General Specifications GX60 I/O Base Unit (Expandable I/O) GX90EX Expansion Module Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan GS 04L53B00-01EN GS 04L53B00-01EN ©Copyright April 2014 10th Edition May. 31, 2021 OVERVIEW GX60 I/O Base Unit (Expandable I/O) The GX60 provides a function to expand an I/O module for recording and controlling, when it is connected to the expansion module that is connected to the GX10/GX20/GP10/GP20/GM using a LAN cable via a private communication network. One GX60 can install up to six I/O modules. Up to six units can be additionally connected to the GX/GP/GM. The communication distance between the GX/ GP/GM and GX60 or between GX60s can be extended by up to 100 m using a LAN cable. * When the measurement mode on the GX/GP/ GM is High speed, expandable I/O units cannot be installed in the GX/GP/GM. GX90EX Expansion Module The expansion module is installed in the GX10/GX20/ GP10/GP20, GX60, GM main unit, and GM sub unit. [If GX90EX expansion module is installed in the GX/GP or I/O base unit] The expansion module, which is supported by the GX/GP and GX60, enables a connection between GX/GP and GX60 or a communication between GX60s. A distributed arrangement with the data time synchronization secured is provided by connecting Expansion modules installed in the GX/GP main unit and GX60 using a LAN cable. Data is transferred to the high-order GX/GP via the expansion module. [If GX90EX expansion module is installed in the GM main unit/sub unit] The expansion module, which is supported by the GM main unit and sub unit, enables a connection between GM main unit and sub unit or a communication between sub units. A distributed arrangement with the data time synchronization secured is provided by connecting Expansion modules installed in the GM main unit and sub unit using a LAN cable. Data is transferred to the high-order GM10 via the expansion module. GX90EX GX60 Power inlet type Power Screw type

General GX60 6SHFL¿FDWLRQV GX90EX Expansion ModuleGX90YA I/O Modules (GS 04L53B01-01EN) and GX90UT PID cControl Module (GS 04L53B01-31EN). Restrictions: Expansion module: 1 module

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • GeneralSpecifications

    GX60I/O Base Unit (Expandable I/O)GX90EXExpansion Module

    Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan

    GS 04L53B00-01EN

    GS 04L53B00-01EN©Copyright April 2014

    10th Edition May. 31, 2021

    OVERVIEWGX60 I/O Base Unit (Expandable I/O)The GX60 provides a function to expand an I/O module for recording and controlling, when it is connected to the expansion module that is connected to the GX10/GX20/GP10/GP20/GM using a LAN cable via a private communication network.

    ● OneGX60caninstalluptosixI/Omodules.● Uptosixunitscanbeadditionallyconnectedto

    the GX/GP/GM.● ThecommunicationdistancebetweentheGX/

    GP/GM and GX60 or between GX60s can be extendedbyupto100musingaLANcable.

    * WhenthemeasurementmodeontheGX/GP/GM is High speed, expandable I/O units cannot be installed in the GX/GP/GM.

    GX90EX Expansion ModuleThe expansion module is installed in the GX10/GX20/GP10/GP20, GX60, GM main unit, and GM sub unit.[IfGX90EXexpansionmoduleisinstalledintheGX/GPor I/O base unit]

    ● Theexpansionmodule,whichissupportedbythe GX/GP and GX60, enables a connection betweenGX/GPandGX60oracommunicationbetween GX60s.

    ● AdistributedarrangementwiththedatatimesynchronizationsecuredisprovidedbyconnectingExpansionmodulesinstalledintheGX/GPmainunitandGX60usingaLANcable.

    ● Dataistransferredtothehigh-orderGX/GPviatheexpansionmodule.

    [IfGX90EXexpansionmoduleisinstalledintheGMmainunit/subunit]

    ● Theexpansionmodule,whichissupportedbytheGMmainunitandsubunit,enablesaconnectionbetweenGMmainunitandsubunitoracommunicationbetweensubunits.

    ● AdistributedarrangementwiththedatatimesynchronizationsecuredisprovidedbyconnectingExpansionmodulesinstalledintheGMmainunitandsubunitusingaLANcable.

    ● Dataistransferredtothehigh-orderGM10viatheexpansionmodule.

    GX90EX

    GX60 Power inlet type

    Power Screw type

  • 2

    All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 31, 2021-00

    GX60 SPECIFICATIONSModule Installation

    • I/Omodule:Max.6modules(Slots0to5) Modules that can be installed PleaserefertotheGeneralSpecificationsofthe

    GX90XA/GX90XD/GX90YD/GX90WD/GX90XP/GX90YA I/O Modules (GS 04L53B01-01EN) and GX90UTPIDcControlModule(GS04L53B01-31EN).

