Introduction Grounding Roadmaps Equipment & Rack Grounding Kits Common Bonding Network (CBN) Components Crimping Tools Technical Information Index S TRUCTURED G ROUND SYSTEM FOR DATA CENTER GROUNDING Table of Contents INTRODUCTION How to Use This Catalog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 The Purpose of Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 GROUNDING ROADMAPS Common Bonding Network (CBN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Service Entrance Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Data Center Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Data Center Rack Grounding (Raised Floor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Telecommunications Room Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Telecommunications Room Rack Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 EQUIPMENT & RACK GROUNDING KITS Features and Benefits — PANDUIT ® STRUCTUREDGROUND System for Data Center Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 Rack Grounding Strip Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Common Bonding Network (CBN) to Rack Jumper Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Equipment Jumper Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Paint Piercing Grounding Washer Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Electrostatic Discharge (ESD) Port Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Retrofit Rack Grounding Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Thread-Forming Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Bonding Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 COMMON BONDING NETWORK (CBN) COMPONENTS BICSI/J-STD-607-A Telecommunications Grounding Busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Telecommunications Grounding and Bonding Conductor Label Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Ring Terminal, Vinyl Expanded Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 Code Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17 Flex Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 Code/Flex Conductor HTAP Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Code/Flex Conductor HTAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Clear Covers for HTCT HTAPs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21 Grounding Clamp, U-Bolt, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 Grounding Clamp for Water Pipes, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 Grounding Rod Clamp, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 CRIMPING TOOLS Hand Operated Plier Type Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 CONTOUR CRIMP Controlled Cycle Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 Die Type, Manual Hydraulic, 14 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 CD-920 Crimping Dies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 TECHNICAL INFORMATION PANDUIT ® STRUCTUREDGROUND System for Data Center Grounding Application Standards . . . . . . . . . . . . . . .28 Specification Layout for Data Center Grounding per BICSI TDM Manual, 10th Edition . . . . . . . . . . . . . . . . . . . .29 Recommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE) per J-STD-607-A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 Recommended Cable Sizes for Grounding Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 Key Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 INDEX Part Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Related Catalogs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 1 S TRUCTURED G ROUND GROUNDING SYSTEM CATALOG WW - PCCB 04

Grounding Materials

Embed Size (px)

DESCRIPTION

Grounding-1

Citation preview

  • Introduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Table of ContentsINTRODUCTION

    How to Use This Catalog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2The Purpose of Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

    GROUNDING ROADMAPSCommon Bonding Network (CBN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Service Entrance Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Data Center Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Data Center Rack Grounding (Raised Floor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Telecommunications Room Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8Telecommunications Room Rack Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

    EQUIPMENT & RACK GROUNDING KITSFeatures and Benefits PANDUIT STRUCTUREDGROUND System

    for Data Center Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10Rack Grounding Strip Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Common Bonding Network (CBN) to Rack Jumper Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Equipment Jumper Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Paint Piercing Grounding Washer Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Electrostatic Discharge (ESD) Port Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Retrofit Rack Grounding Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Thread-Forming Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Bonding Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

    COMMON BONDING NETWORK (CBN) COMPONENTSBICSI/J-STD-607-A Telecommunications Grounding Busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Telecommunications Grounding and Bonding Conductor Label Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Ring Terminal, Vinyl Expanded Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Code Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17Flex Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18Code/Flex Conductor HTAP Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19Code/Flex Conductor HTAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20Clear Covers for HTCT HTAPs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21Grounding Clamp, U-Bolt, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22Grounding Clamp for Water Pipes, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23Grounding Rod Clamp, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

    CRIMPING TOOLSHand Operated Plier Type Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24CONTOUR CRIMP Controlled Cycle Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24Die Type, Manual Hydraulic, 14 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26CD-920 Crimping Dies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

    TECHNICAL INFORMATIONPANDUIT STRUCTUREDGROUND System for Data Center Grounding Application Standards . . . . . . . . . . . . . . .28Specification Layout for Data Center Grounding per BICSI TDM Manual, 10th Edition . . . . . . . . . . . . . . . . . . . .29Recommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE)

    per J-STD-607-A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Recommended Cable Sizes for Grounding Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Key Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

    INDEXPart Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31Related Catalogs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

    1

    STRUCTUREDGROUND GROUNDING SYSTEM C A T A L O G W W - P C C B 0 4

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    2

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    How to Use This Catalog

    Common Bonding Network (CBN)page 4

    Grounding Roadmapspages 5-9

    Detailed ProductInformationpages 11-23

    Technical Information Includes Application Standards and BICSI TDM Manual, 10th Editionpages 28-30

    Detailed ToolInformationpages 24-27

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    4

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    PANDUIT STRUCTUREDGROUND System for Data Center Grounding is a complete, highly reliable line of products to groundyour building and network equipment in compliance with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942,IEEE Std 1100 (IEEE Emerald Book), UL and CSA

    Common Bonding Network (CBN)

    TelecommunicationsRoom(see roadmap on page 8)

    Data Center(see roadmap on page 6)

    Service Entrance(see roadmap on page 5)

    See page 28 for PANDUIT STRUCTUREDGROUND System for Data Center Grounding Application Standards.For more data center grounding information, see www.panduit.com/dcgrounding.

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    6

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Data Center Grounding Roadmap

    Back of Racks Shown

    Telecommunications GroundingBusbar (TGB) and Busbar Label(see page 15)

    AC Panel*

    2

    2

    3

    3

    4

    1

    1

    5

    Raised Floor Pedestal

    Common Bonding Network (CBN)

    Building Steel

    Conduit

    TelecommunicationsBonding Backbone

    (TBB)

    Data Equipment Racks3

    Copper Compression, Two-Hole, LongBarrel with Window Lug: LCC-W (see pages 16-17)

    Copper Compression HTAP and Clear Cover: HTWC(see page 19)

    Bronze, U-Bolt Grounding Clamp: GPL(see page 22)2

    3

    1 4

    Telecommunications Grounding and BondingConductor Label Kit: LTYK(see page 15)

    5

    *AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturers specifications.A typical raised floor includes a multitude of metallic components which are connected together. It is the responsibility of the manufacturer and installer of theraised floor to insure all the raised floor metallic components are bonded which means that they are connected together electrically in accordance withapplicable specifications. The PANDUIT Bonding/Grounding System does not insure required bonding of the raised floor metallic components.

    Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), ULand CSA

    Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity betweenmetallic components and the grounded rack

    Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet membersto the rack grounding strip

    7For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Data Center Rack Grounding (Raised Floor)

    Back of Rack Shown

    Common Bonding Network (CBN) toRack Jumper Kit: RGCBNJ(see page 11)

    Common Bonding Network typically #2 AWGbare copper code conductor is used underfloor

    Equipment Jumper Kit 24" L, 90 Bent: RGEJ(see page 12)

    Equipment Jumper Kit 36" L, 90 Bent: RGEJ(see page 12)

    Equipment Jumper Kit 24" L, 45 Bent: RGEJ(see page 12)

    Electrostatic Discharge (ESD)Port Kit recommended foruse on front and back of rack:RGESD (see page 13)

    Rack Grounding Strip Kit: RGS(see page 11)

    Bonding Screws are used tomount patch panels to the front ofthe rack: RGTBS (see page 14)

    Paint Piercing GroundingWasher Kit: RGW(see page 13)

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    20

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Code/Flex Conductor HTAP

    Used to tap into continuous conductors as asplice or pigtailing

    Each HTAP terminates a wide range ofconductor sizes and combinations of codeand flex conductors Class G, H, I andLocomotive to suit a variety of applications

    Slotted design allows quick and easyassembly of conductor to HTAP using 3PANDUIT 94 V-0 cable ties included

    Tap grooves are separated from one anotherallowing them to function independently soHTAP can be used with a single or multipletaps providing maximum design andinstallation flexibility

    Color coded and marked with PANDUIT dieindex numbers for proper crimp die selection

    Requires crimping tools and dies, see pages25, 26 and 27

    UL Listed and CSA Certified for applicationsup to 600V when crimped with PANDUITand specified competitor crimping tools andPANDUIT crimping dies

    Tin plated to inhibit corrosion

    For additional sizes and configurations and to see the complete line of PAN-LUG Power and Grounding Connectors, see the Termination Solutions Catalog SA-TMCB02.

    For Making Parallel and Multiple Tap Connections on Code and Flex Conductors

    HTAP

    TAP

    RUN

    Part Number

    Copper Conductor Size RangeFigure

    Dimensions (In.)PANDUITCrimping

    Tool

    PANDUITDie Color& Die No.

    WireStrip

    Length(In.)

    Std.Pkg.Qty.

    WireStrandType Run Tap 1 Tap 2 Tap 3 L W H

    HTCT6-6-1Code #6 - #10AWG

    #6 - #14AWG

    .61 .40 .99 CT-930, CT-2931 Orange,PH6

    11/16 1

    Flex#6 - #10

    AWG#6 - #14

    AWGHTCT2-2-1

    Code#2 - #6AWG

    STR/SOL

    #2 - #6 AWGSTR/SOL

    #8 - #14AWG

    #8 - #14AWG

    .76 .61 1.55 CT-930, CT-2931 Brown,PH2

    13/16 1

    Flex#2 - #8AWG

    #2 - #8 AWG #8 - #14AWG

    #8 - #14AWG

    HTCT250-2-1Code 250 kcmil -#2 AWG

    #2 - #6 AWGSTR/SOL

    #8 - #14AWG

    .92 .96 1.92 CT-930, CT-2931 Purple,PH25

    1 1

    Flex4/0 - #2AWG

    #2 - #8 AWG #8 - #14AWG

    HTCT250-250-1Code 250 kcmil -#2 AWG

    250 kcmil -#2 AWG

    .90 .89 1.92 CT-930, CT-2931 Purple,PH25

    1 1

    Flex4/0 - #2AWG

    4/0 - #2AWG

    TAP 1

    RUN

    H

    WL

    WRUN

    TAP 1TAP 2

    TAP 3

    L

    H

    W LRUN

    H

    TAP 1 TAP 2 TAP 1

    W L

    H

    RUN

    HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    26

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool Two stage rapid advance hydraulic system minimizes

    cycle time Provides UL Listed and CSA Certified connections on

    PANDUIT PAN-LUG copper and aluminum lugs andsplices and copper taps

    Open "C-Head" design allows easy loading of crimpingdies and connectors, saves time

    Rubber boot on crimp head provides abrasion protection Ram automatically retracts when crimp cycle is complete

    Tool provided with two, high capacity 12 VDC rechargeablenickel-metal hydride batteries provides for continuousoperation and eliminates "memory" build-up, one hourcharge time

    Eight second crimp cycle time provides quick terminations,saves time

    Uses industry standard Makita* batteries and charger industry proven reliability easy to obtain from localretail sources

    Requires crimping dies, see page 27 Dies installed using spring loaded die retention pins no

    need for tools Crimp head rotates 360 degrees provides versatility for

    use in restricted spaces

    For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.*Makita is a registered trademark of Makita Corporation in the United States.

