GeneralSpecifications
GX90XA/GX90XD/GX90YD/GX90WD/GX90XP/GX90YAI/O Modules
Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
GS 04L53B01-01EN
GS 04L53B01-01EN©Copyright April 2014
11th Edition May 31, 2021
OVERVIEWI/O modules are connected to the GX/GP, Expandable I/O unit, GM main unit, and GM sub unit.● Amoduletypeisseventypes,ananaloginput,a
analog output, a digital input, a digital output, a digital input/output and a pluse input PID control*.* For the GX90UT PID Control Module, please
see GX90UT PID Control Module General Specifications(GS04L53B01-31EN.)
● Inputandoutputhavemodulestructureanditcanextendthemeasily.
● TheGX90XAanaloginputmodulehasthefollowingtypes;(1)universaltypethatallowsthemeasurementinputforDCV(directvoltage),TC(thermocouple),RTD(resistancetemperaturedetector),andDI(contactorTTLlevelvoltage),(2)current input type with the built-in shunt resistor to directlyinputastandardsignalof4-20mADC,(3)electromagneticrelayscannertypeinsusceptibletonoisesthatallowsthemeasurementinputforDCV,TC,andDI,(4)lowwithstandvoltagerelaytypethatoffersalowcost,(5)highwithstandvoltagetypethat600Vwithstandvoltagebetweeninputterminaland ground.
The GX90XA-04-H0 high-speed analog input modulecanmeasureDCV(DCvoltage),TC(thermocouple),RTD(resistancetemperaturedetector),DI(contactorTTLlevelvoltage)inputsattheshortestintervalof1ms.IthasanA/Dconverterforeachinputchannelandemploysascannerlessmethod,whichislesssusceptibletohighfrequencynoise.
TheGX90XA-06-R14-wireRTD/resistanceinputmodulecanreceiveinputfrom4-wireRTDsor4-wire resistors.
Ineachsystem,ameasurementinputsignalcanbeassigned to each channel.
● TheGX90YAanalogoutputmoduleiscapableofretransmissionoutputofvarioustypesofchannelsandalsomanualoutput.Itprovidescurrentoutputwith channels that are isolated.
● TheGX90XDdigitalinputmodule,whichallowsupto 16 digital inputs or pulse inputs, can be used as amultipointdigitalinputorpluseinput.Thismodulecanalsobeusedasaremotecontrolinput.
● TheGX90YDdigitaloutputmoduleisassignedasarelayoutput(contactC)andisusedwhenanalarmactivates.Itcanalsobeusedtoturntheoutputonandoffmanuallyusingthetouchpanel.
● TheGX90WDdigitalinput/outputmoduleprovideseight digital inputs or pulse inputs and six relay outputs.Whentherearesmallamountsofdigitalinputs and digital outputs, you do not need to mounttwomodules.Thisenablesefficientchannelconfiguration.
● GX90XPpulseinputmodulecanreceiveupto10pulseinputs.Themaximuminputfrequencyis20kHz.Themodulecanbeusedtointegratepulsesignalsfromflowmetersorthelike.**Integrationrequiresthemathfunction(/MToption).
● EachmoduleprovidesaM3screwterminalandclampterminal*.Also,theinputterminalcanberemovedandmounted.Thisenableswiringworktobecarriedoutefficiently.
* GX90YD and GX90WD are only M3 screw terminal.
● Themeasuringaccuraciesnotedinthegeneralspecificationshaveamarginoferrorthattakesintoaccounttheproduct'scomponentsandtheequipmentusedforadjustmentandtesting.However,theactualvaluescalculatedfromtheaccuracytestingdatauponshipmentoftheinstrumentfromthefactoryareasfollows.
Input Type Measuring accuracy*1 (typical value*2)
DCV 20mV ±(0.01%ofrdg+5μV)60mV ±(0.01%ofrdg+5μV)6V(1-5V) ±(0.01%ofrdg+2mV)
TC*3 R, S ±1.1°CB ±1.5°CK(−200.0to1370.0°C)
±(0.01%ofrdg+0.2°Cfor0.0to1370.0°C; ±(0.15%ofrdg+0.2°C)for-200.0to 0.0°C
K(−200.0to500.0°C)
±0.2°C for 0.0 to 500.0°C; ±(0.15%ofrdg+0.2°C)for-200.0to 0.0°C
J ± 0.2°C for 0.0 to 1100.0 °C; ±(0.10%ofrdg+0.2°C)for-200.0to 0.0 °C
T ± 0.2°C for 0.0 to 400.0°C; ±(0.10%ofrdg+0.2°C)for-200.0to 0.0 °C
N ±(0.01%ofrdg+0.2°C)for0.0to1300.0 °C; ±(0.22%ofrdg+0.2°C)for-200.0to 0.0 °C
RTD Pt100(-200.0to850.0°C)
±(0.02%ofrdg+0.2°C)
Pt100(highresolution) (-150.00to150.00°C)
±(0.02%ofrdg+0.16°C)
rdg:Readingvalue
*1 AppliestoGX90XA-10-U2,A/Dintegrationtime16.67msormore,Generaloperatingconditions:23±2ºC,55±10%RH,supplyvoltage90–132,180–264VAC,powerfrequencywithin50/60Hz±1%,warm-upof30minutesormore,novibrationsorotherhindrancestoperformance.
*2 Forthemeasuringaccuracy(guaranteed),seepage 3 to 4.
*3 Thesevaluesdonotincludethereferencejunctioncompensationaccuracy.
2
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
INPUT/OUTPUT MODULE SPECIFICATIONS
ANALOG INPUT MODULE (Model GX90XA or GX/GP main unit options /Uxx0)
Thefollowingnotationsareusedtodistinguishthevarioustypes.Type Suffix Code Notation
-U2 Universal
-C1 Current(mA)input
-L1 Lowwithstandvoltagerelay
-T1 Electromagneticrelay
-H0 High-speeduniversal
-R1 4-wireRTD/resistance
-V1 Highwithstandvoltage
• Input Type:
Suffix Code Input Type
Number of inputs
Description (Type)
-U2 DCvoltage,standardsignal,thermocouple(TC),resist-ancetemperaturedetector(RTD),DI(voltage,contact),andDCcurrent(byaddinganexternalshuntresistor)
10 Universal
-C1 DCcurrent(mA),DCcurrentstandardsignal(4-20mA) 10 Current(mA)input
-L1 DCvoltage,standardsignal,thermocouple(TC),DI(voltage,contact),andDCcurrent(byaddinganexter-nalshuntresistor)
10 Lowwithstandvoltagerelay
-T1 DCvoltage,standardsignal,thermocouple(TC),DI(voltage,contact),andDCcurrent(byaddinganexter-nalshuntresistor)
10 Electromagneticrelay
-H0 DCvoltage,standardsignal,thermocouple(TC),resist-ancetemperaturedetector(RTD),DI(voltage,contact),andDCcurrent(byaddinganexternalshuntresistor)
4*1 High-speeduniversal
-R1 4-wireRTD,4-wireresistance 6 4-wireRTD/resistance
-V1 DCvoltage,standardsignal,thermocouple(TC),DI(voltage,contact),andDCcurrent(byaddinganexter-nalshuntresistor)
10 Highwithstandvoltage
*1 However,1pointwhenthescanintervalis1msand2pointswhenitis2ms.• Inputformat:Floatingunbalanced,isolationbetweenchannels(excludingthebterminalonuniversalandlow
withstandvoltagerelaytype)• Measurementinterval:1,2,5,10,20,50,100,200,500ms,1,2,5s(Seethetablebelow.) Scanintervalbymodule
Suffix CodeScan interval
1 ms 2 ms 5 ms 10 ms 20 ms 50 ms 100 ms 200 ms 500 ms 1 s 2 s 5 s-U2 – – – – – –
-C1 – – – – – –
-L1 – – – – – – – –
-T1 – – – – – – – – –
-H0
-R1 – – – – – –
-V1 – – – – – –
• Inputrange:-5%ormoreand105%orless(accuracyisguaranteedintherangefrom0%to100%inclusive)• Operationmode Itispossibletoswitchtoamodethatmakesmeasurementsbyreducingthesupplyfrequencynoise.
Suffix Code Operation mode-U2 2chOnly,Lownoisemodeor10chNormalmode-C1 2chOnly,Lownoisemodeor10chNormalmode-L1 –-T1 –-H0 –-R1 2chOnly,Lownoisemodeor6chNormalmode-V1 2chOnly,Lownoisemodeor10chNormalmode
GX90XA
3
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
• Measurementrangesandaccuracies*2(However,thenumberofdisplaydigitscanbeincreasedbyscaling.)*2 Thefollowingspecificationsapplytooperationoftherecorderunderstandardoperationconditions. Temperature:23±2°C,Humidity:55%±10%RH,Powersupplyvoltage:90to132or180to264VAC,Powersupply
frequency:50/60Hz±1%,Warm-uptime:Atleast30min.Otherambientconditionssuchasvibrationshouldnotadverselyaffectrecorderoperation.
Referencejunctioncompensationaccuracyisnotincludedforthermocouples.Universal, Current (mA) input, Low withstand voltage relay, Electromagnetic relay, 4-wire RTD/resister, High withstand voltage type
Input Type Range Measurement range
Measurement accuracy (digital display) Max. resolution of digital display
A/D integration time: 16.7ms or more *22 A/D integration time: 1.67ms *23
DCV 20mV -20.000 to 20.000mV ±(0.05%ofrdg+12μV) ±(0.1%ofrdg+40μV) 1μV60mV -60.00 to 60.00mV ±(0.05%ofrdg+0.03mV) ±(0.1%ofrdg+0.15mV) 10μV200mV -200.00 to 200.00mV ±(0.05%ofrdg+0.03mV) ±(0.1%ofrdg+0.4mV) 10μV1V -1.0000 to 1.0000V ±(0.05%ofrdg+1.2mV) ±(0.1%ofrdg+4mV) 100μV2V -2.0000 to 2.0000V ±(0.05%ofrdg+1.2mV) ±(0.1%ofrdg+4mV) 100μV6V -6.000 to 6.000V ±(0.05%ofrdg+3mV) ±(0.1%ofrdg+15mV) 1mV20V -20.000 to 20.000V ±(0.05%ofrdg+3mV) ±(0.1%ofrdg+40mV) 1mV50V -50.00 to 50.00V ±(0.05%ofrdg+0.03V) ±(0.1%ofrdg+0.15V) 10mV
Standard signal
0.4-2V 0.3200 to 2.0800V ±(0.05%ofrdg+1.2mV) ±(0.1%ofrdg+4mV) 100μV1-5V 0.800 to 5.200V ±(0.05%ofrdg+3mV) ±(0.1%ofrdg+15mV) 1mV
DC current 0-20mA 0.000 to 20.000mA ±(0.3%ofrdg+5μA) ±(0.3%ofrdg+90μA) 1μVDC current(standardsignal
4-20mA 3.200 to 20.800mA
TC(ExcludingRJCac-curacy)
R*3 0.0 to 1760.0 °C ±(0.15%ofrdg+1.0°C)However, R, S; 0.0 to 800.0°C: ±2.2°C, B; 400.0 to 800.0°C: ±3.0°CAccuracy at less than 400.0°C is not guaranteed.
