14
General Specifications GX90XA/GX90XD GX90YD/GX90WD I/O Modules Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan GS 04L53B01-01EN GS 04L51B01-01EN ©Copyright April 2014 2nd Edition May. 7, 2014 OVERVIEW I/O modules are connected to the GX/GP and Expandable I/O unit. A module type is four types, an analog input, a digital input, a digital output, and a digital input/ output. Input and output have module structure and it can extend them easily. The GX90XA analog input module provides four types: (1) universal type that allows the measurement input for DCV (direct voltage), TC (thermocouple), RTD (resistance temperature detector), and DI (operation record, contact, or TTL level voltage), (2) current input type with the built-in shunt resistor to directly input a standard signal of 4-20mA DC, (3) electromagnetic relay scanner type insusceptible to noises that allows the measurement input for DCV, TC, and DI, and (4) low withstand voltage relay type that offers a low cost. In each system, a measurement input signal can be assigned to each channel. The GX90XD digital input module, which allows up to 16 digital inputs (contact or TTL level voltage), can be used as a multipoint digital input. This module can also be used as a remote control input. The GX90YD digital output module is assigned as a relay output (contact C) and is used when an alarm activates. It can also be used to turn the output on and off manually using the touch panel. The GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and digital outputs, you do not need to mount two modules. This enables efficient channel configuration. Each module provides a M3 screw terminal and clamp terminal *1 . Also, the input terminal can be removed and mounted. This enables wiring work to be carried out efficiently. *1 M3 screw terminal only for the electromagnetic relay scanner type of the GX90YD, GX90WD, and GX90XA The measuring accuracies noted in the general specifications have a margin of error that takes into account the product's components and the equipment used for adjustment and testing. However, the actual values calculated from the accuracy testing data upon shipment of the instrument from the factory are as follows. Input type Measuring accuracy*2 (typical value*3) DCV 20 mV ± (0.01% of reading + 5 μV) 6V (1-5V) ± (0.01% of reading + 2 mV) RTD Pt100 ± (0.02% of reading + 0.2 °C ) Pt100 (high resolution) ± (0.02% of reading + 0.16 °C) *2 General operating conditions: 23±2 ºC, 55±10% RH, supply voltage 90–132, 180–250 VAC, supply frequency within 50/60 Hz ±1%, warm- up of 30 minutes or more, no vibrations or other hindrances to performance. *3 For the measuring accuracy (guaranteed), see next page.

GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

GeneralSpecifications

GX90XA/GX90XDGX90YD/GX90WDI/O Modules

Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan

GS 04L53B01-01EN

GS 04L51B01-01EN©Copyright April 2014

2nd Edition May. 7, 2014

OVERVIEWI/O modules are connected to the GX/GP and Expandable I/O unit.● Amoduletypeisfourtypes,ananaloginput,a

digital input, a digital output, and a digital input/output.

● Inputandoutputhavemodulestructureanditcanextendthemeasily.

● TheGX90XAanaloginputmoduleprovidesfourtypes:(1)universaltypethatallowsthemeasurementinputforDCV(directvoltage),TC(thermocouple),RTD(resistancetemperaturedetector),andDI(operationrecord,contact,orTTLlevelvoltage),(2)currentinputtypewiththebuilt-in shunt resistor to directly input a standard signalof4-20mADC,(3)electromagneticrelayscanner type insusceptible to noises that allows the measurementinputforDCV,TC,andDI,and(4)lowwithstandvoltagerelaytypethatoffersalowcost.Ineachsystem,ameasurementinputsignalcan be assigned to each channel.

● TheGX90XDdigitalinputmodule,whichallowsupto16digitalinputs(contactorTTLlevelvoltage),canbeusedasamultipointdigitalinput.Thismodulecanalsobeusedasaremotecontrolinput.

● TheGX90YDdigitaloutputmoduleisassignedasarelayoutput(contactC)andisusedwhenanalarmactivates.Itcanalsobeusedtoturntheoutputonandoffmanuallyusingthetouchpanel.

● TheGX90WDdigitalinput/outputmoduleprovideseight digital inputs and six relay outputs. When therearesmallamountsofdigitalinputsanddigitaloutputs,youdonotneedtomounttwomodules.Thisenablesefficientchannelconfiguration.

● EachmoduleprovidesaM3screwterminalandclampterminal*1.Also,theinputterminalcanberemovedandmounted.Thisenableswiringworktobecarriedoutefficiently.

*1 M3screwterminalonlyfortheelectromagneticrelayscannertypeoftheGX90YD,GX90WD,and GX90XA

● Themeasuringaccuraciesnotedinthegeneralspecificationshaveamarginoferrorthattakesintoaccounttheproduct'scomponentsandtheequipmentusedforadjustmentandtesting.However,theactualvaluescalculatedfromtheaccuracytestingdatauponshipmentoftheinstrumentfromthefactoryareasfollows.

Input type Measuringaccuracy*2(typicalvalue*3)

DCV 20mV ±(0.01%ofreading+5μV)

6V (1-5V) ±(0.01%ofreading+2mV)

RTD Pt100 ±(0.02%ofreading+0.2°C)

Pt100(high resolution)

±(0.02%ofreading+0.16°C)

*2 Generaloperatingconditions:23±2ºC,55±10%RH,supplyvoltage90–132,180–250VAC,supplyfrequencywithin50/60Hz±1%,warm-upof30minutesormore,novibrationsorotherhindrancestoperformance.

*3 Forthemeasuringaccuracy(guaranteed),seenext page.