    Part Number Part Description

    Std.Pkg.Qty.

    CT-2931 Terminates PANDUIT PAN-LUG Compression Connectors:

    Copper compression lugs and splices for #8 AWG 750 kcmil code conductor Copper compression lugs and splices for #8 AWG 600 kcmil flex conductor Copper compression CTAPF taps for #10 AWG 3/0 AWG code conductor Copper compression CTAP taps for #8 AWG 4/0 AWG code conductor Copper compression HTCT taps for #14 AWG 250 kcmil code conductor, #14 AWG 4/0 AWG flex conductor Aluminum compression lugs and splices for #6 AWG 600 kcmil code conductor Aluminum compression HTAPS for #14 AWG 500 kcmil code conductor PANDUIT PAN-TERM Tubular Terminals for #8 AWG 250 kcmil code conductor

    Warranty: 3 years

    CT-2931 includes: Tool Two 12 VDC, rechargeable NiMH batteries One battery charger Steel tool case with storage for batteries, charger and crimp dies

    1

  • 3For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    What are the effects of improper grounding?

    Decreased Efficiency Electrical noise is introduced on data cables when surges are not properly dissipated by the grounding system.They cause

    faulty data signals and dropped packets, thus decreasing the throughput and overall efficiency of your network.

    Lower Reliability According to insurance industry data, improper grounding of communication systems leads to $500 million per year of

    damage to property and/or equipment due to lightning. (1)

    The Information Technology Industry Council states that grounding is the single-most important factor in reliable networkequipment performance. (2)

    More than 90% of problems in data communications equipment, including reboot, lockup, and data corruption, aretraced to problems with grounding. (3)

    Industry experts estimate that 27%-33% of damaged equipment in a user's facility is caused by electrostatic discharge.The component cost of repairing damaged equipment is substantial for complex circuit boards, especially when laborand downtime are considered. (4)

    According to the IEEE, the typical AC third prong ground is almost never sufficient to prevent damage to network equipment. (5)

    Safety Risks Personal injury from electric shock caused by improper grounding can cause immeasurable human suffering and

    significant expense. Potential fire hazards exist when heat is generated from electrical surges that find a high resistance path to ground.

    Can you afford improper grounding?

    Network equipment, such as switches, routers and storage devices, costs anywhere from thousands of dollars to hundreds ofthousands of dollars.The cost of proper grounding is only a tiny fraction of the cost of the equipment it is protecting.

    Clearly the biggest cost of improper grounding is the inability to service customers properly.

    PANDUIT STRUCTUREDGROUND System for Data Center Grounding gives you what you need to properly protectyour investment.

    TThhee PPuurrppoossee ooff GGrroouunnddiinnggThe grounding system is not just an insurance policy against a lightning strike. It is an active,functioning system that provides protection for personnel and equipment. Proper grounding isessential for efficient network performance.

    The purpose of the grounding system is to create a low impedance path to earth ground for electricalsurges and transient voltages. Lightning, fault currents, circuit switching (motors turning on and off),and electrostatic discharge are the common causes of these surges and transient voltages. Aneffective grounding system minimizes the detrimental effects of these electrical surges.

    A properly designed grounding system is one that is intentional, visually verifiable, adequately sizedto handle expected currents safely, and one that directs these potentially damaging currents awayfrom sensitive communication equipment. Any metallic component that is part of the data centerinfrastructure (such as equipment, racks, ladder racks, enclosures, cable trays, etc.) must be bondedto the grounding system.

    1. Mike Holt, "Prevent Shocks in Your Communications: Understanding How the NEC Relies on Ground Resistance Theory Leads to aSuccessful Application of Communications Grounding," Electrical Construction & Maintenance, September 2002.

    2. Information Technology Industry Council (ITI, formerly CBEMA), Guidelines for Grounding Information Technology Equipment. InformationLetter, ITI, 15 February 1997.

    3. Donald G. Pennington and Paul Holzer, "Doing Battle with Those Ground Transients," Electronic Engineering Times, 8 January 1996.4. ESDA, "Fundamentals of ESD: Part 1 An Introduction to ESD," 2001, (1 October 2004).5. Institute of Electrical and Electronics Engineers, Inc., IEEE Recommended Practice for Powering and Grounding Electronic Equipment, IEEE

    Std 1100-1999, 1999.

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    4

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    PANDUIT STRUCTUREDGROUND System for Data Center Grounding is a complete, highly reliable line of products to groundyour building and network equipment in compliance with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942,IEEE Std 1100 (IEEE Emerald Book), UL and CSA

    Common Bonding Network (CBN)

    TelecommunicationsRoom(see roadmap on page 8)

    Data Center(see roadmap on page 6)

    Service Entrance(see roadmap on page 5)

    See page 28 for PANDUIT STRUCTUREDGROUND System for Data Center Grounding Application Standards.For more data center grounding information, see www.panduit.com/dcgrounding.

  • 5For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Copper Compression, Two-Hole, LongBarrel with Window Lug: LCC-W (see pages 16-17)

    Copper Compression HTAP and Clear Cover: HTWC(see page 19)

    Service Entrance Grounding Roadmap

    Bronze, U-Bolt Grounding Clamp: GPL(see page 22) connected by a cable to

    (HTAP)2

    Bronze, Water Pipe Grounding Clamp: KP(see page 23)

    3

    4

    1

    1

    2

    AC Service Entrance

    Earth Ground

    3

    3

    3

    2

    1

    6

    3

    Telecommunications BondingBackbone (TBB)**

    Grounding Equalizer (GE)

    Cable Entrance

    AC Panel*

    Water Meter4 4

    Complies with J-STD-607-A and IEEE Std 1100 (IEEE Emerald Book) Grounding Equalizer (GE) is required when two or more Telecommunications Bonding Backbones (TBB) are used within a

    multi-story building; bond TBBs together with a GE at the top floor and at a minimum of every third floor in between

    Telecommunications Grounding and BondingConductor Label Kit: LTYK(see page 15)

    5

    5

    Telecommunications MainGrounding Busbar (TMGB) andBusbar Label (see page 15)

    7

    7

    Bronze, Grounding Rod Clamp: WB(see page 23) connected by a cable to

    (U-Bolt Grounding Clamp)

    6

    Conduit

    *AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturers specifications.**Specification J-STD-607-A specifies different size conductors based on the length of the Telecommunications Bonding Backbone (TBB). See page 30 forRecommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE) Per J-STD-607-A.

    2

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    6

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Data Center Grounding Roadmap

    Back of Racks Shown

    Telecommunications GroundingBusbar (TGB) and Busbar Label(see page 15)

    AC Panel*

    2

    2

    3

    3

    4

    1

    1

    5

    Raised Floor Pedestal

    Common Bonding Network (CBN)

    Building Steel

    Conduit

    TelecommunicationsBonding Backbone

    (TBB)

    Data Equipment Racks3

    Copper Compression, Two-Hole, LongBarrel with Window Lug: LCC-W (see pages 16-17)

    Copper Compression HTAP and Clear Cover: HTWC(see page 19)

    Bronze, U-Bolt Grounding Clamp: GPL(see page 22)2

    3

    1 4

    Telecommunications Grounding and BondingConductor Label Kit: LTYK(see page 15)

    5

    *AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturers specifications.A typical raised floor includes a multitude of metallic components which are connected together. It is the responsibility of the manufacturer and installer of theraised floor to insure all the raised floor metallic components are bonded which means that they are connected together electrically in accordance withapplicable specifications. The PANDUIT Bonding/Grounding System does not insure required bonding of the raised floor metallic components.

    Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), ULand CSA

    Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity betweenmetallic components and the grounded rack

    Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet membersto the rack grounding strip

  • 7For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Data Center Rack Grounding (Raised Floor)

    Back of Rack Shown

    Common Bonding Network (CBN) toRack Jumper Kit: RGCBNJ(see page 11)

    Common Bonding Network typically #2 AWGbare copper code conductor is used underfloor

    Equipment Jumper Kit 24" L, 90 Bent: RGEJ(see page 12)

    Equipment Jumper Kit 36" L, 90 Bent: RGEJ(see page 12)

    Equipment Jumper Kit 24" L, 45 Bent: RGEJ(see page 12)

    Electrostatic Discharge (ESD)Port Kit recommended foruse on front and back of rack:RGESD (see page 13)

    Rack Grounding Strip Kit: RGS(see page 11)

    Bonding Screws are used tomount patch panels to the front ofthe rack: RGTBS (see page 14)

    Paint Piercing GroundingWasher Kit: RGW(see page 13)

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    8

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Telecommunications Room Grounding Roadmap

    2

    1

    1

    Building Steel

    3

    3

    5

    Grounding Equalizer (GE)

    Conduit

    AC Panel*

    Back of Racks Shown

    Telecommunications GroundingBusbar (TGB) and Busbar Label(see page 15)

    Copper Compression, Two-Hole, LongBarrel with Window Lug: LCC-W (see pages 16-17)

    Copper Compression HTAP and Clear Cover: HTWC(see page 19)

    Bronze, U-Bolt Grounding Clamp: GPL(see page 22)2

    3

    1 4

    Telecommunications Grounding and BondingConductor Label Kit: LTYK(see page 15)

    5

    *AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturers specifications.A typical overhead cabling system includes a multitude of metallic components which are connected together. It is the responsibility of the installer to insure allof the metallic components are bonded, which means that they are connected together electrically in accordance with applicable specifications. The PANDUITBonding/Grounding System does not insure required bonding of the overhead cabling system metallic components.

