28
Hilti, Inc., 5400 South 122 nd East Avenue, Tulsa, OK 74121, (800) 879-8000 FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and Installation Data UL Certificate of Compliance LEED information MSDS UL Details Concrete Assemblies CAJ 7084b - Max. 20” spiral wound or 12” sheet metal duct CAJ 8166a - HVAC line set (sleeve optional) (bottom side access) CAJ 7051d - Max. 30” x 30” sheet metal duct w/o damper WJ 7021g - Max. 48” x 24” sheet metal duct w/o damper WJ 7022d - Max. 20” spiral wound duct w/o damper, or 12” sheet metal duct WJ 7029a - Max. 24” x 12” sheet metal duct with glass fiber duct insulation WJ 7085a - Max. 24” x 24” sheet metal duct Gypsum Wall Assemblies WL 7040g - Max. 48” x 24” sheet metal duct w/o damper WL 7042d - Max. 20” spiral wound duct w/o damper, or 12” sheet metal duct WL 7096a - Max. 13” x 12” sheet metal duct w/o damper WL 7059a - Max. 24” x 12”sheet metal duct with glass fiber duct insulation WL 7143b - Max. 24” x 24” sheet metal duct w/o damper WL 8047c - HVAC Line Set Wood Floor Assemblies FC 7013c - Max. 4” (28 Ga) diameter sheet metal duct w/o damper FC 7025b - Max. 10” (28Ga) or 4” (30 Ga) diameter sheet metal duct w/o damper FC 7042a - Steel strut, steel cable, steel rod, steel angle FC 8014d - Single HVAC Line Set

FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and

  • Upload
    vantram

  • View
    226

  • Download
    3

Embed Size (px)

Citation preview

Page 1: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and

Hilti, Inc., 5400 South 122nd East Avenue, Tulsa, OK 74121, (800) 879-8000

FIRESTOP SUBMITTAL PACKAGE

HVAC

Materials

FS-ONE Intumesent CaulkCP 606 Acrylic

Includes:Technical and Installation DataUL Certificate of Compliance

LEED informationMSDS

UL Details

Concrete Assemblies CAJ 7084b - Max. 20” spiral wound or 12” sheet metal duct CAJ 8166a - HVAC line set (sleeve optional) (bottom side access)

CAJ 7051d - Max. 30” x 30” sheet metal duct w/o damper WJ 7021g - Max. 48” x 24” sheet metal duct w/o damper

WJ 7022d - Max. 20” spiral wound duct w/o damper, or 12” sheet metal duct WJ 7029a - Max. 24” x 12” sheet metal duct with glass fiber duct insulation

WJ 7085a - Max. 24” x 24” sheet metal duct

Gypsum Wall AssembliesWL 7040g - Max. 48” x 24” sheet metal duct w/o damper

WL 7042d - Max. 20” spiral wound duct w/o damper, or 12” sheet metal ductWL 7096a - Max. 13” x 12” sheet metal duct w/o damper

WL 7059a - Max. 24” x 12”sheet metal duct with glass fiber duct insulationWL 7143b - Max. 24” x 24” sheet metal duct w/o damper

WL 8047c - HVAC Line Set

Wood Floor AssembliesFC 7013c - Max. 4” (28 Ga) diameter sheet metal duct w/o damper

FC 7025b - Max. 10” (28Ga) or 4” (30 Ga) diameter sheet metal duct w/o damperFC 7042a - Steel strut, steel cable, steel rod, steel angle

FC 8014d - Single HVAC Line Set

Page 2: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and

Product Information

Chap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

s

Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide 2007

Hilti. Outperform. Outlast.

sodfm,ev iJdjfiwhriuh. NöoWE

Z8Z23awöp3i4eß0288u27 uze

4i5kirdwiloi4jtf-öx-.vbvbvh, ireiv

u9+ß12oeoo

tlke0´9^)&(/R 84tc )v 6453

FS-ONEHigh Performance Intumescent Firestop Sealant

FS-ONE Technical DataChemical basis Water-based intumescent acrylic

dispersionColor RedApplication temperature 40°F to 104°F (5°C to 40°C) Skin forming time Approx. 20-30 min.Curing time Approx. 2 mm / 3 daysMovement capability Approx. 5%Expansion rate Up to 3-5 times (unrestricted): original volumeTemperature resistance (cured) –40°F to 212°F (–40°C to 100°C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96) Smoke Development: 5Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:108City of New York MEA 326-96-M Vol. IVTested in accordance with • UL 1479

• ASTM E 814• ASTM E 84

At 73°F (23°C) and 50% relative humidity

FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION

FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY

66Y7

FMAPPROVED

For Penetration Fire Stops. Consult the Factory Mutual Research Corporation Approval Guide.

