Generator Protection PPT Turbo

Embed Size (px)

Citation preview

  • 8/13/2019 Generator Protection PPT Turbo

    1/29

    PROTECTION OF 60MW TURBO

    GENERATOR IN VSP

  • 8/13/2019 Generator Protection PPT Turbo

    2/29

    POWER SYSTEM PROTECTION

    The word 'protection' is generally used to

    describe the whole concept of protecting a power

    system.

    Power system protection is the process of

    making the production, transmission, and

    consumption of electrical energy as safe as

    possible from the effects of failures and events

    that lace the ower s stem at risk.

  • 8/13/2019 Generator Protection PPT Turbo

    3/29

    NECESSITY OF PROTECTION

    Three main effects of fault, that state the necessity of

    protection:

    It is likely to cause the individual generators in a

    power station, or groups of generators in different

    stations, to lose synchronism and fall out of step with

    consequent splitting of the system;

    A risk of damage to the affected plant; and

    A risk of damage to healthy plant.

  • 8/13/2019 Generator Protection PPT Turbo

    4/29

    BASIC REQUIRMENTS OF

    PROTECTION:

    Speed

    Selectivity

    Sensitivity

    Reliability

    Simplicity

    Economy

  • 8/13/2019 Generator Protection PPT Turbo

    5/29

    BASIC COMPONENTS OF

    PROTECTIONRelays

    Instrument Transformers

    Circuit breakers

    Tripping Batteries

  • 8/13/2019 Generator Protection PPT Turbo

    6/29

    -CIRCUIT BREAKER

    COMBINATION

  • 8/13/2019 Generator Protection PPT Turbo

    7/29

  • 8/13/2019 Generator Protection PPT Turbo

    8/29

    GENERATOR FAULTS

    Stator Faults

    Rotor Faults

    Faults Due To Mechanical Condition

    External Faults

  • 8/13/2019 Generator Protection PPT Turbo

    9/29

    GENERATOR DIFFERENTIAL

    PROTECTION

    For protection of stator windings against earth faults and phase to phase

    makes use of circulating current principle

    In this scheme of protection currents at the two ends of protected sections

    are compared

  • 8/13/2019 Generator Protection PPT Turbo

    10/29

    STATOR INTERTURN FAULT

    PROTECTIONInterturn faults occur in the stator slots, they quickly

    develop into faults to earth and are cleared by the stator earth

    fault protection

    There is,however,the possibility

    that they may occur at the winding

    ends and so cause extensive

    damage to the generator before the

    fault evolves to one detectable by

    other protection.

  • 8/13/2019 Generator Protection PPT Turbo

    11/29

    REVERSE POWER PROTECTION

    The motoring of the turbine output can be detected by

    reverse power protection relay which is powered by both

    C.T and P.Ts.

    To avoid false tripping due to power swings a time delay

    is incorporated before tripping signal is generated. If the

    unit trips on reverse power protection, the input power to

    the turbine is increased as quickly as possible.

  • 8/13/2019 Generator Protection PPT Turbo

    12/29

    AUTOMATIC FIELD

    SUPPRESSION

    In the event of fault on the

    turbo generator winding even

    if the generator C.B is tripped,

    the fault continues to be fed as

    long as long as excitation willexist because emf is induced in

    the generator itself.

    For the quick removal of fault during emergency, it is

    necessary to disconnect the field simultaneously with the

    disconnection of the generator

  • 8/13/2019 Generator Protection PPT Turbo

    13/29

    LOCAL BREAKER BACK UP

    PROTECTIONThe LBB protection is energized when the breaker trip

    is initiated after a suitable time interval if conformation of

    the breaker tripping from 3poles is not received

    The energized tripping signal from local breaker back up

    protection will trip all 220kv generator breakers and all

    220kv feeder breakers through bus bar protection.

  • 8/13/2019 Generator Protection PPT Turbo

    14/29

    STATOR EARTH FAULT

    PROTECTION

    If a faulty phase windingconnected to ground, the

    normal low neutral voltage

    could rise as high as line-to-

    neutral voltage dependingon the fault location

    The usual method of

    detection fault is bymeasuring the voltage

    across the secondary of

    neutral grounding

    transformer (NGT).

  • 8/13/2019 Generator Protection PPT Turbo

    15/29

    NEGATIVE SEQUENCE OR

    CURRENT UNBALANCE

    PROTECTIONWhen the machine

    delivering the equal currents

    in three phases, no unbalance

    are negative phase sequencecurrent is produced

    An alarm will annunciate at

    annunciation panel it negative

    sequence currents exceed a

    normal level

  • 8/13/2019 Generator Protection PPT Turbo

    16/29

    ROTOR EARTH FAULT

    PROTECTION

    The rotor earth faultmay be caused due toinsulation failure ofwinding or inter-turn

    fault followed by localheat.