±(0.2%ofrdg+6.0°C)However, R, S; 0.0 to 800.0°C: ±7.6°C, B; 400.0 to 800.0°C: ±11.0°CAccuracy at less than 400.0°C is not guaranteed.
0.1°CS *3 0.0 to 1760.0 °CB *3 0.0 to 1820.0 °C
K *3 -270.0 to 1370.0 °C ±(0.15%ofrdg+0.7°C)However, -200.0 to 0.0°C: ±(0.35 % of rdg + 0.7°C)Accuracy at less than -200.0°C is not guaranteed
±(0.2%ofrdg+5.0°C)However, -200.0 to 0.0°C: ±(3 % of rdg + 5.0°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C-200.0 to 500.0 °C
E *3 -270.0 to 800.0 °C ±(0.15%ofrdg+0.5°C)However, -200.0 to 0.0°C: ±(0.35 % of rdg + 0.5°C)Accuracy at less than -200.0°C is not guaranteed
±(0.2%ofrdg+4.0°C)However, -200.0 to 0.0°C: ±(2 % of rdg + 4.0°C)Accuracy at less than -200.0°C is not guaranteed
0.1°CJ *3 -200.0 to 1100.0 °C
T *3 -270.0 to 400.0 °C ±(0.15%ofrdg+0.5°C)However, -200.0 to 0.0°C: ±(0.35 % of rdg + 0.5°C)Accuracy at less than -200.0°C is not guaranteed
±(0.2%ofrdg+2.5°C)However, -200.0 to 0.0°C: ±(2 % of rdg + 2.5°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C
N *3 -270.0 to 1300.0 °C ±(0.15%ofrdg+0.7°C)However, -200.0 to 0.0°C: ±(0.7 % of rdg + 0.7°C)Accuracy at less than -200.0°C is not guaranteed
±(0.3%ofrdg+6.0°C)However, -200.0 to 0.0°C: ±(5 % of rdg + 6.0°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C
W *4 0.0 to 2315.0 °C ±(0.15%ofrdg+1.5°C) ±(0.3%ofrdg+14.0°C)However,morethan1000.0°C:±(0.8%ofrdg+9.0°C)
0.1°C
L *5 -200.0 to 900.0 °C ±(0.15%ofrdg+0.5°C)Lessthan0.0°C:±(0.5%ofrdg+0.5°C)
±(0.2%ofrdg+4.0°C)Lessthan0.0°C:±(3%ofrdg+4.0°C)
0.1°C
U *5 -200.0 to 400.0 °C ±(0.15%ofrdg+0.5°C)Lessthan0.0°C:±(0.7%ofrdg+0.5°C)
±(0.2%ofrdg+2.5°C)Lessthan0.0°C:±(3%ofrdg+2.5°C)
0.1°C
WRe3-25*6 0.0 to 2320.0 °C ±(0.2%ofrdg+2.5°C) ±18.0°CMorethan2000.0°C:±0.9%ofrdg
0.1°C
KpvsAu7Fe*7 0.0 to 300.0 K ±(0.15%ofrdg+2.0K) ±(0.2%ofrdg+7.0K) 0.1 KPLATINEL II *7 0.0 to 1395.0 °C ±(0.25%ofrdg+2.3°C) ±(0.25%ofrdg+8.0°C) 0.1°CPR20-40*8 0.0 to 1900.0°C ±(0.7%ofrdg+0.4°C)
However, accuracy at less than 800.0°C is not guaranteed.
±20.0°CHowever, accuracy at less than 800.0°C is not guaranteed.
0.1°C
NiNiMo *7 0.0 to 1310.0°C ±(0.25%ofrdg+0.7°C) ±(0.5%ofrdg+5.0°C) 0.1°CW/WRe26*9 0.0 to 2320.0°C ±(0.2%ofrdg+2.0°C)
However, accuracy at less than 300.0°C is not guaranteed.
±(0.4%ofrdg+12.0°C)However, accuracy at less than 300.0°C is not guaranteed.
0.1°C
N(AWG14)*10 0.0 to 1300.0°C ±(0.2%ofrdg+1.3°C) ±(0.5%ofrdg+7.0°C) 0.1°CXK GOST *11 -200.0 to 600.0°C ±(0.25%ofrdg+0.8°C) ±(0.5%ofrdg+4.0°C) 0.1°C
RTD(Measuredcurrent:1mA)
Pt100 *12 -200.0 to 850.0°C ±(0.15%ofrdg+0.3°C) ±(0.3%ofrdg+1.5°C) 0.1°C-150.00 to 150.00°C 0.01°C
JPt100 *12 -200.00 to 550.00°C 0.1°C-150.00 to 150.00°C 0.01°C
Cu10 GE -200.0 to 300.0°C ±(0.2%ofrdg+2.0°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
±(0.4%ofrdg+6.0°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
0.1°CCu10 L&N -200.0 to 300.0°CCu10 WEED -200.0 to 300.0°CCu10 BAILEY -200.0 to 300.0°CCu10 at 20°Cα=0.00392
-200.0 to 300.0°C
Cu10 at 20°Cα=0.00393
-200.0 to 300.0°C
Cu25 at 0°Cα=0.00425
-200.0 to 300.0°C ±(0.3%ofrdg+0.8°C) ±(0.5%ofrdg+3.0°C) 0.1°C
Cu53 at 0°Cα=0.00426035
-50.0 to 150.0°C ±(0.15%ofrdg+0.8°C) ±(0.3%ofrdg+4.0°C) 0.1°C
Cu100 at 0°Cα=0.00425
-50.0 to 150.0°C ±(0.2%ofrdg+1.0°C) ±(0.4%ofrdg+5.0°C) 0.1°C
4
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
Continued
Input Type Range Measurement range
Measurement accuracy (digital display) Max. resolution of digital display
A/D integration time: 16.7ms or more *22 A/D integration time: 1.67ms *23
RTD(Measuredcurrent:1mA)
J263B *13 0.0 to 300.0 K ±1.0 KLess than 40.0 K: ±3.0 K
±3.0 KLess than 40.0 K: ±9.0 K
0.1 K
Ni100(SAMA) -200.0 to 250.0°C ±(0.15%ofrdg+0.4°C) ±(0.3%ofrdg+2.0°C) 0.1°CNi100(DIN)*14 -60.0 to 180.0°CNi120 *15 -70.0 to 200.0°CPt25 *16 -200.0 to 550.0°C ±(0.15%ofrdg+0.8°C) ±(0.3%ofrdg+4.0°C) 0.1°CPt50 *17 -200.0 to 550.0°C ±(0.3%ofrdg+0.6°C) ±(0.6%ofrdg+3.0°C) 0.1°CPt200 WEED -100.0 to 250.0°C ±(0.3%ofrdg+1.0°C)Cu10 GOST *18 -200.0 to 200.0°C ±(0.2%ofrdg+2.0°C) ±(0.4%ofrdg+6.0°C) 0.1°CCu50 GOST *19 -200.0 to 200.0°C ±(0.15%ofrdg+0.6°C) ±(0.3%ofrdg+4.0°C) 0.1°CCu100 GOST *20
-200.0 to 200.0°C ±(0.15%ofrdg+0.3°C) ±(0.3%ofrdg+1.5°C) 0.1°C
Pt46 GOST *19 -200.0 to 550.0°C ±(0.3%ofrdg+0.8°C) ±(0.6%ofrdg+4.0°C) 0.1°CPt100 GOST *20 -200.0 to 600.0°C ±(0.15%ofrdg+0.3°C) ±(0.3%ofrdg+2.0°C) 0.1°C
4-wireRTD(Measuredcurrent: 1mA)
Pt100*12 -200.0 to 850.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C-150.00 to 150.00°C 0.01°C
JPt100*12 -200.0 to 550.0°C 0.1°C-150.00 to 150.00°C 0.01°C
Cu10 GE -200.0 to 300.0°C ±(0.1%ofrdg+2.0°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
±(0.2%ofrdg+5.0°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
0.1°CCu10 L&N -200.0 to 300.0°CCu10 WEED -200.0 to 300.0°CCu10 BAILEY -200.0 to 300.0°CCu10 at 20°Cα=0.00392
-200.0 to 300.0°C
Cu10 at 20°Cα=0.00393
-200.0 to 300.0°C
Cu25 at 0°Cα=0.00425
-200.0 to 300.0°C ±(0.1%ofrdg+0.8°C) ±(0.2%ofrdg+2.0°C) 0.1°C
Cu53 at 0°Cα=0.00426035
-50.0 to 150.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°C
Cu100 at 0°Cα=0.00425
-50.0 to 150.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
J263B*13 0.0 to 300.0K ±0.4 KLess than 40.0 K: ±0.8 K
±1.5 KLess than 40.0 K: ±3.0 K
0.1K
Ni100(SAMA) -200.0 to 250.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°CNi100(DIN)*14 -60.0 to 180.0°C 0.1°CNi120*15 -70.0 to 200.0°C 0.1°CPt25*16 -200.0 to 550.0°C ±(0.1%ofrdg+0.8°C) ±(0.2%ofrdg+2.0°C) 0.1°CPt50*17 -200.0 to 550.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CPt200 WEED -100.0 to 250.0°C ±(0.05%ofrdg+1.0°C) ±(0.1%ofrdg+3.0°C) 0.1°CCu10 GOST*18 -200.0 to 200.0°C ±(0.1%ofrdg+2.0°C) ±(0.2%ofrdg+5.0°C) 0.1°CCu50 GOST*19 -200.0 to 200.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CCu100 GOST*20
-200.0 to 200.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
Pt46 GOST*19 -200.0 to 550.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CPt100 GOST*20 -200.0 to 600.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
4-wireRTD(Measuredcurrent: 0.25mA)
Pt500 -200.0 to 850.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°CPt1000 -200.0 to 850.0°C
Resistance(4-wire)
20Ω(Meas-ured current: 1mA)
0.0 to 20.000Ω ±(0.05%ofrdg+0.007Ω) ±(0.1%ofrdg+0.025Ω) 0.001Ω
200Ω(Meas-ured current: 1mA)
0.0 to 200.00Ω ±(0.05%ofrdg+0.03Ω) ±(0.1%ofrdg+0.15Ω) 0.01Ω
2000 Ω(Measuredcurrent: 0.25 mA)
0.0 to 2000.0Ω ±(0.05%ofrdg+0.3Ω) ±(0.1%ofrdg+1.0Ω) 0.1Ω
DI Level Thresholdlevel(Vth=2.4V)Accuracy:±0.1V -Contact *21 Lessthan1kΩ:1(ON),Morethan100kΩ:0(OFF)(parallelcapacitanceof0.01μF
orless)-
rdg:Readingvalue
5
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
High-speeduniversaltype
Input Type Range Measurement range
Measurement accuracy (digital display) Max. resolution of digital display
Scan interval: 50 ms or more(Only the Values in [ ] apply when the
scan interval is 50/100/200 ms)
Scan interval: 20 ms or less(Only the Values in [ ] apply when the
scan interval is 1/2/5 ms)DCV 20mV -20.000 to 20.000mV ±(0.05%ofrdg+5[12]μV) ±(0.1%ofrdg+25[40]μV) 1μV
60mV -60.00 to 60.00mV ±(0.05%ofrdg+0.02mV) ±(0.1%ofrdg+0.1mV) 10μV200mV -200.00 to 200.00mV ±(0.05%ofrdg+0.02[0.03]mV) ±(0.1%ofrdg+0.1[0.4]mV) 10μV1V -1.0000 to 1.0000V ±(0.05%ofrdg+0.2mV) ±(0.1%ofrdg+1.0mV) 100μV2V -2.0000 to 2.0000V ±(0.05%ofrdg+0.5[1.2]mV) ±(0.1%ofrdg+1.0[4.0]mV) 100μV6V -6.000 to 6.000V ±(0.05%ofrdg+2mV) ±(0.1%ofrdg+10mV) 1mV20V -20.000 to 20.000V ±(0.05%ofrdg+2[3]mV) ±(0.1%ofrdg+10[40]mV) 1mV50V -50.00 to 50.00V ±(0.05%ofrdg+0.02V) ±(0.1%ofrdg+0.10V) 10mV100V -100.00 100.00V ±(0.05%ofrdg+0.02V) ±(0.1%ofrdg+0.10V) 10mV
Standard signal
0.4-2V 0.3200 to 2.0800V ±(0.05%ofrdg+0.5[1.2]mV) ±(0.1%ofrdg+1.0[4.0]mV) 100μV1-5V 0.800 to 5.200V ±(0.05%ofrdg+2mV) ±(0.1%ofrdg+10mV) 1mV
TC(ExcludingRJCac-curacy)
R*3 0.0 to 1760.0 °C ±(0.05%ofrdg+1.0°C)However, R, S; 0.0 to 800.0°C: ±1.4°C, B; 400.0 to 800.0°C: ±1.5 [3.0] °CAccuracy at less than 400.0°C is not guaranteed.
