22
ELECTRIC HEATING UNITS FANS AIR DISTRIBUTION DEVICES PUMPS FAN COIL UNITS UNITS INDEX OF DRAWINGS AIR CONTROL UNITS-HOT WATER ROOM HEATING UNITS LOUVER SCHEDULE SHEET DESCRIPTION ELEC. SERVICE TO THREE-PHASE UNITS TO BE THREE-WIRE UNLESS NOTED APPROX. CABINET DIMENSIONS DEPTH VERIFY/COORDINATE CABINET DIMENSIONS, MOUNTING DESCRIPTION AND RECESS REQUIREMENTS WITH ARCHITECTURAL DWGS. PRIOR TO ORDERING. RECESSED UNITS TO HAVE FOUR(4) SIDE OVER LAP UNLESS OTHERWISE NOTED UNIT NO. GENERAL NOTES: BY GEN. CONT'R. HEATING LINTELS IN MASONRY WALLS FOR FULL & SEMI-RECESSED UNIT WALL OPENING PROVIDED THREE(3) PHASE COIL LOADS SHALL BE DIVIDED EVENLY ACROSS EACH PHASE. SERVICE CFM M.B.H. ELEC. SERVICE VOLT KW(MIN) AMP LENGTH PHASE REFER TO NOTE NO. HEIGHT RECESS GENERAL CONTRACTOR. WALL LINTEL FOR WALL OPENING BY WHERE REQUIRED FOR DECK SUPPORT AND STEEL FRAMING AROUND ROOF OPENING. PHASE CONSIDERED MINIMUM. MOTOR HORSEPOWERS LISTED ARE TO BE 300 & 301 MEASURED AT 5 FT. FOR P.R.V.'S. SONES VALUES BASED ON A.M.C.A. BULLETINS DESCRIPTION UNIT NO. GENERAL NOTES CONTRACTOR. VERIFY SIZE & COORDINATE WITH GENERAL ROOF & WALL OPENINGS ARE APPROXIMATE. SERVICE SONES MAX. STATIC WHEEL PRESS CFM DIA. MOTOR H.P. VOLT ROOF/ APPROX. WALL OPG. O.W.B.E. E.C.L. FINISH KEY: "O.W.B.E."-OFF WHITE BAKED ENAMEL, "E.C.L."-ETCHED CLEAR LACQUER OR ANODIZED. SUPPLY AIR DIFFUSERS SHALL BE 4-WAY BLOW UNLESS OTHERWISE NOTED ON DWGS. DESCRIPTION REFER TO SPECIFICATIONS FOR OTHER ALL LAY-IN AIR DEVICES SHALL FIT IN 24"X24" LAY-IN CEILING SYSTEM. SYMBOL GENERAL NOTES MANUFACTURERS. TYPE MOUNTING MATERIAL SURFACE LAY-IN STEEL ALUM. PROVIDE AUX. FRAMES FOR AIR DEVICES IN PLASTER, GYPSUM BOARD, GLAZED TILE OR CERAMIC TILE SURFACES. FINISH CATALOG NUMBER SEE NOTE ACCESSORIES DISCHARGE SUCTION & DESCRIPTION UNIT NO. PERFORMANCE GPM SERVICE MOTOR VOLT FT. HD. H.P. MIN. EFF.% PHASE REMARKS VERIFY/COORDINATE UNIT DIMENSIONS, MOUNTING & RECESS REQUIREMENTS WITH ARCHITECTURAL DWGS. PRIOR TO ORDERING. APPROX. CABINET DIM. WIDTH COOLING CAPACITY BASED ON 45 ENT. WATER HEATING CAPACITY BASED ON 70 ENT. AIR & DESCRIPTION & 80 DB/ 67 WB ENT. AIR TEMP. 140 ENT. WATER. NO. UNIT GENERAL NOTES MAXIMUM WATER PRESS. DROP THRU COIL SENS. TOTAL COOLING MBH MOTOR: 115V.-1PH. UNLESS OTHERWISE MOUNTING CFM MBH HTG. NOTED. 5 FT. CLG. HTG. G.P.M. VALVE AUTO SIZE RUNOUT HEIGHT DEPTH MOTOR BASIS OF DESIGN: TITUS FC-1 HIGH RISE VERTICAL STACK FAN COIL UNIT FLOOR SET NO. MODEL 240 8.8 6.6 9.1 1.1 1.8 0.75"/0.75" 2 WAY 17" 17" 88" 1/10 VSR03 FC-2 HIGH RISE VERTICAL STACK FAN COIL UNIT FLOOR SET 300 10.1 7.5 10.5 1.2 2.1 0.75"/0.75" 2 WAY 17" 17" 88" 1/10 VSR04 INLET TYPES - "V.V." VARIABLE VOLUME; "V.V.R." VARIABLE VOLUME REHEAT; "C.V.R." CONSTANT VOLUME REHEAT. UNIT & COIL AT MAX. CFM. 0.6" S.P. MAX. PRESS. DROP THRU UNIT NO. TYPE DIA. GENERAL NOTES REHEAT COIL CAPACITY BASED ON WINTER MIN. CFM, 55 ENT. AIR & 140 ENT. WATER TEMPERATURE. MBH CFM WINTER MAX. MIN. MIN. SUMMER REHEAT COIL GPM RUNOUT SIZE AUTO. VALVE NOTE SEE 1-1 V.V.R. 14 1310 655 325 22 1.4 0.75 2-WAY 0.75 1.2 18 535 1065 12 V.V.R. 1-2 1 2.9 20 460 920 10 V.V.R. 1-3 0.75 1.3 16 345 690 10 V.V.R. 1-4 0.75 2.3 28 550 1100 12 V.V.R. 1-5 1 3.3 34 600 630 10 V.V.R. 1-6 0.75 1.4 12 285 480 8 V.V.R. 1-7 0.75 1.8 25 490 975 12 V.V.R. 1-8 0.75 0.8 9 210 420 8 V.V.R. 1-9 0.75 1.3 20 635 1270 12 V.V.R. 1-10 1 3.4 21 495 660 10 V.V.R. 1-11 1 3.8 56 1300 1300 14 V.V.R. 1-12 1 3.0 36 700 1420 12 V.V.R. 1-13 0.75 2.3 18 425 880 10 V.V.R. 1-14 0.75 2.1 23 525 1050 12 V.V.R. 1-15 0.75 0.8 9 205 410 8 V.V.R. 1-16 1 4.0 50 1160 1920 16 V.V.R. 1-17 0.75 1.1 11 250 480 8 V.V.R. 1-18 0.75 1.0 11 240 500 8 V.V.R. 1-19 0.75 2.1 21 400 800 10 V.V.R. 1-20 1 2.6 15 400 800 8 V.V.R. 1-21 0.75 1.4 21 750 1500 12 V.V.R. 2-1 0.75 2.9 26 800 1600 14 V.V.R. 2-2 1 2.8 54 1240 1360 14 V.V.R. 2-3 0.75 1.4 21 650 1300 14 V.V.R. 2-4 0.75 1.6 13 320 635 8 V.V.R. 2-5 1 3.2 32 580 1155 12 V.V.R. 2-6 0.75 2.2 24 560 1120 12 V.V.R. 2-7 1 3.7 55 1275 1620 14 V.V.R. 2-8 1 5.8 71 1665 1665 14 V.V.R. 2-9 0.75 0.8 10 205 410 8 V.V.R. 2-10 0.75 0.6 9 275 550 8 V.V.R. 2-11 1 2.9 31 610 1220 12 V.V.R. 2-12 0.75 0.8 9 190 380 8 V.V.R. 2-13 0.75 0.8 6 145 280 6 V.V.R. 2-14 0.75 2.3 22 375 750 10 V.V.R. 2-15 0.75 0.8 11 215 425 8 V.V.R. 2-16 1 3.7 46 1330 1330 12 V.V.R. 2-17 1 3.7 55 1100 1100 14 V.V.R. 2-18 3-WAY 3-WAY 3-WAY 3-WAY TMS SQUARE DIFFUSER RD. NECK A1 50F EGGCRATE RETURN GRILLE J1 BY GEN. CONT'R. LINTELS IN MASONRY WALLS FOR FULL & SEMI-RECESSED UNIT WALL OPENINGS PROVIDED RECESSED UNITS TO HAVE FOUR(4) SIDE OVERLAP UNLESS OTHERWISE NOTED. APPROX. CABINET DIMENSIONS HEATING CAPACITY BASED ON 60 ENT. AIR & 140 ENT. WATER. MAXIMUM WATER PRESS. DROP THRU COIL DESCRIPTION NO. UNIT 5 FT. GENERAL NOTES VERIFY/COORDINATE CABINET DIMENSIONS, MOUNTING & RECESS REQUIREMENTS WITH ARCHITECTURAL DWGS. PRIOR TO ORDERING. MOTOR: 115V.-1PH. UNLESS OTHERWISE CFM MOUNTING NOTED. RUNOUT MBH HTG. GPM SIZE LENGTH VALVE/ AUTO. DEPTH RECESS HEIGHT 230 230 230 325 230 145 325 145 325 230 450 325 230 325 145 580 145 145 230 145 325 450 450 325 145 325 325 450 450 145 145 325 145 80 230 145 325 450 EF-1 EF-2 EF-3 EF-4 EF-5 EF-6 EF-7 EF-8 EF-9 EF-10 EF-11 EF-12 POWER ROOF VENTILATOR ROOF VENTILATOR POWER ROOF VENTILATOR HWP-1 HWP-2 CHWP-3 HP INLINE RECIRC. BOOSTER PUMP INLINE RECIRC. BOOSTER PUMP HWP-3 INLINE PUMP HWP-4 HWP-5 INLINE RECIRC. BOOSTER PUMP HWP-6 INLINE RECIRC. BOOSTER PUMP HWP-7 BASE MT'D END SUCTION HWP-8 BASE MT'D END SUCTION INLINE PUMP AH-1 H.W. COIL AH-2 H.W. COIL CHILLER C.W. PUMP RF-1 VANEAXIAL FAN RF-2 VANEAXIAL FAN NORTH 1ST FLOOR TOILETS 900 1.0" 14" 12.8 0.33 120 1 18.5" x 18.5" SOUTH 1ST FLOOR TOILETS 750 1.0" 14" 12.8 0.33 120 1 18.5" x 18.5" AH1 - RETURN 19,200 AH2 - RETURN VARIBLE FREQUENCY DRIVE BY H.C. 31 13 0.25 120 1 53.7 1.25" & 1.25" 36 14 0.25 55.7 1.25" & 1.25" RED BRICK KITCHEN HOOD-122 850 DELI-SH KITCHEN HOOD-207 1020 ENCOUNTER KITCHEN HOOD-409A/409B 3230 FIRST STOP KITCHEN HOOD-512A/512B 2890 PACIFIC RIM KITCHEN HOOD-614 2210 AMERICAS KITCHEN HOOD-722A/722B 4116 AMERICAS KITCHEN HOOD-728 880 BACK OF HOUSE KITCHEN HOOD- 3155 POT WASH HOOD-832 600 DISHWASHER HOOD-846 550 1.25 36" 84 dBA 10 460 3 - DOAS-1 H.W. COIL 19 13 0.25 120 1 42 1" & 1" DOAS-2 H.W. COIL 120 1 1" & 1" 1.25" 14" 14.1 0.33 120 1 18.5" x 18.5" 1.5" 14" 15.8 0.5 120 1 18.5" x 18.5" 2.25" 24" 25 3 460 3 26.5" x 26.5" 1.75" 18" 19.4 1.5 460 3 20.5" x 20.5" 2.0" 24" 17.8 1.5 460 3 26.5" x26.5" 1.75" 20" 23 3 460 3 20.5" x 20.5" 1.5" 14" 14.8 0.5 120 1 18.5" x 18.5" 1.75" 18" 20 1.5 460 3 20.5" x 20.5" 1.25" 14" 16 0.25 120 1 18.5" x 18.5" 1.0" 10" 11.4 0.25 120 1 14.5" x 14.5" H-1 ARCH. HEAVY DUTY WALL HEATER 1st FLOOR VESTIBULE 100 6.8 2 9.6 208 1 15.8" 4" 19.2" 3" H.W.-RESIDENTIAL 180 75 7.5 460 3 71 2.5" & 2" 460 3 13 30 0.16 120 1 - 1.5" & 1.5" FC-3 HORIZONTAL FAN COIL UNIT SUSPENDED SQUARE DIFFUSER RD. NECK A2 EGGCRATE RETURN GRILLE J2 FC-4 HORIZONTAL FAN COIL UNIT FC-5 HORIZONTAL FAN COIL UNIT FC-6 FC-7 220 9.5 3.2 3.9 1.0 0.8 0.75"/0.75" 25" 23" 12" 1/20 HBP02 1310 42.4 25.9 28.3 4.3 5.6 1"/1" 46" 28" 17" 2@1/4 HHP16 2000 64.7 29.1 32.8 6.6 6.5 1"/1" 51" 28" 17" 2@1/4 HHP18 500 14.7 10.5 14.2 1.8 2.8 0.75"/0.75" 20" 20" 88" 1/10 VSR06 600 18.4 13.5 17.6 2.2 3.5 0.75"/0.75" 1/4 VSR08 HEATING AUTO VALVE SHALL BE 2 WAY UNLESS OTHERWISE NOTED ON THE FLOOR PLAN. 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY 2-WAY AUTO. VLV. CV OBD OMNI OBD BASIS OF DESIGN: TITUS A3 OMNI OBD ARCH. DIFF. ROUND PLAQUE A4 R-OMNI OBD FLOWBAR LINEAR DIFFUSER D1 FL-10 3/4" STEEL SUPPLY GRILLE H1 300RL 3/4" SPACING RETURN GRILLE G1 350RL 50F SPIRAL DUCT MT'D GRILLE S1 S300FS FC-8 HORIZONTAL FAN COIL UNIT SUSPENDED 240 8.8 4.6 5.7 1.2 1.1 0.75"/0.75" 28.5" 23" 12" 1/20 HBP03 FC-9 HORIZONTAL FAN COIL UNIT SUSPENDED 300 10.1 6.7 8.4 1.3 1.7 0.75"/0.75" 34.5" 23" 12" 1/20 HBP04 H-2 4 PIPE SYSTEM FC-10 800 24.5 17.7 23.5 3.0 4.7 0.75"/1" 2 WAY 24" 24" 88" 1/4 VSR10 TMS SQUARE DIFFUSER RD. NECK A5 SQUARE DIFFUSER RD. NECK 0.7 0.6 1.4 0.6 1.1 1.6 0.7 0.8 0.4 0.64 1.6 1.8 1.4 1.1 1.0 0.4 1.9 0.5 0.5 1.0 1.2 0.9 0.9 1.3 0.7 0.8 1.5 1.0 1.7 2.7 0.4 0.3 1.4 0.4 0.4 1.1 0.4 1.7 1.7 0.75 0.8 5 120 240 6 V.V.R. 2-19 80 2-WAY 0.4 1 3.2 35 805 1610 14 V.V.R. 2-20 450 2-WAY 1.5 BORDER SHALL BE TYPE 11. AIR DEVICE SHALL MATCH GALVANIZED FINISH OF DUCT. L-1 AH-1/KMUA-1 252"/36"/6" 0.05 31.12 19,555 INTAKE AIR L-2 AH-1/AH-2 72"/24"/6" 0.1 5.94 5345 INTAKE AIR L-3 AH-1/DOAS-1 240"/36"/6" 0.09 27.0 24,000 RELIEF L-4 AH-2 252"/36"/6" 0.05 28.6 14,655 INTAKE AIR L-5 KMUA-2 72"/36"/6" 0.05 19.1 6300 INTAKE AIR L-6 AH-2/DOAS-2 240"/36"/6" 0.08 30.9 19,200 RELIEF AIR HOT WATER UNIT HEATER WALL/CEILING MOUNTED 800 24.2 4.5 1.0" 3 WAY/ 21" 18.5" 21" - SIZE 2.1" NOTES SUSPENDED SUSPENDED WEIGHT lbs. 230 230 65 175 195 270 280 70 80 310 WEIGHT lbs. 85 85 85 175 125 175 85 145 85 125 85 60 1230 821A/821B HWP-9 HWP-10 BASE MT'D END SUCTION BASE MT'D END SUCTION H.W.-KITCHEN/DINING 300 78 10 460 3 77.3 3" & 2.5" H.W.-RESIDENTIAL 75 7.5 2.5" & 2" H.W.-KITCHEN/DINING INLINE PUMP CHILLER H.W. PUMP 120 1 25 30 0.40 - 1.5" & 1.5" CP-1 CHWP-1 INLINE PUMP - BASE BID BASE MT'D END SUCTION KITCHEN CONDENSER WATER C.W.-RESIDENTIAL 53 220 65 190 25 460 460 3 3 54 62.8 1.25" & 1.25" 3" & 2" CHWP-2 BASE MT'D END SUCTION C.W.-KITCHEN/DINING 305 193 30 460 3 62 2.5" & 2" 54 3 460 65 53 KITCHEN CONDENSER WATER INLINE PUMP - BASE BID CP-2 2 WAY 2 WAY 2 WAY 2 WAY 2 WAY 2 WAY 2 WAY ALL COOLING COIL VALVES SHALL BE 2 WAY. 7" 8" 22" 22" 1 208 9.6 2 6.8 283 CEILING HEATER H-9 FORCED FAN 1st FLOOR ENCOUNTER & LOBBY VESTIBULES 350 10.2 3 14.5 208 1 14" 7.5" 16" - ELECTRICAL ROOM BASEMENT FORCED FAN HEATER H-17 PROVIDE DISCONNECT. OTHERWISE. 3" & 2.5" 77.3 3 460 10 78 300 UPBLAST POWER UPBLAST POWER ROOF VENTILATOR UPBLAST POWER ROOF VENTILATOR UPBLAST POWER ROOF VENTILATOR UPBLAST POWER ROOF VENTILATOR UPBLAST POWER ROOF VENTILATOR UPBLAST POWER ROOF VENTILATOR UPBLAST POWER ROOF VENTILATOR UPBLAST POWER ROOF VENTILATOR UPBLAST POWER ROOF VENTILATOR FANS REQUIRE AN INVERTER DUTY MOTOR. FAN COIL UNIT EXP. HORIZONTAL FC-12 FAN COIL UNIT FC-11 EXP. HORIZONTAL SUSPENDED SUSPENDED HHE14 HHE06 200 120 1/4 2@1/4 2 WAY 46" 30" 19" 2 WAY 29" 30" 19" 1"/1" 4.8 3.4 23.8 22.3 27.6 1300 0.75"/0.75" 2.0 1.4 10.0 9.7 11.3 535 GENERAL NOTES A ALL BRANCH DUCTS TO AIR DEVICES AND AIR TERMINAL BOXES SHALL BE EQUAL IN SIZE TO THE NECK OF THE AIR DEVICE OR TERMINAL BOX, UNLESS OTHERWISE NOTED. B REFER TO ARCHITECTURAL CEILING PLANS FOR EXACT LOCATION OF CEILING DEVICES. C FLEXIBLE DUCTWORK MAY UTILIZED ONLY AS INDICATED IN THE DETAILS. D AIR VENTS SHALL BE PROVIDED ON ALL POINTS THAT COULD TRAP AIR AND AS INDICATED IN DETAILS. PROVIDE BALL VALVE AND THREADED CONNECTION FOR VENTING. E AIRFOIL TURNING VANES SHALL BE INSTALLED IN ALL 90 DEGREE DUCT ELBOWS EXCEPT TRANSFER DUCTS AND OPEN RETURN AIR BOOTS. F FLOOR PLANS DO NOT INDICATE ALL POINTS OF VALVING, DEVICES, ETC. ON THE PIPING REQUIRED. REFER TO STANDARD DETAILS, FLUID FLOW DIAGRAMS AND SPECIFICATION FOR ADDITIONAL REQUIREMENTS. G ALL BRANCH DUCT TEE FITTINGS UPSTREAM OF VAV BOXES SHALL BE OF THE CONICAL TYPE. H ANNULAR SPACE OF PIPE, DUCT, CONDUIT, AND SIMILAR PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. REFER TO ARCHITECTURAL DRAWINGS FOR CONSTRUCTION, LAYOUT, AND RATINGS OF WALLS, PARTITIONS, AND OTHER BUILDING ELEMENTS. I HVAC CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL PIPES, DUCTS, UNITS, ETC. WITH ALL OTHER TRADES. PROVIDE ADJUSTMENTS OR OFFSETS WHERE NECESSARY. J ALL DUCTS AND PIPES TO BE RUN ABOVE CEILING. WHERE NO CEILINGS ARE INSTALLED, HOLD AS HIGH AS POSSIBLE TO STRUCTURE UNLESS OTHERWISE NOTED. 120 1 L-7 ELEC. ROOM 84"/102"/6" 0.1 8250 INTAKE AIR 12" 12" 12" 12" 12" 19,200 1.25 36" 84 dBA 10 460 3 - 1230 L-8 MECH./ELEC. 56"/48"/6" 0.08 10.3 8250 RELIEF AIR 5'-0" EF-13 MECHANICAL ROOM-B14 750 0.5" 12" 5.8 0.16 120 1 - 70 INLINE CENTRIFUGAL FAN B10/B12 LAUNDRY-B08 650 0.4" - - 300 W 120 1 - 70 BASIS OF DESIGN: FANTECH "FG" SERIES. EF-14 INLINE DRYER EXHAUST FAN - 0 1175 12 V.V. K1-1 0 1940 14 K1-2 0 1735 14 K1-3 0 1895 14 K2-1 0 0 0 0 1865 14 K2-2 0 0 2475 16 K2-3 0 V.V. V.V. V.V. V.V. V.V. - - - - - - - - - - - - - - - - - - - - - - - THIS BOX IS VAV SHUTOFF, NO REHEAT. 0 EF-15 ELECTRICAL ROOM-B12 7500 0.5" 24" 25 5 460 3 - 415 INLINE CENTRIFUGAL FAN B12 LINEAR 2 SLOT DIFFUSER M1 ML-38 180 71 31 14 46.4 0.33 MOTOR HP - VOLT - PHASE - H-19 AIR CURTAIN STRUCTURE 8000 160 18.9 1.5" 3 WAY/ 106" 20" 18" - 5.2" 2@1 hp 460 3 FLOOR SET FLOOR SET FLOOR SET HIGH RISE VERTICAL STACK FAN COIL UNIT HIGH RISE VERTICAL STACK FAN COIL UNIT HIGH RISE VERTICAL STACK FAN COIL UNIT 20" 20" 88" PROVIDE FRESH AIR OPENING. INFLOOR HEATING PUMP 15 40 0.4 - 1.5" & 1.5" 120 1 6" H-20 AIR CURTAIN WALL 2550 52 0.5 hp 208 1 6.2 1.0 2 WAY/ 2.9" 46" 16.5" 14" - 1 2 36 900 1800 14 V.V.R. 2-21 450 2-WAY 0.95 1 2.0 36 900 1800 14 V.V.R. 1-22 450 2-WAY 0.95 L-9 DOAS-1 72"/24"/6" 0.06 5.94 4000 INTAKE AIR L-10 DOAS-2 72"/24"/6" 0.05 5.94 3300 INTAKE AIR OBD OBD OBD OBD ASD HW/CW LOUVER SHALL BE MOUNTED IN FAUX CHIMNEY. REFER TO ARCHITECTURAL PLANS FOR MOUNTING HEIGHT. 10.3 SQ. FT. THRU OPEN PORTION OF LOUVER. CP-1 INLINE PUMP - ALT #11 KITCHEN CONDENSER WATER 20 90 2 460 3 33 33 3 460 2 90 20 KITCHEN CONDENSER WATER INLINE PUMP - ALT #11 CP-2 1.25" & 1.25" 1.25" & 1.25" 1.25" & 1.25" 2 2 INSULATED 1. LOW PRESSURE SUPPLY DUCT SHALL BE OF DOUBLE WALL CONSTRUCTION WHERE NOTED ON PLANS. 24 CLASS LEAKAGE 24 12 24 X X X INSULATION EXTERNAL LINED INTERNALLY X WALL INSULATED DOUBLE NOT REMARKS LOW PRESSURE RETURN DUCTWORK LOW PRESSURE SUPPLY DUCTWORK: KMUA'S, DUCT SYSTEM SHEET METAL DUCT, EXTERIOR INSULATION, ETC. REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION: OUTSIDE AIR DUCTWORK/PLENUM GENERAL EXHAUST DUCTWORK GENERAL NOTES B -1.5" -1.5" -1.0" B B S.M.A.C.N.A. CLASS. CLASS S.P. CON- +2.0" STRUCT. SEAL B COOLING COIL LEAV. AIR DB/WB ENERGY RECOVERY WHEEL EXHAUST FAN LEAV. AIR DB/WB-SUMMER ELECTRIC PRE-HEAT REQUIRED VIBRATION ISOLATORS MIN OUTSIDE AIR CAPACITY KW/VOLT/PHASE STAGES MAX. AIR P.D. - INCHES W.G. LEAV. AIR DB/WB-WINTER EXH. AIR DB/WB-WINTER EXH. AIR DB/WB-SUMMER EXH. AIR THRU WHEEL - CFM OUTSIDE AIR DB/WB - WINTER OUTSIDE AIR DB/WB - SUMMER WHEEL OUTSIDE AIR CFM VOLTAGE/PHASE MOTOR HP TOTAL S.P. - IN W.G. EXT. S.P. IN W.G. WHEEL TYPE/DIAMETER (IN) MOTOR (MIN. H.P) VFD CFM AUTO. VALVE MIN. CV & TYPE GPM/PIPE RUNOUT MAX WATER P.D.- FT. MAX. AIR P.D.- INCHES W.G. SUPPLY FAN HEATING COIL HEATING COIL CAPACITY BASED ON 140 DEG ENT. WATER MOTOR - 460V - 3PHASE UNLESS NOTED OTHERWISE S.P. ENT. AIR DB/WB TOTAL MBH SENSIBLE MBH MIN. FACE AREA (SQ. FT.) TOTAL S.P. - IN W.G. AUTO. VALVE MIN. CV & TYPE GPM/PIPE RUNOUT MAX. WATER P.D.- FT. MAX. AIR P.D. INCHES W.G. WHEEL TYPE/DIAMETER (IN) MOTOR (MIN. H.P.) LEAV. AIR (DEG. F.) ENT. AIR (DEG. F.) CAPACITY MBH MIN. FACE AREA VFD (SQ. FT) COOLING COIL CAPACITY BASED ON 45 DEG ENT. WATER. EXT. S.P. - IN W.G. DESIGN BASIS UNIT CONFIGURATION GENERAL NOTES UNIT LOCATION AREA SERVED CFM UNIT NUMBER SUMMER 93db/74wb, WINTER 0 db ENERGY RECOVERY WHEEL O.A. CONDITIONS: VARIABLE FREQUENCY DRIVE BY H.C. AH-1 AH-2 KMUA-1 KMUA-2 DOAS-1 DOAS-2 2 FANS @15,000 LEGEND & SCHEDULES H001 DETAILS H003 DETAILS H004 BASEMENT FLOOR PLAN - DUCTWORK H100 FIRST FLOOR PLAN - DUCTWORK H101 SECOND FLOOR PLAN - DUCTWORK H102 THIRD FLOOR PLAN - DUCTWORK H103 4000 6600 1 2 ROOF PLAN H104 FILTER TTL. PRESS. DROP IN W.G. CLEAN FACE AREA (SQ FT). EFFICIENCY % / MERV TYPE/SIZE NORTH DINING SOUTH DINING 3RD FLOOR - NORTH 3RD FLOOR - SOUTH TRANE TRANE 2.0 5.9 2 @ 25 PLENUM/27 YES (2) 37.5 459.3 33.8 55.0 0.085 31/2" 14.6, 3-WAY 38.5 706.4 1070.44 84/69.2 52/51.9 1.12 10.6 153/4" 72.3, 2-WAY CART./12" 36.0 1.67" 85/13 NORTH DORM/CORR. SOUTH DORM CORR. 3RD FLOOR - NORTH 3RD FLOOR - SOUTH TRANE TRANE 1.0 4.5 7.5 FC/12 YES 1.0 4.4 7.5 AF/15 YES 10.0 13.7 283.2 460.3 15.0 15.0 75.0 75.0 0.15 0.21 19/1.5" 31/2" 9, 2-WAY 14.6, 3-WAY 10.0 12.3 115.2 191.3 152.2 246.1 79.0/65.9 79.3/66.0 55/54.5 55/54.2 0.53 0.87 21/2" 35/2" 9.9, 2-WAY 16.5, 2-WAY CART./4" 9.72 1.5" 85/13 CART./4" 18.9 1.4" 85/13 4352 7074 1.0 1.0 2.2 2.2 5 7.5 FC/12 FC/15 YES YES 5000 7000 93/74 93/74 0/-1 0/-1 4352 7074 75/63 75/63 70/53 70/53 79.0/65.9 79.3/66.0 55.3/44.3 53.2/43.1 0.15 1.0 0.5 0.5 460/3 460/3 YES YES 20.7/480/3 33.6/480/3 SCR CONTROL - 100% 100% 59% 60% 12 MEDIUM PRESSURE SUPPLY DUCTWORK +3.0" A 12 X RELIEF AIR DUCTWORK/PLENUM +1.5" B X 2. KITCHEN HOOD EXHAUST DUCT SHALL BE CONTINUOUS WELDED SEAM LIQUID TIGHT. DUCT SHALL BE SLOPED NO LESS THAN 0.25" PER 12" HORIZONTAL RUN. REFER TO SPECIFICATIONS FOR DUCT INSULATION. - KITCHEN HOOD EXHAUST DUCTWORK -4.0" - 2 - DISHWASH/POT WASH EXHAUST DUCTWORK -2.0" - PIPING SCHEMATICS H005 UNIT SHALL BE MOUNTED 18 INCHES AFF. BASIS OF DESIGN: Q-MARK "AWH" SERIES. 1 1 PRE FILTER TYPE/SIZE/MERV PLEATED/2"/8 PLEATED/2"/8 PLEATED/2"/8 1 1 4900 NORTH KITCHENS 3RD FLOOR - NORTH TRANE 1.5 3.9 10 FC/12 YES 6.4 425.12 0 80.0 0.73 6.33 28/2" 13.4, 2-WAY CART./4" 9.72 1.47" 85/13 PLEATED/2"/8 6300 SOUTH KITCHENS 3RD FLOOR - SOUTH TRANE 1.5 4.1 10 FC/15 YES 9.4 546.6 0 80.0 0.54 37/2" 17.2, 2-WAY CART./4" 13.3 1.44" 85/13 PLEATED/2"/8 100% 100% CONTROL DIAGRAMS H006 CONTROL DIAGRAMS H007 1 1 1 X 1 1 1 2 GENERAL NOTES BY THE ARCHITECT. COLOR TO BE SELECTED CFM FROM BOTTOM OF LOUVER MOUNTING HEIGHT IS MAX. APD. UNIT FACE DIMENSIONS W/H/D NET FREE TO FINISHED FLOOR/ROOF. AREA (S.F.) MOUNTING HEIGHT SERVICE DUTY UNIT NO. VARIABLE FREQUENCY DRIVE BY H.C. 1 1 1 FILTER TYPE/MERV 2 2 2.0 5.5 2 @ 25 PLENUM/27 YES (2) 37.5 542.3 30.0 55.00 0.095 36/2" 17, 2-WAY 38.5 732.4 1062.0 85.2/69.1 52/51.9 1.09 151/4" 71.3, 2-WAY CART./12" 36.0 1.67" 85/13 PLEATED/2"/8 1 2 2 1 BASIS OF DESIGN: AIROLITE K6776 WALL/CEILING MOUNTING BRACKET SHALL BE PROVIDED WITH UNIT. 1 2 1 BASIS OF DESIGN: REZNOR "WS" SERIES. 2 1 1 INFINITE SCR CONTROL - INFINITE PLEATED/8 PLEATED/8 OUTDOOR AIR SHALL BE CONTROLLED BY CO2 SENSOR. REFER TO SPECIFICATIONS. UNIT WEIGHT (lbs.) 7900 7900 1300 1600 4300 4800 1 1 2 2 2 2 2 2 2 2 2 2 2 2 BASIS OF DESIGN: Q-MARK "CDF" SERIES. UNIT SHALL BE MOUNTED 8 FT. AFF. BASIS OF DESIGN: Q-MARK "MUH" SERIES. 3 3 2 2 2 2 2 2 2 H108 H107 H106 H105 THIRD FLOOR PLAN - PIPING SECOND FLOOR PLAN - PIPING FIRST FLOOR PLAN - PIPING BASEMENT FLOOR PLAN - PIPING 1 2 2 H008 CONTROL DIAGRAMS H109 ENLARGED MECHANICAL ROOM PLAN INTERNAL INTERNAL INTERNAL INTERNAL INTERNAL INTERNAL 3 3. WET EXHAUST DUCT SHALL BE CONTINUOUS WELDED SEAM LIQUID TIGHT. DUCT SHALL BE OF STAINLESS STEEL CONSTRUCTION AND PITCHED BACK TO DRAIN. UPSTREAM OF VAV BOXES MUA'S, FC'S, & DOWNSTREAM OF VAV BOXES AUTO. VALVE MIN. CV & TYPE GPM/PIPE RUNOUT MAX. WATER P.D.- FT. MAX. AIR P.D. INCHES W.G. LEAV. AIR (DEG. F.) ENT. AIR (DEG. F.) CAPACITY MBH MIN. FACE AREA (SQ. FT) 10.0 12.5 94.4 153.4 55.0 55.0 75.0 75.0 0.15 0.15 0.25 0.37 6/1" 10/1.25" 2.8,2-WAY 4.7, 2-WAY REHEAT COIL 3 3 1 1 1 1 1 1 1 1 DRAW THRU DRAW THRU DRAW THRU DRAW THRU 10.6 10.6 10.6 DRAW THRU DRAW THRU 6.33 6.33 6.33 6.33 6.33 SCHEDULES H002 3 BASIS OF DESIGN: MARS "HV" SERIES 3 3 3 3 3 4 BASIS OF DESIGN: MARS "STD" SERIES 3 H110 FIRST FLOOR RADIANT PIPING PLAN 1 1 1 3 3 FACE & BYPASS DAMPER. 3 2 2 24 LOCKER ROOM EXHAUST DUCTWORK -1.0" B 3 X 1 FINAL FILTER CHARCOAL CHARCOAL - - - - H009 SECTIONS & ELEVATIONS 1 1 1 1 2 2 H010 BUILDING H.W. PIPING SCHEMATIC DESIGN TOTAL 20,000 SUPPLY FANS SIZED FOR 75% REDUNDANCY. 4 4 2 FANS @15,000 DESIGN TOTAL 20,000 4 1 H011 PIPING SCHEMATICS PROVIDED UNDER BASE BID 2 PROVIDED UNDER ALTERNATE #11 3 3 2 2 1 1 3 3 1 1 1 3 DUCT CONSTRUCTION, SEALING, & INSULATION AIR SUPPLY UNITS LEGEND SD A M M 26/20 26"D HWR RL RS HWS CHWS 5 D CWS CWR MPS LPC MPC LPS CHWR T C PRESSURE GUAGE TEMPERATURE GAUGE OR THERMOMETER P UNION CLEANOUT STRAINER EXPANSION JOINT SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS PIPE DISCHARGE TO FLOOR DRAIN UNLESS NOTED OTHERWISE. FOR STEAM SYSTEMS PIPE DISCHARGE TO OUTDOORS. THERMOSTAT. MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT. STRAINER WITH A BLOW DOWN VALVE AND HOSE CONNECTION CHECK VALVE SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS.) COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS.) SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS.) THERMODYNAMIC STEAM TRAP AND DRIP ASSEMBLY TD IB INVERTED BUCKET STEAM TRAP AND DRIP ASSEMBLY FT FLOAT AND THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY TS THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY BM BI-METALIC STEAM TRAP AND DRIP ASSEMBLY 10" = NECK SIZE. 300 = REQUIRED CFM. ALL AIR DEVICE DISCHARGE 4-WAY UNLESS NOTED WITH FLOW ARROWS. AIR DEVICE SHOWN IS 2-WAY SIDE THROW. METHOD OF IDENTIFICATION ALSO APPLIES TO OTHER CEILING MOUNTED AIR DEVICES. WALL OR DUCTWORK MOUNTED AIR DEVICE. SG1 = DESIGNATION (REFER TO AIR DEVICE SCHEDULE). 20"X12" = DUCT CONNECTION SIZE. 200 = REQUIRED CFM. 9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF GRILLE. MANUAL BALANCING VALVE DAMPER WITH LOCKING DEVICE AIR TERMINAL UNIT T CONCENTRIC PIPE REDUCER MANUAL AIR VENT AUTOMATIC AIR VENT PRESSURE AND TEMPERATURE TEST PLUG DETAIL: B = DETAIL DESIGNATION. H2 = SHEET WHERE DETAIL IS LOCATED. SECTION: 1 = SECTION DESIGNATION. H2 = SHEET WHERE SECTION IS LOCATED. EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO SCHEDULES. OR H1 PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN UNLESS NOTED OTHERWISE. DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL. PRESSURE REDUCING VALVE 2 PORT AUTOMATIC CONTROL VALVE 3 PORT AUTOMATIC CONTROL VALVE DUCT MOUNTED SMOKE DETECTOR FURNISHED AND INSTALLED BY OTHERS. COORDINATE LOCATION. DRAIN VALVE WITH HOSE END CONNECTION RECTANGULAR DUCTWORK DIMENSIONS (W X H) ROUND DUCTWORK DIMENSIONS (DIA) H1 2 3 B H2 1 H2 HEATING HOT WATER SUPPLY PIPE HEATING HOT WATER RETURN PIPE CHILLED WATER SUPPLY PIPE CHILLED WATER RETURN PIPE CONDENSER WATER SUPPLY PIPE CONDENSER WATER RETURN PIPE STEAM SUPPLY PIPE - NUMBER INDICATES P.S.I.G. REFRIGERANT LIQUID LINE REFRIGERANT SUCTION LINE DRAIN LINE. PITCH IN DIRECTION INDICATED A-D FIRE DAMPER- A = TYPE. REFER TO DETAIL AND SPECIFICATIONS. D OR S = DYNAMIC OR STATIC SD SMOKE DAMPER FS COMBINATION FIRE - SMOKE DAMPER MEDIUM PRESSURE STEAM SUPPLY PIPE LOW PRESSURE STEAM SUPPLY PIPE LOW PRESSURE CONDENSATE RETURN PIPE MEDIUM PRESSURE CONDENSATE RETURN PIPE CO2 SENSOR. MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT. DATE ISSUED PROJECT # REVISIONS # DATE DESCRIPTION Heapy Engineering Project No. Enter address here 11/10/2011 3:40:27 PM C:\BIM\Model\2010-06019-Central_JLWETZEL.rvt H001 LEGEND & SCHEDULES 2010-06019 Nov. 11, 2011 MAPLE STREET DINING FACILITY 2010-06019

