Indor Ekhvmyd-A en Tcm135-164553

Embed Size (px)

Citation preview

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    1/19

    E E D E N 1 0 - 7 2 1

    D a i k i n A l t h e r m a

    Heating

    Technical Data

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    2/19

    E E D E N 1 0 - 7 2 1

    D a i k i n A l t h e r m a

    Heating

    Technical Data

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    3/19 Heating Daikin Altherma 1

    Indoor Unit EKHVMYD-A

    TABLE OF CONTENTS

    EKHVMYD-A

    1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    3 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    4 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    5 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    6 External connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    External Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    7 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Sound Power Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    8 Hydraulic performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Static Pressure Drop Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    4/19

    Indoor Unit EKHVMYD-A

    11

    Heating Daikin Altherma2

    1 Features

    Daikin Heating EKHVMYD- Indoor High temperature application: up to 80C without electric heater

    Possible to choose between low temperature and high temperature

    heat emitters

    Cost effective alternative to a fossil fuel boiler

    Low energy bills and low CO2 emissions

    Heating and cooling in one system

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    5/19

    3

    12

    Heating Daikin Altherma 3

    Indoor Unit EKHVMYD-A

    2 Specifications

    2-1 Technical Specifications EKHVMYD50AAV1 EKHVMYD80AAV1

    Casing Colour Metallic grey

    Material Precoated sheet metal

    Dimensions Unit Height mm 705

    Width mm 600Depth mm 695

    Packed unit Height mm 860

    Width mm 680

    Depth mm 800

    Weight Unit kg 120

    Packed unit kg 135

    Packing Material EPSCardboard + MDFWood (pallet) + Metal

    Weight kg 8.75

    Pump Type DC motor

    Nr of speeds Inverter controlled

    Nominal ESP unit Heating kPa 83.7 58.8

    Expansion vessel Heating Volume l 7

    Cooling Volume l 2

    Max. water pressure bar 3

    Pre pressure bar 1

    Sound pressure level Nom. dBA 40 (4) + 43 (5) 42 (4) + 43 (5)

    Night quiet mode Level 1 dBA 38

    Operation range Heating Ambient Min. C -15

    Max. C 20

    Water

    side

    Min. C 25

    Max. C 80

    Cooling Ambient Min. CDB 10

    Max. CDB 43

    Water

    side

    Min. C 5 (10)

    Max. C 20 (10)Domestic hot water Ambient Min. CDB -15

    Max. CDB 35

    Water

    side

    Min. C 45

    Max. C 75

    Refrigerant Type R-134a

    Charge kg 2

    Refrigerant circuit Gas side diameter mm 12.7

    Suction side diameter mm 15.9

    Liquid side diameter mm 9.52

    High pressure side Design pressure bar 38

    Water circuit Piping connections diameter inch G 1" (female)

    Piping inch 1"

    Safety valve bar 3

    Manometer Yes

    Drain valve / fill valve Yes

    Shut off valve Yes

    Air purge valve Yes

    Heating water

    system

    Water

    volume

    Min. l 20

    Max. l 200

    Refrigerant oil Type FVC50K

    Charged volume l 0.75

    Refrigerant side heat

    exchanger

    Type Plate heat exchanger

    Quantity 1

    Plates Quantity 66

    Material AISI 316

    Insulation material Felt type

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    6/19

    Indoor Unit EKHVMYD-A

    12

    Heating Daikin Altherma4

    2 Specifications

    Water side Heat

    exchanger

    Water flow rate Min. l/min 5

    Heating Nom. l/min 16.1 25.8

    Cooling Nom. l/min 14.3 22.9

    Heating Type Plate heat exchanger

    Quantity 1

    Plates Quantity 72

    Material AISI 316

    Water volume l 2.2

    Insulation material Felt type

    Cooling Type Plate heat exchanger

    Quantity 1

    Plates Quantity 42

    Material AISI 316

    Water volume l 0.82

    Insulation material EPDM type

    Water filter Diameter perforations mm 1

    Material Brass

    Cascade compressor Quantity 1

    Motor Type Hermetically sealed swing compressor

    Starting method Direct on line

    Installation place Indoor

    2-2 Electrical Specifications EKHVMYD50AAV1 EKHVMYD80AAV1

    Power supply Name V1

    Phase 1~

    Frequency Hz 50

    Voltage V 220-240

    Voltage range Min. % -10

    Max. % 6

    Current Zmax Text 0.46

    Minimum Ssc value kVa 1,459

    Maximum running

    current

    Heating A 16.5

    Recommended fuses A 20

    Wiring connections For power supply Quantity 2G

    Type of wires Select diameter and type according to national and local regulations