    3

    4

    TelecommunicationsBonding Backbone

    (TBB)

    Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), ULand CSA

    Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity betweenmetallic components and the grounded rack

    Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet membersto the rack grounding strip

    1

  • 9For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Telecommunications Room Rack Grounding

    Aisle Ground typically #2 AWG insulated copper codeconductor is used overhead

    Back of Rack Shown

    Common Bonding Network (CBN) toRack Jumper Kit: RGCBNJ(see page 11)

    Equipment Jumper Kit 24" L, 90 Bent: RGEJ(see page 12)

    Equipment Jumper Kit 36" L, 90 Bent: RGEJ(see page 12)

    Equipment Jumper Kit 24" L, 45 Bent: RGEJ(see page 12)

    Electrostatic Discharge (ESD)Port Kit recommended foruse on front and back of rack:RGESD (see page 13)

    Rack Grounding Strip Kit: RGS(see page 11)

    Bonding Screws are used tomount patch panels to the front ofthe rack: RGTBS (see page 14)

    Paint Piercing GroundingWasher Kit: RGW(see page 13)

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    10

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Rack Grounding Strip is made from highconductivity, low resistance wrought copperand tin plated to inhibit corrosion, providing

    the lowest impedance path to ground

    Jumper has UL, VW-1 flame rated greeninsulation and is factory terminated withcopper compression, two-hole, long barrelwith window lug; lug is UL Listed, CSACertified and meets NEBS Level 3 with a singlestud hole and slot which allows mounting for" to 5/8" hole spacing and accommodatesstud sizes ", #12 and 6mm

    Paint Piercing Grounding Washer ismade from hardened steel and electro zinc plated which inhibits corrosion to provide asuperior bond between frame members onbolt-together racks

    Thread-Forming Screws are made fromelectro zinc plated steel and provide a bond tothe rack by removing paint from threadedholes without creating metal shavings

    Electrostatic Discharge (ESD) Port is madefrom high conductivity, low resistance copperand tin plated to inhibit corrosion plus itfunctions as an ESD wrist strap hanger

    Electrostatic Discharge (ESD) ProtectionSticker is provided in black and yellow forhigh visibility and easy identification as anESD port

    Copper Compression HTAP is UL Listed andCSA Certified; used to make a highly reliable,permanent bond between the commonbonding network and common bondingnetwork (CBN) to rack jumper kit

    Features and Benefits PANDUIT STRUCTUREDGROUND System for DataCenter GroundingPANDUIT offers a variety of kits with premium components to ensure superior grounding with the highest reliability available. Provides highest reliability with an all-copper rack

    grounding system to maintain data center systemperformance and protect network equipment

    Complies with data center standard TIA-942 and is UL Listed and CSA Certified

    Incorporates a flexible design that can be used withracks which meet EIA-310-D

    Offers ease of installation no paint scraping required to bond racks; factory terminated jumpers simplybolt in place

    ElectrostaticDischarge (ESD)Port Kit(see page 13)

    RackGroundingStrip Kit(see page 11)

    Common Bonding Network (CBN)to Rack Jumper Kit (see page 11)

    Equipment Jumper Kit(see page 12)

    A

    B

    C

    D

    E

    F

    G

    C

    C

    C

    A

    C

    C

    D

    E

    F

    B

    G

    BD

    D

  • 11For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Equipment & Rack Grounding Kits

    Rack Grounding Strip Kits Bonds up to 44 RU per rack EIA Universal mounting hole pattern

    Common Bonding Network (CBN) to Rack Jumper Kit Bonds the rack grounding strip to the CBN HTAP, included in kit, requires crimping tool and die; see

    the CT-930 crimping tool on page 25, the CT-2931 crimp-ing tool on page 26 and the CD-930H-250 crimping die onpage 27

    HTAP is UL Listed and CSA Certified for applications up to600V when crimped with PANDUIT and specifiedcompetitor crimping tools and PANDUIT crimping dies;see the Termination Solutions Catalog SA-TMCB02 for thecomplete line of PANDUIT crimping tools

    *An equal number of M6 x 12mm thread-forming screws also provided in each kit.**HTAP also sold separately, see page 20.

    *An equal number of M6 x 12mm thread-forming screws also provided in each kit.

    Part Number Part Description

    Std.Pkg.Qty.

    RGS134-1 Rack grounding strip; 78.65" length; .67" width; .05" thickness;provided with .16 oz (5cc) of antioxidant and three #12-24 x 1/2"thread-forming screws*

    1

    RGS134-10-1 10 rack grounding strips; 78.65" length; .67" width; .05" thickness;provided with .16 oz (5cc) of antioxidant and 30 #12-24 x 1/2"thread-forming screws*

    1

    Part Number Part Description

    Std.Pkg.Qty.

    Std.Ctn.Qty.

    RGCBNJ660P #6 AWG jumper; 60" length; 45 bent lug on grounding strip side;provided with .16 oz (5cc) of antioxidant, two #12-24 x 1/2"thread-forming screws* and a copper compression HTAP** forconnecting to the CBN in sizes ranging from #2 AWG to 250 kcmil

    1 10

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    12

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    3" or smaller

    Equipment Jumper Kits

    Bonds network equipment to rack grounding strip Jumper kit available with both ends factory terminated to

    provide a bolt on solution Jumper kit available with one end factory terminated to

    attach to the rack grounding strip; free end accommodatesunique equipment terminations

    Use jumpers with 90 bent lug, on grounding strip side, forhigh density grounding requirements up to one groundpoint per RU

    Use jumpers with 45 bent lugs, on grounding strip side, forimproved cable management

    Use 24" jumpers when network equipment ground point islocated near the grounding strip side of the rack

    Use 36" jumpers when network equipment ground point islocated away from the grounding strip side of the rack

    RGEJ1024PF

    3" or larger

    RGEJ1057PF

    Select equipment jumpers with 45 lugsfor lower density applications or shallowdepth equipment to provide improved cablemanagement.

    Select 24" equipment jumpers with 90lugs when equipment grounding connectionis close to the grounding strip.

    Select 36" equipment jumpers with 90 lugswhen equipment grounding connection is onthe opposite side from the grounding strip.

    How to Select the Appropriate Equipment Jumper

    *An equal number of M6 x 12mm thread-forming screws also provided in each kit.

    Part Number Part Description

    Std.Pkg.Qty.

    Std.Ctn.Qty.

    #10 AWG equipment jumpers factory terminated on both endsRGEJ1024PH #10 AWG jumper; 24" length; 45 bent lug on grounding strip side

    to straight lug on equipment; provided with .16 oz (5cc) ofantioxidant and four #12-24 x 1/2" thread-forming screws*

    1 10

    RGEJ1024PF #10 AWG jumper; 24" length; 90 bent lug on grounding strip sideto straight lug on equipment; provided with .16 oz (5cc) ofantioxidant and four #12-24 x 1/2" thread-forming screws*

    1 10

    RGEJ1036PF #10 AWG jumper; 36" length; 90 bent lug on grounding strip sideto straight lug on equipment; provided with .16 oz (5cc) ofantioxidant and four #12-24 x 1/2" thread-forming screws*

    1 10

    #6 AWG equipment jumpers factory terminated on both endsRGEJ624PH #6 AWG jumper; 24" length; 45 bent lug on grounding strip side to

    straight lug on equipment; provided with .16 oz (5cc) of antioxidantand four #12-24 x 1/2" thread-forming screws*

    1 10

    RGEJ624PF #6 AWG jumper; 24" length; 90 bent lug on grounding strip side tostraight lug on equipment; provided with .16 oz (5cc) of antioxidantand four #12-24 x 1/2" thread-forming screws*

    1 10

    RGEJ636PF #6 AWG jumper; 36" length; 90 bent lug on grounding strip side tostraight lug on equipment; provided with .16 oz (5cc) of antioxidantand four #12-24 x 1/2" thread-forming screws*

    1 10

    #10 AWG equipment jumper factory terminated on one endRGEJ1057PF #10 AWG jumper; 57" length; 90 bent lug on grounding strip side;

    provided with .16 oz (5cc) of antioxidant and two #12-24 x 1/2"thread-forming screws*

    1 10

    #6 AWG equipment jumper factory terminated on one endRGEJ657PF #6 AWG jumper; 57" length; 90 bent lug on grounding strip side;

    provided with .16 oz (5cc) of antioxidant and two #12-24 x 1/2"thread-forming screws*

    1 10

  • 13For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingSTRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Electrostatic Discharge (ESD) Port Kit Accommodates standard ESD wrist strap 4mm plug Can be mounted to front or back of rack for

    convenient access

    Bent 45, acts as a hook to hold wrist strap Barrel permanently marked with the protective earth

    (ground) symbol

    Paint Piercing Grounding Washer Kits Bonds frame members on bolt-together racks No paint scraping required

    Green color coding to indicate bonding application

    Contact your local electrical distributor for their selection of Electrostatic Discharge (ESD) wrist straps.*One M6 x 12mm thread-forming screw also provided in each kit.ESD port must be attached to a grounded member.

