1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine, P.E. Levine Lectronics and Lectric E-mail: [email protected] GE Multilin / Instrument Transformers, Inc.

Ieee Cts and Pts 6-10

Embed Size (px)

Citation preview

Page 1: Ieee Cts and Pts 6-10

1GE Multilin

Instrument Transformers, Inc.

Are you using the right CT's and PT's for your application?

John Levine, P.E.

Levine Lectronics and LectricE-mail: [email protected]

GE Multilin / Instrument Transformers, Inc.

Page 2: Ieee Cts and Pts 6-10

2GE Multilin

Instrument Transformers, Inc.

Alternate Title of Presentation

Now I know what I do not know about CT’s and PT’s.

As engineers we do not need to know all the answers just where to get them.

Page 3: Ieee Cts and Pts 6-10

3GE Multilin

Instrument Transformers, Inc.

Current & Voltage Transformer Basics (IEEE Standards)

Page 4: Ieee Cts and Pts 6-10

4GE Multilin

Instrument Transformers, Inc.

Agenda

Current TransformersVoltage TransformersRequired Information for Specifying CTs & VTsTake Home Rules” for CTs & VTsApplications where used

Page 5: Ieee Cts and Pts 6-10

5GE Multilin

Instrument Transformers, Inc.

Why use Instrument Transformers?

Circuit Isolation

Reduce voltage and currents to reasonable working levels.

Phasor combinations for summing and measuring power

Page 6: Ieee Cts and Pts 6-10

6GE Multilin

Instrument Transformers, Inc.

CURRENT TRANSFORMERS   TYPES OF C.T. CONSTRUCTION 

The most common type of C.T. construction is the “DOUGHNUT” type. It is constructed of an iron toroid, which forms the core of the transformer, and is wound with secondary turns. 

            

Secondary Winding Primary Conductor

Iron Core

Page 7: Ieee Cts and Pts 6-10

7GE Multilin

Instrument Transformers, Inc.

Transformer ratio (TR)

Primary Current(100 amps)

Secondary Current (5 amps)

Primary CurrentSecondary Current

Transformer Ratio = _____________________

100 5___ = 100:5 or 20:1

Page 8: Ieee Cts and Pts 6-10

8GE Multilin

Instrument Transformers, Inc.

PolarityDirection ofPrimary Current

Direction of Secondary Current

H1X1

Primary current into “polarity” = Secondary current out of “polarity”

P1

IEEE

IEC

Primary PolarityMarks

IEEEIECS1

Secondary PolarityMarks

Remember:

Page 9: Ieee Cts and Pts 6-10

9GE Multilin

Instrument Transformers, Inc.

Polarity

Direction ofPrimary Current

Direction of Secondary Current

H1

X1

P1

IEEE

IEC

Primary PolarityMarks

IEEEIECS1

Secondary PolarityMarks

Primary current into “non-polarity” = Secondary current out of “non-polarity”

Remember:

Page 10: Ieee Cts and Pts 6-10

10GE Multilin

Instrument Transformers, Inc.

Generator typical wiring

Page 11: Ieee Cts and Pts 6-10

11GE Multilin

Instrument Transformers, Inc.

What is your application?

If your application is metering , how high do I need to go in current? 2 times ?

If your application is protective relaying, how high do I need to go in current? 20 times ? 40 times ?

Page 12: Ieee Cts and Pts 6-10

12GE Multilin

Instrument Transformers, Inc.

CT Rating Factor (RF) -- IEEERated current x (RF) =

Maximum continuous current carrying capability:

Without exceeding temperature limits

Without loss of published accuracy class

Typical rating factors for Metering CTs are:

1.0, 1.33, 1.5, 2.0, 3.0, 4.0

Page 13: Ieee Cts and Pts 6-10

13GE Multilin

Instrument Transformers, Inc.

0.30

0.30

0.60

0.60

Rating Factor

Accu

racy

Cla

ss -

%CT Rating Factor (RF) -- IEEE

10% 100% 200% 300% 400%

1.0 2.0 3.0 4.0

IEEE C57.13 Accuracy0.3% @ BX.X RF 4.0

0.3% Accuracy Region

0.6% Accurac

y Region

Page 14: Ieee Cts and Pts 6-10

14GE Multilin

Instrument Transformers, Inc.