Page 2: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

2

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

INPUT/OUTPUT MODULE SPECIFICATIONS

ANALOG INPUT MODULE (Model GX90XA or GX/GP main unit options /Uxx0)

• Numberofinputs:10• InputType:

Suffix Code Input Type Description

-U2 DCvoltage,standardsignal,thermocouple(TC),resistancetemperaturedetector(RTD),DI(voltage,contact),andDCcurrent(byaddinganexternalshuntresistor)

Universal

-C1 DCcurrent(mA),DCcurrentstandardsignal(4-20mA) Current input

-L1 DCvoltage,standardsignal,thermocouple(TC),DI(voltage,contact),andDCcurrent(byaddinganexternalshuntresistor)

Lowwithstandvoltagerelay

-T1 DCvoltage,standardsignal,thermocouple(TC),DI(voltage,contact),andDCcurrent(byaddinganexternalshuntresistor)

Electromagneticrelay

GX90XA

• Measurementinterval:100*1 *2, 200 *1 *2,500ms*1, 1, 2, 5 s• Inputrange:-5%ormoreand105%orless(accuracyisguaranteedintherangefrom0%to100%inclusive)• Measurementrangesandaccuracies*3(However,thenumberofdisplaydigitscanbeincreasedbyscaling.)

*1 Cannotbespecifiedfortheelectromagneticrelayscannertype(TypeSuffixCode:-T1).*2 CannotbespecifiedforL-modelDCV/TC/DI,scannertype(TypeSuffixCode:-L1).*3 Thefollowingspecificationsapplytooperationoftherecorderunderstandardoperationconditions. Temperature:23±2°C,Humidity:55%±10%RH,Powersupplyvoltage:90to132or180to250VAC,Powersupply

frequency:50/60Hz±1%,Warm-uptime:Atleast30min.Otherambientconditionssuchasvibrationshouldnotadverselyaffectrecorderoperation.

Input Type Range Measurement accuracy (digital display) Max. resolution of

digital displayA/D integration time: 16.7ms or more A/D integration time: 1.67ms

DCV 20mV -20.000 to 20.000mV ±(0.05%ofrdg+12μV) ±(0.1%ofrdg+40μV) 1μV

60mV -60.00 to 60.00mV ±(0.05%ofrdg+0.03mV) ±(0.1%ofrdg+0.15mV) 10μV

200mV -200.00 to 200.00mV ±(0.05%ofrdg+0.03mV) ±(0.1%ofrdg+0.4mV) 10μV

1V -1.0000 to 1.0000V ±(0.05%ofrdg+1.2mV) ±(0.1%ofrdg+4mV) 100μV

2V -2.0000 to 2.0000V ±(0.05%ofrdg+1.2mV) ±(0.1%ofrdg+4mV) 100μV

6V -6.000 to 6.000V ±(0.05%ofrdg+3mV) ±(0.1%ofrdg+15mV) 1mV

20V -20.000 to 20.000V ±(0.05%ofrdg+3mV) ±(0.1%ofrdg+40mV) 1mV

50V -50.00 to 50.00V ±(0.05%ofrdg+0.03V) ±(0.1%ofrdg+0.15V) 10mV

Standard signal 0.4-2V 0.3200 to 2.0800V ±(0.05%ofrdg+1.2mV) ±(0.1%ofrdg+4mV) 100μV

1-5V 0.800 to 5.200V ±(0.05%ofrdg+3mV) ±(0.1%ofrdg+15mV) 1mV

DC current 0-20mA 0.000 to 20.000mA ±(0.3%ofrdg+5μA) ±(0.3%ofrdg+90μA) 1μV

DC current(standardsignal

4-20mA 3.200 to 20.800mA

TC(ExcludingRJCaccuracy)

R 0.0 to 1760.0 °C ±(0.15%ofrdg+1.0°C)However,R,S;0.0to800.0°C:±2.2°C, B;400.0to800.0°C:±3.0°CAccuracy at less than 400.0 °C is not guaranteed.

±(0.2%ofrdg+6.0°C)However,R,S;0.0to800.0°C:±7.6°C, B;400.0to800.0°C:±11.0°CAccuracy at less than 400.0 °C is not guaranteed.

0.1 °C

S 0.0 to 1760.0 °C

B 0.0 to 1820.0 °C

K -270.0 to 1370.0 °C ±(0.15%ofrdg+0.7°C)However,-200.0to0.0°C:±(0.35%ofrdg+0.7°C)Accuracy at less than -200.0 °C is not guaranteed

±(0.2%ofrdg+5.0°C)However,-200.0to0.0°C:±(3%ofrdg+5.0°C)Accuracy at less than -200.0 °C is not guaranteed

0.1 °C

-200.0 to 500.0 °C

E -270.0 to 800.0 °C ±(0.15%ofrdg+0.5°C)However,-200.0to0.0°C:±(0.35%ofrdg+0.5°C)Accuracy at less than -200.0 °C is not guaranteed

±(0.2%ofrdg+4.0°C)However,-200.0to0.0°C:±(2%ofrdg+4.0°C)Accuracy at less than -200.0 °C is not guaranteed

0.1 °C

J -200.0 to 1100.0 °C

T -270.0 to 400.0 °C ±(0.15%ofrdg+0.5°C)However,-200.0to0.0°C:±(0.35%ofrdg+0.5°C)Accuracy at less than -200.0 °C is not guaranteed

±(0.2%ofrdg+2.5°C)However,-200.0to0.0°C:±(2%ofrdg+2.5°C)Accuracy at less than -200.0 °C is not guaranteed

0.1 °C

N -270.0 to 1300.0 °C ±(0.15%ofrdg+0.7°C)However,-200.0to0.0°C:±(0.7%ofrdg+0.7°C)Accuracy at less than -200.0 °C is not guaranteed

±(0.3%ofrdg+6.0°C)However,-200.0to0.0°C:±(5%ofrdg+6.0°C)Accuracy at less than -200.0 °C is not guaranteed

0.1 °C

W 0.0 to 2315.0 °C ±(0.15%ofrdg+1.5°C) ±(0.3%ofrdg+14.0°C)However,morethan1000.0°C:±(0.8%ofrdg+9.0°C)

0.1 °C

L -200.0 to 900.0 °C ±(0.15%ofrdg+0.5°C)Lessthan0.0°C:±(0.5%ofrdg+0.5°C)

±(0.2%ofrdg+4.0°C)Lessthan0.0°C:±(3%ofrdg+4.0°C)

0.1 °C

U -200.0 to 400.0 °C ±(0.15%ofrdg+0.5°C)Lessthan0.0°C:±(0.7%ofrdg+0.5°C)

±(0.2%ofrdg+2.5°C)Lessthan0.0°C:±(3%ofrdg+2.5°C)

