 hose flowing 30 gpm at 60 psi
EP= NP + FL + BP + APP
EP = 60 + (30 X 2) + 0 + 0
EP = 60 + 60
EP = 120 psi
Note: FL figures must be multiplied by the number of 100 of
hose
When there are no figures for BP or APP, use 0
b) 200 of 1 handline with a fog tip nozzle flowing 100 gpm
EP = NP + FL + BP + APP
EP = 80 + (35 X 2) + 0 + 0
EP = 80 + 70
EP = 150 psi
b) 400 of 2 handline with a barrel tip nozzle flowing 250 gpm on
a
hill 50 above the fire truck
EP = NP + FL + BP + APP
EP = 50 + (15 X 4) + (5 X 5) + 0
EP = 50 + 60 + 25 + 0
8/3/2019 Fire 11
39/63
EP = 135 psi
6) Siamesed Hoselines
When two or more hoselines are used to supply water to a desired point or
appliance, calculations are simplified by calculating the friction loss in theaverage length of the siamesed hoselines. Each hoseline will deliver its
equal share of water because the pressure applied by the fire pump will
equalize in the hoselines. The discharge rate (GPM) will be divided by the
number of siamesed hoselines when determining gpm for each hoseline.
The average length of the siamesed hoses is 600
total length number of hoses
(600 + 600) 2 = 600
The average flow of the hoses is 250 gpm
Total gpm number of hoses
500 gpm 2 = 250
Using fire ground calculations, we know that each 100 length
of 2 hose flowing 250 gpm has a friction loss of 15 psi.
600 100 = 6
6 X 15 = 90psi
The total friction loss in the siamesed hoses is 90 psi.
Work Problem: Using Fire Ground Calculations, find the EP of the
following evolution.
EP = NP + FL + BP + APP
8/3/2019 Fire 11
40/63
Step 1: Find NP
The NP for a master stream using a fog nozzle is 100
NP = 100 psi
Step 2: Find FL
The average length of siamesed hoses is 400:
(400 + 350 + 450) 3
1200 3 = 400
The average flow of the siamesed hoses is 200 GPM
600 GPM 3 = 200
FL = 10 psi for every 100 of 2 hose flowing 200 GPM
FL = 10 X 4
FL = 40 psi
Step 3: Find BP
There is no BP for this problem
BP = 0
Step 4: Find APP
The appliance loss figure for a Deluge is 25 psi
APP = 25 psi
Step 5: Plug all the figures into the formula
EP = NP + FL + BP + APP
EP = 100 + 40 + 0 + 25
EP = 165 psi
7) Wyed Hoselines
8/3/2019 Fire 11
41/63
For wyed lines of equal diameter with nozzles of the same size, the friction
loss for the average length of wyed lines will be considered. Find the
average length and treat as one line. This means that the nozzle pressure
of only one hose will be added to the NP portion of the EP formula. The
hoseline supplying the wyed lines (before the wye) must provide the total
amount of GPM to all the wyed lines. The total GPM will be used for allfriction loss calculations behind (pump side) the wye. For all calculations
in front of the wye (nozzle side of wye), use the discharge of only one
hoseline. The following example should make this a little clearer.
Work Problem: Using Fire Ground Calculations, find the EP of the
following evolution.
EP = NP + FL + BP + APP
Step 1: Find NP
Find the nozzle pressure of only one nozzle
The NP for a handline using a fog nozzle is 80 psi
NP = 80 psi
Step 2: Find FL in the wyed hoselines
The average length of wyed hoses is 200:
(150 + 250) 2
400 2 = 200
The flow of one of the wyed hoses is 100 GPM
FL = 35 psi for every 100 of 1 hose flowing 100 GPM
FL = 10 X 2
FL = 70 psi
8/3/2019 Fire 11
42/63
Step 3: Find FL in the 2 hoseline before the wye
Find the total GPM in the 2 hoseline (total of all discharge)
The total flow of all the wyed hoses is 200 GPM
100 GPM + 100 GPM = 200 GPM
The length of the 2 hose is 200
FL = 10 psi for every 100 of 2 hose flowing 200 GPM
FL = 10 X 2
FL = 20 psi
Step 4: Find the total Friction loss by all hoses
Total the friction loss in the wyed lines and the 2 line
Add the results from steps 2 and 3
70 + 20 = 90
FL = 90 psi
Step 5: Find BP
There is no BP for this problem
BP = 0
Step 4: Find APP
The appliance loss figure for a Wye is 5 psi
APP = 5 psi
Step 5: Plug all the figures into the formula
EP = NP + FL + BP + APP
EP = 80 + 90 + 0 + 5
EP = 175 psi
8/3/2019 Fire 11
43/63
Do problems on worksheet provided for extra practice. Contact the
instructor if you need a worksheet or have any questions.