Short-Time Thermal Current Rating

One (1) – second thermal ratingExpressed as value of RMS primary currentMain influencing factor:

CT primary & secondary wire size Can be converted to thermal rating for any time period (t) up to five (5) seconds:

(New RF at new Ambient/Stated RF at 30 degrees C)2=85-New Ambient/New Ambient

Example: CT with rating factor of 4 at 30 degrees = rating factor of 2.95 at 55 degreesX2/42=85-55/55 X=2.95

Page 15: Ieee Cts and Pts 6-10

15GE Multilin

Instrument Transformers, Inc.

CT Metering Accuracy

Actual secondary

current

Rated secondary

current=

Difference in % is known as the “Accuracy”

of the CT

Page 16: Ieee Cts and Pts 6-10

16GE Multilin

Instrument Transformers, Inc.

IEEE CT Metering AccuracyAccuracy Class ( * )

Application

0.15 High Accuracy Metering0.15S “Special” High Accuracy Metering0.3 Revenue Metering0.6 Indicating Instruments1.2 Indicating Instruments* All accuracy classes defined by IEEE C57.13 or C57.13.6

* Accuracy classes include both ratio & phase angle error

Page 17: Ieee Cts and Pts 6-10

17GE Multilin

Instrument Transformers, Inc.

IEEE CT Metering Accuracy

BurdenLoad connected to CT secondaryIncludes devices & connecting leads

Expressed in ohms Standard values = B0.1, B0.2, B0.5, B0.9,

B1.8 E0.04, E0.2All burdens defined by IEEE C57.13 or C57.13.6 for 60 Hz only

Page 18: Ieee Cts and Pts 6-10

18GE Multilin

Instrument Transformers, Inc.

Application Burden Designation

Impedance (Ohms)

VA @ 5 amps

Power Factor

Metering B0.1 0.1 2.5 0.9B0.2 0.2 5 0.9B0.5 0.5 12.5 0.9B0.9 0.9 22.5 0.9B1.8 1.8 45 0.9

Standard IEEE CT Burdens (5 Amp) (Per IEEE Std. C57.13-1993 & C57.13.6)

IEEE CT Metering Accuracy

E0.2E0.04

0.20.04

51

1.01.0

Page 19: Ieee Cts and Pts 6-10

19GE Multilin

Instrument Transformers, Inc.

A current transformer for metering purposes may typically have an accuracy of 0.3%. The C.T. must maintain this accuracy for normal load currents, provided the rated burden on the C.T. is not exceeded. It is quite acceptable, and in fact desirable, for the C.T. to saturate when fault current flows. The accuracy for a typical metering C.T. is specified as:  0.3 M 0.9

O.3% METERING O.9 OHMS BURDEN

This metering C.T. has an accuracy of 0.3% when the connected burden does not exceed 0.9 OHMS.

CT CLASSIFICATION for MeteringCT CLASSIFICATION for Metering

Page 20: Ieee Cts and Pts 6-10

20GE Multilin

Instrument Transformers, Inc.

IEEE CT Metering Accuracy

Accuracy Class(0.3, 0.6, 1.2) (*)

Burden (Ohms)(B0.1, B0.2, B0.5, B0.9, B1.8)

+

“Accuracy” expressed as:

0.3B0.20.6B0.91.2B1.80.15E0.2

=Typical

Examples

* Accuracy class is stated at 100% rated current* At 10% rated current, twice the error is allowed (5% for 0.15 class)

(0.15*, 0.15S^) E0.2, E0.04)

^ Accuracy class is stated at 100% to 5% rated current

Page 21: Ieee Cts and Pts 6-10

21GE Multilin

Instrument Transformers, Inc.

0.30

0.30

0.60

0.60

Rating Factor

Accu

racy

Cla

ss -

%

10% 200% 300%

1.0 2.0 3.0 4.0

IEEE C57.13 Accuracy0.3 @ BX.X; RF 4.0

0.3% Accuracy Region

0.6% AccuracyRegion

IEEE CT Metering Accuracy

100% 400%

No accuracy guaranteed at current levels less than 10%

Page 22: Ieee Cts and Pts 6-10

23GE Multilin

Instrument Transformers, Inc.

IEEE CT Metering Accuracy

Corrected to 0.3% Class

CT Parallelogram – IEEE C57.130.3 classparallelogram

0.6 classparallelogram

100%

10%

Note:Burden must be specified

Page 23: Ieee Cts and Pts 6-10

26GE Multilin

Instrument Transformers, Inc.