    The protection schemeconsists of a highresistance connectedacross the rotor circuitand its mid point isgrounded through asensitive relay

  • 8/13/2019 Generator Protection PPT Turbo

    17/29

    OVER FLUXOR OVER

    EXCITATION PROTECTION

    This problem may occur in turbo generators that are

    connected to the grid if they experience generating voltage

    regulation problems

    It may also occur for units during start-up or

    resynchronizing following a trip.

    A specialized volts/hertz relay is used to detect this

    condition, and will trip the generator if excessive

    volts/hertz conditions are detected

  • 8/13/2019 Generator Protection PPT Turbo

    18/29

  • 8/13/2019 Generator Protection PPT Turbo

    19/29

    STATOR FRAME OVER HEATING

    PROTECTION

    For the protection of the turbo generator against any

    possible fire accident twelve fire detector relays are

    provided on either side of the stator winding

    The set of contacts will close when the temperature

    surrounding the fire relay exceeds 80OC. The other relay

    one when the temperature exceeds 100OC

    These contacts are wired to CO2fire extinguishing

    system

  • 8/13/2019 Generator Protection PPT Turbo

    20/29

    ABNORMAL FREQUENCY

    PROTECTIONThe abnormal over frequency on the machine may be

    due to improper speed control adjustment or disoperation

    of the speed controller or severe grid disturbance orsudden load thrown off.

    If the unit trips due to abnormal frequency protectionthen change the governor speed until machine reaches full

    speed. Even after 2to3 attempts the machine is running at

    lower speed, probably the governor of the turbine is faulty.

  • 8/13/2019 Generator Protection PPT Turbo

    21/29

    LOSS OF FIELD OR LOSS OF

    EXCITATION PROTECTION

    This fault is caused due to

    open circuit of field, short

    circuit of field, accidental

    tripping of field breaker, poorbrush contact

    The mho relay is placed which is designed to detect

    the change of impedance from the normal load valuemay therefore be used to provide protection against

    asynchronous operation resulting from the loss of

    excitation.

  • 8/13/2019 Generator Protection PPT Turbo

    22/29

    POLE SLIP PROTECTION

    A generator may lose

    synchronising with power

    system without failure of

    excitation system, becauseof severe fault disturbance

    or operation at a high load

    with leading power factor

    and hence a relatively weakfield

  • 8/13/2019 Generator Protection PPT Turbo

    23/29

    OVER SPEED PROTECTION

    Bearing over heating can be detected by a

    relay actuated by a thermometer-type bulb

    inserted in a hole in the bearing, or by a

    resistance-temperature-detector relay, such as

    used for stator over heating protection, with the

    detector embedded in the bearing

  • 8/13/2019 Generator Protection PPT Turbo

    24/29

    PROTECTION AGAINST

    VIBRATIONS

    A vibration detector may be mounted on one of

    the bearing pedestals in the case of a horizontal

    shaft generating set, or on the upper guide-

    bearing in case of a vertical shaft generating

    set. It may be set to trip the machine or initiate

    an alarm when the radial deflections of certain

    duration exceed a per-determined value.

  • 8/13/2019 Generator Protection PPT Turbo

    25/29

    BEARING OVER HEATING

    PROTECTION

    Bearing over heating can be detected by a

    relay actuated by a thermometer-type bulb

    inserted in a hole in the bearing, or by a

    resistance-temperature-detector relay, such as

    used for stator over heating protection, with the

    detector embedded in the bearing

  • 8/13/2019 Generator Protection PPT Turbo

    26/29

    ANTI MOTORING PROTECTION

    In the event of prime-mover failurethe generator continues to rotate as a

    synchronous motor drawing electrical

    power from the system and driving theprime mover.

    A single element directional powerrelay is used to sense (reverse power

    relay)the direction of power flow in any

    one phase.

  • 8/13/2019 Generator Protection PPT Turbo

    27/29

    CONCLUSION

    A generator is the most important and most costly equipmenentin a power system. It is subjected to more number of troubles

    than any other equipment.

    The basic function of protection applied to generators is

    therefore to reduce the outage period to a minimum by rapid

    discriminative clearance of faults.

    While selecting the scheme for generator protection, theprotection of complete unit and the stability of the system due to

    disturbance, in a generator should be considered in addition to

    protection of the generator itself.

  • 8/13/2019 Generator Protection PPT Turbo

    28/29

    QUERIES?

  • 8/13/2019 Generator Protection PPT Turbo

    29/29

    THANK YOU