Indoor Unit EKHVMYD-A
TABLE OF CONTENTS
EKHVMYD-A
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6 External connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
External Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Sound Power Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Hydraulic performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Static Pressure Drop Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
4/19
Indoor Unit EKHVMYD-A
11
Heating Daikin Altherma2
1 Features
Daikin Heating EKHVMYD- Indoor High temperature application: up to 80C without electric heater
Possible to choose between low temperature and high temperature
heat emitters
Cost effective alternative to a fossil fuel boiler
Low energy bills and low CO2 emissions
Heating and cooling in one system
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
5/19
3
12
Heating Daikin Altherma 3
Indoor Unit EKHVMYD-A
2 Specifications
2-1 Technical Specifications EKHVMYD50AAV1 EKHVMYD80AAV1
Casing Colour Metallic grey
Material Precoated sheet metal
Dimensions Unit Height mm 705
Width mm 600Depth mm 695
Packed unit Height mm 860
Width mm 680
Depth mm 800
Weight Unit kg 120
Packed unit kg 135
Packing Material EPSCardboard + MDFWood (pallet) + Metal
Weight kg 8.75
Pump Type DC motor
Nr of speeds Inverter controlled
Nominal ESP unit Heating kPa 83.7 58.8
Expansion vessel Heating Volume l 7
Cooling Volume l 2
Max. water pressure bar 3
Pre pressure bar 1
Sound pressure level Nom. dBA 40 (4) + 43 (5) 42 (4) + 43 (5)
Night quiet mode Level 1 dBA 38
Operation range Heating Ambient Min. C -15
Max. C 20
Water
side
Min. C 25
Max. C 80
Cooling Ambient Min. CDB 10
Max. CDB 43
Water
side
Min. C 5 (10)
Max. C 20 (10)Domestic hot water Ambient Min. CDB -15
Max. CDB 35
Water
side
Min. C 45
Max. C 75
Refrigerant Type R-134a
Charge kg 2
Refrigerant circuit Gas side diameter mm 12.7
Suction side diameter mm 15.9
Liquid side diameter mm 9.52
High pressure side Design pressure bar 38
Water circuit Piping connections diameter inch G 1" (female)
Piping inch 1"
Safety valve bar 3
Manometer Yes
Drain valve / fill valve Yes
Shut off valve Yes
Air purge valve Yes
Heating water
system
Water
volume
Min. l 20
Max. l 200
Refrigerant oil Type FVC50K
Charged volume l 0.75
Refrigerant side heat
exchanger
Type Plate heat exchanger
Quantity 1
Plates Quantity 66
Material AISI 316
Insulation material Felt type
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
6/19
Indoor Unit EKHVMYD-A
12
Heating Daikin Altherma4
2 Specifications
Water side Heat
exchanger
Water flow rate Min. l/min 5
Heating Nom. l/min 16.1 25.8
Cooling Nom. l/min 14.3 22.9
Heating Type Plate heat exchanger
Quantity 1
Plates Quantity 72
Material AISI 316
Water volume l 2.2
Insulation material Felt type
Cooling Type Plate heat exchanger
Quantity 1
Plates Quantity 42
Material AISI 316
Water volume l 0.82
Insulation material EPDM type
Water filter Diameter perforations mm 1
Material Brass
Cascade compressor Quantity 1
Motor Type Hermetically sealed swing compressor
Starting method Direct on line
Installation place Indoor
2-2 Electrical Specifications EKHVMYD50AAV1 EKHVMYD80AAV1
Power supply Name V1
Phase 1~
Frequency Hz 50
Voltage V 220-240
Voltage range Min. % -10
Max. % 6
Current Zmax Text 0.46
Minimum Ssc value kVa 1,459
Maximum running
current
Heating A 16.5
Recommended fuses A 20