    Benefit kWh rate

    power supply

    installations

    Quantity 2G+2G

    Type of wires Select diameter and type according to national and local regulations

    For power supply

    multi tenant

    Quantity 2G

    Remark Select diameter and type according to national and local regulations

    For connection with

    outdoor unit

    Quantity 2

    Remark F1 + F2

    Power supply intake Both indoor and outdoor unit

    Notes Cooling leaving water temperature depends on indoor unit operation status and other setpoints

    Multi tenant Power supply Voltage V 24

    Voltage

    range

    Min. % -20

    Max. % 20

    Current Maximum

    running current

    A 1

    Recommended

    fuses

    A 3

    2-1 Technical Specifications EKHVMYD50AAV1 EKHVMYD80AAV1

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    7/19

    3

    13

    Heating Daikin Altherma 5

    Indoor Unit EKHVMYD-A

    3 Dimensional drawings

    3 - 1 Dimensional Drawings

    3TW59914-1A

    EKHVMYD50-80A

    left installation right installation

    Screw fixation of top plate

    (Both sides)

    Min

    .500

    Min.600

    Space required for switch boxremoval)

    upwiring

    Model A B C

    EKHVMYD* 340 290 315

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    8/19

    Indoor Unit EKHVMYD-A

    13

    Heating Daikin Altherma6

    3 Dimensional drawings

    3 - 1 Dimensional Drawings

    3TW59914-1A

    EKHVMYD50-80A 1 Suction/gas pipe connectionJ15.9Solder(R410A)2 Discharge/gas pipe connectionJ12.7Solder(R410A)3 Liquid pipe connectionJ9.5Solder(R410A)4 R1340 Service ports5/16flare(2x)5 Pressure gauge6 Blow off valve(2x)

    7 Drain water circuit5/16SAE (2x)8 Air purge (2x)9 Shut-off valves (2x)

    10 Water filter11 Water in connectionG 1(Female)12 Water out connectionG 1(Female)13 Control wiring intake(Knock out holeJ37)14 Power supply wiring intake (Knock out holeJ37)15 Knock-out holes for refrigerant piping and water piping16 Levelling feet17 Remote controller(delivered as accessory)

    Installation location is outside the unit18 Suction/gas stop valveJ15.9Solder(R410A)19 Discharge/gas stop valveJ12.7Solder(R410A)20 Liquid stop valveJ9.5Solder(R410A)

    DetailAScale1/3

    If required(e.g. Wall fixation)

    Pressure gauge can be removed from waterfilter, maximumdistance between waterfilter and pressure gauge +/- 600mm

    left installation right installation

    DetailA

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    9/19

    3

    14

    Heating Daikin Altherma 7

    Indoor Unit EKHVMYD-A

    4 Piping diagrams

    4 - 1 Piping Diagrams

    EKHVMYD50-80AAV1

    3TW59915-1A

    R 1 1T S uc ti on t he rm is to r R 4 10 A

    R10T L i qu i d t h erm is t or R410A Coo li n g

    R9T L eav i ng wa ter c ool i ng t h erm is t or

    R 7T L iq ui d t he rm is to r R 13 4a

    R 6T D is ch ar ge t he rm is to r

    R5T L eav i ng wa ter h eat i ng t h erm is t or

    R 4 T R et ur ni ng w at er t he rm is to r

    R 3T L iq ui d t he rm is to r R 41 0A

    S 1P H H ig h p re ss ur e s wi tc h

    B 1P L L ow p re ss ur e s ens or

    B 1P H H ig h p re ss ur e s en so r

    K 3E E le ct ro ni c e xp an si on v al ve

    K 2E E le ct ro ni c e xp an si on v al ve

    K 1E E le ct ro ni c e xp an si on v al ve

    K3S Solenoid valve

    K 2 S 3 w ay v al ve ( Co ol in g/ He at in g)