R

C

LASSIFIED

FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY

UNDERWRITERS LABORATORIES, INC. FOR USE IN TROUGH-PENETRATION

FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY

66Y7

Product description• Intumescent (expands when exposed to fire) firestop sealant that

helps protect combustible and non-combustible penetrations forup to 4 hours fire rating

Product features• Smoke, gas and water resistant after material has cured

• Contains no halogen, solvents or asbestos

• High fire rating properties

• Water based, easy to clean

• Protects most typical firestop penetration applications

• Can be painted

• Single component systems available

• Meets LEED™ requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings

Areas of application• Steel, copper and EMT pipes

• Insulated steel and copper pipes

• Cable bundles

• Closed or vented plastic pipes

• HVAC penetrations

For use with• Concrete, masonry, drywall and wood floor assemblies

• Wall and floor assemblies rated up to 4 hours

Examples• Sealing around plastic pipe penetrations in fire rated construction

• Sealing around combustible and non-combustible penetrations infire rated construction

1. Clean opening. 2. Pack mineral wool.(If required)

3. Apply FS-ONE. 4. Smooth FS-ONE.

5. Leave completedseal undisturbed for 48hours.

6. Fasten identificationplate (if required).

1. Clean opening. 2. Pack mineral wool.(If required)

3. Apply FS-ONE. 4. Smooth FS-ONE.

5. Leave completedseal undisturbed for 48hours.

6. Fastenidentification plate (ifrequired).

Firestop System

Notice • Before handling, read Material Safety DataSheet and

product label for safe usage and health information.

• Instructions below are general guidelines — alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information

Opening 1. Clean the opening. Surfaces to which FS-ONE will be

applied should be cleaned of loose debris, dirt, oil,moisture, frost and wax. Structures supportingpenetrating items must be installed in compliancewith local building and electrical standards.

Application of firestop sealant 2. Install the prescribed backfilling material type and

depth to obtain the desired rating (if required). Leavesufficient depth for applying FS-ONE.

3. Application of firestop sealant: Apply FS-ONE to therequired depth in order to obtain the desired fire rating.Make sure FS-ONE contacts all surfaces to providemaximum adhesion. For application of FS-ONE use astandard caulking gun, foil pack gun, bulk loader andbulk gun. With FS-ONE buckets, Graco type sealantpumps may be used. (Contact pump manufacturer forproper selection).

4. Smoothing of firestop sealant: To complete the seal,tool immediately to give a smooth appearance.Excess sealant, prior to curing, can be cleanedaway from adjacent surfaces and tools with water.

5. Leave completed seal undisturbed for 48 hours.

6. For maintenance reasons, a penetration seal couldbe permanently marked with an identification plate.In such a case, mark the identification plate andfasten it in a visible position next to the seal.

Not for use • High movement expansion joints

• Underwater

• On materials where oil, plasticizers or solvents maybleed i.e. impregnated wood, oil based seals, greenor partially vulcanized rubber

• In any penetration other than those specificallydescribed in this manual or the test reports

Storage • Store only in the original packaging in a location

protected from moisture at temperatures between 40°F (5°C) and 86°F (30°C)

• Observe expiration date on the packaging

Installation instructions for FS-ONE

Firestop System

Firestop System

CA

BLE

PIP

E

Page 3: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 4: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 5: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 6: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and

Hilti, Inc. 5400 South 122nd East Avenue

Tulsa, OK 74146

1-800-879-8000 www.hilti.com

February 24, 2009 To Whom It May Concern: Re: Hilti FS-ONE Intumescent Firestop – LEED Info. The Hilti FS-ONE Intumescent Firestop is manufactured in Kaufering, Germany. The FS-ONE pail is made of polyethylene and can be completely recycled. There is no post-consumer or post-industrial content in FS-ONE and it cannot be recycled. The VOC content for FS-ONE is 75 grams/liter. FS-ONE is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc (918) 872 3704 [email protected] Rev. Date: 2/24/09

Page 7: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and

Product Information

Chap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

s

Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide 2007

Hilti. Outperform. Outlast.

