2
Installation manual MFM 2220 / 2240 / 2250, Art. No 603.291 Headquarters: Axetris AG, Switzerland Schwarzenbergstrasse 10 CH-6056 Kaegiswil Switzerland phone: +41 41 662 76 76 fax: +41 41 662 75 25 [email protected] www.axetris.com USA: Leister Technologies LLC 1275 Hamilton Parkway Itasca, IL 60143 USA phone: +1 630 760 1000 fax: +1 630 760 1001 [email protected] www.axetris.com Contact Swiss Made Quality. Axetris is an ISO 9001 certified enterprise. Specifications are subject to change without prior notice. China: Leister Technologies Ltd. Building 11, 155 Yuanke Road Xinzhuang Industry Park Shanghai 201 109 China phone: +86 21 6442 2398 fax: +86 21 6442 2338 [email protected] www.axetris.cn Japan: Leister Technologies KK Shinyokohama Bousei Bldg 1F 3-20-12, Shinyokohama, Kohoku-ku Yokohama 222-0033 / Japan phone: +81 45 477 36 37 fax: +81 45 477 36 38 [email protected] www.axetris.jp www.axetris.com 1 3 4 1 2 Particle Gas flow direction Installation vertical or horizontial Storage IN OUT external inlet filter (5-200 μm) is recommended Non dewing conditions only Specifications Installation manual MFM 2220 / MFM 2240 / MFM 2250 Mass Flow Meter module external inlet filter (5–200 μm) is recommended Non dewing conditions only Air, N2, O2, Ar, CO2, He, H2 corrosive poisonous Gases Type Max. tolerated flow MFM 2220-A < 1000 sccm MFM 2240-B < 2000 sccm MFM 2250-C < 10000 sccm Handling of ESD Sensitive Devices (ESD: Electrostatic Discharge) 1 MΩ Earth 90° < ESD > ACHTUNG Nur geschultes Personal darf die Verpackung öffnen Elektrostatisch gefährdete Bauelemente (EGB) ATTENTION Observe Precautions for Handling Elektrostatic Sensitive Devices Step 1: Assembly instruction (typical example only) 1x Dowel pin Ø 2m6 x 6 [mm] DIN 6325 2x O-Ring Normatec FKM Ød1 3.5 x Ød2 1.5 [mm] DIN 3771/ISO 3601/1 1x Screw M3 x 20 [mm] – ISO 14583 1x Module 1x Flow connection block 5 6 Dimensions and tolerances see data sheet Reverse to connect

IN OUT - LeisterTechnologies

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

1

11

1

11

1

11

Inst

alla

tion

man

ual M

FM 2

220

/ 224

0 / 2

250,

Art

. No

603.

291Headquarters:

Axetris AG, Switzerland Schwarzenbergstrasse 10CH-6056 KaegiswilSwitzerlandphone: +41 41 662 76 76fax: +41 41 662 75 [email protected]

USA:Leister Technologies LLC1275 Hamilton ParkwayItasca, IL 60143USAphone: +1 630 760 1000fax: +1 630 760 [email protected]

Contact

Swiss Made Quality. Axetris is an ISO 9001 certified enterprise. Specifications are subject to change without prior notice.

China:Leister Technologies Ltd.Building 11, 155 Yuanke RoadXinzhuang Industry ParkShanghai 201 109Chinaphone: +86 21 6442 2398fax: +86 21 6442 [email protected]

Japan:Leister Technologies KKShinyokohama Bousei Bldg 1F3-20-12, Shinyokohama, Kohoku-ku Yokohama 222-0033 / Japan phone: +81 45 477 36 37 fax: +81 45 477 36 38 [email protected]

www.axetris.com

13

4

1

2

Particle

Gas flow direction

Installation vertical or horizontialStorage

IN

OUT

external inlet filter (5-200 μm) is recommended

Non dewing conditions only

Specifications

Installation manual MFM 2220 / MFM 2240 / MFM 2250Mass Flow Meter module

external inlet filter (5–200 μm) is recommended

Non dewing conditions only

Air, N2, O2, Ar, CO2, He, H2

corrosivepoisonous Gases

Type Max. tolerated flowMFM 2220-A < 1000 sccmMFM 2240-B < 2000 sccmMFM 2250-C < 10000 sccm

Handling of ESD Sensitive Devices (ESD: Electrostatic Discharge)

1 MΩ

Earth

90°

< ESD >

ACHTUNGNur geschultes Personaldarf die Verpackung öffnen

Elektrostatisch gefährdeteBauelemente (EGB)

ATTENTIONObserve Precautions for Handling

Elektrostatic SensitiveDevices

1

11

1

1

1

1

1

1

11

1

1

1

1

1

Step 1: Assembly instruction (typical example only)

1xDowel pin Ø 2m6 x 6 [mm] DIN 6325

2xO-Ring Normatec FKM Ød1 3.5 x Ød2 1.5 [mm] DIN 3771/ISO 3601/1

1xScrew M3 x 20 [mm] – ISO 14583

1xModule

1xFlow connection block

5

6

Dimensions and tolerances see data sheet

Reverse toconnect

1

11

1

11

Step 3: Cable installation detail Step 2: Cable assembly instruction

1xKlick cable

19

10

7

8

> 2 kΩ < 100 nF

Analog load

R C

Pin 6

Pin 5

Pin Typ MFM 2240 RS 485 Half Duplex1 Power Supply + 24 Volt2 Power Supply GND3 Digital Non Inverting Input-Output / D+4 Digital Inverting Input-Output / D- 5 nc6 nc7 nc 8 nc

Pin Typ MFM 2250 RS 485 Full Duplex1 Power Supply + 24 Volt2 Power Supply GND3 Digital In Non Inverting Receiver Input / R+4 Digital In Inverting Receiver Input / R- 5 nc6 Digitalg Out Inverting Transmitter Output / T-7 Digitalg Out Non Inverting Transmitter Output / T+8 nc

Pin Typ MFM 2220 RS 232 EIA Level1 Power Supply + 24 Volt2 Power Supply GND3 Digital In RxD4 Digital Out TxD5 Analog GND6 Analog Out Flow value 7 nc 8 nc

nc = not connected

MFM 2220 / 2240 / 2250Connector type: Micromatch 8-pole

12

34

56

78

Reverse angle

11

12

Analog topology – Best practices

Recommendations:

1. Separate analog ground line from power supply ground line.

2. Separate power supply from the command signals.

3. Use power supply galvanically insulated from its power source to avoid ground loops.

For more information please visit: www.axetris.com

Notes

D

D

A

A

DA

Power Supply

Power GND

Flow value

Flow Set-point

Valve Override

Analog GND

AC line

MFx 3rd party host system

Galv. Insulated

AnalogI/O