H:L600 0-06019REVIT2012Model 0-06019-Central JLWETZEL · 2011. 11. 11. · basis of design: titus a3 omni obd a4 arch. diff. round plaque r-omni obd d1 flowbar linear diffuser fl-10

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

  • ELECTRIC HEATING UNITS

    FANS

    AIR DISTRIBUTION DEVICES

    PUMPS

    FAN COIL UNITS UNITS

    INDEX OF DRAWINGS

    AIR CONTROL UNITS-HOT WATER

    ROOM HEATING UNITS

    LOUVER SCHEDULE

    SHEET DESCRIPTION

    ELEC. SERVICE TO THREE-PHASE UNITSTO BE THREE-WIRE UNLESS NOTED

    APPROX. CABINET DIMENSIONS

    DEPTH

    VERIFY/COORDINATE CABINET DIMENSIONS, MOUNTING

    DESCRIPTION

    AND RECESS REQUIREMENTS WITH ARCHITECTURALDWGS. PRIOR TO ORDERING.

    RECESSED UNITS TO HAVE FOUR(4) SIDE OVERLAP UNLESS OTHERWISE NOTED

    UNITNO.

    GENERAL NOTES:

    BY GEN. CONT'R.

    HEATING

    LINTELS IN MASONRY WALLS FOR FULL &SEMI-RECESSED UNIT WALL OPENING PROVIDED

    THREE(3) PHASE COIL LOADS SHALL BE DIVIDEDEVENLY ACROSS EACH PHASE.

    SERVICE CFMM.B.H.

    ELEC. SERVICE

    VOLTKW(MIN) AMP LENGTHPHASEREFER TONOTE NO.HEIGHT RECESS

    GENERAL CONTRACTOR.WALL LINTEL FOR WALL OPENING BYWHERE REQUIRED FOR DECK SUPPORT ANDSTEEL FRAMING AROUND ROOF OPENING.

    PHASE

    CONSIDERED MINIMUM.MOTOR HORSEPOWERS LISTED ARE TO BE

    300 & 301 MEASURED AT 5 FT. FOR P.R.V.'S.SONES VALUES BASED ON A.M.C.A. BULLETINS

    DESCRIPTIONUNITNO.

    GENERAL NOTES

    CONTRACTOR.VERIFY SIZE & COORDINATE WITH GENERALROOF & WALL OPENINGS ARE APPROXIMATE.