0.1 °C

Page 3: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

3

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

Continued

Input Type Range Measurement accuracy (digital display) Max. resolution of digital display

A/D integration time: 16.7ms or more A/D integration time: 1.67ms (fast sampling mode)

TC(ExcludingRJCaccuracy)

W97Re3-W75Re25 0.0 to 2320.0 °C ±(0.2%ofrdg+2.5°C) ±18.0 °CMorethan2000.0°C:±0.9%ofrdg

0.1 °C

KpvsAu7Fe 0.0 to 300.0 K ±(0.15%ofrdg+2.0K)0.15to280.15K:guaranteedrange

±(0.2%ofrdg+7.0K)0.15to280.15K:guaranteedrange

0.1 K

Platinel 2 0.0 to 1395.0 °C ±(0.25%ofrdg+2.3°C) ±(0.25%ofrdg+8.0°C) 0.1 °C

PR20-40 0.0 to 1900.0 °C ±(0.7%ofrdg+0.4°C)However,accuracyatlessthan800.0°Cis not guaranteed.

±20.0 °CHowever,accuracyatlessthan800.0°Cisnotguaranteed.

0.1 °C

NiNiMo 0.0 to 1310.0 °C ±(0.25%ofrdg+0.7°C) ±(0.5%ofrdg+5.0°C) 0.1 °C

W/WRe26 0.0 to 2320.0 °C ±(0.2%ofrdg+2.0°C)However,accuracyatlessthan300.0°Cis not guaranteed.

±(0.4%ofrdg+12.0°C)However,accuracyatlessthan300.0°Cisnotguaranteed.

0.1 °C

N(AWG14) 0.0 to 1300.0 °C ±(0.2%ofrdg+1.3°C) ±(0.5%ofrdg+7.0°C) 0.1 °C

XK GOST -200.0 to 600.0 °C ±(0.25%ofrdg+0.8°C) ±(0.5%ofrdg+4.0°C) 0.1 °C

RTD Pt100 -200.0 to 850.0 °C ±(0.15%ofrdg+0.3°C) ±(0.3%ofrdg+1.5°C) 0.1 °C

-150.00 to 150.00 °C 0.01 °C

JPt100 -200.00 to 550.00 °C 0.1 °C

-150.00 to 150.00 °C 0.01 °C

Cu10 GE -200.0 to 300.0 °C ±(0.2%ofrdg+2.0°C)guaranteed rangeCu10GE:-70.0to170.0°CCu10L&N:-75.0to150.0°CCu10WEED:-200.0to260.0°COtherrange:-200.0to300.0°C

±(0.4%ofrdg+6.0°C)guaranteed rangeCu10GE:-70.0to170.0°CCu10L&N:-75.0to150.0°CCu10WEED:-200.0to260.0°COtherrange:-200.0to300.0°C

0.1 °C

Cu10 L&N -200.0 to 300.0 °C

Cu10 WEED -200.0 to 300.0 °C

Cu10 BAILEY -200.0 to 300.0 °C

Cu10(20°C)alpha=0.00392

-200.0 to 300.0 °C

Cu10(20°C)alpha=0.00393

-200.0 to 300.0 °C

Cu25(0°C)alpha=0.00425

-200.0 to 300.0 °C ±(0.3%ofrdg+0.8°C) ±(0.5%ofrdg+3.0°C) 0.1 °C

Cu53(0°C)alpha=0.00426035

-50.0 to 150.0 °C ±(0.15%ofrdg+0.8°C) ±(0.3%ofrdg+4.0°C) 0.1 °C

Cu100(0°C)alpha=0.00425

-50.0 to 150.0 °C ±(0.2%ofrdg+1.0°C) ±(0.4%ofrdg+5.0°C) 0.1 °C

J263B 0.0 to 300.0 K ±1.0 KLessthan40.0K:±3.0K

±3.0 KLessthan40.0K:±9.0K

0.1 K

Ni100(SAMA) -200.0 to 250.0 °C ±(0.15%ofrdg+0.4°C) ±(0.3%ofrdg+2.0°C) 0.1 °C

Ni100(DIN) -60.0 to 180.0 °C

Ni120 -70.0 to 200.0 °C

Pt25 -200.0 to 550.0 °C ±(0.15%ofrdg+0.8°C) ±(0.3%ofrdg+4.0°C) 0.1 °C

Pt50 -200.0 to 550.0 °C ±(0.3%ofrdg+0.6°C) ±(0.6%ofrdg+3.0°C) 0.1 °C

Pt200 WEED -100.0 to 250.0 °C

Cu10 GOST -200.0 to 200.0 °C ±(0.2%ofrdg+2.0°C) ±(0.4%ofrdg+6.0°C) 0.1 °C

Cu50 GOST -200.0 to 200.0 °C ±(0.15%ofrdg+0.6°C) ±(0.3%ofrdg+4.0°C) 0.1 °C

Cu100 GOST -200.0 to 200.0 °C ±(0.15%ofrdg+0.3°C) ±(0.3%ofrdg+1.5°C) 0.1 °C

Pt46 GOST -200.0 to 550.0 °C ±(0.3%ofrdg+0.8°C) ±(0.6%ofrdg+4.0°C) 0.1 °C

Pt100 GOST -200.0 to 600.0 °C ±(0.15%ofrdg+0.3°C) ±(0.3%ofrdg+2.0°C) 0.1 °C

DI Level Thresholdlevel(Vth=2.4V)Accuracy:±0.1V -

Contact *4 Less than 1 kΩ:1(ON),Morethan100kΩ:0(OFF)(parallelcapacitanceof0.01μForless) -

*4 Thedetectedcurrentvalueisapprox.10μA.

Measurementaccuracyatscaling:measurementaccuracyatscaling(digits)=measurementaccuracy(digits)xscalingspan(digits)/measurementspan(digits)+2digits

*Roundingupdecimalplaces

Page 4: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

4

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

• Burnoutdetection:Burnoutupscale,downscale,orOFFselectable(foreachchannel).