    Part Number Part Description

    Std.Pkg.Qty.

    RGW-12-1 12 paint piercing bonding washers for 3/8" stud size; .875 O.D.; providedwith .16 oz (5cc) of antioxidant; for use with standard equipment racks:CMR19X84, CMR19X84S and CMR23X84

    1

    RGW-32-1 32 paint piercing bonding washers for 3/8" stud size; .875 O.D.; providedwith .16 oz (5cc) of antioxidant; for use with 4 post rack NF4PR84 anddata rack DR84

    1

    RGW-100-1 100 paint piercing bonding washers for 3/8" stud size; .875 O.D.; providedwith .16 oz (5cc) of antioxidant

    1

    Part Number Part Description

    Std.Pkg.Qty.

    RGESD-1 ESD port kit; provided with an ESD protection sticker, .16 oz (5cc) ofantioxidant and one #12-24 x 1/2" thread-forming screw*

    1

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    14

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Thread-Forming Screws Thread-forming, provides a bond to the rack by removing

    paint from threaded holes without creating metal shavings Easily installed with 5/16" socket head wrench or flat

    blade screwdriver

    Retrofit Rack Grounding Kits Provides a dedicated ground system to maintain system

    performance and protect network equipment when RGSrack grounding strip kit cannot be used (see page 11)

    Optimized for installation on 19" racks that meet EIA-310-D,with functioning equipment, and are deployed in the field

    Provides a complete system of matched components thatcan be easily selected to save cost and labor

    remove paint from the rack

    RGRKCBNJEJ RGRKCBNJ

    NetworkEquipment

    HTAP(seepage 20)

    RackGroundingBusbarRGRB19

    Lug(see pages16-18)

    RackGroundingKitRGRKCBNJEJ

    Rack Grounding KitRGRKCBNJ

    GroundingJumperRGREJ696orRGREJ1096

    GroundingJumperRGREJ696

    Part Number Part Description

    Std.Pkg.Qty.

    Std.Ctn.Qty.

    RGRKCBNJEJ Rack grounding kit to ground the rack and one piece of equipment;includes one RGRB19 busbar, one HTCT250-2-1 HTAP and twoRGREJ696 grounding jumpers

    1 10

    RGRKCBNJ Rack grounding kit to ground the rack; includes one RGRB19busbar, one HTCT250-2-1 HTAP and one RGREJ696grounding jumper

    1 10

    RGRB19 Rack grounding busbar; can be positioned anywhere on the rack;19" length; tin plated; 14 holes arranged for flexibility in mounting;mounting hole sets have 1/2" spacing; provided with two#12-24 x 1/2" thread-forming screws* for mounting

    1 10

    RGREJ696 Grounding jumper; #6 AWG; 96" length; one end factoryterminated to lug; provided with .16 oz (5cc) of antioxidant and four#12-24 x 1/2" thread-forming screws* and other mounting hardwareas appropriate

    1 10

    RGREJ1096 Grounding jumper; #10 AWG; 96" length; one end factoryterminated to lug; provided with .16 oz (5cc) of antioxidant and four#12-24 x 1/2" thread-forming screws* and other mounting hardwareas appropriate

    1 10

    Part Number Part Description

    Std.Pkg.Qty.

    RGTS-C Thread-forming grounding screw, #12-24 x 1/2" 100RGTSM6-C Thread-forming grounding screw, M6 x 12mm 100

    Bonding Screws Creates an electrical bond between painted patch panels

    and racks Serrations on bottom of screw remove paint from patch

    panel, thus providing metal-to-metal contact

    Thread-forming, provides a bond to the rack by removingpaint from threaded holes without creating metal shavings

    Easily installed with Phillips screwdriver

    Part Number Part Description

    Std.Pkg.Qty.

    RGTBS-C Thread-forming bonding screw, #12-24 x 1/2" 100RGTBSM6-C Thread-forming bonding screw, M6 x 15mm 100

    *An equal number of M6 x 12mm thread-forming screws also provided in each kit.

    Thread-forming screws eliminate the need to manually

  • 15For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingSTRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    BICSI/J-STD-607-A Telecommunications Grounding Busbars

    Common Bonding Network (CBN) ComponentsULRC US

    Meets BICSI and J-STD-607-A requirements for networksystems grounding applications

    Made of high conductivity copper and tin plated toinhibit corrosion

    Comes pre-assembled with brackets and insulatorsattached for quick installation

    Use PANDUIT self-laminating laser/ink jet labels to identifybusbars to meet TIA/EIA-606-A

    TGB

    TMGB

    C200X100FJJ

    For additional label sizes, materials and print technologies and to see the complete line of PANDUIT identificationproducts, see the Identification Solutions Catalog SA-IDCB16.*Busbar labels sold separately.

    Part Number Bar Size

    No. of 5/16"hole sets,

    5/8" spacing

    No. of 7/16"hole sets,1" spacing

    Can Be ClearlyIdentified with PANDUIT

    Laser/Ink Jet Label*

    Std.Pkg.Qty.

    Telecommunications Grounding Busbars (TGB)GB2B0304TPI-1 1/4" x 2" x 10" 4 3

    C200X100FJJ1

    GB2B0306TPI-1 1/4" x 2" x 12" 6 3 1GB2B0312TPI-1 1/4" x 2" x 20" 12 3 1Telecommunications Main Grounding Busbars (TMGB)GB4B0612TPI-1 1/4" x 4" x 12" 12 6 C200X100FJJ 1GB4B0624TPI-1 1/4" x 4" x 20" 24 6 1

    Telecommunications Grounding and Bonding Conductor Label Kit

    For additional label sizes, materials and print technologies and to see the complete line of PANDUIT identificationproducts, see the Identification Solutions Catalog SA-IDCB16.

    Meets labeling requirements of J-STD-607-A; eachtelecommunications grounding and bonding conductor shallbe labeled as close as practicable to its point of termination ina readable position

    Can be applied as a wrap-around marker (parallel to cable) orflag marker (45 or 90) to cable

    Kit includes everything needed to properly label cables; oneflame retardant cable tie and one rigid plastic yellow tagprinted with IF THIS CONNECTOR OR CABLE IS LOOSEOR MUST BE REMOVED, PLEASE CALL THE BUILDINGTELECOMMUNICATIONS MANAGER

    Part Number Part Description

    Std.Pkg.Qty.

    LTYK Label kit includes printed tag and one flame retardant cable tie 10

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    16

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    For Use with Stranded Copper Conductors

    Code Conductor, Two-Hole, Long Barrel with Window Lug

    Meets J-STD-607-A requirements fornetwork systems grounding applications

    Tested by Telcordia meets NEBSLevel 3

    Requires crimping tools and dies, seepages 24, 25, 26 and 27

    UL Listed for use up to 35KV**, temperaturerated 90C and CSA Certified to 600V whencrimped with PANDUIT and specifiedcompetitor crimping tools and dies

    UL Listed and CSA Certified for wirerange-taking capability when crimped withPANDUIT UNI-DIE dieless crimping tools

    Color coded barrels marked with PANDUITand specified competitor die index numbersfor proper crimp die selection

    Long barrel maximizes number of crimpsand provides premium wire pull-out strengthand electrical performance

    Inspection window to visually assure fullconductor insertion

    Tin plated to inhibit corrosion Available with NEMA hole sizes and spacing

    Ring Terminal, Vinyl Expanded Insulation Expanded wire entry allows for large O.D. wire insulation or

    multiple wire crimps within one wire barrel Industry standard color coding to indicate wire range

    Brazed seam assures a reliable crimp Insulation support Requires crimping tools, see page 24

    C

    L

    W

    For additional sizes and configurations and to see the complete line of PAN-TERM Terminals, see the TerminationSolutions Catalog SA-TMCB02.UL and CSA approved tooling/product combinations. For crimping tools see page 24.**To order in bulk, replace -C in the part number with -M for a bulk package of 1000 and replace -L with -D for abulk package of 500.

    PartNumber

    WireRange

    ColorCode

    StockThickness

    Max.Ins.

    StudSize

    FigureDimensions (In.) PANDUITCrimping

    Tool

    Std.Pkg.Qty.**

    Std.Ctn.Qty.L W C

    PV14-6RX-C

    16-14AWG Blue

    .03 .200 #6 .96 .31 .25

    CT-100,CT-1550

    100 500PV14-8RX-C .03 .200 #8 .96 .31 .25 100 500PV14-10RX-C .03 .200 #10 .96 .31 .25 100 500PV14-14RX-C .03 .200 1/4" 1.16 .46 .37 100 500PV10-6RX-L

    12-10AWG Yellow

    .04 .250 #6 1.10 .31 .30

    CT-100,CT-1550

    50 500PV10-8RX-L .04 .250 #8 1.10 .31 .30 50 500PV10-10RX-L .04 .250 #10 1.10 .31 .30 50 500PV10-14RX-L .04 .250 1/4" 1.29 .52 .39 50 500

  • 17For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingSTRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    W

    HOLESPACING

    L

    T

    BINSPECTION

    WINDOW

    W

    HOLESPACING

    L

    T

    BINSPECTIONWINDOW

    Figure 1 Figure 2: Slotted Lug

    B

    INSPECTIONWINDOW

    W

    HOLESPACING

    L

    T45

    HOLESPACING

    L

    T

    B

    INSPECTIONWINDOW

    90

    W

    Figure 3: Slotted Lug45Bent

    Figure 4: Slotted Lug90Bent

    Code Conductor, Two-Hole, Long Barrel with Window Lug (continued)

    For additional sizes and configurations and to see the complete line of PAN-LUG Power and Grounding Connectors, see the Termination SolutionsCatalog SA-TMCB02.*Not tested to NEBS Level 3 requirements.**Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000V.

    Part NumberFigure

    No.