IEEE CT Relay AccuracyProtection CT

Standard Relay Accuracy Classes

C or T100C or T200C or T400C or T800

What do these mean?

Page 24: Ieee Cts and Pts 6-10

27GE Multilin

Instrument Transformers, Inc.

IEEE CT Relay Accuracy

Relay class (C or T___ ) designates minimum secondary terminal volts…

At 20 times rated currentWithout exceeding 10% ratio errorInto a maximum specified burden

Now that everyone is totally confused let’s look at some simple examples …

Page 25: Ieee Cts and Pts 6-10

28GE Multilin

Instrument Transformers, Inc.

T = Determined by test

CT CLASSIFICATION for RELAYINGCT CLASSIFICATION for RELAYING

10 C 40010 C 400

Protection Class CT’sProtection Class CT’s - Must supply 20 times rated current- Must supply 20 times rated current

C = CalculatedK = CalculatedL = Low internal secondary impedanceH = High internal secondary impedance

Format

LetterAccuracy Voltage at 20 times CT

Page 26: Ieee Cts and Pts 6-10

29GE Multilin

Instrument Transformers, Inc.

Primary current24,000 amps(20 x 1200)

IEEE CT Relay Accuracy

CT1200:5

C or T100

X1X2 Burden of

Devices ()

Burden ofLeads ()

Secondary current 100 amps (20 x 5)

Total Ext Burden1.0

C or T100 example

Terminal Volts = (20 times rated) (Total external burden) 100 Volts = (100 amps) (1.0 )

Term

inal

Vol

ts =

100

Page 27: Ieee Cts and Pts 6-10

30GE Multilin

Instrument Transformers, Inc.

Primary current24,000 amps(20 x 1200)

IEEE CT Relay Accuracy

CT1200:5

C or T200

X1X2 Burden of

Devices ()

Burden ofLeads ()

Secondary current 100 amps (20 x 5)

Total Ext Burden2.0

C or T200 example

Terminal volts = (20 times rated) (Total external burden) 200 Volts = (100 amps) (2.0 )

Term

inal

Vol

ts =

200

Page 28: Ieee Cts and Pts 6-10

31GE Multilin

Instrument Transformers, Inc.

Standard IEEE CT Burdens (5 Amp) (Per IEEE Std. C57.13-1993)

IEEE CT Relay Accuracy

Application Burden Designation

Impedance (Ohms)

VA @ 5 amps

Power Factor

Relaying B1 1 25 0.5

B2 2 50 0.5 B4 4 100 0.5 B8 8 200 0.5

Page 29: Ieee Cts and Pts 6-10

32GE Multilin

Instrument Transformers, Inc.

IEEE CT Relay AccuracyExcitation curve includesvoltage required to overcome internal resistance (DCR) of CT.Approximately 32 volts.

10% ratio error = (20 x 5) (10%) = (100) (0.10) = 10 ampsHow many terminal

volts would you estimate this CT can produce?

Page 30: Ieee Cts and Pts 6-10

33GE Multilin

Instrument Transformers, Inc.

1000:5 CT

1000 Amps 5ampsIE<0.5amps

IB >4.5 amps

With 10% error, IB is anywhere from 4.5 to 5.5 amps

Most Protection CT’s also have a Metering CT accuracy so you could use this value for calculating the error at lower currents

Page 31: Ieee Cts and Pts 6-10

34GE Multilin

Instrument Transformers, Inc.

CT Burden Calculation

Primary Current

CT

X1X2 Burden of

Devices ()

Burden ofLeads ()

Secondary current

Total Burden ZT

How do we calculate this?

Page 32: Ieee Cts and Pts 6-10

35GE Multilin

Instrument Transformers, Inc.

CT Burden Calculation

Assumption: 3 phase CTs are “Y” connected

ZT = RCT + RL + ZB

ZT =Total burden in ohms (vector summation of resistance and inductance components)

RCT = CT secondary resistance in ohms @75 deg C (DCR)

RL =Resistance of leads in ohms (Total loop distance)

ZB = Device impedance in ohms

Page 33: Ieee Cts and Pts 6-10

36GE Multilin

Instrument Transformers, Inc.

GE Multilin Electronic Relay Burden

VA = VI. V= IR, So 0.2 = I*I*R.