Availableinput:TC,RTD,StandardsignalDetectioncondition;TC;Normal:2kΩorless.,Burnout:200kΩor

more(parallelcapacitanceof0.01μForless) Detectioncurrent:Approx.10μARTD;Normal:wiringresistanceorless,

Burnout:200kΩormore parallelcapacitanceoflessthan0.01μFor

less Detectioncurrent:Approx.10μAStandardsignal: Normal:Withinmeasuringrange Burnout:Dependsonthesettingofthe

burnoutjudgmentvalue.Theburnoutjudgmentvalueshallbesetwiththepercentageofthespecifiedspanwidth.

Lowerlimit:-20.0to-5.0% Upperlimit:105to120%

• Inputexternalresistance:DCvoltage,thermocoupleinput:2kΩorbelowResistancetemperaturedetectorinput:10Ω

orbelowineachwire(Sameresistanceinthreewires)

• Inputbiascurrent:±10nAorless(whenburnoutfunctiondoesnotwork)

• Measuredcurrent(forRTD):Approx.1mA• Inputresistance:

10MΩormoreforTC/DCvoltage(1Vrangeorless)input Approx.1MΩforDCvoltage(2Vrangeormore)/standardsignalinput 250Ω(249.5Ωtyp)forDCmA

*typ:Typicalvalue(Typical)• Allowablesignalsourceresistance:2kΩorless

forTC/DCvoltage(1Vrangeorless)input• Effectofsignalsourceresistance:

±10μV/1kΩorlessforTC/DCvoltage(1Vrangeorless)input ±0.15%/1kΩorlessforDCvoltage(2Vrangeormore)/standardsignalinput

• Allowablewiringresistance:Max.10ΩperlineforRTDinput(conductorresistancebetweenthethreelinesshallbeequal)

• Effectofwiringresistance:±0.1°C/10ΩforRTDinput(conductorresistancebetweenthethreelinesshallbeequal)

• Allowableinputvoltage: ±10VDCforTC/DCvoltage(1Vrangeorless)/RTD/DIinput,DCmA ±60VDCforDCvoltage(2Vrangeormore)input

• Allowableinputcurrent(currentscannertype):24mA,50/60Hz,peakvalueincludingsignal

• Noisereductionratio

Integration time *1 Normal mode Common mode1.67ms 50/60Hz,nonoise

reductionMore than 80 dB *2 *4

Morethan16.7ms More than 40 dB *2 *3

More than 120 dB *2 *4

*1 Afrequencydiscriminationsettingismadeinthemainunit.

*2 Aresistancetemperaturedetectorrangeisaconvertedvalueofvoltagewhenameasuredcurrentflows.

*3 50/60Hz±0.1%*4 50/60Hz±0.1%,500Ωimbalance,between

minusmeasuringterminalandground

• NormalmodevoltageforTC/DCvoltage(1Vrangeorless)/DI(voltage):1.2timesorlessofrated range

Standardsignal0.4to2Vrange:2.4V Standardsignal1-5Vrange:6V RTD(100Ω):50mVpeak RTD(50Ω):10mVpeak* 50/60Hz,Thepeakvalueincludingthesignal.

• Normalmodecurrent(current,scannertype):24mADC(Valueconvertedtovoltage:6V)

*50/60Hz,Thepeakvalueincludingthesignal.• Maximumcommonmodevoltageformeasuring

input:30VACrms(50/60Hz)or60VDC(Maximumcommonmodenoisevoltageformeasuringinput:250VACrms)

• Maximumvoltagebetweenmeasuringinputchannels:30VACrms(50/60Hz)or60VDC(Maximumcommonmodenoisevoltagebetweenmeasuringinputchannels:250VACrms(60VACrmsforlow-voltagerelaytype)

• Referencejunctioncompensationaccuracy: Whenmeasuringtemperaturegreaterthan

orequalto0°Candwheninputterminaltemperatureisbalanced

TypeK,E,J,T,N,XKGOST:±0.5°C(23°C±2°C),±0.7°C(0to50°C),±1.0°C(-20to60°C)

TypeR,S,W,L,U,W97Re3-W75Re25,Platinel2,NiNiMo,W/WRe26,N(AWG14):±1.0°C(23°C±2°C),±1.4°C(0to50°C),±2.0°C(-20to60°C)

TypeKpvsAu7Fe:±1.0K(23°C±2°C),±1.4K(0to50°C),±2.0K(-20to60°C)

TypeB,PR20-40:Internalreferencecompensationisfixedto0°C

• Samplinginterval/A/Dintegrationtime: 10ch.mode

Solid state relay scanner type*1 / Current scanner type*1

Sampling interval Integration time100ms/200ms 1.67ms

500msormore 16.7ms/20ms

1sormore 36.7ms

2sormore 100ms

ElectromagneticrelayscannertypeSampling interval Integration time

1sormore 16.7ms/20ms

2sormore 36.7ms

5 s 100ms

Scannertype(DCV/TC/DI,400VAC,1min)Sampling interval Integration time

500msormore 16.7ms/20ms

2sormore 36.7ms

5sormore 100ms

Page 5: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

5

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

2ch.mode*2

Sampling interval Integration time100msormore 16.7ms/20ms

1sormore 36.7ms

2sormore 100ms*1 In10chmode,whenthescanintervalissetto100

msor200ms,theA/Dintegrationtimeisfixedat1.67ms.Thispreventspowerfrequencynoisefrombeingeliminated,causingmeasuredvaluesto wobble.

*2 Cannotbespecifiedfortheelectromagneticrelayscannertype(TypeSuffixCode:-T1),Lowwithstandvoltagerelaytype(TypeSuffixCode:-L1).

• Calibrationcorrection: Mode:LinearizerApproximation,LinearizerBias Numberofsetpoints:12

• Terminaltype*:M3screwterminalorClampterminal* M3screwterminalsonlyfortheelectromagnetic

relay scanner type.• Withstandvoltage Universal,Solidstaterelayscannertype,

Electromagneticrelayscannertype;betweentheinputcircuitsandtheinternalcircuit:3000VACforoneminute

Current,Scannertype,lowwithstandvoltagetype;betweentheinputcircuitsandtheinternalcircuit:1500VACforoneminute

Betweentheanaloginputchannels:1000VACforoneminute(excludingb-terminal)

• Insulationresistance: Betweentheinputterminalandtheinternalcircuit:20MΩorgreaterat500VDC

• Recommendedreplacementperiodofelectromagneticrelayscannertypemodules:

Electromagneticrelayscannertypemodulesmakemeasurementsbyswitchingmechanicalcontactrelaysonandoff.