    CopperConductor

    Size

    StudHoleSize(In.)

    StudHole

    Spacing(In.)

    FigureDimensions (In.) PANDUITCrimping

    Tool

    PANDUITDie Color& Die No.

    BurndyDieNo.

    T&BDieNo.

    WireStrip

    Length(In.)

    Std.Pkg.Qty.W B T L

    LCC10-14JAW-L* 2#14 #10AWG STR,#12 #10AWG SOL

    1/4 .50 .63 .42 .53 .05 1.93

    CT-100,CT-1570

    9/16 50LCC10-14JAWH-L* 3 1/4 .50 .63 .42 .53 .05 1.78 9/16 50LCC10-14JAWF-L* 4 1/4 .50 .63 .42 .53 .05 1.56 9/16 50LCC10-14BW-L* 1 1/4 .75 .42 .53 .05 2.06 9/16 50LCC8-10ABW-L 2

    #8 AWG

    #10 .63 .75 .41 .70 .08 2.14CT-1700,CT-930,CT-2931

    Red P21 49 21 3/4 50LCC8-14ABW-L 2 1/4 .63 .75 .48 .70 .07 2.23 Red P21 49 21 3/4 50LCC8-14DW-L 1 1/4 1.00 .48 .70 .07 2.48 Red P21 49 21 3/4 50LCC8-38DW-L 1 3/8 1.00 .60 .70 .05 2.70 Red P21 49 21 3/4 50LCC6-10ABW-L 2

    #6 AWG

    #10 .63 .75 .46 1.07 .08 2.52

    CT-1700,CT-930,CT-2931

    Blue P24 7 24 1 1/8 50LCC6-14JAW-L 2 1/4 .50 .63 .48 1.07 .08 2.49 Blue P24 7 24 1 1/8 50LCC6-14JAWH-L 3 1/4 .50 .63 .48 1.07 .08 2.08 Blue P24 7 24 1 1/8 50LCC6-14JAWF-L 4 1/4 .50 .63 .48 1.07 .08 1.66 Blue P24 7 24 1 1/8 50LCC6-14BDW-L 2 1/4 .75 1.00 .48 1.07 .08 2.86 Blue P24 7 24 1 1/8 50LCC6-14EW-L 1 1/4 1.25 .48 1.07 .08 3.11 Blue P24 7 24 1 1/8 50LCC6-56BW-L 1 5/16 .75 .56 1.07 .07 2.73 Blue P24 7 24 1 1/8 50LCC6-38BDW-L 2 3/8 .75 1.00 .62 1.07 .06 3.08 Blue P24 7 24 1 1/8 50LCC4-14ADW-L 2

    #4 #3AWG STR

    1/4 .63 1.00 .55 1.05 .09 2.63 CT-1700,CT-930,CT-2931

    Gray P29 8 29 1 1/8 50LCC4-38DW-L 1 3/8 1.00 .62 1.05 .08 3.09 Gray P29 8 29 1 1/8 50LCC2-14AW-Q 1

    #2 AWG1/4 .63 .60 1.16 .10 2.67 CT-1700,

    CT-930,CT-2931

    Brown P33 10 33 1 1/4 25

    LCC2-38DW-Q 1 3/8 1.00 .66 1.16 .10 3.24 Brown P33 10 33 1 1/4 25

    LCC1-14AW-E 1#1 AWG

    1/4 .63 .70 1.36 .11 2.89 CT-1700,CT-930,CT-2931

    Green P37 11 37 1 7/16 20

    LCC1-38DW-E 1 3/8 1.00 .70 1.36 .11 3.46 Green P37 11 37 1 7/16 20

    LCC1/0-14AW-X 11/0 AWG

    1/4 .63 .76 1.44 .12 3.07 CT-930,CT-2931

    Pink P42 12 42 1 1/2 10LCC1/0-38DW-X 1 3/8 1.00 .76 1.44 .12 3.57 Pink P42 12 42 1 1/2 10LCC2/0-14AW-X 1

    2/0 AWG1/4 .63 .85 1.50 .13 3.23 CT-930,

    CT-2931Black P45 13 45 1 9/16 10

    LCC2/0-38DW-X 1 3/8 1.00 .85 1.50 .13 3.67 Black P45 13 45 1 9/16 10LCC3/0-38DW-X 1

    3/0 AWG3/8 1.00 .96 1.50 .13 3.70 CT-930,

    CT-2931Orange P50 14 50 1 9/16 10

    LCC3/0-12W-X 1 1/2 1.75 .96 1.50 .13 4.87 Orange P50 14 50 1 9/16 10

    LCC4/0-14AW-X 14/0 AWG

    1/4 .63 1.06 1.56 .14 3.35 CT-930,CT-2931

    Purple P54 15 54 1 5/8 10LCC4/0-38DW-X 1 3/8 1.00 1.06 1.56 .14 3.81 Purple P54 15 54 1 5/8 10LCC250-38DW-X 1

    250 kcmil3/8 1.00 1.17 1.61 .14 3.89 CT-930,

    CT-2931Yellow P62 16 62 1 11/16 10

    LCC250-12DW-X 1 1/2 1.00 1.17 1.61 .14 4.12 Yellow P62 16 62 1 11/16 10

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    18

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Flex Conductor, Two-Hole, Long Barrel with Window Lug

    Meets J-STD-607-A requirements fornetwork systems grounding applications

    Requires crimping tools and dies, see pages24, 25, 26 and 27

    UL Listed for use up to 35KV**, temperaturerated 90C and CSA Certified to 600V whencrimped with PANDUIT and specifiedcompetitor crimping tools and dies

    Color coded barrels marked with PANDUITand specified competitor die index numbersfor proper crimp die selection

    Can be used with code conductor andflex conductor class: G, H, I, K, M andLocomotive

    Long barrel maximizes number of crimpsand provides premium wire pull-out strengthand electrical performance

    Inspection window to visually assure fullconductor insertion

    Generously beveled wire entry preventsbent back strands when inserting conductorinto barrel

    Tin plated to inhibit corrosion Available with NEMA hole sizes and spacing

    For additional sizes and configurations and to see the complete line of PAN-LUG Power and Grounding Connectors, see the Termination SolutionsCatalog SA-TMCB02.**Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000V.

    W

    HOLESPACING

    L

    INSPECTIONWINDOW

    T

    B

    For Use with Flexible, Extra-Flexible and Code Stranded Copper Conductors

    Figure 1 Figure 2: Slotted Lug

    W

    HOLESPACING

    L

    T

    BINSPECTIONWINDOW

    Part NumberFigure

    No.

    FlexConductor

    Size CodeConductor

    Size

    StudHoleSize(In.)

    StudHole

    Spacing(In.)

    FigureDimensions

    (In.) PANDUITCrimping

    Tool

    PANDUITDie Color& Die No.

    WireStrip

    Length(In.)

    Std.Pkg.Qty.

    ClassG, H, I, K, M Locomotive W B T L

    LCCX8-10AB-L 2

    #8 AWG #8 AWG #8 AWG

    #10 .63 .75 .41 .70 .08 2.14CT-1700,CT-930,CT-2931

    Red P21 3/4 50LCCX8-14AB-L 2 1/4 .63 .75 .48 .70 .07 2.23 Red P21 3/4 50LCCX8-14D-L 1 1/4 1.00 .48 .70 .07 2.48 Red P21 3/4 50LCCX8-38D-L 1 3/8 1.00 .60 .70 .05 2.70 Red P21 3/4 50LCCX6-10B-L 1

    #6 AWG #6 AWG #6 AWG

    #10 .75 .46 1.07 .08 2.52CT-1700,CT-930,CT-2931

    Blue P24 1 1/8 50LCCX6-14AB-L 2 1/4 .63 .75 .48 1.07 .08 2.61 Blue P24 1 1/8 50LCCX6-14D-L 1 1/4 1.00 .48 1.07 .08 2.86 Blue P24 1 1/8 50LCCX6-38AC-L 2 3/8 .63 .88 .62 1.07 .06 2.96 Blue P24 1 1/8 50LCCX6-38D-L 1 3/8 1.00 .62 1.07 .06 3.08 Blue P24 1 1/8 50LCCX4-14AB-L 2

    #4 AWG #5, #4, #3AWG#4 #3

    AWG STR

    1/4 .63 .75 .55 1.05 .09 2.63 CT-1700,CT-930,CT-2931

    Gray P29 1 1/8 50LCCX4-38BD-L 2 3/8 .75 1.00 .62 1.05 .08 3.09 Gray P29 1 1/8 50

    LCCX2-38D-E 1 #2 AWG #2 AWG #2 AWG 3/8 1.00 .70 1.36 .11 3.46 CT-1700,CT-930,CT-2931

    BrownP33

    1 7/16 20

    LCCX1-14A-X 1#1 AWG #1 AWG #1 AWG

    1/4 .63 .76 1.44 .12 3.07 CT-930,CT-2931

    Green P37 1 1/2 10LCCX1-38D-X 1 3/8 1.00 .76 1.44 .12 3.57 Green P37 1 1/2 10LCCX1/0-14A-X 1 1/0 AWG 1/0 AWG 1/0 AWG 1/4 .63 .85 1.50 .13 3.23 CT-930,CT-2931

    Pink P42 1 9/16 10LCCX1/0-38D-X 1 3/8 1.00 .85 1.50 .13 3.67 Pink P42 1 9/16 10LCCX2/0-14A-X 1 2/0 AWG 2/0 AWG 2/0 AWG 1/4 .63 .96 1.50 .13 3.27 CT-930,CT-2931

    Black P45 1 9/16 10LCCX2/0-38D-X 1 3/8 1.00 .96 1.50 .13 3.70 Black P45 1 9/16 10LCCX3/0-38D-X 1 3/0 AWG 3/0 AWG 3/0 AWG 3/8 1.00 1.06 1.56 .14 3.81 CT-930,