Wiring connections For power supply Quantity 2G
Type of wires Select diameter and type according to national and local regulations
Benefit kWh rate
power supply
installations
Quantity 2G+2G
Type of wires Select diameter and type according to national and local regulations
For power supply
multi tenant
Quantity 2G
Remark Select diameter and type according to national and local regulations
For connection with
outdoor unit
Quantity 2
Remark F1 + F2
Power supply intake Both indoor and outdoor unit
Notes Cooling leaving water temperature depends on indoor unit operation status and other setpoints
Multi tenant Power supply Voltage V 24
Voltage
range
Min. % -20
Max. % 20
Current Maximum
running current
A 1
Recommended
fuses
A 3
2-1 Technical Specifications EKHVMYD50AAV1 EKHVMYD80AAV1
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
7/19
3
13
Heating Daikin Altherma 5
Indoor Unit EKHVMYD-A
3 Dimensional drawings
3 - 1 Dimensional Drawings
3TW59914-1A
EKHVMYD50-80A
left installation right installation
Screw fixation of top plate
(Both sides)
Min
.500
Min.600
Space required for switch boxremoval)
upwiring
Model A B C
EKHVMYD* 340 290 315
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
8/19
Indoor Unit EKHVMYD-A
13
Heating Daikin Altherma6
3 Dimensional drawings
3 - 1 Dimensional Drawings
3TW59914-1A
EKHVMYD50-80A 1 Suction/gas pipe connectionJ15.9Solder(R410A)2 Discharge/gas pipe connectionJ12.7Solder(R410A)3 Liquid pipe connectionJ9.5Solder(R410A)4 R1340 Service ports5/16flare(2x)5 Pressure gauge6 Blow off valve(2x)
7 Drain water circuit5/16SAE (2x)8 Air purge (2x)9 Shut-off valves (2x)
10 Water filter11 Water in connectionG 1(Female)12 Water out connectionG 1(Female)13 Control wiring intake(Knock out holeJ37)14 Power supply wiring intake (Knock out holeJ37)15 Knock-out holes for refrigerant piping and water piping16 Levelling feet17 Remote controller(delivered as accessory)
Installation location is outside the unit18 Suction/gas stop valveJ15.9Solder(R410A)19 Discharge/gas stop valveJ12.7Solder(R410A)20 Liquid stop valveJ9.5Solder(R410A)
DetailAScale1/3
If required(e.g. Wall fixation)
Pressure gauge can be removed from waterfilter, maximumdistance between waterfilter and pressure gauge +/- 600mm
left installation right installation
DetailA
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
9/19
3
14
Heating Daikin Altherma 7
Indoor Unit EKHVMYD-A
4 Piping diagrams
4 - 1 Piping Diagrams
EKHVMYD50-80AAV1
3TW59915-1A
R 1 1T S uc ti on t he rm is to r R 4 10 A
R10T L i qu i d t h erm is t or R410A Coo li n g
R9T L eav i ng wa ter c ool i ng t h erm is t or
R 7T L iq ui d t he rm is to r R 13 4a
R 6T D is ch ar ge t he rm is to r
R5T L eav i ng wa ter h eat i ng t h erm is t or
R 4 T R et ur ni ng w at er t he rm is to r
R 3T L iq ui d t he rm is to r R 41 0A
S 1P H H ig h p re ss ur e s wi tc h
B 1P L L ow p re ss ur e s ens or
B 1P H H ig h p re ss ur e s en so r
K 3E E le ct ro ni c e xp an si on v al ve
K 2E E le ct ro ni c e xp an si on v al ve
K 1E E le ct ro ni c e xp an si on v al ve
K3S Solenoid valve
K 2 S 3 w ay v al ve ( Co ol in g/ He at in g)
K1S 3 way valve
Q2L Th erm is t or p rot ect o r wa terp ip i ng
M1C Compressor
M1P DC inver tor pump
Refrigerant side
Shut offvalve
3 wayvalve
Outdoor unit
Field
piping
J
12.7
C
1220T-
0
Check valve
Accumulator
Filter
