6
HAI NAM SWITCHBOARD MANUFACTURE Co., Ltd. PRODUCT CERTIFICATION 010 Address: Lot No. C 32, Road No. 9, Hiep Phuoc Industrial Park, Ho Chi Minh City, Vietnam Tel.: (+84) 8 8734 066 Fax: (+84) 8 8734 067 Email: [email protected] 24 Hour Hot - Line Numbers: 095 888 9670 or 095 888 9680 boundaryless production environment safe modifications functional floor space fast delivery resistant lower investment Good Records Complete Documentation Technical document; As-built drawings are in hard and soft copies. Maintenance free busbar system Lower investment costs Durable surface protection Shock and scratch resistant Minimise damages during transportation Smart and simple design Secure fast deliveries Compact Increase functional floor space in building services Internal form of separation Up to Form 4B as per IEC 60439-1 Enables safe modification under energised conditions Dust and waterproof IP30 up to IP54 as per IEC 529-1 Enables the erection of the equipment in a production environment Test & Standards Type – Tested Switchboard as per IEC 60439-1:2004 and BS EN 60439-1 Certificate by ASTA. Hai nam, your right choice! Why? Hai Nam, manufacture of ASTA-certified reliable switchboards Hai Nam, manufacture of ASTA-certified reliable switchboards

Hai nam, your right choice! Why? HAI NAM · Internal form of separation Up to Form 4B as per IEC 60439-1 Enables safe modification under energised conditions Dust and waterproof IP30

Embed Size (px)

Citation preview

HAI NAMSWITCHBOARD MANUFACTURE Co., Ltd.

PRODUCTCERTIFICATION

010

Address: Lot No. C 32, Road No. 9, Hiep Phuoc Industrial Park, Ho Chi Minh City, VietnamTel.: (+84) 8 8734 066 Fax: (+84) 8 8734 067Email: [email protected]

24 Hour Hot - Line Numbers: 095 888 9670 or 095 888 9680

boundaryless

production environment

safe modifications

functional floor space

fast delivery

resistant

lower investment

Good RecordsComplete DocumentationTechnical document; As-built drawings are in hard and soft copies.

Maintenance free busbar systemLower investment costs

Durable surface protectionShock and scratch resistantMinimise damages during transportation

Smart and simple designSecure fast deliveries

CompactIncrease functional floor space in building services

Internal form of separationUp to Form 4B as per IEC 60439-1Enables safe modification under energised conditions

Dust and waterproofIP30 up to IP54 as per IEC 529-1Enables the erection of the equipment in a production environment

Test & StandardsType – Tested Switchboard as per IEC 60439-1:2004 andBS EN 60439-1 Certificate by ASTA.

Hai nam, your right choice! Why?

Hai Nam, manufacture of ASTA-certified reliable switchboardsHai Nam, manufacture of ASTA-certified reliable switchboards

HAI NAMSWITCHBOARD MANUFACTURE Co., Ltd.

3PRODUCTCERTIFICATION

010

Design with electrical contractors for electrical contractors.

Our Clients:Commercial

▪ Small and large offices

▪ Warehouses

▪ Shopping malls

▪ Schools

▪ Hospitals

▪ Airports

Industrial

▪ Printing

▪ Machinery

▪ Pharmaceutical

▪ Automotive, paper & pulp

▪ Chemical industry

▪ Marine

Utilities

▪ Water treatment plants

▪ Waste management

▪ Energy distribution (electricity, gas)

▪ Telecommunications

▪ Cable providers

▪ Public transport

2

Vacuum circuit breaker panel (Extension)

Sub-distribution Board

Fire FightingControl PanelDistribution Board Distribution Board Motor Control Center

5PRODUCTCERTIFICATION

010

HAI NAMSWITCHBOARD MANUFACTURE Co., Ltd.

Sub-distribution Board

Vacuum circuit breaker panel

Main LV Switchboard 6300A

Subdistribution BoardIn up to 4000AIcw: upon your requestIpk: upon your request

Subdistribution BoardIn up to 4000AIcw: upon your requestIpk: upon your request

Main LVSwitchboardIn up to 8000AIcw:upon your requestIpk:upon your request

Main LV SwitchboardIn up to 8000AIcw: upon your requestIpk: upon your request

Medium - Voltage SwitchboardsUr up to 24 (kV) rmsIn up to 2500AIcw: upon your requestIpk: upon your request

Distribution BoardIn up to 3200AIcw: upon your requestIpk: upon your request

Fire Fighting ControlPanelIn up to 3200AIcw: upon your requestIpk: upon your request

Motor Control CenterIn up to 3200AIcw: upon your requestIpk: upon your request

INTERLOCK

1. Isolator switch (incoming) panel2. Isolator switch (outgoing) panel3. Vacuum circuit breaker panel4. Current and voltage measurements5. Fuse switch panel6. Vacuum circuit breaker panel (outgoing feeder)

ATS

M M M MMM M M

1 2 3 4 5 6

HAI NAMSWITCHBOARD MANUFACTURE Co., Ltd.

4 PRODUCTCERTIFICATION

010

Hai Nam, complete range of electrical switchboardsto meet all your needs.

ASTA type test certificate, a guaranteeof quality!Electrical Switchboards fulfill a vital function in a company’s operations, and must be perfectly suited to our client’s needs. Companies purchasing Hai Nam’s Electrical Switchboards will be able to take full advantage of Hai Nam’s know-how and years of manufacturing experience in production of internationally-qualified ASTA certified switchboards. Hai Nam enables its clients to choose the equipment best suited for their applications.

Temperature–rise limits.

Dielectric properties.

Short-circuit to withstand strength.

Effectiveness of the protective circuit

Clearance and creepage distances.

Mechanical operation.

Degree of protection.