    CT-2931Orange

    P501 5/8 10

    LCCX4/0-38D-X 1 4/0 AWG 4/0 AWG 4/0 AWG 3/8 1.00 1.19 2.24 .16 4.55 CT-930,CT-2931

    PurpleP54

    2 5/16 10

    LCCX250-38D-X 1 250 kcmil 262.6 kcmil 3/8 1.00 1.28 2.24 .17 4.59 CT-930,CT-2931

    Yellow P62 2 5/16 10

  • 19For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Code/Flex Conductor HTAP Kit Includes all components to make a complete HTAP and

    cover installation: HTCT HTAP, matching CLRCVR clearcover and cable ties

    Each HTCT HTAP designed to terminate a wide range ofcopper code and flex conductor combinations toaccommodate a variety of applications

    HTAPs incorporate a unique slotted design that allows forquick and easy installation using supplied PANDUIT cableties; saves time and cost

    Matching clear covers are made from high impact plasticand provide high impact strength and 360 viewing ofinstalled HTAP

    Clear covers have a UL 94 V-0 flame rating and anoxygen index of 28 providing self-extinguishing, flameretardant properties

    Requires crimping tools and dies, see pages 25, 26 and27

    UL Listed and CSA Certified for applications up to 600Vwhen crimped with PANDUIT and specified competitor

    For additional sizes and configurations and to see the complete line of PAN-LUG Power and Grounding Connectors, see the Termination SolutionsCatalog SA-TMCB02.See pages 20 and 21 for more information on HTAPs and clear covers, including crimping tools.Labels for clear covers are sold separately and are printed with the PANDUIT LS7 Printer. For information on the LS7 Printer and to see the complete line ofPANDUIT identification products, see the Identification Solutions Catalog SA-IDCB16.

    TAP 1

    RUN

    H

    WL

    WRUN

    TAP 1TAP 2

    TAP 3

    L

    H

    W LRUN

    H

    TAP 1 TAP 2 TAP 1

    W L

    H

    RUN

    HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250

    Part Number

    Components Copper Conductor Size RangeStd.Pkg.Qty.

    HTAPPart No.

    ClearCover

    Part No.

    WireStrandType Run Tap1 Tap 2 Tap 3

    HTWC6-6-1 HTCT6-6-1 CLRCVR1-1 Code #6 #10 AWG #6 #14 AWG

    1Flex #6 #10 AWG #6 #14 AWG

    HTWC2-2-1 HTCT2-2-1 CLRCVR2-1 Code #2 #6 AWGSTR/SOL#2 #6 AWG

    STR/SOL#8 #14 AWG #8 #14 AWG 1

    Flex #2 #8 AWG #2 #8 AWG #8 #14 AWG #8 #14 AWGHTWC250-2-1 HTCT250-2-1 CLRCVR3-1 Code 250 kcmil #2AWG

    #2 #6 AWGSTR/SOL

    #8 #14 AWG

    1

    Flex 4/0 #2 AWG #2 #8 AWG #8 #14 AWGHTWC250-250-1 HTCT250-250-1 CLRCVR3-1 Code 250 kcmil #2AWG

    250 kcmil #2AWG

    1

    Flex 4/0 #2 AWG 4/0 #2 AWG

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    20

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Code/Flex Conductor HTAP

    Used to tap into continuous conductors as asplice or pigtailing

    Each HTAP terminates a wide range ofconductor sizes and combinations of codeand flex conductors Class G, H, I andLocomotive to suit a variety of applications

    Slotted design allows quick and easyassembly of conductor to HTAP using 3PANDUIT 94 V-0 cable ties included

    Tap grooves are separated from one anotherallowing them to function independently soHTAP can be used with a single or multipletaps providing maximum design andinstallation flexibility

    Color coded and marked with PANDUIT dieindex numbers for proper crimp die selection

    Requires crimping tools and dies, seepages 25, 26 and 27

    UL Listed and CSA Certified for applicationsup to 600V when crimped with PANDUITand specified competitor crimping tools andPANDUIT crimping dies

    Tin plated to inhibit corrosion

    For additional sizes and configurations and to see the complete line of PAN-LUG Power and Grounding Connectors, see the Termination Solutions Catalog SA-TMCB02.

    For Making Parallel and Multiple Tap Connections on Code and Flex Conductors

    HTAP

    TAP

    RUN

    TAP 1

    RUN

    H

    WL

    WRUN

    TAP 1TAP 2

    TAP 3

    L

    H

    W LRUN

    H

    TAP 1 TAP 2 TAP 1

    W L

    H

    RUN

    HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250

    Part Number

    Copper Conductor Size RangeFigure

    Dimensions (In.)PANDUITCrimping

    Tool

    PANDUITDie Color& Die No.

    WireStrip

    Length(In.)

    Std.Pkg.Qty.

    WireStrandType Run Tap 1 Tap 2 Tap 3 L W H

    HTCT6-6-1Code #6 #10AWG

    #6 #14AWG

    .61 .40 .99 CT-930, CT-2931 Orange,PH6

    11/16 1

    Flex#6 #10

    AWG#6 #14

    AWGHTCT2-2-1

    Code#2 #6AWG

    STR/SOL

    #2 #6 AWGSTR/SOL

    #8 #14AWG

    #8 #14AWG

    .76 .61 1.55 CT-930, CT-2931 Brown,PH2

    13/16 1

    Flex#2 #8AWG

    #2 #8 AWG #8 #14AWG

    #8 #14AWG

    HTCT250-2-1Code 250 kcmil #2 AWG

    #2 #6 AWGSTR/SOL

    #8 #14AWG

    .92 .96 1.92 CT-930, CT-2931 Purple,PH25

    1 1

    Flex4/0 #2

    AWG#2 #8 AWG #8 #14

    AWGHTCT250-250-1

    Code 250 kcmil #2 AWG250 kcmil

    #2 AWG

    .90 .89 1.92 CT-930, CT-2931 Purple,PH25

    1 1

    Flex4/0 #2

    AWG4/0 #2

    AWG

  • 21For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Clear Covers for HTCT HTAPs

    Made of high impact plastic to provide high impact strengthand 360 inspections of crimped connection to assure thecrimp is complete and the correct die was used

    Incorporate dual self-latching spring loaded latches andsupplied with two PANDUIT UL 94 V-0 cable ties allowfor easy snap-on assembly and ensure covers are secured

    Low profile design minimizes space requirements Each cover half supports installation information labels

    inside plastic retainer strips to allow labels to be viewedon either side of cover and to protect labels frombeing removed

    Incorporate molded in flash barriers which encompass theHTAP installation providing protection against electricalflash over

    UL 94 V-0 flame rating and oxygen index of 28 providingself-extinguishing, flame retardant properties

    Part number, voltage rating, temperature rating and HTCTpart number molded into cover for easy identification

    Flexible fingers located at each end of cover preventforeign objects from entering cover and are made fromductile plastic material that allows easy installation andwill not damage conductor insulation

    For additional sizes and configurations and to see the complete line of PAN-LUG Power and GroundingConnectors, see the Termination Solutions Catalog SA-TMCB02.Labels for clear covers are sold separately and are printed with the PANDUIT LS7 Printer. For information on theLS7 Printer and to see the complete line of PANDUIT identification products, see the Identification SolutionsCatalog SA-IDCB16.

    H

    L W

    Part NumberUse With HTAP

    Part Number

    Figure Dimensions(In.) Std.Pkg.

    Qty.L W HCLRCVR1-1 HTCT6-6 4.48 1.41 1.20 1CLRCVR2-1 HTCT2-2 5.10 1.66 1.40 1CLRCVR3-1 HTCT250-2, HTCT250-250 5.35 2.16 1.40 1

    Shown Assembled

    For Use with PANDUIT HTCT HTAPs

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    22

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Grounding Clamp, U-Bolt, Bronze Used to ground copper conductor parallel or at a right

    angle to a rod, tube or pipe Made from high strength, electrolytic cast bronze High strength silicon bronze hardware provides long term

    reliable assembly

    Accommodates a wide range of pipe, tube, rod andconductor sizes minimizes inventory

    UL Listed for grounding and bonding and suitable for directburial in earth or concrete

    For the complete line of PAN-LUG Power and Grounding Connectors, see the Termination Solutions Catalog SA-TMCB02.

    ULRC US

    H

    LW

    Part Number

    GroundRod Size

    (In.)Iron

    Pipe Size(In.)

    ConductorSize Range

    Figure Dimensions(In.) BoltDia.

    (In.)HexSize(In.)

    TighteningTorque

    (In.-Lbs.)Std.Pkg.Qty.L W H

    GPL-8-Q 7/8 or 1 1/2 or 3/4 #8 SOL #4 STR 2.38 1.38 2.63 3/8 9/16 110 25GPL-14-X 1 #8 SOL #4 STR 2.63 1.38 2.75 3/8 9/16 110 10GPL-15-X 1 #4 SOL 2/0 STR 2.63 1.63 2.75 3/8 9/16 180 10

  • 23For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Grounding Clamp for Water Pipes, Bronze Used to ground copper code conductor to water pipe or

    copper tube Cast from high strength, electrolytic bronze to provide

    reliable grounding connections Plated steel screws provide high strength and

    inhibit corrosion

    Accommodates a wide range of pipe, tube, rod andconductor sizes minimizes inventory

    UL Listed for grounding and bonding and suitable for directburial in earth or concrete

    For the complete line of PAN-LUG Power and Grounding Connectors, see the Termination SolutionsCatalog SA-TMCB02.

    L W

    Grounding Rod Clamp, Bronze Used for grounding copper conductor parallel to

    ground rods Made from high strength, seamless electrolytic bronze to

    provide long term durability High strength silicon bronze hardware provides long term

    reliable assembly

    Accommodates a wide range of rod and conductorsizes minimizes inventory

    UL Listed and CSA Certified for grounding and bondingand suitable for direct burial in earth and concrete

    For the complete line of PAN-LUG Power and Grounding Connectors, see the Termination SolutionsCatalog SA-TMCB02.