Plate heat exchangerR410A/R134a
Expansion vessel
Safety valve
G 1 Female
Water inlet
Option domestic hotwater tank
Shut offvalve
Field installation(delivered withOption domestic hot water tank)
Cooling heatexchanger
R410A
Blow off
Pressure gauge
Water outlet
G 1 Female
Filter
Air purge
Standard
Field
piping
J
9.5
2
C
1220T-
0
Filter
Filter
Filter
C he ck v al ve F la re c on ne ct io n Screw connection Flange connection Pinched pipe Spinned pipe
Heating
Cooling
Field
piping
J
15.9
C
1220T-
0
Muffler
Service
port5/16
Service
port5/16
Heating heatexchanger
R134a
Drain port
Drain port
Safety valve
Blow off
3 way valveAir purge
Expansionvessel
Flowswitch
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
10/19
Indoor Unit EKHVMYD-A
15
Heating Daikin Altherma8
5 Wiring diagrams
5 - 1 Wiring Diagrams
4TW59916-1A
Legend
* : included in option kit# : field supplied
A1P : Main PCB
A2P : User interface PCB A3P : control PCB A4P : Inverter PCB A5P : QA PCB A6P : Filter PCB A7P * : Digital I/O PCB A8P * : Demand PCB A9P : Multi tenant PCB A10P * : Thermostat PCB A11P * : Receiver PCBB1PH : High pressure sensorB1PL : Low pressure sensorC1-C3 : Filter capacitorC1-C3 (ASP) : PCB CapacitorDS1 (A*P) : DipswitchF1U : Fuse (T,3.2A, 250V)F1U (A1P,A3P,A9P) : Fuse (T, 3.15A, 250V)F1U (A6P) : Fuse (T, 6.3A, 250V)F1U-F2U (A7P) : Fuse (5A, 250V)F3U-F4U (A*P) : Fuse (T, 6.3A, 250V)HAP (A*P) : PCB LEDIPMI : Integrated power moduleK1A-K3A : Interface relayK1E-K3E : Electronic expansion valveK*R (A*P) : PCB RelayK1S * : 3 way valveK2S : 3 way valveK3S : 2 way valveK4S # : 2 way valveM1C : CompressorM1F : Switchbox cooling fanM1P-M2P : DC inverter pumpPC (A11P) * : Power circuitPHC1 : Optocoupler input circuitPS (A*P) : Switching power supplyQ1DI-Q2DI #: Earth leakage protectorQ2L : Thermal protector water pipingR1-R2 (A4P) : ResistanceR1L : Reactor
R1H (A10P) * : Humidity sensorR1T (A10P) * : Ambient sensorR2T * : Domestic hot water tank ThermistorR2T * : External sensor (floor or ambient)R3T : Liquid thermistor R410AR4T : Returning water thermistorR5T : Leaving water thermistor (heating)R6T : Discharge thermistorR7T : Liquid thermistor R134aR8T : Fin thermist orR9T : Leaving water thermistor (cooling)R10T : Liquid thermistor (cooling)R11T : Suction thermistor (cooling)RC (A*P) : Receiver circuitS1PH : High pressure switchS1S #: benefit kWh rate power supply contactS3S #: Input multiple setpointS4S #: Input multiple setpointSS1 (A1P) : Selector switch (emergency)
SS1 (A2P) : Selector switch (master slave)SS1 (A7P) * : Selector switchTC (A*P) : Transmitter circuitT1R-T2R (A*P) : Diode bridgeT3R : P ower moduleV1C-V8C : Ferrite core noise filterX1M-X3M : Terminal stripX*M (A*P)* : PCB terminal stripX1Y-X4Y : ConnectorZ1F-Z5F (A*P) : Noise filter
NOTES TO GO THROUGH BEFORE STARTING THE UNIT
X1M : Main terminalX2M : Field wiring terminal for high voltageX3M : Field wiring terminal for low voltage
C : Earth wiringF : Field supply
: Option
: Wiring depending on model
: Not mounted in switchbox
: PCB
X**/12.2 : Connection ** continues on page 12 column 2
: Several wiring possibilities
User installed:
*KHTS* = Domestic hot water tank*KRTW* = Room thermostat (Wired)*KRTR* = Room thermostat (Wireless)*KRTETS = External temperature sensor for *KRTR**KRUAHT = Remote user interface*KRP1HB* = Digital I/O PCB*KRP1AHT* = Demand PCB
