Automation & Control Pvt. LtdGCU 101
GCU 101 is a1-Phase/3-Phase automatic/manual generator
controller module. It controls start and stop function of the
engine, monitors the generator operations in both automatic &
manual mode. It uses an advanced single chip microcomputer
for sophisticated automation for generator plant, it is designed
by taking great care related with electromagnetic interfaces for
trouble free operation in harsh electrical environment.
If the mains fails due to over or under voltage or loss of mains, GCU 101 initiates an automatic genset start cycle
following complete AMF function sequence including load transfer to the generator by switching the generator and
mains contactors. It is possible to select up to 5 start attempts with both crank and rest period adjustable. After engine
warm up period has expired the generator supply is connected . After main supply returns and it gets restore the load
will automatically transfer back to the mains and genset will stop after cooling down time. During all cycles, generator
is fully protected against all types of given fault conditions. All alarms occurring at abnormal genset conditions are
computed and displayed either by LED or by four-digit display and if necessary the genset is get stopped. The manual
mode is selected by means of push button switches. The generator start & stop functions are carried out by means of
push button switches & contactor change over is performed by internal logic automatically. Values of Voltage, Current
frequency to initiate genset start cycle and timer settings of preheat, cooling down time etc. are free programmable.
The GCU 101 has 43 powerful programmable parameters to fit the program "ow to customer needs.
Microprocessor based design
8 digital inputs, 9 relay outputs
Automatic, Manual, Test, Periodic test operating modes
Display Parameters AC Voltage, AC Current
Frequency, Hours, Battery Voltage, Charge Voltage
Configurable solid state outputs
Configurable timer setting
Solid state fuel and crank outputs
External remote start inputs
LED alarm indications
Start/Stop delay timer
Warm up / Cooling down timer
Energized to stop timer
Single / Three Phase Mains Sensing
Load contactor control solid state output
Preheat, glow plug timer
Over & Under speed shutdown
Automatic crank disconnection
Serial communication option
Inhibit mode operation
Electronic charge Lamp
Charge voltage display
Periodic Auto Start and Stop
Features-
Control and Fault inputs with front PanelVisual Indications :
Mains Supply On
Mains Contactor On
Generator Supply On
Generator Contactor On
Battery Low Voltage / Charge Fail
Low Oil Pressure
High Engine Temperature
Generator Over Speed Fault
Low Fuel Level
Generator Over Load Fault
Features-
General Description-
DC Supply : 8 to 35 V DC,
Continuous Reverse Polarity Protected
Able to survive 0V for 50mS,Cranking Dropouts :
Providing Supply Voltage was at least 10 V
Before drop out and supply recovers to 5V
This is achieved without need of internal Batteries.
Operating 75 mA, Standby 10mAMaximum Current :
75 (Ph-N) to 300(Ph-N) +20%Alternator I/P Range :
50-60 Hz at ratedAlternator I/P Frequency:
engine speed, Crank disconnect from 20V AC Ph-N
Short Circuit Protected transistorSolid State outputs :
open collector, Maximum Sink current 500mA
12V = 8V CF, 24V=16V CFCharge Fail :
-30 to 70 degree COperating Temp. Range :
Din Standard- 192mmX96mmX60mmEnclosure:
Cutout dimensions-186mm X 91mm
Generator Fail to Start
Alarm- 1
Alarm- 2
* Due to continuous product improvements specs. are subject to change without notice.
* Due to continuous product improvements specs. are subject to change without notice.
P 4/5, Information Technology Park
Old MIDC, Satara, 415 004, INDIA
Ph:- +91 2162 246821 / 29
Email- [email protected]
www.utopiacontrol.com
Automation & Control Pvt. Ltd
Authorised Dealer
BATTERY +VE
BATTERY -VE
BATTERY +VE
START
STOP / FUEL
HORN
MAINS CONTACTOR
GENERATOR CONTACTOR
EXTRA 1
EXTRA 2
EXTRA 3
EXTRA 4
CHARGING ALTERNATORWL/POINT / +D
C.T.1
C.T.2
C.T.3
AMMETERSELECTOR SWITCH
SEC.2
SEC.1
B 10
B 9
A 12
A 11
A 10
A 8
A 9
A 7
A 6
A 5
A 4
A 3
A 2
A 1C1
C2
C3
C12
C11
C4
C5
C6
C7
C8
C9
C10
GENERATOR NEUTRAL
NO CONNECTION
GENERATOR LINE
NO CONNECTION
NO CONNECTION
VOLTAGESELECTOR SWITCH
230V AC
GENERATOR
L1
L2
L3
LLOP
HCT
LOW FUEL
OVER LOAD
ALARM 1
ALARM 2
L 1
L 2
L 3
MAINS
LINE VOLTAGEMONITOR
BATTERY +VE
NO CONNECTION
NO CONNECTION
GCU 101
B1
B2B3
B4
B5
B6
B7
BATTERY +VE
BATTERY -VE
BATTERY +VE
START
STOP / FUEL
HORN
MAINS CONTACTOR
GENERATOR CONTACTOR
EXTRA 1
EXTRA 2
EXTRA 3
EXTRA 4
CHARGING ALTERNATORWL/POINT / +D
B 10
B 9
A 12
A 11
A 10
A 8
A 9
A 7
A 6
A 5
A 4
A 3
A 2
A 1C1
C2
C3
C12
C10
C4
C5
C6
C7
C8
C9
GENERATOR NEUTRAL
NO CONNECTION
GENERATOR LINE
NO CONNECTION
230V AC
LLOP
HCT
LOW FUEL
OVER LOAD
ALARM 1
ALARM 2
BATTERY +VE
NO CONNECTION
NO CONNECTION
GCU 101
B1
B2
B3
B4
B5
B6
B7
C.T (S1)
C.T (S2)NO CONNECTION B8
C11REMOTE
MAINS LINE
NO CONNECTION
MAINS NEUTRAL
230V AC
R1
R2
R3
R4
R5
R6
R7
R8
R9
3 Phase Connection Diagram-
1 Phase Connection Diagram-