Installation and ServicingInstructions

Type C Boilers

microGENUS HE 24 MFFI G.C.N: 47-116-37microGENUS HE 28 MFFI G.C.N:47-116-38microGENUS HE 32 MFFI G.C.N:47-116-39

LEAVE THESE INSTRUCTIONS WITHTHE END-USER

Country of destination: GB / IE

12

34

56

12

3 4

56

II

E C

Page 2: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

2

TABLE OF CONTENTS

1. GENERAL INFORMATION PAGE. 31.1 GENERAL INSTRUCTIONS PAGE. 31.2 OVERALL VIEW PAGE. 4

2. INSTALLATION PAGE. 52.1 REFERENCE STANDARDS PAGE. 52.2 SITING THE APPLIANCE PAGE. 52.3 OVERALL DIMENSIONS PAGE. 62.4 CLEARANCES PAGE. 62.5 MOUNTING THE APPLIANCE PAGE. 62.6 ELECTRICAL CONNECTION PAGE. 72.7 GAS CONNECTION PAGE. 82.8 WATER CONNECTION PAGE. 8

2.8.1 CONDENSATE REMOVAL PAGE. 102.9 FLUE CONNECTION PAGE. 12

2.9.1 FITTING THE COAXIAL FLUE

( 60/100 HORIZONTAL) PAGE. 132.9.2 FITTING THE 5” FLUE

( 80/125 HORIZONTAL/VERTICAL) PAGE. 142.9.3 FITTING THE COAXIAL FLUE

( 60/100 VERTICAL) PAGE. 152.9.4 FITTING THE TWIN PIPE ( 80/80) PAGE. 16

2.10 CONTROL PANEL PAGE. 212.11 DIGITAL DISPLAY AND FAULT CODES PAGE. 212.12 REMOVING THE FRONT PANEL PAGE. 222.13 ROOM THERMOSTAT / REMOTE CLOCK

CONNECTION PAGE. 222.14 FITTING THE DIGITAL CLOCK PAGE. 232.15 SETTING THE MECHANICAL CLOCK PAGE. 242.16 SETTING THE DIGITAL CLOCK PAGE. 242.17 ELECTRICAL/SYSTEM DIAGRAMS PAGE. 262.18 WATER CIRCUIT DIAGRAM PAGE. 28

3. COMMISSIONING PAGE. 293.1 INITIAL PREPARATION PAGE. 293.2 INITIAL START-UP PAGE. 313.3 OPERATIONAL ADJUSTMENTS PAGE. 323.4 COMBUSTION ANALYSIS PAGE. 323.5 PRODUCT OF COMBUSTION

DISCHARGE MONITORING PAGE. 323.6 COMFORT MODE PAGE. 323.7 BOILER SAFETY SYSTEMS PAGE. 333.8 DRAINING THE SYSTEM PAGE. 343.9 COMPLETION PAGE. 353.10 OPERATIONAL CHECKS PAGE. 353.11 INSTRUCTING THE END USER PAGE. 36

4. GAS ADJUSTMENTS PAGE. 374.1 CHANGING THE TYPE OF GAS PAGE. 374.2 ADJUSTING THE GAS PRESSURES PAGE. 37

5. MAINTENANCE PAGE. 41

6. SERVICING INSTRUCTIONS PAGE. 426.1 REPLACEMENT OF PARTS PAGE. 426.2 TO GAIN GENERAL ACCESS PAGE. 42

6.2.1 REMOVING THE FRONT PANEL PAGE. 426.2.2 REMOVING THE SEALED CHAMBER

FRONT PANEL PAGE. 43

6.2.3 REMOVING THE SIDE PANELS PAGE. 43

6.3 ACCESS TO THE COMBUSTION CHAMBER PAGE. 446.3.1 REMOVING THE COMBUSTION

CHAMBER PAGE. 446.3.2 REMOVING THE BURNER AND JETS PAGE. 446.3.3 REMOVING THE ELECTRODES PAGE. 446.3.4 REMOVING THE MAIN HEAT EXCHANGER PAGE. 456.3.5 REMOVING THE AIR PRESSURE SWITCH PAGE. 466.3.6 REMOVING THE FAN PAGE. 476.3.7 REMOVING THE FLUE / CONDENSATE