±(0.1%ofrdg+4.0[6.0]°C)However, R, S; 0.0 to 800.0°C: ±4.8 [7.6] °C, B; 400.0 to 800.0°C: ±7.0 [11.0]°CAccuracy at less than 400.0°C is not guaranteed.
0.1°CS *3 0.0 to 1760.0 °CB *3 0.0 to 1820.0 °C
K *3 -270.0 to 1370.0 °C ±(0.05%ofrdg+0.7°C)However, -200.0 to 0.0°C: ±(0.2 % of rdg + 0.7°C)Accuracy at less than -200.0°C is not guaranteed
±(0.1%ofrdg+3.5°C)However, -200.0 to 0.0°C: ±(2 % of rdg + 3.5°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C-200.0 to 500.0 °C
E *3 -270.0 to 800.0 °C ±(0.05%ofrdg+0.5°C)However, -200.0 to 0.0°C: ±(0.2 % of rdg + 0.5°C)Accuracy at less than -200.0°C is not guaranteed
±(0.1%ofrdg+2.5°C)However, -200.0 to 0.0°C: ±(2 % of rdg + 2.5°C)Accuracy at less than -200.0°C is not guaranteed
0.1°CJ *3 -200.0 to 1100.0 °C
T *3 -270.0 to 400.0 °C ±(0.05%ofrdg+0.5°C)However, -200.0 to 0.0°C: ±(0.2 % of rdg + 0.5°C)Accuracy at less than -200.0°C is not guaranteed
±(0.1%ofrdg+2.5°C)However, -200.0 to 0.0°C: ±(2 % of rdg + 2.5°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C
N *3 -270.0 to 1300.0 °C ±(0.05%ofrdg+0.7°C)However, -200.0 to 0.0°C: ±(0.5 % of rdg + 0.7°C)Accuracy at less than -200.0°C is not guaranteed
±(0.1%ofrdg+4.0°C)However, -200.0 to 0.0°C: ±(3.5 % of rdg + 4.0°C)Accuracy at less than -200.0°C is not guaranteed
0.1°C
W *4 0.0 to 2315.0 °C ±(0.05%ofrdg+1.0°C)Morethan1000.0°C:±(0.15%ofrdg)
±(0.1%ofrdg+7.0°C)However,morethan1000.0°C:±(0.8%ofrdg)
0.1°C
L *5 -200.0 to 900.0 °C ±(0.05%ofrdg+0.5°C)Lessthan0.0°C:±(0.25%ofrdg+0.5°C)
±(0.1%ofrdg+2.5°C)Lessthan0.0°C:±(3%ofrdg+4.0°C)
0.1°C
U *5 -200.0 to 400.0 °C ±(0.05%ofrdg+0.5°C)Lessthan0.0°C:±(0.5%ofrdg+0.5°C)
±(0.1%ofrdg+2.5°C)Lessthan0.0°C:±(2%ofrdg+2.5°C)
0.1°C
WRe3-25*6 0.0 to 2320.0 °C ±(0.05%ofrdg+2.0°C)Morethan2000.0°C:±(0.15%ofrdg)
±(0.1%ofrdg+8.0°C)Less than 200.0°C: 12.0°CMorethan2000.0°C:±(0.1%ofrdg+13.0°C)
0.1°C
KpvsAu7Fe*7 0.0 to 300.0 K ±(0.05%ofrdg+0.7[2.0]K) ±(0.1%ofrdg+3.5[7.0]K) 0.1 KPLATINEL II *7 0.0 to 1395.0 °C ±(0.05%ofrdg+1.0°C) ±(0.1%ofrdg+4.0°C) 0.1°CPR20-40*8 0.0 to 1900.0°C ±(0.05%ofrdg+2.5[5.5]°C)
However, accuracy at less than 800.0°C is not guaranteed.
±(0.1%ofrdg+12.0[18.0]°C)However, accuracy at less than 800.0°C is not guaranteed.
0.1°C
NiNiMo *7 0.0 to 1310.0°C ±(0.05%ofrdg+0.7°C) ±(0.1%ofrdg+2.7°C) 0.1°CW/WRe26*9 0.0 to 2320.0°C ±(0.05%ofrdg+2.0°C)
However, accuracy at less than 300.0°C is not guaranteed.
±(0.1%ofrdg+10.0°C)However, accuracy at less than 300.0°C is not guaranteed.
0.1°C
N(AWG14)*10 0.0 to 1300.0°C ±(0.05%ofrdg+0.7°C) ±(1.0%ofrdg+4.0°C) 0.1°CXK GOST *11 -200.0 to 600.0°C ±(0.05%ofrdg+0.5°C)
Less than 0.0°C:±(0.2%ofrdg+0.5°C)±(0.1%ofrdg+2.5°C)Less than 0.0°C: ±(1%ofrdg+2.5°C)
0.1°C
6
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
Continued
Input Type Range Measurement range
Measurement accuracy (digital display) Max. resolution of digital display
Scan interval: 50 ms or more(Only the Values in [ ] apply when the
scan interval is 50/100/200 ms)
Scan interval: 20 ms or less(Only the Values in [ ] apply when the
scan interval is 1/2/5 ms)RTD(Measuredcurrent: 1mA)
Pt100 *13 -200.0 to 850.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C-150.00 to 150.00°C 0.01°C
JPt100 *13 -200.0 to 550.0°C 0.1°C-150.00 to 150.00°C 0.01°C
Cu25 at 0°Cα=0.00425
-200.0 to 300.0°C ±(0.1%ofrdg+0.8°C) ±(0.2%ofrdg+2.0°C) 0.1°C
Cu53 at 0°Cα=0.00426035
-50.0 to 150.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°C
Cu100 at 0°Cα=0.00425
-50.0 to 150.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
J263B *14 0.0 to 300.0 K ±4.0 KLess than 40.0 K: ±0.8 K
±1.5 KLess than 40.0 K: ±3.0 K
0.1 K
Ni100(SAMA) -200.0 to 250.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°CNi100(DIN)*15 -60.0 to 180.0°CNi120 *16 -70.0 to 200.0°CPt25 *17 -200.0 to 550.0°C ±(0.1%ofrdg+0.8°C) ±(0.2%ofrdg+2.0°C) 0.1°CPt50 *18 -200.0 to 550.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CPt200 WEED -100.0 to 250.0°C ±(0.05%ofrdg+1.0°C) ±(0.1%ofrdg+3.0°C) 0.1°CCu50 GOST *20 -200.0 to 200.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CCu100 GOST *21
-200.0 to 200.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
Pt46 GOST *20 -200.0 to 550.0°C ±(0.05%ofrdg+0.6°C) ±(0.1%ofrdg+1.5°C) 0.1°CPt100 GOST *21 -200.0 to 600.0°C ±(0.05%ofrdg+0.3°C) ±(0.1%ofrdg+1.5°C) 0.1°C
RTD(Measuredcurrent: 1.6mA)
Cu10 GE -200.0 to 300.0°C ±(0.1%ofrdg+0.7[2.0]°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
±(0.2%ofrdg+2.5[5.0]°C)guaranteed rangeCu10 GE: -70.0 to 170.0°CCu10 L&N: -75.0 to 150.0°CCu10 WEED: -200.0 to 260.0°COther range: -200.0 to 300.0°C
0.1°CCu10 L&N -200.0 to 300.0°CCu10 WEED -200.0 to 300.0°CCu10 BAILEY -200.0 to 300.0°CCu10 at 20°Cα=0.00392
-200.0 to 300.0°C
Cu10 at 20°Cα=0.00393
-200.0 to 300.0°C
Cu10 GOST *19 -200.0 to 200.0°C ±(0.1%ofrdg+0.7[2.0]°C) ±(0.2%ofrdg+2.5[5.0]°C) 0.1°CDI Level Thresholdlevel(Vth=2.4V)Accuracy:±0.1V -
Contact *22 Less than 100Ω:1(ON),Morethan10kΩ:0(OFF) -rdg:Readingvalue
*3 R,S,B,K,E,J,T,N:IEC60584-1,DINEN60584,JISC1602, ASTM E230*4 W:W-5%Re/W-26%Re(HoskinsMfg.Co.)ASTME988-96 (TypeCequivalentofOMEGAEngineeringInc.)*5 L: Fe-CuNi, DIN43710, U: Cu-CuNi, DIN43710*6 WRe3-25:W-3%Re/W-25%Re(HoskinsMfg.Co.)ASTME988-96 (TypeDequivalentofOMEGAEngineeringInc.)*7 KpvsAu7Fe,PLATINELII,NiNiMo:ASTME1751*8 PR20-40:PtRH20%-PtRh40%(JohnsonMattheyPlc)ASTME1751*9 W/WRe26:W/W-26%Re(HoskinsMfg.Co.)ASTME1751 (TypeGequivalentofOMEGAEngineeringInc.)*10 N(AWG14):NBS*11 XKGOST:TypeL(GOSTR8.525-2001)*12 Pt100: JIS C1604, IEC60751, DIN EN60751 JPt100: JIS C1604, JIS C1606*13 J263B: Yokogawa Electric Corporation J263*B*14 Ni100(DIN):DIN43760*15 Ni120:McGRAWEDISONCOMPANY*16 Pt25:One-fourthofJPt100resistancevalue*17 Pt50: JIS C1604, JIS C1606*18 Cu10GOST:One-tenthofCu100GOSTresistancevalue*20 Cu50 GOST, Pt46 GOST: GOST 6651-94*20 Cu100 GOST, Pt100 GOST: GOST 6651-2009*21 Thedetectedcurrentvalueisapprox.10μA.*22 10channelmodewithscanintervalsetto500msorhigher,or2channelmode*23 10channelmodewithscanintervalsetto100msor200ms
Measurementaccuracyatscaling:measurementaccuracyatscaling(digits)=measurementaccuracy(digits)×scalingspan(digits)/measurementspan(digits)+1digit
*Roundingupdecimalplaces
7
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
• Burnout detection*1 *2: Burnout upscale, downscale,orOFFselectable(foreachchannel).