    Restrictions:Expansionmodule:1module(expansion

    moduleslot“EXT”)Forotherlimitations,seetheGX10/GX20

    Paperless Recorder (Panel Mount Type) GeneralSpecifications(GS04L51B01-01EN).

    Names of Channels• ThemoduleinstalledintheGX60hasachannel

    namethatconsistsoftheunitnumber,slotnumber,andchannelnumber.

    012345

    Channel name

    Unit number

    Slot number

    Channel numberI/O modules

    Channel number; Analog input: 01 to 10 Digital input: 01 to 16 Digital output: 01 to 06Digital input/output: DI 01 to 08

    DO 09 to 14

    Slot number; 0 to 5Unit number; 1 to 6

    Pulse input: 01 to 10 Analog output: 01 to 04PID control, input/output: 01 to 26

    Safety and EMC Standards• CSA: CSA C22.2 No. 61010-1,

    CSA-C22.2 No. 61010-2-030, CAN/CSA-C22.2 No.61010-2-201 *4, OvervoltageCategoryII *1,PollutionDegree2 *2, MeasurementCategory *3

    • UL: UL 61010-1, UL Std. No. 61010-2-030, UL 61010-2-201 *4 (CSA NRTL/C),

    OvervoltageCategoryII *1,PollutionDegree2 *2, MeasurementCategory *3

    • CE/EMCdirective: EN 61326-1 Class A Table 2 (For use in

    industriallocations)compliant ENIEC61000-3-2compliant EN61000-3-3compliant EN55011ClassAGroup1compliant• CE/Lowvoltagedirective: EN 61010-1, EN 61010-2-030,

    EN IEC 61010-2-201 *4 compliant OvervoltageCategoryII *1,PollutionDegree2 *2,

    MeasurementCategory *3• EURoHSdirective:ENIEC63000• WEEEDirective:Compliant• EMCRegulatoryArrangementinAustraliaand

    NewZealand(RCM):EN55011ClassAGroup1compliant

    • KCmarking:KSC9811,KSC9610-6-2compliant*1 OvervoltageCategoryII: Describesanumberwhichdefinesatransient

    overvoltagecondition. Impliestheregulationforimpulsewithstand

    voltage. “II”appliestoelectricalequipmentwhich

    issuppliedfromthefixedinstallationlikeadistribution board.

    *2 PollutionDegree2: Describesthedegreetowhichasolid,liquid,

    or gas which deteriorates dielectric strength or surfaceresistivityisadhering.

    “2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.

    *3 MeasurementCategory: Dependsonthespecificationofeachmodules.*4 Thisproductisdesignedasopenequipment

    undertherelevantstandard,installitasfollows: • Install the GX60 in a panel with a door. •Theinstrumentationpanelorpanelusedfor

    supportmustcomplywithCSA/UL/EN61010-2-201ormustbeatleastIP1X(degreesofprotection) and at least IK09.

  • 3

    All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 31, 2021-00

    Construction• Frontpanel(terminal):Wateranddust-proof,

    ComplieswithIEC529-IP20• Material:Polycarbonate,aluminumalloy• Color;

    Bezel:Smokeblue(Munsell4.1PB6.0/4.5equivalent)

    • Dimensions:412.5mm(W)x164.7mm(H)x127.8mm(D)

    • Weight:Approx.3.2kg(installing6modules)

    Power Supply• Ratedsupplyvoltage:100to240VAC• Allowablepowersupplyvoltagerange:90to132,

    180to264VAC• Ratedpowersupplyfrequency:50/60Hz• Powerconsumption:

    Supply voltage Normal operation *

    Maximum

    100VAC 20VA 40VA

    240VAC 30VA 55VA

    * Whenusing6analoginputmodules.• Allowableinterruptiontime:Lessthan1cycleof

    thepowersupplyfrequency

    Isolation• Insulationresistance:Betweeneachinsulation

    terminals,andearth:20MΩorgreaterat500VDC

    • Withstandvoltage: Betweenthepowerterminalandearth:3000VACat50/60Hzforoneminute

    Betweentheinput/outputmodulesandearth:DependsonthespecificationofI/Omodule.

    • Grounding:Besuretosetalowgroundingresistance.

    • Isolation:

    Power terminal

    The circuits divided by lines are insulated mutually.

    Internal circuit

    Input and output module terminal

    Input and output module internal circuitEarth (PE) terminal

    External DimensionsPowerscrewterminaltype

    127.8 (5.03)

    148

    (5.8

    3)

    412.5 (16.2)162 (6.38)48 156 (6.14)

    164.