Remember: If you encounter a work problem that has a GPM value
not covered in the Field Calculation Chart, or if you forget a FL of a
hose, you can always find it by using 2Q2 + Q. But remember, thisformula is only for every 100 of 2 hose. Hoses of all other
diameters need to be converted to an equivalent length.
8) Supplying Multiple Hoselines
Some incidents require that hoselines of different lengths and diameters be
used simultaneously from the same fire truck. The pump operator must be
able to quickly determine the proper pump pressure for each of the
different lines. Below is an example of a common hose evolution
involving different hose diameters and lengths
The EP for each of the 1 hoselines is 150 psi
The EP for the 2 hoseline is 95 psi
What engine pressure should the operator pump?
Modern fire trucks have multiple discharge outlets, each equipped with
individual gates and pressure gauges. The pump operator would have
to set the pump speed at the pressure of the highest discharge pressure.
In the above example, the pump pressure would have to be set at 150
psi. This would give the 1 hoselines the proper pressure. As forthe 2 hoseline, the operator would have to choke down or only
partially open the gate valve to obtain the desired pressure of 95 psi. If
the 2 gate valve was fully opened, the pressure would be too high
for the hoseline, and if the pump speed was lowered to 95 psi, the
pressure would be insufficient for the 1 hoselines.
Some older fire trucks have multiple discharges, but only one pressure
gauge. This makes it very difficult when pumping multiple hoselines
requiring different pressures. One method of pumping these types of
evolutions is to take the average pressure of all hoselines and set the
pump pressure to that average. This only works if the different
pressures are moderately close. The old timers used to set the pump to
8/3/2019 Fire 11
44/63
the highest hose pressure and choke down on the other lines that
require lower pressures. They would check the pressure by stepping
on the hose and feeling for the perfect hardness.
9) Aerial Streams (Ladderpipe and Platform Operations)
Aerial streams are master stream nozzles that are elevated to heights up to
100 through use of an aerial ladder or an aerial platform. These ladders or
platforms are mounted directly onto an apparatus called a Ladder Truck or
Snorkel. Ladder trucks or Snorkel trucks are not required to have their
own pumps, although some models do. Usually, in an aerial stream
operation, the truck providing the aerial stream will set up operations in a
way that best utilizes their aerial stream. Once the aerial is in place, a fire
truck with a pump will provide water to the aerial truck. It is important for
the pumper truck to deliver the proper pressure so that an effective fire
stream is delivered.
As noted earlier in this chapter, the APP loss for a ladderpipe operation is
80 psi. This figure is only for the friction loss of components after the
supply lines and before the nozzle (siamese, hose, BP of elevation). This
means that operators will have to find the friction loss in the supply lines
(method for finding FL in siamesed lines) and find the appropriate FL for
the nozzle used. These figures will be added to the constant APP loss of
80 psi to get the engine pressure.
Work Problem: Find the EP of the above ladderpipe operation.
EP = NP + FL + BP + APP
Step 1: Find NP
The NP for a master stream using a fog nozzle is 100 psi
(given)
NP = 100 psi
8/3/2019 Fire 11
45/63
Step 2: Find FL in the supply hoselines
The average length of wyed hoses is 200:
(200 + 200) 2
400 2 = 200
The average flow of the hoses is 300 gpm
Total gpm number of hoses
600 gpm 2 = 300
Using fire ground calculations, we know that each 100 length
of 2 hose flowing 300 gpm has a friction loss of 21 psi.