Hilti FirestopSaving Livesthrough innovationand education

CP 606Flexible Firestop Sealant

CP 606 Technical DataChemical basis Acrylic based firestop sealantColor Available in red or whiteApplication temperature 40°F to 104°F (5°C to 40°C)Skin-forming time Approx. 15 minCuring time Approx. 3 mm / 3 daysVolume shrinkage Less than 20%Movement capability Approx. 10%Temperature resistance –22°F to 176°F (–30°C to 80°C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96) Smoke Development: 5Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 1452-1200:112

Listing No. 1451-1200:121Listing No. 4485-1200:132

City of New York MEA 100-99-M, Vol. IVTested in accordance with • UL 2079 • ASTM E 814

• ASTM E 1966 • ASTM E 84• UL 1479

At 73°F (23°C) and 50% relative humidity

FMAPPROVED

For Penetration Fire Stops. Consult the Factory Mutual Research Corporation Approval Guide.

R

C

LASSIFIED

FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY

UNDERWRITERS LABORATORIES, INC. FOR USE IN TROUGH-PENETRATION

FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY

66Y7

FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION

FIRESTOP SYSTEMS AND JOINT SYSTEMS

SEE UL FIRE RESISTANCE DIRECTORY 66Y7

Product description• An acrylic based firestop sealant that provides movement

capability in fire rated joints and seals through penetrationsapplications

Product features• Silicone free

• Halogen, asbestos and solvent free

• UV-resistant

• Paintable

• Meets 500 cycle requirements (ASTM E 1966 & UL 2079)

• Smoke, fume and water resistant

• Easy clean up with water

• Single component systems available

• Meets LEED™ requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings

Areas of application• Sealing construction/expansion joints

• Top-of-wall joints

• Metal pipes

• Cable bundles

• HVAC penetrations

For use with• Various base materials such as masonry, concrete, metal, etc.

• Wall and floor assemblies rated up to 3 hours

Examples• Where a gypsum wall assembly meets the underside of

a metal or concrete deck

• Sealing expansion joints to impede the passage of fire, smoke andtoxic fumes

• Sealing around HVAC penetrations through fire-rated assemblies

Notice • Before handling, read Material Safety DataSheet and

product label for safe usage and health information.

• Instructions below are general guidelines — alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information

Opening1. Clean the opening. Surfaces to which CP 606 will

be applied should be cleaned of loose debris, dirt,oil, wax and grease. The surface should bemoisture and frost free.

Application of firestop2. Insert fill of mineral wool or backer (as required).

3. Apply firestop over backer.

4. Smooth firestop sealant with a trowel before theskin forms. Once cured, CP 606 can only beremoved mechanically.

5. For maintenance reasons, a penetration seal can bepermanently marked with an identification plate andfastened in a visible position next to the seal.

Not for use• On areas immersed in water

Storage• Store only in the original packaging in a location

protected from moisture at a temperature of 40°F to77°F (5°C to 25°C)

• Observe expiration date on package

Installation instructions for CP 606

1. Clean opening 2. Insert backingmaterial compressedper UL System

3. Apply CP 606 4. Smooth CP 606 5. Fasten identificationplate (if required)

1. Clean opening 2. Insert backingmaterial

3. Apply CP 606 4. Smooth CP 606 5. Fasten identificationplate (if required)

Firestop System

Firestop System

JO

INT

DU

CT

Page 8: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 9: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 10: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 11: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and

Hilti, Inc. 5400 South 122nd East Avenue

Tulsa, OK 74146

1-800-879-8000 www.hilti.com

February 24, 2009 To Whom It May Concern: Re: Hilti CP 606 Flexible Firestop – LEEDs Info. The Hilti CP 606 Flexible Firestop Sealant is manufactured in Kaufering, Germany. The CP 606 pail is made of polyethylene and can be completely recycled. There is no post-consumer or post-industrial content in CP 606 and it cannot be recycled. The CP 606 does not contain any Rapidly Renewable Materials. The VOC content for CP 606 is 71.0 grams/liter. CP 606 is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc. 918 872 3704 [email protected] Rev. Date: 2/24/09

Page 12: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and

Sheet Drawing No.HILTI, Inc.