    SERVICESONESMAX.STATIC WHEEL

    PRESSCFM

    DIA.

    MOTOR

    H.P. VOLTROOF/APPROX.

    WALL OPG.

    O.W.B.E. E.C.L.

    FINISH KEY: "O.W.B.E."-OFF WHITE BAKED ENAMEL,"E.C.L."-ETCHED CLEAR LACQUER OR ANODIZED.

    SUPPLY AIR DIFFUSERS SHALL BE 4-WAYBLOW UNLESS OTHERWISE NOTED ON DWGS.

    DESCRIPTION

    REFER TO SPECIFICATIONS FOR OTHER

    ALL LAY-IN AIR DEVICES SHALL FIT IN24"X24" LAY-IN CEILING SYSTEM.

    SYMBOL

    GENERAL NOTES

    MANUFACTURERS.

    TYPE MOUNTING MATERIAL

    SURFACELAY-IN STEEL ALUM.

    PROVIDE AUX. FRAMES FOR AIR DEVICES INPLASTER, GYPSUM BOARD, GLAZED TILE ORCERAMIC TILE SURFACES.

    FINISH CATALOG NUMBER SEENOTEACCESSORIES

    DISCHARGESUCTION &

    DESCRIPTIONUNITNO.

    PERFORMANCE

    GPMSERVICE

    MOTOR

    VOLTFT. HD. H.P.

    MIN.EFF.%PHASE

    REMARKS

    VERIFY/COORDINATE UNIT DIMENSIONS,MOUNTING & RECESS REQUIREMENTS WITHARCHITECTURAL DWGS. PRIOR TO ORDERING.

    APPROX. CABINET DIM.

    WIDTH

    COOLING CAPACITY BASED ON 45 ENT. WATER

    HEATING CAPACITY BASED ON 70 ENT. AIR &

    DESCRIPTION

    & 80 DB/ 67 WB ENT. AIR TEMP.

    140 ENT. WATER.

    NO.UNIT

    GENERAL NOTES

    MAXIMUM WATER PRESS. DROP THRU COIL

    SENS. TOTAL

    COOLING MBH

    MOTOR: 115V.-1PH. UNLESS OTHERWISE

    MOUNTING CFMMBHHTG.

    NOTED.

    5 FT.

    CLG.HTG.

    G.P.M.VALVEAUTO

    SIZERUNOUT

    HEIGHTDEPTH

    MOTOR

    BASIS OF DESIGN: TITUS

    FC-1 HIGH RISE VERTICALSTACK FAN COIL UNIT

    FLOOR SET

    NO.MODEL

    240 8.8 6.6 9.1 1.1 1.8 0.75"/0.75" 2 WAY 17" 17" 88" 1/10 VSR03

    FC-2 HIGH RISE VERTICALSTACK FAN COIL UNIT

    FLOOR SET 300 10.1 7.5 10.5 1.2 2.1 0.75"/0.75" 2 WAY 17" 17" 88" 1/10 VSR04

    INLET

    TYPES - "V.V." VARIABLE VOLUME;"V.V.R." VARIABLE VOLUME REHEAT;"C.V.R." CONSTANT VOLUME REHEAT.

    UNIT & COIL AT MAX. CFM.0.6" S.P. MAX. PRESS. DROP THRU

    UNITNO.

    TYPEDIA.

    GENERAL NOTESREHEAT COIL CAPACITY BASED ONWINTER MIN. CFM, 55 ENT. AIR &140 ENT. WATER TEMPERATURE.

    MBH

    CFM

    WINTERMAX.MIN. MIN.

    SUMMER

    REHEAT COIL

    GPM RUNOUTSIZE

    AUTO.VALVE

    NOTESEE

    1-1 V.V.R. 14 1310 655 325 22 1.4 0.75 2-WAY

    0.751.218535106512V.V.R.1-2

    12.92046092010V.V.R.1-3

    0.751.31634569010V.V.R.1-4

    0.752.328550110012V.V.R.1-5

    13.33460063010V.V.R.1-6

    0.751.4122854808V.V.R.1-7

    0.751.82549097512V.V.R.1-8

    0.750.892104208V.V.R.1-9

    0.751.320635127012V.V.R.1-10

    13.42149566010V.V.R.1-11

    13.8561300130014V.V.R.1-12

    13.036700142012V.V.R.1-13

    0.752.31842588010V.V.R.1-14

    0.752.123525105012V.V.R.1-15

    0.750.892054108V.V.R.1-16

    14.0501160192016V.V.R.1-17

    0.751.111250480

    8V.V.R.1-18 0.751.011240500

    8V.V.R.1-19

    0.752.12140080010V.V.R.1-20

    12.6154008008V.V.R.1-21

    0.751.421750150012V.V.R.2-1

    0.752.926800160014V.V.R.2-2

    12.8541240136014V.V.R.2-3

    0.751.421650130014V.V.R.2-4

    0.751.6133206358V.V.R.2-5

    13.232580115512V.V.R.2-6

    0.752.224560112012V.V.R.2-7

    13.7551275162014V.V.R.2-8

    15.8711665166514V.V.R.2-9

    0.750.8102054108V.V.R.2-10

    0.750.692755508V.V.R.2-11

    12.931610122012V.V.R.2-12

    0.750.891903808V.V.R.2-13

    0.750.861452806V.V.R.2-14

    0.752.32237575010V.V.R.2-15

    0.750.8112154258V.V.R.2-16

    13.7461330133012V.V.R.2-17

    13.7551100110014V.V.R.2-18

    3-WAY

    3-WAY

    3-WAY

    3-WAY

    TMSSQUARE DIFFUSER RD. NECKA1

    50FEGGCRATE RETURN GRILLEJ1

    BY GEN. CONT'R.

    LINTELS IN MASONRY WALLS FOR FULL &

    SEMI-RECESSED UNIT WALL OPENINGS PROVIDED

    RECESSED UNITS TO HAVE FOUR(4) SIDE

    OVERLAP UNLESS OTHERWISE NOTED.

    APPROX. CABINET DIMENSIONS

    HEATING CAPACITY BASED ON 60 ENT. AIR &

    140 ENT. WATER.

    MAXIMUM WATER PRESS. DROP THRU COIL

    DESCRIPTIONNO.

    UNIT

    5 FT.

    GENERAL NOTES

    VERIFY/COORDINATE CABINET DIMENSIONS,

    MOUNTING & RECESS REQUIREMENTS WITH

    ARCHITECTURAL DWGS. PRIOR TO ORDERING.

    MOTOR: 115V.-1PH. UNLESS OTHERWISE

    CFMMOUNTING

    NOTED.

    RUNOUT

    MBH

    HTG.GPM

    SIZE LENGTHVALVE/

    AUTO.

    DEPTH RECESSHEIGHT

    230

    230

    230

    325

    230

    145

    325

    145

    325

    230

    450

    325

    230

    325

    145

    580

    145

    145

    230

    145

    325

    450

    450

    325

    145

    325

    325

    450

    450

    145

    145

    325

    145

    80

    230

    145

    325

    450

    EF-1

    EF-2

    EF-3

    EF-4

    EF-5

    EF-6

    EF-7

    EF-8

    EF-9

    EF-10

    EF-11

    EF-12

    POWER ROOF VENTILATOR

    ROOF VENTILATOR

    POWER ROOF VENTILATOR

    HWP-1

    HWP-2

    CHWP-3

    HP

    INLINE RECIRC. BOOSTER PUMP

    INLINE RECIRC. BOOSTER PUMP

    HWP-3 INLINE PUMP

    HWP-4

    HWP-5

    INLINE RECIRC. BOOSTER PUMP

    HWP-6

    INLINE RECIRC. BOOSTER PUMP

    HWP-7

    BASE MT'D END SUCTION

    HWP-8

    BASE MT'D END SUCTION

    INLINE PUMP

    AH-1 H.W. COIL

    AH-2 H.W. COIL

    CHILLER C.W. PUMP

    RF-1 VANEAXIAL FAN

    RF-2 VANEAXIAL FAN

    NORTH 1ST FLOOR TOILETS 900 1.0" 14" 12.8 0.33 120 1 18.5" x 18.5"

    SOUTH 1ST FLOOR TOILETS 750 1.0" 14" 12.8 0.33 120 1 18.5" x 18.5"

    AH1 - RETURN 19,200

    AH2 - RETURN

    VARIBLE FREQUENCY DRIVE BY H.C.

    31 13 0.25 120 1 53.7 1.25" & 1.25"

    36 14 0.25 55.7 1.25" & 1.25"

    RED BRICK KITCHEN HOOD-122 850

    DELI-SH KITCHEN HOOD-207 1020

    ENCOUNTER KITCHEN HOOD-409A/409B 3230

    FIRST STOP KITCHEN HOOD-512A/512B 2890

    PACIFIC RIM KITCHEN HOOD-614 2210

    AMERICAS KITCHEN HOOD-722A/722B 4116

    AMERICAS KITCHEN HOOD-728 880

    BACK OF HOUSE KITCHEN HOOD- 3155

    POT WASH HOOD-832 600

    DISHWASHER HOOD-846 550

    1.25 36" 84 dBA 10 460 3 -

    DOAS-1 H.W. COIL 19 13 0.25 120 1 42 1" & 1"

    DOAS-2 H.W. COIL 120 1 1" & 1"

    1.25" 14" 14.1 0.33 120 1 18.5" x 18.5"

    1.5" 14" 15.8 0.5 120 1 18.5" x 18.5"

    2.25" 24" 25 3 460 3 26.5" x 26.5"

    1.75" 18" 19.4 1.5 460 3 20.5" x 20.5"

    2.0" 24" 17.8 1.5 460 3 26.5" x26.5"

    1.75" 20" 23 3 460 3 20.5" x 20.5"

    1.5" 14" 14.8 0.5 120 1 18.5" x 18.5"

    1.75" 18" 20 1.5 460 3 20.5" x 20.5"

    1.25" 14" 16 0.25 120 1 18.5" x 18.5"

    1.0" 10" 11.4 0.25 120 1 14.5" x 14.5"

    H-1 ARCH. HEAVY DUTYWALL HEATER

    1st FLOOR VESTIBULE 100 6.8 2 9.6 208 1 15.8" 4" 19.2" 3"

    H.W.-RESIDENTIAL 180 75 7.5 460 3 71 2.5" & 2"

    460 3

    13 30 0.16 120 1 - 1.5" & 1.5"

    FC-3 HORIZONTAL FANCOIL UNIT

    SUSPENDED

    SQUARE DIFFUSER RD. NECKA2

    EGGCRATE RETURN GRILLEJ2

    FC-4 HORIZONTAL FANCOIL UNIT

    FC-5 HORIZONTAL FANCOIL UNIT

    FC-6

    FC-7

    220 9.5 3.2 3.9 1.0 0.8 0.75"/0.75" 25" 23" 12" 1/20 HBP02

    1310 42.4 25.9 28.3 4.3 5.6 1"/1" 46" 28" 17" 2@1/4 HHP16

    2000 64.7 29.1 32.8 6.6 6.5 1"/1" 51" 28" 17" 2@1/4 HHP18

    500 14.7 10.5 14.2 1.8 2.8 0.75"/0.75" 20" 20" 88" 1/10 VSR06

    600 18.4 13.5 17.6 2.2 3.5 0.75"/0.75" 1/4 VSR08

    HEATING AUTO VALVE SHALL BE 2 WAY UNLESS OTHERWISE NOTED ON THE FLOOR PLAN.

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    2-WAY

    AUTO.VLV. CV

    OBD

    OMNI OBD

    BASIS OF DESIGN: TITUS

    A3 OMNI OBD

    ARCH. DIFF. ROUND PLAQUEA4 R-OMNI OBD

    FLOWBAR LINEAR DIFFUSERD1 FL-10

    3/4" STEEL SUPPLY GRILLEH1 300RL

    3/4" SPACING RETURN GRILLEG1 350RL

    50F

    SPIRAL DUCT MT'D GRILLES1 S300FS

    FC-8 HORIZONTAL FANCOIL UNIT

    SUSPENDED 240 8.8 4.6 5.7 1.2 1.1 0.75"/0.75" 28.5" 23" 12" 1/20 HBP03

    FC-9 HORIZONTAL FANCOIL UNIT

    SUSPENDED 300 10.1 6.7 8.4 1.3 1.7 0.75"/0.75" 34.5" 23" 12" 1/20 HBP04

    H-2

    4 PIPE SYSTEM

    FC-10 800 24.5 17.7 23.5 3.0 4.7 0.75"/1" 2 WAY 24" 24" 88" 1/4 VSR10

    TMSSQUARE DIFFUSER RD. NECKA5

    SQUARE DIFFUSER RD. NECK

    0.7

    0.6

    1.4

    0.6

    1.1

    1.6

    0.7

    0.8

    0.4

    0.64

    1.6

    1.8

    1.4

    1.1

    1.0

    0.4

    1.9

    0.5

    0.5

    1.0

    1.2

    0.9

    0.9

    1.3

    0.7

    0.8

    1.5

    1.0

    1.7

    2.7

    0.4

    0.3

    1.4

    0.4

    0.4

    1.1

    0.4

    1.7

    1.7

    0.750.851202406V.V.R.2-19 80 2-WAY0.4

    13.235805161014V.V.R.2-20 450 2-WAY1.5

    BORDER SHALL BE TYPE 11. AIR DEVICE SHALL MATCH GALVANIZED FINISH OF DUCT.

    L-1 AH-1/KMUA-1 252"/36"/6" 0.05 31.12 19,555 INTAKE AIR

    L-2 AH-1/AH-2 72"/24"/6" 0.1 5.94 5345 INTAKE AIR

    L-3 AH-1/DOAS-1 240"/36"/6" 0.09 27.0 24,000 RELIEF

    L-4 AH-2 252"/36"/6" 0.05 28.6 14,655 INTAKE AIR

    L-5 KMUA-2 72"/36"/6" 0.05 19.1 6300 INTAKE AIR

    L-6 AH-2/DOAS-2 240"/36"/6" 0.08 30.9 19,200 RELIEF AIR

    HOT WATER UNIT HEATER WALL/CEILING MOUNTED 800 24.2 4.5 1.0" 3 WAY/ 21" 18.5" 21" -

    SIZE

    2.1"

    NOTES

    SUSPENDED

    SUSPENDED

    WEIGHTlbs.

    230

    230

    65

    175

    195

    270

    280

    70

    80

    310

    WEIGHTlbs.

    85

    85

    85

    175

    125

    175

    85

    145

    85

    125

    85

    60

    1230

    821A/821B

    HWP-9

    HWP-10

    BASE MT'D END SUCTION

    BASE MT'D END SUCTION

    H.W.-KITCHEN/DINING 300 78 10 460 3 77.3 3" & 2.5"

    H.W.-RESIDENTIAL 75 7.5 2.5" & 2"

    H.W.-KITCHEN/DINING

    INLINE PUMP CHILLER H.W. PUMP 120 125 30 0.40 - 1.5" & 1.5"

    CP-1

    CHWP-1

    INLINE PUMP - BASE BID

    BASE MT'D END SUCTION

    KITCHEN CONDENSER WATER

    C.W.-RESIDENTIAL

    53

    220

    65

    190 25

    460

    460

    3

    3

    54

    62.8

    1.25" & 1.25"

    3" & 2"

    CHWP-2 BASE MT'D END SUCTION C.W.-KITCHEN/DINING 305 193 30 460 3 62 2.5" & 2"

    5434606553KITCHEN CONDENSER WATERINLINE PUMP - BASE BIDCP-2

    2 WAY

    2 WAY

    2 WAY

    2 WAY

    2 WAY

    2 WAY

    2 WAY

    ALL COOLING COIL VALVES SHALL BE 2 WAY.

    7"8"22"22"12089.626.8283CEILING HEATER

    H-9 FORCED FAN 1st FLOOR ENCOUNTER& LOBBY VESTIBULES

    350 10.2 3 14.5 208 1 14" 7.5" 16" -ELECTRICAL ROOM

    BASEMENTFORCED FAN HEATERH-17

    PROVIDE DISCONNECT.

    OTHERWISE.

    3" & 2.5"77.334601078300

    UPBLAST POWER

    UPBLAST POWERROOF VENTILATORUPBLAST POWER

    ROOF VENTILATORUPBLAST POWER

    ROOF VENTILATORUPBLAST POWER

    ROOF VENTILATOR

    UPBLAST POWERROOF VENTILATORUPBLAST POWER

    ROOF VENTILATORUPBLAST POWER

    ROOF VENTILATORUPBLAST POWER

    ROOF VENTILATORUPBLAST POWER

    ROOF VENTILATOR

    FANS REQUIRE AN INVERTER DUTY MOTOR.

    FAN COIL UNITEXP. HORIZONTALFC-12

    FAN COIL UNITFC-11 EXP. HORIZONTAL SUSPENDED

    SUSPENDED

    HHE14

    HHE06

    200

    120

    1/4

    2@1/4

    2 WAY 46" 30" 19"

    2 WAY 29" 30" 19"

    1"/1"4.83.423.822.327.61300

    0.75"/0.75"2.01.410.09.711.3535

    GENERAL NOTESA ALL BRANCH DUCTS TO AIR DEVICES AND AIR TERMINAL BOXES SHALL BE EQUAL IN SIZE TO THE NECK OF THE AIR DEVICE OR TERMINAL BOX, UNLESS OTHERWISE NOTED.

    B REFER TO ARCHITECTURAL CEILING PLANS FOR EXACT LOCATION OF CEILING DEVICES.

    C FLEXIBLE DUCTWORK MAY UTILIZED ONLY AS INDICATED IN THE DETAILS.

    D AIR VENTS SHALL BE PROVIDED ON ALL POINTS THAT COULD TRAP AIR AND AS INDICATED IN DETAILS. PROVIDE BALL VALVE AND THREADED CONNECTION FOR VENTING.

    E AIRFOIL TURNING VANES SHALL BE INSTALLED IN ALL 90 DEGREE DUCT ELBOWS EXCEPT TRANSFER DUCTS AND OPEN RETURN AIR BOOTS.

    F FLOOR PLANS DO NOT INDICATE ALL POINTS OF VALVING, DEVICES, ETC. ON THE PIPING REQUIRED. REFER TO STANDARD DETAILS, FLUID FLOW DIAGRAMS AND SPECIFICATION FOR ADDITIONAL REQUIREMENTS.

    G ALL BRANCH DUCT TEE FITTINGS UPSTREAM OF VAV BOXES SHALL BE OF THE CONICAL TYPE.

    H ANNULAR SPACE OF PIPE, DUCT, CONDUIT, AND SIMILAR PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. REFER TO ARCHITECTURAL DRAWINGS FOR CONSTRUCTION, LAYOUT, AND RATINGS OF WALLS, PARTITIONS, AND OTHER BUILDING ELEMENTS.

    I HVAC CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL PIPES, DUCTS, UNITS, ETC. WITH ALL OTHER TRADES. PROVIDE ADJUSTMENTS OR OFFSETS WHERE NECESSARY.

    J ALL DUCTS AND PIPES TO BE RUN ABOVE CEILING. WHERE NO CEILINGS ARE INSTALLED, HOLD AS HIGH AS POSSIBLE TO STRUCTURE UNLESS OTHERWISE NOTED.

    120 1

    L-7 ELEC. ROOM 84"/102"/6" 0.1 8250 INTAKE AIR

    12"

    12"

    12"

    12"

    12"

    19,200 1.25 36" 84 dBA 10 460 3 - 1230

    L-8 MECH./ELEC. 56"/48"/6" 0.08 10.3 8250 RELIEF AIR5'-0"

    EF-13 MECHANICAL ROOM-B14 750 0.5" 12" 5.8 0.16 120 1 - 70INLINE CENTRIFUGAL FAN

    B10/B12

    LAUNDRY-B08 650 0.4" - - 300 W 120 1 - 70

    BASIS OF DESIGN: FANTECH "FG" SERIES.

    EF-14 INLINE DRYEREXHAUST FAN

    -0117512V.V.K1-1

    0194014K1-2

    0173514K1-3

    0189514K2-1

    0

    0

    0

    0186514K2-2 0

    0247516K2-3 0

    V.V.

    V.V.

    V.V.

    V.V.

    V.V.

    - - -

    - - - -

    - - - -

    - - - -

    - - - -

    - - - -

    THIS BOX IS VAV SHUTOFF, NO REHEAT.