200 100 = 2
2 X 21 = 42 psi
FL = 42 psi
Step 3: Find BP
The BP for ladderpipe operations is included in the APP loss
BP = 0
Step 4: Find APP
The appliance loss figure for a ladderpipe operation is 80 psi
APP = 80 psi
Step 5: Plug all the figures into the formula
EP = NP + FL + BP + APP
EP = 100 + 42 + 0 + 80
EP = 222 psi
10) Relay Pumping
Relay pumping is used when the distance from the water supply (firehydrant) to the incident is longer than the supply lines carried by a single
8/3/2019 Fire 11
46/63
fire truck. A relay operation consists of two or more fire trucks, in
concession, providing water to the next fire truck.
Each fire truck, except for the truck pumping the firefighting lines, should
provide 20 psi residual pressure to the next fire truck. To accomplish this,
pump operators must pump 20 psi above the friction loss of the relay
hose. If the 20 psi is not added, the receiving truck will have 0 psi coming
in and will not be able to deliver any water to the next fire truck. The gpm
used for finding the friction loss is determined by the amount of water
flowing through the firefighting lines.
Engine #1: EP = FL + 20 psi
Pumping 250 gpm through 1500 of 2
FL for 2 flowing 250 gpm = 15 per 100
1500 100 = 15
FL = 15 X 15
FL = 225
Add 20 psi residual pressure
EP = 225 + 20
EP = 245 psi
Engine #2: EP = FL + 20 psi
Pumping 250 gpm through 1000 of 2
FL for 2 flowing 250 gpm = 15 per 100
1000 100 = 10
FL = 15 X 10
FL = 150
Add 20 psi residual pressure
EP = 150 + 20
8/3/2019 Fire 11
47/63
EP = 170 psi
Engine #3: EP = NP + FL + BP + APP
NP = 80 psi
FL = 60 psi (400 2 flowing 250 = 4 X 15)
BP = 0
APP = 0
EP = 80 + 60 + 0 + 0
EP = 140 psi
The quickest method in setting up a relay operation is to pump all relaying fire
trucks at the same pressure (except truck pumping firefighting lines). The pressure
used should be that of the truck with the longest hose lay. This will ensure
adequate pressure to all trucks in the relay operation. Once the relay operation is
set up, adjustments can be made to the pressure. In a relay operation it is difficult
to tell exactly how much hose is initially laid out, especially if the fire truck did not
lay out its entire compliment of hose. After water is flowing, there will be time to
fine- tune the operation.
Chapter 7: Fire Streams
1) General Information
A good fire stream will extinguish a fire in the shortest period of time with a
minimum amount of water. A good fire stream must have a sufficient amount
of volume and reach to get to the seat of the fire and cool burning materials
below their ignition temperature. Some characteristics of a good fire stream
are as follows:
a. Does not break up before reaching the fire
b. Compact enough to reach the height or distance needed
8/3/2019 Fire 11
48/63
c. Compact enough so that:
I. 90% of its volume fits within a 15-inch circle
OR
ii. 75% of its volume fits within a 10-inch circle
b. With no wind, a good fire stream should be able to enter a room
through a window and strike the ceiling with enough force to
splatter well enough to extinguish a fire (indirect attack)
There are several factors that affect a fire stream:
a. Air resistance (friction of fire stream traveling through air)
b. Gravity
c. Wind Conditions
1. Moderate tail winds will increase the horizontal reach but
will decrease the vertical reach
2. Head winds will raise the vertical reach but will shorten
horizontal reach
d. Condition of nozzle
2) Nozzle Size and Pressure
Each nozzle tip has an optimal nozzle pressure. If the pressure is
substantially lower or higher than the rated (recommended) nozzle
pressure, the fire stream produced by that nozzle will be inefficient or
ineffective. In other words, if a pump operator does not provide the proper
nozzle pressure, the fire stream produced will break up before reaching the
fire. As a general rule of thumb, nozzle pressure recommendations are as
follows:
Handlines Master Streams
Barrel Tip (solid stream) 50 psi 80 psi
Fog Nozzle (fog or straight stream) 80 psi 100 psi
note: For safety reasons handlines and master stream devices (deluge,
turret, ladder pipe) should not be pumped from the same pumper
at
the same time. If a master stream device should suddenly shut
8/3/2019 Fire 11
49/63
down, the pressure being used for the master stream device
could be
absorbed by the handlines causing them to burst or injuring the
firefighters on those handlines. Separate fire trucks should beused
for incidents requiring the simultaneous use of handlines and
master stream devices
The nozzle size must also be suited for the diameter of hoseline that is
being used. As a general rule, the diameter of the nozzle should not
exceed of the hose diameter. This means that a 1 hoseline should not
use a nozzle with a diameter of greater than .