.2/25 = .008 ohms

Page 34: Ieee Cts and Pts 6-10

37GE Multilin

Instrument Transformers, Inc.

100:5 C.T. Secondary Winding Resistance (DCR) = .062 ohm

Resistance of Cable from C.T. to Relay and back = .1 ohms

Resistance of Relay Coil = .02 ohms

Total Resistance = .182 ohms

If we have a fault of 2,000 amps and the C.T. ratio is 100:5 then the C.T. secondary current is 100 amps. Therefore we will produce a voltage of 100 amps x .182 ohms = 18.2 Volts. To prevent CT saturation, select a CT with a knee point above 18.2 Volts.

.062

.1

.02

Page 35: Ieee Cts and Pts 6-10

38GE Multilin

Instrument Transformers, Inc.

780-102 is a 1000 to 5 CT, Class C100

1000:5 C.T. Secondary Winding Resistance (DCR) = .32 ohm

Resistance of Cable from C.T. to Relay and back = .1 ohms

Resistance of Relay Coil = .008 ohms

Total Resistance = .428 ohms

If we have a fault of 20,000 amps and the C.T. ratio is 1000:5 then the C.T. secondary current is 100 amps. Therefore we will produce a voltage of 100 amps x .428 ohms = 42.8 Volts. To prevent CT saturation, select a CT with a knee point above 42.8 Volts.

What happens if the fault current is 40,000 amps?

.32

.1

.008

Page 36: Ieee Cts and Pts 6-10

39GE Multilin

Instrument Transformers, Inc.

Factors Influencing CT Accuracy Frequency

Current Ratio

Burden

“Low frequency” and “High accuracy” are not friends!!

“Low ratio” and “high accuracy” are not friends!!

“High burden” and “High Accuracy” are not friends!!

Page 37: Ieee Cts and Pts 6-10

40GE Multilin

Instrument Transformers, Inc.

CT Saturation

What is CT Saturation?

Page 38: Ieee Cts and Pts 6-10

41GE Multilin

Instrument Transformers, Inc.

Power Systems Relay Committee (PSRC) Saturation Calculator

Page 39: Ieee Cts and Pts 6-10

42GE Multilin

Instrument Transformers, Inc.

Factors Affecting Degree of Saturation and Time to Saturation

DC OffsetFault Magnitude (symmetrical current)•100 to 5 CT@20 times= 2000 amps, at 20,000 amps we have 200 times CT

CT Turns RatioSecondary BurdenCT AccuracyRemanence Flux • Can occur if current interrupted when core is saturated• If DC flows in windings during testing• Need a voltage above 60% of knee point to reduce the

remanence to less than 10% of saturation flux density.

Page 40: Ieee Cts and Pts 6-10

43GE Multilin

Instrument Transformers, Inc.

Tips for Avoiding CT SaturationUse higher ratio CTsUse separate set of high ratio CTs for high fault current trippingReduce secondary burden

Select low burden relays & metersDistribute single phase burdens among

phasesIncrease size of secondary leadsReduce length of secondary leads

Use “step down” auxiliary CTs

Page 41: Ieee Cts and Pts 6-10

44GE Multilin

Instrument Transformers, Inc.

Potential Transformers

Page 42: Ieee Cts and Pts 6-10

45GE Multilin

Instrument Transformers, Inc.

DefinitionsVoltage Transformer (VT)

An instrument transformer used to reflect a primary voltage into a secondary voltage through a magnetic medium. Always connected in parallel with primary conductor across a circuit load.

Secondary (measuring) voltage is usually 115 or 120 volts nominally. The secondary voltage level is selected for ease of measurement and safety.Control Power Transformer (CPT)

Designed to provide power for contractors, relays and devices with high inrush currents, Regulation is not as critical.

Page 43: Ieee Cts and Pts 6-10

46GE Multilin

Instrument Transformers, Inc.

Page 44: Ieee Cts and Pts 6-10

47GE Multilin

Instrument Transformers, Inc.

POTENTIAL TRANSFORMERSPOTENTIAL TRANSFORMERS

VVPP

VsVs

Relay

14,400/120 = 120/1

4200/120 = 35/1

2400/120 = 20/1

Page 45: Ieee Cts and Pts 6-10

48GE Multilin

Instrument Transformers, Inc.