SENSOR PAGE. 476.3.8 REMOVING THE RECUPERATOR PAGE. 486.3.9 REMOVING THE RECUPERATOR HOUSING PAGE. 496.3.10 REMOVING THE CONDENSATE TRAP PAGE. 49

6.4 ACCESS TO THE GAS VALVE PAGE. 506.4.1 REMOVING THE SPARK GENERATOR PAGE. 506.4.2 REMOVING THE GAS VALVE PAGE. 50

6.5 ACCESS TO THE WATER CIRCUIT PAGE. 516.5.1 REMOVING THE D.H.W. (SECONDARY)

EXCHANGER PAGE. 516.5.2 REMOVING THE PUMP PRESSURE

SWITCH PAGE. 526.5.3 REMOVING THE SAFETY VALVE PAGE. 526.5.4 REMOVING THE AUTOMATIC AIR VENT PAGE. 536.5.5 REMOVING THE PUMP PAGE. 536.5.6 REMOVING THE PRESSURE GAUGE PAGE. 546.5.7 REMOVING THE EXPANSION VESSEL PAGE. 556.5.8 REMOVING THE OVERHEAT THERMOSTAT PAGE. 556.5.9 REMOVING THE C.H. TEMPERATURE

SENSOR (N.T.C.) PAGE. 566.5.10 REMOVING THE D.H.W. TEMPERATURE

SENSOR (N.T.C.) PAGE. 566.5.11 REMOVING THE DIVERTER VALVE

ACTUATOR PAGE. 566.5.12 REMOVING THE D.H.W. FLOW

SWITCH PAGE. 576.6 ACCESS TO THE CONTROL SYSTEM PAGE. 57

6.6.1 CHECKING THE FUSES PAGE. 576.6.2 REMOVING THE P.C.B. PAGE. 586.6.3 REMOVING THE TIME CLOCK PAGE. 59

7. FAULT FINDING PAGE. 607.1 FAULT FINDING GUIDE (FLOW-CHARTS) PAGE. 60

8. SHORT SPARE PARTS LIST PAGE. 63

9. TECHNICAL INFORMATION PAGE. 66

10. BENCHMARK COMMISSIONINGCHECKLIST PAGE. 68

11. SERVICE INTERVAL RECORD PAGE. 69

Page 3: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

3

This manual is an integral and essential part of theproduct. It should be kept with the appliance so that it canbe consulted by the user and our authorised personnel.

Please carefully read the instructions and notices aboutthe unit contained in this manual, as they provideimportant information regarding the safe installation, useand maintenance of the product.

For operating instructions please consult the separate EndUser Manual.

1. GENERAL INFORMATION1.1 GENERAL INSTRUCTIONS

Read the instructions and recommendations in theseInstallation and Servicing Instructions carefully to ensureproper installation, use and maintenance of theappliance.

Keep this manual in a safe place. You may need it for yourown reference while Servicing Technicians or yourinstaller may need to consult it in the future.

This is a condensing combined appliance for theproduction of central heating (C.H.) and domestic hotwater (D.H.W.).

This appliance must be used only for domestic use.The manufacturer declines all liability for damage causedby improper or negligent use.

No asbestos or other hazardous materials have beenused in the fabrication of this product.

MTS recommends the use of protective clothing wheninstalling and working on this appliance i.e. gloves.

Before connecting the appliance, check that theinformation shown on the data plate and the table inSection 9 comply with the electric, water and gas mainsof the property. You will find the data plate on the inside ofthe left hand casing panel.The gas with which this appliance operates is also shownon the label at the bottom of the boiler.

Do not install this appliance in a damp environment orclose to equipment which spray water or other liquids.Do not place objects on the appliance.Do not allow children or inexperienced persons to usethe appliance without supervision.

If you smell gas in the room, do not turn on or off lightswitches, use the telephone or any other object whichmight cause sparks.Open doors and windows immediately to ventilate theroom.Shut the gas mains tap (at or adjacent to the gas meter)or the valve of the gas cylinder and call your Gas Supplierimmediately.If you are going away for a long period of time, rememberto shut the mains gas tap or the gas cylinder valve.

Always disconnect the appliance either by unplugging itfrom the mains or turning off the mains switch beforecleaning the appliance or carrying out maintenance.