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
11/19
3
15
Heating Daikin Altherma 9
Indoor Unit EKHVMYD-A
5 Wiring diagrams
5 - 1 Wiring Diagrams
4TW59916-1A
Power supply(Only for benefit kWh rate power supply installation)
EKHVMYD50-80
Power supply(Only for normal power supply installation)
**:Remove 2 wire bridges on X2M terminal positions 8-10 and 9-11.See page 6 for installation of the benefit KWh rate power supplycontact. (see installation manual)
Only for*KHVMYD*
150Hz 24V ACMulti tenant power supply
(Refer to manual for more details)
150Hz 220-240 VACNormal kWh rate power supply
150Hz 220-240 VACbenefit kWh rate power supply
contact150Hz 220-240 VAC
Power supply
150Hz 24V ACMulti tenant power supply
(Refer to manual for more details)
Only for*KHVMYD*Only for*KHVMYD*
Compressor circuit
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
12/19
Indoor Unit EKHVMYD-A
15
Heating Daikin Altherma10
5 Wiring diagrams
5 - 1 Wiring Diagrams
4TW59916-1A
Only for benefit kWh ratepower supply installation
EKHVMYD50-80A
Only for *KHVMYD*Only for *KHTS*
Only for *KHTS*
Only for *KRTW*
Only for *KRP1AHT*
Only for *KRTR* Only for *KRTETS
Only for *KRUAHT*
Transmission wiring:Indoor/outdoor unit wiring(Refer to manual for more details)
CONTROL CIRCUIT
User interface
Remote user interfaceMaximum load:
0.3 A - 250 VACMinimum load:20 mA - 5VDC
220-240 VACOutputMaximum load: 0.3 A
Unitheating/coolingon/offoutput
Alarm
output
DHW
mode
on/offoutput
Only for *KHVMYD*Only for *KHVMYD*
220-240VAC OutputMaximum load:0.3A
Coolingmode
on/offoutput
Only for *KHVMYD*
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
13/19
3
15
Heating Daikin Altherma 11
Indoor Unit EKHVMYD-A
5 Wiring diagrams
5 - 1 Wiring Diagrams
EKBUH-AA6V3
Part number Description Part number Description
A8P Demand PCB (Indoor unit option) S1L Flowswitch
E1H, E2H Backup heater elements Q1DI # Earth leakage protector
F1B, F2B Fuse backup heater (20A 400V) Q1L Thermal protector backup heater (manual reset)
F1U Fuse (5A T 250V) Q2L Thermal protector inlet water (automatic reset)
F1T Thermal fuse backup heater R1 Inline resistor for flowswitch
K1A Time relay (on-delay) X1M,X2M Terminal strip
K1M, K2M Contactor backup heater step X801M PCB terminal strip
K5M, K6M Contactor for backup heater (all pole disconnection)
*: optional #: field supplied
NOTES
: Main terminal
: Field wiring terminal
: Earth wiring: Wire number 15
: Field supply
: Several wiring possibilities
: Wiring depending on model
: Not mounted in switch box: Option
: PCB
4TW59726-1
Power supply Indoor unit
Switch box layout
Option demand PCB
Common
BUHste
p2(6kW)
BUHste
p1(3kW)
1N~230V 50Hz
1
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
14/19
Indoor Unit EKHVMYD-A
15
Heating Daikin Altherma12
5 Wiring diagrams
5 - 1 Wiring Diagrams
EKBUH-AA6W1
Part number Description Part number Description
A8P Demand PCB (Indoor unit option) K5M Contactor for backup heater (all pole disconnection)
E1H, E2H, E3H Backup heater elements S1L Flowswitch
F1B Fuse backup heater (20A 400V) Q1DI # Earth leakage protector
F1U Fuse (5A T 250V) Q1L Thermal protector backup heater (manual reset)
F1T Thermal fuse backup heater Q2L Thermal protector inlet water (automatic reset)
K1A Time relay (on-delay) R1 Inline resistor for flowswitch
K2A Auxilary relay X1M,X2M Terminal strip