    0

    EF-15 ELECTRICAL ROOM-B12 7500 0.5" 24" 25 5 460 3 - 415INLINE CENTRIFUGAL FAN

    B12

    LINEAR 2 SLOT DIFFUSERM1 ML-38

    180 71

    31 14 46.40.33

    MOTOR

    HP

    -

    VOLT

    -

    PHASE

    -

    H-19 AIR CURTAIN STRUCTURE 8000 160 18.9 1.5" 3 WAY/ 106" 20" 18" -5.2"

    2@1 hp 460 3

    FLOOR SET

    FLOOR SET

    FLOOR SET

    HIGH RISE VERTICALSTACK FAN COIL UNITHIGH RISE VERTICALSTACK FAN COIL UNIT

    HIGH RISE VERTICALSTACK FAN COIL UNIT

    20" 20" 88"

    PROVIDE FRESH AIR OPENING.

    INFLOOR HEATING PUMP 15 40 0.4 - 1.5" & 1.5"120 1

    6"

    H-20 AIR CURTAIN WALL 2550 52 0.5 hp 208 1 6.2 1.0 2 WAY/2.9"

    46" 16.5" 14" -

    1236900180014V.V.R.2-21 450 2-WAY0.95

    12.036900180014V.V.R.1-22 450 2-WAY0.95

    L-9 DOAS-1 72"/24"/6" 0.06 5.94 4000 INTAKE AIR

    L-10 DOAS-2 72"/24"/6" 0.05 5.94 3300 INTAKE AIR

    OBD

    OBD

    OBD

    OBD

    ASD

    HW/CW

    LOUVER SHALL BE MOUNTED IN FAUX CHIMNEY. REFER TO ARCHITECTURALPLANS FOR MOUNTING HEIGHT.

    10.3 SQ. FT. THRU OPEN PORTION OF LOUVER.

    CP-1 INLINE PUMP - ALT #11 KITCHEN CONDENSER WATER 20 90 2 460 3 33

    33346029020KITCHEN CONDENSER WATERINLINE PUMP - ALT #11CP-2

    1.25" & 1.25"

    1.25" & 1.25"

    1.25" & 1.25"

    2

    2

    INSULATED

    1. LOW PRESSURE SUPPLY DUCT SHALL BE OF DOUBLE WALL CONSTRUCTION WHERE NOTED ON PLANS.

    24

    CLASSLEAKAGE

    24

    12

    24

    X

    X

    X

    INSULATIONEXTERNAL

    LINEDINTERNALLY

    X

    WALLINSULATED

    DOUBLE NOTREMARKS

    LOW PRESSURE RETURN DUCTWORK

    LOW PRESSURE SUPPLY DUCTWORK: KMUA'S,

    DUCT SYSTEM

    SHEET METAL DUCT, EXTERIOR INSULATION, ETC. REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:

    OUTSIDE AIR DUCTWORK/PLENUM

    GENERAL EXHAUST DUCTWORK

    GENERAL NOTES

    B-1.5"

    -1.5"

    -1.0"

    B

    B

    S.M.A.C.N.A. CLASS.

    CLASSS.P. CON-

    +2.0"

    STRUCT.SEAL

    B

    CO

    OLIN

    G C

    OIL

    LEAV. AIR DB/WB

    EN

    ER

    GY

    RE

    CO

    VE

    RY

    WH

    EE

    LE

    XH

    AU

    ST

    FA

    N

    LEAV. AIR DB/WB-SUMMER

    ELECTRIC PRE-HEAT REQUIRED

    VIBRATION ISOLATORS

    MIN OUTSIDE AIR

    CAPACITY KW/VOLT/PHASE

    STAGES

    MAX. AIR P.D. - INCHES W.G.

    LEAV. AIR DB/WB-WINTER

    EXH. AIR DB/WB-WINTER

    EXH. AIR DB/WB-SUMMER

    EXH. AIR THRU WHEEL - CFM

    OUTSIDE AIR DB/WB - WINTER

    OUTSIDE AIR DB/WB - SUMMER

    WHEEL OUTSIDE AIR CFM

    VOLTAGE/PHASE

    MOTOR HP

    TOTAL S.P. - IN W.G.

    EXT. S.P. IN W.G.

    WHEEL TYPE/DIAMETER (IN)

    MOTOR (MIN. H.P)

    VFD

    CFM

    AUTO. VALVE MIN. CV & TYPE

    GPM/PIPE RUNOUT

    MAX WATER P.D.- FT.

    MAX. AIR P.D.- INCHES W.G.

    SU

    PP

    LY

    FA

    NH

    EA

    TIN

    G C

    OIL

    HEATING COIL CAPACITY BASED ON 140 DEG ENT. WATER MOTOR - 460V - 3PHASE UNLESS NOTED OTHERWISE

    S.P

    .

    ENT. AIR DB/WB

    TOTAL MBH

    SENSIBLE MBH

    MIN. FACE AREA (SQ. FT.)

    TOTAL S.P. - IN W.G.

    AUTO. VALVE MIN. CV & TYPE

    GPM/PIPE RUNOUT

    MAX. WATER P.D.- FT.

    MAX. AIR P.D. INCHES W.G.

    WHEEL TYPE/DIAMETER (IN)

    MOTOR (MIN. H.P.)

    LEAV. AIR (DEG. F.)

    ENT. AIR (DEG. F.)

    CAPACITY MBH

    MIN. FACE AREA

    VFD

    (SQ. FT)

    COOLING COIL CAPACITY BASED ON 45 DEG ENT. WATER.

    EXT. S.P. - IN W.G.

    DESIGN BASIS

    UNIT CONFIGURATION

    GENERAL NOTES

    UNIT LOCATION

    AREA SERVED

    CFM

    UNIT NUMBER

    SUMMER 93db/74wb, WINTER 0 db

    ENERGY RECOVERY WHEEL O.A. CONDITIONS:

    VARIABLE FREQUENCY DRIVE BY H.C.

    AH-1 AH-2 KMUA-1 KMUA-2 DOAS-1 DOAS-2

    2 FANS @15,000

    LEGEND & SCHEDULESH001

    DETAILSH003

    DETAILSH004

    BASEMENT FLOOR PLAN - DUCTWORKH100

    FIRST FLOOR PLAN - DUCTWORKH101

    SECOND FLOOR PLAN - DUCTWORKH102

    THIRD FLOOR PLAN - DUCTWORKH103

    4000 6600

    1

    2

    ROOF PLANH104

    FIL

    TE

    R

    TTL. PRESS. DROP IN W.G. CLEAN

    FACE AREA (SQ FT).

    EFFICIENCY % / MERV

    TYPE/SIZE

    NORTH DINING SOUTH DINING

    3RD FLOOR - NORTH 3RD FLOOR - SOUTH

    TRANE TRANE

    2.0

    5.9

    2 @ 25

    PLENUM/27

    YES (2)

    37.5

    459.3

    33.8

    55.0

    0.085

    31/2"

    14.6, 3-WAY

    38.5

    706.4

    1070.44

    84/69.2

    52/51.9

    1.12

    10.6

    153/4"

    72.3, 2-WAY

    CART./12"

    36.0

    1.67"

    85/13

    NORTH DORM/CORR. SOUTH DORM CORR.

    3RD FLOOR - NORTH 3RD FLOOR - SOUTH

    TRANE TRANE

    1.0

    4.5

    7.5

    FC/12

    YES

    1.0

    4.4

    7.5

    AF/15

    YES

    10.0 13.7

    283.2 460.3

    15.0 15.0

    75.0 75.0

    0.15 0.21

    19/1.5" 31/2"

    9, 2-WAY 14.6, 3-WAY

    10.0 12.3

    115.2 191.3

    152.2 246.1

    79.0/65.9 79.3/66.0

    55/54.5 55/54.2

    0.53 0.87

    21/2" 35/2"

    9.9, 2-WAY 16.5, 2-WAY

    CART./4"

    9.72

    1.5"

    85/13

    CART./4"

    18.9

    1.4"

    85/13

    4352 7074

    1.0 1.0

    2.2 2.2

    5 7.5

    FC/12 FC/15

    YES YES

    5000 7000

    93/74 93/74

    0/-1 0/-1

    4352 7074

    75/63 75/63

    70/53 70/53

    79.0/65.9 79.3/66.0

    55.3/44.3 53.2/43.1

    0.15 1.0

    0.5 0.5

    460/3 460/3

    YES YES

    20.7/480/3 33.6/480/3

    SCR CONTROL -

    100% 100%59% 60%

    12MEDIUM PRESSURE SUPPLY DUCTWORK +3.0" A

    12 XRELIEF AIR DUCTWORK/PLENUM +1.5" B

    X

    2. KITCHEN HOOD EXHAUST DUCT SHALL BE CONTINUOUS WELDED SEAM LIQUID TIGHT. DUCT SHALL BE SLOPED NO LESS THAN0.25" PER 12" HORIZONTAL RUN. REFER TO SPECIFICATIONS FOR DUCT INSULATION.

    -KITCHEN HOOD EXHAUST DUCTWORK -4.0" - 2

    -DISHWASH/POT WASH EXHAUST DUCTWORK -2.0" -

    PIPING SCHEMATICSH005

    UNIT SHALL BE MOUNTED 18 INCHES AFF. BASIS OF DESIGN: Q-MARK "AWH" SERIES.1

    1

    PRE FILTER TYPE/SIZE/MERV PLEATED/2"/8 PLEATED/2"/8 PLEATED/2"/8

    1

    1

    4900

    NORTH KITCHENS

    3RD FLOOR - NORTH

    TRANE

    1.5

    3.9

    10

    FC/12

    YES

    6.4

    425.12

    0

    80.0

    0.73

    6.33

    28/2"

    13.4, 2-WAY

    CART./4"

    9.72

    1.47"

    85/13

    PLEATED/2"/8

    6300

    SOUTH KITCHENS

    3RD FLOOR - SOUTH

    TRANE

    1.5

    4.1

    10

    FC/15

    YES

    9.4

    546.6

    0

    80.0

    0.54

    37/2"

    17.2, 2-WAY

    CART./4"

    13.3

    1.44"

    85/13

    PLEATED/2"/8

    100% 100%

    CONTROL DIAGRAMS

    H006

    CONTROL DIAGRAMS

    H007

    1

    1

    1

    X

    1

    1

    1 2

    GENERAL NOTES

    BY THE ARCHITECT.

    COLOR TO BE SELECTED

    CFM

    FROM BOTTOM OF LOUVER

    MOUNTING HEIGHT IS

    MAX.APD.

    UNIT FACEDIMENSIONS

    W/H/D

    NET FREE

    TO FINISHED FLOOR/ROOF.

    AREA (S.F.)MOUNTINGHEIGHT

    SERVICE DUTYUNITNO.

    VARIABLE FREQUENCY DRIVE BY H.C.1

    1

    1

    FILTER TYPE/MERV

    2 2

    2.0

    5.5

    2 @ 25

    PLENUM/27

    YES (2)

    37.5

    542.3

    30.0

    55.00

    0.095

    36/2"

    17, 2-WAY

    38.5

    732.4

    1062.0

    85.2/69.1

    52/51.9

    1.09

    151/4"

    71.3, 2-WAY

    CART./12"

    36.0

    1.67"

    85/13

    PLEATED/2"/81 2

    2

    1

    BASIS OF DESIGN: AIROLITE K6776

    WALL/CEILING MOUNTING BRACKET SHALL BE PROVIDED WITH UNIT.

    1 2

    1 BASIS OF DESIGN: REZNOR "WS" SERIES.2

    1

    1

    INFINITESCR CONTROL -

    INFINITE

    PLEATED/8 PLEATED/8

    OUTDOOR AIR SHALL BE CONTROLLED BY CO2 SENSOR. REFER TO SPECIFICATIONS.

    UNIT WEIGHT (lbs.) 7900 7900 1300 1600 4300 4800

    1

    1

    2

    2

    2

    2

    2

    2

    2

    2

    2

    2

    2

    2 BASIS OF DESIGN: Q-MARK "CDF" SERIES.

    UNIT SHALL BE MOUNTED 8 FT. AFF. BASIS OF DESIGN: Q-MARK "MUH" SERIES.3

    3

    2

    2

    2

    2

    2

    2

    2

    H108

    H107

    H106

    H105

    THIRD FLOOR PLAN - PIPING

    SECOND FLOOR PLAN - PIPING

    FIRST FLOOR PLAN - PIPING

    BASEMENT FLOOR PLAN - PIPING

    1

    2

    2

    H008

    CONTROL DIAGRAMS

    H109 ENLARGED MECHANICAL ROOM PLAN

    INTERNAL INTERNAL INTERNAL INTERNAL INTERNAL INTERNAL

    3

    3. WET EXHAUST DUCT SHALL BE CONTINUOUS WELDED SEAM LIQUID TIGHT. DUCT SHALL BE OF STAINLESS STEEL CONSTRUCTIONAND PITCHED BACK TO DRAIN.

    UPSTREAM OF VAV BOXES

    MUA'S, FC'S, & DOWNSTREAM OF VAV BOXES

    AUTO. VALVE MIN. CV & TYPE

    GPM/PIPE RUNOUT

    MAX. WATER P.D.- FT.

    MAX. AIR P.D. INCHES W.G.

    LEAV. AIR (DEG. F.)

    ENT. AIR (DEG. F.)

    CAPACITY MBH

    MIN. FACE AREA (SQ. FT) 10.0 12.5

    94.4 153.4

    55.0 55.0

    75.0 75.0

    0.15 0.15

    0.25 0.37

    6/1" 10/1.25"

    2.8,2-WAY 4.7, 2-WAY

    RE

    HE

    AT

    CO

    IL

    3

    3

    1

    1

    1

    1

    1

    1

    1

    1

    DRAW THRU DRAW THRUDRAW THRUDRAW THRU

    10.6 10.6 10.6

    DRAW THRUDRAW THRU

    6.336.33 6.33 6.33 6.33

    SCHEDULESH002

    3

    BASIS OF DESIGN: MARS "HV" SERIES3

    3

    3

    3

    3

    4

    BASIS OF DESIGN: MARS "STD" SERIES3

    H110 FIRST FLOOR RADIANT PIPING PLAN

    1

    1

    1

    3 3

    FACE & BYPASS DAMPER.3

    2

    2

    24LOCKER ROOM EXHAUST DUCTWORK -1.0" B 3X

    1

    FINAL FILTER CHARCOAL CHARCOAL - -- -

    H009

    SECTIONS & ELEVATIONS

    1

    1

    1

    1

    2

    2

    H010

    BUILDING H.W. PIPING SCHEMATIC

    DESIGN TOTAL 20,000

    SUPPLY FANS SIZED FOR 75%REDUNDANCY.

    4

    4 2 FANS @15,000DESIGN TOTAL 20,0004

    1

    H011

    PIPING SCHEMATICS

    PROVIDED UNDER BASE BID2 PROVIDED UNDER ALTERNATE #113

    3

    2

    2

    1

    1

    3

    3

    1

    1

    1

    3

    DUCT CONSTRUCTION, SEALING, & INSULATION

    AIR SUPPLY UNITSLEGEND

    SD

    A

    M

    M

    26/20

    26"D

    HWR

    RL

    RS

    HWS

    CHWS

    5

    D

    CWS

    CWR

    MPS

    LPC

    MPC

    LPS

    CHWR

    T

    C

    PRESSURE GUAGE

    TEMPERATURE GAUGE OR THERMOMETER

    P

    UNION

    CLEANOUT

    STRAINER

    EXPANSION JOINT

    SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS PIPE DISCHARGETO FLOOR DRAIN UNLESS NOTED OTHERWISE. FOR STEAMSYSTEMS PIPE DISCHARGE TO OUTDOORS.

    THERMOSTAT. MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. WHENMOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.

    STRAINER WITH A BLOW DOWN VALVE AND HOSE CONNECTION

    CHECK VALVE

    SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE

    BASED ON APPLICATIONS.)

    COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO

    SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS.)

    SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE

    BASED ON APPLICATIONS.)

    THERMODYNAMIC STEAM TRAP AND DRIP ASSEMBLYTD

    IBINVERTED BUCKET STEAM TRAP AND DRIP ASSEMBLY

    FTFLOAT AND THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY

    TSTHERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY

    BMBI-METALIC STEAM TRAP AND DRIP ASSEMBLY

    10"� = NECK SIZE. 300 = REQUIRED CFM. ALL AIR DEVICE DISCHARGE4-WAY UNLESS NOTED WITH FLOW ARROWS. AIR DEVICE SHOWN IS 2-WAYSIDE THROW. METHOD OF IDENTIFICATION ALSO APPLIES TO OTHER CEILINGMOUNTED AIR DEVICES.

    WALL OR DUCTWORK MOUNTED AIR DEVICE. SG1 = DESIGNATION (REFER TO AIR

    DEVICE SCHEDULE). 20"X12" = DUCT CONNECTION SIZE. 200 = REQUIRED CFM.

    9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF GRILLE.

    MANUAL BALANCING VALVE DAMPER WITH LOCKING DEVICE

    AIR TERMINAL UNIT

    T

    CONCENTRIC PIPE REDUCER

    MANUAL AIR VENT

    AUTOMATIC AIR VENT

    PRESSURE AND TEMPERATURE TEST PLUG

    DETAIL: B = DETAIL DESIGNATION. H2 = SHEET WHERE DETAIL IS LOCATED.

    SECTION: 1 = SECTION DESIGNATION. H2 = SHEET WHERE SECTION IS LOCATED.

    EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO SCHEDULES.OR H1

    PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN UNLESS NOTEDOTHERWISE.

    DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

    PRESSURE REDUCING VALVE

    2 PORT AUTOMATIC CONTROL VALVE

    3 PORT AUTOMATIC CONTROL VALVE

    DUCT MOUNTED SMOKE DETECTOR FURNISHED AND INSTALLED BY OTHERS.COORDINATE LOCATION.

    DRAIN VALVE WITH HOSE END CONNECTION

    RECTANGULAR DUCTWORK DIMENSIONS (W X H)

    ROUND DUCTWORK DIMENSIONS (DIA)

    H1

    2

    3

    B

    H2

    1

    H2

    HEATING HOT WATER SUPPLY PIPE

    HEATING HOT WATER RETURN PIPE

    CHILLED WATER SUPPLY PIPE

    CHILLED WATER RETURN PIPE

    CONDENSER WATER SUPPLY PIPE

    CONDENSER WATER RETURN PIPE

    STEAM SUPPLY PIPE - NUMBER INDICATES P.S.I.G.

    REFRIGERANT LIQUID LINE

    REFRIGERANT SUCTION LINE

    DRAIN LINE. PITCH IN DIRECTION INDICATED

    A-D FIRE DAMPER- A = TYPE. REFER TO DETAIL AND SPECIFICATIONS. D ORS = DYNAMIC OR STATIC

    SDSMOKE DAMPER

    FSCOMBINATION FIRE - SMOKE DAMPER

    MEDIUM PRESSURE STEAM SUPPLY PIPE

    LOW PRESSURE STEAM SUPPLY PIPE

    LOW PRESSURE CONDENSATE RETURN PIPE

    MEDIUM PRESSURE CONDENSATE RETURN PIPE

    CO2 SENSOR. MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. WHENMOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.

    DATE ISSUEDPROJECT #

    REVISIONS

    # DATE DESCRIPTION

    Heapy Engineering

    Project No.

    Enter address here

    11

    /10

    /20

    11 3

    :40

    :27

    PM

    C:\B

    IM\M

    ode

    l\20

    10-0

    601

    9-C

    en

    tra

    l_JL

    WE

    TZ

    EL.r

    vt

    H001

    LEGEND & SCHEDULES

    2010-06019 Nov. 11, 2011

    MAPLE STREET DININGFACILITY

    2010-06019

  • PERSONZONEUNIT

    ROOM

    1-1 101 - RED BRICK PIZZA 1 7.5 40 379 0.18 460 1310

    20077101A - RED BRICK VESTIBULE1-2

    80013526587.5101 - RED BRICK PIZZA 31-3

    630100498105.0135 - BREAK ROOM1-4

    1000299288257.5102 - DELI-SH 11-5

    63014141957.5102 - DELI-SH 21-6

    360281416207.5102 - DELI-SH 31-7

    10051103A - PATISSERIE VESTIBLUE1-8

    42017054557.5103 - PATISSERIE 21-9

    1260581708457.5104 - ENCOUNTER 11-10

    665530857367.5104 - ENCOUNTER 21-11

    130010429447.5129 - ENCOUNTER KITCHEN1-12

    10061105A - FIRST STOP VESTIBULE1-13

    880561493487.5105 - FIRST STOP 21-14

    10508281053637.5105 - FIRST STOP 31-15

    205126123 - WOMENS ROOM1-16

    205108

    122 - FIRST STOP KITCHEN1-17

    5003817945.0130 - PRODUCTION OFFICE1-18

    4802618425.0128 - STUDENT MGR1-19

    45017870827.5113A - NORTH KITCHEN 11-20

    48013045437.5113A - NORTH KLITCHEN 21-21

    0.18

    0.06

    0.18

    0.18

    0.18

    0.18

    0.18

    0.18

    0.18

    0.18

    0.18

    0.06

    0.06

    0.18

    0.18

    18007240397 - NORTH MECHANICAL ROOM1-22

    VENTILATION SCHEDULE AH-1

    NO.OA CFM/

    POPULTN.ZONE

    (SQ. FT.)AREA

    (CFM/SQ. FT.)O.A.

