HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

User Manual

HydroTrac™

Iris Power Engineering Inc. 1 Westside Drive, Unit 2

Etobicoke, Ontario CANADA, M9C 1B2

Page 2: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

The information contained in this document is the property of Iris Power Engineering Inc., and is to be considered proprietary material. No part of this document may be reproduced or transmitted in any form

or by any means, electronic or mechanical, including photocopying and recording, for distribution to a Third Party without the express written permission of Iris Power Engineering.

HydroTrac User Manual Version 4.0 November 2004 © Iris Power Engineering Inc., 2004. All rights reserved. HydroTrac, TracCon, TracLink, TracWiz and PDView are trademarks of Iris Power Engineering. Windows 98, ME, 2000 & XP are registered trademarks of Microsoft® Corporation.

Page 3: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Contents 1. Introduction ........................................................................................................ 1-1

1.1 Overview.........................................................................................................................1-1 1.2 HydroTrac Front Panel ...................................................................................................1-2 1.3 Definitions .......................................................................................................................1-4 1.4 Manual Conventions.......................................................................................................1-5

1.4.1 Screens and Menus ................................................................................................1-5 1.4.2 HydroTrac User Interface Usage ............................................................................1-6

2. HydroTrac Menu Commands ............................................................................ 2-1 2.1 Operating Modes ............................................................................................................2-6

2.1.1 Remote Control Mode .............................................................................................2-6 2.1.2 Continuous On-line Mode .......................................................................................2-7 2.1.3 Idle Mode.................................................................................................................2-7

2.2 Power Up Options ..........................................................................................................2-8 3. Menu System & Display Screens...................................................................... 3-1

3.1 Power Up ........................................................................................................................3-1 3.2 Idle Mode Main Menu (HydroTrac Main Menu)..............................................................3-1 3.3 Measurements Measurement Menu ..........................................................................3-2

3.3.1 Measurements Measurement Menu Continuous On-Line .............................3-2 3.3.2 Measurements Measurement Menu Single Shot ...........................................3-2

3.4 HydroTrac Main Menu Settings..................................................................................3-4 3.4.1 Settings Settings Menu #1 ..................................................................................3-4 3.4.2 Settings Settings Menu #2 ..................................................................................3-5 3.4.3 Settings Settings Menu #3 ..................................................................................3-5 3.4.4 Settings Settings Menu #4 ..................................................................................3-6 3.4.5 Settings Settings Menu #5 ..................................................................................3-7 3.4.6 Settings Settings Menu #6 ..................................................................................3-8 3.4.7 Settings Settings Menu #7 ..................................................................................3-8 3.4.8 Settings Settings Menu #8 ..................................................................................3-9 3.4.9 Settings Settings Menu #8 ..................................................................................3-9 3.4.10 Settings Settings Menu #9 ................................................................................3-10

3.5 HydroTrac Main Menu Diagnostics Menu................................................................3-11 3.5.1 Diagnostics Menu Events Log ..........................................................................3-11 3.5.2 Diagnostics Menu Maintenance........................................................................3-14 3.5.3 Diagnostics Menu Self Tests ............................................................................3-17

4. Continuous On-Line Mode ................................................................................ 4-1 4.1 Continuous On-Line Monitoring Procedure....................................................................4-1 4.2 Continuous On-Line Monitoring Display Data ................................................................4-2

5. Termination Panel .............................................................................................. 5-1 5.1 Description......................................................................................................................5-1

6. Troubleshooting & Support .............................................................................. 6-1 6.1 Troubleshooting Guide ...................................................................................................6-1 6.2 Customer Support Services............................................................................................6-3

6.2.1 Technical Support ...................................................................................................6-3 6.2.2 Sales........................................................................................................................6-3 6.2.3 Maintenance & Service ...........................................................................................6-4 6.2.4 Product Updates, New Products .............................................................................6-4

HydroTrac User Manual i Iris Power Engineering Inc.

Page 4: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

7. Specifications..................................................................................................... 7-1

8. Index.................................................................................................................... 8-3

List Of Figures Figure 1-1. HydroTrac Front Panel. .............................................................................................1-2 Figure 1-2. Circular Buffer Memory..............................................................................................1-5 List Of Tables Table 1. HydroTrac Front Panel Display......................................................................................1-3 Table 2. HydroTrac Front Panel Buttons .....................................................................................1-6 Table 3. HydroTrac Menu Commands.........................................................................................2-6

ii HydroTrac User Manual Iris Power Engineering Inc.

Page 5: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

1. Introduction

1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument is the cost-effective solution to the continuous partial discharge (PD) monitoring of hydrogenerators. This manual explains, and gives various examples of, the usage for your HydroTrac instrument. Installation of the sensors (epoxy-mica capacitive couplers) and the HydroTrac instrument are described in the PDA Coupler Installation Guide and HydroTrac Installation Guide, respectively. There are three companion software packages, which are described in other documentation:

TracLink™ – to download archived data from the HydroTrac TracCon™ – to download pulse height analysis PD plots through the

HydroTrac TracWiz™ – to configure the HydroTrac

To begin with, some basic information about HydroTrac is listed below to help you get familiar with the instrument. The HydroTrac instrument is a very sophisticated piece of technology that is remarkably simple to use. The instrument’s interface design is easy to use. Six buttons are used to enter all the information HydroTrac will ever need. However, this six-button limitation does make some tasks a little more time-consuming. Reading through this manual will make entering the setup information of the instrument a breeze. See Section 3, for more information on the Setup mode.

Your HydroTrac instrument panel is located inside the HydroTrac Enclosure and contains a 4-line LCD display, which can be viewed through the case window. This display can be configured to inform you of:

• NQN and Qm (Qmax) information • Instrument setup information

The HydroTrac instrument also informs users of: • Alarms signaled by an LED and/or relay. Alarms remain on until acknowledged

by the user. • A low battery level in the instrument.

• Status LEDs notify the user when the unit is acquiring data and if the instrument needs immediate attention for a malfunction, or a variety of user-defined monitoring conditions.

HydroTrac User Manual Introduction • 1-1 Iris Power Engineering Inc.

Page 6: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

1.2 HydroTrac Front Panel

LCD Contrast Control

Access Panel

Figure 1-1. HydroTrac Front Panel.

The front panel of the HydroTrac instrument is simple which makes the instrument easier to use. To access the buttons on this panel, the Enclosure door must be opened.

Each area of the front panel is described in the following table.

Item Description

AcquiringData

This LED will light up for the period of time it takes to collect a reading (usually 45-50 seconds). When the instrument is in the process of retrieving data from the various sensors this will blink off briefly once every five seconds. This signals the changing of the pulse magnitude window being monitored. If this light is blinking at a rate of more than once every five seconds, or it does not stay on for a full five seconds, it indicates a problem with the reference signal.

New Data

This LED simply informs the user that new data has been collected and is available to the user. It will remain lit for a period of 5 seconds once the collection of data is complete.

1-2 • Introduction HydroTrac User Manual Iris Power Engineering Inc.

Page 7: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

NQN / QMaxAlarm

This LED signals the sensors have picked up partial discharge signals above the threshold set by the user. This light will remain on until acknowledged. An output relay is also activated when this light is on.

F1

This button has various functionalities dependent on the menu screen visible. It can be used to clear alarms when operating in the Continuous On-line mode.

F2

This button has various functionalities dependent on the menu screen visible.

This is a cursor movement and scroll button. It will move the flashing cursor to the left. At times it will also act as a scrolling button for screens and menus.

This is a cursor movement, scroll and change data button. It will move the flashing cursor up. At times it will also act as a scrolling button for on screen input values. It will sometimes allow you to change data where the input cursor is.

This is a cursor movement, scroll and change data button. It will move the flashing cursor down. At times it will also act as a scrolling button for on screen input values. It will sometimes allow you to change data where the input cursor is.

This is a cursor movement and scroll button. It will move the flashing cursor to the right. At times it will also act as a scrolling button for screens and menus.

Cancel

This is the Cancel or Escape button of the instrument. It will allow you to back up to the previous screen or escape a screen without saving any changes.

OK

This is the instrument’s enter button. It will be used to make choices and enter information.

Attention

This LED will indicate the instrument has a problem based on the setting configuration. The light will flash until the problem is corrected. See Section Error! Reference source not found..

This is a communications port allowing test result data to be downloaded to a computer for analysis. See the TracLink User’s Manual for a complete description of the method of downloading data and the possible uses of the downloaded data.

Table 1. HydroTrac Front Panel Display

HydroTrac User Manual Introduction • 1-3 Iris Power Engineering Inc.

Page 8: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

1.3 Definitions There are some terms used throughout this manual that are technical or specialized in nature. For a better and much quicker understanding of this instrument and maximum productivity, please read through these definitions.

NQN: NQN (normalized quantity number) is a partial discharge (PD) quantity that is proportional to the total partial discharge activity measured by a PD sensor. Negative NQN refers to the total activity from negative PD pulses. Positive NQN refers to the total PD activity from positive PD pulses. NQN is an indicator of the average condition of the stator winding insulation. For further information regarding PD theory, please contact Iris Power Engineering.

Qm (Qmax): Qm, or Qmax, is the magnitude of the PD activity, measured in millivolts, corresponding to a pulse repetition rate of 10 pulses per second. Qm is an indicator of how severe the PD is at the most deteriorated part of the winding. Positive and negative Qm refer to the peak PD activity from positive and negative PD pulses, respectively. The terms Qm and Qmax are used interchangeably throughout the manual and the instrument software.

2-D Data: PD data results are often displayed in a two-dimensional display depicting polarity, pulse-count rate, and magnitude. The pulse totals displayed are separated and classified based on characteristics and source. This data is downloaded using the TracCon application.

Archived Data: The Daily Archived Data is a summary of all the PD readings taken over the last month, in day-by-day records. The Monthly Archived Data is a further summary of the last 24 Daily Archived Data records for a total summary time span of two years. Archived data includes maximum, minimum and average readings for each of the +/- NQN and +/- Qm values for each coupler. This is accessed using the TracLink application.

Multiplexor or Termination Board: This is the internal circuit board to which external inputs are connected. This circuit board serves four purposes:

• It accesses each of the input couplers (a measurement is only performed on one coupler at a time).

• It provides output connectors (BNC-type) to connect to external equipment, when required.

. Alarm: The alarm will signal that partial discharge readings have been received which are higher than the thresholds set by the user in the configuration of the instrument. Once the alarm is triggered, it will remain on until acknowledged.