    7 (6

    .48)

    6-Φ5 hole(1.89)

    8.7

    (0.3

    4)

    (6-Φ0.2) hole

    Power inlet type

    127.8 (5.03)

    148

    (5.8

    3)

    412.5 (16.2)162 (6.38)48 156 (6.14)

    8.7

    (0.3

    4)

    164.

    7 (6

    .48)

    6-Φ5 hole(1.89)(6-Φ0.2) hole

    Withmodules

    147 (5.79)

    48(1.89)

    412.5 (16.2)162 (6.38)156 (6.14)

    6-Φ5 hole(6-Φ0.2) hole

    148

    (5.8

    3)

    164.

    7 (6

    .48)

    8.7

    (0.3

    4)

  • 4

    All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 31, 2021-00

    185±

    0.4

    (7.2

    8±0.

    0157

    )

    162±0.2(6.38±0.0078)

    156±0.2(6.14±0.0078)

    6-Φ4.5 hole or M4

    Dimensions of fixing hole

    (0.24-Φ0.18) hole or M4

    148±

    0.4

    (5.8

    3±0.

    0157

    )

    Unit: mm (approx. inch)Unless otherwise specified, tolerance is ±3% (however, tolerance is ±0.3 mm when below 10 mm).

    Normal Operating Conditions• Powersupplyvoltage:100to240VAC±10%• Powersupplyfrequency:50/60Hz±2%• Ambienttemperature:0to50°C• Ambienthumidity:20to80%RH(However,less

    thanmoisturecontentof40°C80%RHat40°Cormore),Nocondensation

    • Magneticfield:400A/morless(DCand50/60Hz)

    • Vibration: 5≤f<8.4Hzamplitude3.5mm(peak)

    8.4≤f≤160Hzacceleration9.8m/s2 or less• Shock(IEC-60068-2-27):

    Non-energization,500m/s2orless,approximate10ms,6directions(±X,±Y,±Z)

    • Mountingposition:Canbeinclinedupto30degreesbackward.Leftandrighthorizontalwheninstallingthepanelmountandwallmount.

    • Altitude:2000morless• Installationlocation:Indoors• Warm-uptime:Atleast30minutesafterpower

    on

    Transport and Storage Conditions• Ambienttemperature:–25to60°C• Ambienthumidity:5to95%RH(no

    condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged

    condition)

    Effects of Operating Conditions• Powersupplyvariation:Shallsatisfythe

    accuracyspecificationintherangeof90to132VACor180to250VAC(frequency:50/60Hz).Powersupplyfrequencyfluctuation:Shallsatisfytheaccuracyspecificationintherangeofratedsupplyfrequency+/-2Hz(power-supplyvoltage:100VAC).

    GX90EX SPECIFICATIONSCommunication Functions CommunicationbetweenGX/GPandGX60,

    betweenGX60s,betweenGMmainunitandsubunit,betweenGMsubunitsviadedicatedcommunicationnetwork.• Baudrate:10Base-T/100Base-TX(Auto)*1• Numberofports:2• Connectioncable:STPcable,CAT5orgreater• Inter-moduleconnection:Cascadeconnection

    (Ring connection is disabled.)• Maximumcommunicationdistance:100m*2• Connector:RJ-45*1Canbefixedto10Base-TbyDIPswitchsettings.*2DistanceextensionthroughHUBconnectionor

    LAN repeaters is not possible.

    Display Functions• SystemstatusLEDindicators: RDY(green):LightsupwhentheCPUisrunning

    normally. MAIN(green):Turnsoninmastermodeandoff

    inslavemode. FAIL(red):Lightsupwhenasystemerror

    occurs.• 7-segmentLEDindicator:Indicatesaunit

    numberoroperationerror.• EthernetstatusindicatorLED:LINKACT(green),

    SPEED(orange)

    Address Setting Functions Switchsettings:

    Switch No. Descriptions1 Forunitnumbersetting

    2

    3

    4

    5 -

    6 -

    7 10 Mpbs/100 Mbps switching

    8 MASTER/SLAVEswitching

    Master / Slave FunctionsCanbesettomastermode(wheninstalledintheGX/GPorGMmainunit),orslavemode(wheninstalledintheGX60orGMsubunit)usingtheDIPswitches.