3) Horizontal Reach
Firefighters may encounter situations requiring the use of long-range fire
streams. Some examples are:
a. Fires producing extreme heat
b. Unusual structural conditions
c. Dangerous fires
i. Flammable tanks
ii. Gas tanks
iii. Reactive materials
d. Limited access
i. Junk yards
ii. Lumber yards
iii. Brush fires
In theory, a fire stream angled at 45will produce the greatest horizontalreach. However for firefighting purposes, the maximum effective horizontal range of
a fire stream can be obtained from a fire stream angled between 30-34
8/3/2019 Fire 11
50/63
The formula for finding the horizontal reach of a fire stream is:
Horizontal Reach = x Nozzle Pressure + 26 feet
HR = NP + 26
This formula is based on a nozzle size of . For every 1/8
over
, 5 feet must be added to the 26.
Work Problem: What is the horizontal reach of a fire stream flowing
50
psi through a 1 tip (nozzle)?
HR = NP + 26 (+5 for every 1/8 over )
Step 1: Find difference in eighths between 1 and
1 (8/8) minus (6/8) = 2/8
1 is 2 eighths over
Step 2: Multiply 5 by the total number of eighths over
5 x 2 = 10
Step 3: Add the figure in step two into the formula
HR = NP + 26 + 10
Step 4: Solve problem (using adjusted formula in step 3)
HR = NP + 26 + 10
HR = (50) + 26 + 10
HR = 25 + 26 + 10
HR = 61 feet
8/3/2019 Fire 11
51/63
Work Problem: What is the horizontal reach of a fire stream flowing
60
psi through a 1 1/8 tip (nozzle)?
HR = NP + 26 (+5 for every 1/8 over )
Step 1: Find difference in eighths between 1 1/8 and
1 1/8 (9/8) minus (6/8) = 3/8
1 1/8 is 3 eighths over
Step 2: Multiply 5 by the total number of eighths over
5 x 3 = 15
Step 3: Add the figure in step two into the formula
HR = NP + 26 + 15
Step 4: Solve problem (using adjusted formula in step 3)
HR = NP + 26 + 15
HR = (60) + 26 + 15
HR = 30 + 26 + 15
HR = 71 feet
4) Vertical Reach
Firefighters may encounter situations requiring the use of long vertical fire
streams. Some examples are:
a. Multi-storied buildings
b. Hillside fires
c. Use of fire streams to disperse contaminants or smoke
In theory, a fire stream angled at 90will produce the greatest vertical
reach. However for firefighting purposes, the maximum effective vertical
range of a fire stream can be obtained from a fire stream angled between
60-75
8/3/2019 Fire 11
52/63
When using a vertical fire stream on a multi-story building, firefighters
should consider the following factors:
a. The third floor is considered the highest story that a fire stream may
be
applied effectively from the street level.
a. The fire stream should not be angled greater than 50. This isbecause
an angle is needed so that the stream may enter the building and
deflect off the ceiling towards the fire. If the angle is too steep, the
stream will not reach the fire within the structure, but rather hit the
ceiling and fall straight down.
b. If using a deluge or deck gun (turret), park the apparatus on the
opposite side of street from the fire to help achieve the effective
angle of discharge (50).
The formula for finding the vertical reach of a fire stream is:
Vertical Reach = 5/8 x Nozzle Pressure + 26 feet
VR = 5/8 NP + 26
This formula is based on a nozzle size of . For every 1/8
over
, 5 feet must be added to the 26.
Work Problem: What is the vertical reach of a fire stream flowing 40
8/3/2019 Fire 11
53/63
psi through a 1 tip (nozzle)?