Note: HydroTrac has a built-in single-output alarm, but can also be connected to a separate Alarm Output Module. If you have the Alarm Output Module option installed, the ‘Latched Output’ will remain on, or set, as long as any alarm is active. The ‘Momentary Output’ will set and automatically reset after a few seconds.

Sensitivity Range: This range determines the upper and lower boundaries of the partial discharge detection of the instrument. For example, if the 5-85 mV sensitivity range is selected, then only PD pulses within the range will be counted; pulses of magnitude greater than 85 mV will be over range. It is possible that if the sensitivity range is set too low or too high, then no NQN or Qm can be calculated.

1-4 • Introduction HydroTrac User Manual Iris Power Engineering Inc.

Page 9: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Phase Shift: In order to properly calibrate the HydroTrac instrument, the phase shift between the power frequency reference voltage and the voltage of the phase under test must be determined. With EMC’s, this shift is +90 degrees.

Alarm Threshold: The alarm threshold is a number set by the user as an upper limit of NQN or Qm acceptability. Once this value is exceeded in the monitoring process, an alarm is triggered.

Circular Buffer: See Figure 1-2. Circular Buffer Memory. This diagram illustrates the concept of the circular buffer method of data storage. The buffer is based on a FIFO (first in first out) architecture in order to preserve the most recent data.

Add to top of stack

Remove from bottom of stack

CircularBuffer

FIFO

Newest Data

Oldest Data

Figure 1-2. Circular Buffer Memory.

1.4 Manual Conventions

1.4.1 Screens and Menus The HydroTrac display is designed in such a way that it resembles a group of menus that are interlinked with some user input or output screens. The difference between a menu and a screen is that a menu lists choices of further menus or screens, whereas the screen is the final node in its path. A screen will either require input from the user or will display gathered data for the user.

Courier font surrounded by a border

In this manual, the actual on screen text for each HydroTrac menu or screen will be shown as follows.

Our recommended settings will be shown as:

HydroTrac User Manual Iris Power Engineering Inc.

Disabled

Introduction • 1-5

Page 10: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

1.4.2 HydroTrac User Interface Usage

HydroTrac Button

Represented in the manual by

This button will be referred to as . Thus, when the manual asks you to press the button, it means you should press this button.

This button will be referred to as . Thus, when the manual asks you to press the button, it means you should press this button.

This button will be referred to as . Thus, when the manual asks you to press the button, it means you should press this button.

This button will be referred to as . Thus, when the manual asks you to press the button, it means you should press this button.

OK

This button will be referred to as OK. Thus, when the manual asks you to press the OK button, it means you should press this button.

Cancel

This button will be referred to as Cancel. Thus, when the manual asks you to press the Cancel button, it means you should press this button.

F1

This button will be referred to as F1. Thus, when the manual asks you to press the F1 button, it means you should press this button.

F2

This button will be referred to as F2. Thus, when the manual asks you to press the F2 button, it means you should press this button.

Table 2. HydroTrac Front Panel Buttons

1-6 • Introduction HydroTrac User Manual Iris Power Engineering Inc.

Page 11: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

2. HydroTrac Menu Commands The following table represents a summary of the most common HydroTrac Commands as well as a short cut menu path for the command.

Command Menu Path (From root)

Description Of Command

AC Line Sync ⇒Settings ⇒Settings Menu #2

Used to select the source of the line frequency synchronization signal. Partial Discharge measurements must be made relative to the phase of the line voltage of the equipment being monitored.

AC Sync Voltage ⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #2

Used to measure and view the AC synchronization signal magnitude.

Alarms ⇒Settings ⇒Settings Menu #3

Used to set absolute NQN and / or QMax alarm values for each input pair. Short Cut: Press F1 to copy the currently displayed NQN and QMax alarm limits to all the coupler inputs. This includes No NQN and No QMax alarm limits. IMPORTANT: If the alarm levels are set to 0, no alarm checking is performed. IMPORTANT: An alarm is signaled when either the measured ±NQN or measured ±QMax values are greater than the alarm limit specified. When an alarm becomes active, HydroTrac’s NQN / QMax Alarm indicator turns on. The indicator will remain on even if subsequent readings result in values lower than the Alarm Threshold. The indicator is ‘latching’ and must be cleared by user intervention.

Change Date ⇒Settings ⇒Settings Menu #7

Used to change HydroTrac’s date and time. Also, you can enable or disable automatic Daylight Savings time adjustments, as per United States calendar.

Change Name ⇒Settings ⇒Settings Menu #6

Used to change the instrument identification name.

HydroTrac User Manual HydroTrac Menu Commands • 2-1 Iris Power Engineering Inc.

Page 12: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Command Menu Path (From root)

Description Of Command

Check Battery ⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #6

Used to check the back-up battery voltage.

Check High Power Supplies

⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #4

Used to view the status of the +/- 15 volt power supplies.

Check Indicators ⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #3

Used to test the front panel indicators.

Check Line Frequency

⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #2

Used to measure and view the line frequency.

Check Low Power Supplies

⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #5

Used to view the status of the +/- 5 volt power supplies.

Check Multiplexor ⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #9

Used to check the status of the external multiplexor.

Check Network Communications Port

⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #7

Used to check the network communication port.

Check Reference Power

⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #6

Used to view the status of the memory backup battery and the internal voltage reference. NOTE: This reference does not refer to the AC Sync.

Check RS232 Communications Port

⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #7

Used to check the RS232 communication port.

Check Temperature ⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #8

Used to measure and view the internal operating temperature of the HydroTrac enclosure.

Clear Alarm Counters

⇒Diagnostics ⇒Events Log ⇒Events Logged #4

Used to clear the counters that are associated with the Alarm Thresholds for each coupler pair input.

Clear Alarm Flags ⇒Diagnostics ⇒Maintenance ⇒Maintenance Menu #1

Used to clear the Alarm Indicator flags.

2-2 • HydroTrac Menu Commands HydroTrac User Manual Iris Power Engineering Inc.

Page 13: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Command Menu Path (From root)

Description Of Command

Clear Attention Flags ⇒Diagnostics ⇒Maintenance ⇒Maintenance Menu #2

Used to clear the Attention Indicator flags.

Clear Communication Errors Counter

⇒Diagnostics ⇒Events Log ⇒Events Logged #3

Used to clear the RS232 communications error counter.

Clear Daily Data ⇒Diagnostics ⇒Maintenance ⇒Maintenance Menu #4

Used to clear this day’s accumulated readings.

Clear Event Log ⇒Diagnostics ⇒Maintenance ⇒Maintenance Menu #3

Used to clear all counters in the Events Log. Each counter in the Events Log can be cleared separately using the command found in Diagnostics⇒Events Log menu items.

Clear High Temperature Counter

⇒Diagnostics ⇒Events Log ⇒Events Logged #2

Used to clear the counter that increments every minute or so, when HydroTrac is subjected to operating temperatures above its maximum rating. This counter is incremented when HydroTrac measures internal temperatures above 70 ºC.

Clear Low Temperature Counter

⇒Diagnostics ⇒Events Log ⇒Events Logged #2

Used to clear the counter that increments every minute or so, when HydroTrac is subjected to operating temperatures below its maximum rating. This counter is incremented when HydroTrac measures internal temperatures below -20 ºC.

Clear Network Errors Counter

⇒Diagnostics ⇒Events Log ⇒Events Logged #3

Used to clear the Network communications error counter.

Clear Power Supply Fault Counter

⇒Diagnostics ⇒Events Log ⇒Events Logged #5

Used to clear the counter that gets incremented every time the HydroTrac detects an out-of-tolerance condition on its power supplies.

Clear Reset Count ⇒Diagnostics ⇒Events Log ⇒Events Logged #1

Used to clear the counter reset counter. Every time HydroTrac experiences a reset, this counter is incremented. During a power up cycle the counter gets incremented. When power is removed, the HydroTrac is reset.

Clear System Errors Counter

⇒Diagnostics ⇒Events Log ⇒Events Logged #5

Used to clear the System Errors counter.

Continuous On-Line ⇒Measurements Places HydroTrac on-line. It will ti l it bl d i t l

HydroTrac User Manual HydroTrac Menu Commands • 2-3 Iris Power Engineering Inc.

Page 14: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Command Menu Path (From root)

Description Of Command

⇒Continuous On-Line continuously monitor enabled input coupler pairs until the user manually stops monitoring (via keypad) or a power interruption occurs.

Enable MUX ⇒Settings ⇒Settings Menu #8

Used to enable or disable the external multiplexor. Under some conditions, it is beneficial to disable the external multiplexor from HydroTrac.

Enable SOM ⇒Settings ⇒Settings Menu #8

Used to enable or disable the external Sensor Output Module (optional accessory for HydroTrac).

Factory Setup ⇒Diagnostics ⇒Maintenance ⇒Maintenance Menu #3

Used to restore HydroTrac’s setup to from-factory condition.

Instrument Information

⇒Diagnostics ⇒Self Tests ⇒Self-Test Menu #1

Used to view instrument information, such as hardware version, firmware version, serial number and more.

Last Reset Date ⇒Diagnostics ⇒Events Log ⇒Events Logged #1

This command can be used to reset the last-reset-on-date to the current date.

Measurement Duration

⇒Settings ⇒Settings Menu #9

This command selects the test measurement duration. It is a global setting, applied to all coupler input pairs.

Network ⇒Settings ⇒Settings Menu #4

HydroTrac has two communications modes built in. The first is an RS232 protocol available on the front panel DB9 type connector. The second mode of communication is an RS485 protocol (optional fiber optic connections are also available internally), which uses a networked addressing scheme. These two modes are mutually exclusive – you must disable one protocol to enable the other.

Note: When Network is ENABLED, the RS232 protocol is not available. When the Network is DISABLED, the RS232 protocol is available.

Phase Adjust ⇒Settings ⇒Settings Menu #2

Used to specify a phase adjustment for the AC line synchronization source. When measurements are made from a capacitive coupler, the phase adjustment is normally set to +090, signifying 90 degrees, or one-quarter of the phase cycle. This is required because capacitive coupling shifts the low

2-4 • HydroTrac Menu Commands HydroTrac User Manual Iris Power Engineering Inc.

Page 15: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Command Menu Path (From root)

Description Of Command

frequency ac line voltage by 90 degrees. Power On Mode ⇒Settings

⇒Settings Menu #4

Used to select the mode of operation when HydroTrac is powered up, or after a reset.