Eletromanagnectic compatibility (EMC).

IP Test Short Circuit Test

High Voltage Test

Temperature-rise Test

Temperature-rise Test

Temperature-rise Test

Impulse Voltage Withstand Test

HAI NAMSWITCHBOARD MANUFACTURE Co., Ltd.

6 PRODUCTCERTIFICATION

010

To obtain international certification for its switchboards, tests have been carried out on the whole configuration, including metal work structures, circuit breaker and busbar system. Verifications has been conducted on the excellency of Hai Nam’s Switchboard products, including:

Short Circuit Test From Control Room High Voltage TestTemperature-rise Test

HAI NAMSWITCHBOARD MANUFACTURE Co., Ltd.

7PRODUCTCERTIFICATION

010

High quality! Great benefit!

HAI NAMSWITCHBOARD MANUFACTURE Co., Ltd.

8 PRODUCTCERTIFICATION

010

HAI NAMSWITCHBOARD MANUFACTURE Co., Ltd.

9PRODUCTCERTIFICATION

010

The quality and reliability of Hai Nam are based on close collaboration with our partners.In addition to the technical excellence of the products, Hai Nam also participates actively in the success of your projects today and tomorow.

The proximity of Hai Nam engineers guarantees fast response and effective servicing for your installation.

Distribution Board

Control Table

Subdistribution Board

Main LV Switchboard

Kiosk Station

This involvement means: Fast response to requests for quotes or tenders. Design of competitive solution with outstanding features.

Hai Nam’s modular design makes it possible to rotationalise installation costs.The high quality and reliability of switchgear guaran-tee continuity of service and a durable system.

Technical Data

Standard and Specifications

Temperature-rise limits (Clause 8.2.1)

Dielectric properties (Clause 8.2.2)

Short-circuit withstand strength(Clause 8.2.3)

Effectiveness of the protective circuit (Clause 8.2.4)

Clearance and creepage distances (Clause 8.2.5)

Mechanical operation (Clause 8.2.6)

Degree of protection (Clause 8.2.7)Electromagnetic Compatibility(EMC) Tests (Clause 8.2.8)

Switchgear rated currents

Internal separation

Finishing

Material

Hinge

Dimensions

Type Test Switchgear and Control gear assembly (TTA)

Rated current of the assembly

Rated current of incoming 3200A ACB unit

Rated diversity factor of the outgoing units

Outgoing 3200A MCCB unit

Rated insulation voltage of the assembly

Rated impulse withstand voltage of the assembly

Rated conditional short-circuit current

(Clause 8.2.3.2.3 a&b)

- Incomming 6300A ACB unit

- Outgoing 3200A MCCB unit

Rated peak and short-time withstand current

( Clause 8.2.3.2.3 b)

- Incoming 6300A 3P ACB 3P unit and its

connection phase busbars

- Main horizontal phase busbars 3P tinned Cu

busbars

Rated peak and short-time withstand current

( Clause 8.2.3.2.3 d)

- Main horizontal neutral busbars (half size)

Effective connection between exposed

conductive parts and the protective circuit

(clause 8.2.4.1)

Rated conditional short-circuit current

(Clause 8.2.4.2)

Protective circuit of the outgoing MCCB unit

Rated insulation Voltage 690V (Ui) for

pollution degree 3

Incoming ACB unit

and Outgoi ng MCCB's

Emission and immunity tests for Environment A

conditions

Form 1 to form 4

Frame Part

Enclosure

Door

Type:

Thickness:

Material:

Type:

Swing Angle:

IEC Publication 60439-1:2001 Edition 4.1 and BS EN 60439-1: 1999 with Admendment 1:2004 Clause 8.2.1, 8.2.2, 8.2.3, 8.2.4,8.2.5, 8.2.6, 8.2.7 and 8.2.8

150kA at 400V, pf=0.20

Up to

Up to

Up to

Up to

Up to

6300A

3200A

6300A

6300A

0.8

3200A

690V

6kV

150kA rms for 3 s, 330 kA Peak

90kA rms for 3 s, 198kA Peak

Verified

90kA rms for 3 s, 198kA Peak

Verified

Verified

Verified

IP 30 to IP 54

Verified

Incoming Air Circuit Breakers

Outgoing feeders

IEC 60439-1, section 7.7, BS EN 60439-1

Electro-Galvanized / Electro Powder Coated not less than 50µm

Electro Powder Coated not less than 50µm

Electro Powder Coated not less than 50µm

Electro-Galvanized Steel Sheet

2mm, 3mm

Aluminium

Die-Cast

180O

Height: 2090 mm

Width: 800,1000,1200 mm

Depth: 800, 1000, 1200, 1400 mm

11PRODUCT

CERTIFICATION

010

HAI NAMSWITCHBOARD MANUFACTURE Co., Ltd.

To produce in accordance with the process.

10PRODUCT

CERTIFICATION

010

HAI NAMSWITCHBOARD MANUFACTURE Co., Ltd.

Step 1: Quotation- Well-trained personel- Specific software

Step 2: CAD/CAM Design- Qualified engineers- In-house CAD/CAM faclifities

Step 3: Sheet Metal Fabrication- 30 ton CNC turret punch with ability to process up to 6mm thick metal sheet- CNC shearing and bending machines

Step 4: Electro-Powder Coating- Semi auto powder-coating system- Colour-customisation faclifitied available- Minimum thickness: 50µm

Step 5: Mechanical Assembly- Modular design- G-profile frames for added strength

Step 6: Electrical Assembly- Well-trained technician- Appropriate tools for electrical wiring

Step 7: Final Quality Control- Primary and secondary injection tests- Dielectric test- Functional test

Step 8: Delivery- Professional team- Always on time

Step 9: Testing & Commissioning at site- Experienced engineers- Good action