Availableinput:TC,RTD,StandardsignalDetection condition;TC; Universal,Lowwithstandvoltagerelay,Electromagneticrelay,Highwithstandvoltage type Normal:2kΩorless.,Burnout:200kΩor
more(parallelcapacitanceof0.01μForless) Detectioncurrent:Approx.10μAHigh-speeduniversaltype Detection current: Approx. 50 nA,
SuperposedelectriccurrentsystemRTD;Universaltype Normal:wiringresistanceorless,Burnout:
200kΩormore parallelcapacitanceoflessthan0.01μFor
less Detectioncurrent:Approx.10μAHigh-speeduniversaltype Detection current: Approx. 100 nA,
SuperposedelectriccurrentsystemStandard signal: Normal:Withinmeasuringrange Burnout: Depends on the setting of the
burnoutjudgmentvalue.Theburnoutjudgmentvalueshallbesetwiththepercentageofthespecifiedspanwidth.
Lowerlimit:-20.0to-5.0% Upperlimit:105to120%*1Noneforthe4-wireRTD/resistancetype*2IfthescanintervalonthehighspeedAI
moduleis1to20ms,burnoutdetectionwillnot work correctly.
• Input external resistance:DCvoltage,thermocoupleinput:2kΩorbelowResistancetemperaturedetectorinput:10Ω
orbelowineachwire(Sameresistanceinthreewires)
• Inputbiascurrent:±10nAorless(whenburnoutfunctiondoesnotwork)
• Measuredcurrent(forRTD): universaltype:Approx.1mA High-speeduniversaltype:Approx.1mA/1.6mA
(dependsontherange) 4-wireRTD/resistance:Approx.1mA/0.25mA
(dependsontherange)• Input resistance:
10MΩormoreforTC/DCvoltage(1Vrangeorless)input Approx.1MΩforDCvoltage(2Vrangeormore)/standardsignalinput/DIvoltage(High-speeduniversaltype)/whilemeasurementisstopped(High-speeduniversaltype) 250Ω(249.5Ωtyp)forDCmA
*typ:Typicalvalue(Typical)• Allowablesignalsourceresistance:2kΩorless
forTC/DCvoltage(1Vrangeorless)input• Effectofsignalsourceresistance:
±10μV/1kΩorlessforTC/DCvoltage(1Vrangeorless)input ±0.15%ofrdg/1kΩorlessforDCvoltage(2Vrangeormore)/standardsignalinput
• Allowablewiringresistance:Max.10ΩperlineforRTDinput(conductorresistancebetweenthethreelinesshallbeequal)
• Effectofwiringresistance:±0.1°C/10ΩforRTDinput(conductorresistancebetweenthethreelinesshallbeequal),±1°C/10Ω(50Ωsystemorless,High-speeduniversaltype)
4-wireRTD/resistancetype 4-wireRTD100Ωsystemormore:±0.1°C/10Ω 4-wireRTD50Ωsystemorless:±1°C/10Ω Resistance20Ω:±0.001Ωorless Resistance200Ω:±0.01Ωorless Resistance2000Ω:±0.1Ωorless• Allowableinputvoltage:
Universal,Lowwithstandvoltagerelay,Electromagneticrelay,Highwithstandvoltage type:
±10VDCforTC/DCvoltage(1Vrangeorless)/RTD/DI(contact)input,DCmA ±60VDCforDCvoltage(2Vrangeormore)input/DI(level)input
High-speeduniversaltype: ±120VDC• Allowableinputcurrent(current(mA)inputtype):
24mA,50/60Hz,peakvalueincludingsignal• Noise reduction ratio Universal,Lowwithstandvoltagerelay,current
(mA)input,Electromagneticrelay,4-wireRTD/resistance,Highwithstandvoltage type:
Integration time *1 Normal mode Common mode1.67ms 50/60 Hz, no
noise reductionMore than 80 dB *2 *4
More than 16.67 ms
More than 40 dB *2 *3
More than 120 dB *2 *4
High-speeduniversaltype:Scan interval *1 Normal mode Common mode
20msorless 50/60 Hz, no noise reduction
More than 80 dB *2 *4
Morethan50ms More than 40 dB *2 *3
More than 120 dB *2 *4
*1 Afrequencydiscriminationsettingismadeinthemainunit.
*2 Aresistancetemperaturedetectorrangeisaconvertedvalueofvoltagewhenameasuredcurrentflows.
*3 50/60Hz±0.1%*4 50/60Hz±0.1%,500Ωimbalance,between
minusmeasuringterminalandground• NormalmodevoltageforTC/DCvoltage(1V
rangeorless)/DI(voltage):1.2timesorlessofrated range
Standardsignal0.4to2Vrange:2.4V Standardsignal1-5Vrange:6V RTD(100Ωsystemormore):50mVpeak RTD(50Ωsystemorless):10mVpeak* 50/60Hz,Thepeakvalueincludingthesignal.
4-wireRTD/resistance Resistance(2000Ω),RTD(100Ω,500Ω
1000Ωsystem):50mVpeak Resistance(200Ω),RTD(10Ω,25Ω50Ω
system):10mVpeak Resistance(20Ω):4mVpeak• Normalmodecurrent(current(mA)inputtype):
24mADC(Valueconvertedtovoltage:6V) *50/60Hz,Thepeakvalueincludingthesignal.
8
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
2ch.mode*2
Scan interval Integration time100msormore 16.67ms/20ms1 s 36.67ms2sormore 100ms
*1 In10chmode,whenthescanintervalissetto100msor200ms,theA/Dintegrationtimeisfixedat1.67ms.Thispreventspowerfrequencynoisefrombeingeliminated,causingmeasuredvaluesto wobble.
*2 Cannotbespecifiedfortheelectromagneticrelaytype,Lowwithstandvoltagerelaytype,High-speeduniversaltype.
*3 Forthe4-wireRTD/resistancetype.• Scaninterval/filtertype: High-speeduniversaltype
Scan interval Filter20msorless Non*50ms/100ms/200ms 50 Hz/60 Hz
Simultaneousremovalof50Hzand 60 Hz
500msormore 50 Hz/60 Hz/10 Hz* Withthehigh-speeduniversaltype,whenthe
scanintervalis20msorless,supplyfrequencynoiseisnotremoved.Assuch,themeasuredvaluesmayfluctuateespeciallyintemperaturemeasurementusingthermocouples.
• Calibration correction: Mode:LinearizerApproximation,LinearizerBias Numberofcorrectingpoints:12
• Movingaveragefunction: CanbeswitchedOn/Off(Settableforeachchannel)
Movingaveragenumbercanbeselectedfrom2to100times
Selectfrom2to500forthehigh-speeduniversaltype.
• First-orderlaginputfilter(high-speeduniversaltype):Canbeturnedon/offforeachchannelTimeconstant:Scaninterval×NwhereNisbetween3and300)
• Referencejunctioncompensation: Mode: Can be switch internal or external (Settableforeachchannel) (Setthevalueofthecompensationtemperatureatexternal)
• Input calculation: Linearscaling,squareroot*,differentialcalculations(Settableforeachchannel)
* Notavailableforthe4-wireRTD/resistancetype• Bias function:
Canbesetthebiasvaluetobeaddedtotheinputvalue(Settableforeachchannel)
• Terminaltype:M3screwterminalorClampterminal• Withstandvoltage Universal,Electromagneticrelay,4-wireRTD/
resistance type; Betweentheinputterminalsandtheinternal
circuit:3000VACforoneminute Betweentheanaloginputchannels:1000VAC
foroneminute(excludingb-terminal) Current(mA)inputtype; Betweentheinputterminalsandtheinternal
circuit:1500VACforoneminute Betweentheanaloginputchannels:1000V
ACforoneminute(excludingb-terminal)
• Commonmodevoltageformeasuringinput:30VACrms(50/60Hz)or±60VDC(Maximumcommonmodenoisevoltageformeasuringinput:250VACrms)
High-speeduniversaltypeonly 300VACrms(50/60Hz),Double insulation Highwithstandvoltagetypeonly 600VACrms(50/60Hz)or600VDC,Double
insulation 1000VDC,Basicinsulation*
* Whenthemoduleisusedunderbasic insulation conditions, external supplementaryinsulationisrequiredforsafeuse.Whenthesystemisusedinacommonmodevoltageenvironmentthatexceeds600V,toaddsupplementaryinsulation,youneedtoinstallthesysteminapanel,addanovercurrentprotectiondevice,andaddaninsulationdevice.RefertotheFirstStepGuide(IM04L51B01-02EN,IM04L55B01-02EN),andtaketheappropriatemeasures.
• Maximumvoltagebetweenmeasuringinputchannels:30VACrms(50/60Hz)or±60VDC(Maximumcommonmodenoisevoltagebetweenmeasuringinputchannels:250VACrms(60VACrmsforlow-voltagerelaytype))
High-speeduniversaltype 300VACrms(50/60Hz),Double insulation• Referencejunctioncompensationaccuracy: Whenmeasuringtemperaturegreaterthanor
equalto0°CandwhenIntegraltime16.6msormoreorscaninterval50msormore(forthehigh-speeduniversaltype)andwheninputterminaltemperatureisbalanced
TypeK,E,J,T,N,XKGOST:±0.5°C(23°C±2°C),±0.7°C(0to50°C),±1.0°C(-20to60°C)
TypeR,S,W,L,U,W97Re3-W75Re25,Platinel2,NiNiMo,W/WRe26,N(AWG14):±1.0°C(23°C±2°C),±1.4°C(0to50°C),±2.0°C(-20to60°C)
TypeKpvsAu7Fe:±1.0K(23°C±2°C),±1.4K(0to50°C),±2.0K(-20to60°C)
TypeB,PR20-40:Internalreferencecompensationisfixedto0°C
• Scaninterval/A/Dintegrationtime: 10ch.mode,6chmode*3
Universal*1,Current(mA)input*1 ,4-wireRTD/resistance,Highwithstandvoltage*1 type
Scan interval Integration time100ms/200ms 1.67ms500msormore 16.67ms/20ms1 s 36.67ms2sormore 100ms
ElectromagneticrelayscannertypeScan interval Integration time
1sormore 16.67ms/20ms2 s 36.67ms5 s 100ms
LowwithstandvoltagerelaytypeScan interval Integration time
500msormore 16.67ms/20ms2 s 36.67ms5 s 100ms
9
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN July 30, 2021-00
Lowwithstandvoltagetype; Betweentheinputterminalsandtheinternal
circuit:1500VACforoneminute Betweentheanaloginputchannels:400VAC
foroneminute(excludingb-terminal) High-speeduniversaltype; Betweentheinputterminalsandtheinternal
circuit:3000VACforoneminute Betweentheanaloginputchannels:3000V
ACforoneminute Highwithstandvoltage Betweentheinputterminalsandtheinternal
circuit:3700VACforoneminute Betweentheanaloginputchannels:1000V
ACforoneminute• Insulation resistance:
Betweentheinputterminalsandtheinternalcircuit:20MΩorgreaterat500VDC
Betweentheanaloginputchannels*:20MΩorgreaterat500VDC
* Excludesthebterminaloftheuniversaltype• Recommendedreplacementperiodof
electromagneticrelayscannertypemodules: Electromagneticrelayscannertypemodules
makemeasurementsbyswitchingmechanicalcontactrelaysonandoff.