    K1S 3 way valve

    Q2L Th erm is t or p rot ect o r wa terp ip i ng

    M1C Compressor

    M1P DC inver tor pump

    Refrigerant side

    Shut offvalve

    3 wayvalve

    Outdoor unit

    Field

    piping

    J

    12.7

    C

    1220T-

    0

    Check valve

    Accumulator

    Filter

    Plate heat exchangerR410A/R134a

    Expansion vessel

    Safety valve

    G 1 Female

    Water inlet

    Option domestic hotwater tank

    Shut offvalve

    Field installation(delivered withOption domestic hot water tank)

    Cooling heatexchanger

    R410A

    Blow off

    Pressure gauge

    Water outlet

    G 1 Female

    Filter

    Air purge

    Standard

    Field

    piping

    J

    9.5

    2

    C

    1220T-

    0

    Filter

    Filter

    Filter

    C he ck v al ve F la re c on ne ct io n Screw connection Flange connection Pinched pipe Spinned pipe

    Heating

    Cooling

    Field

    piping

    J

    15.9

    C

    1220T-

    0

    Muffler

    Service

    port5/16

    Service

    port5/16

    Heating heatexchanger

    R134a

    Drain port

    Drain port

    Safety valve

    Blow off

    3 way valveAir purge

    Expansionvessel

    Flowswitch

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    10/19

    Indoor Unit EKHVMYD-A

    15

    Heating Daikin Altherma8

    5 Wiring diagrams

    5 - 1 Wiring Diagrams

    4TW59916-1A

    Legend

    * : included in option kit# : field supplied

    A1P : Main PCB

    A2P : User interface PCB A3P : control PCB A4P : Inverter PCB A5P : QA PCB A6P : Filter PCB A7P * : Digital I/O PCB A8P * : Demand PCB A9P : Multi tenant PCB A10P * : Thermostat PCB A11P * : Receiver PCBB1PH : High pressure sensorB1PL : Low pressure sensorC1-C3 : Filter capacitorC1-C3 (ASP) : PCB CapacitorDS1 (A*P) : DipswitchF1U : Fuse (T,3.2A, 250V)F1U (A1P,A3P,A9P) : Fuse (T, 3.15A, 250V)F1U (A6P) : Fuse (T, 6.3A, 250V)F1U-F2U (A7P) : Fuse (5A, 250V)F3U-F4U (A*P) : Fuse (T, 6.3A, 250V)HAP (A*P) : PCB LEDIPMI : Integrated power moduleK1A-K3A : Interface relayK1E-K3E : Electronic expansion valveK*R (A*P) : PCB RelayK1S * : 3 way valveK2S : 3 way valveK3S : 2 way valveK4S # : 2 way valveM1C : CompressorM1F : Switchbox cooling fanM1P-M2P : DC inverter pumpPC (A11P) * : Power circuitPHC1 : Optocoupler input circuitPS (A*P) : Switching power supplyQ1DI-Q2DI #: Earth leakage protectorQ2L : Thermal protector water pipingR1-R2 (A4P) : ResistanceR1L : Reactor

    R1H (A10P) * : Humidity sensorR1T (A10P) * : Ambient sensorR2T * : Domestic hot water tank ThermistorR2T * : External sensor (floor or ambient)R3T : Liquid thermistor R410AR4T : Returning water thermistorR5T : Leaving water thermistor (heating)R6T : Discharge thermistorR7T : Liquid thermistor R134aR8T : Fin thermist orR9T : Leaving water thermistor (cooling)R10T : Liquid thermistor (cooling)R11T : Suction thermistor (cooling)RC (A*P) : Receiver circuitS1PH : High pressure switchS1S #: benefit kWh rate power supply contactS3S #: Input multiple setpointS4S #: Input multiple setpointSS1 (A1P) : Selector switch (emergency)

    SS1 (A2P) : Selector switch (master slave)SS1 (A7P) * : Selector switchTC (A*P) : Transmitter circuitT1R-T2R (A*P) : Diode bridgeT3R : P ower moduleV1C-V8C : Ferrite core noise filterX1M-X3M : Terminal stripX*M (A*P)* : PCB terminal stripX1Y-X4Y : ConnectorZ1F-Z5F (A*P) : Noise filter

    NOTES TO GO THROUGH BEFORE STARTING THE UNIT

    X1M : Main terminalX2M : Field wiring terminal for high voltageX3M : Field wiring terminal for low voltage