    10 Mbps Fixed ModeCanbesettothe10MbpsfixedmodeusingtheDIPswitches.

    MountingCanbemountedintheGX/GP,GX60,GMmainunit,and GM sub unit.• Mountingposition: GX10/GP10:Slot2 GX20/GP20:Slot9 GX60:EXTslot GMmainunit:Leftmostposition GMsubunit:Nexttothepowersupplymodule

  • 5

    All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 31, 2021-00

    Safety and EMC Standards• CSA: CSA C22.2 No. 61010-1,

    OvervoltageCategoryIIorI *1,PollutionDegree2 *2• UL: UL 61010-1 (CSA NRTL/C),

    OvervoltageCategoryIIorI *1,PollutionDegree2 *2• CE/EMCdirective: EN 61326-1 Class A Table 2 (For use in

    industriallocations)compliant ENIEC61000-3-2compliant EN61000-3-3compliant EN55011ClassAGroup1compliant• CE/Lowvoltagedirective EN61010-1compliant,

    OvervoltageCategoryIIorI *1,PollutionDegree2 *2• EURoHSdirective:ENIEC63000• WEEEDirective:Compliant• EMCRegulatoryArrangementinAustraliaand

    NewZealand(RCM):EN55011ClassAGroup1compliant

    • KCmarking:KSC9811,KSC9610-6-2compliant*1 OvervoltageCategory: Describesanumberwhichdefinesatransient

    overvoltagecondition. Impliestheregulationforimpulsewithstand

    voltage. IIorIdependsonthepowersupplyspecification

    oftheGX/GPmainunit,GMmainunitorsubunit.*2 PollutionDegree2: Describesthedegreetowhichasolid,liquid,

    or gas which deteriorates dielectric strength or surfaceresistivityisadhering.

    “2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.

    Construction• Frontpanel(terminal):Wateranddust-proof,

    ComplieswithIEC529-IP20• Material:Polycarbonate• Color;

    Front:Charcoalgreylight(Munsell10B3.6/0.3equivalent) Bezel:Smokeblue(Munsell4.1PB6.0/4.5equivalent)

    • Dimensions:45.2mm(W)x111mm(H)x107.1mm(D)(D:includingterminalcover)

    • Weight:Approx.0.18kg

    Power Supply SuppyfromGX/GP,GX60expandableI/O,or

    GM90PSpowersupplymodule.• Powerconsumption:1.8Worless

    External DimensionsUnit: mm (approx. inch)

    45.2(1.78)

    107.

    1

    3(0.

    12)

    8(0.

    31)1

    00(3

    .94)

    31.9

    82.1

    (3.2

    3)Normal Operating Conditions

    Fornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):ThisGeneral

    SpecificationsGMSpecifications:GS04L55B01-01EN

    Transport and Storage Conditions• Ambienttemperature:–25to70°C• Ambienthumidity:5to95%RH(no

    condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged

    condition)

    Effects of Operating Conditions None

  • 6

    All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 31, 2021-00

    MODEL AND SUFFIX CODESMODEL and SUFFIX Code (GX60)

    Model Suffix Code DescriptionGX60 I/O Base UnitType -EX I/O ExpansionArea N GeneralPower supply 1 100VAC,240VACPower cord D Power cord UL/CSA standard

    F PowercordVDEstandardR Power cord AS standardQ Power cord BS standardH Power cord GB standardN Power cord NBR standardW Screwterminal(M3)

    *OneGX90EX(I/Oexpansionmodule)isprovided.MODEL and SUFFIX Code (GX90EX)

    Model Suffix Code DescriptionGX90EX I/O Expansion ModulePort -02 2 portsType -TP1 Twisted Pair Cable- N Always NArea -N General

    Standard AccessoriesProduct Qty

    Power cord 1*

    Stopper (Antiskid rubber) (A9088ZM) 2

    * ExceptGX60powercordsuffixcode:W

    Optional Accessories (Sold Separately)ThedummycoverisforemptyslotsonGX/GPandGX60.ThedummycoverisnotattachedtotheGX60whenshippedfromthefactory.Ifyouneedthedummycover,pleasepurchaseitseparately.

    Product Part no.Dummycover B8740CZ

    Test certificate (QIC, sold separately)When ordering the GX60, GX90EX gets its own QIC (one QIC per unit).Whenorderingtheexpansionmodulesseparately,eachmodulegetsitsownQIC(oneQICpermodule).

    User's ManualProductuser'smanualscanbedownloadedorviewedatthefollowingURL.Toviewtheuser'smanual,youneedtouseAdobeReader7orlaterbyAdobeSystems.URL: www.smartdacplus.com/manual/en/Trademarks TheTCP/IPsoftwareusedinthisproductandthedocumentforthatTCP/IPsoftwarearebasedinpartonBSDnetworkingsoftware,Release1licensedfromTheRegentsoftheUniversityofCalifornia.

    •SMARTDAC+isregisteredtrademarksofYokogawaElectricCorporation.•Microsoft,MSandWindowsareregisteredtrademarksofMicrosoftCorporationUSA.•PentiumareregisteredtrademarksofIntelCorporation.•ModbusisaregisteredtrademarkofAEGSchneider.•Othercompanyand/orproductnamesareregisteredtrademarkoftheirmanufactures.