Toensurethatthemodulescontinuetooperatereliablyandcorrectly,replacethem

Continuoususeatmeasurementinterval1s:1year Continuoususeatmeasurementinterval2s:2years Continuoususeatmeasurementinterval5s:5years

Safety and EMC Standards• CSA:CSA22.2No.61010-1,installationcategory

II *1, pollution degree 2 *2, and CSA-C22.2 NO. 61010-2-030-12

• UL:UL61010-1,UL61010-2-030(CSANRTL/C)• CE: EMCdirective EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1 Lowvoltagedirective EN61010-1, EN 61010-2-030 Installation category II *1

Pollution degree 2 *2

MeasurementcategoryII*3• Maximuminputvoltageformeasuringinput:±60VDC• Maximumcommonmodenoisevoltagefor

measuringinput:30VACrms50/60Hzor60VDC(However,maximumcommonmodenoisevoltageformeasuringinput:250VAC)

• EMCRegulatoryArrangementinAustraliaandNewZealand(RCM):EN55011compliance,Class A Group 1

• KCmarking:Electromagneticwaveinterferencepreventionstandard,electromagneticwaveprotectionstandardcompliance*1 Installationcategory(overvoltagecategory)II: Describesanumberwhichdefinesatransient

overvoltagecondition. Impliestheregulationforimpulsewithstandvoltage. “II”appliestoelectricalequipmentwhich

issuppliedfromthefixedinstallationlikeadistribution board.

*2 Pollutiondegree2: Describes the degree to which a solid, liquid,

or gas which deteriorates dielectric strength or surfaceresistivityisadhering.

“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.

*3 MeasurementcategoryII(CATII): Appliestomeasuringcircuitsconnectedtolow

voltageinstallation,andelectricalinstrumentssuppliedwithpowerfromfixedequipmentsuchaselectric switchboards.

• WEEEDirective:Compliant

Construction• Frontpanel(terminal):Wateranddust-proof,

ComplieswithIEC529-IP20• Material:Polycarbonate• Color;

Front:Charcoalgreylight(CC28) Bezel:Smokeblue(CC53)

• Dimensions:45mm(W)x100mm(H)x133mm(D)(D:includingterminalcover)

• Weight:Approx.0.3kg

Power Supply SuppyfromGX/GPmainunitorGX60expandable

I/O.• Powerconsumption: GX90XA-10-U2:0.7Worless GX90XA-10-T1:0.9Worless GX90XA-10-C1:0.7Worless GX90XA-10-L1:0.7Worless

Isolation

Functional insulation

Reinforced insulation

Analog input CH1Analog input CH2Analog input CH3Analog input CH4Analog input CH5Analog input CH6Analog input CH7Analog input CH8Analog input CH9Analog input CH10

Input circuit Internal circuit

Page 6: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

6

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

Terminal arrangementsM3 screw terminal

No. Symbol No. Symbol No. Symbol301 CH1(/b)*1 201 CH1(-/B) 101 CH1(+/A)

302 CH2(/b)*1 202 CH2(-/B) 102 CH2(+/A)

303 CH3(/b)*1 203 CH3(-/B) 103 CH3(+/A)

304 CH4(/b)*1 204 CH4(-/B) 104 CH4(+/A)

305 CH5(/b)*1 205 CH5(-/B) 105 CH5(+/A)

306 CH6(/b)*1 206 CH6(-/B) 106 CH6(+/A)

307 CH7(/b)*1 207 CH7(-/B) 107 CH7(+/A)

308 CH8(/b)*1 208 CH8(-/B) 108 CH8(+/A)

309 CH9(/b)*1 209 CH9(-/B) 109 CH9(+/A)

310 CH10(/b)*1 210 CH10(-/B) 110 CH10(+/A)

*1 "NC"(Notconnected)fortheelectromagneticrelayscannertype,thelowwithstandvoltagetype, and the current scanner type.

* RTDinputterminalbisshortedinternallyacrossall channels.

Clamp terminal (Except Electromagnetic relay scanner type)

No. Symbol No. Symbol201 CH2(+/A) 101 CH1(+/A)

202 CH2(-/B) 102 CH1(-/B)

203 CH2(/b)*1 103 CH1(/b)*1

204 CH4(+/A) 104 CH3(+/A)

205 CH4(-/B) 105 CH3(-/B)

206 CH4(/b)*1 106 CH3(/b)*1

207 CH6(+/A) 107 CH5(+/A)

208 CH6(-/B) 108 CH5(-/B)

209 CH6(/b)*1 109 CH5(/b)*1

210 CH8(+/A) 110 CH7(+/A)

211 CH8(-/B) 111 CH7(-/B)

212 CH8(/b)*1 112 CH7(/b)*1

213 CH10(+/A) 113 CH9(+/A)

214 CH10(-/B) 114 CH9(-/B)

215 CH10(/b)*1 115 CH9(/b)*1

*1 "NC"(Notconnected)fortheelectromagneticrelayscannertype,thelowwithstandvoltagerelay type, and the current scanner type.

* RTDinputterminalbisshortedinternallyacrossallchannels.

A/D Calibration Value TwotypesofA/Dcalibrationvalues(factory

shipmentsettingandusersetting)canbesaved.Iftheusersettingisnotproper,itcanberestoredtothecalibrationvalueatfactoryshipment.

External DimensionsM3 screw terminal

107.

1(4.

22)

26(1

.02)

92(3

.62)

100(

3.94

)3(

0.12

)8(

0.31

)

(0.0

7)1.

9

45.1(1.78)

43.8(1.72)

Unit: mm(approx. inch)

Clamp terminal

107.

1(4.

22)

26(1

.02)

92(3

.62)

100(

3.94

)3(

0.12

)8(

0.31

)

(0.0

7)1.