VR = 5/8 NP + 26 (+5 for every 1/8 over )
Step 1: Find difference in eighths between 1 and
1 (8/8) minus (6/8) = 2/8
1 is 2 eighths over
Step 2: Multiply 5 by the total number of eighths over
5 x 2 = 10
Step 3: Add the figure in step two into the formula
VR = 5/8 NP + 26 + 10
Step 4: Solve problem (using adjusted formula in step 3)
VR = 5/8 NP + 26 + 10
HR = 5/8 (40) + 26 + 10 (convert 5/8 to decimal on
calc.)
HR = 25 + 26 + 10
HR = 61 feet
Work Problem: What is the vertical reach of a fire stream flowing 80
psi through a 1 1/8 tip (nozzle)?
VR = 5/8 NP + 26 (+5 for every 1/8 over )
Step 1: Find difference in eighths between 1 1/8 and
1 1/8 (9/8) minus (6/8) = 3/8
1 1/8 is 3 eighths over
Step 2: Multiply 5 by the total number of eighths over
5 x 3 = 15
Step 3: Add the figure in step two into the formula
VR = 5/8 NP + 26 + 15
Step 4: Solve problem (using adjusted formula in step 3)
8/3/2019 Fire 11
54/63
VR = 5/8 NP + 26 + 15
HR = 5/8 (80) + 26 + 15 (convert 5/8 to decimal on
calc.)
HR = 50 + 26 + 15
HR = 91 feet
Note: to increase horizontal or vertical range, increase pressure
by 1 psi for every foot needed. (i.e. if 10 more feet of reach is needed, increasing the
nozzle pressure by 10 psi would get the approximate distance needed)
Chapter 8: Standpipe Systems
General Remarks
1) Where required
a. Tall Buildings
b. Large Buildings
c. Special Occupancies
2) Enforcement in Hawai`i
a. Building Department Uniform Building Code
b. Fire Department Uniform Fire Code
Types of Standpipe Systems in Hawai`i
1) Dry Standpipe System (designed for Fire Department
use)
Dry standpipe systems are required in certain types of occupancies and are
installed to help provide a water supply throughout the occupancy. A dry
standpipe system provides 2 hose outlets to each floor of a building.
These outlets are connected to a pipe, called a riser, which is connected to
a siamese connection located on the street level at the front of the
building. When firefighters need water, a fire truck will have to connect toa fire hydrant (intake side of pump) and supply lines to the siamese
8/3/2019 Fire 11
55/63
connection (discharge side of pump). Once the fire truck begins
discharging water to the siamese connection, water will fill the risers and
will be distributed to all the 2 outlets. Each outlet has an individual
shut-off, and firefighters can connect their firefighting lines to the desired
outlet. Once the hoselines are connected and in place, firefighters can then
open the 2 outlets to allow water to flow through their hoselines.
The following are guidelines for dry standpipe systems:
a. Required in buildings 4 or more stories
b. Riser Size (pipe) 4 6 inches (found within stairwells)
c. Fire Department Siamese Connection
i. Located on street front of building
ii. 2 or 4 way connection for Fire Department use
d. 2 hose outlets for each riser
i. 1 per floor level (optional for 1st floor)
ii. Roof outlet requires a two-way 2 connection
2) Wet Standpipe System (designed for occupant / tenant
use)
Wet standpipe systems are similar to the dry standpipe system, but there
are a few differences. Wet standpipes have hose cabinets on each floor.
These hose cabinets contain 1 fire hose with a nozzle. In case of a fire,
tenants can open the hose cabinet, pull out the hose and then open thevalve allowing water to flow through the hose. With this having been said,
8/3/2019 Fire 11
56/63
this type of system requires that water be provided and pressurized up to
each hose cabinet at all times. Buildings can either use county water
pressure, or have some type of pressure booster, such as a pump.