Purge Storage Memory

⇒Diagnostics ⇒Maintenance ⇒Maintenance Menu #4

Used to purge the storage memory.

Once purged, the memory cannot be restored.

Restore Settings ⇒Settings ⇒Settings Menu #1

Used to load previously saved settings into memory. All settings are preserved in non-volatile memory and are restored at power up. Any changes made to the setup will remain in effect until they are changed or until Restore Settings is used to restore previously saved settings. Restore Settings allows a user to restore settings that may have been modified during diagnostics or test measurements. Of course, the settings should have been previously saved using the Save Settings command.

Save Settings ⇒Settings ⇒Settings Menu #1

Used to save the current setup parameters to non-volatile memory. Saved settings are not automatically restored at power up. You must restore saved settings using the Restore Settings command. When settings are saved, the New Data indicator will blink momentarily indicating a successful save.

Set Sensitivity ⇒Settings ⇒Settings Menu #5

Used to select the sensitivity ranges for each of the coupler pairs. The sensitivities are coupler pair specific – each input can have a unique sensitivity selected. There are six sensitivity ranges available, plus a Disabled setting. The Disabled setting is used to disable a coupler pair from being selected during Continuous On-line Mode.

If all inputs are Disabled, then Continuous On-line Mode cannot be executed.

Single Shot Get New Data

⇒Measurements ⇒Single Shot ⇒Single Shot Menu #2

Performs a single shot measurement on the selected input coupler pair, using the sensitivity selected.

Single Shot Sensitivity

⇒Measurements ⇒Single Shot ⇒Single Shot Menu #1

Selects the Single Shot Measurement sensitivity range to use.

Single Shot Source ⇒Measurements Selects the coupler pair to be used for a S S

HydroTrac User Manual HydroTrac Menu Commands • 2-5 Iris Power Engineering Inc.

Page 16: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Command Menu Path (From root)

Description Of Command

⇒Single Shot ⇒Single Shot Menu #1

Single Shot Measurement.

Single Shot View Last Data

⇒Measurements ⇒Single Shot ⇒Single Shot Menu #2

Used to view the last data obtained when running a Single Shot Measurement.

Upgrade Firmware ⇒Diagnostics ⇒Maintenance ⇒Maintenance Menu #5

Used to put the instrument into a special mode that allows new firmware to be transmitted into the instrument.

User Attention Flag Set/Reset

⇒Diagnostics ⇒Maintenance ⇒Maintenance Menu #2

Used to set or clear the User Attention Flag.

Table 3. HydroTrac Menu Commands

2.1 Operating Modes The HydroTrac has two main modes: the Remote Control Mode and the Continuous On-line Mode. Also, two distinct connection modes can be used when collecting data with HydroTrac: Single Direct Connection and Multiple Addressed Connection. For more information regarding connection modes, please refer to the HydroTrac Installation Guide.

The two main operating modes are mutually exclusive; you cannot operate in both modes simultaneously. However, you can switch back and forth between the modes. Most customers will probably choose one mode of operation and have little need to change it.

There is a third mode of operation that may be used occasionally: the Idle Mode. This mode is used for configuring the HydroTrac via the keypad, and once this is done, the Idle Mode will rarely be needed. A road map of the menu system is provided in Section 3.

2.1.1 Remote Control Mode HydroTrac is configured for Remote Control Mode when a host computer controller is used to acquire data from a HydroTrac that is permanently connected to a hydrogenerator. The host computer controller can be configured through TracCon™ to acquire readings at specific time intervals, such as hourly or daily, and automatically retrieve and store this data to the database files. These readings can be viewed using PDView. TracLink™ can be used to remotely download the data archived within the HydroTrac memory. Please refer to the appropriate User’s Manuals for information on these software packages.

Optionally, a user could occasionally visit, or connect to, a HydroTrac and perform a measurement in Remote Control Mode using TracCon or download the archived data using TracLink. A permanent connection to a host computer is not required.

2-6 • HydroTrac Menu Commands HydroTrac User Manual Iris Power Engineering Inc.

Page 17: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

In the Remote Control Mode of operation using TracCon, a host computer controller signals a HydroTrac to perform a measurement on any one of its coupler pair inputs. The host computer controller performs a measurement automatically with no user intervention required. The data type retrieved is called 2-D Data.

The Remote Control Operating Mode HydroTrac has a distinctive message displayed on its liquid crystal display.

HydroTrac Vx.xx Iris Power Eng. Remote Control ->*<-

The display, shown above, shows the current firmware version number, and the bottom line shows a moving cursor that moves laterally. This indicates the HydroTrac is functioning properly. Normally, a HydroTrac instrument is only placed into Remote Control Mode by a host computer connected via the RS485 or fiber optic interface when a measurement is desired. It is also possible to place HydroTrac in Remote Control Mode if the key is pressed during power up. However, once powered up, it is not possible to place a HydroTrac instrument into Remote Control Operating Mode manually via the front panel keypad.

2.1.2 Continuous On-line Mode When in Continuous On-line Mode, HydroTrac is always on-line. At power up, HydroTrac displays the current firmware version, and a message indicating it is initializing.

The HydroTrac can be configured to go to on-line immediately at power up. If not configured to do so, the HydroTrac enters Idle Mode and is ready for user input via the keypad. Please note, that unless the instrument is On-Line, it is not actively collecting data and monitoring alarm levels.

Unlike the Single Shot Operating Mode where 2-D data is generated, the Continuous On-line Mode stores two types of archived data: Daily Archived Data and Monthly Archived Data. The Daily Archived Data is a summary of all the readings taken over the last month, in day-by-day records. The Monthly Archived Data is a further summary of the last 24 Daily Archived Data records for a total summary time span of two years. This data can be downloaded using TracLink.

2.1.3 Idle Mode Pressing the Cancel key on the front panel once will bring the HydroTrac into Idle Mode once the current test sequence is completed.

In this mode of operation, the HydroTrac accepts commands from the front panel keypad. The user will configure all aspects of the HydroTrac operation and then, usually, command the HydroTrac to go On-Line.

HydroTrac User Manual HydroTrac Menu Commands • 2-7 Iris Power Engineering Inc.

Page 18: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

2.2 Power Up Options The HydroTrac has some operating modes that are only accessible while pressing a special key on the front panel display during power up. These special modes of operation are:

• Remote Control Operating Mode Press at power up to place HydroTrac into Single Shot Operating Mode. While in this mode, pressing any key returns the user to Continuous On-line Mode.

• Restore Factory Setup Press F1 at power up to restore the factory default settings. The Event Log, all Alarm Flags and all Attention Flags will be cleared.

This page is left blank intentionally.

2-8 • HydroTrac Menu Commands HydroTrac User Manual Iris Power Engineering Inc.

Page 19: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

3. Menu System & Display Screens The following sections describe all the menu commands and display screens for HydroTrac. Alternatively, the HydroTrac can be configured using the TracWiz program. Please refer to its help document for further information regarding this application.

3.1 Power Up HydroTrac Vxx.xx Copyright (c) 2000 Iris Power Eng. Initializing...

The power up message is usually displayed for only a few seconds, after which, the instrument will either go immediately on-line or idle.

3.2 Idle Mode Main Menu (HydroTrac Main Menu) HydroTrac Main Menu ->Measurements Settings Diagnostics

Use the keys to navigate the menus.

There are three main menu items logically separating the three main functionalities of the HydroTrac. The Measurements menu contains command items used to place the HydroTrac on-line (monitoring) or to perform single shot measurements. The Settings menu contains menu items used to setup the HydroTrac. The Diagnostics menu contains menu items that can be used to perform self-tests, diagnostics and maintenance.

HydroTrac User Manual Menu System & Display Screens • 3-1 Iris Power Engineering Inc.

Page 20: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

3.3 Measurements Measurement Menu The Measurement Menu displays the Continuous On-Line monitoring command and the Single Shot sub-menu. The screen looks like this:

Measurement Menu ->Continuous On-Line Single Shot

3.3.1 Measurements Measurement Menu Continuous On-Line Select the Continuous On-Line command to place the HydroTrac On-Line. Please note that to configure the HydroTrac you must select the Settings command on the HydroTrac Main Menu. To perform a single measurement, select the Single Shot command.

3.3.2 Measurements Measurement Menu Single Shot The Single Shot sub-menus allow the user to select a coupler input pair and a measurement sensitivity range. The Single Shot menu looks like this:

Single Shot Menu #1 ->More... 500mV-8000mV Range Couplers P1-A

The Single Shot Menu #1 display shows the user what the current sensitivity range is, (500mV to 8500mV range is shown) and the current inputs enabled (Couplers P1-A is shown). The user can select from the following ranges:

• 5 mV-85 mV Range is the most sensitive range, uses internal amplifiers. • 10 mV-170 mV Range uses internal amplifiers. • 20 mV-340 mV Range • 50 mV-850 mV Range • 100 mV-1700 mV Range • 200 mV-3400 mV Range, uses internal attenuators • 500 mV-8500 mV Range is the least sensitive range, uses internal attenuators.

Also, the user can choose from six coupler pairs. The coupler pairs are:

• Couplers P1-A, the first pair of couplers on the A phase input. • Couplers P1-B, the first pair of couplers on the B phase input. • Couplers P1-C, the first pair of couplers on the C phase input. • Couplers P2-A, the second pair of couplers on the A phase input. • Couplers P2-B, the second pair of couplers on the B phase input. • Couplers P2-C, the second pair of couplers on the C phase input.

3-2 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 21: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Please note, if the external multiplexor is not installed, or not functioning properly, the user only has a single option for the input, the Couplers P1-A input.

Single Shot Menu #2 ->More... Get New Data View Last Data

The Single Shot Menu #2 has two commands: Get New Data and View Last Data. Select the Get New Data command to run a single measurement. If the HydroTrac was configured to run a 1 Second test, then each measurement sweep takes one second to complete, and the entire test will be completed in about 45 seconds. If the HydroTrac was configured to run a 5 Second test then each measurement sweep takes five seconds to complete, and the entire test will be completed in about 3 minutes.

The Get New Data command is used to perform a Single Shot Test measurement. This command is used to help users determine the proper sensitivity to select for a particular coupler pair. When this command is issued, the data obtained is not stored in the Daily Archived Data or the Monthly Archived Data archive – it is discarded.

When a 1 second test is selected, the display shows the following information:

Acquiring data Running test X..........

Where X indicates the current magnitude window (there are 16 in all). As the test progresses, the X will move along the bottom of the display, and an * will be displayed in its place, indicating that the measurement step is complete.