    O.A.ZONE

    SUPPLYACTUAL

    CFM

    945 865101 - RED BRICK PIZZA 2 7.5 4 0.18 250

    6059138 - WOMENS ROOM

    6079137 - MENS ROOM

    6040134 - STAFF TOILET

    10095102A - DELI-SH VESTIBULE

    6058140 - WOMENS ROOM

    6060139 - MENS ROOM

    875283423207.5103 - PATISSERIE 1 0.18

    1320278568167.5105 - FIRST STOP 1 0.18

    124 - MENS ROOM

    192021072357.5 0.18

    150100131 - STORAGE

    10065132 - STORAGE

    10066133 - STORAGE

    220181804-7.5113A - NORTH KLITCHEN 3 0.18

    5059125 - STORAGE

    5070126 - STORAGE

    PERSONZONEUNIT

    ROOM

    2-1 106A - PACIFIC RIM VESTIBULE

    7.5 47 722 0.18 603 1600

    10047

    106 - PACIFIC RIM 22-2

    136021072757.5106 - PACIFIC RIM 32-3

    1300778998597.5106 - PACIFIC RIM 42-4

    108 - MENS ROOM2-5

    1155457657337.5107 - AMERICAS 12-6

    1120403665277.5107 - AMERICAS 22-7

    2-8

    166524675987.5107 - AMERICAS 52-9

    410170338107.5107B - AMERICAS PRIVATE ROOM2-10

    5002914235.0142 - RES. LIFE OFFICE2-11

    100135

    119 - BUSINESS OFFICE2-13

    2802516125.0118 - MANAGER2-14

    7506333565.0117 - ASST. MANAGER2-15

    200570110 - RECEIVING2-16

    22548

    113B - SOUTH KITCHEN 12-17

    1100297115247.5113B - SOUTH KITCHEN 22-18

    19019096027.5113C - SOUTH KITCHEN 12-19

    1610399690267.5107 - AMERICAS 32-20

    0.18

    0.18

    0.18

    0.18

    0.18

    0.18

    0.06

    0.06

    0.06

    0.18

    0.18

    0.18

    VENTILATION SCHEDULE AH-2

    NO.OA CFM/

    POPULTN.ZONE

    (SQ. FT.)AREA

    (CFM/SQ. FT.)O.A.

    O.A.ZONE SUPPLY

    ACTUAL

    CFM

    1620399690267.5107 - AMERICAS 4 0.18

    2802516425.0

    121 - STAFF WC

    0.06

    111 - RECEIVING CLERK

    133020675047.5 0.18

    741 1200106 - PACIFIC RIM 1 7.5 30 0.18 448

    255192

    109 - WOMENS ROOM 330190

    5070116 - STORAGE

    5067142A - STORAGE

    5084120 - STORAGE2-12

    1170152115677.5141 - RESIDENTIAL LOBBY 0.06

    1015.0 0.06

    18007600398 - SOUTH MECHANICAL ROOM2-21

    PERSONZONEUNIT

    ROOM

    FC-10-1 A218 - NORTH SUITE 800781

    VENTILATION SCHEDULE DOAS-1

    NO.OA CFM/

    POPULTN.ZONE

    (SQ. FT.)AREA

    (CFM/SQ. FT.)O.A.

    O.A.ZONE

    SUPPLYACTUAL

    CFM

    7.5 14 0.06 190

    FC-10-2 B218 - CENTRAL SUITE 8009187.5 14 0.06 200

    A219 - KITCHEN 2001477.5 2 0.18 52

    A220 - TRASH/RECYCLING 58 90

    A221 - ACCESSIBLE RESTROOM 72 90

    A222 - BATHROOM 174 180

    A223 - BATHROOM 121 90

    A224 - BATHROOM 114 90

    A225 - BATHROOM 178 180

    B219 - KITCHEN 2001277.5 2 0.18 47

    B220 - BATHROOM 178 180

    B221 - ACCESSIBLE RESTROOM 83 90

    B222 - BATHROOM 86 90

    B223 - BATHROOM 88 90

    B224 - BATHROOM 174 180

    B225 - TRASH/RECYCLING 75 90

    299 - CORRIDOR 1 1403 580

    299 - CORRIDOR 2 305 100

    299 - CORRIDOR 3 305 190

    302 - MENS ROOM 81 65

    303 - WOMENS ROOM 125 90

    399 - CORRIDOR 539 200

    PERSONZONEUNIT

    ROOM

    FC-3 305 - STUDY 200133

    VENTILATION SCHEDULE DOAS-2

    NO.OA CFM/

    POPULTN.ZONE

    (SQ. FT.)AREA

    (CFM/SQ. FT.)O.A.

    O.A.ZONE SUPPLY

    ACTUAL

    CFM

    5.0 6 0.06 47

    FC-4 304A - LIVING/DINING 7354125.0 2 0.06 43

    304B - MASTER BR 1702645.0 1 0.06 26

    304C - SECOND BR 1201425.0 1 0.06 17

    304D - BATHROOM 6592

    304E - BATHROOM/LAUNDRY 22061

    FC-5 300 - MULTI-PURPOSE ROOM 200018615.0 30 0.06 327

    FC-6-1 202 - STUDY 5003305.0 8 0.06 75

    FC-6-2 203 - STUDY 5003165.0 8 0.06 74

    FC-7 204 - LAUNDRY ROOM 6002137.5 2 0.06 35

    FC-10-3 C218 - SOUTH SUITE 8008287.5 14 0.06 193

    FC-11 B08 - LAUNDRY 1300153

    FC-12 B04 - REFRIG. EQUIPMENT 535344

    B01 - RES. LIFE STORAGE 2501287

    B05 - DINING STORAGE 100267

    B06 - MENS LOCKER ROOM 280473

    B07 - WOMENS LOCKER ROOM 280481

    B11 - SECURITY 5019

    B99 - CORRIDOR 4001353

    201 - RESIDENTIAL LOBBY 67514377.5 6 0.06 164

    299 - CORRIDOR 4 220243

    299 - CORRIDOR 5 3601266

    C219 - KITCHEN 2001697.5 2 0.18 57

    C221 - ACCESSIBILE BATHROOM 9072

    C222 - BATHROOM 180186

    C223 - BATHROOM 90140

    C224 - BATHROOM 90145

    C225 - BATHROOM 180168

    -- -

    60

    60

    -- -

    60-- -

    60-- -

    60-- -

    -- -

    -- -

    205

    205

    -- - 255

    330-- -

    -- - 100

    90

    90

    180

    90

    90

    180

    180

    90

    90

    90

    180

    90

    65

    90

    A226 - JANITORS CLOSET 50 90

    205 - JANITORS CLOSET 70 65

    70

    B04 - JANITORS CLOSET 115128

    C226 - JANITORS CLOSET 5031

    GRAVITY ROOF VENTILATORS

    STEEL FRAMING AROUND ROOF OPENINGS, WHERE REQUIREDFOR DECK SUPPORT, TO BE PROVIDE BY GEN. CONT'R.

    NECK SIZES ARE APPROXIMATE. VERIFY SIZE & COORDINATEROOF OPENING REQUIREMENTS WITH GEN. CONT'R.

    DESCRIPTIONUNITNO.

    GENERAL NOTES:

    CFMSERVICE NECK SIZE/STATICPRESS.

    MAX.

    ROOF OPG.

    APPROX.

    HEIGHTCURB

    (INCL.CURB)HEIGHTAPPROX.

    REMARKS

    V-1 ELEVATOR HOISTWAY VENTING 3200ELEV 1 - 399 .02 52x52 12" 34" DO NOT PROVIDE DAMPER

    EQUIPMENT DATA

    H-3 (2) HOT WATER CONVERTER - SHELL & TUBE TYPE - TYPICAL OF TWOCAPACITY: HEAT 500 GPM OF WATER FROM EWT 110 DEG. TO LWT 140 DEG. THRU TUBES, WITHMAXIMUM 5 FT. OF HEAD PRESSURE DROP, WITH 15 PSIG STEAM IN THE SHELL.MINIMUM 137 SQ. FT. HEATING SURFACE AREA.FOULING FACTOR: 0.0007APPROX. DIM.: 14" DIA. x 57" LONGBASIS OF DESIGN: B&G

    H-4 AIR SEPARATOR (HOT WATER SYSTEM)

    H-5 EXPANSION TANK - DIAPHRAGM TYPE

    H-6 HOT WATER (BUILDING) SYSTEM FILTER FEEDER

    INLINE TYPE COMBINATION AIR & DIRT SEPARATOR

    H-7 AUTOMATIC WATER MAKE-UP ASSEMBLY-HOT WATERPROVIDE SHUTOFF VALVE, STRAINER, UNION, PRESSURE REDUCING VALVE SETAT 30 PSIG (ADJUSTABLE), UNION, SAFETY RELIEF VALVE SET AT 75 PSIG, ANDSHUTOFF VALVE, AT 0.75" SIZE. PROVIDE 0.75" BYPASS WITH GLOBE VALVE.

    H-8 SPLIT SYSTEM - COOLING ONLYINDOOR UNIT:CAPACITY: 17.2 MBH TOTAL, 12.2 MBH SENSIBLEINDOOR: 80 DEG. F. DB, 67 DEG. F. WBOUTDOOR: 95 DEG. F. DB, 75 DEG. F. WBAIRFLOW: 275 CFM-LISTED @ LOW FAN SPEEDFAN: 0.76 FLA, ELECTRIC: 1.0 MCA @ 208V,1 PHASEWEIGHT: 22 lbs.

    OUTDOOR UNIT:CAPACITY: 1.5 TONSFAN: 0.93 FLA, ELECTRIC: 14 MCA, 15 MOCP @ 208V, 1 PHASEWEIGHT: 119 lbs.REFRIGERANT PIPE: 0.25"O.D. LIQUID, 0.5"O.D. SUCTIONUNIT SHALL HAVE LOW AMBIENT CONTROL, AND FAN SPEED WITH REMOTETHERMOSTAT.DISCONNECT BY E.C.BASIS OF DESIGN: MITSUBISHI - MSY

    H-10 HEAT PUMP CHILLER: PACKAGED, HEAT RECOVERY HEAT PUMP CHILLER

    CHILLED WATER PERFORMANCE: 169,000 BTUH OF COOLING, WITH 13 GPM OFWATER FLOW, ENTERING AT 70 DEGREES F. AND LEAVING AT 44 DEGREES F.MAXIMUM PRESSURE DROP SHALL BE 5 FT. HD.

    CONDENSER WATER PERFOMANCE: 249,000 BTUH OF HEAT REJECTION, WITH25 GPM OF WATER FLOW, ENTERING AT 120 DEGREES F. AND LEAVING AT 140DEGREES F. MAXIMUM PRESSURE DROP 5 FT. HD.

    POWER REQUIREMENT: UNIT MCA 38.0, 460 VOLT/3 PHASE.

    BASIS OF DESIGN MULTISTACK MS15. REFER TO SPECIFICATION SECTION 23 7001 FOR COMPLETE REQUIREMENTS. EQUIPMENT PART OF ALTERNATE #11.

    H-11 CONDENSER WATER EXPANSION TANK: HORIZONTAL BLADDER STYLECAPACITY: 21 GALLONS MINIMUMACCEPTANCE VOLUME: 11 GALLONS MINIMUMAIR PRESSURE: 10 PSIGAPPROX. DIMENSIONS: 16” DIA. X 29” LONG.

    H-12 CONDENSER WATER AUTOMATIC WATER MAKEUP ASSEMBLY. PROVIDESHUTOFF VALVE, STRAINER UNIONS, PRESSURE REDUCING VALVE SET FOR 10PSIG (ADJUSTABLE), UNION, SHUTOFF VALVE AND SAFETY RELIEF VALVE SET AT50 PSIG, ALL 0.75” SIZE. PROVIDE0.75” BYPASS WITH GLOBE VALVE.

    H-13 AIR SEPERATOR, CONDENSER WATER SYSTEM: INLINE, COMBINATION AIRAND DIRT SEPERATOR.FLOW RATE: 20 GPMLINE SIZE: 2”MAX PRESSURE DROP: 3 FT. HD AT SPECIFIED FLOW RATEAPPROXIMATE DIMENSIONS: 6” DIA. X 25” TALLSPIROTHERM VDT-1A OR APPROVED EQUAL

    H-14 CHEMICAL SHOT FEEDER, CONSENSER WATER (KITCHEN) SYSTEM FEEDERSIZE 1 GALLON, WITH SHUTOFF VALVES ON INLET, OUTLET AND DRAIN.

    FLOW RATE: 500 GPMLINE SIZE: 8”MAX PRESSURE DROP: 2 FT. HD AT SPECIFIED FLOW RATEAPPROXIMATE DIMENSIONS: 16” DIA. X 52” TALLSPIROTHERM VDN-800-FL OR APPROVED EQUAL

    SIZE 5 GALLON, WITH SHUTOFF VALVES ON INLET, OUTLET AND DRAIN.

    H-15 DOMESTIC HOT WATER HEATER CONDENSATE PUMPDUPLEX TYPE WITH 14 GALLON RECEIVER.CAPACITY: 12,000 EDR WITH 12 GPM AT 25 PSI DISCHARGEMOTOR: 0.5 HP- 120 VOLT- 1 PHASE, 3500 RPM

    H-16 BUILDING SYSTEM CONDENSATE PUMPDUPLEX TYPE WITH 52 GALLON RECEIVER.CAPACITY: 45,000 EDR WITH 45 GPM AT 30 PSI DISCHARGEMOTOR: 1.5 HP- 460 VOLT- 3 PHASE, 3500 RPM

    ITT DOMESTIC SERIES CC

    ITT DOMESTIC SERIES CB

    H-18 SPLIT SYSTEM - COOLING ONLYINDOOR UNIT:CAPACITY: 9.0 MBH TOTAL, 7.38 MBH SENSIBLEINDOOR: 80 DEG. F. DB, 67 DEG. F. WBOUTDOOR: 95 DEG. F. DB, 75 DEG. F. WBAIRFLOW: 170 CFM-LISTED @ LOW FAN SPEEDFAN: 0.76 FLA, ELECTRIC: 1.0 MCA @ 208V,1 PHASEWEIGHT: 22 lbs.

    OUTDOOR UNIT:CAPACITY: 0.75 TONSFAN: 0.50 FLA, ELECTRIC: 12 MCA, 15 MOCP @ 208V, 1 PHASEWEIGHT: 66 lbs.REFRIGERANT PIPE: 0.375"O.D. LIQUID, 0.25"O.D. SUCTIONUNIT SHALL HAVE LOW AMBIENT CONTROL, AND FAN SPEED WITH REMOTETHERMOSTAT.DISCONNECT BY E.C.BASIS OF DESIGN: MITSUBISHI - MSY

    PRS-1 PRESSURE REDUCING STATION #1 - 110 PSI TO 15 PSI2.5" X 4" SR VALVE @ 20 PSI, STRAINER, UNION, ECCENTRICREDUCER. PRESSURE REDUCING VALVE AT 3340 LBS/HR.,1.5" SIZE AND DIFFRACTOR NEEDLE VALVE, NOISE DIFFUSERS,PRESSURE GAGES UPSTREAM. REFER TO DETAIL.

    PRS-2 PRESSURE REDUCING STATION #2 - 110 PSI TO 15 PSI4" X 6" SR VALVE @ 20 PSI, STRAINER, UNION, ECCENTRICREDUCER. PRESSURE REDUCING VALVE AT 6685 LBS/HR.,2.5" SIZE AND DIFFRACTOR NEEDLE VALVE, NOISE DIFFUSERS,PRESSURE GAGES UPSTREAM. REFER TO DETAIL.

    CAPACITY: 68 GALS.ACCEPTANCE VOLUME: 34 GALS.APPROXIMATE SIZE: 24" DIA. X 48" HIGHWORKING PRESSURE: 150 PSIAMTROL AX-120V

    C-1 AIR SEPARATOR (CHILLED WATER SYSTEM)INLINE TYPE COMBINATION AIR & DIRT SEPARATORFLOW RATE: 525 GPMLINE SIZE: 8"MAX. PRESSURE DROP: 2 FT. HD. AT SPECIFIED FLOW RATEAPPROXIMATE DIMENSIONS: 16"DIA. x 52" TALLSPIROTHERM VDN-800-FL OR APPROVED EQUAL.

    EQUAL TO NEPTUNE FTF-5DB

    C-2 EXPANSION TANK - DIAPHRAGM TYPECAPACITY: 8 GALS.ACCEPTANCE VOLUME: 2.4 GALS.APPROXIMATE SIZE: 12" DIA. X 20" HIGHWORKING PRESSURE: 150 PSIAMTROL AX-15V

    H-19 AIR COOLED FLUID COOLERCAPACITY: 250 MBH AT 53 GPM FROM 80 DEG F EWT TO 70 DEG F LWT AT60 DEG F AMBIENT TEMPERATURE WITH 30% GLYCOL.MOTOR: 6 FANS EACH AT 0.25 HP, 460V-3PH, SINGLE-POINT POWER CONNECT.CONTROLS: 120V-1PHMOUNT ON TYPE A1 VIBRATION ISOLATORS AND EQUIPMENT SUPPORTRAIL.

    H-20 HEAT EXCHANGER - PLATE AND FRAMECOLD SIDE CAPACITY: 50 GPM (WATER) WITH 45 DEG F EWT TO 55 DEG F LWT15 FTHD PRESSURE DROPHOT SIDE CAPACITY: 53 GPM (30% E.G.) WITH 80 DEG F EWT TO 70 DEG F LWT20 FTHD PRESSURE DROP

    H-21 ETHYLENE GLYCOL FEED SYSTEM30% GLYCOL BY VOLUME, FACTORY MIXEDGLYCOL MANUFACTURER SPECIFIED IN SECTION 23 21 17.PROVIDE PORTABLE DRUM PUMP, 120V-1PH WITH 16 FT POWER CORD AND PLUGPUMP CLEAR WATER CAPACITY: 20 GPM AT 20 FTHDDRUM SHALL BE MOUNTED ON 4" HOUSEKEEPING PAD

    PROVIDE REMOVABLE INSULATED BOARD CASING WITH PROTECTIVE METALJACKET

    DATE ISSUEDPROJECT #

    REVISIONS

    # DATE DESCRIPTION

    Heapy Engineering

    Project No.

    Enter address here

    11

    /10

    /20

    11 3

    :12

    :27

    PM

    C:\B

    IM\M

    ode

    l\20

    10-0

    601

    9-C

    en

    tra

    l_JL

    WE

    TZ

    EL.r

    vt

    H002

    SCHEDULES

    2010-06019 Nov. 11, 2011

    MAPLE STREET DININGFACILITY

    2010-06019

  • B

    H003

    A

    H003

    C

    H003

    E

    H003

    F

    H003

    K

    H003

    L

    H003

    M

    H003

    D

    H003

    G

    H003

    I

    H003

    J

    H003

    N

    H003

    H

    H003

    NECK SIZE, SEE SCHEDULE

    7

    8

    5

    4

    1

    6

    2

    3

    6

    4

    7

    8

    7

    6

    5

    4

    3

    2

    1 BASE MOUNTED END SUCTION CENTRIFUGAL PUMP WITH

    FLANGED PIPE CONNECTIONS.

    CONCRETE BASE.

    SUCTION DIFFUSER WITH INTEGRAL FINE MESH START-UP

    STRAINER AND ADJUSTABLE SUPPORT. REMOVE MESH

    AFTER PIPING IS CLEANED.

    SPHERICAL FLEXIBLE PIPE CONNECTOR.

    PRESSURE GAUGE WITH INTERCONNECTING PIPING AND

    VALVES.

    PIPE REDUCER WHEN PIPE SIZE DIFFERS FROM PUMP

    CONNECTION SIZE.

    SPRING HANGER.

    BALANCING VALVE, SIZED FOR 3 TO 5 FT. HD. WPD AT FULLPUMP GPM. PROVIDE REDUCERS IN AND OUT. FOR PUMPS

    FITTED WITH AN ADJUSTABLE FREQUENCY MOTORCONTROLLER LEAVE THE BALANCING VALVE FULL OPEN.

    FLOOR

    10

    10

    6

    6

    5

    7

    8

    5

    946321

    9

    8

    7

    5

    4

    3

    2

    1 CONICAL SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE.INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR

    TAP FITTING TO MAIN SUPPLY DUCT WITH INTERNALINSULATION.

    ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS AIRTERMINAL UNIT INLET SIZE UNLESS NOTED OTHERWISE.