Tulsa, Oklahoma USA (918) 252-6000Date

Scale

TOP VIEWA

A

SECTION A-A

NOTES : 1. MAXIMUM AREA OF OPENING = 1024 SQUARE INCHES WITH A MAXIMUM DIMENSION OF 32 INCHES.

2. ANNULAR SPACE = MINIMUM 1/4", MAXIMUM 1-3/4". 3. MINIMUM 1" DEPTH HILTI CP 606/FS-ONE FIRESTOP SEALANT AND STEEL ANGLES ARE

REQUIRED ON BOTH SIDES OF A WALL ASSEMBLY. 4. AFTER SEALING SPACE BETWEEN DUCT AND CONCRETE FLOOR/WALL ASSEMBLY WITH

HILTI CP 606, FASTEN STEEL ANGLE (L2 X 2 X MIN. 16 GA.) TO DUCT WITH NO. 8 (OR LARGER) STEEL SHEET METAL SCREWS. ANGLE DOES NOT HAVE TO BE FASTENED TO CONCRETE FLOOR/WALL ASSEMBLY.

1. CONCRETE FLOOR OR WALL ASSEMBLY (3-HR FIRE-RATING): A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MIN. 4-1/2" THICK). B. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MIN. 5-1/2" THICK). C. ANY UL/ULC CLASSIFIED CONCRETE BLOCK WALL.

2. MAXIMUM 30" X 30" RECTANGULAR STEEL DUCT (MINIMUM 24 GAUGE). (NOTE: NOT FOR USE IN DUCT SYSTEMS CONTAINING A DAMPER).

3. MINIMUM 3-1/2" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY) TIGHTLY PACKED. 4. MINIMUM 1" DEPTH HILTI CP 606 FLEXIBLE FIRESTOP SEALANT OR HILTI FS-ONE

INTUMESCENT FIRESTOP SEALANT. 5. SEE NOTE NO. 4 BELOW.

CAJ7051d

1 of 1

5/64" = 1"

NOV. 2, 2000

UL/cUL SYSTEM NO. C-AJ-7051

F-RATING = 3-HR.T-RATING = 1-HR.

CAJ7

051d

.1102

00

3" C/C MAXIMUM SPACING(SEE NOTE NO. 4)

1

2

3

4

5

Page 13: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 14: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 15: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 16: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 17: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 18: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 19: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 20: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 21: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 22: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 23: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and

Sheet Drawing No.HILTI, Inc.

Tulsa, Oklahoma USA (918) 252-6000Date

Scale

FRONT VIEW

A

A

SECTION A-A

NOTES : 1. MAXIMUM AREA OF OPENING = 1300 SQ. IN. WITH A MAXIMUM DIMENSION OF 50 IN. 2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 2". 3. AFTER SEALING SPACE BETWEEN DUCT AND GYPSUM WALL ASSEMBLY WITH HILTI

FIRESTOP SEALANT, FASTEN STEEL ANGLE (MIN. 18 GA.) TO DUCT WITH MINIMUM NO. 8 x 3/4" LONG SHEET METAL SCREWS. STEEL ANGLE TO OVERLAP DUCT BY MINIMUM 2" AND GYPSUM WALL ASSEMBLY BY MINIMUM 1". ANGLE DOES NOT HAVE TO BE FASTENED TO GYPSUM WALL ASSEMBLY.

1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED U300 OR U400 SERIES WALL) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).

2. (NOT SHOWN). WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER. STEEL STUDS TO BE MINIMUM 2-1/2" WIDE.

3. RECTANGULAR SHEET METAL DUCT (MAXIMUM SIZE : 24" x 48", MINIMUM 24 GA. THICKNESS). (NOTE : NOT FOR USE IN DUCT SYSTEMS CONTAINING A FIRE DAMPER).