In the case of faults or failure, switch off the applianceand turn off the gas tap. Do not tamper with theappliance.For repairs, call your local Authorised Servicing Agentand request the use of original spare parts. For in-guarantee repairs contact MTS (GB) Limited.

Page 4: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

4

25

26

27

24

23

222120

1918171615

1413121110

9

876

54

3

2

1 28

LEGEND:

1. Flue Manifold2. Air Intake for Twin Pipe Flue Systems3. Fan4. Combustion Chamber Hood5. Main Heat Exchanger6. Overheat Thermostat7. Central Heating Flow Temperature Probe8. Combustion Chamber Insulation Panel9. Burner10. Detection Electrode11. Ignition Electrodes12. Motorised Valve13. Condensate trap14. Domestic Hot Water Temperature Probe15. Low Water Pressure Switch16. Secondary Heat Exchanger17. Gas Valve18. Spark Generator19. Cold Water Inlet Filter20. Pump (w/auto air vent)21. Safety Valve22. D.H.W. Flow Switch23. Condensate Trap Tube24. Combustion Chamber25. Condensate Sensor26. Latent Heat Collector27. Air Pressure Switch28. Combustion Analysis Test Point

1.2 OVERALL VIEW

FIG. 1.0

Page 5: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

5

2.1 REFERENCE STANDARDS

2. INSTALLATION

The technical information and instructions providedherein below are intended for the installer / ServicingTechnician so that the unit may be installed and servicedcorrectly and safely.

In the United Kingdom the installation and initial start upof the boiler must be by a CORGI Registered Installer inaccordance with the installation standards currently ineffect, as well as with any and all local health and safetystandards i.e. CORGI.

In the Republic of Ireland the installation and initial startup of the appliance must be carried out by a CompetentPerson in accordance with the current edition of I.S.813“Domestic Gas Installations”, the current BuildingRegulations, reference should also be made to thecurrent ETCI rules for electrical installation.

This appliance must be installed by a competentinstaller in accordance with current Gas Safety(installation & use) Regulations.

The installation of this appliance must be in accordancewith the relevant requirements of the Local BuildingRegulations, the current I.E.E. Wiring Regulations, thebylaws of the local water authority, in Scotland, inaccordance with the Building Standards (Scotland)Regulation and Health and Safety document No. 635“Electricity at work regulations 1989” and in the Republicof Ireland with the current edition of I.S. 813, the LocalBuilding Regulations (IE).

C.O.S.H.H.

Materials used in the manufacture of this appliance arenon-hazardous and no special precautions are requiredwhen servicing.Installation should also comply with the following BritishStandard Codes of Practice

and in the Republic of Ireland in accordance with thefollowing Codes of Practice:

BS 7593:1992 Treatment of water in domestic hot watercentral heating systems

BS 5546:2000 Installation of hot water supplies fordomestic purposes

BS 5440-1:2000 FluesBS 5440-2:2000 Air supplyBS 5449:1990 Forced circulation hot water systemsBS 6798:2000 Installation of gas fired hot water boilers

of rated input not exceeding 70kWBS 6891:1998 Installation of low pressure gas pipe up to

28mmBS 7671:2001 IEE wiring regulationsBS 4814:1990 Specification for expansion vesselsBS 5482:1994 Installation of L.P.G.

I.S. 813 Domestic Gas Installations

The appliance may be installed in any room or indoorarea, although par ticular attention is drawn to therequirements of the current I.E.E. Wiring Regulations, andin Scotland, the electrical provisions of the BuildingRegulations applicable in Scotland, with respect to theinstallation of the combined appliance in a roomcontaining a bath or shower, the location of the boiler in aroom containing a bath or shower should only beconsidered if there is no alternative.

Where a room-sealed appliance is installed in a roomcontaining a bath or shower the appliance and anyelectrical switch or appliance control, utilising mainselectricity should be situated so that it cannot betouched by a person using the bath or shower,specifically in accordance with current IEE WiringRegulations.

The location must permit adequate space for servicingand air circulation around the appliance as indicated inSection 2.4.The location must permit the provision of an adequateflue and termination.For unusual locations special procedures may benecessary.BS 6798-2000 gives detailed guidance on this aspect.A compartment used to enclose the appliance must bedesigned specifically for this purpose. No specificventilation requirements are needed for the installationwithin a cupboard.This appliance is not suitable for outdoor installation.