IEEE VT Accuracy ClassMetering Accuracy Classes (% error)

0.3

0.6

1.2

0.15

Defined by IEEE C57.13

Applicable from 90% to 110% rated voltage

Defined by IEEE C57.13.6

Page 46: Ieee Cts and Pts 6-10

49GE Multilin

Instrument Transformers, Inc.

IEEE VT Accuracy Class

These standard burden designations have no significance at frequencies other than 60 Hz.

Burden VA PF

W 12.5 0.10X 25 0.70M 35 0.20Y 75 0.85Z 200 0.85

ZZ 400 0.85

Metering Accuracy

Class Burdens

Page 47: Ieee Cts and Pts 6-10

50GE Multilin

Instrument Transformers, Inc.

IEEE VT Accuracy ClassExpressed as:

Accuracy Class + Burden Code

0.3 W,X,Y0.6 Z

1.2 ZZ

These standard designations have no significance at frequencies other than 60 Hz.

Page 48: Ieee Cts and Pts 6-10

51GE Multilin

Instrument Transformers, Inc.

Page 49: Ieee Cts and Pts 6-10

52GE Multilin

Instrument Transformers, Inc.

VT Installation Guidelines Caution:

Rated voltage: Do not operate above 110%

Line to ground rated: Do not connect line to lineDo not use on ungrounded systems w/o consulting factory

Rated Frequency: Do not operate below rated frequency w/o consulting factory

Page 50: Ieee Cts and Pts 6-10

53GE Multilin

Instrument Transformers, Inc.

IEEE VT Groups VT

Group

No. of Bushin

g

Connection Method

Neutral Grounding

Notes

1 2 open Y-Y possible

Any Withstand 25% over rated voltage on an emergency basis

2 2 open Y-Y possible

Any Withstand 10% over rated voltage continuously. Primary rated for line to line voltage.

3 1 Y-Y-Y Any Outdoor, two secondary windings. Withstand 10% over rated voltage continuously.

4A 1 Y-Y Effectively Withstand 10% over rated voltage continuously & 25% on an emergency basis. For operation at 100% rated voltage.

4B 1 Y-YY-Broken Corner

Non-effectively

Withstand 10% overvoltage continuously. For operation at 58% rated voltage.

5 1 Y-Y Effectively Outdoor. Withstand 40% over rated voltage for 1 minute and 10% over rated voltage continuously

Page 51: Ieee Cts and Pts 6-10

54GE Multilin

Instrument Transformers, Inc.

VT Typical Connections

Open Delta Connection(2) Double Bushing VTs

Y – Y Connection(3) Single Bushing VTs

Page 52: Ieee Cts and Pts 6-10

60GE Multilin

Instrument Transformers, Inc.

Required Information for Specifying CTs & VTs

Page 53: Ieee Cts and Pts 6-10

61GE Multilin

Instrument Transformers, Inc.

Current Transformer (CT) RFQ Specification Environment: ___Indoor ___Outdoor

System Voltage (kV)0.6

0.723.65.07.28.712152425

34.534.5

Power Frequency (kV)4310192026283450407070

BIL (kV)10

4060607575110125125150200

Standard (Check one)IEEE __IEC __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEEE __IEEE __

CT Application: ___Metering ___Protection Dimensions: ___ Inches ___ mm

Max. Outside: L ______ x W ______ x D ______

CT Window: Round: ______ Diameter; Rectangular: L ______ x W ______ ; Primary Bar: _____

Current Ratio: _______ : 5 _______ : 1

Continued next slide

Page 54: Ieee Cts and Pts 6-10

62GE Multilin

Instrument Transformers, Inc.

Current Transformer (CT) RFQ Specification (Continued)Accuracy:

Indication Only: _____ %, _____VA (Skip metering & protection selections)Metering Class:

IEEE: ___0.3 ___0.6 ___1.2 ___2.4 ________OtherIEC: ___0.2 ___0.5 ___1.0 ________Other

Metering Burden:IEEE (Ohms): ___B0.1 ___B0.2 ___B0.5 ___B0.9 ___B1.8 ______OtherIEC (VA): ___2.5 ___5.0 ___10 ___15 ___30 ______Other

Protection Class: C______(IEEE) ___VA, ___P___(IEC)

Operating Frequency: ___60HZ ___50HZ

Rating Factor: ___1.0 ___1.33 ___1.5 ___2.0 ______Other

Secondary Connections: ___Terminals ___24 inch leads

Outer Insulation: ___Standard ___Cotton tape & varnish ___Polyester tapeInsulation Class: ___105 0C (Standard) _____Other

Other Special Requirements (dimensional constraints, mounting requirements, …etc):____________________________________________________________________________________________________________________________________________________________

Page 55: Ieee Cts and Pts 6-10

63GE Multilin

Instrument Transformers, Inc.