4. OPENING TO BE "FRAMED OUT" WITH LIGHTGAGE METAL FRAMING STUDS. 5. MINIMUM 5/8" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, HILTI CP 601S ELASTO- MERIC

FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT. 6. (NOT SHOWN). APPLY MINIMUM 1/2" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, HILTI CP

601S ELASTOMERIC FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT AT POINT OF CONTACT PRIOR TO ATTACHING STEEL ANGLE.

WL7040g

1 of 1

5/64" = 1"

Sept. 11, 2001

UL/cUL SYSTEM NO. W-L-7040

F-RATING = 1-HR. OR 2-HR.T-RATING = 0-HR.

WL7

040g

.0911

01

12

3

4 5

6

MAXIMUM 6" C/C SPACING(SEE NOTE NO. 3 BELOW)

Page 24: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and

Sheet Drawing No.

HILTI, Inc.Tulsa, Oklahoma USA (918) 252-6000

Date

Scale

FRONT VIEW

A

A

SECTION A-A

NOTES : 1. MAXIMUM DIAMETER OF OPENING FOR STEEL STUD WALLS = 21-3/4" 2. MAXIMUM DIAMETER OF OPENING FOR WOOD STUD WALLS = 14-1/2". 3. ANNULAR SPACE = MINIMUM 0", MAXIMUM 1-1/2".

1. GYPSUM WALL ASSEMBLY (UL/ULC U300 OR U400 SERIES WALL SERIES) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).

2. (NOT SHOWN). WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER. STEEL STUDS TO BE MINIMUM 2-1/2" WIDE.

3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING : A. MAXIMUM 20" NOMINAL DIAMETER SPIRAL WOUND SHEET METAL DUCT (MIN. 24 GA.). B. MAXIMUM 12" NOMINAL DIAMETER SHEET METAL DUCT (MIN. 28 GAUGE).

4. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, HILTI CP 601S ELASTOMERIC FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT :

A. MINIMUM 5/8" DEPTH, FOR A 1-HR. FIRE RATING. B. MINIMUM 1-1/4" DEPTH, FOR A 2-HR. FIRE RATING.

5. MINIMUM 1/2" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT OR CP 601S ELASTOMERIC FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT AT POINT OF CONTACT.

WL7042d

1 of 1

3/32" = 1"

Jan. 15, 2001

UL/cUL SYSTEM NO. W-L-7042

F-RATING = 1-HR. OR 2-HR.T-RATING = 0-HR.

WL7

042d

.0115

01

12

3

4

5

Page 25: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and

Sheet Drawing No.HILTI, Inc.

Tulsa, Oklahoma USA (918) 252-6000Date

Scale

FRONT VIEW

A

A

SECTION A-A

NOTES : 1. MAX. AREA OF OPENING = 395 SQ. IN. WITH A MAX. DIM. OF 26-3/4". 2. INSULATION SHOULD BE COMPRESSED 50% SUCH THAT THE

ANNULAR SPACE = MIN. 1/4", MAX. 1".

1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED U400 SERIES WALL) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).

2. (NOT SHOWN). STEEL STUDS TO BE MINIMUM 2-1/2" WIDE. OPENING TO BE "FRAMED OUT" ON ALL SIDES OF OPENING WITH LIGHTGAGE METAL STUD MATERIAL.

3. MAXIMUM 24" x 12" RECTANGULAR SHEET METAL DUCT (MINIMUM 24 GA.). (NOTE : NOT FOR USE IN DUCT SYSTEMS CONTAINING A FIRE DAMPER).

4. MAXIMUM 1-1/2" THICKNESS GLASS FIBER DUCT INSULATION (MIN. 3/4 PCF DENSITY) WITH FOIL-SCRIM-KRAFT FACING. (SEE NOTE NO. 2 BELOW).

5. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT : A. MINIMUM 5/8" DEPTH OF SEALANT FOR A 1-HR. FIRE-RATING. B. MINIMUM 1-1/4" DEPTH OF SEALANT FOR A 2-HR. FIRE-RATING.

WL7059a

1 of 1

3/32" = 1"

Feb. 1, 2001

UL/cUL SYSTEM NO. W-L-7059

F-RATING = 1-HR. OR 2-HR.T-RATING = 1/2-HR. OR 3/4-HR.

WJ7

059a

.0201

01

12

3

4 5

Page 26: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 27: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and
Page 28: FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop...FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and