9
ApplicationSeparable straight plugdesigned to connect polymericinsulated cable to cable.Mates with the elbow, straightand branch joint connectors.
Up to 24 kV - 200 A
151SPINTERFACE A
STRAIGHT PLUG
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
Technical characteristics• The thick conductive EPDM
jacket provides a total safe totouch screen which ensuressafety for personnel.
• Each straight plug is testedfor AC withstand and partialdischarge prior to leaving thefactory.
DesignSeparable connectorcomprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer
moulded between the insertand the jacket.
4. Type A - 250 A interfaceas described by CENELECEN 50180 and 50181.
5. Conductor connector.
Separableplugtype
VoltageUm(kV)
CurrentIr
(A)
Conductor sizes (mm2)(for information only)
min. max.151SPK151SP
1224
200200
1616
9595
5
2223 mm
Dia.54 mm
4
1
3
10
Kit contentsThe complete (K)151SP straightplug kit comprises the followingcomponents:
The kit also comprises lubricant, wipers,installation instructions and crimp chart.
Straight plug housing(K)151SPH-W
Conductorcontact
151SPC-X
Cableadaptor
11TL
+ + (K)151SP-W-X+11TLstraight plug kit
=
Ordering instructionsSelect the part numberwhich gives the best centringto the cable core insulationdiameter and substitute Xusing table X, according to theconductor size and type.Add a 'K' for use up to 24 kV.
Orderingpart number
Dia. over core insulation (mm)
min. max.
151SP-EB-X+11TL151SP-EF-X+11TL151SP-FA-X+11TL151SP-FAB-X+11TL151SP-FB-X+11TL151SP-FG-X+11TL151SP-GA-X+11TL
151SP-GAB-X+11TL151SP-GB-X+11TL
12.613.314.615.917.218.419.721.022.2
14.916.117.418.719.921.222.523.825.0
Example:The copper wire screened cableis 12 kV, 50 mm2 strandedaluminium with a diameter overcore insulation of 16.9 mm.Order a 151SP-FA-50(K)M-12-2+11TL straight connector kit.
Table X
Table W
For adaptedbail restraints:
see 'Bail restraints andtypical applications'.
For outdoorapplications.
Order: +MWS.
Components can beordered individually.
For use withcopper tape
screened cables.Order: Kit MT.
For use with Alupe orC 33-226 cables.
Please contact ourrepresentative.
For use withother cable types.
Please contact ourrepresentative.
Conductorsizes
(mm²)
Aluminium Copper
DIN hexagonal Deep indent DIN hexagonal
162535507095
-25(K)M-12-235(K)M-12-250(K)M-12-270(K)M-12-295(K)M-12-2
-25KM-12-135KM-12-1
50(K)M-12-170(K)M-12-195(K)M-12-1
16(K)M-11-225(K)M-11-235(K)M-11-250(K)M-11-270(K)M-11-295(K)M-11-2