Upload
duongtuyen
View
230
Download
2
Embed Size (px)
Citation preview
AC100/200 AND ACM100 SERIES DYNAMIC BRAKING OPTION (FOR USE WITH EXTERNAL RESISTORS)
INSTALLATION AND OPERATION INSTRUCTIONSManual Number: 250-0308r1
The AC200 Series Dynamic Braking option can be used with all AC100/200 & ACM100 models.
PROGRAMMING THE SC SERIES DRIVE FOR DYNAMIC BRAKING
AC100 Series: Set Parameter 06 (TB-14 OUTPUT) to DB BRAKE (11).AC200 Series: Set Parameter 09 (TB-31 OUTPUT) to DYNAMIC BRAKING (04).
ACM100 Series: Set Parameter 12 (TB-13E FUNCTION) to DYNAMIC BRAKING (20).
WIRING THE DB MODULE TO THE AC100/200 & ACM100 SERIES DRIVE
The diagrams below illustrate how the DB module is wired to either the AC100/200 & ACM100 drive.
NOTE 1: External resistors are required when using Dynamic Braking modules 840-117, 840-118, and 840-119. Externalresistor assemblies are available from Minarik (refer to the next page for resistor information).
NOTE 2: Use 18 gauge wire for control connections. Tighten terminals to a torque of 2lb-in (0.2Nm).
NOTE 3: Use minimum 14 gauge wire for connections B+, B-, R+, and R-. Tighten terminals to a torque of 4.5lb-in (0.5Nm). The B+ and B- wires MUST be twisted together and must be less than 12 inches long. Twisting the R+ and R-wires together is also recommended.
Variable Speed AC Motor Drives250-0308r1 1 of 2
Minarik Drives � 14300 De La Tour Drive � South Beloit, IL 61080 � Ph: (800)MINARIK � Fax: (800) 624-6960 � www.minarikdrives.com
WARNING! AC100 control terminals are hot to ground! Do not touch!�
Warning
DO NOT use the Dynamic Braking Module with AC200 drives of Parameter Version 305 and lower! The Dynamic Brakingmodule may operate with some AC200 drives prior to parameter version 306, but these drives do not provide the necessarythermal protection for the Dynamic Braking module.
�
Warning
Incorrect wiring of the B+ and B- terminals will result in equipment damage! The B+ terminal on the DB module must beconnected to the B+ terminal on the AC100/200 or ACM100 drive, and the B- terminal on the DB module must be connected tothe B- terminal on the AC100/200 or ACM100 drive.
�
AC100/200 AND ACM100 SERIES DYNAMIC BRAKING OPTION (FOR USE WITH EXTERNAL RESISTORS)
INSTALLATION AND OPERATION INSTRUCTIONSManual Number: 250-0308r1
The AC200 Series Dynamic Braking option can be used with all AC100/200 & ACM100 models.
PROGRAMMING THE SC SERIES DRIVE FOR DYNAMIC BRAKING
AC100 Series: Set Parameter 06 (TB-14 OUTPUT) to DB BRAKE (11).AC200 Series: Set Parameter 09 (TB-31 OUTPUT) to DYNAMIC BRAKING (04).
ACM100 Series: Set Parameter 12 (TB-13E FUNCTION) to DYNAMIC BRAKING (20).
WIRING THE DB MODULE TO THE AC100/200 & ACM100 SERIES DRIVE
The diagrams below illustrate how the DB module is wired to either the AC100/200 & ACM100 drive.
NOTE 1: External resistors are required when using Dynamic Braking modules 840-117, 840-118, and 840-119. Externalresistor assemblies are available from Minarik (refer to the next page for resistor information).
NOTE 2: Use 18 gauge wire for control connections. Tighten terminals to a torque of 2lb-in (0.2Nm).
NOTE 3: Use minimum 14 gauge wire for connections B+, B-, R+, and R-. Tighten terminals to a torque of 4.5lb-in (0.5Nm). The B+ and B- wires MUST be twisted together and must be less than 12 inches long. Twisting the R+ and R-wires together is also recommended.
Variable Speed AC Motor Drives250-0308r1 1 of 2
Minarik Drives � 14300 De La Tour Drive � South Beloit, IL 61080 � Ph: (800)MINARIK � Fax: (800) 624-6960 � www.minarikdrives.com
WARNING! AC100 control terminals are hot to ground! Do not touch!�
Warning
DO NOT use the Dynamic Braking Module with AC200 drives of Parameter Version 305 and lower! The Dynamic Brakingmodule may operate with some AC200 drives prior to parameter version 306, but these drives do not provide the necessarythermal protection for the Dynamic Braking module.