When a 5 second test is selected, the display shows the following information:

Acquiring data Running test 1..........

Where 1 indicates the current magnitude window step (there are 5 in all) and the current magnitude window (there are 16 in all). As the test progresses, the 1 will increment to 2,3,4 and 5 and then move along the bottom of the display, and an * will be displayed in its place, indicating that the measurement step is complete.

Some errors can be reported here. For example:

Acquiring data Waiting for sync ***X..........

Indicates that the line-frequency synchronization signal is absent. The HydroTrac will wait forever to complete a test if the synchronization signal is absent.

Acquiring data Running test ***?..........

Occasionally, the HydroTrac will detect a glitch on the line frequency. If too many glitches are detected, the HydroTrac will show a '?' in place of the X cursor as shown.

The HydroTrac will continue with the test, but will wait until it can complete a measurement cycle without detecting any glitches before continuing.

During a Single Shot Test the user can press the CANCEL key to abort the test and the display will show:

HydroTrac User Manual Menu System & Display Screens • 3-3 Iris Power Engineering Inc.

Page 22: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

User abort Test aborted Press OK

If the user does not press OK within 30 seconds, the screen returns to Single Shot Menu #2.

The View Last Data command is used to view the results of the last test. Please note that if a test was aborted or otherwise incomplete, this command will still show Test data is invalid.

+NQN: 0, 0 -NQN: 0, 0 +QMax: 0, 0 -QMax: 0, 0

The two columns of numbers represent the +NQN , -NQN, +QMax and -QMax values for the first coupler, C1, on the left and the second coupler, C2, on the right.

These values are truncated integer values and are rounded up or down to the nearest whole number. Press OK or CANCEL to return to the menu display.

When performing single-shot measurements, the Alarm Thresholds are ignored.

3.4 HydroTrac Main Menu Settings

3.4.1 Settings Settings Menu #1 Settings Menu #1 More... ->Restore Settings Save Settings

Restore Settings

This command is used to restore all current settings from the permanent non-volatile memory. This is useful if you want to re-call a previously saved configuration.

Press either , or the OK key to restore the saved settings when the cursor is displayed to the left of the Restore Settings command item. The New Data Indicator should blink (green) momentarily to let you know the settings were actually restored.

Save Settings

This command is used to save all current settings to permanent non-volatile memory. This is useful if you want to temporarily reconfigure the HydroTrac and then restore its setup to the previous condition.

Press either , or the OK key to save the current settings, when the cursor is displayed to the left of the Save Settings command item. The New Data Indicator should blink (green) momentarily to let you know the settings were actually saved.

3-4 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 23: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

3.4.2 Settings Settings Menu #2 Settings Menu #2 More... ->AC Line Sync (C1) Phase Adjust +090

AC Line Sync

This command is used to select the source oThere are two sources for the AC Line Sync

Press either , or the OK key to toggle th

When C1 is selected, the AC Line Sync sourEXT is selected, the AC Line Sync source is

Note: If a valid AC synchronization signal cannbe made.

The External Reference input must be >

Phase Adjust

This command is used to shift HydroTrac’s inNormally, the AC Line Sync is derived from in a voltage shift of 90 degrees from the high

The shift is incremented or decremented degrees.

Note: A shift of 345 degrees is the same as a s

3.4.3 Settings Settings Menu #3 Settings Menu #3 More... ->Coupler P1-A Alarm=No NQN,No Qm

Alarm Threshold settings are only in effect wMode. There are six pairs of alarm settings, available. An alarm can be based on an absgiven pair. If the Alarm Threshold is zero, th

Select the Alarm Threshold of an input pair bmenu item and then use the keys to sele

Move the cursor to the Alarm menu item andcurrent alarm levels for the Coupler pair prev

HydroTrac User Manual Iris Power Engineering Inc.

C1 090 Deg

f the AC line frequency signal source. signal: C1 or External.

e selection.

ce is coupler C1, the first coupler. When the external reference.

ot be detected, measurements will not

100 mVAC and less than 250 VAC.

ternal zero crossing detector trigger. C1, which is a capacitive coupler that results voltage on the generator.

by 15 degree steps, from 0 degrees to 345

hift of –15 degrees!

hen the HydroTrac is in Continuous On-line one for each of the six input pairs that are olute NQN value and/or QMax value for a e alarm is disabled.

y moving the cursor down to the Coupler ct the pair.

press OK. The display will show the iously selected.

Menu System & Display Screens • 3-5

Page 24: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Select Alarm Level: [ NQN ],[Qmax ] -OFF- , -OFF- ^

When the Alarm Level is displayed, use the keys to move the cursor from field to field.

Select Alarm Level: [ NQN ],[Qmax ] -OFF- , 00400 ^

Use the keys to increment or decrement the number above the ^ cursor. Alarm Threshold values range from 1 to 65535. Press F1 to reset both Alarm Threshold levels to 0.

Note: In reality, it is not possible to obtain readings of 65535 for NQN or QMax. The HydroTrac instrument does allow for these values, even though they are not practical values.

Before HydroTrac indicates an Alarm Condition, an alarm threshold must be exceeded on four consecutive tests.

Settings Menu #3 More... Coupler P1-A ->Alarm=No NQN,00400

To accept the changes, press OK. The display will now show the updated Alarm Threshold value for the selected input pair information.

If you press F1 in this menu, the currently displayed values for the given coupler pair will be copied into all Alarm Thresholds for all coupler pairs.

Note: When the coupler pair selection cannot be changed, and a double asterisk appears next to the P1-A coupler, the multiplexor cannot be found, so other coupler pair selections are disabled.

3.4.4 Settings Settings Menu #4 Power On Mode

When HydroTrac is powered up, or reset, it can be programmed to go immediately to On-Line or Idle. The selection is made by the Power On command.

Go to Idle mode at power up, or after reset.

Settings Menu #4 More... ->Power On: IDLE Network: ENABLED

Go to On-Line at power up, or after reset.

Settings Menu #4 More... ->Power On: ON-LINE Network: ENABLED

Network

On-Line

3-6 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 25: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

HydroTrac has three communications protocols built in – RS232, RS485 and fiber optics (available internally, jumpers must be set – see HydroTrac Installation Guide for more information.)

The RS485/fiber optics protocol uses a multi-drop addressing scheme that allows up to 99 devices to be networked together on a simple four-wire RS485 connection. Due to the complexity of the addressing scheme, the RS485/fiber optics and RS232 protocols are mutually exclusive. You must disable one protocol in order to use the other.

Settings Menu #4 More... Power On: ON-LINE ->Network: ENABLED

In the above screenshot, networked RS485/fiber optics protocol is ENABLED, and therefore, the RS232 protocol is disabled.

Set More...

tings Menu #4

Power On: ON-LINE ->Network: DISABLED

In the above screenshot, networked RS485/fiber optics protocol is DISABLED, and therefore, the RS232 protocol is enabled.

3.4.5 Settings Settings Menu #5 Sensitivity

HydroTrac has six sensitivity ranges spanning 5 mV to 8500 mV. Each input pair can have its own sensitivity range selected.

Settings Menu #5 More... Couplers P1-A ->Disabled

If Disabled is selected, the coupler pair will not be monitored when the HydroTrac is in Continuous On-line Mode. For each coupler pair, the user selects the sensitivity ranges. (see Section 3.3.2)

Press F1 to copy the sensitivity last used in the Single Shot Get New Data command.

Press F2 to select Disabled.

Note: If a double asterisk appears next to the coupler pair P1-A, the HydroTrac cannot detect the external multiplexor, and therefore does not allow the user to choose ranges for these coupler pairs.

Generally speaking, the +Qmax or –Qmax values should be about half the value of the maximum sensitivity selected. Refer to Section 3.3.2 on how to collect a single shot of data to determine where to set the sensitivity range. Use the following table to select the proper sensitivity range:

HydroTrac User Manual Menu System & Display Screens • 3-7 Iris Power Engineering Inc.

Page 26: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Sensitivity Range Maximum QMax Value (Highest sensitivity) 5 mV to 85 mV < 45 mV 10 mV to 170 mV < 90 mV 20 mV to 320 mV < 180 mV 50 mV to 850 mV < 450 mV 100 mV to 1700 mV < 900 mV 200 mV to 3200 mV < 1800 mV (Lowest sensitivity) 500 mV to 8500 mV < 4500 mV

Table 3-1. Maximum QMax Values vs Sensitivities.

Note: If you expect partial discharge levels to rise over time, it would be wise to use a lower sensitivity range from the start. This is because NQN and QMax values are not easily normalized across ranges – experienced user interpretation is required to compare NQN and QMax values obtained from different sensitivity readings.

3.4.6 Settings Settings Menu #6 Change Name

Each HydroTrac needs a unique name of up to 16 characters. This name is primarily used for identification purposes when multiple HydroTracs are networked together. We suggest you name the HydroTrac appropriately for the machine or equipment to which the HydroTrac is connected.

Settings Menu #6 More... ->Change Name >HydroTrac 001 <

To change the name, move the cursor to the Change Name command line. Press OK.

Change Instrument’s Name >HydroTrac 001 ^

Use the keys to move the cursor ^ and the keys to adjust the character displayed.

Press OK to accept the changes.

Press CANCEL to abort without making any changes.

If the HydroTrac remains idle for more than 30 seconds while the Change Instrument’s Name screen is displayed, the HydroTrac will automatically issue a CANCEL.

3.4.7 Settings Settings Menu #7 Change Date

HydroTrac has a built-in real-time clock. This clock uses a lithium battery source to provide and maintain power when the HydroTrac is not power by an external electrical

3-8 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 27: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

source. Normally, the clock should be checked every six months to a year, and adjusted for drift.

Settings Menu #7 More... ->Date Setup

Select the Date Setup command and press OK.

The current date: *Daylight Saving On Jan 01/00 01:00:01

Press OK to accept the current date and time, without making any changes.

Press F2 to toggle the Daylight Saving On/Off.

Change month.. *Daylight Saving On Feb 01/00 01:00:01 ^^^

Press to change the date and time.

Press OK when finished. The internal clock restarts.

Note: Invalid dates can lead to unpredictable results.

3.4.8 Settings Settings Menu #8 Enable MUX

Most HydroTracs are shipped with an external six-pair input multiplexor (MUX). The multiplexor is designed on a multi-layered circuit board which allows high frequency signals to be switched in and out of the measurement circuit path as necessary. In some circumstances, it may be beneficial to access the external coupler connections via the BNC-type connectors provided on the front panel of the multiplexor. When this is required, you must disable the multiplexor control via HydroTrac’s Enable Mux command.