    Part Number

    GroundRodSize

    Conductor SizeRange

    FigureDimensions (In.)

    HexSize(In.)

    TighteningTorque

    (In.-Lbs.)Std.Pkg.Qty.L W H

    WB12-L 1/2 #2 #10 STR#10 SOL

    .88 .84 1.28 1/2 180 50

    WB34-X 5/83/4

    1/0 #8 STR#2 #8 STR

    1.03 1.06 1.54 1/2 180 10

    WB58-Q 5/8 1/0 #8 STR 1.04 .92 1.40 1/2 180 25

    W L

    H

    Part Number

    Water PipeRange

    (In.)ConductorSize Range

    FigureDimensions (In.)

    Tightening Torque(In.-Lbs.)

    Std.Pkg.Qty.L W Conductor Clamp

    KP1-C 1/2 1 #10 SOL #2 STR 2.28 .66 50 50 100KP2-L 1 1/4 2 #10 SOL #2 STR 3.58 .73 50 50 50

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    24

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Hand Operated Plier Type Tool

    Crimping Tools

    Plier type Installer controlled crimp

    For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.

    Part Number Part Description

    Std.Pkg.Qty.

    CT-100 Crimps most PANDUIT #26 #10 AWG insulated and non-insulatedterminals, disconnects and splices. Cuts #4, #6, #8 and #10 screw sizes.Cuts and strips wire. Excellent all-around application tool of heat treatedfinished steel with comfortable cushioned plastic grip handles.

    1

    CONTOUR CRIMP Controlled Cycle Tools Specifically designed for the installation of PAN-TERM

    terminals, disconnects and splices Low handle effort increases productivity

    Superior crimp performance Reliable backed by a two year warranty

    CT-1550

    CT- 1700

    For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.

    Part Number Part Description

    Std.Pkg.Qty.

    CT-1550 Crimps most PAN-TERM #22 #10 AWG nylon and vinyl insulatedterminals, splices and disconnects. The CT-1550 has the red/blue pocketclosest to the pivot which provides a reduced crimp effort for those whomake red/blue terminations.

    1

    CT-1570 Crimps most PAN-TERM #22 #10 AWG and .5-6.0mm non-insulatedterminals and disconnects. Crimps PANDUIT #22 #10 AWG and.5-6.0mm non-insulated splices, and #10 AWG compression lugs.

    1

    CT-1700 Crimps PANDUIT #8 #2 AWG non-insulated tubular terminals (Sseries), #8 #1 AWG copper lugs and splices, #6 #4 AWG aluminumlugs and splices and CTAPF copper taps for #14 #3 AWG. Includes 5position, color coded rotating die.

    1CT-1570

  • 25For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Die Type, Manual Hydraulic, 14 Ton, Crimping Tool Two-stage rapid advance hydraulic system minimizes

    number of pumps required to complete a crimp saves time

    Cushioned grip prevents hands from slipping on tool reduces fatigue

    Provides UL Listed and CSA Certified connections onPANDUIT PAN-LUG copper and aluminum lugs andsplices and copper taps

    Open C-Head design allows easy loading of crimping diesand connectors, saves time

    Requires crimping dies, see page 27 Dies installed using spring loaded die retention pins, no

    need for tools Rubber boot on crimp head provides abrasion protection Audible pop-off valve indicates crimp completion Crimp head rotates 180, provides versatility for use in

    restricted spaces

    For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.

    Part Number Part Description

    Std.Pkg.Qty.

    CT-930 Terminates PANDUIT PAN-LUG Compression Connectors:

    Copper compression lugs and splices for #8 AWG 750 kcmil code conductor Copper compression lugs and splices for #8 AWG 600 kcmil flex conductor Copper compression CTAPF taps for #10 AWG 3/0 AWG code conductor Copper compression CTAP taps for #8 AWG 4/0 AWG code conductor Copper compression HTCT taps for #14 AWG 250 kcmil code conductor, #14 AWG 4/0 AWG flex conductor Aluminum compression lugs and splices for #6 AWG 600 kcmil code conductor Aluminum compression HTAPS for #14 AWG 500 kcmil code conductor PANDUIT PAN-TERM Tubular Terminals for #8 AWG 250 kcmil code conductor

    Warranty: 5 years

    CT-930 includes: Tool Plastic tool case with die storage

    1

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    26

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool Two stage rapid advance hydraulic system minimizes

    cycle time Provides UL Listed and CSA Certified connections on

    PANDUIT PAN-LUG copper and aluminum lugs andsplices and copper taps

    Open C-Head design allows easy loading of crimpingdies and connectors, saves time

    Rubber boot on crimp head provides abrasion protection Ram automatically retracts when crimp cycle is complete

    Tool provided with two, high capacity 12 VDC rechargeablenickel-metal hydride batteries provides for continuousoperation and eliminates memory build-up, one hourcharge time

    Eight second crimp cycle time provides quick terminations,saves time

    Uses industry standard Makita* batteries and charger industry proven reliability easy to obtain from localretail sources

    Requires crimping dies, see page 27 Dies installed using spring loaded die retention pins no

    need for tools Crimp head rotates 360 provides versatility for use in

    restricted spaces

    For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.*Makita is a registered trademark of Makita Corporation.

    Part Number Part Description

    Std.Pkg.Qty.

    CT-2931 Terminates PANDUIT PAN-LUG Compression Connectors:

    Copper compression lugs and splices for #8 AWG 750 kcmil code conductor Copper compression lugs and splices for #8 AWG 600 kcmil flex conductor Copper compression CTAPF taps for #10 AWG 3/0 AWG code conductor Copper compression CTAP taps for #8 AWG 4/0 AWG code conductor Copper compression HTCT taps for #14 AWG 250 kcmil code conductor, #14 AWG 4/0 AWG flex conductor Aluminum compression lugs and splices for #6 AWG 600 kcmil code conductor Aluminum compression HTAPS for #14 AWG 500 kcmil code conductor PANDUIT PAN-TERM Tubular Terminals for #8 AWG 250 kcmil code conductor

    Warranty: 3 years

    CT-2931 includes: Tool Two 12 VDC, rechargeable NiMH batteries One battery charger Steel tool case with storage for batteries, charger and crimp dies

    1

  • 27For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    CD-920 Crimping Dies Crimping dies and connectors are color coded for

    easy matching Embosses die index number on connector barrels for post

    crimp inspection

    Part number permanently marked on crimping die foreasy identification

    Provides circumferential crimp results in terminations withpremium electrical and mechanical performance

    Used in PANDUIT crimping tools; see the CT-930 crimpingtool on page 25, the CT-2931 crimping tool on page 26and the complete line of PANDUIT crimping tools in theTermination Solutions Catalog SA-TMCB02

    CD-920

    For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.

    Die Number

    DieColor

    Part Number

    Used to Install PANDUIT HTAP Part Numbers Std.Pkg.Qty.Copper HTAP and Die Color & Die No.

    CD-920H-6 HTCT6-6-1, Orange PH6 1CD-920H-2 HTCT2-2-1, Brown PH2 1CD-930H-250 HTCT250-2-1,

    HTCT250-250-1, Purple PH251

    Part Number

    Used to Install PANDUIT Compression Lug & Splice Sizes Std.Pkg.Qty.Copper Code Conductor Size and Die Color & Die No.

    CD-920-8 #8 AWG, Red P21 1CD-920-6 #6 AWG, Blue P24 1CD-920-4 #4 AWG, Gray P29 1CD-920-2 #2 AWG, Brown P33 1CD-920-1 #1 AWG, Green P37 1CD-920-1/0 1/0 AWG, Pink P42 1CD-920-2/0 2/0 AWG, Black P45 1CD-920-3/0 3/0 AWG, Orange P50 1CD-920-4/0 4/0 AWG, Purple P54 1CD-920-250 250 kcmil, Yellow P62 1

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    28

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    PANDUIT STRUCTUREDGROUND System for Data Center GroundingApplication Standards

    IEEE Std 1100-1999 (IEEE Emerald Book) IEEERecommended Practice for Powering and GroundingElectronic Equipment

    The main objective of the Emerald Book is to provide a consensus ofrecommended practices to address electronic equipmentperformance issues while maintaining a safe installation, asspecified in the National Electrical Code (NEC) (NFPA 70-1999)and recognized testing laboratories' standards.

    Alliance for Telecommunications IndustrySolutions ATIS

    ATIS is a technical planning and standards development organization that is committed to rapidly developing and promotingtechnical and operations standards for the communications andrelated information technologies industry worldwide using a pragmatic, flexible and open approach. Over 1,200 participants frommore than 400 communications companies are active in ATIS 22industry committees, and its Incubator Solutions Program.www.atis.org

    J-STD-607-A-2002, Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications is jointly developed by TIA/EIA and ATIStechnical committee T1E1. This document is available on the ATIS Document Center at www.atis.org.

    Adhering to the grounding principles outlined in J-STD-607-A helpsensure that telecommunications equipment and systems operate reliably. As stated in J-STD-607-A, the preferred means ofconnecting conductors to busbars is by using two-hole irreversible compression lugs listed by a nationally recognized testing laboratory (NRTL) such as UL. PANDUIT PAN-LUG CopperCompression Connectors meet these requirements, in all of thebarrel sizes specified by the 607 standard.

    Telecommunications Industry Association TIA

    The Telecommunications Industry Association is a leading U.S.non-profit trade association serving the communications andinformation technology industry. TIA represents providers ofcommunications and information technology products and servicesfor the global marketplace through its core competencies instandards development.