Voltage Transformer (VT) RFQ Specification Environment: ___Indoor ___Outdoor

System Voltage (kV)0.6

0.723.65.07.28.712152425

34.534.5

Power Frequency (kV)4310192026283450407070

BIL (kV)10

4060607575110125125150200

Standard (Check one)IEEE __IEC __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEEE __IEEE __

Continued next slide

Operating Frequency: ___60HZ ___50HZ

Accuracy:IEEE: ___W ___X ___M ___Y ___Z ___ZZ ________Other

(Enter 0.3, 0.6, 1.2, or leave blank)

IEC: ___10VA ___25VA ___50VA ___100VA ___200VA ___500VA______Other

(Enter 0.2, 0.5, 1.0, or leave blank)

Page 56: Ieee Cts and Pts 6-10

64GE Multilin

Instrument Transformers, Inc.

Voltage Transformer (VT) RFQ Specification (Continued)

Thermal Rating: _______VA (Optional)

Primary Voltage: ___1 bushing _________VAC - Phase to neutral

___2 bushing _________VAC - Phase to phase

Secondary Voltage: ___120V ___115V ___110V ___100V___120/3 ___115/3 ___110/3 ___100/3___Other _________________

Rated Voltage Factor (RVF) (1 bushing only): ___1.9 for 30s ___1.9 for 8 hours ___Other____________

Fuses:

___Primary ___Secondary ___None (600 – 720 V)

___Primary ___Live parts only ___Switchgear Style ___Unfused (2.5kV – 15kV)

Note integral fusing not available above 15kV

Page 57: Ieee Cts and Pts 6-10

65GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 1

CTs are intended to be proportional current devices. Very high voltages can result from open circuiting the secondary circuit of an energized CT. Even very small primary currents can cause damage… Consult the factory if you have questions.

Never open circuit a current transformer secondary while the primary is energized

Page 58: Ieee Cts and Pts 6-10

66GE Multilin

Instrument Transformers, Inc.

Never short circuit the secondary of an energized VT

Take Home Rule # 2

VTs are intended to be used as proportional voltagedevices. Damaging current will result from short circuiting the secondary circuit of an energized VT.

Page 59: Ieee Cts and Pts 6-10

67GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 3

Metering applications do not require a “C” class CT“C” class ratings are specified for protection purposes only. With some exceptions metering class CTs are typically smaller and less expensive.

Page 60: Ieee Cts and Pts 6-10

68GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 4

CT secondary leads must be added to the CT burdenElectronic relays usually represent very little burden to the CT secondary circuit. In many cases the major burden is caused by the CT secondary leads.

Page 61: Ieee Cts and Pts 6-10

69GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 5

Never use a 60 Hz rated VT on a 50 Hz System60 Hz VTs may saturate at lower frequencies and exceed temperature limitations. VT failure is likely…severe equipment damage is possible.

Page 62: Ieee Cts and Pts 6-10

70GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 6

Exercise caution when connecting grounded VTs to ungrounded systems Line to ground voltage on any VT may exceed the primary voltage rating during a fault condition… VT must be designed for application.

Page 63: Ieee Cts and Pts 6-10

71GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 7

It is common practice to apply 600 Volt CT to systems with higher voltages. This practice is done by passing fully insulated conductors through the Window.

Page 64: Ieee Cts and Pts 6-10

72GE Multilin

Instrument Transformers, Inc.

QUESTIONS?

Page 65: Ieee Cts and Pts 6-10

73GE Multilin

Instrument Transformers, Inc.

Page 66: Ieee Cts and Pts 6-10

74GE Multilin

Instrument Transformers, Inc.

Page 67: Ieee Cts and Pts 6-10

75GE Multilin

Instrument Transformers, Inc.

LV SwitchboardsLV Panelboards

5 Series

8SHT

19RT

Typical CT Models

Page 68: Ieee Cts and Pts 6-10

76GE Multilin

Instrument Transformers, Inc.