Settings Menu #8 More... ->MUX Enabled SOM Enabled

Use the keys to toggle the choices.

Enabled

The external multiplexor has a green indicator in the lower right-hand corner. The indicator must be lit for normal HydroTrac operation.

Note: When the external multiplexor is disabled, Continuous On-line Mode cannot proceed.

3.4.9 Settings Settings Menu #8 Enable SOM and AOM

The Sensor Output Module (SOM) and the Alarm Output Module (AOM) are optional accessories for HydroTrac. The SOM converts the measured NQN and QMax values to an analog signal, suitable for continuous monitoring by systems like PLC’s. The AOM is

HydroTrac User Manual Menu System & Display Screens • 3-9 Iris Power Engineering Inc.

Page 28: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

used to provide alarm signals for a monitoring system. The AOM is auto detected, but the SOM must be enabled.

Settings Menu #8 More... MUX Enabled ->SOM Enabled

Use the keys to toggle the choices.

The external SOM and AOM have a yellow indicator that blinks every second or so, indicating that they are working properly.

As applicable

3.4.10 Settings Settings Menu #9 Test Duration

This command is used to select the Test Duration. It can be set for either 1s or 5s test duration.

Settings Menu #9 More... ->1 Second Test

Use the keys to toggle the choices.

When the 1 Second Test is enabled, the HydroTrac performs an entire test in about 45 seconds. This is beneficial during the Continuous On-line Mode because it results in quicker test cycles – more measurements are performed on the enabled coupler pairs in one day.

When the 5 Second Test is enabled, the HydroTrac performs an entire test in about 3 minutes. This is beneficial when very low partial discharges level are present – the longer measurement cycle results in more pulses captured.

The actual acquired data is normalized such that under normal conditions, the same values should be recorded regardless of the Test Duration used.

5 Second Test

3-10 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 29: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

3.5 HydroTrac Main Menu Diagnostics Menu When entering the Diagnostics menu, the Diagnostics submenu is displayed. These menu items navigate the user through all of HydroTrac’s diagnostic parameters.

The Diagnostics menu has three submenus that logically split the diagnostic details into three categories: Events Log, Maintenance and Self Tests.

3.5.1 Diagnostics Menu Events Log HydroTrac keeps track of some operating events, such as, number of times the instrument was reset. These events are recorded in a counter that is incremented every time the event occurs. The commands listed in this section are used for diagnostics purposes only; they do not affect the operation of HydroTrac’s data acquisition system.

Each Events Log counter has a maximum value of 65535 counts.

3.5.1.1 Diagnostics Events Log Events Logged #1 Reset On

This command resets the date the HydroTrac has recorded as its last reset date. Normally, HydroTrac reads the date from its real time clock every time it is reset, and stores this information into the Reset On date in the Events Log.

Events Logged #1 More... ->Reset On Jan 01/00 Reset Count= 00001

Press to reset the date to the current date and increment the reset counter by 1.

Press to perform a soft reset.

Note: HydroTrac performs a reset during power up and power down. If power is removed then re-applied, the reset counter will increment by two.

Reset Count

This command clears the counter which increments every time the HydroTrac is reset.

Events Logged #1 More... Reset On Jan 01/00 ->Reset Count= 00001

Press to clear the Reset Count to 0.

Note: This counter can be useful in determining how frequently the HydroTrac experiences power outages or brown-outs.

3.5.1.2 Diagnostics Events Log Events Logged #2 Clear High Temperature Counter

This command clears the counter which increments every minute or so when the HydroTrac measures internal operating temperatures above 70º C.

HydroTrac User Manual Menu System & Display Screens • 3-11 Iris Power Engineering Inc.

Page 30: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Most electronic equipment, HydroTrac included, will operate out-of-manufacturer’s specification when subjected to temperature extremes. When this occurs, HydroTrac will continue to operate and monitor if programmed to do so, but may yield inaccurate results and perhaps lead to failure of the liquid crystal display. The High Temperature Counter can be used as a diagnostics indicator when suspect data is recorded.

Events Logged #2 More... ->High Temp = 00000 Low Temp = 00000

Press to clear the High Temperature counter to 0.

Clear Low Temperature Counter

This command clears the counter which increments every minute or so when the HydroTrac measures internal operating temperatures below -20º C.

Most electronic equipment, HydroTrac included, will operate out-of-manufacturer’s specification when subjected to temperature extremes. When this occurs, HydroTrac will continue to operate, and monitor if programmed to do so, but may yield inaccurate results. The Low Temperature Counter can be used as a diagnostics indicator when suspect data is recorded.

Events Logged #2 More... High Temp = 00000 ->Low Temp = 00000

Press to clear the Low Temperature counter to 0.

3.5.1.3 Diagnostics Events Log Events Logged #3 Clear Comm Errors Counter

This command clears the counter which increments every time the HydroTrac detects a communication error.

This counter is provided so that users can assess the quality of the communication signals connecting HydroTrac to a host computer controller, when running automated tests. In this situation, communication errors can interrupt critical measurement cycles.

Events Logged #3 More... ->Comm Errors= 00000 Net Errors = 00000

Press to clear the Comm Error counter to 0.

Clear Net Errors Counter

This command clears the counter which increments every time the HydroTrac detects a communication error.

This counter is provided so that users can assess the quality of the communication signals connecting HydroTrac to a host computer controller, when running automated test. In this situation, communication errors can interrupt critical measurement cycles.

Events Logged #3 More... Comm Errors= 00000

Press to clear the Network Error counter to 0.

3-12 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 31: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

->Net Errors = 00000

3.5.1.4 Diagnostics Events Log Events Logged #4 Clear Alarm Counter

HydroTrac counts the number of times an Alarm Threshold is exceeded for each of its six coupler-pair inputs in Continuous On-line Mode. Whenever HydroTrac measures NQN or QMax values that exceed the programmed Alarm Threshold, the corresponding alarm counter increments; the alarm is set and remains set even if the alarm condition no longer exists.

The maximum alarm count is 65535. The counters can be displayed so the user can determine the frequency of the alarm condition, in order to determine if the alarm is a one-time anomaly or a cause for concern.

Events Logged #4 More... ->Coupler P1-A Alarm Count= 00000

Press to cycle through the six input pairs.

Events Logged #4 More... Coupler P1-A ->Alarm Count= 00000

Press to clear the Alarm Count.

Note: Clearing the alarm counter does not clear the active alarm. If the Alarm Indicator is lit, you must clear the alarm condition as well – the counters and the alarm status are separate flags.

3.5.1.5 Diagnostics Events Log Events Logged #5 Clear Power Supply Faults

HydroTrac monitors the faults that occur with its power supplies in a counter called Power Supply. This counter is incremented every time HydroTrac’s automatic self-test reports a power supply is out of tolerance. An out of tolerance supply occurs when a voltage is +/- 5% out of its rating.

HydroTrac performs a self-test only at power up and after each measurement cycle when it is in Continuous On-line Mode. If a HydroTrac is in Idle Mode, it does not perform self-tests automatically.

Events Logged #5 More... ->Power Supply=00000 System Errs =00000

Press to clear the Power Supply fault counter.

Clear System Errors Counter

HydroTrac monitors various system operating conditions such as clock failures, memory failures and so on. Most system faults must be investigated at the factory, so this

HydroTrac User Manual Menu System & Display Screens • 3-13 Iris Power Engineering Inc.

Page 32: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

counter is provided only as an indicator of overall operating condition. If a large number of System Errors are recorded, please consult the factory for further instructions.

Events Logged #5 More... Power Supply=00000 ->System Errs= 00000

Press to clear the System Errors counter.

3.5.2 Diagnostics Menu Maintenance The Maintenance submenu, under the Diagnostics menu, is used to clear flags that may have been set during normal operation. Specifically, the Alarm Indicator, the Attention Indicator and storage memory status can be viewed and/or cleared using the Maintenance command.

3.5.2.1 Diagnostics Maintenance Maintenance Menu #1 Clear Alarm Indicator

Whenever an Alarm Threshold is exceeded in four consecutive tests, as setup in Settings Alarm Thresholds, a flag is set in the Alarm Indicator. These flags are latched such that if set, it remains set even after the alarm condition no longer exits. The Alarm Indicator flag must be manually cleared.

Note: It is not possible to clear the Alarm Indicator flag for only a particular coupler pair input – all alarm flags are simultaneously cleared.

The screen displays the current Alarm Indicator status; either Alarm is Clear or Alarm is SET is displayed. When Alarm is SET is displayed, a code is provided which indicates which coupler pair(s) set the Alarm Indictor flag.

Maintenance Menu #1 More... ->Alarm is Clear Code = ------ =00

Press to clear the Alarm Indicator. All alarm flags are cleared.

Press to set the User Alarm Flag in the Alarm Indicator.

See below for an example of the User Alarm Flag setting. When the User Alarm Flag (or any alarm flag) is set, the HydroTrac front panel NQN / QMax Alarm indicator is lit.

Maintenance Menu #1 More... ->Alarm is SET Code = ------U=40

For example,

3-14 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 33: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Maintenance Menu #1 More... ->Alarm is SET Code = -23--6-=26

The display shows three active alarms, code ‘26’. There is an alarm on coupler pair #2, coupler pair #3 and coupler pair #6. For more information about Alarm codes, see Section 6.

3.5.2.2 Diagnostics Maintenance Maintenance Menu #2 Clear Attention Indicator

HydroTrac has user definable Attention Flags. These flags can be programmed to activate the front panel indicator named Attention Indicator to blink, at a rate of twice per second. See Section Error! Reference source not found. for more information about setting Attention Flags.

The purpose of these flags is to allow users to define specific conditions that should visually alert maintenance personnel that the HydroTrac requires attention.

However, even if the Attention flag is set, the Attention Indicator for a particular condition can be disabled, so no visual status is provided.

The Attention Indicator is a status indicator only, and does not affect HydroTrac operation.

Maintenance Menu #2 More... ->Attention is Off Code = 0000

Press to set the User Attention Flag.

Press to clear all Attention Flags, including the User Attention Flag.

Note: All Attention Flags are cleared simultaneously – it is not possible to clear only one flag.

3.5.2.3 Diagnostics Maintenance Maintenance Menu #3 Factory Setup

This command restores the HydroTrac’s configuration to default settings.