�
Warning
Incorrect wiring of the B+ and B- terminals will result in equipment damage! The B+ terminal on the DB module must beconnected to the B+ terminal on the AC100/200 or ACM100 drive, and the B- terminal on the DB module must be connected tothe B- terminal on the AC100/200 or ACM100 drive.
�
AC100/200 AND ACM100 SERIES DYNAMIC BRAKING OPTION (FOR USE WITH EXTERNAL RESISTORS)
INSTALLATION AND OPERATION INSTRUCTIONSManual Number: 250-0308r1
The AC200 Series Dynamic Braking option can be used with all AC100/200 & ACM100 models.
PROGRAMMING THE SC SERIES DRIVE FOR DYNAMIC BRAKING
AC100 Series: Set Parameter 06 (TB-14 OUTPUT) to DB BRAKE (11).AC200 Series: Set Parameter 09 (TB-31 OUTPUT) to DYNAMIC BRAKING (04).
ACM100 Series: Set Parameter 12 (TB-13E FUNCTION) to DYNAMIC BRAKING (20).
WIRING THE DB MODULE TO THE AC100/200 & ACM100 SERIES DRIVE
The diagrams below illustrate how the DB module is wired to either the AC100/200 & ACM100 drive.
NOTE 1: External resistors are required when using Dynamic Braking modules 840-117, 840-118, and 840-119. Externalresistor assemblies are available from Minarik (refer to the next page for resistor information).
NOTE 2: Use 18 gauge wire for control connections. Tighten terminals to a torque of 2lb-in (0.2Nm).
NOTE 3: Use minimum 14 gauge wire for connections B+, B-, R+, and R-. Tighten terminals to a torque of 4.5lb-in (0.5Nm). The B+ and B- wires MUST be twisted together and must be less than 12 inches long. Twisting the R+ and R-wires together is also recommended.
Variable Speed AC Motor Drives250-0308r1 1 of 2
Minarik Drives � 14300 De La Tour Drive � South Beloit, IL 61080 � Ph: (800)MINARIK � Fax: (800) 624-6960 � www.minarikdrives.com
WARNING! AC100 control terminals are hot to ground! Do not touch!�
Warning
DO NOT use the Dynamic Braking Module with AC200 drives of Parameter Version 305 and lower! The Dynamic Brakingmodule may operate with some AC200 drives prior to parameter version 306, but these drives do not provide the necessarythermal protection for the Dynamic Braking module.
�
Warning
Incorrect wiring of the B+ and B- terminals will result in equipment damage! The B+ terminal on the DB module must beconnected to the B+ terminal on the AC100/200 or ACM100 drive, and the B- terminal on the DB module must be connected tothe B- terminal on the AC100/200 or ACM100 drive.
�
AC100/200 AND ACM100 SERIES DYNAMIC BRAKING OPTION (FOR USE WITH EXTERNAL RESISTORS)
INSTALLATION AND OPERATION INSTRUCTIONSManual Number: 250-0308r1
The AC200 Series Dynamic Braking option can be used with all AC100/200 & ACM100 models.
PROGRAMMING THE SC SERIES DRIVE FOR DYNAMIC BRAKING
AC100 Series: Set Parameter 06 (TB-14 OUTPUT) to DB BRAKE (11).AC200 Series: Set Parameter 09 (TB-31 OUTPUT) to DYNAMIC BRAKING (04).
ACM100 Series: Set Parameter 12 (TB-13E FUNCTION) to DYNAMIC BRAKING (20).
WIRING THE DB MODULE TO THE AC100/200 & ACM100 SERIES DRIVE
The diagrams below illustrate how the DB module is wired to either the AC100/200 & ACM100 drive.
NOTE 1: External resistors are required when using Dynamic Braking modules 840-117, 840-118, and 840-119. Externalresistor assemblies are available from Minarik (refer to the next page for resistor information).
NOTE 2: Use 18 gauge wire for control connections. Tighten terminals to a torque of 2lb-in (0.2Nm).
NOTE 3: Use minimum 14 gauge wire for connections B+, B-, R+, and R-. Tighten terminals to a torque of 4.5lb-in (0.5Nm). The B+ and B- wires MUST be twisted together and must be less than 12 inches long. Twisting the R+ and R-wires together is also recommended.
Variable Speed AC Motor Drives250-0308r1 1 of 2
Minarik Drives � 14300 De La Tour Drive � South Beloit, IL 61080 � Ph: (800)MINARIK � Fax: (800) 624-6960 � www.minarikdrives.com
WARNING! AC100 control terminals are hot to ground! Do not touch!�
Warning
DO NOT use the Dynamic Braking Module with AC200 drives of Parameter Version 305 and lower! The Dynamic Brakingmodule may operate with some AC200 drives prior to parameter version 306, but these drives do not provide the necessarythermal protection for the Dynamic Braking module.