    C : Earth wiringF : Field supply

    : Option

    : Wiring depending on model

    : Not mounted in switchbox

    : PCB

    X**/12.2 : Connection ** continues on page 12 column 2

    : Several wiring possibilities

    User installed:

    *KHTS* = Domestic hot water tank*KRTW* = Room thermostat (Wired)*KRTR* = Room thermostat (Wireless)*KRTETS = External temperature sensor for *KRTR**KRUAHT = Remote user interface*KRP1HB* = Digital I/O PCB*KRP1AHT* = Demand PCB

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    11/19

    3

    15

    Heating Daikin Altherma 9

    Indoor Unit EKHVMYD-A

    5 Wiring diagrams

    5 - 1 Wiring Diagrams

    4TW59916-1A

    Power supply(Only for benefit kWh rate power supply installation)

    EKHVMYD50-80

    Power supply(Only for normal power supply installation)

    **:Remove 2 wire bridges on X2M terminal positions 8-10 and 9-11.See page 6 for installation of the benefit KWh rate power supplycontact. (see installation manual)

    Only for*KHVMYD*

    150Hz 24V ACMulti tenant power supply

    (Refer to manual for more details)

    150Hz 220-240 VACNormal kWh rate power supply

    150Hz 220-240 VACbenefit kWh rate power supply

    contact150Hz 220-240 VAC

    Power supply

    150Hz 24V ACMulti tenant power supply

    (Refer to manual for more details)

    Only for*KHVMYD*Only for*KHVMYD*

    Compressor circuit

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    12/19

    Indoor Unit EKHVMYD-A

    15

    Heating Daikin Altherma10

    5 Wiring diagrams

    5 - 1 Wiring Diagrams

    4TW59916-1A

    Only for benefit kWh ratepower supply installation

    EKHVMYD50-80A

    Only for *KHVMYD*Only for *KHTS*

    Only for *KHTS*

    Only for *KRTW*

    Only for *KRP1AHT*

    Only for *KRTR* Only for *KRTETS

    Only for *KRUAHT*

    Transmission wiring:Indoor/outdoor unit wiring(Refer to manual for more details)

    CONTROL CIRCUIT

    User interface

    Remote user interfaceMaximum load:

    0.3 A - 250 VACMinimum load:20 mA - 5VDC

    220-240 VACOutputMaximum load: 0.3 A

    Unitheating/coolingon/offoutput

    Alarm

    output

    DHW

    mode

    on/offoutput

    Only for *KHVMYD*Only for *KHVMYD*

    220-240VAC OutputMaximum load:0.3A

    Coolingmode

    on/offoutput

    Only for *KHVMYD*

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    13/19

    3

    15

    Heating Daikin Altherma 11

    Indoor Unit EKHVMYD-A

    5 Wiring diagrams

    5 - 1 Wiring Diagrams

    EKBUH-AA6V3

    Part number Description Part number Description

    A8P Demand PCB (Indoor unit option) S1L Flowswitch

    E1H, E2H Backup heater elements Q1DI # Earth leakage protector

    F1B, F2B Fuse backup heater (20A 400V) Q1L Thermal protector backup heater (manual reset)

    F1U Fuse (5A T 250V) Q2L Thermal protector inlet water (automatic reset)

    F1T Thermal fuse backup heater R1 Inline resistor for flowswitch

    K1A Time relay (on-delay) X1M,X2M Terminal strip

    K1M, K2M Contactor backup heater step X801M PCB terminal strip

    K5M, K6M Contactor for backup heater (all pole disconnection)

    *: optional #: field supplied

    NOTES

    : Main terminal

    : Field wiring terminal

    : Earth wiring: Wire number 15

    : Field supply

    : Several wiring possibilities

    : Wiring depending on model

    : Not mounted in switch box: Option

    : PCB

    4TW59726-1

    Power supply Indoor unit

    Switch box layout

    Option demand PCB

    Common

    BUHste

    p2(6kW)

    BUHste

    p1(3kW)

    1N~230V 50Hz

    1

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    14/19

    Indoor Unit EKHVMYD-A

    15

    Heating Daikin Altherma12

    5 Wiring diagrams

    5 - 1 Wiring Diagrams

    EKBUH-AA6W1

    Part number Description Part number Description

    A8P Demand PCB (Indoor unit option) K5M Contactor for backup heater (all pole disconnection)