The type C appliances (in which the combustioncircuit, air vent intake and combustion chamber areair-tight with respect to the room in which theappliance is installed) can be installed in any type ofroom. However, as the appliance has manyfunctioning components, pay particular attentionwhen siting the appliance in room such as bedroomsas operating noise may be a nuisance.

Secondary ventilation is not required with this boiler. Theboiler must be installed on a solid, non-combustible,permanent wall to prevent access from the rear.

2.2 SITING THE APPLIANCE

Page 6: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

6

After removing the boiler from its packaging, remove thetemplate from the separate box containing the connectionkit. NOTE: Pay particular attention to any test water thatmay spill from the appliance.

Place the template in the position the appliance is to bemounted and after ensuring it is hanging squarely, use itto mark the holes for the hanging bracket, connection kitand flue pipe(s) NB: For further information relating to theflue installation please refer to Section 2.9 FLUE

CONNECTION. (If the appliance is to be fitted on a wall ofcombustible material, the wall must be protected by asheet of fireproof material).If the appliance is to be fitted into a timber framedbuilding, guidance should be sought from the Institute ofGas Engineers document REF: IGE/UP/7.

2.5 MOUNTING THE APPLIANCE

FIG. 2.2

In order to allow access to the interior of the boiler formaintenance purposes, the boiler must be installed incompliance with the minimum clearances indicated in FIG. 2.2

2.4 CLEARANCES

120

LEGEND:

A = Central Heating Flow (3/4” - 22mm Copper Tail)B = Domestic Hot Water Outlet (1/2” - 15mm Copper Tail)C = Gas Inlet (3/4” - 15mm Copper Tail)D = Domestic Cold Water Inlet (1/2” - 15mm Copper Tail)E = Central Heating Return (3/4” - 22mm Copper Tail)

2.3 OVERALL DIMENSIONS

FIG. 2.1

* Clearance for Servicing 25mm if behind a temporary closure i.e. door.

Page 7: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

7

For safety purposes, have a competent person carefullycheck the electrical system in the property, as themanufacturer will not be held liable for damage caused bythe failure to earth the appliance properly or by anomaliesin the supply of power. Make sure that the residentialelectrical system is adequate for the maximum powerabsorbed by the unit, which is indicated on the ratingplate. In addition, check that the section of cabling isappropriate for the power absorbed by the boiler.

The boiler operates with alternating current, as indicatedin the Technical Information table in Section 9, where themaximum absorbed power is also indicated. Ensure thatthe connections for the live, neutral and earth wirescorrespond with the indications in the diagram (Fig. 2.4).The appliance electrical connections are situated on thePCB, see Section 2.17

IMPORTANT!In the event that the power supply cord must be changed,replace it with one with the same specifications.Note: The diagrams for the electrical system are indicatedin Section 2.17.

Warning, this appliance must be earthed.

External wiring to the appliance must be carried out by acompetent person and be in accordance with the currentI.E.E. Regulations and applicable local regulations.The appliance is supplied with a f ly-lead alreadyconnected, this must be connected to a 240v supplyfused at 3A and must facilitate complete electricalisolation of the appliance, by the use of a fused doublepole isolator having a contact separation of at least 3 mmin all poles or alternatively, by means of a 3 A fusedthree pin plug and unswitched, shuttered socket outletboth complying with BS 1363.The point of connection to the Electricity supply must bereadily accessible and adjacent to the appliance unlessthe appliance is installed in a bathroom when this mustbe sited outside the bathroom (see Section 2.2).

Should external controls be required, the design of theexternal electrical circuits should be undertaken by acompetent person, see Section 2.13 for fur therinformation.

2.6 ELECTRICAL CONNECTION

FIG. 2.3

2.5.1. Drill the wall and plug using those supplied withthe connections kit, position the hanging bracket andsecure with the wall bolts supplied, assemble theconnection kit and secure to the wall. NOTE: It is highlyrecommended that a spirit level be used to position theappliance to ensure that it is perfectly level.

2.5.2. Position the appliance on the hanging bracketand connect the connection kit to the boiler connections.(see also Sections 2.7 Gas Connections, 2.8 WaterConnections & FIG. 2.3).