Toensurethatthemodulescontinuetooperatereliablyandcorrectly,replacethem
Continuoususeatmeasurementinterval1s:1year Continuoususeatmeasurementinterval2s:2years Continuoususeatmeasurementinterval5s:5years
Safety and EMC Standards• CSA: CSA C22.2 No. 61010-1,
CSA-C22.2 No. 61010-2-030, OvervoltageCategoryIIorI *1, Pollution Degree 2 *2, MeasurementCategoryII *4
• UL: UL61010-1,ULStd.No.61010-2-030(CSA
NRTL/C),OvervoltageCategoryIIorI *1, Pollution Degree 2 *2,MeasurementCategoryII *4
• CE/EMCdirective *3: EN 61326-1 ClassATable2(Foruseinindustrial
locations)compliant ENIEC61000-3-2compliant EN61000-3-3compliant EN55011ClassAGroup1compliant• CE/Lowvoltagedirective *3: EN61010-1,EN61010-2-030compliant,
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2, MeasurementCategory II *4
• EURoHSdirective:ENIEC63000• WEEE directive:Compliant• EMCRegulatoryArrangementinAustraliaand
NewZealand(RCM):EN55011ClassAGroup1compliant
• KCmarking:KSC9811,KSC9610-6-2compliant*1 OvervoltageCategory:Describesanumberwhich
definesatransientovervoltagecondition.Impliestheregulationforimpulsewithstandvoltage.Appliestoelectricalequipmentwhichissuppliedfromthefixedinstallationlikeadistributionboard.IIorIdependsonthepowersupplyspecificationofthemainunit.
*2 Pollution Degree 2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
*3 TheCEstandardsformodulesrepresentstandardsthataremetwhenthemoduleisinstalledinthemainunit.
*4 MeasurementCategoryII(CATII): Appliestomeasuringcircuitsconnectedtolow
voltageinstallation,andelectricalinstrumentssuppliedwithpowerfromfixedequipmentsuchaselectric switchboards.
Construction• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20• Material: Polycarbonate• Color;
Front:Charcoalgreylight(Munsell10B3.6/0.3equivalent) Bezel:Smokeblue(Munsell4.1PB6.0/4.5equivalent)
• Dimensions:45.2mm(W)x111mm(H)x133.1mm(D)(D:includingterminalcover)
• Weight: Approx. 0.3 kg
Power Supply SuppyfromGX/GP,GX60expandableI/O,GM90PSpowersupplymodule.• Powerconsumption: GX90XA-10-U2: 0.7 W or less GX90XA-10-T1: 0.9 W or less GX90XA-10-C1: 0.7 W or less GX90XA-10-L1: 0.7 W or less GX90XA-04-H0: 2.0 W or less GX90XA-06-R1:0.7Worless GX90XA-10-V1:1.0Worless
10
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
Terminal arrangementsM3 screw terminal Universal,Lowwithstandvoltagerelay,Electromagneticrelay,Current(mA)input,High withstandvoltagetype
No. Symbol No. Symbol No. Symbol301 CH1(/b)*1 201 CH1(-/B) 101 CH1(+/A)302 CH2(/b)*1 202 CH2(-/B) 102 CH2(+/A)303 CH3(/b)*1 203 CH3(-/B) 103 CH3(+/A)304 CH4(/b)*1 204 CH4(-/B) 104 CH4(+/A)305 CH5(/b)*1 205 CH5(-/B) 105 CH5(+/A)306 CH6(/b)*1 206 CH6(-/B) 106 CH6(+/A)307 CH7(/b)*1 207 CH7(-/B) 107 CH7(+/A)308 CH8(/b)*1 208 CH8(-/B) 108 CH8(+/A)
309 CH9(/b)*1 209 CH9(-/B) 109 CH9(+/A)310 CH10(/b)*1 210 CH10(-/B) 110 CH10(+/A)
*1 Therearenosymbolindicationsfortheelectromagneticrelaytype,current(mA)inputtype,lowwithstandvoltagerelaytype,or high withstandvoltagetype.
* RTDinputterminalbisshortedinternallyacrossall channels.
High-speeduniversaltype
No. Symbol No. Symbol No. Symbol301 CH1(/A) 201 CH1(-/b) 101 CH1(+/B)
304 CH2(/A) 204 CH2(-/b) 104 CH2(+/B)
307 CH3(/A) 207 CH3(-/b) 107 CH3(+/B)
310 CH4(/A) 210 CH4(-/b) 110 CH4(+/B)
4wireRTD/resistancetype
No. Symbol No. Symbol No. Symbol301 CH1(B) 201 CH1(A) 101 CH1(I)302 CH1(C) 202 Not Used 102 CH2(C)303 CH2(B) 203 CH2(A) 103 CH2(I)304 CH3(B) 204 CH3(A) 104 CH3(I)305 CH3(C) 205 Not Used 105 CH4(C)306 CH4(B) 206 CH4(A) 106 CH4(I)307 CH5(B) 207 CH5(A) 107 CH5(I)308 CH5(C) 208 Not Used 108 CH6(C)
309 CH6(B) 209 CH6(A) 109 CH6(I)310 Not Used 210 Not Used 110 Not Used
Isolation Universal,Lowwithstandvoltagerelay,Electromagneticrelay,Current(mA)inputtype
Functional insulation
Reinforced insulation
Analog input CH1Analog input CH2Analog input CH3Analog input CH4Analog input CH5Analog input CH6Analog input CH7Analog input CH8Analog input CH9Analog input CH10
Input circuit Internal circuit
Highwithstandvoltagetype
Functional insulation
Double insulation (600 V ACrms 50/60 Hz, 600 V DC) or Basic insulation (1000 V DC)
Analog input CH1Analog input CH2Analog input CH3Analog input CH4Analog input CH5Analog input CH6Analog input CH7Analog input CH8Analog input CH9Analog input CH10
Input circuit Internal circuit
High-speeduniversaltype
Double insulation (300 Vrms 50/60Hz)
Internal circuit
Analog input CH1Analog input CH2Analog input CH3Analog input CH4
4-wireRTD/resistancetype
Analog input CH1Analog input CH2Analog input CH3Analog input CH4Analog input CH5Analog input CH6
Input circuit Internal circuit
Functional insulation
Reinforced insulation
11
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
Clamp terminal Universal,Lowwithstandvoltagerelay,Electromagneticrelay,Current(mA)inputtype,High withstandvoltagetype
No. Symbol No. Symbol201 CH2(+/A) 101 CH1(+/A)
202 CH2(-/B) 102 CH1(-/B)
203 CH2(/b)*1 103 CH1(/b)*1
204 CH4(+/A) 104 CH3(+/A)
205 CH4(-/B) 105 CH3(-/B)
206 CH4(/b)*1 106 CH3(/b)*1
207 CH6(+/A) 107 CH5(+/A)
208 CH6(-/B) 108 CH5(-/B)
209 CH6(/b)*1 109 CH5(/b)*1
210 CH8(+/A) 110 CH7(+/A)
211 CH8(-/B) 111 CH7(-/B)
212 CH8(/b)*1 112 CH7(/b)*1
213 CH10(+/A) 113 CH9(+/A)
214 CH10(-/B) 114 CH9(-/B)
215 CH10(/b)*1
115 CH9(/b)*1
*1 Therearenosymbolindicationsfortheelectromagneticrelaytype,current(mA)inputtype,lowwithstandvoltagerelaytype,or high withstandvoltagetype.
* RTDinputterminalbisshortedinternallyacrossall channels.
High-speeduniversaltype
No. Symbol No. Symbol201 CH1(+/B) 101 Not Used
202 CH1(-/b) 102 Not Used
203 CH1(/A) 103 Not Used
204 Not Used 104 Not Used
205 CH2(+/B) 105 Not Used
206 CH2(-/b) 106 Not Used
207 CH2(/A) 107 Not Used
208 Not Used 108 Not Used
209 CH3(+/B) 109 Not Used
210 CH3(-/b) 110 Not Used
211 CH3(/A) 111 Not Used
212 Not Used 112 Not Used
213 CH4(+/B) 113 Not Used
214 CH4(-/b) 114 Not Used
215 CH4(/A) 115 Not Used
4-wireRTD/resistance
No. Symbol No. Symbol201 CH2(I) 101 CH1(I)
202 CH2(A) 102 CH1(A)
203 CH2(B) 103 CH1(B)
204 CH2(C) 104 CH1(C)
205 Not Used 105 Not Used
206 CH4(I) 106 CH3(I)
207 CH4(A) 107 CH3(A)
208 CH4(B) 108 CH3(B)
209 CH4(C) 109 CH3(C)
210 Not Used 110 Not Used
211 CH6(I) 111 CH5(I)
212 CH6(A) 112 CH5(A)
213 CH6(B) 113 CH5(B)
214 CH6(C) 114 CH5(C)
215 Not Used 115 Not Used
A/D Calibration Value TwotypesofA/Dcalibrationvalues(factory
shipmentsettingandusersetting)canbesaved.If the user setting is not proper, it can be restored tothecalibrationvalueatfactoryshipment.
12
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
• High speed universal type and high withstand voltage type
M3 screw terminal
3 (0.12)
8 (0.31)
45.2 (1.78)
Unit: mm(approx. inch)
133.1 (5.24)
100(3.94)
Clamp terminal
3 (0.12)
8 (0.31)
45.2 (1.78)
Unit: mm(approx. inch)
133.1 (5.24)
100(3.94)
External Dimensions• Except high speed universal type and high
withstand voltage type M3 screw terminal
133.1 (5.24)
8(0.31)
3(0.12)
45.2(1.78)
100(3.94)
Unit: mm(approx. inch)
Clamp terminal
133.1 (5.24)
8(0.31)
3(0.12)
45.2(1.78)
100(3.94)
Unit: mm(approx. inch)
13
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O)Specifications:GS
04L53B00-01ENGMSpecifications:GS04L55B01-01EN
Transport and Storage Conditions• Ambienttemperature:–25to70°C• Ambienthumidity:5to95%RH(no
condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged
condition)
Effects of Operating ConditionsIntegraltime16.67msormoreorscaninterval50msormore(forthehigh-speeduniversaltype)• Influenceofambienttemperature:variation
againstachangeof10°Catanaccumulationtimeof16.67msormore±(0.05%ofrdg+0.05%ofrange)orbelow. (Incaseofcurrent(mA)inputtype,±(0.075%ofrdg+0.05%ofrange)orbelow.)
KpvsAu7Fe,PR20-40:±(0.05%ofrdg+0.1% of range)orbelow,Cu10Ωsystemorless:±(0.2%ofrdg+0.1°C)orbelow No reference contact accuracy is guaranteed.
