11
Foam Application Rates for E85 and E-95

Foam Calculation (1)

Embed Size (px)

DESCRIPTION

Foam Calculation

Citation preview

  • Foam Application Rates for E85 and E-95

  • Application Rates

    Described in Terms of the Amount in Gallons of Foam Solution Reaching the Total Square Footage of the Fuel Surface Every Minute

    Critical Application Rate - lowest rate at which a foam will extinguish a fire under a particular set of ideal conditions (.06 for gasoline)Minimum application rate - the amount found by tests to be the most practical in terms of speed and control of agent required

  • Application Rates

    Foam concentrate application rates may be as low as 0.06 gpm for gasoline to as much as 0.20 for polar solvents (ethanol).

  • Minimum foam concentrate application rates.Application rates are listed as gpm .10 for flammable liquid spill/fire.16 for tank diameter of less than 150.18 for tank diameter of less than 200.20 for tank diameter of less than 250.20 Polar solvent spill/fire

    Polar Solvent = Ethanol

  • NFPA 11

    Tests have shown that foam may travel effectively across at least 100 feet of burning liquid surface.

    Sometimes

  • Application Rates Calculated

    Determine Area of Hazard Choose Appropriate Application Rate Rate x Area = GPM of Foam Solution Solution GPM x % Used = Concentrate GPM Concentrate GPM x Time = Total Concentrate

    Storage Tanks - 60 Minute Flow Time Spills - 15 Minutes Flow Time

  • Application Rates CalculatedExampleDetermine Area of Hazard = 3000 sq. ftApplication Rate = 0.20 GPMRate x Area + 600 GPM of Solution600 GPM x 3% Used = 18 GPM Concentrate18 x 15 minutes application time = 270 gals neededThis calculation example is based on a spill area of 75 x 40.

  • RequirementsBased upon the 75 x 40 spill footprint one can see that 270 gallons of 3% foam concentrate would be needed.If we assume every gallon of 3% foam concentrate requires 97 gallons of water, we can see that we would also need 26,190 gallons of water (97 x 270) to maintain the required 15-minute application period.

  • PreplanBased upon the previous example:

    Where would you get 270-gallons of 3% AR-AFFF concentrate?Where would you get 26,190-gallons of water in an area without hydrants?

  • Quick Foam Flow Work Sheet

    Determine Area of Hazard* = SQ. FT.* (L x W) or (.785 D2)

    2. Choose Application Rate =

    3. X =

    4. X =Flow rate of solution % of FLC Gallons of FLC per/minute

    5. X = Gallons of FLC per/minutes Duration of flow Total FLC Required

    GPMSq. Ft.GPMGPMGPM%GallonsGallonsMinutes Gallons

  • NFPA 11 states that a minimum15-minute flow duration is required. If you calculate this minimum requirement in all of your foam concentrate requirements this should get you off to a good start.Do not hesitate to calculate more if there is a large spill or fire.Gasohol (not E-95 or E-85) fires may be extinguished using conventional AFFF and AR-AFFF but increased application rates may be necessary especially for prolonged burn back resistance.