K1M, K2M Contactor backup heater step X801M PCB terminal strip
*: optional #: field supplied
NOTES
: Main terminal
: Field wiring terminal
: Earth wiring
: Wire number 15
: Field supply
: Several wiring possibilities
: Wiring depending on model
: Not mounted in switch box: Option
: PCB
4TW59726-2
Power supply Indoor unit
Switch box layout
Option demand PCB
Common
BUHste
p2(6kW)
BUHste
p1(3kW)3N~400V 50Hz
1
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
15/19
3
16
Heating Daikin Altherma 13
Indoor Unit EKHVMYD-A
6 External connection diagrams
6 - 1 External Connection Diagrams
EKHVMYD
3TW59919-4A
NOTE
In case of signal cable or communication cable, keep minimum distance to power cables > 25mm
Please check unit wiring diagram for more details
Outdoor unit power supply (benefit kWh rate power supply is NOT allowed)
380V - 415V + earth
220V - 240V + earth
Possibility 1: Only for normal power supply installation
Possibility 1
Possibility 2
Possibility 2: Only for benefit kWh rate power supply installationBenefit kWh rate power supply:220V - 240V + earth
Normal kWh rate power supply:220V - 240V + earth
Benefit kWh rate power supply contact
R2T- Thermistorwater temperature
Coolingmodeon/offoutput
DHWmodeon/off output
Cooling/heatingmodeon/offoutput
R2TExternalsensor( floor
orambient)
Alarmoutput
Inputmultiplesetpoint1
Inputmultiplesetpoint2
K1S (WhenEKHTS* isinstalled) selectiondomestichotwater- heating
Indoor unit multi-tenant power supply:Ensure correct multi-tenant operation, if not installed, the outdoor unitwill stop and display an error when one or more tenants cut off theindoor unit power supply
Indoor unit power supply only for EKRP1HBAA
only for *KBUH*
only for EKRTW (wired roomthermostat)
only for EKRP1AHTA
only for EKRTR (wirelessroom thermostat) only for EKRTETS
Only for EKHVMYD*
Backup heater
Room thermostat
Only for EKHVMYD*
Only for EKHVMYD*
Only for EKHTS*
Only for EKRAUHT*
Field supply
Field supply
Optional parts
3 way valve
Domestic hotwater tank
Outdoor unit
Indoor unit 1
Indoor unit 2 Indoor unit n (2n8)
Standard parts
Optional parts
User interface User interface
5 core
3 core
3 core
3 core
2 core
2 core
2 core
2 core
2 core
Optional power supply:cooling/heating on/off output
Optional power supply:alarm output
Optional power supply:380V-415V or 220V-240V + earth
2 core
2 core
5 or 3 core
2 core (3m included)
2 core
2 core
3 core
2 core
2 core
2 core
2 core
2 core
2 core
1 core
1 core
1 core
1 core
2 core 2 core
2
core
2
cor
e
3 core
2 core
2 core
signal
signal
signal
signal
signal
signal
signal
signal
signal
communication
communication communication communication
communication
communication
X1M:L1-L2-L3-N-ear th
L-N-earth
L-N-earth
L1-L2-L3-earthorL-N-earth
*removewirebridges
Electrical connection diagram Daikin Altherma
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
16/19
Indoor Unit EKHVMYD-A
17
Heating Daikin Altherma14
7 Sound data
7 - 1 Sound Power Spectrum
3TW59917-2
EKHVMYD50-80A
Notes
- Measured according to ISO3744- Reference acoustic pressure 0dB = 10E-6W/m_- dBA=A-weighted sound power level
- Unit condition: Ta=7/6C - Heating setpoint 55/65C - Maximum compressor frequency
- If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and soundreflections. Choose the installation location carefully and do not install in a sound sensitive environment (e.g. living room, bedroom, . . .)