• Influenceofpowersupplyvoltagevariation:Accuracyissatisfiedintherangeofratedpowersupplyvoltage.
• Influenceofexternalmagneticfield:VariationsagainstanACexternalmagneticfield(50/60Hz,400A/m)are±(0.1%ofrdg+0.1% of range)orbelow.
Installation limitationsIfyouwanttousetheelectromagneticrelaytypeorhigh-speeduniversaltypemodulesonaGM10singleunit,uptoeightmodulescanbeinstalled.
14
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
Safety and EMC Standards• CSA: CSA C22.2 No. 61010-1,
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• UL: UL61010-1(CSANRTL/C),Overvoltage
Category II or I *1, Pollution Degree 2 *2
• CE/EMCdirective *3: EN61326-1ClassATable2(Foruseinindustrial
location)compliant ENIEC61000-3-2compliant EN61000-3-3compliant EN55011ClassAGroup1compliant• CE/Lowvoltagedirective *3: EN61010-1compliant,
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• EURoHSdirective:ENIEC63000• WEEEDirective:Compliant• EMCRegulatoryArrangementinAustraliaand
NewZealand(RCM):EN55011ClassAGroup1compliant
• KCmarking:KSC9811,KSC9610-6-2compliant*1 OvervoltageCategory:Describesanumberwhich
definesatransientovervoltagecondition.Impliestheregulationforimpulsewithstandvoltage.Appliestoelectricalequipmentwhichissuppliedfromthefixedinstallationlikeadistributionboard.IIorIdependsonthepowersupplyspecificationofthemainunit.
*2 Pollution Degree 2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
*3 TheCEstandardsformodulesrepresentstandardsthataremetwhenthemoduleisinstalledinthemainunit.
Construction• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20• Material: Polycarbonate• Color;
Front:Charcoalgreylight(Munsell10B3.6/0.3equivalent) Bezel:Smokeblue(Munsell4.1PB6.0/4.5equivalent)
• Dimensions:45.2mm(W)x111mm(H)x133.1mm(D)(D:includingterminalcover)
• Weight: Approx. 0.3 kg
Power Supply SuppyfromGX/GP,GX60expandableI/O,GM90PSpowersupplymodule.• Powerconsumption:0.7Worless
DIGITAL INPUT MODULE (Model GX90XD or GX/GP main unit options /CRx1)
GX90XD
• Application:Remotecontrolinput,pulseinput*1, etc
• Numberofinputs:16• input type: DI, pulse*1
• Measurementinterval:100ms(shortest)• Inputtype:OpencollectororVoltage-freecontact• Insulationtype:Photocoupler,Trance(power
supply)• Contactrating:12VDC,20mAormore• Inputresistance:Approx.1kΩ• Allowableinputvoltage:+10V• ON/OFF detection Open collector contact input:
VoltageinONstate:0.5VDCorlessLeakagecurrentinOFFstate:0.5mAorless
Voltage-freecontactinput:ContactresistanceinONstate:200ΩorlessContactresistanceinOFFstate:50kΩor
more• Numberofcommon:2(1point/8channels)• Terminaltype:M3screwterminalorClamp
terminal (IncaseofOptions/CRx1,adigitalinputmodulehasM3screwterminals.)
• Withstandvoltage Betweentheinputterminalsandtheinternal
circuit:1500VACforoneminute• Insulation resistance:
Betweentheinputterminalsandtheinternalcircuit:20MΩorgreaterat500VDC
[Pulseinputspecifications]*1• Countingsystem:Therisingedgeofthepulseis
counted. Opencollector:Thesignallevelattheinput
terminalchangesfromhightolow.
Voltage-freecontact:Thecontactchangesfromopen to close.
• Max. pulse period: 250Hz(Thechatteringfilter:Off) 125Hz(Thechatteringfilter:On)• Min.detectionpulsewidth:Low(close),High
(open),bothis2msormore• Pulsedetectionperiod:1ms• Pulsemeasuringaccuracy:±1pulse• Pulsecountinterval:mesurementinterval• Filter:ThechatteringfiltercanbeswitchedOn/
Off*.*Whenthechatteringfilterisoff,connectGX/GP/GMsothatitisnotaffectedbythenoise.
*1 MATHfunction(optionalcode/MT)isrequired.
15
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
Isolation
Digital input CH1Digital input CH2Digital input CH3Digital input CH4Digital input CH5Digital input CH6Digital input CH7Digital input CH8Digital input CH9Digital input CH10Digital input CH11Digital input CH12Digital input CH13Digital input CH14Digital input CH15Digital input CH16
Non-isolated Functional insulation
Input circuit Internal circuit
Terminal arrangementsM3 screw terminal/Clamp terminal
No. Symbol No. Symbol21 DI9 11 DI1
22 DI10 12 DI2
23 DI11 13 DI3
24 DI12 14 DI4
25 DI13 15 DI5
26 DI14 16 DI6
27 DI15 17 DI7
28 DI16 18 DI8
29 COM2 19 COM1
30 - 20 -
External DimensionsM3 screw terminal
97.1
(3.8
2)
82.1
(3.2
3)
36(1
.42)
92(3
.62)
100(
3.94
)3(
0.12
)8(
0.31
)
(0.0
7)1.
9
45.2(1.78)
31.9(1.26)
Unit: mm(approx. inch)
Clamp terminal
97.1
(3.8
2)
82.1
(3.2
3)
36(1
.42)
92(3
.62)
100(
3.94
)3(
0.12
)8(
0.31
)
(0.0
7)1.
9
45.2(1.78)
31.9(1.26)
Unit: mm(approx. inch)
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):GS04L53B00-
01ENGMSpecifications:GS04L55B01-01EN
Transport and Storage ConditionsSameastheGX90XA.
Installation limitationsWhenthemeasurementmodeisHighspeed,
asinglemodule,eitherthismoduleortheGX90WD,canbeinstalled.DIinputisfixedtoremotemode.Measurementandrecordingarenot possible.
16
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
*1 OvervoltageCategory:Describesanumberwhichdefinesatransientovervoltagecondition.Impliestheregulationforimpulsewithstandvoltage.Appliestoelectricalequipmentwhichissuppliedfromthefixedinstallationlikeadistributionboard.IIorIdependsonthepowersupplyspecificationofthemainunit.
*2 Pollution Degree 2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
*3 TheCEstandardsformodulesrepresentstandardsthataremetwhenthemoduleisinstalledinthemainunit.
Construction• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20• Material: Polycarbonate• Color;
Front:Charcoalgreylight(Munsell10B3.6/0.3equivalent) Bezel:Smokeblue(Munsell4.1PB6.0/4.5equivalent)
• Dimensions:45.2mm(W)x111mm(H)x133.1mm(D)(D:includingterminalcover)
• Weight: Approx. 0.3 kg
Power Supply SuppyfromGX/GP,GX60expandableI/O,GM90PSpowersupplymodule.• Powerconsumption:1.4Worless
Isolation
Digital output CH1Digital output CH2Digital output CH3Digital output CH4Digital output CH5Digital output CH6
Output circuit Internal circuit
Functional insulation
Reinforced insulation
DIGITAL OUTPUT MODULE (Model GX90YD, or GX/GP main unit options /CR1x, /CR2x, /CR4x)
GX90YD
• Application:Alarmoutput,etc• Numberofoutputs:6• Outputupdateinterval:100ms(shortest)• Outputtype:Relaycontactoutput,SPDT(NO-C-
NC)• Insulation type: Mechanical• Ratedloadvoltage:30VDCor250VACorless• Max.loadcurrent:3A(DC)/3A(AC),resistance
load, each channel• Min.loadvoltage/current:5VDC/10mA• Recommendedreplacementperiodsofcontact:
Mechanical5,000,000moreON-OFFoperations Electrical30,000moreON-OFFoperations(250
VAC3Aor30VDC3A,resistanceload)• Numberofcommon:6• Terminaltype:M3screwterminal• Withstandvoltage Betweentheoutputterminalsandtheinternal
circuit:3000VACforoneminute Betweentheoutputterminals:3000VACforone
minute• Insulation resistance:
Betweentheoutputterminalsandtheinternalcircuit:20MΩorgreaterat500VDC
Betweentheoutputterminals:20MΩorgreaterat500VDC
Safety and EMC Standards• CSA: CSA C22.2 No. 61010-1,
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• UL: UL61010-1(CSANRTL/C),
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• CE/EMCdirective *3: EN61326-1ClassATable2(Foruseinindustrial
locations)compliant ENIEC61000-3-2compliant EN61000-3-3compliant EN55011ClassAGroup1compliant• CE/Lowvoltagedirective *3: EN61010-1compliant,
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• EURoHSdirective:ENIEC63000• WEEEDirective:Compliant• EMCRegulatoryArrangementinAustraliaand
NewZealand(RCM):EN55011ClassAGroup1compliant
• KCmarking:KSC9811,KSC9610-6-2compliant
17
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
Terminal arrangementsM3 screw terminal
No. Symbol No. Symbol21 DO4 N.C. 11 DO1 N.C.
22 DO4 COM 12 DO1 COM
23 DO4 N.O. 13 DO1 N.O.
24 DO5 N.C. 14 DO2 N.C.
25 DO5 COM 15 DO2 COM
26 DO5 N.O. 16 DO2 N.O.
27 DO6 N.C. 17 DO3 N.C.
28 DO6 COM 18 DO3 COM
29 DO6 N.O. 19 DO3 N.O.
30 Not Used 20 Not Used
External DimensionsM3 screw terminal
97.1
(3.8
2)
82.1
(3.2
3)
36(1
.42)
92(3
.62)
100(
3.94
)3(
0.12
)8(
0.31
)
(0.0
7)1.
9
45.2(1.78)
31.9(1.26)
Unit: mm(approx. inch)
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.However,excludingtheshockat energization.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):ThisGeneral
SpecificationsGMSpecifications:GS04L55B01-01EN
Transport and Storage ConditionsSameastheGX90XA.
Installation limitations When using the GX90WD digital input/output
modulesandGX90UTPIDcontrolmodulestogether,uptoatotalof10modulescanbeinstalled.
18
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
Digital Output Specifications• Application:Alarmoutput,etc• Numberofoutputs:6• Outputupdateinterval:100ms(shortest)• Outputtype:Relaycontactoutput,SPDT(NO-C-
NC)• Insulation type: Mechanical• Ratedloadvoltage: Max.150VACwhenconnectedtothemains
circuit(primarypowersource). Max.250VACwhenconnectedtoacircuit
(secondarypowersource)derivedfromthemainscircuit(primarypowersource)ofupto300VAC,orMax.30VDC.