�
Warning
Incorrect wiring of the B+ and B- terminals will result in equipment damage! The B+ terminal on the DB module must beconnected to the B+ terminal on the AC100/200 or ACM100 drive, and the B- terminal on the DB module must be connected tothe B- terminal on the AC100/200 or ACM100 drive.
�
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
2 B+B-
ACM100 CONTROLTERMINALS
ACM100 POWERTERMINALS
ACM100 DIAGRAM
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
2 B+B-
ACM100 CONTROLTERMINALS
ACM100 POWERTERMINALS
ACM100 DIAGRAM
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
2 B+B-
ACM100 CONTROLTERMINALS
ACM100 POWERTERMINALS
ACM100 DIAGRAM
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
2 B+B-
ACM100 CONTROLTERMINALS
ACM100 POWERTERMINALS
ACM100 DIAGRAM
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
2 B+B-
ACM100 CONTROLTERMINALS
ACM100 POWERTERMINALS
ACM100 DIAGRAM
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
2 B+B-
ACM100 CONTROLTERMINALS
ACM100 POWERTERMINALS
ACM100 DIAGRAM
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
2 B+B-
ACM100 CONTROLTERMINALS
ACM100 POWERTERMINALS
ACM100 DIAGRAM
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
2 B+B-
ACM100 CONTROLTERMINALS
ACM100 POWERTERMINALS
ACM100 DIAGRAM
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
312 B+B-
AC200 CONTROLTERMINALS
AC200 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC200 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
312 B+B-
AC200 CONTROLTERMINALS
AC200 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC200 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
312 B+B-
AC200 CONTROLTERMINALS
AC200 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC200 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
312 B+B-
AC200 CONTROLTERMINALS
AC200 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC200 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
312 B+B-
AC200 CONTROLTERMINALS
AC200 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC200 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
312 B+B-
AC200 CONTROLTERMINALS
AC200 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC200 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
312 B+B-
AC200 CONTROLTERMINALS
AC200 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC200 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
312 B+B-
AC200 CONTROLTERMINALS
AC200 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC200 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
1114 B+B-
AC100 CONTROLTERMINALS
AC100 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC100 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
1114 B+B-
AC100 CONTROLTERMINALS
AC100 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC100 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
1114 B+B-
AC100 CONTROLTERMINALS
AC100 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC100 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
1114 B+B-
AC100 CONTROLTERMINALS
AC100 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC100 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
1114 B+B-
AC100 CONTROLTERMINALS
AC100 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC100 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
1114 B+B-
AC100 CONTROLTERMINALS
AC100 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC100 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
1114 B+B-
AC100 CONTROLTERMINALS
AC100 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC100 DIAGRAM
GND
42 43 46 47 B- R+B+ R-
DB OPTION MODULE
1114 B+B-
AC100 CONTROLTERMINALS
AC100 POWERTERMINALS
EXTERNAL RESISTORASSEMBLY (see NOTE 1)
AC100 DIAGRAM
MOUNTING THE DYNAMIC BRAKING MODULE
The diagram below illustrates how to mount the DB Module. The DB Module is compatible with the DIN Rail Mounting Kitoption, or can simply be mounted to a flat surface such as an electrical panel.
SELECTING EXTERNAL RESISTORS
Use the chart below to select the proper external resistor assembly:
Minarik Drives ❏ 14300 De La Tour Drive ❏ South Beloit, IL 61080 ❏ Ph: (800)MINARIK ❏ Fax: (800) 624-6960 ❏ www.minarikdrives.com
NOTE: These resistor assemblies are the same as those used with the AC300 and AC400 Series drives. The DB Module doesnot include short-circuit protection for the external resistors. If short-circuit protection is desired, fusing must be supplied by thecustomer. Consult Minarik.
Warning
Hazard of electric shock! External resistors are connected to the drive’s DC bus, which can reach 950 VDC. Connections toexternal resistors must be electrically insulated and mechanically shielded for safety. High Voltage warning signs are alsorecommended.
�
Warning
DO NOT mount the resistors below the AC100/200 or ACM100 Series drive! The resistors generate heat, and must be mountedabove or to the side of the drive.
�
EXTERNAL RESISTOR ASSEMBLIESHP 240 / 200 Vac 480 / 400 Vac 590 / 480 Vac
0.25 - 0.5 841-100 841-101 N/A1 - 1.5 841-101 841-101 841-100
2 841-102 841-102 841-1013 841-104 841-104 841-1035 841-105 841-105 841-104
7.5 - 10 841-106 841-106 841-10715 - 20 841-108 841-108 841-109
25 N/A 841-110 841-111
Variable Speed AC Motor Drives250-0308r1 2 of 2