Sound power Lw per Octave band (dB) Total (dBA)
125 250 500 1000 2000 4000 8000 LwA
EKHVMYD50AAV1 38 49 49 47 41 41 39 54EKHVMYD80AAV1 39 50 51 45 45 43 41 55
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
17/19
3
17
Heating Daikin Altherma 15
Indoor Unit EKHVMYD-A
7 Sound data
7 - 2 Sound Pressure Spectrum
3TW59917-1
EKHVMYD50-80A
Notes
- The above data is valid in free field condition, because it is measured in a semi-anechoicroom. If sound is measured under actual installation conditions, the measured value will behigher due to environmental noise and sound reflections. Choose the installation locationcarefully and do not install in a sound sensitive environment (e.g. living room, bedroom, . . .)
- dB(A) = A-weighted sound pressure level (A-scale according to IEC)- EW = Entering water temperature - LW= Leaving water temperature- Reference acoustic pressure 0dB = 20Pa- Sound pressure level of low sound mode n2 and n3 is lower than n1- (*) Does not occur simultanuously on all sides.
Sound pressure [dBA]
[EW/LW 55/65C]FrontLeft / Right / Back (*)
EKHVMYD
50 80
4040
4241
[EW/LW 70/80C]FrontLeft / Right / Back (*)
4040
4342
[EW/LW 55/65C] - Low sound mode n1
Front
Right (*) 38 38
= Microphone
Front
Sound levels
Left
Back
Position of microphones
Right
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
18/19
Indoor Unit EKHVMYD-A
18
Heating Daikin Altherma16
8 Hydraulic performance
8 - 1 Static Pressure Drop Unit
3TW59919-5
1. The ESP curves are the maximum ESP curves for different DT types(pump rpm=4000for_T=5C;pump rpm=3600 for_T=10C)The pump of the indoor module is inverter controlled and controls to have a fixed_T between return and leaving water temperature.
2. In case of installing a domestic hot water tank there is an additional pressure drop over the three way valve (delivered as accessory with thetank)
ESP: External static pressureFlow: waterflow through the unit
Warning1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water
flowrange in the technical specifications.2. Water quality must be according to EN directive EC 98/83 EC.
Note:In case of stand alone tank, available ESP during DHW mode: to be confirmed
EKHVMYD50-80A
unit ESP without DHW 3way valve
ESP[kPa]
unit ESP including DHW 3way valve
max. ESP if_T = 10C(heating)
max. ESP if_T = 5C(heating)
Flow [l/min]
max. ESP if_T = 5C(cooling)
Unit ESP
8/3/2019 Indor Ekhvmyd-A en Tcm135-164553
19/19
10-721CD08/10CopyrightDaikin
esentpublicationsup
ersedesEEDEN09-721
inBelgiumb
yLanno
o
(www.lannooprint.be),acompanywhoseconcernfor
vironmontissetintheEMASandISO14001systems.
nsibleEditor:DaikinEuropeN.V.,
Zandvoordestraat300,
B-8400Oostende
Daikin products are distributed by:
The present leaflet is drawn up by way of information only and does not constitute an offer binding upon
Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge.
No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular
purpose of its content and the products and services presented therein. Specifications are subject to change
without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in
the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is
copyrighted by Daikin Europe N.V.
Daikins unique position as a manufacturer of air
conditioning equipment, compressors and refrigerants
has led to its close involvement in environmental issues.
For several years Daikin has had the intention to become
a leader in the provision of products that have limited
impact on the environment. This cha llenge demands the
eco design and development of a wide range of products
and an energy management system, resulting in energy
conservation and a reduction of waste.
Daikin Europe N.V. participates in the Eurovent
Certification Programme for Air Conditioners (AC),
Liquid Chilling Packages (LCP) and Fan Coil Units (FC);
the certified data of certified models are listed in the
Eurovent Directory. Multi units are Eurovent certified for
combinations up to 2 indoor units.