The following are guidelines for dry standpipe systems:
a. Required in buildings 4 stories or more
Note: Not required in buildings equipped with an automatic
sprinkler system.
b. Riser size (pipe) 2 2
c. Outlet (Fire hose cabinet) on each floor level
d. Building fire pumps may be needed to meet flow and pressure
requirements (UL Underwriters Laboratory FM FactoryMutual)
3) Combination / Combined Systems
It is not uncommon to find occupancies having a combination of systems
for fire protection. Examples of combination systems are:
a. Combination System (Wet standpipe and Dry standpipe)
b. Combined System (Dry standpipe and Automatic SprinklerSystem)
Pumping Operations:
The following is an example of a typical dry standpipe operation. Using fire
ground calculations, figure out the engine pressure of a fire truck pumping this
evolution.
8/3/2019 Fire 11
57/63
EP= FL ( 2 hoses to siamese) 2 2-1/2 lines flowing 200 gpm 3 psi
FL (2 hose on fire floor) 1 2-1/2 line flowing 200 gpm
10 psi
FL (1 firefighting lines) 1 1-1/2 line flowing 100
gpm 35 psi
FL (Appliance for siamese)
25 psi
FL (Wye on the fire floor) 5
psi
BP (Back pressure 11 floors)
50 psi
NP (Nozzle pressure) 80
psi
Engine Pressure =
208 psi
note: The way I like to figure this one out is to break up the evolution into 3
parts.
First, figure the friction loss for the evolution on the fire floor.
Step 1: Find the friction loss in the wyed hoses
8/3/2019 Fire 11
58/63
Find the average length of the wyed hoses
100 ft + 100 ft = 200 ft
200 ft 2 = 100 ft
1 flowing 100 gpm = 35 psi / 100
FL = 35 psi
Step 2: Find friction loss in 2 hose
Total flow = 200 gpm (both 1 hoses)
2 hose flowing 200 gpm = 10 / 100
FL = 10 psi
Step 3: Find NP and Appliance loss
NP = 80 psi
Appliance Loss = 5 psi (2 to 1 wye)
Total other losses = 85 psi
Step 4: Combine figures for steps 1 - 3
35 + 10 + 85
130 psi
Second, find friction loss for hoses supplying the siamese.
Step 1: Find the friction loss in the siamesed hoses
Find the average length of the wyed hoses
100 ft + 100 ft = 200 ft
200 ft 2 = 100 ft
Find the flow for each 2 hose
200 gpm (both 1 hoses)
divided by 2 (number of siamesed hoses)
Each hose is flowing 100 gpm
8/3/2019 Fire 11
59/63
2 flowing 100 gpm = 3 psi / 100
FL = 3 psi
Step 2: Find Appliance loss
Appliance Loss = 25 psi (siamese connection)
Step 3: Combine figures for steps 1 - 2
3 + 25
28 psi
Third, find back pressure and add this figure to the totals of the above
steps.
BP = 10 x 5 (fire on 11th floor = 10 floors above ground)
BP = 50
Now we can add all the figures from the 3 parts.
Part 1 = 130
Part 2 = 28
Part 3 = 50
Total = 208 psi
Chapter 9: Automatic Sprinkler
SystemsGeneral Information
1) History
Sprinkler systems were developed around the 1850s. These early systems
were made up of perforated piping and were not automatic. In 1878, USA
saw its first automatic sprinkler system and shortly afterward, Federick
Grinnel began rapid commercial development of these automatic sprinkler
systems. Nowadays, law requires automatic sprinkler systems in certain
8/3/2019 Fire 11
60/63
occupancies. These requirements vary from local jurisdictions. Hawai`i
law requires automatic sprinkler systems in the following occupancies:
a. High Rise Buildings (required since 1972)
b. Hotels
c. Large Retail Stores
d. Hospitals
e. Large Assembly Buildings
f. Basements
g. Hazardous Storage Areas
These modern sprinkler systems are very efficient, extinguishing
approximately 96% of all fires before firefighters arrive at the scene.
2) Design & Installation per Occupancy Classification
Sprinkler systems are usually activated when a sprinkler head is exposed
to extreme heat. Sprinkler heads have links or fuses that are designed to
open at a pre-determined temperature. Once this temperature is reached,the link or fuse will break and water will begin to flow. Each sprinkler
head has its own fuse or link, and only those exposed to the pre-
determined temperature will flow water. In other words, if a fire starts in a
corner of the room, only the sprinkler heads affected by the fire will
activate. The heads in the opposite corner may not be exposed to enough
heat to activate them.