Maintenance Menu #3 More... ->Factory Setup Clear Event Log

Press to restore HydroTrac’s configuration to default settings.

The New Data Indicator should blink momentarily (green) to indicate the setup was actually restored.

The default settings are as follows:

• AC Line Sync (C1)

HydroTrac User Manual Menu System & Display Screens • 3-15 Iris Power Engineering Inc.

Page 34: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

• Phase Adjust +090 • Alarm Thresholds are set to 0 for all coupler pair inputs. • Normal power-up mode causes HydroTrac to go to Idle Mode. • The Network communications is ENABLED; therefore, the RS232 communication

is disabled. • Couplers P1-A are enabled, 500mV-8500mV sensitivity. • Couplers P1-B, P1-C, P2-A, P2-B and P2-C are DISABLED. • External multiplexor is enabled, MUX Enabled.

Clear Event Log

This command clears all Event Log counters.

Maintenance Menu #3 More... Factory Setup ->Clear Event Log

Press to clear all Event Log counter to 0.

The New Data Indicator should blink momentarily (green) to indicate the Event Log was actually cleared.

3.5.2.4 Diagnostics Maintenance Maintenance Menu #4 Purge Daily Data

This command clears this day’s measurements. This is useful if, while experimenting with different configuration settings, data was recorded which may be inaccurate or not useful. Normally, HydroTrac commits all daily readings to non-volatile memory at the end of each day.

Maintenance Menu #4 More... ->Purge Daily Data Used memory: 004%

Press to purge this day’s accumulated data.

The New Data Indicator should blink momentarily (green) to indicate the data was actually erased.

Purge Storage Memory

This command clears HydroTrac’s storage memory. The memory storage contains a summary of the last month’s daily data, and 24 months of summarized monthly data.

The display shows the used memory. At the end of every month, the used memory increases by about 4%. When in Continuous On-line Mode, the memory will fill in 24 months.

Note: Once the storage memory is purged, it cannot be restored.

3-16 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 35: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Maintenance Menu #4 More Purge Daily Data ->Used memory: 0%

Press to purge all accumulated data.

The New Data Indicator should blink momentarily (green) to indicate the memory was actually erased.

The keypad becomes unresponsive for a few moments while the memory is being permanently erased.

3.5.2.5 Diagnostics Maintenance Maintenance Menu #5 Upgrade

This command places HydroTrac into a special programming mode, called Code Loader Mode. While in this mode of operation, the HydroTrac’s firmware can be upgraded by Iris’s Upgrade utility program. See the instructions supplied with the Upgrade version for more information or contact Technical Support at Iris Power Engineering for more information. (see Section 6.2.1)

Maintenance Menu #5 More... ->Upgrade...

Press to place the instrument into Code Loader Mode.

Note: Normally, the firmware upgrade utility will automatically return the HydroTrac to normal operation once the upgrade process is complete. However, if you must set the HydroTrac to normal operating mode, simply remove and re-apply the power. Once in Code Loader Mode, the HydroTrac becomes completely unresponsive and will not be able to take any measurements until the instrument is restored to normal operation.

3.5.3 Diagnostics Menu Self Tests The Self Test commands are used to check the operating condition of the HydroTrac.

3.5.3.1 Diagnostics Self Tests Self-Test Menu #1 Instrument Information

This command displays HydroTrac model information, hardware and firmware versions, the HydroTrac’s programmed name, serial number, installed options and, finally, Iris Power Engineering’s worldwide web address.

Self-Test Menu #1 More... ->Information

Press to view the instrument’s information.

HydroTrac User Manual Menu System & Display Screens • 3-17 Iris Power Engineering Inc.

Page 36: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Press OK to view the next screen. There are three screens in total.

Model: HydroTrac H/Ware: HYDRTRC1 S/Ware: 04.03

The Model Name is HydroTrac. The hardware version is HYDRTRC1. The software, or firmware, version is 04.03.

Instrument Name: >HydroTrac 001 < SN# HYDTR9934701 Options: 0279

The name of The instrument is HydroTrac 001. The serial number is HYDTR9934701. The installed options code is 0279.

Iris Power Eng Toronto, CANADA www.irispower.com

Our company name is Iris Power Engineering. The instrument was manufactured in Toronto, Canada. Iris’s worldwide web address.

3.5.3.2 Diagnostics Self Tests Self-Test Menu #2 Check Line Frequency

The Check Line Frequency command verifies the zero crossings of the AC synchronization signal detected by the HydroTrac. (see Section 3.4.2)

Note: HydroTrac can track small changes in the line frequency and operates from 32 Hz to 75 Hz.

Self-Test Menu #2 More... ->Check Line Freq. AC Sync Voltage

Press to view the measured line frequency and its period.

AC Line Frequency 60.000 Hz 16.667 mSec

Press CANCEL to return to Self Test Menu #2.

AC Sync Voltage

This command measures the magnitude of the AC signal measured on coupler C1, the External Reference Input, which ever is used as the AC Sync Source.

The voltage displayed is presented as a range. For example, if the input voltage is 162 mVAC, the display will show 150 to 200 mVAC.

Self-Test Menu #2 More... Check Line Freq. ->AC Sync Voltage

Press to view the measured synchronization signal magnitude. After each update, the New Data Indicator (green) will blink.

3-18 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 37: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

AC Sync Voltage 150 to 200 mVAC

3.5.3.3 Diagnostics Self Tests Self-Test Menu #3 Check Indicators

This command is used to check the operating condition of HydroTrac’s front panel indicators.

Note: In order to test the Attention Indicator, the User Attention Flag must be set.

Self-Test Menu #3 More... ->Check Indicators

Press to start the indicator test. Press CANCEL to stop the test.

IMPORTANT: If you Check Indicators, the NQN / QMax Alarm indicator will also be set, and will trigger an alarm in the Alarm Output Module, if it is installed.

3.5.3.4 Diagnostics Self Tests Self-Test Menu #4 Check High Power Supplies

This menu item displays the status of the +/- 15 volt power supplies in the HydroTrac.

When the power supplies are +/-10% out of tolerance, they are reported as BAD.

Self-Test Menu #4 ->More... +15 Power = Ok -15 Power = Ok

Press F1 to update the display.

3.5.3.5 Diagnostics Self Tests Self-Test Menu #5 Check Low Power Supplies

This menu item displays the status of the +/- 5 volt supplies in the HydroTrac.

When the power supplies are +/-10% out of tolerance, they are reported as BAD.

Self-Test Menu #5 ->More... +5 Power = Ok -5 Power = Ok

Press F1 to update the display.

3.5.3.6 Diagnostics Self Tests Self-Test Menu #6 Check Reference Power

HydroTrac User Manual Menu System & Display Screens • 3-19 Iris Power Engineering Inc.

Page 38: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

This menu item displays the current status of the battery used to save settings information, and the internal voltage reference.

When these voltages are +/-10% out of tolerance, they are reported as BAD.

Self-Test Menu #6 ->More Battery = Ok VRef. = Ok

Press F1 to update the display.

Note: For information on how to replace the battery, please see the HydroTrac Installation Guide.

Note: VRef does NOT refer to the AC Sync voltage; it refers to an internal reference voltage used for decoding PD pulses.

3.5.3.7 Diagnostics Maintenance Self-Test Menu #7 Check RS232 Port

This command checks the RS232 port operating status.

When the port is operating properly, no error message is displayed. This self-test is used at the factory.

Self-Test Menu #7 More... ->Check COMM Check Network

Press to start the test. After a successful test, the New Data Indicator (green) will blink once.

Check Network Port

This command is used to check the network port operating status.

When the port is operating properly, no error message is displayed. This self-test is typically used at the factory.

Self-Test Menu #7 More... Check COMM ->Check Network

Press to start the test. After a successful test, the New Data Indicator (green) will blink once.

3.5.3.8 Diagnostics Self Tests Self-Test Menu #8 Check Temperature

This command checks the internal temperature of the HydroTrac. The temperature is measured directly on the data acquisition board and reflects the temperature in Celsius of the circuit board, not the ambient temperature.

3-20 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 39: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Self-Test Menu #8 ->More... Temperature +030.0

Press F1 to update the temperature. The New Data Indicator (green) will blink once when the temperature is updated.

3.5.3.9 Diagnostics Self Tests Self-Test Menu #9 Check Multiplexer

This command checks the status of the externally connected multiplexor.

Self-Test Menu #9 ->More... MUX Status - Enabled

The multiplexor is enabled.

Self-Test Menu #9 ->More... MUX Status - DISABLED

The multiplexor is disabled.

Self-Test Menu #9 ->More... MUX Status - NOT Found

This message appears when the external multiplexor is not detected. In this case, the multiplexor may be disconnected from the HydroTrac, or it may be mal-functioning. See the HydroTrac Installation Guide for more information.

HydroTrac User Manual Menu System & Display Screens • 3-21 Iris Power Engineering Inc.

Page 40: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

This page left blank intentionally.

3-22 • Menu System & Display Screens HydroTrac User Manual Iris Power Engineering Inc.

Page 41: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

4. Continuous On-Line Mode

4.1 Continuous On-Line Monitoring Procedure The following section describes, in step-by-step fashion, the procedure the user must follow to set up HydroTrac for the Continuous On-line Mode.

Before beginning, determine whether the AC Synchronization Signal will be obtained from the C1 input or an external reference.

HydroTrac V04.03 Copyright (c) 2000. Iris Power Eng Initializing...

Power up the HydroTrac. Press CANCEL to make sure HydroTrac is off-line. (Alternatively, you can press F1 at power up to reset all of HydroTrac’s configuration settings to Factory Default values.)

HydroTrac Main Menu Measurements ->Settings Diagnostics

Select the Settings menu item and press OK or .

Settings Menu #2 ->More... AC Line Sync (C1) Phase Adjust +090

Press to move the cursor the Settings Menu #2 menu item.

Select the AC Line Sync menu item, and press to toggle.

Select the Phase Adjust menu item, and press to adjust the phase offset.

Settings Menu #3 More... ->Couplers P1-A Alarm=No NQN,No Qm

Select the Couplers P1-A menu item and press to cycle through all the Alarm Thresholds for the

coupler pairs.

Select Alarm Level: [ NQN ],[ Qm ] -OFF- , -OFF- ^

To change the Alarm Threshold, press to move the cursor from left to right and press to adjust the Alarm Threshold level.

Press OK to accept the changes.