• Maximumvoltagebetweenoutputterminalchannels:250VAC,Basicinsulation
• Max.loadcurrent:2A(DC)/2A(AC),resistanceload, each channel
• Min.loadvoltage/current:5VDC/10mA• Recommendedreplacementperiodsofcontact:
Mechanical5,000,000moreON-OFFoperations Electrical30,000moreON-OFFoperations(250
VAC2Aor30VDC2A,resistanceload)• Numberofcommon:6(All-contactindependent)• Terminaltype:M3screwterminal• Withstandvoltage Betweentheoutputterminalsandtheinternal
circuit:2700VACforoneminute Betweentheoutputterminals:1350VACforone
minute• Insulation resistance:
Betweentheoutputterminalsandtheinternalcircuit:20MΩorgreaterat500VDC
Betweentheoutputterminals:20MΩorgreaterat500VDC
Safety and EMC Standards• CSA: CSA C22.2 No. 61010-1,
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• UL: UL61010-1(CSANRTL/C),
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• CE/EMCdirective *3: EN61326-1ClassATable2(Foruseinindustrial
locations)compliant ENIEC61000-3-2compliant EN61000-3-3compliant EN55011ClassAGroup1compliant• CE/Lowvoltagedirective *3: EN61010-1compliant,
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• EURoHSdirective:ENIEC63000• WEEEDirective:Compliant• EMCRegulatoryArrangementinAustraliaand
NewZealand(RCM):EN55011ClassAGroup1compliant
• KCmarking:KSC9811,KSC9610-6-2compliant*1 OvervoltageCategory:Describesanumberwhich
definesatransientovervoltagecondition.Impliestheregulationforimpulsewithstandvoltage.Appliestoelectricalequipmentwhichissupplied fromthefixedinstallationlikeadistributionboard.IIorIdependsonthepowersupplyspecificationofthemainunit.
DIGITAL INPUT/OUTPUT MODULE (Model GX90WD)
GX90WD
Digitalinput/outputmodulecanbeusedonemoduleonGX/GPmainunit,ExpandableI/O,GMmainunit,and GM sub unit.
Digital Input Specifications• Application:Remotecontrolinput,pulseinput*1,
etc• Numberofinputs:8• input type: DI, pulse*1
• Measurementinterval:100ms(shortest)• Inputtype:OpencollectororVoltage-freecontact• Insulationtype:Photocoupler,Trance(power
supply)• Contact rating: Use an external contact of 12
VDCand20mAormore.• Inputresistance:Approx.2.4kΩ• Allowableinputvoltage:+10V• ON/OFF detection Open collector contact input:
VoltageinONstate:0.5VDCorlessLeakagecurrentinOFFstate:0.5mAorless
Voltage-freecontactinput:ContactresistanceinONstate:200ΩorlessContactresistanceinOFFstate:50kΩor
more• Numberofcommon:1(1point/8channels)• Terminaltype:M3screwterminal• Withstandvoltage Betweentheinputterminalsandtheinternal
circuit:1500VACforoneminute• Insulation resistance:
Betweentheinputterminalsandtheinternalcircuit:20MΩorgreaterat500VDC
[Pulseinputspecifications]*1• Countingsystem:Therisingedgeofthepulseis
counted. Opencollector:Thesignallevelattheinput
terminalchangesfromhightolow.
Voltage-freecontact:Thecontactchangesfromopen to close.
• Max. pulse period: 250Hz(Thechatteringfilter:Off) 125Hz(Thechatteringfilter:On)• Min.detectionpulsewidth:Low(close),High
(open),bothis2msormore• Pulsedetectionperiod:1ms• Pulsemeasuringaccuracy:±1pulse• Pulsecountinterval:mesurementinterval• Filter:ThechatteringfiltercanbeswitchedOn/
Off*.*Whenthechatteringfilterisoff,connectGX/GP/GMsothatitisnotaffectedbythenoise.
*1 MATHfunction(optionalcode/MT)isrequired.
19
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
*2 Pollution Degree 2: Describes the degree to which asolid,liquid,orgaswhichdeterioratesdielectricstrengthorsurfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
*3 TheCEstandardsformodulesrepresentstandardsthataremetwhenthemoduleisinstalledinthemainunit.
Construction• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20• Material: Polycarbonate• Color;
Front:Charcoalgreylight(Munsell10B3.6/0.3equivalent) Bezel:Smokeblue(Munsell4.1PB6.0/4.5equivalent)
• Dimensions:45.2mm(W)x111mm(H)x133.1mm(D)(D:includingterminalcover)
• Weight: Approx. 0.3 kg
Power Supply SuppyfromGX/GP,GX60expandableI/O,GM90PSpowersupplymodule.• Powerconsumption:1.6Worless
Isolation
Functional insulation
Digital input CH1-CH8
Reinforced insulationBasic insulation
Digital output CH1Digital output CH2Digital output CH3Digital output CH4Digital output CH5Digital output CH6
Input circuit
Internal circuit
Note: Sincetheinsulationspecificationbetweenoutputterminalchannelsisbasicinsulation,connectsothatthepotentialdifferencebetweenadjacentchannelsdoesnotexceed30VACor60VDC.Ifthepotentialdifferencefromadjacentchannelexceeds30VACor60VDC,insert an unconnected channel between the two channels.
Terminal arrangementsM3 screw terminal
No. Symbol No. Symbol No. Symbol301 DI3 201 DI2 101 DI1
302 DI6 202 DI5 102 DI4
303 DI COM 203 DI8 103 DI7
304 Not Used 204 Not Used 104 Not Used
305 DO1 N.O. 205 DO1 COM 105 DO1 N.C.
306 DO2 N.O. 206 DO2 COM 106 DO2 N.C.
307 DO3 N.O. 207 DO2 COM 107 DO3 N.C.
308 DO4 N.O. 208 DO4 COM 108 DO4 N.C.
309 DO5 N.O. 209 DO5 COM 109 DO5 N.C.
310 DO6 N.O. 210 DO6 COM 110 DO6 N.C.
External DimensionsM3 screw terminal
133.1 (5.24)
8(0.31)
3(0.12)
45.2(1.78)
100(3.94)
Unit: mm(approx. inch)
20
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.However,excludingtheshockat energization.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):ThisGeneral
SpecificationsGMSpecifications:GS04L55B01-01EN
Transport and Storage ConditionsSameastheGX90XA.
Installation limitations• Asinglemodulecanbeinstalledineachunit.• When using the GX90YD digital outputmodules
andGX90UTPIDcontrolmodulestogether,uptoatotalof10modulescanbeinstalled.
• WhenthemeasurementmodeisHighspeed,asinglemodule,eitherthismoduleortheGX90XD,canbeinstalled.DIinputisfixedtoremotemode.Measurementandrecordingarenot possible.
The DO function cannot be used.
21
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN July 30, 2021-00
PULSE INPUT MODULE (Model GX90XP)
GX90XP
• Application:Pulseinput(flowsumandthelike)• Numberofinputs:10• Measurementinterval:100ms(shortest)• Inputtype:Contact(opencollector,voltage-free
contact),level(5Vlogic)• Inputformat:Pulleduptoapprox.5Vthrough5
kΩ,commonpotentialsharedwithinthesamemodule
• Input range: Up to 20 kHz**30Hzwhenthechatteringfilterisinuse(On)
• Minimumdetectionpulsewidth:25μs**15mswhenthechatteringfilterisinuse(On)
• Measurementaccuracy:Count±1pulse Forintegrationcomputation*,thefollowing
accuracies are added. Computationstart:+1scaninterval Computationstop:−1scaninterval*Integrationrequiresthemathfunction(/MToption).
• Chatteringfilter:Removeschatteringupto5ms(canbeturnedon/offoneachchannel)*Whenthechatteringfilterisoff,connectGX/GP/GMsothatitisnotaffectedbythenoise.
• Inputthresholdlevel:Contact(opencollector,voltage-freecontact): Countedwhenachangefrom100kΩor
higherto200ΩorlowerisdetectedLevel(5Vlogic): Countedwhenachangefrom1Vorlower
to3Vorhigherisdetected• Hysteresiswidth:Approx.0.2V• Contact, transistor rating:
Contact:15VDCorhigherand30mAorhigherrating.Minimumapplicableloadcurrent1mAorless.
Transistor:Withthefollowingratings:Vce>15VDC,Ic>30mA
• Allowableinputvoltage:±10VDC• Insulation type: Photocoupler isolation,
transformerisolation• Terminaltype:M3screwterminalorclamp
terminal• Withstandvoltage: Betweentheinputterminalsandtheinternal
circuit:1500VACfor1minute• Insulation resistance: Betweentheinputterminalsandtheinternal
circuit:20MΩorgreaterat500VDC
Safety and EMC Standards• CSA: CSA C22.2 No. 61010-1,
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• UL: UL61010-1(CSANRTL/C),
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• CE/EMCdirective *3: EN61326-1ClassATable2(Foruseinindustrial
locations)compliant ENIEC61000-3-2compliant EN61000-3-3compliant EN55011ClassAGroup1compliant• CE/Lowvoltagedirective *3: EN61010-1compliant,
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• EURoHSdirective:ENIEC63000• WEEEDirective:Compliant• EMCRegulatoryArrangementinAustraliaand
NewZealand(RCM):EN55011ClassAGroup1compliant
• KCmarking:KSC9811,KSC9610-6-2compliant*1 OvervoltageCategory:Describesanumberwhich
definesatransientovervoltagecondition.Impliestheregulationforimpulsewithstandvoltage.Appliestoelectricalequipmentwhichissuppliedfromthefixedinstallationlikeadistributionboard.IIorIdependsonthepowersupplyspecificationofthemainunit.
*2 Pollution Degree 2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
*3 TheCEstandardsformodulesrepresentstandardsthataremetwhenthemoduleisinstalledinthemainunit.
Construction• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20• Material: Polycarbonate• Color;
Front:Charcoalgreylight(Munsell10B3.6/0.3equivalent) Bezel:Smokeblue(Munsell4.1PB6.0/4.5equivalent)
• Dimensions:45.2mm(W)x111mm(H)x133.1mm(D)(D:includingterminalcover)
• Weight: Approx. 0.3 kg
Power Supply SuppyfromGX/GP,GX60expandableI/O,GM90PSpowersupplymodule.• Powerconsumption:0.9Worless
22
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
External DimensionsM3 screw terminal
97.1
(3.8
2)
82.1
(3.2
3)
36(1
.42)
92(3
.62)
100(
3.94
)3(
0.12
)8(
0.31
)
(0.0
7)1.
9
45.2(1.78)
31.9(1.26)
Unit: mm(approx. inch)
Clamp terminal
97.1
(3.8
2)
82.1
(3.2
3)
36(1
.42)
92(3
.62)
100(
3.94
)3(
0.12
)8(
0.31
)
(0.0
7)1.
9
45.2(1.78)
31.9(1.26)
Unit: mm(approx. inch)
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.GXSpecifications:GS04L51B01-01ENGPSpecifications:GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):
GS 04L53B00-01ENGMSpecifications:GS04L55B01-01EN
Transport and Storage ConditionsSameastheGX90XA.