    INSULATED FLEXIBLE DUCT. 4 FT. MAXIMUM LENGTH.STRETCH FLEXIBLE DUCT TO 90% OF FULLY EXTENDED

    LENGTH.

    AIR TERMINAL UNIT.

    MINIMUM FOUR STRAP HANGERS FOR UNIT (CORNERPOINTS). ATTACH TO STRUCTURE.

    TRANSITION WHEN REQUIRED.

    MINIMUM STRAIGHT LENGTH OF DUCT SHALL BE

    TERMINAL UNIT MANUFACTURER'S REQUIRED

    LENGTH, BUT AT LEAST 2.0 TIMES UNIT INLETDIAMETER.

    STRAP HANGER. ATTACH TO STRUCTURE.

    DUCT SHALL BE FULL SIZE OF UNIT OUTLET

    UNLESS NOTED OTHERWISE ON FLOOR PLANS.

    REHEAT COIL WHEN SPECIFIED. REFER TO COIL

    DETAIL.

    SQUARE-TO-ROUND ADAPTER IF DIFFUSER NECK ISSQUARE.

    INSULATED FLEXIBLE DUCT SAME DIAMETER AS BRANCH

    DUCT , 7 FT. MAXIMUM TOTAL LENGTH PER AIRDEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF

    FULLY EXTENDED LENGTH.

    SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE WITHMANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL.INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR

    TAP FITTING TO MAIN DUCT WITH INTERNAL INSULATION,AND EXTENDED DAMPER SHAFT AND HANDLE WITH

    STAND-OFF TO ACCOMMODATE EXTERNAL INSULATION.

    DUCT STRAP HANGER. ATTACH TO STRUCTURE.

    STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCTIS LONGER THAN 4 FT.

    MINIMUM CENTERLINE RADIUS EQUAL TO DUCTDIAMETER.

    ROUND SHEET METAL BRANCH DUCT, SAME SIZE ASDIFFUSER INLET UNLESS NOTED OTHERWISE.

    FLEXIBLE DUCT ELBOW SUPPORT, INSTALLED WITHNYLON BANDING PER MANUFACTURER'S INSTRUCTIONS.

    A RADIUS'D SHEET METAL ELBOW MAY BE USED IN LIEU

    OF A FLEXIBLE ELBOW SUPPORT WHEN CONNECTEDDIRECTLY TO AIR DEVICE.

    CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS).

    COORDINATE WITH CEILING CONTRACTOR AND VERIFYT-BAR TYPE FOR COMPATIBILITY WITH DIFFUSER.

    8

    44 34

    5

    6

    9

    827

    10

    1

    6

    10

    9

    8

    7

    6

    5

    4

    7

    3

    2

    1

    8

    7

    6

    5

    4

    2 65 3 7 5

    4

    8

    1

    3

    7

    3

    2

    1

    ROUND SHEETMETAL BRANCH DUCT

    BRANCH CFM RD. DUCT SIZE

    0 TO 80 CFM 6"D

    81 TO 120 CFM 7"D

    121 TO 200 CFM 8"D

    201 TO 400 CFM 10"D

    401 TO 700 CFM 12"D

    701 TO 1000 CFM 14"D

    SHEET METAL PLENUM, FULL SIZE OF GRILLE NECK,

    MINIMUM 4" TALLER THAN DUCT RUNOUT SIZE, WITH SAME

    INTERNAL OR EXTERNAL INSULATION AS RETURN OREXHAUST DUCT.

    FLEXIBLE DUCT, SAME DIAMETER AS BRANCH DUCT ,7 FT. MAXIMUM TOTAL LENGTH PER AIR DEVICE. STRETCH

    FLEXIBLE DUCT TO AT LEAST 90% OF FULLY EXTENDED

    LENGTH.

    SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE WITH

    MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL.INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP

    FITTING TO MAIN DUCT WITH INTERNAL INSULATION.

    EXTENDED DAMPER SHAFT AND HANDLE WITH STAND-OFFREQUIRED FOR EXTERNALLY INSULATED DUCTWORK.

    SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO

    DAMPER.

    DUCT STRAP HANGER. ATTACH TO STRUCTURE.

    STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE

    DUCT IS LONGER THAN 4 FT.

    ROUND SHEET METAL BRANCH DUCT, SIZE AS

    INDICATED IN ADJACENT SCHEDULE UNLESS NOTEDOTHERWISE ON PLANS.

    CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS).COORDINATE WITH CEILING CONTRACTOR AND

    VERIFY T-BAR TYPE FOR COMPATIBILITY WITH GRILLE.

    6

    7

    5

    3 1 3 2

    4

    3

    1

    7

    6

    5

    4

    3

    2

    1 45 DEGREE STATIC BOOT AND MANUAL DAMPER. INTEGRALINSULATION GUARD SLEEVE REQUIRED WHEN MAIN DUCT HAS

    INTERNAL INSULATION. EXTENDED DAMPER SHAFT AND

    HANDLE WITH STAND-OFF REQUIRED FOR EXTERNALLYINSULATED DUCTWORK.

    SHEET METAL DUCT, SIZE AS NOTED ON PLANS.

    DUCT STRAP HANGER.

    STATIC BOOT SIMILAR TO EXCEPT NO DAMPER.

    SHEET METAL DUCT, FULL SIZE OF GRILLE NECK SIZE.

    FLEXIBLE DUCT CONNECTOR.

    CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS).

    COORDINATE WITH CEILING CONTRACTOR AND VERIFY T-BAR

    TYPE FOR COMPATIBILITY WITH GRILLE.

    4

    431

    2

    531

    2

    5

    4

    3

    2

    1 DRAIN PIPE, SAME SIZE AS UNIT DRAIN PAN

    CONNECTION.

    VERIFY REQUIRED HEIGHT FOR DRAIN PIPE AND

    TRAP INSTALLATION. PROVIDE ADDITIONAL

    BEAMS OR BACK-TO-BACK CHANNELS UNDERUNIT, IF REQUIRED, TO ATTAIN REQUIRED HEIGHT.

    TEE WITH CLEANOUT PLUG.

    4" MINIMUM - CENTERLINE TO CENTERLINE.

    CENTERLINE DIMENSION NOT LESS THAN SUPPLY

    FAN T.S.P. (INCH W.G.) + 2".

    GENERAL NOTES

    A. FIRE DAMPERS SHALL BE UL LABELED.

    B. INSTALLATION OF FIRE DAMPERS AND ACCESSORIES SHALL CONFORM TO NFPA 90A, SMACNA AND MANUFACTURER'S INSTRUCTIONS.

    C. DETAILS SHOW INSTALLATION OF FIRE DAMPER IN WALL. DAMPER INSTALLATION IN FLOOR SIMILAR. ACCESS

    LOCATIONS SHALL BE COORDINATED WITH ARCHITECT AND GENERAL TRADES CONTRACTOR.

    D. INSULATE RETAINING ANGLES FOR SYSTEMS REQUIRED TO BE INSULATED.

    FIRE DAMPER, FOLDED BLADE CURTAIN TYPE, EXCEPT AS NOTED. VERTICAL MOUNT, GRAVITY DROP; HORIZONTALMOUNT, SPRING LOADED TO CLOSE. REFER TO SPECS FOR VELOCITY LIMITATIONS OF EACH TYPE. REFER TO

    DRAWINGS FOR STATIC OR DYNAMIC REQUIREMENTS. TYPE "A" - BLADES STORED IN AIR STREAM. RECTANGULAR, ROUND OR OVAL DUCT CONNECTION.

    TYPE "B" - BLADES STORED OUT OF AIR STREAM. RECTANGULAR, ROUND OR OVAL DUCT CONNECTION.

    SHEET METAL WALL SLEEVE, SAME MATERIAL AS DUCT (EXCEPT GALVANIZED SHEET METAL FOR FIBERGLASS

    DUCT). SHEET METAL GAUGE PER SMACNA. USE EXTENDED HEAVY GAUGE SLEEVES WHEN INSTALLED CONDITION REQUIRES.

    DUCT/SLEEVE CONNECTION. BREAKAWAY TYPE SHOWN. CONNECTION MAY BE RIGID TYPE IF ALLOWED BY CODE

    AUTHORITY.

    RETAINING ANGLE ALL FOUR SIDES, GAUGE PER SMACNA. 1" MINIMUM OVERLAP OF WALL OPENING. LONGER LEGMAY BE REQUIRED TO ATTAIN REQUIRED OVERLAP. BOLT, SCREW OR TACK WELD TO WALL SLEEVE. SPACING OF

    FASTENERS PER SMACNA.

    DUCT ACCESS PANEL OR DOOR. REFER TO SPECIFICATIONS.

    CEILING ACCESS PANEL IF CEILING IS NOT ACCESSIBLE.

    DUCT EXTENSION ATTOP OF DAMPER

    FIRE RATED WALLOR PARTITION

    FIRE RATED WALLOR PARTITION

    6

    2

    44

    3

    1

    3

    5

    6

    244

    3

    1

    3

    5

    1

    2

    3

    4

    5

    6

    1

    2

    3

    4

    1

    2 3

    4

    TYPE "A"

    DUCT

    3" MINIMUM 3" MINIMUM

    DUCT

    TYPE "B"

    NOMENCLATURE

    MOTOR HOUSING

    ELECTRICAL CONDUIT GUIDE

    WOOD NAILING STRIP

    PREFABRICATEDROOF CURB

    CURB CAP

    SEE NOTE #1

    SEE NOTE #2

    ROOFSEE NOTE #2

    RIGID CONDUIT TO

    ACCOMMODATE

    ELECTRICAL WIRES

    MOTORIZED BACKDRAFT

    DAMPER

    TRANSITION DUCT

    TO FULL SIZE OF DAMPER

    SUPPLIED WITH ROOF VENTILATOR

    DUCT

    NOTES :

    1 SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" CADMIUM PLATED LAG

    BOLTS NOT OVER 12" ON CENTER

    2 SECURE ROOF CURB, DUCT AND DAMPER TO ROOF WITH EXPANSION BOLTS

    (CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).

    3 SIZE OF DUCT THROUGH ROOF SHALL NOT BE LARGER THAN CURB SUPPLIED

    WITH ROOF VENTILATOR.

    4 RUN ELECTRIC LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER,

    THEN THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.

    UPBLAST EXHAUST FANSCALE: NONE

    5" CONCRETE PAD REINFORCED WITH WELDED WIRE FABRIC 6x6 - W2.9 x W2.9.

    IN EACH DIRECTION (NOT INCLUDING PERIMETER CURB) AND SHALL BE SET ON KINETICS NOISE CONTROL

    ISOLATION BOARD SHALL BE 3/4" THICK RESILIENT MATERIAL AS RECOMMENDED BY THE MANUFACTURER.PADS, & SHALL COVER A MINIMUM OF 95% OF THE AREA BETWEEN THE ISOLATION PADS. PERIMETERDENSITY FIBERGLASS ABSORPTION MATERIAL, WITH AN NRC RATING OF .87, SHALL BE BONDED TO THE ISOLATIONPADS SHALL BE 2" THICK AND BE SPACED AS RECOMMENDED BY THE MANUFACTURER. 1-1/2" THICK LOWDENSITY MOLDED FIBERGLASS PADS INDIVIDUALLY COATED WITH A FLEXIBLE ELASTOMERIC MEMBRANE. ISOLATIONTHE KINETICS MODEL RIM FIBERGLASS ISOLATION MAT SHALL CONSIST OF HIGH& EDGES CLEANED. SEAL EXPOSED EDGE OF RIM MAT WITH PERIMETER

    MODEL RIM FIBERGLASS ISOLATION MAT. OR EQUAL BY VIBRATION ELIMINATOR, KORFUND OR AMBER/BOOTH CO..

    HOUSEKEEPING PADS FOR AIR HANDLING UNIT EQUIPMENT SHALL BE 4" WIDER THAN THE AIR HANDLING EQUIPMENT

    654

    PROVIDE #5 REBAR DOWELS & EPOXY INTO SLAB AND CURB AT 24" ON CENTER.

    6" WIDE CONCRETE PERIMETER CURB, REINFORCED WITH 6 X 6 #10 W.W.F.

    SILICON CAULK AROUND ENTIRE PERIMETER.

    KINETICS ISOLATION MAT MODEL RIM WITH ISOLATION PADS &

    2" ISOLATION PADS SPACED PER MANUFACTURER'S RECOMMENDATIONS.

    1/2" PLYWOOD POURING FORM.

    PERIMETER ISOLATION BOARD

    (2) LAYERS 6 MIL POLYETHYLENE

    8

    9

    FIBERGLASS INFILL.6

    7

    5

    4

    1

    3

    2

    8

    AHU HOUSEKEEPING PADS

    12

    3 87

    9

    ALL CONCRETE FLASHING FROM PAD TOWARD FLOOR OVER EXPOSED EDGE OF RIM MAT SHALL BE REMOVEDISOLATION BOARD & CAULK.

    AIR HANDLER HOUSEKEEPING PADSCALE: NONE

    BASE MOUNTED PUMPSCALE: NONE

    AIR TERMINAL UNIT DUCT CONNECTIONSCALE: NONE

    SUPPLY DUCT

    TO AIR DEVICES

    CEILING DIFFUSER DUCT CONNECTIONSCALE: NONE

    SUPPLY DUCT

    CEILING DIFFUSERCEILING

    RETURN/EXHAUST DUCT

    RETURN ORCEILINGEXHAUST GRILLE

    RETURN/EXHAUST GRILLE DUCT CONNECTION - 2ND FLOORSCALE: NONE

    RETURN/EXHAUST DUCT

    RETURN ORCEILINGEXHAUST GRILLE

    6" MAX.

    RETURN/EXHAUST GRILLE DUCT CONNECTIONSCALE: NONE

    A.H. UNIT

    A.H. UNIT

    TRAP

    FLOOR DRAIN

    TRAP

    FLOOR DRAIN

    DRAW-THRU UNIT

    BLOW-THRU UNIT

    AIR HANDLING UNIT DRAIN PIPING

    SCALE: NONE

    FLOOR MOUNTED

    1" C TO CL L

    OF DUCT IN THE FIRST 20'.

    DUCT TO 20' BEYOND PLENUM

    ALL PLENUM JOINTS TO BE WATER

    WELDED STAINLESS STEEL DRAINPAN

    WHERE STAINLESS STEEL CONNECTS TO

    CONTINUE SLOPE TO DRAINABLE LOUVER,

    SEAMS SHOULD NOT BE AT THE BOTTOM

    GALVANIZED COMBINE WITH DISSIMILAR

    DUCTWORK/PLENUM TO BE HEAVILY CAULKEDAT SEAMS ON INSIDE. SEAL OUTSIDE SEAMSWITH EXTERIOR GRADE HARDCAST.

    SLOPE DRAIN PAN - 1/4" PER 1'

    DUCTWORK AND/OR PLENUM TO BE WRAPPED.

    DRAIN TO BE INSULATED EQUAL TO STORMJANITOR'S SINK/MECHANICAL ROOM FLOOR

    TIGHT(TYPICAL) MAINTAIN WATER TIGHT

    DROP 1" COPPER DRAIN PIPE DOWN TO

    10

    5

    METAL TAPE

    8

    9

    7

    6

    LOUVER

    TO DRAIN.

    DRAINS.

    3

    4

    1

    2

    9

    HINGED ACCESS DOOR.

    ELBOWS AND A TEE.TRAP TO BE ASSEMBLED FROM 90 DEG.

    3/4" BRASS PLUG FOR CLEANOUT ACCESS.

    13

    12

    11

    11

    7

    FASTENER

    12

    3

    64

    13

    8

    10

    LOUVER PLENUM

    DUCTWORK

    5

    2

    5

    BIRD SCREEN

    1

    LOUVER PLENUM/DUCT DRAIN DETAILSCALE: NONE

    AIR SOUND BOOT DUCT.INTERNALLY LINED RETURN

    12"

    AIR DEVICE

    DUCT SIZE, SEE SCHEDULE

    24x12

    RETURN AIRDEVICE

    24x24

    TO PLENUM

    SIZE

    DUCT OPEN

    22x10

    22x12

    NECK SIZE

    22x8

    22x12

    DUCT SIZE

    1ST FLOOR PLENUM RETURN AIR SOUND BOOTSCALE: NONE

    FIRE DAMPER TYPE "A"SCALE: NONE

    FIRE DAMPER TYPE "B"SCALE: NONE

    4

    58

    NOTE: REFER TO DRAWINGS FOR LOCATION OF SMOKE DAMPERS APPLIES TO ALL AIR DUCTS WITH SMOKE DAMPERS AND

    12

    FA

    11

    10

    FA

    7

    6

    13

    14

    15

    17

    2

    3

    1

    2'-0"

    12"X12" HINGED & GASKETED ACCESS DOOR

    PROVIDE 1/2" RIGID INSULATION ON BACK

    SEAL AND CAULK TO PREVENT AIR LEAKAGE

    SMOKE DETECTOR FURNISHED BY E.C. AND

    WITH LATCH.

    INSTALLED BY H.C.

    OF DUCTWORK THAT IS INSULATED.

    AT INSERTION HOLE.

    HANGER BY E.C.

    15

    17

    16

    12

    13

    14

    CEILING.

    DUCT CONNECTOR-MINIMUM OF 1" OVERLAP ON

    POWER SUPPLY AND WIRING BY E.C.

    MOTOR HOUSING FOR MOTOR & CONTACTS

    SEAL SPACE AROUND DAMPER FRAM. SEE SPECS.

    (OUT OF AIR SPACE).

    ALL SIDES OF DAMPER.

    REMOTE TEST STATION BY E.C. WALL MOUNT

    WIRING AND CONDUIT BY E.C.

    NOT USED.

    18 GA. SLEEVE 16" LONG.

    SMOKE WALL.7

    8

    10

    9

    11

    4

    6

    5

    DUCT.

    SMOKE DAMPER. SEE SPECS.2

    1

    3

    16

    AIR VELOCITIES GREATER THAN 400 FT./MIN.

    NEAR DETECTOR AT 46" M.H.

    SMOKE DAMPERSCALE: NONE

    STEEL PLATE4"x4"x1/4"

    LAG SCREW

    WOOD NAILER

    FIBERGLASS INSULATION

    CONCRETE DECK

    EXPANSION LAGS TO DECK.

    7-1/2" MIN. - 9" MAX. HEIGHT

    LEG. SCREW ATTACHMENT TO DECKEXTENDS 6" BEYOND LAST EQUIP.HEAVY GAUGE CONTINUOUS SUPPORT

    COUNTER-FLASHING BY H.C.

    INSULATION

    ROOFING

    ROOF EQUIPMENT SUPPORTSCALE: NONE

    5 BACKDRAFT DAMPER SHALL NOT BE PROVIDED FOR FANS SERVING KITCHEN HOODS.

    WHERE POSSIBLE.

    NOTE: DETAIL APPLIES TO DRAINS FROM LOUVER PLENUMS OR DUCTS CONNECTED TO LOUVER. DUCT CONNECTION TO LOUVER AND LOUVER SHAPE IS NOT TYPICAL.

    DATE ISSUEDPROJECT #

    REVISIONS

    # DATE DESCRIPTION

    Heapy Engineering

    Project No.

    Enter address here

    11

    /10

    /20

    11 3

    :12

    :30

    PM

    C:\B

    IM\M

    ode

    l\20

    10-0

    601

    9-C

    en

    tra

    l_JL

    WE

    TZ

    EL.r

    vt

    H003

    DETAILS

    2010-06019 Nov. 11, 2011

    MAPLE STREET DININGFACILITY

    2010-06019

  • M

    M M

    G

    H004

    H

    H004

    A

    H004B

    H004

    E

    H004

    F

    H004

    I

    H004

    J

    H004

    K

    H004

    K

    H004

    P

    H004

    M

    H004L

    H004

    DH004

    C

    H004

    OH004

    A

    ~

    ~~

    ~

    ~

    ~

    P

    P

    V

    V

    LPC

    HW

    S

    HW

    R

    HW

    S

    HW

    R

    CND

    CH

    R

    CH

    S

    HW

    R

    HW

    S

    ~

    ~

    ~

    M

    MM

    M

    M

    AIR LOADING PILOT

    ALTERNATE

    ~

    ~

    1

    2

    3

    2

    1

    3

    PIPE REDUCER IF COIL CONNECTION SIZEDIFFERS FROM PIPE SIZE.

    0.75" CONDENSATE DRAIN PIPE. CONNECT TOUNIT PAN WITH FLEXIBLE POLYETHYLENE

    TUBING.

    FACTORY ASSEMBLED PIPING PACKAGE

    (OPTIONAL).

    2 WAY, 2 POSITION VALVE.

    1 ALL PIPING SHALL BE FULL SIZE OF MAIN

    RUN-OUT PIPING UNLESS NOTED OTHERWISE.

