2
HIPPS (Refer to P&ID RFT-0000-PPI-10170.01) HIPPS valves XV-172/173 are provided to protect the low pressure section (design pressure of 63.5 barg) downstream of pressure control valve 860-PV-170. The HIPPS valves 860-XV-172/173 are closed by 2oo3 voted high high pressure 860-PAHH-171A/B/C downstream of PRS which are set at 57 barg. The operating scenario under which HIPPS is actuated are : ¨ When a valve downstream of pressure reduction valve is closed inadvertently. ¨ If the pressure control valve fails to regulate pressure. The loop response time of the HIPPS is set at 2 seconds which restricts the pressure increase in the low pressure section, due to closure of downstream valve, to 110% of 63.5 barg in the worst operating scenario. HIPPS valves conform to SIL-3 rating and other components in the HIPPS system conforms to SIL-4 rating. When the HIPPS valves of all the trains are closed due to any process upset, it will also initiate closure of facility ESD valves.

HIPPS

Embed Size (px)

DESCRIPTION

HIPPS

Citation preview

Page 1: HIPPS

HIPPS (Refer to P&ID RFT-0000-PPI-10170.01)

HIPPS valves XV-172/173 are provided to protect the low pressure section (design pressure of

63.5 barg) downstream of pressure control valve 860-PV-170. The HIPPS valves 860-XV-

172/173 are closed by 2oo3 voted high high pressure 860-PAHH-171A/B/C downstream of PRS

which are set at 57 barg. The operating scenario under which HIPPS is actuated are :

¨ When a valve downstream of pressure reduction valve is closed inadvertently.

¨ If the pressure control valve fails to regulate pressure.

The loop response time of the HIPPS is set at 2 seconds which restricts the pressure increase in

the low pressure section, due to closure of downstream valve, to 110% of 63.5 barg in the worst

operating scenario.

HIPPS valves conform to SIL-3 rating and other components in the HIPPS system conforms to

SIL-4 rating.

When the HIPPS valves of all the trains are closed due to any process upset, it will also initiate

closure of facility ESD valves.

In addition, XV-172 is also closed in case of a PSD (Process Shut Down) like malfunction of the

pressure control valve PV-170 i.e. when there is a deviation of the valve position more than 10%

than controller output signal or when the pressure downstream of PV-170 reaches 55 barg.

Semoga membantu, kalau perlu P&ID nya silahkan lewat japri.