Isolation
Pulse input CH1Pulse input CH2Pulse input CH3Pulse input CH4Pulse input CH5Pulse input CH6Pulse input CH7Pulse input CH8Pulse input CH9Pulse input CH10
Non-isolated Functional insulation
Input circuit Internal circuit
Terminal arrangementsM3 screw terminal/Clamp terminal
No. Symbol No. Symbol21 CH6 + 11 CH1 +
22 − 12 −
23 CH7 + 13 CH2 +
24 − 14 −
25 CH8 + 15 CH3 +
26 − 16 −
27 CH9 + 17 CH4 +
28 − 18 −
29 CH10 + 19 CH5 +
30 − 20 −
* Negativeterminal(common)potentialshared
23
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
ANALOG OUTPUT MODULE (Model GX90YA)
GX90YA
• Application:Retransmissionoutput,Manualoutput
• Numberofoutputs:4(isolatedbetweenchannels)
• Outputtype:4to20mAor0to20mA• Outputupdateinterval:100ms(shortest)• Loadresistance:600Ωorless• Outputrange:0to22mA• Outputaccuracy:±0.1%ofF.S.(1mAormore)
(F.S.=20mA)• Resolution:0.002%• Operatingtemperaturerange:−20to50°C• Terminaltype:M3screwterminalorClamp
terminal• Withstandvoltage Betweentheoutputterminalsandtheinternal
circuit:1500VACforoneminute Betweentheoutputterminalsandtheoutput
terminals:500VACforoneminute• Insulation resistance: Betweentheoutputterminalsandtheinternal
circuit:20MΩorgreaterat500VDC Betweentheoutputterminalsandtheoutput
terminal:20MΩorgreaterat500VDC
Safety and EMC Standards• CSA: CSA C22.2 No. 61010-1,
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• UL: UL61010-1(CSANRTL/C),
OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• CE/EMCdirective *3: EN61326-1ClassATable2(Foruseinindustrial
locations)compliant ENIEC61000-3-2compliant EN61000-3-3compliant EN55011ClassAGroup1compliant• CE/Lowvoltagedirective *3
EN61010-1compliant, OvervoltageCategoryIIorI *1, Pollution Degree 2 *2
• EURoHSdirective:ENIEC63000• WEEEDirective:Compliant• EMCRegulatoryArrangementinAustraliaand
NewZealand(RCM):EN55011ClassAGroup1compliant
• KCmarking:KSC9811,KSC9610-6-2compliant
*1 OvervoltageCategory:Describesanumberwhichdefinesatransientovervoltagecondition.Impliestheregulationforimpulsewithstandvoltage.Appliestoelectricalequipmentwhichissuppliedfromthefixedinstallationlikeadistributionboard.IIorIdependsonthepowersupplyspecificationofthemainunit.
*2 Pollution Degree 2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
*3 TheCEstandardsformodulesrepresentstandardsthataremetwhenthemoduleisinstalledinthemainunit.
Construction• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20• Material: Polycarbonate• Color; Front:Charcoalgreylight(Munsell10B3.6/0.3
equivalent) Bezel:Smokeblue(Munsell4.1PB6.0/4.5
equivalent)• Dimensions:45.2mm(W)x111mm(H)x
133.1mm(D) (D:includingterminalcover)• Weight: Approx. 0.2 kg
Power SupplySuppyfromGX/GP,GX60expandableI/O,GM90PSpowersupplymodule.
• Powerconsumption:3Worless
Isolation
Functional insulation
Analog output CH1Analog output CH2Analog output CH3Analog output CH4
Internal circuit
Terminal arrangementsM3 screw terminal/Clamp terminal
Term. No. Symbol11 CH1 +
12 −
13 CH2 +
14 −
15 CH3 +
16 −
17 CH4 +
18 −
19 Not Used
20 Not Used
24
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
D/A Calibration Value TwotypesofD/Acalibrationvalues(factory
shipmentsettingandusersetting)canbesaved.If the user setting is not proper, it can be restored tothecalibrationvalueatfactoryshipment.
External DimensionsM3 screw terminal/Clamp terminal
82.1(3.23)
107.
1(4.
22)
26 (1.0
2)92
(3.6
2)
100(
3.94
)3(
0.12
)8(
0.31
)
(0.0
7)1.
9
45.2(1.78)
43.8(1.72)
Unit: mm(approx. inch)
Normal Operating ConditionsFornormaloperatingconditionsofthismodule,pleaserefertotheGeneralSpecificationsofthedevice(GX/GP,I/OBaseUnit,orGM)thatthismoduleismounted.GXSpecifications:GS04L51B01-01ENGPSpecifications;GS04L52B01-01ENI/OBaseUnit(ExpandableI/O):GS04L53B00-
01ENGMSpecifications:GS04L55B01-01EN
Transport and Storage ConditionsSameastheGX90XA.
Effects of Operating Conditions• Influenceofpowersupplyvoltagevariation:
Accuracyissatisfiedintherangeofratedpowersupplyvoltage.
• emperatureinfluence:±200ppmofF.S./°Corless
Installation Conditions• Installationlimitationsbyunit GX10/GP10:Upto1module GX20/GP20:Upto2module GM10/GX60:Upto2modulesperunit• Systemlimitations GX10/GX20-1:Upto10module GX20-2:Upto12module• Ifyouwanttousethismodulesimultaneously
withtheGX90XA-04-H0(high-speeduniversaltype)module,thefollowinglimitationappliestothenumberofmodules(includingexpansionmodules)thatcanbeused.
Model Number of modulesGP10(12VDC) Uptotwomodulestotal
GX20/GP20 Uptoninemodulestotal
GX60 Nolimit
GM10 Single unit Uptosevenmodulestotal
GM10Multiunit(mainunit/Subunit)
Nolimit
• Performingthermocouplemeasurementonaslotleftofthismodule(above,below,left,andrightfortheGX20/GP20)mayincreaseRJCerrorsonthatmodule.
25
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
MODEL AND SUFFIX CODESAnalog input module, Digital I/O module (sold separately):MODEL and SUFFIX Code (GX90XA)
Model Suffix Code DescriptionGX90XA Analog Input ModuleNumberofchannels -04 4channels(Type-H0only)
-06 6channels(Type-R1only)-10 10channels(Type-C1,-L1,-U2,-T1,-V1)
Type -C1 Current,scannertype(isolatedbetweenchannels)-L1 DCV/TC/DI,lowwithstandvoltagescannertype(isolatedbetweenchan-
nels)-U2 Universal,Solidstaterelayscannertype(3-wireRTDb-terminalcommon)-T1 DCV/TC/DI,Electromagneticrelayscannertype(isolatedbetweenchan-
nels)-H0 High-speeduniversal,individualA/Dtype(isolatedbetweenchannels)-R1 4-wireRTD/resistance,scannertype(isolatedbetweenchannels)-V1 DCV/TC/DI,highwithstandvoltagescannertype(isolatedbetweenchan-
nels)- N Always NTerminalform -3 Screwterminal(M3)
-C ClampterminalArea N General
MODEL and SUFFIX Code (GX90XD)Model Suffix Code Description
GX90XD Digital Input Module*Numberofchannels -16 16 channelsType -11 Opencollector/Non-voltage,contact(sharedcommon),Rated5VDC- N Always NTerminalform -3 Screwterminal(M3)
-C ClampterminalArea N General
* Ifyouwanttointegratepulseinput,amathfunction(/MToption)isrequiredintheGX/GP/GMmainunit.MODEL and SUFFIX Code (GX90YD)
Model Suffix Code DescriptionGX90YD Digital Output ModuleNumberofchannels -06 6 channelsType -11 Relay,SPDT(NO-C-NC)- N Always NTerminalform -3 Screwterminal(M3)Area N General
MODEL and SUFFIX Code (GX90WD)Model Suffix Code Description
GX90WD Digital Iutput/Output Module*Numberofchannels -0806 8 channel DIs, 6 channel DOsType -01 Opencollector/non-voltagecontact(sharedcommon),rated5VDC;
Relay,SPDT(NO-C-NC)- N Always NTerminalform -3 Screwterminal(M3)Area N General
* Ifyouwanttointegratepulseinput,amathfunction(/MToption)isrequiredintheGX/GP/GMmainunit.
26
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN May 31, 2021-00
MODEL and SUFFIX Code (GX90XP)Model Suffix Code Description
GX90XP Pulse Iutput Module*Numberofchannels -10 10 channelsType -11 DCvoltage/opencollector/non-voltagecontact(sharedcommon),rated
5VDC- N Always NTerminalform -3 Screwterminal(M3)
-C ClampterminalArea N General
* Ifyouwanttointegratepulseinput,amathfunction(/MToption)isrequiredintheGX/GP/GMmainunit.MODEL and SUFFIX Code (GX90YA)
Model Suffix Code DescriptionGX90YA Analog Output ModuleNumberofchannels -04 4 channelsType -C1 Current(isolatedbetweenchannels)- N Always NTerminalform -3 Screwterminal(M3)
-C ClampterminalArea N General
Optional Accessories (Sold Separately)Product Model/part no.
ShuntresisterforM3terminal(250Ω±0.1%) 415940
ShuntresisterforM3terminal(100Ω±0.1%) 415941
ShuntresisterforM3terminal(10Ω±0.1%) 415942
ShuntresisterforClampterminal(250Ω±0.1%) 438920
ShuntresisterforClampterminal(100Ω±0.1%) 438921
ShuntresisterforClampterminal(10Ω±0.1%) 438922
Calibration certificate (sold separately)WhenorderingtheGX10/GX20/GP10/GP20withoptions(analoginput),thecalibrationcertificateforthemodulesisincludedinandshippedwiththecalibrationcertificateofthemainunit.Whenorderingananaloginputmodule,eachmodulegetsitsowncalibrationcertificate(onecertificatepermodule).
Test certificate (QIC, sold separately)WhenorderingtheGX10/GX20/GP10/GP20withoptions(analog/digialI/O),theQICforeachmoduleisincludedinandshippedwiththeQICofthemainunit.WhenorderinganaloginputmodulesanddigitalI/Omodules,eachmodulegetsitsownQIC(oneQICpermodule).
User's ManualProductuser'smanualscanbedownloadedorviewedatthefollowingURL.Toviewtheuser'smanual,youneedtouseAdobeReader7orlaterbyAdobeSystems.URL: www.smartdacplus.com/manual/en/
Product Purchase Specifications•TheGX10/GX20/GP10/GP20iscomposedofthemainunit,I/Omodules,theexpandableI/O,andtheexpansionmodule.
TherearetwowaystopurchaseI/Omodules. OnewayistopurchasethemindividuallybyspecifyingmodelsGX90XA,GX90XD,GX90YD,GX90WD,GX90XP,
and GX90YA, . Theotherwayistopurchasethemasanoption(/UCxxor/USxx).Purchasingthemasanoptionisconvenient,butthisplaceslimitationsonthenumberofanaloginputsthatyoucanobtain.
Ifyouwanttousemorethan51channels,pleasepurchasetheI/Omodulesindividually.•TheGMiscomposedofthedataaquisitionmodule,thepowersupplymodule,themodulebase,theI/Omodule,andtheexpansionmodule.
Pleasepurchasethemodulesandmodulebaseindividually.
27
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B01-01EN July 30, 2021-00Subject to change without notice.
Trademarks The TCP/IP software used in this product and the documentforthatTCP/IPsoftwarearebasedinpartonBSDnetworkingsoftware,Release1licensedfromTheRegentsoftheUniversityofCalifornia.
•SMARTDAC+isregisteredtrademarksortrademarksof Yokogawa Electric Corporation.
• Microsoft, MS and Windows are registered trademarksortrademarksofMicrosoftCorporationUSA.
•PentiumareregisteredtrademarksofIntelCorporation.
•ModbusisaregisteredtrademarkofAEGSchneider.•Othercompanynamesandproductnamesappearinginthisdocumentareregisteredtrademarksortrademarksoftheirrespectiveholders.