9

45.1(1.78)

43.8(1.72)

Unit: mm(approx. inch)

Normal Operating Conditions• Powersupplyvoltage:100to240VAC±10%• Powersupplyfrequency:50/60Hz±2%• Ambienttemperature:0to50°C• Ambienthumidity:20to80%RH(at5to40°C)

(nocondensation)• Magneticfield:400A/morless(DCand50/60

Hz)• Vibration(IEC-60068-2-6):

Power supply ON, 3 directions, 10 cycles, 1 oct/min(±10%)

5≤f<8.4Hzamplitude3.5mm(peak) 8.4≤f≤160Hzacceleration9.8m/s2(peak)• Shock(IEC-60068-2-27):

Non-energization,500m/s2,approximate10ms,6directions(±X,±Y,±Z),3timesineachdirection

• Mountingposition:Canbeinclinedupto30degreesbackward.Leftandrighthorizontal.

• Altitude:2000morless

Page 7: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

7

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

• Installationlocation:Indoors• Warm-uptime:Atleast30minutesafterpower

on

Transport and Storage Conditions• Ambienttemperature:–25to60°C• Ambienthumidity:5to95%RH(no

condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged

condition)

Effects of Operating Conditions• Influenceofambienttemperature:variation

againstachangeof10°Catanaccumulationtimeof16.67msormore±(0.05%ofrdg+0.05%ofrange)orbelow. (Incaseofcurrentscannertype,±(0.075%ofrdg+0.05%ofrange)orbelow.)

KpvsAu7Fe,PR20-40:±(0.05%ofrdg+0.1%)orbelow,Cu10Ω:±(0.2%ofrdg+0.1°C)orbelow Noreferencecontactaccuracyisguaranteed.

• Influenceofpowersupplyvoltagevariation:Accuracyissatisfiedintherangeofratedpowersupplyvoltage.

• Influenceofexternalmagneticfield:VariationsagainstanACexternalmagneticfield(50/60Hz,400A/m)are±(0.1%ofrdg+0.1%)orbelow.

Page 8: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

8

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

DIGITAL INPUT MODULE (Model GX90XD or GX/GP main unit options /CRx1)

GX90XD

• Application:Remotecontrolinput,etc• Numberofinputs:16• Measurementinterval:100ms(shortest)• Inputtype:OpencollectororVoltage-freecontact• Insulationtype:Photocoupler,Trance(power

supply)• Contactrating:12VDC,20mAormore• Inputresistance:Approx.1kΩ• Allowableinputvoltage:10V• ON/OFFdetection Opencollectorcontactinput:

VoltageinONstate:0.5VDCorlessLeakagecurrentinOFFstate:0.5mAorless

Voltage-freecontactinput:ContactresistanceinONstate:200ΩorlessContactresistanceinOFFstate:50kΩor

more• Numberofcommon:2(1point/8channels)• Terminaltype:M3screwterminalorClamp

terminal (IncaseofOptions/CRx1,adigitalinputmodulehasM3screwterminals.)

• Withstandvoltage Betweentheinputterminalsandtheinternal

circuit:1500VACforoneminute• Insulationresistance:

Betweentheinputterminalsandtheinternalcircuit:20MΩorgreaterat500VDC

Safety and EMC Standards• CSA:CSA22.2No.61010-1,installationcategory

II(*1),pollutiondegree2(*2)• UL:UL61010-1(CSANRTL/C)• CE: EMCdirective EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1 Lowvoltagedirective EN61010-1 InstallationcategoryII(*1) Pollutiondegree2(*2) Notincludedinthemeasurementcategory• EMCRegulatoryArrangementinAustraliaand

NewZealand(RCM):EN55011compliance,Class A Group 1

• KCmarking:Electromagneticwaveinterferencepreventionstandard,electromagneticwaveprotectionstandardcompliance

*1 Installationcategory(overvoltagecategory)II: Describesanumberwhichdefinesatransient

overvoltagecondition. Impliestheregulationforimpulsewithstand

voltage. “II”appliestoelectricalequipmentwhich

issuppliedfromthefixedinstallationlikeadistribution board.

*2 Pollutiondegree2: Describes the degree to which a solid, liquid,

or gas which deteriorates dielectric strength or surfaceresistivityisadhering.

“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.

• WEEEDirective:Compliant

Construction• Frontpanel(terminal):Wateranddust-proof,

ComplieswithIEC529-IP20• Material:Polycarbonate• Color;

Front:Charcoalgreylight(CC28) Bezel:Smokeblue(CC53)

• Dimensions:45mm(W)x100mm(H)x133mm(D)(D:includingterminalcover)

• Weight:Approx.0.3kg

Power Supply SuppyfromGX/GPmainunitorGX60expandable

I/O.• Powerconsumption:0.7Worless

Isolation

Digital input CH1Digital input CH2Digital input CH3Digital input CH4Digital input CH5Digital input CH6Digital input CH7Digital input CH8Digital input CH9Digital input CH10Digital input CH11Digital input CH12Digital input CH13Digital input CH14Digital input CH15Digital input CH16

Non-isolated

Functional insulation

Reinforced insulation

Input circuit Internal circuit

Page 9: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

9

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

Terminal arrangementsM3 screw terminal/Clamp terminal

No. Symbol No. Symbol21 DI9 11 DI1

22 DI10 12 DI2

23 DI11 13 DI3

24 DI12 14 DI4

25 DI13 15 DI5

26 DI14 16 DI6

27 DI15 17 DI7

28 DI16 18 DI8

29 COM 19 COM

30 - 20 -

External DimensionsM3 screw terminal

97.1

(3.8

2)

82.1

(3.2

3)

36(1

.42)

92(3

.62)

100(

3.94

)3(

0.12

)8(

0.31

)

(0.0

7)1.

9

45.1(1.78)

31.9(1.26)

Unit: mm(approx. inch)

Clamp terminal

97.1

(3.8

2)

82.1

(3.2

3)

36(1

.42)

92(3

.62)

100(

3.94

)3(

0.12

)8(

0.31

)

(0.0

7)1.

9

45.1(1.78)

31.9(1.26)

Unit: mm(approx. inch)

Normal Operating ConditionsSameastheGX90XA.