    2 REFER TO EQUIPMENT SCHEDULE FOR

    AUTOMATIC CONTROL VALVE SIZE.

    GENERAL NOTES:

    COOLING COIL

    3

    2

    1

    HEATING COIL

    PIPE REDUCER IF COIL CONNECTION SIZE DIFFERSFROM PIPE SIZE.

    INSULATE PIPING UP TO SHUT-OFF VALVE.

    MAXIMUM DISTANCE FROM SHUT-OFF VALVE TO

    COIL IS 48".

    TRUE "T" FITTING (NOT A PORT OFF ANACCESSORY).

    1 ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING

    UNLESS NOTED OTHERWISE.

    2 REFER TO EQUIPMENT SCHEDULE FOR AUTOMATIC CONTROL

    VALVE SIZE. VERIFY VALVE PORTING AND CONNECT PIPINGTO PROPER PORTS, PER MANUFACTURER'S

    RECOMMENDATIONS.

    GENERAL NOTES:

    1

    7

    7 2

    4 3

    5

    5

    6

    7

    6

    5

    4

    3

    2

    1 FACTORY ASSEMBLED PIPING PACKAGE

    (OPTIONAL).

    PIPE REDUCER IF REQUIRED.

    PIPE REDUCER/INCREASER IF COIL CONNECTION

    SIZE DIFFERS FROM AUTO CONTROL VALVE SIZE.

    PIPING SAME SIZE AS AUTO CONTROL VALVE OR

    COIL CONNECTION, WHICH EVER IS LARGER.

    6" MINIMUM LENGTH INCLUDES ANY REQUIRED

    ELBOWS AND OFFSETS. INSULATE PIPING FROM

    COIL TO UNION.

    MAXIMUM DISTANCE FROM SHUT-OFF VALVE TO

    COIL IS 48".

    INSULATE PIPING UP TO SHUT-OFF VALVE.

    0.5" DRAIN VALVE

    A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT

    PIPING UNLESS NOTED OTHERWISE.

    B. REFER TO AIR TERMINAL UNIT SCHEDULE FOR

    AUTOMATIC CONTROL VALVE SIZE.

    GENERAL NOTES:

    9

    8

    7

    6

    5

    4

    3

    1

    2

    8

    9

    1

    7

    7 2

    4 3

    5

    5

    6 FACTORY ASSEMBLED PIPING PACKAGE

    (OPTIONAL).

    PIPE REDUCER IF REQUIRED.

    PIPE REDUCER/INCREASER IF COIL

    CONNECTION SIZE DIFFERS FROM AUTOCONTROL VALVE SIZE.

    PIPING SAME SIZE AS AUTO CONTROL VALVEOR COIL CONNECTION, WHICH EVER IS

    LARGER.

    6" MINIMUM LENGTH INCLUDES ANY

    REQUIRED ELBOWS AND OFFSETS. INSULATE

    PIPING FROM COIL TO UNION.

    MAXIMUM DISTANCE FROM SHUT-OFF VALVE

    TO COIL IS 48".

    INSULATE PIPING UP TO SHUT-OFF VALVE.

    UNION OR SCREWED VALVE FITTING.

    TRUE "T" FITTING (NOT A PORT OFF ANACCESSORY).

    0.5" DRAIN VALVE

    A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT

    PIPING UNLESS NOTED OTHERWISE.

    B. REFER TO AIR TERMINAL UNIT SCHEDULE FOR

    AUTOMATIC CONTROL VALVE SIZE. VERIFY VALVE

    PORTING AND CONNECT PIPING TO PROPERPORTS, PER MANUFACTURER'S

    RECOMMENDATIONS.

    GENERAL NOTES:

    HEATING COIL

    GENERAL NOTES:1 ALL PIPING SHALL BE FULL SIZE OF MAIN

    RUN-OUT PIPING UNLESS NOTED OTHERWISE.

    2 REFER TO EQUIPMENT SCHEDULE FORAUTOMATIC CONTROL VALVE SIZE.

    PIPE REDUCER IF COIL CONNECTION SIZE

    DIFFERS FROM PIPE SIZE.

    INSULATE PIPING UP TO SHUT-OFF VALVE.

    MAXIMUM DISTANCE FROM SHUT-OFF VALVE TOCOIL IS 48".

    2

    1

    4

    4

    PUMP WITH FLANGED CONNECTIONS.

    SPRING HANGER.

    TURNBUCKLE ADJUSTMENT.

    BALANCING VALVE, SIZED FOR 3 TO 5 FT. HD. WPD ATFULL PUMP GPM. PROVIDE REDUCERS IN AND OUT. FOR

    PUMPS FITTED WITH AN ADJUSTABLE FREQUENCYMOTOR CONTROLLER LEAVE THE BALANCING VALVEFULL OPEN.

    REDUCER WHEN PUMP CONNECTION SIZE DIFFERSFROM PIPE SIZE.

    LEAVE SPACE TO ALLOW MOTOR TO BE PULLED.

    DRAIN VALVE WITH HOSE CONNECTION.

    PRESSURE GAUGE WITH INTERCONNECTING PIPING AND

    VALVES.

    1

    2

    3

    4

    5

    6

    7

    8

    1

    22

    3 4

    5

    6

    77

    8

    DISCHARGEPUMP

    STEAM MAIN (ABOVE 15 PSIG).

    COLLECTING POCKET AND DIRT LEG SAMESIZE AS MAIN.

    LENGTH FROM INVERT OF MAIN TO DRIP PIPE,1-1/2 X MAIN DIAMETER, 8" MINIMUM.

    THERMODYNAMIC STEAM TRAP, 0.75" SIZEUNLESS NOTED OTHERWISE.

    CONDENSATE RETURN, FULL SIZE OF TRAP

    DISCHARGE, 0.75" MINIMUM.

    0.75" BY-PASS WITH NORMALLY CLOSEDGLOBE VALVE.

    1

    2

    3

    4

    5

    6

    6

    2

    54

    3

    1

    N.C.

    N.C.

    P

    CONDENSATE RECEIVER.

    CONDENSATE PUMPS.

    DISCHARGE PIPE CONNECTIONS WITH UNION,SPRING LOADED CHECK VALVE, GLOBEVALVE, AND SHUT OFF VALVE FOR EACHPUMP.

    FULL SIZE VENT CONNECTION TO OUTDOORS.

    CONCRETE BASE.

    FULL SIZE DRAIN TO FLOOR DRAIN.

    FULL SIZE OVERFLOW DRAIN, TRAPPED AND

    VENTED AND PIPED TO FLOOR DRAIN.T

    (SIMPLEX SIMILAR)

    1

    2

    3

    4

    5

    6

    7

    3

    71

    4

    2 5 6

    2"

    ba

    DRIP.

    DATA FOR CAPACITY, SIZE, ETC.

    1 PRESSURE REDUCING VALVE WITH PILOT AND

    RELATED CONTROL TUBING. REFER TO EQUIPMENT

    FULL SIZE DIRT LEG AND 3/4" STEAM MAIN

    TAPER PIPE REDUCER.

    CONTROL TUBING WITH NEEDLE VALVE.

    SAFETY RELIEF VALVE. REFER TO EQUIPMENT DATAFOR APPROXIMATE SIZE AND DISCHARGE SETTING.EXTEND DISCHARGE PIPE (SAME SIZE AS

    S.R.V. OUTLET) TO SAFE LOCATION.

    DRIP PAN ELBOW. EXTEND 3/4" DRAIN PIPING.

    PRESSURE GAUGE WITH COCK AND SIPHON

    LOOP.

    9" LONG NIPPLE SCREWED INTO DRIP PANELBOW AND INSERTED INTO RISER PIPE.

    RISER PIPE ONE OR TWO PIPE SIZES LARGERTHAN S.R.V. DISCHARGE PIPE, PERMANUFACTURERS RECOMMENDATIONS.

    SUPPORT RISER PIPE INDEPENDENT OF DRIP

    STEEL BELLOWS TYPE WITH WOVEN WIRE

    PAN ELBOW.

    FLEXIBLE PIPE CONNECTOR, STAINLESS

    REINFORCING JACKET.

    UNION ON BOTH SIDES OF SCREWED END

    VALVE REQUIRED IF BY-PASS REQUIRED.

    HORIZONTAL (PITCH TO DRAIN) OR DOWN.

    VALVE.

    3

    4

    2

    6

    5

    7

    11

    8

    9

    12

    10

    COMPRESSED AIR - 10 PSIABOVE REDUCED STEAMPRESSURE

    5

    AIR LOADING PILOTWITH FILTER

    PIPEHANGER

    TO OUTDOORSEXTERNAL STEAM PILOT

    OUTLET

    COND. RETURN

    STRAIGHT PIPE LENGTH

    1/2" - 1-1/2"

    INLET

    aVALVE SIZE

    D

    2" - 4"

    4'-0"

    24"MAX.

    5" - 8"

    3'-0"

    1'-6"

    b

    3'-0"

    4

    6'-0"

    P

    8

    5'-0"

    5

    3

    83 P

    1

    1311

    106

    122

    9

    7

    6

    STEAM MAIN (15 PSIG AND BELOW).

    F. & T. STEAM TRAP, 0.75" SIZE UNLESSNOTED OTHERWISE.

    COLLECTING POCKET AND DIRT LEG SAMESIZE AS MAIN.

    LENGTH FROM INVERT OF MAIN TO DRAIN

    PIPE, 1-1/2 X MAIN DIAMETER, 8" MINIMUM.

    CONDENSATE RETURN, FULL SIZE OF TRAPDISCHARGE, 0.75" MINIMUM.

    1

    2

    3

    4

    5

    3

    2

    4

    1

    5

    12"MIN.

    AUTOMATIC THREE-PORT CONTROL VALVE.NORMALLY OPEN THRU COIL.

    0.5" DRAIN VALVE.

    PIPE REDUCER IF COIL CONNECTION

    DIFFERS FROM PIPE SIZE.

    LEAVE WIDE OPEN UNLESS NEEDED TOEVENLY DISTRIBUTE FLOW THRU COILS OR

    TO BALANCE PUMP GPM.

    COIL RECIRCULATING PUMP.

    WITH AUTOMATIC CONTROL VALVE IN FULLBYPASS, SET BALANCING VALVE TO MATCH

    PRESSURE DROP THRU COIL.

    A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUTPIPING UNLESS NOTED OTHERWISE. BRANCH PIPING

    TO EACH COIL ONE SIZE SMALLER THAN MAINRUN-OUT PIPING, BUT NO SMALLER THAN COILCONNECTION SIZE.

    B. REFER TO AIR HANDLING UNIT SCHEDULE FORAUTOMATIC CONTROL VALVE SIZE. VERIFY VALVEPORTING AND CONNECT PIPING TO PROPER PORTS,

    PER MANUFACTURER'S RECOMMENDATIONS.

    AUTOMATIC TWO-PORT CONTROL VALVE.NORMALLY OPEN THRU COIL.

    0.5" DRAIN VALVE.

    PIPE REDUCER IF COIL CONNECTION

    DIFFERS FROM PIPE SIZE.

    LEAVE WIDE OPEN UNLESS NEEDED TOEVENLY DISTRIBUTE FLOW THRU COILS

    OR TO BALANCE PUMP GPM.

    COIL RECIRCULATING PUMP.

    A. ALL PIPING SHALL BE FULL SIZE OF MAIN

    RUN-OUT PIPING UNLESS NOTEDOTHERWISE. BRANCH PIPING TO EACHCOIL ONE SIZE SMALLER THAN MAIN

    RUN-OUT PIPING, BUT NO SMALLER THANCOIL CONNECTION SIZE.

    B. REFER TO AIR HANDLING UNIT SCHEDULE

    FOR AUTOMATIC CONTROL VALVE SIZE.

    GENERAL NOTES:

    GENERAL NOTES:

    AUTOMATIC TWO-PORT CONTROL VALVE.

    NORMALLY CLOSED THRU COIL.

    0.5" DRAIN VALVE.

    PIPE REDUCER IF COIL CONNECTIONDIFFERS FROM PIPE SIZE.

    DRAIN PAN

    DRAIN PIPE, SAME SIZE AS PAN

    CONNECTION, WITH DEEP SEAL TRAP.REFER TO CONDENSATE DRAIN PIPINGDETAIL.

    LEAVE WIDE OPEN UNLESS NEEDED TOEVENLY DISTRIBUTE FLOW THRU COILS.

    A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUTPIPING UNLESS NOTED OTHERWISE. BRANCH PIPINGTO EACH COIL ONE SIZE SMALLER THAN MAIN

    RUN-OUT PIPING, BUT NO SMALLER THAN COILCONNECTION SIZE.

    B. REFER TO AIR HANDLING UNIT SCHEDULE FOR

    AUTOMATIC CONTROL VALVE SIZE.

    GENERAL NOTES:

    1

    2

    3

    4

    5

    5

    3

    3

    4

    2

    1

    1

    2

    3

    4

    5

    6

    6

    1

    34

    3

    2

    1

    2

    3

    4

    5

    61

    6

    3

    63

    5

    4

    2

    5

    C. COORDINATE WITH AHU MANUFACTURERFOR # OF COIL SECTIONS AT EACH AHU.

    C. COORDINATE WITH AHU MANUFACTURERFOR # OF COIL SECTIONS AT EACH AHU.

    C. COORDINATE WITH AHU MANUFACTURERFOR # OF COIL SECTIONS AT EACH AHU.

    9

    CHECK VALVE - OMIT FOR SINGLE PUMP INSTALLATIONS.9

    AUTOMATIC TWO-PORT CONTROL VALVE.

    NORMALLY OPEN THRU COIL.

    0.5" DRAIN VALVE.

    PIPE REDUCER IF COIL CONNECTIONDIFFERS FROM PIPE SIZE.

    LEAVE WIDE OPEN UNLESS NEEDED TOEVENLY DISTRIBUTE FLOW THRU COILS.

    A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED

    OTHERWISE. BRANCH PIPING TO EACH

    COIL ONE SIZE SMALLER THAN MAINRUN-OUT PIPING, BUT NO SMALLER THANCOIL CONNECTION SIZE.

    B. REFER TO AIR HANDLING UNIT SCHEDULEFOR AUTOMATIC CONTROL VALVE SIZE.

    GENERAL NOTES:

    2

    34

    43

    1

    4

    3

    2

    1

    C. COORDINATE WITH AHU MANUFACTURER

    FOR # OF COIL SECTIONS AT EACH AHU.

    8

    8

    10

    10

    13

    BUILDING ISOLATION VALVE.13

    FLOOR SLAB

    CONCRETE BASE, 4" DEPTH.

    #3 REBAR, 12" O.C.

    DOWEL BASE TO FLOOR.

    1

    4

    23

    4

    3

    2

    1

    ASME STAMPED FLASH TANK, 12" DIA. x 24"LONG.

    PERFORATED STAINLESS STEEL DISPERSION TUBE,

    MINIMUM 24" LONG.

    0.75" DRAIN VALVE.

    PRESSURE GAUGE WITH SIPHON LOOP, SNUBBERAND SHUT-OFF VALVE.

    THERMOSTATIC AIR VENT. EXTEND DISCHARGEPIPE TO FLOOR DRAIN.

    0.75" F. & T. TRAP ASSEMBLY.

    LOW PRESSURESTEAM LINE

    P

    2"WATER LINE

    MIN. 4"BELOWWATER LINE

    4

    3

    4

    5

    2

    1

    6

    6

    5

    3

    2

    11"

    TO CONDENSATERETURN PUMP

    0.75"

    1"

    COIL

    48" MAX

    4

    1

    4

    3

    2

    2

    COIL

    48" MAX 3

    1

    2

    23

    FOR KMUA-1 & KMUA-2, HOT WATER COILIS FACE AND BYPASS TYPE.

    5M

    A.H. UNIT CHILLED WATER COILSCALE: NONE

    FAN COIL UNIT PIPING

    CND

    COIL DRAIN PAN

    UNIT DRAIN PAN

    & AIR CURTAIN UNIT PIPING

    SCALE: NONE

    AIR TERMINAL UNIT REHEAT COILSCALE: NONE

    6" MIN.

    6" MIN.

    48" MAX.

    6" MIN.

    6" MIN.

    48" MAX.

    HWR

    HWS

    AIR TERMINAL UNIT REHEAT COILSCALE: NONE

    HWR

    HWS

    A.H. UNIT HOT WATER COILSCALE: NONE

    A.H. UNIT HOT WATER COILSCALE: NONE

    SCALE: NONE

    & AIR CURTAIN UNIT PIPING

    SCALE: NONE

    PIPE MOUNTED PUMPSCALE: NONE

    DUPLEX CONDENSATE PUMPSCALE: NONE

    HIGH PRESSURE STEAM DRIPSCALE: NONE

    LOW PRESSURE STEAM DRIPSCALE: NONE

    STEAM PRESSURE REDUCING STATIONSCALE: NONE

    AIR

    FLOW

    AIR

    FLOW

    AIR

    FLOW

    AIR

    FLOW

    AIR

    FLOW

    AIR

    FLOW

    AIR

    FLOW

    AIR

    FLOW

    DOAS 1 & DOAS 2 REHEAT COILSCALE: NONE

    KMUA-1 & KMUA-2 HOT WATER COIL

    CONCRETE EQUIPMENT PADSCALE: NONE

    STEAM FLASH TANKSCALE: NONE

    FAN COIL UNIT PIPING

    CABINET UNIT HEATER PIPINGFAN COIL UNIT PIPING,

    DATE ISSUEDPROJECT #

    REVISIONS

    # DATE DESCRIPTION

    Heapy Engineering

    Project No.

    Enter address here

    11

    /10

    /20

    11 3

    :12

    :33

    PM

    C:\B

    IM\M

    ode

    l\20

    10-0

    601

    9-C

    en

    tra

    l_JL

    WE

    TZ

    EL.r

    vt

    H004

    DETAILS

    2010-06019 Nov. 11, 2011

    MAPLE STREET DININGFACILITY

    2010-06019

  • CHILLED WATER PIPING SCHEMATIC

    TO KITCHEN/DINING

    FROM KITCHEN/DINING

    4"

    6"

    6"

    4"

    6"

    SCALE: NONE

    FROM RESIDENTIAL

    EXTERIOR

    TUNNEL

    4"

    6"

    TO RESIDENTIAL

    4"

    CHWP-1 CHWP-2

    PT

    P

    PT

    PT

    T

    FLOOR

    SYSTEM SYSTEM

    SYSTEM

    SYSTEM

    T

    T

    F T

    F T

    BTU METER FORKITCHEN/DINING AREAS

    BTU METER FORRESIDENTIAL AREAS

    WALL

    REFER TO PUMPDETAIL C/HOO2

    REFER TO PUMPDETAIL C/HOO2

    CHILLED WATER PUMP1

    AIR/DIRT SEPARATOR2

    BLADDER STYLE EXPANSION TANK3

    SHUT-OFF VALVE (TYPICAL)4

    1" DRAIN VALVE WITH HOSE THREAD CONNECTION5

    LARGE CAPACITY AIR VENT6

    MANUAL AIR VENT7

    CONCRETE PAD8

    1" BLOW DOWN VALVE SHALL BE PIPED TO FLOOR DRAIN9

    PRESSURE RELIEF VALVE, SET AT 50 PSI.10

    NOTES - CHILLED WATER

    11

    6"

    5

    C-2

    3 8

    9

    C-1

    2

    6

    10

    4

    4

    P

    4

    7

    EP

    PROVIDE UPSTRAM & DOWNSTREAMPIPING CONDITIONS PER METERMANUFACTURERS DIRECTIONS

    NC

    4"

    CHWR CHWR

    CHWS CHWS

    CHWS

    DOMESTIC WATER HEATER STEAM PIPING SCHEMATICSCALE: NONE

    H.C. HEADER SHALL DRAIN BY

    3" STEAM HEADER BY H.C.

    3"

    3"

    GRAVITY TO PUMP H-15

    3"

    3"

    2"

    2"

    DIRT LEG

    DWH-1

    DWH-2

    STEAM TRAPLOW PRESSURE

    2" CONDENSATE RETURN BY

    THIS POINT BACK TO STEAMPIPING AND VALVES FROM

    AND CONDENSATE HEADERBY HC.

    DIRT LEG

    STEAM TRAPLOW PRESSURE

    THIS POINT BACK TO STEAMPIPING AND VALVES FROM

    AND CONDENSATE HEADERBY HC.

    THIS POINT BACK TOPIPING AND VALVES FROM

    CONDENSATE HEADER BY H.C.

    THIS POINT BACK TOPIPING AND VALVES FROM

    CONDENSATE HEADER BY H.C.