Light hazard occupancies (low combustibility) require sprinkler heads to
open when exposed to temperatures around 135 - 150. Examples of theseoccupancies are:
a. Churches
b. Schools
c. Office Buildings
Ordinary hazard occupancies (moderate quantity of combustibles) require
sprinkler heads to open when exposed to temperatures of 160and above.
Examples of these occupancies are:
8/3/2019 Fire 11
61/63
a. Warehouses
b. Laundries
c. Manufacturing Occupancies
Extra (high) hazard occupancies require sprinkler heads to open when
exposed to temperatures of 325and above. Examples of theseoccupancies are:
a. Airplane Hangars
b. Occupancies dealing with explosives
c. Occupancies dealing with flammable liquids or gases
Basic Types of Automatic Sprinkler Systems
1) Wet-pipe System
Wet-pipe sprinkler systems are the most common in use today. These
systems contain water under pressure to each individual sprinkler head. When a head
is exposed to a pre-determined temperature, the fuse or link will break and water will
begin to flow.
2) Dry-pipe System
Dry-pipe systems are usually installed in occupancies where there is a
chance of the water freezing in the lines. Dry-pipe systems have air or nitrogen under
pressure to each sprinkler head. The pressure in these lines is slightly above the
water pressure, and this pressure difference is what keeps the water out of the
sprinkler lines. When a sprinkler head is activated, the air will begin to expel, and the
air pressure will drop. As the air pressure drops, water will begin to advance
throughout the lines and flow through the activated heads.
3) Preaction System
Pre-action systems are usually installed in areas or occupancies that are
concerned about water damage from broken or faulty sprinkler lines or
heads. Water is stopped at the feeders (in the walls before the pipes
supplying the sprinkler heads) by a valve. This valve is electronically
activated by a heat-detecting device within the area. Once the heat-
detecting device detects heat, a signal is sent to the valve and the valve
opens. Water will then flow to all heads, but will only discharge through
the activated heads. If a forklift or some other type of equipment breaks a
sprinkler line, water will not immediately discharge because the valve is
holding back the water flow and not the sprinkler heads (unlike the wet-
pipe or dry-pipe systems).
8/3/2019 Fire 11
62/63
4) Deluge System
Deluge systems are generally installed in hazardous areas requiring the
immediate application of water. This system is very similar to the
preaction system, except all sprinkler heads are open (no activating
device). Once the heat-detecting device activates the valve, water willflow from all heads within the area.
Pumping Operations
Sprinkler systems are installed in accordance with building and fire codes, and
therefore usually designed with adequate pressure to supply water. However,
there may be circumstances when a fire pumper is needed to supplement the
system. Examples are:
a. City water main broken or out of order
b. Building fire pump not working
When pumping into sprinkler systems, fire pumps may attach hoses to the
sprinkler systems siamese connection (similar to a standpipe connection). It
is recommended that:
a. Initial water pressure be 100 psi
b. Minimum of 2 supply lines (2 )
Most sprinkler heads have a discharge opening. Each head can cover
approximately 100 (10 x 10) square feet. The discharge for sprinkler heads
can be found using the following formula:
Sprinkler Discharge = Pressure + 15
Sprinkler Discharge = P + 15
note: this formula is to find discharge per head (must multiply # of heads
flowing)
Work Problem: A sprinkler system has 8 sprinkler heads activated at
40 psi. Find the total gpm (discharge)
Discharge = P + 15
Discharge = (40) + 15
Discharge = 20 + 15
Discharge = 35 (per head)
8/3/2019 Fire 11
63/63
Total Discharge = 35 x 8 (# of heads flowing)
Total Discharge = 280 gpm
The pressure of a sprinkler head can be found using the following formula:
Sprinkler Pressure = 2 x (Sprinkler Discharge 15)
P = 2 (Dis 15)
Work Problem: An activated sprinkler head is flowing 35
gpm. What is the pressure of that sprinkler head?
Pressure = 2 ( Dis 15)
Pressure = 2 (35 15)
Pressure = 2 (20)
Pressure = 40 psi