Inspection Checklist SMDBs & MDBs
Sr.No.
Description Yes
No
N.A
Comments
Statutory Inspection and Test for o! "olta#e $."% Installation."isual Inspection
'orkin# Space & (acilitiesa. Adequacy working space and safe access
provided for switch room and /or electrical
facilities.
b. Entrance /exit to switch room and/or
electrical facilities are free of obstruction.c. Suitable locking facilities provided for
switch room and /or electrical facilities.d. Suitable lighting provision provided for
switch room and /or electrical facilities.e. Suitable ventilation provision provided for
switch room and /or electrical facilities.f. Suitable tools for withdrawal of fuses at
fuse board provided.g. A warning notice A!"E# $ E%E&'#(&(')*
+!A+',-#(SE E!'#) #-,(('E0 and
provided at every entrance of switch room.h. 1ire barriers and other measures for
protection against thermal e2ects areproperly installed.
i. anger notices* warning notices* schematic
diagrams* instructions and similar
information are correctly and adequately
provided.3. 4arning notices for substations and switch
roomsk. 4arning notices for earthing and main
bondingl. All switchgears* distribution boards and
electrical equipment properly labeled.m. (nspect cabinets for signs of rust* corrosion*
or deteriorating paint.) S!itch*oards+ Main S!itch and Circuit Breaker
a. An up5to5date notice of periodic inspection
and testing provided at point of supply 6i.e.
a switchboard* a circuit breaker or a
7/24/2019 Inspection Checklist for SMDBs & MDBs
2/5
Inspection Checklist SMDBs & MDBs
Sr.
No.
Description Ye
s
N
o
N.
A
Comments
distribution board7 of the installation.b. 8isually check the Switch oard* cover*
cabinet* conduits* raceways* and
conductors for proper grounding and
bonding.c. &ircuits* fuses* switches* terminals* etc. are
provided with a legible and durable
identi9cation label.d. (nspect the Switch board for overall general
condition and for physical damage. &heck
for broken studs and loose or damaged
wires* connectors* terminations* etc.!o visible damage to impair safety.
e. 4ork done properly recorded in logbook
f. An up5to5date schematic diagram displayed
g. All accessible live parts screened with
insulating plate or earthed metal.h. All exposed conductive parts e2ectively
earthedi. Earthing system e2ectively connected
3. Earth wire has been installed for hinged
doorsk. 'he A& ratings are in accordance with the
approved working drawings.
l. 4arning notice displayed at main bonding
connections.m. All protective devices are functioned
properly and correctly set.n. Suitable interlock scheme provided to
prevent parallel operation of two or more
sources of supply and :5pole incoming and
interconnecting circuit breakers provided
for supply to be taken from more than one
source and is interconnected.o. 'he breaking capacity of all circuit breakers
/interconnection devices is able to
withstand the prospective fault current.
7/24/2019 Inspection Checklist for SMDBs & MDBs
3/5
Inspection Checklist SMDBs & MDBs
Sr.
No.
Description Ye
s
N
o
N.
A
Comments
p. rotective relays have been correctly setand over current protective devices suitably
set for all circuits.q. rotective type current transformers are
used for protective relays.r. A means of isolation provided for every
circuit.
s. -peration of circuit breakers and mainswitches checked.
t. (ndication checked.
u. !o undersi;ed conductor used between themain bus bar and fuse/
7/24/2019 Inspection Checklist for SMDBs & MDBs
4/5
Inspection Checklist SMDBs & MDBs
Sr.
No.
Description Ye
s
N
o
N.
A
Comments
b. A notice of periodic testing provided at ornear the main distribution boardincorporating a residual current device.
c. All accessible live parts screened with
insulating plate or earthed metal.d. Earthing system e2ectively connected
e. Earth wire has been installed for hinged
doorsf. istribution boards securely mounted on
suitable supports.
g. A suitable switch provided to control eachdistribution board.
h. hase barriers for =5phase distributionboard provided.
i. (nspect the istribution board for overall
general condition and for physical damage.
&heck for broken studs and loose or
damaged wires* connectors* terminations*
etc.
!o visible damage to impair safety.
3. 'he breaking capacity of
7/24/2019 Inspection Checklist for SMDBs & MDBs
5/5
Inspection Checklist SMDBs & MDBs