85 mm

220 mm

FIG. 2.4

Page 8: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

8

VIEW OF THE BOILER CONNECTIONS

LEGEND:

A = Central Heating FlowB = Domestic Hot Water OutletC = Gas InletD = Domestic Cold Water InletE = Central Heating ReturnF = Condensate dischargeG = Drain valveH = Safety Valve Outlet

2.8 WATER CONNECTIONS

2.7 GAS CONNECTION The local gas region contractor connects the gas meter tothe service pipe.If the gas supply for the boiler serves other appliancesensure that an adequate supply is available both to theboiler and the other appliances when they are in use atthe same time.Pipe work must be of an adequate size. Pipes of asmaller size than the boiler inlet connection should not beused.

FIG. 2.5

FIG. 2.6 KT007A

CENTRAL HEATING

Detailed recommendations are given in BS 6798:2000and BS 5449-1:1990, the following notes are given forgeneral guidance.

PIPE WORK:Copper tubing to BS EN 1057:1996 is recommended forwater pipes. Jointing should be either with capillarysoldered or compression fittings.Where possible pipes should have a gradient to ensureair is carried naturally to air release points and waterflows naturally to drain taps.The appliance has a built-in automatic air release valve,however it should be ensured as far as possible that theappliance heat exchanger is not a natural collecting pointfor air.Except where providing useful heat, pipes should beinsulated to prevent heat loss and avoid freezing.Particular attention should be paid to pipes passingthrough ventilated spaces in roofs and under floors.

BY-PASS:The appliance includes an automatic by-pass valve,which protects the main heat exchanger in case ofreduced or interrupted water circulation through theheating system, due to the closing of thermostatic valvesor radiators.

SYSTEM DESIGN:This boiler is suitable only for sealed systems.

DRAIN COCKS:These must be located in accessible positions to permitthe draining of the whole system and should be fitted atall low points. The taps must be at least 15mm nominalsize and manufactured in accordance with BS 2870:1980.

A BC

D E

G

F H

Page 9: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

9

SAFETY VALVE DISCHARGE:The discharge should terminate facing downward on theexterior of the building in a position where discharging(possibly boiling water & steam) will not create danger ornuisance, but in an easily visible position, and not causedamage to electrical components and wiring.The discharge must not be over an entrance or a windowor any other type of public access.

AIR RELEASE POINTS:These must be fitted at all high points where air naturallycollects and must be sited to facilitate complete filling ofthe system.The appliance has an integral sealed expansion vessel toaccommodate the increase of water volume when thesystem is heated.It can accept up to 6 litres (1.3 gal) of expansion water. Ifthe heating circuit has an unusually high water content,calculate the total expansion and add an additionalsealed expansion vessel with adequate capacity. Thisshould be located on the return pipe work as close aspossible to the pump inlet.

MAINS WATER FEED - CENTRAL HEATING:A method for initially filling the heating system is suppliedwith the connection kit. The filling loop is connectedbetween the cold water inlet and the central heating flowconnections, and incorporates a non-return valve. Tooperate the filling loop, it is necessary to open bothquarter turn handles, once the required pressure hasbeen achieved, close both handles and disconnect thehose in accordance with water byelaws. NOTE: Theinstaller should ensure that there are no leaks as frequentfilling of the heating system can lead to premature scalingof the main exchanger and failure of hydrauliccomponents.

VR003A

RESIDUAL HEAD OF THE BOILER DT 20°C

DOMESTIC WATER:The domestic water must be in accordance with therelevant recommendation of BS 5546:1990. Coppertubing to BS EN 1057:1996 is recommended for watercarrying pipe work and must be used for pipe workcarrying drinking water, a scale reducer should also beused to reduce the risk of scale forming in the domesticside of the heat exchanger.

WATER TREATMENT

The boiler is equipped with a secondary heat exchanger(recuperator) made from stainless steel as well as thecopper main heat exchanger.The detailed recommendations for water treatment aregiven in BS 7593:1992 (Treatment of water in domestichot water central heating systems); the following notesare given for general guidance;

- If the boiler is installed on an existing system, anyunsuitable additives must be removed;

- Under no circumstances should the boiler be firedbefore the system has been thoroughly flushed; theflushing procedure must be in line with BS7593:1992.We highly recommend the use of a flushing detergentappropriate for the metals used in the circuit. Theseinclude cleansers produced by Fernox andBetzDearborn, whose function is to dissolve anyforeign matter that may be in the system;In hard water areas or where large quantities of waterare in the system the treatment of the water to preventpremature scaling of the main heat exchanger isnecessary.