Settings Menu #4 ->More... Power-On: ON-LINE Network: ENABLED

Select the Power-On: IDLE line and press to toggle the default power on mode of operation and network status.

HydroTrac User Manual Continuous On-Line Mode • 4-1 Iris Power Engineering Inc.

Page 42: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Settings Menu #5 ->More... Couplers P1-A 20mV-340mV Range

Select the Couplers menu item. Use to cycle through all the coupler pairs to set the sensitivity ranges.

Settings Menu #8 ->More... MUX Enabled SOM Disabled

Use to Enable the (MUX) and SOM (if the SOM is installed)

Settings Menu #9 ->More... 5 Second Test

Use to select test duration. We recommend the 1 Second Test setting.

HydroTrac Main Menu ->Measurements Settings Diagnostics

Press CANCEL to return to the top level menu.

Press to move the cursor the Measurements menu item.

Press OK or to display the Measurements Menu items.

Measurement Menu ->Continuous On-Line Single Shot

Select Continuous On-Line and press OK to begin on-line monitoring.

4.2 Continuous On-Line Monitoring Display Data While in Continuous On-Line mode, the HydroTrac cycles through a number of screens. Which screens are displayed is configured via the TracWiz software application, refer to the TracWiz User Manual for further information.

Every five seconds or so, each enabled screen is displayed.

To speed up the display cycle, press and hold the key. While pressed, the display will cycle every second.

To hold the display on a particular screen, press and hold the key. The display will be held until the key is released. The display will be updated every 5 seconds.

4-2 • Continuous On-Line Mode HydroTrac User Manual Iris Power Engineering Inc.

Page 43: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Temperature: +038.0 Temperature is ok. Jan 21/00 12:01:59

This screen shows the current HydroTrac internal temperature, +038.0, in Celsius.

The temperature status, Temperature is ok.

The date and time. The time is not continuously updated.

Diagnostics Power Supplies=ok. Sync Reference=ok. System Faults=ok.

The self-test diagnostics status is shown.

The power supplies are ok, or BAD when out of tolerance by +/- 10%.

The external AC Synchronization Signal status is ok or BAD.

The operating system status is ok or BAD.

When BAD is displayed, contact Technical Support for further instructions.

HydroTrac Model II Version 04.03 SN: 9934701

This screen shows the instrument model number, HydroTrac Model II, the software version number, 04.03 and the instrument’s serial number 9934701.

Today Max: P1-A NQN = 0, 0 Qmax= 0, 0 Alrm= No alarm. 0:4 Today Max: P1-B NQN = 108, 0 Qmax= 199, 0 Alrm= YES 4:4 Today Max: P1-C NQN = 0, 0 Qmax= 0, 0 Alrm= No Alarm. 1:4

Today Max: P2-A NQN = 0, 0 Qmax= 0, 0 Alrm= No Alarm. 0:4

Today Max: P2-B NQN = -OFF-,-OFF- Qmax= -OFF-,-OFF- Alrm= No Alarm. 2:4

Today Max: P2-C NQN = -OFF-,-OFF- Qmax= -OFF-,-OFF- Alrm= No Alarm. 0:4

Each of the next six screens, when enabled, show the daily maximum values for each of the coupler pair inputs.

The NQN value for C1 is displayed, followed by the NQN value for C2.

The QMax value for C1 is displayed, followed by the QMax value for C2.

The current Alarm Flag status is either No Alarm or YES.

The 0:4 indicate how many consecutive tests of the last four have exceeded the alarm settings. When 4:4, the alarm is set.

When Alrm = YES is displayed, the Alarm Indicator is set. If the alarm condition clears itself the text will return to Alrm= No Alarm; however the Alarm Indicator will remain lit until the user manually clears it.

When a particular input pair is disabled, the NQN and QMax values are displayed as -OFF-, indicating no reading.

Active Coupler Pair Input: P1-A Range: 20mV-340mV

This screen shows the active input.

The active input is P1-A and its sensitivity is 20mV-340mV.

HydroTrac User Manual Continuous On-Line Mode • 4-3 Iris Power Engineering Inc.

Page 44: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

AC Voltage mVac: 50 to 100 Frequency: 59.9 Hz

This screen shows the AC Synchronization Signal voltage magnitude and frequency.

The voltage magnitude is displayed as a range, i.e.: 50-100mVAC.

The frequency is displayed in Hertz, 59.9 Hz.

Alarm Code: 07 Attention: 1000 Memory Used: 004% Status: 00

This display shows the Alarm Code, the Attention Flags, the Memory Used and the Status Codes.

Please see Section 6 for explanation.

Sync signal error. Trying next coupler pair. Wait a moment...

This screen is displayed when there is a loss of the AC Synchronization Signal. When this occurs, HydroTrac will skip the inactive input pair and proceed to the next enabled input pair.

MUX error. Trying next coupler pair. Wait a moment...

This screen is displayed when there is a malfunction in the multiplexor. As before, when this occurs, HydroTrac will skip the inactive input pair and proceed to the next enabled input pair.

4-4 • Continuous On-Line Mode HydroTrac User Manual Iris Power Engineering Inc.

Page 45: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

5. Termination Panel

5.1 Description

The Termination Panel is used to connect up to six pairs (12 couplers) to the HydroTrac instrument.

The Termination Panel is housed inside the HydroTrac enclosure, and internally connected to the HydroTrac electronics.

The Termination Panel receives power and control signals from the HydroTrac Electronics.

The Termination Panel contains a single green indicator that is turned on when HydroTrac performs a measurement.

HydroTrac automatically selects the coupler pair when a measurement is performed.

The Termination Panel contains surge protection circuitry.

For detailed information and dimensional diagrams on the Termination Panel, see the HydroTrac Installation Guide.

HydroTrac User Manual Termination Panel • 5-1 Iris Power Engineering Inc.

Page 46: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

This page left blank intentionally.

5-2 • Termination Panel HydroTrac User Manual Iris Power Engineering Inc.

Page 47: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

6. Troubleshooting & Support

6.1 Troubleshooting Guide The following section is meant to be used as a simple guide for troubleshooting common problems. If you experience difficulties in getting your HydroTrac to function properly, contact Technical Support at Iris Power Engineering.

The HydroTrac display is blank, and does not appear to be working.

1. Check the AC power supply. 2. Check the fuses. Refer to the HydroTrac Installation

Guide for more information on the fuse type and location.

3. Check the liquid crystal display contrast control. Under some circumstance, the display may become too dim to read. You can increase the contrast by turning the LCD Contrast Control clockwise. See Figure 1-1. HydroTrac Front Panel.

4. Contact Iris Power Engineering for technical support. See Maintenance & Service in Section 6.2.3.

The HydroTrac ‘NQN/QMax Alarm’ indicator is set’

1. Reset the alarm. See Diagnostics Maintenance Maintenance Menu #1, Section 3.5.2.1.

The ‘Attention’ indicator is blinking, but the HydroTrac appears to be working properly.

1. Check the ‘Attention Code’, as described in Diagnostics Maintenance Maintenance Menu #2 Section 3.5.2.2. The Attention Code is a hexadecimal representation of 16 flags. The flags are described as follows: 0001 Temperature limits exceeded 0002 Power supply malfunction 0004 Instrument was reset 0008 Communications errors detected 0010 Network errors detected 0020 User defined 0040 Memory more than 90% full 0080 No AC Sync signal available 0100 Memory faults detected 0200 Clock error 0400 Battery needs replacing 0800 Multiplexor is disabled

2. Read the codes as follows: 8 + 1 = 9 8+2 = A 8+1+2 = B 8+4 = C 8+1+4 = D 8+2+4 = E

HydroTrac User Manual Troubleshooting & Support • 6-1 Iris Power Engineering Inc.

Page 48: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

8+1+2+4 = F

3. If Flag 0001 is set, the HydroTrac has experienced temperature extremes outside its operating limits. Check the Events Log in Section Diagnostics Menu Events Log.

4. If Flag 0002 is set, Contact Iris Power Engineering for technical support. See Maintenance & Service in Section 6.2.3.

5. If Flag 0004 is set, the HydroTrac was reset by a power-up operation, or by a user. Check the Events Log in Section Diagnostics Menu Events Log on page 3-11.

6. If Flag 0008 is set, HydroTrac has experienced at least one communications error. Check the Events Log in Section Diagnostics Menu Events Log.

7. If Flag 0010 is set, HydroTrac has experienced at least one network error on its RS485 or fiber optic communications bus. Check the Events Log in Section Diagnostics Menu Events Log.

8. If Flag 0020 is set, a user has turned ‘on’ the Attention Indicator. See Diagnostics Maintenance Maintenance Menu #2 Section 3.5.2.2.

9. If Flag 0040 is set, HydroTrac’s memory is more than 90% full. You should download HydroTrac’s memory. After a successful download, erase the memory. See Diagnostics Maintenance Maintenance Menu #4.

10. If Flag 0080 is set, HydroTrac is not detecting any AC Sync voltage. This may be normal if HydroTrac is off-line. Try running the diagnostics. See Diagnostics Self Tests Self-Test Menu #2.

11. If Flag 0100 is set, the HydroTrac experienced a memory fault. Contact Iris Power Engineering for technical support. See Maintenance & Service in Section 6.2.3.

12. If Flag 0200 is set, set HydroTrac’s clock.

13. If Flag 0400 is set, replace HydroTrac’s battery. See HydroTrac Installation Guide for more information.

14. If Flag 0800 is set, the external multiplexor is not connected, is malfunctioning or was disabled. Try enabling the multiplexor. See Settings Settings Menu #8.

Reset the Attention Indicator as described in Diagnostics Maintenance Maintenance Menu #2 Section

3.5.2.2. The ‘Attention’ indicator is blinking, and the HydroTrac does not appear to be working

1. Check the power supply. HydroTrac will blink its Attention Indicator if a brownout condition exists.

2. Contact Iris Power Engineering for technical support. See Maintenance & Service in Section 6 2 3

6-2 • Troubleshooting & Support HydroTrac User Manual Iris Power Engineering Inc.

Page 49: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

properly. See Maintenance & Service in Section 6.2.3.

Measurements cannot be performed because there is a ‘Sync Signal Error’ message.

1. Check the coupler inputs. HydroTrac requires at least 100 mVrms to synchronize on the power supply frequency. Try running the diagnostics. See Diagnostics Self Tests Self-Test Menu #2.

2. The Synchronization Source may be incorrectly set. See Settings Settings Menu #2. Normally, the AC Line Sync must be Coupler C1, not External.