Transport and Storage ConditionsSameastheGX90XA.

Page 10: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

10

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

DIGITAL OUTPUT MODULE (Model GX90YD, or GX/GP main unit options /CR1x, /CR2x, /CR4x)

GX90YD

• Application:Alarmoutput,etc• Numberofoutputs:6• Outputupdateinterval:100ms(shortest)• Outputtype:Relaycontactoutput,SPDT(NO-C-

NC)• Insulationtype:Mechanical• Ratedloadvoltage:30VDCor250VACorless• Max.loadcurrent:3A(DC)/3A(AC),resistance

load, each channel• Min.loadvoltage/current:5VDC/10mA• Recommendedreplacementperiodsofcontact:

Mechanical5,000,000moreON-OFFoperations Electrical30,000moreON-OFFoperations(250

VAC3Aor30VDC3A,resistanceload)• Numberofcommon:6• Powersupply:Notnecessary• Terminaltype:M3screwterminal• Withstandvoltage Betweentheoutputterminalsandtheinternal

circuit:3000VACforoneminute• Insulationresistance:

Betweentheoutputterminalsandtheinternalcircuit:20MΩorgreaterat500VDC

Safety and EMC Standards• SafetyandEMCStandards:Sameasthedigital

inputmodule• WEEEDirective:Compliant

Construction• Frontpanel(terminal):Wateranddust-proof,

ComplieswithIEC529-IP20• Material:Polycarbonate• Color;

Front:Charcoalgreylight(CC28) Bezel:Smokeblue(CC53)

• Dimensions:45mm(W)x100mm(H)x133mm(D)(D:includingterminalcover)

• Weight:Approx.0.3kg

Power Supply SuppyfromGX/GPmainunitorGX60expandable

I/O.• Powerconsumption:1.4Worless

Isolation

Digital output CH1Digital output CH2Digital output CH3Digital output CH4Digital output CH5Digital output CH6

Output circuit Internal circuit

Functional insulation

Reinforced insulation

Terminal arrangementsM3 screw terminal

No. Symbol No. Symbol21 DO4 N.C. 11 DO1 N.C.

22 DO4 COM 12 DO1 COM

23 DO4 N.O. 13 DO1 N.O.

24 DO5 N.C. 14 DO2 N.C.

25 DO5 COM 15 DO2 COM

26 DO5 N.O. 16 DO2 N.O.

27 DO6 N.C. 17 DO3 N.C.

28 DO6 COM 18 DO3 COM

29 DO6 N.O. 19 DO3 N.O.

30 - 20 -

External DimensionsM3 screw terminal

97.1

(3.8

2)

82.1

(3.2

3)

36(1

.42)

92(3

.62)

100(

3.94

)3(

0.12

)8(

0.31

)

(0.0

7)1.

9

45.1(1.78)

31.9(1.26)

Unit: mm(approx. inch)

Normal Operating ConditionsSameastheGX90XA.

Transport and Storage ConditionsSameastheGX90XA.

Page 11: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

11

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

DIGITAL INPUT/OUTPUT MODULE (Model GX90WD)

GX90WD

Digitalinput/outputmodulecanbeusedonemoduleonGX/GPmainunitorExpandableI/O.

Digital Input Specifications• Application:Remotecontrolinput,etc• Numberofinputs:8• Measurementinterval:100ms(shortest)• Inputtype:OpencollectororVoltage-freecontact• Insulationtype:Photocoupler,Trance(power

supply)• Contactrating:Useanexternalcontactof12

VDCand20mAormore.• Inputresistance:Approx.2.4kΩ• Allowableinputvoltage:10V• ON/OFFdetection Opencollectorcontactinput:

VoltageinONstate:0.5VDCorlessLeakagecurrentinOFFstate:0.5mAorless

Voltage-freecontactinput:ContactresistanceinONstate:200ΩorlessContactresistanceinOFFstate:50kΩor

more• Numberofcommon:1(1point/8channels)• Terminaltype:M3screwterminal• Withstandvoltage Betweentheinputterminalsandtheinternal

circuit:1500VACforoneminute• Insulationresistance:

Betweentheinputterminalsandtheinternalcircuit:20MΩorgreaterat500VDC

Digital Output Specifications• Application:Alarmoutput,etc• Numberofoutputs:6• Outputupdateinterval:100ms(shortest)• Outputtype:Relaycontactoutput,SPDT(NO-C-

NC)• Insulationtype:Mechanical• Ratedloadvoltage: Max.150VACwhenconnectedtothemain

circuit(primarypowersource),Max.250VACwhenconnectedtoacircuit(secondarypowersource)derivedfromthemaincircuit,

orMax.30VDC• Max.loadcurrent:2A(DC)/2A(AC),resistance

load, each channel• Min.loadvoltage/current:5VDC/10mA• Recommendedreplacementperiodsofcontact:

Mechanical5,000,000moreON-OFFoperations Electrical30,000moreON-OFFoperations(250

VAC2Aor30VDC2A,resistanceload)• Numberofcommon:6(All-contactindependent)• Terminaltype:M3screwterminal

• Withstandvoltage Betweentheoutputterminalsandtheinternal

circuit:2700VACforoneminute• Insulationresistance:

Betweentheoutputterminalsandtheinternalcircuit:20MΩorgreaterat500VDC

Safety and EMC Standards• SafetyandEMCStandards:Sameasthedigital

inputmodule• WEEEDirective:Compliant

Construction• Frontpanel(terminal):Wateranddust-proof,

ComplieswithIEC529-IP20• Material:Polycarbonate• Color;

Front:Charcoalgreylight(CC28) Bezel:Smokeblue(CC53)

• Dimensions:45mm(W)x100mm(H)x133mm(D)(D:includingterminalcover)

• Weight:Approx.0.3kg

Power Supply SuppyfromGX/GPmainunitorGX60expandable

I/O.• Powerconsumption:1.6Worless

Isolation

Functional insulation

Digital input CH1-CH8

Reinforced insulation

Digital output CH1Digital output CH2Digital output CH3Digital output CH4Digital output CH5Digital output CH6

Output circuit

Input circuit

Internal circuit

Terminal arrangementsM3 screw terminal

No. Symbol No. Symbol No. Symbol301 DI3 201 DI2 101 DI1

302 DI6 202 DI5 102 DI4

303 DI COM 203 DI8 103 DI7

304 NC 204 NC 104 NC

305 DO1 N.O. 205 DO1 COM 105 DO1 N.C.

306 DO2 N.O. 206 DO2 COM 106 DO2 N.C.

307 DO3 N.O. 207 DO2 COM 107 DO3 N.C.

308 DO4 N.O. 208 DO4 COM 108 DO4 N.C.

309 DO5 N.O. 209 DO5 COM 109 DO5 N.C.

310 DO6 N.O. 210 DO6 COM 110 DO6 N.C.

Page 12: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

12

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

External DimensionsM3 screw terminal

107.