    E1H, E2H, E3H Backup heater elements S1L Flowswitch

    F1B Fuse backup heater (20A 400V) Q1DI # Earth leakage protector

    F1U Fuse (5A T 250V) Q1L Thermal protector backup heater (manual reset)

    F1T Thermal fuse backup heater Q2L Thermal protector inlet water (automatic reset)

    K1A Time relay (on-delay) R1 Inline resistor for flowswitch

    K2A Auxilary relay X1M,X2M Terminal strip

    K1M, K2M Contactor backup heater step X801M PCB terminal strip

    *: optional #: field supplied

    NOTES

    : Main terminal

    : Field wiring terminal

    : Earth wiring

    : Wire number 15

    : Field supply

    : Several wiring possibilities

    : Wiring depending on model

    : Not mounted in switch box: Option

    : PCB

    4TW59726-2

    Power supply Indoor unit

    Switch box layout

    Option demand PCB

    Common

    BUHste

    p2(6kW)

    BUHste

    p1(3kW)3N~400V 50Hz

    1

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    15/19

    3

    16

    Heating Daikin Altherma 13

    Indoor Unit EKHVMYD-A

    6 External connection diagrams

    6 - 1 External Connection Diagrams

    EKHVMYD

    3TW59919-4A

    NOTE

    In case of signal cable or communication cable, keep minimum distance to power cables > 25mm

    Please check unit wiring diagram for more details

    Outdoor unit power supply (benefit kWh rate power supply is NOT allowed)

    380V - 415V + earth

    220V - 240V + earth

    Possibility 1: Only for normal power supply installation

    Possibility 1

    Possibility 2

    Possibility 2: Only for benefit kWh rate power supply installationBenefit kWh rate power supply:220V - 240V + earth

    Normal kWh rate power supply:220V - 240V + earth

    Benefit kWh rate power supply contact

    R2T- Thermistorwater temperature

    Coolingmodeon/offoutput

    DHWmodeon/off output

    Cooling/heatingmodeon/offoutput

    R2TExternalsensor( floor

    orambient)

    Alarmoutput

    Inputmultiplesetpoint1

    Inputmultiplesetpoint2

    K1S (WhenEKHTS* isinstalled) selectiondomestichotwater- heating

    Indoor unit multi-tenant power supply:Ensure correct multi-tenant operation, if not installed, the outdoor unitwill stop and display an error when one or more tenants cut off theindoor unit power supply

    Indoor unit power supply only for EKRP1HBAA

    only for *KBUH*

    only for EKRTW (wired roomthermostat)

    only for EKRP1AHTA

    only for EKRTR (wirelessroom thermostat) only for EKRTETS

    Only for EKHVMYD*

    Backup heater

    Room thermostat

    Only for EKHVMYD*

    Only for EKHVMYD*

    Only for EKHTS*

    Only for EKRAUHT*

    Field supply

    Field supply

    Optional parts

    3 way valve

    Domestic hotwater tank

    Outdoor unit

    Indoor unit 1

    Indoor unit 2 Indoor unit n (2n8)

    Standard parts

    Optional parts

    User interface User interface

    5 core

    3 core

    3 core

    3 core

    2 core

    2 core

    2 core

    2 core

    2 core

    Optional power supply:cooling/heating on/off output

    Optional power supply:alarm output

    Optional power supply:380V-415V or 220V-240V + earth

    2 core

    2 core

    5 or 3 core

    2 core (3m included)

    2 core

    2 core

    3 core

    2 core

    2 core

    2 core

    2 core

    2 core

    2 core

    1 core

    1 core

    1 core

    1 core

    2 core 2 core

    2

    core

    2

    cor

    e

    3 core

    2 core

    2 core

    signal

    signal

    signal

    signal

    signal

    signal

    signal

    signal

    signal

    communication

    communication communication communication

    communication

    communication

    X1M:L1-L2-L3-N-ear th

    L-N-earth

    L-N-earth

    L1-L2-L3-earthorL-N-earth

    *removewirebridges

    Electrical connection diagram Daikin Altherma

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    16/19

    Indoor Unit EKHVMYD-A

    17

    Heating Daikin Altherma14

    7 Sound data

    7 - 1 Sound Power Spectrum

    3TW59917-2

    EKHVMYD50-80A

    Notes

    - Measured according to ISO3744- Reference acoustic pressure 0dB = 10E-6W/m_- dBA=A-weighted sound power level

    - Unit condition: Ta=7/6C - Heating setpoint 55/65C - Maximum compressor frequency

    - If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and soundreflections. Choose the installation location carefully and do not install in a sound sensitive environment (e.g. living room, bedroom, . . .)