    P

    T

    T

    P

    FLOOR

    4" H.W. SUPPLY TO

    RESIDENTIAL SYSTEM

    4" H.W. RETURNFROM RESIDENTIAL SYSTEM

    REFER TO PUMP DETAIL "C"

    ON SHEET "H002".

    HWP-7HWP-6

    HOT WATER CONVERTER.

    LOW PRESSURE DRIP TRAP.

    1" DRAIN VALVE WITH HOSE THREAD FITTING.

    HIGH PRESSURE DRIP TRAP. BEST-o-BELL, MODEL M-10.

    CONDENSATE RETURN PUMP.

    VENT LINE TO EXTERIOR OF BUILDING THRU AREA WELL FROM

    PRESSURE REDUCING VALVE.

    CONCRETE PAD.

    HOT WATER PUMP. REFER TO EQUIPMENTSCHEDULE.

    CHEMICAL SHOT FEEDER, VALVES OR INLET AND OUTLETNORMALLY CLOSED.

    BLADDER STYLE EXPANSION TANK, REFER TO EQUIPMENTDATA. CHARGE TO SPECIFIED PRESSURE.

    LARGE CAPACITY AUTOMATIC AIR VENT, PIPE DISCHARGETO FLOOR DRAIN.

    AIR/DIRT SEPARATOR, REFER TO EQUIPMENT DATA.

    WATER METER WITH REMOTE "GALLON" READ-OUTMOUNTED ON WALL.

    AUTOMATIC MAKE-UP ASSEMBLY. REFER TO EQUIPMENTDATA.

    MANUAL AIR VENT AT HIGH POINTS OF PIPING (LOCATIONS

    SHOWN ARE ARBITRARY. ADJUST LOCATIONS PER ACTUALINSTALLATION.).

    F & T TRAP ASSEMBLY.

    PN.C.

    N.C.

    T T

    N.C.

    NOTES - STEAM/HOT WATER

    SCALE: NONE

    STEAM/HOT WATER PIPING SCHEMATIC0.5" VACUUM BREAKER.

    2/3 CONTROL VALVE.

    1/3 CONTROL VALVE.

    FULL SIZE DRIP LEG WITH 1" DRAIN VALVE, PLUGGED.

    PP

    LPS

    LPR

    P

    HPSTO/FROM CAMPUSSTEAM SYSTEM

    0.75"

    4"

    1"

    4"4"

    0.75"

    T

    RPBFP

    BY P.C.BY H.C.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    99

    1011

    8

    3

    3

    15

    16

    12

    13

    19

    19

    18

    22

    22

    3

    1

    2

    2

    21

    7

    74

    22

    6

    5

    8

    22

    18

    222

    20

    22

    9 9

    HWP-8

    ON SHEET "H002".

    REFER TO PUMP DETAIL "C"

    TT

    6" 6"

    6"KITCHEN/DINING SYSTEM

    6" H.W. RETURN FROM

    KITCHEN/DINING SYSTEM6" H.W. SUPPLY TO

    17

    17

    23

    23 BTU METER FOR RESIDENTIAL AREA.

    15 PSIG STEAM PIPING TO DOMESTIC WATER HEATERS.

    24

    H-3

    H-3

    1

    H-4

    H-6

    H-5

    6"

    6"

    T T FT T F

    6"

    H-16

    H-7

    26

    BTU METER FOR KITCHEN/DINING AREA.24

    143"

    1.25"

    25

    25 CONDENSATE RETURN LINE FROM DOMESTIC WATER HEATER.

    6"

    8"

    3"

    2.5"

    HWP-9

    2"

    2"

    26 HOT WATER SUPPLY AND RETURN LINES FROM HEAT PUMP

    CHILLER. REFER TO KITCHEN COOLING SYSTEMSDIAGRAM ON THIS SHEET.

    T

    T

    T

    P

    MECH. ROOM B10. DO NOT RUN VENT THRU ELEC. ROOM B12.

    6"6"

    6"

    27 STEAM FLOW METER-PROVIDE STRAIGHT PIPE WHEN AT

    28 FLASH TANK-REFER TO DETAIL ON SHEET H004.

    METER PER MANUFACTURERS DIRECTIONS.

    PROVIDE UPSTREAM & DOWNSTREAMPIPING CONDITIONS PER METERMANUFACTURERS DIRECTIONS.

    27

    27

    28

    PROVIDE UPSTREAM & DOWNSTREAMPIPING CONDITIONS PER METERMANUFACTURERS DIRECTIONS.

    PRV-1

    PRV-2

    A

    EP

    HWS

    HWS

    HWR

    HWS

    HWRHWR

    HWR HWR

    HWS

    M

    M

    P

    2"

    3"

    6"

    3"

    4" 5"

    3.5"

    3"

    8"

    3"

    3"

    8"

    8"

    3.5"

    5"

    DATE ISSUEDPROJECT #

    REVISIONS

    # DATE DESCRIPTION

    Heapy Engineering

    Project No.

    Enter address here

    11

    /10

    /20

    11 3

    :45

    :32

    PM

    C:\B

    IM\M

    ode

    l\20

    10-0

    601

    9-C

    en

    tra

    l_JL

    WE

    TZ

    EL.r

    vt

    H005

    PIPING SCHEMATICS

    2010-06019 Nov. 11, 2011

    MAPLE STREET DININGFACILITY

    2010-06019

  • EP

    CWS

    CWR CWR CWR

    CWS

    M

    M

    M M

    M

    2.5"

    2.5"

    CP-1

    CP-2

    AIR SEPARATOR

    WATER CHILLER FOR KITCHENREFRIGERATION EQUIPMENT, N.I.H.C.

    T

    T2.5"

    2.5"

    EXTERIOR WALL OF BUILDING NOTES - KITCHEN COOLING SYSTEM0.75" DRAIN VALVE WITH HOSE THREAD OUTLET.

    FLEXIBLE PIPE CONNECTION.

    MANUAL BYPASS VALVE, NORMALLY CLOSED.

    CONDENSER WATER CONTROL VALVE, FURNISHED BYOTHERS, INSTALLED BY H.C.

    CHILLER IS FURNISHED AND INSTALLED BY OTHERS,

    PIPING BY H.C. AS SHOWN HERE.

    PIPING SHALL BE EXTENDED TO HEATING HOT WATER SYSTEM.REFER TO STEAM/HOT WATER DIAGRAM ON THIS SHEET.

    REFER TO PUMP DETAIL ON SHEET H003.

    PA

    CONDENSER WATEREXPANSION TANK

    0.75"

    1

    7

    6

    5

    4

    3

    2

    1

    5

    4

    1

    1

    0.75"

    1" DRAIN VALVES WITH HOSE THREAD OUTLET88

    T

    T

    T

    T

    1 4

    2 (TYP.)

    NOTE: ALL WORK SHOWN IN THIS DETAIL IS TO BE INCLUDED AS PART OF THE BASE BID

    7

    7

    H-13

    H-11

    PLATE & FRAMEHEAT EXCHANGER

    H-20

    FLUID COOLER

    H-19

    T

    P T

    P

    T P

    T P

    2.5"

    2.5"

    AUTOMATIC 3-WAY, 2-POSITION, BYPASS VALVE9

    9 9

    TO CHILLED WATER

    FROM CHILLED WATER

    AUTOMATIC 2-WAY, MODULATING VALVE10

    11

    GLYCOL MAKEUP PUMP PACKAGE, REFER TO SPECIFICATION11

    SECTION 23 21 17 AND EQUIPMENT DATA.

    DDC SENSORS12

    TP

    TP

    T

    P

    T

    P1212

    12

    12

    GLYCOL FEEDSYSTEM

    H-21

    T

    P

    6" HOUSEKEEPING PAD13

    T

    T

    12

    12

    12

    T

    P

    P

    12

    13 13

    GRADE

    KITCHEN REFRIGERATION COOLING SYSTEM DIAGRAMSCALE: NONE

    H

    H

    EP

    CWR

    CWS

    T

    M

    M T

    P

    2"

    2"

    CONDENSER WATER AUTOMATIC

    MAKE-UP ASSEMBLY

    CP-1

    CP-2AIR SEPARATOR

    CHEMICAL SHOTFEEDERWATER CHILLER FOR KITCHEN

    REFRIGERATION EQUIPMENT, N.I.H.C.

    CHWP-3

    HEAT PUMP

    CHILLER

    CONDENSERWATER PUMPS

    2"

    1.5"

    CHILLER CHILLEDWATER PUMP

    T

    2"

    2"

    2"

    EXTERIOR WALL OF BUILDING

    TO GEOTHERMAL

    THWP-10

    CHILLER HOTWATER PUMP

    NOTES - KITCHEN COOLING SYSTEM0.75" DRAIN VALVE WITH HOSE THREAD OUTLET.

    FLEXIBLE PIPE CONNECTION.

    MANUAL BYPASS VALVE, NORMALLY CLOSED.

    CONDENSER WATER CONTROL VALVE, FURNISHED BYOTHERS, INSTALLED BY H.C.

    CHILLER IS FURNISHED AND INSTALLED BY OTHERS,

    PIPING BY H.C. AS SHOWN HERE.

    PIPING SHALL BE EXTENDED TO HEATING HOT WATER SYSTEM.REFER TO STEAM/HOT WATER DIAGRAM ON THIS SHEET.

    REFER TO PUMP DETAIL ON SHEET H003.

    PA

    CONDENSER WATER

    EXPANSION TANK

    WELL FIELD - ALL

    1

    7

    6

    5

    4

    3

    2

    1

    7

    6

    5

    4

    1

    2

    1

    37

    7

    1

    0.75"

    0.75"

    UNDERGROUNDPIPING SHALL BEHDPE PERSPECIFICATIONS

    1" DRAIN VALVES WITH HOSE THREAD OUTLET88

    T

    T

    T

    T

    1 4

    2 (TYP.)

    NOTE: ALL WORK SHOWN IN THIS DETAIL IS PART OF ALTERNATE #11

    0.75"

    2"

    1.5"

    H-14

    H-13

    H-10

    H-11

    H-12BY H.C.BY E.C.

    KITCHEN REFRIGERATION COOLING SYSTEM DIAGRAMSCALE: NONE

    DATE ISSUEDPROJECT #

    REVISIONS

    # DATE DESCRIPTION

    Heapy Engineering

    Project No.

    Enter address here

    11

    /10

    /20

    11 4

    :10

    :34

    PM

    C:\B

    IM\M

    ode

    l\20

    10-0

    601

    9-C

    en

    tra

    l_JL

    WE

    TZ

    EL.r

    vt

    H006

    PIPING SCHEMATICS

    2010-06019 Nov. 11, 2011

    MAPLE STREET DININGFACILITY

    2010-06019

  • COMMENTS

    M

    M

    FILTER

    SCALE: NONE

    CLG. COIL

    DRIVE SPEED

    START/STOP

    SUPPLY FAN

    SUPPLY AIR

    AH-1/2

    AH-1/2 2

    AH-1/AH-2 CONTROL DIAGRAM

    AH-1 POINTS LIST

    AH-11

    NUMBER NAME TYPE CONTROL MONITOR ALARM

    VFD FAULT - S.F. DI X

    C.W. VALVE POSITION AO X

    H.W. VALVE POSITION AO X

    COMMENT

    S.F. SPEED AO X

    S.F. START/STOP DO X

    R.F. SPEED AO X

    OUTDOOR AIR

    HTG.COIL

    O.A. DAMPER POSITION AO X

    RET. AIR DAMPER POSITION AO X

    VFD FAULT - R.F. DI X

    R.F. START/STOP DO XRELIEF AIR RETURN AIR

    AH-1/2 9

    DAMPER POSITION

    M

    AH-1/2 11

    DAMPER POSITION

    M

    M

    T

    M.A.T.

    AH-1/2 14

    AH-1/2 10

    DAMPER POSITION

    DP

    FILTERHI-LIMIT

    AH-1/2 18

    T

    LO-LIMIT

    AH-1/2 19

    T

    COIL L.W.T.

    AH-1/2 17

    AH-1/2 12

    START/STOP

    AH-1/2 13

    PUMP FAILURE

    AH-1/2 8

    VALVE POSITION

    VALVE POSITION

    AH-1/2 7VFD

    VFD FAULT

    AH-1/2 3

    DP

    HI-LIMIT

    AH-1/2 20

    T

    S.A.T.

    AH-1/2 15

    DP

    DUCT STATIC

    AH-1/2 22

    DP

    LO-LIMIT

    AH-1/2 21

    T

    R.A.T.

    AH-1/2 16

    DRIVE SPEED

    START/STOP

    AH-1/2 4

    AH-1/2 5

    VFD

    VFD FAULT

    AH-1/2 6

    RETURN FAN

    AH-1 2

    AH-1 3

    AH-1 4

    AH-1 5

    AH-1 6

    AH-1 7

    AH-1 8

    AH-1 9

    AH-1 10

    AH-1 11

    AH-1 12

    AH-1 13

    AH-1 14

    AH-1 15

    AH-1 16

    AH-1 17

    AH-1 18

    AH-1 19

    AH-1 20

    AH-1 21

    AH-1 22

    AH-1 23

    ON FAULT

    ON FAULT

    RELIEF DAMPER POSITION AO X

    H.W. PUMP START/STOP DO X

    PUMP FAILURE DI X ON FAILURE

    MIXED AIR TEMP AI X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    ON TRIP

    ON TRIP

    ON TRIP

    LEAVING AIR TEMP AI

    RETURN AIR TEMP AI

    H.W. COIL L.W.T. AI

    FILTER HI- LIMIT DI

    FREEZE STAT DI

    SUPPLY DUCT HI-LIMIT DI

    RETURN DUCT LO-LIMIT DI

    SUPPLY DUCT S.P. AI

    SPACE CO2 LEVEL AI

    AH-2 POINTS LIST

    AH-21

    NUMBER NAME TYPE CONTROL MONITOR ALARM

    VFD FAULT - S.F. DI X

    C.W. VALVE POSITION AO X

    H.W. VALVE POSITION AO X

    COMMENT

    S.F. SPEED AO X

    S.F. START/STOP DO X

    R.F. SPEED AO X

    O.A. DAMPER POSITION AO X

    RET. AIR DAMPER POSITION AO X

    VFD FAULT - R.F. DI X

    R.F. START/STOP DO X

    AH-2 2

    AH-2 3

    AH-2 4

    AH-2 5

    AH-2 6

    AH-2 7

    AH-2 8

    AH-2 9

    AH-2 10

    AH-2 11

    AH-2 12

    AH-2 13

    AH-2 14

    AH-2 15

    AH-2 16

    AH-2 17

    AH-2 18

    AH-2 19

    AH-2 20

    AH-2 21

    AH-2 22

    AH-2 23

    ON FAULT

    ON FAULT

    RELIEF DAMPER POSITION AO X

    H.W. PUMP START/STOP DO X

    PUMP FAILURE DI X ON FAILURE

    MIXED AIR TEMP AI X

    X

    X

    X

    X

    X

    X

    X

    X

    X

    ON TRIP

    ON TRIP

    ON TRIP

    LEAVING AIR TEMP AI

    RETURN AIR TEMP AI

    H.W. COIL L.W.T. AI

    FILTER HI-LIMIT DI

    FREEZE STAT DI

    SUPPLY DUCT HI-LIMIT DI

    RETURN DUCT LO-LIMIT DI

    SUPPLY DUCT S.P. AI

    SPACE CO2 LEVEL AI

    FILTER

    SCALE: NONE

    DRIVE SPEED

    START/STOP

    SUPPLY FAN

    SUPPLY AIR

    KMUA-1/21

    KMUA-1/2 2

    KMUA-1/KMUA-2 CONTROL DIAGRAM

    KMUA-1 POINTS LIST

    KMUA-1 1

    NUMBER NAME TYPE CONTROL MONITOR ALARM

    VFD FAULT - S.F. DI X

    DI X

    H.W. VALVE POSITION

    AI X

    COMMENT

    S.F. SPEED AO X

    S.F. START/STOP DO X

    DO X

    OUTDOOR AIR

    HTG.COIL

    O.A. DAMPER POSITION

    AI X

    DI X

    AO X

    AO X

    KMUA-1/2 5

    DAMPER POSITION

    M

    DP

    FILTERHI-LIMIT

    KMUA-1/2 10

    T

    LO-LIMIT

    KMUA-1/2 11

    T

    COIL L.W.T.

    KMUA-1/2 9

    KMUA-1/24VALVE POSITION

    VFD

    VFD FAULT

    KMUA-1/2 3

    DP

    HI-LIMIT

    KMUA-1/2 12

    T

    S.A.T.

    KMUA-1/2 8

    DP

    DUCT STATIC

    KMUA-1/2 13

    ON FAULT

    DI X

    DI X

    AI X

    ON FAILUREPUMP FAILURE

    LEAVING AIR TEMP

    H.W. COIL L.W.T.

    FILTER HI-LIMIT

    FREEZE STAT

    SUPPLY DUCT HI-LIMIT

    SUPPLY DUCT S.P.

    F & B DAMPER POSITION

    ON TRIP

    ON TRIP

    ON TRIP

    KMUA-1 2

    KMUA-1 3

    KMUA-1 4

    KMUA-1 5

    KMUA-1 6

    KMUA-1 7

    KMUA-1 8

    KMUA-1 9

    KMUA-1 10

    KMUA-1 11

    KMUA-1 12

    KMUA-1 13

    KMUA-2 POINTS LIST

    KMUA-2 1

    NUMBER NAME TYPE CONTROL MONITOR ALARM

    VFD FAULT - S.F. DI X

    DI X

    H.W. VALVE POSITION

    AI X

    COMMENT

    S.F. SPEED AO X

    S.F. START/STOP DO X

    DO XO.A. DAMPER POSITION

    AI X

    DI X

    A0 X

    AO X

    ON FAULT

    DI X

    DI X

    AI X

    ON FAILUREPUMP FAILURE

    LEAVING AIR TEMP

    H.W. COIL L.W.T.

    FILTER HI-LIMIT

    FREEZE STAT

    SUPPLY DUCT HI-LIMIT

    SUPPLY DUCT S.P.

    F & B DAMPER POSITION

    ON TRIP

    ON TRIP

    ON TRIP

    KMUA-2 2

    KMUA-2 3

    KMUA-2 4

    KMUA-2 5

    KMUA-2 6

    KMUA-2 7

    KMUA-2 8

    KMUA-2 9

    KMUA-2 10

    KMUA-2 11

    KMUA-2 12

    KMUA-2 13

    COIL PUMP

    T

    L.W.T.

    HW 14

    CONVERTER #2

    T

    L.W.T.

    HW 13

    CONVERTER #1

    DRIVE SPEED

    START/STOP

    HW 1

    HW 2

    VFD

    VFD FAULT

    HW 3

    PUMP

    PUMP

    DRIVE SPEED

    START/STOP

    HW 4

    HW 5

    VFD

    VFD FAULT

    HW 6

    T

    T

    DP

    SYSTEM DIFF. PRESSURE

    HW 7

    SCALE: NONE

    STEAM & HOT WATER SYSTEM CONTROL DIAGRAM

    STEAM & HOT WATER SYSTEM POINTS LIST

    HW 1

    NUMBER NAME TYPE CONTROL MONITOR ALARM

    VFD FAULT DI X

    COMMENT

    PUMP SPEED AO X

    PUMP START/STOP DO X

    PUMP SPEED AO X

    CONVERTER STEAM VALVE AO X

    AO X

    VFD FAULT DI X

    PUMP START/STOP DO X

    ON FAULT

    ON FAULT

    BUILD. SUPPLY WATER TEMP. AI X

    BUILD. RETURN WATER TEMP. AI X

    CONVERTER L.W.T. AI X

    CONVERTER L.W.T. AI X

    XSYSTEM DIFF. PRESSURE AI

    HW 2

    HW 3

    HW 4

    HW 5

    HW 6

    HW 7

    HW 8

    HW 18

    HW 19

    HW 11

    HW 12

    HW 13

    HW 14

    HW 15

    HW 16

    HW 17 CONVERTER STEAM VALVE

    SPACE CO2(TYPICAL FOR

    2-AHU-2)

    AH-1/2 23

    SPACE CO2(TYPICAL FOR

    5-AHU-1)

    CO2

    SUPPLY AIR CFM

    RETURN AIR CFM

    AFMS

    AH-1/2 24

    AFMS

    AH-1/2 26

    AH-1 24

    AH-1 25

    AH-1 26 OUTSIDE AIR CFM

    XAI

    XAI

    XAI

    SUPPLY AIR CFM

    RETURN AIR CFM

    AH-2 24

    AH-2 25

    AH-2 26 OUTSIDE AIR CFM

    XAI

    XAI

    XAI

    AFMS

    KMUA-1/2 14

    OA DAMPER XDIKMUA-1 14 OA DAMPER XDIKMUA-2 14

    XMAKE