1(4.

22)

26(1

.02)

92(3

.62)

100(

3.94

)3(

0.12

)8(

0.31

)

(0.0

7)1.

9

45.1(1.78)

43.8(1.72)

Unit: mm(approx. inch)

Normal Operating ConditionsSameastheGX90XA.

Transport and Storage ConditionsSameastheGX90XA.

Page 13: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

13

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

MODEL AND SUFFIX CODESAnalog input module, Digital I/O module (sold separately):MODEL and SUFFIX Code (GX90XA)

Model Suffix Code DescriptionGX90XA AnalogInputModuleforGX/GPseries

Numberofchannels -10 10 channels

Type -C1 Current,scannertype(isolatedbetweenchannels)

-L1 LowwithstandvoltageDCV/TC/DI,scannertype(isolatedbetweenchannels)

-U2 Universal,Solidstaterelayscannertype(3-wireRTDb-terminalcommon)

-T1 DCV/TC/DI,Electromagneticrelayscannertype(Isolatedbetweenchannels)

- N Always N

Terminalform -3 Screwterminal(M3)

-C Clampterminal*

Area N General* Cannotbespecifiedfortheelectromagneticrelayscannertype.

MODEL and SUFFIX Code (GX90XD)Model Suffix Code Description

GX90XD DigitalInputModuleforGX/GPseries

Numberofchannels -16 16 channels

Type -11 Opencollector/Non-voltage,contact(sharedcommon),Rated5VDC

- N Always N

Terminalform -3 Screwterminal(M3)

-C Clampterminal

Area N General

MODEL and SUFFIX Code (GX90YD)Model Suffix Code Description

GX90YD DigitalOutputModuleforGX/GPseries

Numberofchannels -06 6 channels

Type -11 Relay,SPDT(NO-C-NC)

- N Always N

Terminalform -3 Screwterminal(M3)

Area N General

MODEL and SUFFIX Code (GX90WD)Model Suffix Code Description

GX90WD DigitalIutput/OutputModuleforGX/GPseries

Numberofchannels -0806 8 channel DIs, 6 channel DOs

Type -01 Opencollector/non-voltagecontact(sharedcommon),rated5VDC;Relay,SPDT(NO-C-NC)

- N Always N

Terminalform -3 Screwterminal(M3)

Area N General

Page 14: GX90XA/GX90XD/GX90YD/GX90WD I/O ModulesThe GX90WD digital input/output module provides eight digital inputs and six relay outputs. When there are small amounts of digital inputs and

14

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May. 7, 2014-00

Optional Accessories (Sold Separately)Product Model/part no.

ShuntresisterforM3terminal(10Ω±0.1%) X010-010-3

ShuntresisterforM3terminal(100Ω±0.1%) X010-100-3

ShuntresisterforM3terminal(250Ω±0.1%) X010-250-3

ShuntresisterforClampterminal(10Ω±0.1%) 438922

ShuntresisterforClampterminal(100Ω±0.1%) 438921

ShuntresisterforClampterminal(250Ω±0.1%) 438920

Calibration certificate (sold separately)WhenorderingtheGX10/GX20/GP10/GP20withoptions(analoginput),thecalibrationcertificateforthemodulesisincludedinandshippedwiththecalibrationcertificateofthemainunit.Whenorderingananaloginputmodule,eachmodulegetsitsowncalibrationcertificate(onecertificatepermodule).

Test certificate (QIC, sold separately)WhenorderingtheGX10/GX20/GP10/GP20withoptions(analog/digialI/O),theQICforeachmoduleisincludedinandshippedwiththeQICofthemainunit.WhenorderinganaloginputmodulesanddigitalI/Omodules,eachmodulegetsitsownQIC(oneQICpermodule).

User's ManualProductuser'smanualscanbedownloadedorviewedatthefollowingURL.Toviewtheuser'smanual,youneedtouseAdobeReader7orlaterbyAdobeSystems.URL: www.smartdacplus.com/manual/en/

Product Purchase SpecificationsTheGX10/GX20/GP10/GP20iscomposedofthemainunit,I/Omodules,theexpandableI/O,andtheexpansionmodule.TherearetwowaystopurchaseI/Omodules.OnewayistopurchasethemindividuallybyspecifyingmodelsGX90XA,GX90XD,GX90YD,andGX90WD.Theotherwayistopurchasethemasanoption(/UCxxor/USxx).Purchasingthemasanoptionisconvenient,butthisplaceslimitationsonthenumberofanaloginputsthatyoucanobtain.Ifyouwanttousemorethan51channels,pleasepurchasetheI/Omodulesindividually.

Trademarks TheTCP/IPsoftwareusedinthisproductandthedocumentforthatTCP/IPsoftwarearebasedinpartonBSDnetworkingsoftware,Release1licensedfromTheRegentsoftheUniversityofCalifornia.

•SMARTDAC+isaregisteredtrademarkofYokogawaElectricCorporation.•Microsoft,MSandWindowsareregisteredtrademarksofMicrosoftCorporationUSA.•PentiumareregisteredtrademarksofIntelCorporation.•EthernetisaregisteredtrademarkofXEROXCorporation.ModbusisaregisteredtrademarkofAEGSchneider.•Othercompanyand/orproductnamesareregisteredtrademarkoftheirmanufactures.