3. Contact Iris Power Engineering for technical support. See Maintenance & Service in Section 6.2.3.

Unable to communicate with HydroTrac via front panel RS232 connector.

1. Make sure the Network is disabled. See Section Settings Settings Menu #4.

2. Make sure your RS232 cable is less than 2 meters, or 6 feet in length.

3. Make sure you have the correct communications port selected on your computer.

Unable to communicate with the HydroTrac via the RS485 or fiber optic network.

1. Make sure you have the correct Multi-drop address selected. See HydroTrac Installation Guide on information about setting the correct address.

2. Make sure the Network is enabled. See Section Settings Settings Menu #4.

3. Make sure the RS485 Modem or Fiber Optic Modem is powered, and connected to the correct communications port on your computer.

4. Make sure you have the wiring to the RS485 terminals correct. See HydroTrac Installation Guide for wiring instructions.

6.2 Customer Support Services

6.2.1 Technical Support If you require additional technical support, please contact Iris Power Engineering’s Technical Support at e-mail [email protected] or fax 416-620-1995 or telephone 416-620-5600 from 9:00 a.m. to 3:00 p.m. Eastern Standard Time.

6.2.2 Sales If you would like to obtain additional materials, please contact your sales representative at Iris Power Engineering at 416-620-5600, 9:00 a.m. to 3:00 PM Eastern Standard Time.

HydroTrac User Manual Troubleshooting & Support • 6-3 Iris Power Engineering Inc.

Page 50: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

6.2.3 Maintenance & Service For maintenance or repair services, contact Iris Power Engineering’s Manufacturing Department, at 416-620-5600, 9:00 a.m. to 3:00 p.m. Eastern Standard Time.

Iris Power Engineering is an ISO Certified company.

6.2.4 Product Updates, New Products For firmware upgrades, software upgrades, product updates and new products, visit our website, www. irispower. com regularly or contact your sales representative at iris Power Engineering.

6-4 • Troubleshooting & Support HydroTrac User Manual Iris Power Engineering Inc.

Page 51: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

7. Specifications

Electrical Specifications:

Supply Voltage 85 VAC to 260 VAC, line frequency of 50 Hz or 60 Hz, auto sensing. Will continue to operate under brown-out conditions where the AC supply voltage drops as low as 40 VAC.

Supply Power < 30 Watts

Fuse 2.5A Fast Blow. Size: 1¼”x¼” AGC Type fuse. To replace the fuse, use a screwdriver to gently press down on fuse holder cap and rotate it counter-clockwise. The fuse is fit into the cap.

Optional External Voltage Reference Input

2.5 VAC to 250 VAC Must be provided by SMA-Type terminated connector and must be connected inside the instrument.

Coupler Input Sensitivity 5 mVpk to 8500 Vpk, in six user selectable ranges. 5 mV to 85 mV in 5 mV steps 10 mV to 170 mV in 10 mV steps 20 mV to 340 mV in 20 mV steps 50 mV to 850 mV in 50 mV steps 100 mV to 1700 mV in 100 mV steps 200 mV to 3400 mV in 200 mV steps 500 mV to 8500 mV in 500 mV steps A minimum of 80 mVAC must be present to synchronize to the power line frequency.

Test Duration 1 Second Test or 5 Second Test, user selectable.

Input Signal Frequency 32 Hz to 75 Hz The instrument automatically adjusts measurement cycles based on the input frequency of the AC Synchronization Signal. The instrument can track small changes in the frequency during a test cycle. All measurement data is normalized to the AC Synchronization Signal frequency. The power line frequency measured by the instrument is accurate to +/-2%.

HydroTrac User Manual Specifications • 7-1 Iris Power Engineering Inc.

Page 52: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

Environmental Conditions:

Operating Temperature When applying power, ambient temperature must be at least 0 ºC (32 ºF), and at most 35 ºC (95 ºF).

Storage Temperature -20 ºC (-5 ºF) to 70 ºC (150 ºF)

Temporary Operating Temperature Extremes

-20 ºC (-5 ºF) to 50 ºC (120 ºF)

Humidity Should be keep out of direct water spray.

Physical Specifications:

Dimensions H = 12” (30 cm), W = 10” (25 cm), D = 7” (18 cm)

Weight 10 lbs (5 kg)

Features:

Communication RS232 Direct Connect, via front panel DB9 connector. Optional RS485 four-wire multi-drop connection. Optional fiber optic converters.

New Data Indicator Turns on when new data is available. Acquiring Data Indicator Turns on when acquiring new data. Alarm Indicator Turns on if alarms are set and if alarm thresholds are

exceeded. Attention Indicator Turns on under various user-definable conditions. Display Screen 20 character by 4 line backlit LCD display. Keypad Eight, waterproof tactile-feedback keypad. Can be cleaned

with alcohol-based cleaners. Keypad life span >1,000,000 cycles.

Enclosure NEMA 4 Rated enclosure. In order to maintain NEMA 4 rating, user must supply water tight connections for power and optional RS485 or fiber optic communications.

Required Connections:

AC Power (If this option is installed)

85 VAC to 260 VAC, single phase, auto-sensing, < 30 Watts

Signal Inputs Two couplers (one pair) can be connected at any time. The inputs are made via the Termination Panel. Avoid excessive signal input on the 5 mV and 10 mV ranges. When not making a measurement, the input signal is automatically isolated from the measurement circuitry.

7-2 • Specifications HydroTrac User Manual Iris Power Engineering Inc.

Page 53: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

8. Index 2

2-D data ................................................ 1-4, 2-6

A

Acquiring Data front panel indicator ...................................1-2

Alarm Output Module configure alarm levels ....................... 2-1, 3-5 operation....................................................1-4

alarm threshold, definition.............................1-5 Alarms

Clearing alarms .......................................3-14 configure alarm levels ...............................3-5 definition ....................................................1-4

Archived Data Daily................................................... 1-4, 2-7 Monthly .............................................. 1-4, 2-7

Attention codes .........................................................6-1 front panel indicator ...................................1-3 reset attention indicator ...........................3-15

B

battery check voltage................................... 2-1, 3-19 replacing ..................................................3-20

C

circular buffer, definition................................1-5 clock

setting ........................................................3-8 command

change clock...................................... 2-1, 3-8 change instrument name................... 2-1, 3-8 check AC sync frequency................ 2-2, 3-18 check AC sync voltage .................... 2-1, 3-18 check battery voltage ...................... 2-1, 3-19 check indicators............................... 2-2, 3-19 check instrument information .......... 2-4, 3-17 check instrument temperature......... 2-2, 3-20 check last reset date ....................... 2-4, 3-11 check multiplexer............................. 2-2, 3-20 check network communications ...... 2-2, 3-20 check power supply......................... 2-2, 3-19 check reference power supply ........ 2-2, 3-19 check RS232 communcations......... 2-2, 3-20 clear alarm counters........................ 2-2, 3-13 clear alarms ..................................... 2-2, 3-14 clear attention flags ......................... 2-2, 3-15

clear daily data .................................2-3, 3-16 clear event log..................................2-3, 3-16 clear high temperature counter ........2-3, 3-11 clear low temperature counter .........2-3, 3-12 clear network comm. error counter ..2-3, 3-12 clear power supply fault counter ......2-3, 3-13 clear reset counter ...........................2-3, 3-11 clear RS232 comm error counter.....2-3, 3-12 clear system errors counter .............2-3, 3-13 configure AC line sync .......................2-1, 3-5 configure alarm levels ........................2-1, 3-5 configure measurement duration .....2-4, 3-10 configure measurement sensitivity.....2-5, 3-7 configure network communcations ....2-4, 3-6 configure phase adjustment...............2-4, 3-5 configure power-on mode ..................2-4, 3-6 configure RS232 communications .....2-4, 3-6 configure Single Shot sensitivity ........2-5, 3-2 configure Single Shot test source ......2-5, 3-2 enable multiplexer ..............................2-4, 3-9 enable Sensor Output Module ...........2-4, 3-9 go On-Line..........................................2-3, 3-2 purge archive memory .....................2-5, 3-16 restore factory setup ........................2-4, 3-15 restore settings...................................2-5, 3-4 run Single Shot test............................2-5, 3-3 save settings ......................................2-5, 3-4 upgrade firmware .............................2-6, 3-17 user attention flag.............................2-6, 3-15 view last Single Shot test ...................2-6, 3-3

command summary ......................................2-1 Communications

RS232 connector ......................................1-3

D

Daily Archived Data ....................... 1-4, 2-7, 3-3 date & time.........................................See Clock Daylight Savings Time .......................See Clock definitions

Termination Board.....................................1-4 Definitions

alarm .........................................................1-4 alarm threshold .........................................1-5 circular buffer ............................................1-5 NQN ..........................................................1-4 phase shift .................................................1-5 QMax.........................................................1-4 sensitivity range ........................................1-4

E

error codes

HydroTrac User Manual Index • 8-3 Iris Power Engineering Inc.

Page 54: HydroTrac User Manualdocshare01.docshare.tips/files/29152/291529073.pdf · 2016-05-30 · 1. Introduction 1.1 Overview Welcome to the HydroTrac™ User Manual. The HydroTrac instrument

attention.....................................................6-1

F

front panel indicators Acquiring Data ...........................................1-2 Attention ....................................................1-3 New Data...................................................1-2 NQN / QMax Alarm....................................1-3

I

Idle Mode .............................................. 2-7, 3-1

L

liquid crystal display adjusting contrast ......................................1-2 specifications .............................................7-2

M

menus menu map..................................................3-1 menu paths................................................2-1 navigating ..................................................1-6

Monthly Archived Data ................... 1-4, 2-7, 3-3 multiplexor...................... See termination board

N

New Data front panel indicator ...................................1-2

NQN / QMax Alarm front panel indicator ...................................1-3 reset alarm...............................................3-14

NQN, definition..............................................1-4

O

operating mode Continuous On-Line ..................................2-7 Idle......................................................2-7, 3-1 Remote Control ..................................2-6, 2-7

P

phase shift, definition ....................................1-5

Q

Qm (Qmax), definition...................................1-4

R

restore factory setup .....................................2-7 RS232 communications

connector...................................................1-3

S

sensitivity range definition ....................................................1-4

settings default......................................................3-15

Standard Time ...................................See Clock

T

Termination Board, definition........................1-4 time & date.........................................See Clock

8-2 • Index HydroTrac User Manual Iris Power Engineering Inc.