    Sound power Lw per Octave band (dB) Total (dBA)

    125 250 500 1000 2000 4000 8000 LwA

    EKHVMYD50AAV1 38 49 49 47 41 41 39 54EKHVMYD80AAV1 39 50 51 45 45 43 41 55

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    17/19

    3

    17

    Heating Daikin Altherma 15

    Indoor Unit EKHVMYD-A

    7 Sound data

    7 - 2 Sound Pressure Spectrum

    3TW59917-1

    EKHVMYD50-80A

    Notes

    - The above data is valid in free field condition, because it is measured in a semi-anechoicroom. If sound is measured under actual installation conditions, the measured value will behigher due to environmental noise and sound reflections. Choose the installation locationcarefully and do not install in a sound sensitive environment (e.g. living room, bedroom, . . .)

    - dB(A) = A-weighted sound pressure level (A-scale according to IEC)- EW = Entering water temperature - LW= Leaving water temperature- Reference acoustic pressure 0dB = 20Pa- Sound pressure level of low sound mode n2 and n3 is lower than n1- (*) Does not occur simultanuously on all sides.

    Sound pressure [dBA]

    [EW/LW 55/65C]FrontLeft / Right / Back (*)

    EKHVMYD

    50 80

    4040

    4241

    [EW/LW 70/80C]FrontLeft / Right / Back (*)

    4040

    4342

    [EW/LW 55/65C] - Low sound mode n1

    Front

    Right (*) 38 38

    = Microphone

    Front

    Sound levels

    Left

    Back

    Position of microphones

    Right

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    18/19

    Indoor Unit EKHVMYD-A

    18

    Heating Daikin Altherma16

    8 Hydraulic performance

    8 - 1 Static Pressure Drop Unit

    3TW59919-5

    1. The ESP curves are the maximum ESP curves for different DT types(pump rpm=4000for_T=5C;pump rpm=3600 for_T=10C)The pump of the indoor module is inverter controlled and controls to have a fixed_T between return and leaving water temperature.

    2. In case of installing a domestic hot water tank there is an additional pressure drop over the three way valve (delivered as accessory with thetank)

    ESP: External static pressureFlow: waterflow through the unit

    Warning1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water

    flowrange in the technical specifications.2. Water quality must be according to EN directive EC 98/83 EC.

    Note:In case of stand alone tank, available ESP during DHW mode: to be confirmed

    EKHVMYD50-80A

    unit ESP without DHW 3way valve

    ESP[kPa]

    unit ESP including DHW 3way valve

    max. ESP if_T = 10C(heating)

    max. ESP if_T = 5C(heating)

    Flow [l/min]

    max. ESP if_T = 5C(cooling)

    Unit ESP

  • 8/3/2019 Indor Ekhvmyd-A en Tcm135-164553

    19/19

    10-721CD08/10CopyrightDaikin

    esentpublicationsup

    ersedesEEDEN09-721

    inBelgiumb

    yLanno

    o

    (www.lannooprint.be),acompanywhoseconcernfor

    vironmontissetintheEMASandISO14001systems.

    nsibleEditor:DaikinEuropeN.V.,

    Zandvoordestraat300,

    B-8400Oostende

    Daikin products are distributed by:

    The present leaflet is drawn up by way of information only and does not constitute an offer binding upon

    Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge.

    No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular

    purpose of its content and the products and services presented therein. Specifications are subject to change

    without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in

    the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is

    copyrighted by Daikin Europe N.V.

    Daikins unique position as a manufacturer of air

    conditioning equipment, compressors and refrigerants

    has led to its close involvement in environmental issues.

    For several years Daikin has had the intention to become

    a leader in the provision of products that have limited

    impact on the environment. This cha llenge demands the

    eco design and development of a wide range of products

    and an energy management system, resulting in energy

    conservation and a reduction of waste.

    Daikin Europe N.V. participates in the Eurovent

    Certification Programme for Air Conditioners (AC),

    Liquid Chilling Packages (LCP) and Fan Coil Units (FC);

    the certified data of certified models are listed in the

    Eurovent Directory. Multi units are Eurovent certified for

    combinations up to 2 indoor units.