    ANSI/TIA-942 Draft 5.0a Telecommunications Infrastructure Standard for Data Centers

    TIA-942 states that electrical continuity is required throughout therack materials. Adhering to these principles protects networkequipment and maintains system performance. PANDUIT STRUCTUREDGROUND System for Data Center Grounding meetsTIA-942 requirements by incorporating an all-copper grounding path.Paint piercing grounding washers ensure metal to metal contact ofrack members and two-hole compression lugs for a permanent andreliable connection.

    The Institute of Electrical and ElectronicsEngineers, Inc. (IEEE)The IEEE promotes the engineering process of creating,developing, integrating, sharing, and applying knowledge aboutelectro and information technologies and sciences for the benefitof humanity and the profession.

    NEBS Level 3 Criteria is the minimum level of environmental compatibility needed to provide maximum assurance of equipment operability within the network facility environment.

    The Level 3 Criteria is the highest assurance of product operability.Products that meet NEBS Level 3 Criteria are suited for equipmentapplications which demand minimal service interruptions over the lifespan of the equipment. PANDUIT is the first in the industry to have asystem of copper compression lugs and splices (#8 AWG 1,000kcmil) and crimping tools physically and rigorously tested byTelcordia Technologies to meet NEBS Level 3 compliance.

    NEBS Level 3 Approval as Tested by Telcordia Technologies

    Telcordia Technologies, formerly known as Bellcore, serves as thetesting agency for the Regional Bell Operating Companies. NetworkEquipment-Building Systems (NEBS) was developed by Bellcoreand is currently maintained by Telcordia Technologies. NEBS wasdeveloped to standardize requirements for Central Office Equipmentand to develop criteria for personal safety, protection of property andoperational continuity.

    Canadian Standards Association

    Canadian Standards Association is a not-for-profit membershipbased association serving business, industry, government, and consumers in Canada and the global marketplace. C.S.A. works inCanada and around the world to develop standards that enhancepublic safety and health.

    Underwriters Laboratories, Inc.

    Underwriters Laboratories, Inc. is an independent, not-for-profitsafety testing and certification organization based in theUnited States.

    UL 467 Grounding and Bonding Equipment UL 486A Wire Connectors and Soldering Lugs for Use with

    Copper Conductors Covers pressure wire connectors and soldering lugs for use with copper conductors according to the National Electrical Code NFPA 70

    UL VW-1 Flammability Rating

    Underwriters Laboratories, Inc. Standards applicable to specified PANDUIT STRUCTUREDGROUND System for Data Center Groundingand PAN-LUG Power and Grounding Connectors.

    C22.2 NO. 41-M1987 (R2004) Grounding and Bonding Equipment

    C22.2 NO. 65-03 Wire Connectors

    Canadian Standards Association standards that are applicable tospecified PANDUIT STRUCTUREDGROUND System for Data CenterGrounding and PAN-LUG Power and Grounding Connectors.

  • 29For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Roof

    Backbone pathwaySuspended ceiling area

    TR

    Bui

    ldin

    g st

    eel

    TGB

    GE TR

    TGB

    TGB TGB

    Bui

    ldin

    g st

    eel

    Backbone pathway

    Backbone pathway

    Suspended ceiling area

    TR

    (TBB

    )

    Ext

    erio

    r bu

    ildin

    g w

    all

    Ext

    erio

    r bu

    ildin

    g w

    all

    TBB

    Sleeve

    Suspended ceiling area

    TBB within conduitACEG (T

    BB)

    ElectricalEF

    Groundingelectrodesystem

    GEC

    TMGB

    BCT

    Primary cableprotection

    EF ER

    Panelboard

    TGB

    (TBB

    )

    TR

    ACEG = Alternating current equipment ground BC = Bonding conductor BCT = Bonding conductor for telecommunications EF = Entrance facility ER = Equipment room GE = Grounding equalizer GEC = Grounding electrode conductor TBB = Telecommunications bonding backbone TGB = Telecommunications grounding busbar TMGB = Telecommunications main grounding busbar TR = Telecommunications room

    Red iron

    Red iron

    Red iron

    GE

    Source: BICSI TDM Manual, 10th Edition

    Specification Layout for Data Center Grounding per BICSI TDM Manual,10th Edition

    For more technical grounding information, please see the Data Center Grounding White Paper at www.panduit.com/dcgrounding.

  • Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    30

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Ground A conducting connection, whether intentional or accidental, by which an electric circuit or equipment is connected to the earth, or to some conducting body of relatively large extent that serves in place of the earth.

    Bonding The permanent joining of metallic parts to form an electrically conductive path that will assure electrical continuity and the capacity to conduct safely any current likely to be imposed.

    Common Bonding Network (CBN) The principal means for affecting bonding and earthing inside a building.

    Key Terminology

    Recommended Sizing of the Telecommunications Bonding Backbone (TBB)and Grounding Equalizer (GE) per J-STD-607-A

    Recommended Cable Sizes for Grounding Applications

    The TBB shall be a copper conductor. The minimum conductor size shall be a No. 6 AWG. The TBBshall be sized at 2 kcmil per linear foot of conductor length up to a maximum size of a 3/0 AWG. TheTBB may be insulated. The Bonding conductor for Telecommunications (BCT) shall be, as a minimum,the same size as the TBB.(1)

    1. Telecommunications Industry Association, Commercial Building Grounding (Earthing) and Bonding Requirements For Telecommunications, J-STD-607-A,October 2002.

    Purpose

    Use theFollowing

    Code CablesOther connections to the TGB and TMGB,including building steel, main water pipe, etc.

    #6 AWG, green insulated

    Underfloor CBN #2 AWG, bareConnections to Underfloor CBN from pipes,ventilation ducts, etc.

    #6 AWG, bare

    Connection from Underfloor CBN to TGB 2/0 AWG, bare

    Sizing of the TBB

    TBB Lengthlinear M (ft) TBB Size (AWG)

    less than 4 (13) 64 6 (14 20) 46 8 (21 26) 38 10 (27 33) 210 13 (34 41) 113 16 (42 52) 1/016 20 (53 66) 2/0

    greater than 20 (66) 3/0**3/0 may not always be available. 4/0 is a more common size that may be substituted.

  • 31For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

    STRUCTUREDGROUND System for Data Center GroundingIntroduction

    STRUCTUREDGROUND System for Data Center Grounding

    Introduction

    GroundingRoadmaps

    Equipment& Rack

    GroundingKits

    CommonBondingNetwork

    (CBN)Components

    CrimpingTools

    TechnicalInformation

    Index

    STRUCTUREDGROUND SYSTEM FOR DATA CENTER GROUNDING

    Part Number Index

    Part Number PageNumber

    CCD-920-1 . . . . . . . . . . . . . . . . . . . . .27CD-920-1/0 . . . . . . . . . . . . . . . . . . . .27CD-920-2 . . . . . . . . . . . . . . . . . . . . .27CD-920-2/0 . . . . . . . . . . . . . . . . . . . .27CD-920-250 . . . . . . . . . . . . . . . . . . .27CD-920-3/0 . . . . . . . . . . . . . . . . . . . .27CD-920-4 . . . . . . . . . . . . . . . . . . . . .27CD-920-4/0 . . . . . . . . . . . . . . . . . . . .27CD-920-6 . . . . . . . . . . . . . . . . . . . . .27CD-920-8 . . . . . . . . . . . . . . . . . . . . .27CD-920H-2 . . . . . . . . . . . . . . . . . . . .27CD-920H-6 . . . . . . . . . . . . . . . . . . . .27CD-930H-250 . . . . . . . . . . . . . . . . . .27CLRCVR1-1 . . . . . . . . . . . . . . . . . . .21CLRCVR2-1 . . . . . . . . . . . . . . . . . . .21CLRCVR3-1 . . . . . . . . . . . . . . . . . . .21CT-100 . . . . . . . . . . . . . . . . . . . . . . .24CT-1550 . . . . . . . . . . . . . . . . . . . . . .24CT-1570 . . . . . . . . . . . . . . . . . . . . . .24CT-1700 . . . . . . . . . . . . . . . . . . . . . .24CT-2931 . . . . . . . . . . . . . . . . . . . . . .26CT-930 . . . . . . . . . . . . . . . . . . . . . . .25

    GGB2B0304TPI-1 . . . . . . . . . . . . . . . .15GB2B0306TPI-1 . . . . . . . . . . . . . . . .15GB2B0312TPI-1 . . . . . . . . . . . . . . . .15GB4B0612TPI-1 . . . . . . . . . . . . . . . .15GB4B0624TPI-1 . . . . . . . . . . . . . . . .15GPL-14-X . . . . . . . . . . . . . . . . . . . . .22GPL-15-X . . . . . . . . . . . . . . . . . . . . .22GPL-8-Q . . . . . . . . . . . . . . . . . . . . . .22

    HHTCT2-2-1 . . . . . . . . . . . . . . . . . . . .20HTCT250-2-1 . . . . . . . . . . . . . . . . . .20HTCT250-250-1 . . . . . . . . . . . . . . . .20HTCT6-6-1 . . . . . . . . . . . . . . . . . . . .20HTWC2-2-1 . . . . . . . . . . . . . . . . . . . .19HTWC250-2-1 . . . . . . . . . . . . . . . . . .19HTWC250-250-1 . . . . . . . . . . . . . . . .19HTWC6-6-1 . . . . . . . . . . . . . . . . . . . .19

    KKP1-C . . . . . . . . . . . . . . . . . . . . . . .23KP2-L . . . . . . . . . . . . . . . . . . . . . . . .23

    LLCC1-14AW-E . . . . . . . . . . . . . . . . . .17LCC1-38DW-E . . . . . . . . . . . . . . . . .17LCC1/0-14AW-X . . . . . . . . . . . . . . . .17LCC1/0-38DW-X . . . . . . . . . . . . . . . .17LCC10-14BW-L . . . . . .