LV SwitchboardsLV Panelboards

Typical VT Models

460, 467, 475, 2VT460, 3VT460

Page 69: Ieee Cts and Pts 6-10

77GE Multilin

Instrument Transformers, Inc.

L.V. MCC’s

8SHT

19RT

5 Series

3P85

Typical CT Models

Page 70: Ieee Cts and Pts 6-10

79GE Multilin

Instrument Transformers, Inc.

L.V. Switchgear

Page 71: Ieee Cts and Pts 6-10

80GE Multilin

Instrument Transformers, Inc.

L.V. Switchgear Current TransformersGE 2000 amp frameModel 560 MeteringModel 561 Protection

Page 72: Ieee Cts and Pts 6-10

81GE Multilin

Instrument Transformers, Inc.

Current TransformersGE 4000 amp frameModel 562 MeteringModel 563 Protection

L.V. Switchgear

Page 73: Ieee Cts and Pts 6-10

82GE Multilin

Instrument Transformers, Inc.

L.V. Switchgear

No more room in the front? We can recommend a different model CT for the rear bus area.

Page 74: Ieee Cts and Pts 6-10

83GE Multilin

Instrument Transformers, Inc.

L.V. SwitchgearTypical 3 Phase VTInstallation

3VTL4603 Phase VT

Page 75: Ieee Cts and Pts 6-10

84GE Multilin

Instrument Transformers, Inc.

M.V. SwitchgearTypical Line Up

Where are the CTs, VTs, and CPTs?

Page 76: Ieee Cts and Pts 6-10

85GE Multilin

Instrument Transformers, Inc.

Current Transformers778 / 779 680 /780 Series Typical IEEE Metering & Protection

M.V. Switchgear

Page 77: Ieee Cts and Pts 6-10

86GE Multilin

Instrument Transformers, Inc.

M.V. SwitchgearCurrent TransformersMetering & Protection

Model 780, 778

Model 785

Page 78: Ieee Cts and Pts 6-10

87GE Multilin

Instrument Transformers, Inc.

M.V. Switchgear

Model 203 CTs mounted in rear bus compartment

Page 79: Ieee Cts and Pts 6-10

88GE Multilin

Instrument Transformers, Inc.

M.V. SwitchgearZero Sequence CTModel 593, 594

Is this better than a Residual Connection?

Page 80: Ieee Cts and Pts 6-10

89GE Multilin

Instrument Transformers, Inc.

M.V. SwitchgearTypical VT Rollout Drawer

Installed in enclosure

Withdrawn from enclosure

(2) PTG5’s in open deltaconfiguration

Page 81: Ieee Cts and Pts 6-10

90GE Multilin

Instrument Transformers, Inc.

M.V. SwitchgearTypical CPT Rollout Drawer

Installed in enclosure

Withdrawn from enclosure

CPT5 & 15 kV5 to 15 kVA

Page 82: Ieee Cts and Pts 6-10

91GE Multilin

Instrument Transformers, Inc.

MV MCC’s

Let’s open a door and see what’s inside

Page 83: Ieee Cts and Pts 6-10

92GE Multilin

Instrument Transformers, Inc.

MV MCC’s

Typical CT Models112113114115117

Page 84: Ieee Cts and Pts 6-10

93GE Multilin

Instrument Transformers, Inc.

Generators

Board Mounted Generator CT

Page 85: Ieee Cts and Pts 6-10

94GE Multilin

Instrument Transformers, Inc.

Station Class Circuit Breakers

Polyester Taped Bushing CT on Outdoor Circuit Breaker

Page 86: Ieee Cts and Pts 6-10

95GE Multilin

Instrument Transformers, Inc.

Station Class Circuit Breakers

Outdoor BO7 - Replaces BCT’s in shielded aluminum housing

Ground Shield

Page 87: Ieee Cts and Pts 6-10

96GE Multilin

Instrument Transformers, Inc.

Outdoor Type BO7 for Retrofit

Power TransformersSlip over current transformer for installation over exterior of outdoor bushing

Page 88: Ieee Cts and Pts 6-10

97GE Multilin

Instrument Transformers, Inc.

Power TransformersMetering applications for indoor instrument transformerson outdoor power transformers

Air terminal chamber

Indoor PT and Bar type CT

Page 89: Ieee Cts and Pts 6-10

98GE Multilin

Instrument Transformers, Inc.

Page 90: Ieee Cts and Pts 6-10

99GE Multilin

Instrument Transformers, Inc.