The formation of scale strongly compromises theefficiency of the thermic exchange because smallareas of scale cause a high increase of thetemperature of the metallic walls and therefore add tothe thermal stress of the heat exchanger.Demineralised water is more aggressive so in this

FIG. 2.7

Page 10: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

10

12

3 4

56

12

3 4

56

E C

II

1. Internal termination of condensate drainage pipe to internal stack

situation it is necessary to treat the water with anappropriate corrosion inhibitor.

- Any treatment of water by additives in the system forfrost protection or for corrosion inhibition has to beabsolutely suitable for all the metals used in the circuit.The use of a corrosion inhibitor in the system such asFernox MB-1, BetzDeaborn Sentinel X100 or FernoxSystem Inhibitor is recommended to prevent corrosion(sludge) damaging the boiler and systems;

- If anti-freeze substances are to be used in the system,check carefully that they are compatible with the metalsused in the circuit.MTS suggests the use of suitable anti-freeze productssuch as Fernox ALPHI 11, which will prevent rust andincrustation taking place.Periodically check the pH of the water/anti-freezemixture of the boiler circuit and replace it when theamount measured is out of the range stipulated by themanufacturer ( 7 < pH < 8).DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE

- In under-floor systems, the use of plastic pipes withoutprotection against penetration of oxygen through thewalls can cause corrosion of the systems metal parts (metal piping, boiler, etc), through the formation ofoxides and bacterial agents.To prevent this problem, it is necessary to use pipeswith an “oxygen-proof barrier”, in accordance withstandards DIN 4726/4729. If pipes of this kind arenot used, keep the system separate by installingheat exchangers of those with a specific systemwater treatment.

IMPORTANT Failure to carry out the water treatment procedure willinvalidate the appliance warranty.

CONDENSATE DISCHARGE:A flexible hose connected to the bottom of the boilershould be inserted into a tundish (not supplied).

NOTE: IT MAY BE NECESSARY TO REMOVE THE CASING TO PULL

THE CONDENSATE HOSE OUT OF THE BOTTOM OF THE BOILER.

The condensate discharge hose from the boiler musthave a continuous fall of at least 2.5° and must beconnected to a visible tundish and inserted by at least50mm into a suitable acid resistant pipe with a nominaldiameter of 32mm e.g. plastic waste pipe or overflowpipe. The condensate discharge pipe must have acontinuous fall and preferably be installed and terminatedwithin the building to prevent freezing.The discharge pipe must be terminated in one of thefollowing positions, allowing for a safe discharge:

i) Connecting in to an internal soil stack (at least 450 mmabove the invert of the stack). A trap giving a waterseal of at least 75 mm must be incorporated into thepipe run, there also must be an air break upstream ofthe trap i.e. tundish.

2.8.1 CONDENSATE REMIOVAL

Page 11: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

11

3. External termination of condensate drainage pipe via internal discharge branch (e.g. sink waste - proprietary fitting).

4. External termination of condensate drainage pipe viacondensate siphon

2. External termination of condensate drainage pipe viainternal discharge branch (e.g. sink waste) and condensatesiphon

ii) Connecting into the waste system of the building suchas a washing machine or sink trap. The connectionmust be upstream of the washing machine/sink (If theconnection is down stream of the waste trap then anadditional trap giving a minimum water seal of 75 mmand an air break must be incorporated in the pipe run,as above.

iii)Terminating into a gully, below the grid level but abovethe water level.

iv)Into a soakway.

NOTE: If any condensate pipe work is to be installedexternally, then it should be kept to a minimum and beinsulated with a waterproof insulation and have acontinuous fall.

Some examples of the type of condensate drains canbe found in this section.

Page 12: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

12

2.9. CONNECTING THE FLUE

IMPORTANT!!BEFORE CONNECTING THE FLUE, ENSURE THAT 1 LITRE OF

WATER HAS BEEN POURED INTO THE EXHAUST CONNECTION TO

FILL THE CONDENSATE TRAP (FIG.2.8). SHOULD THE TRAP BE

EMPTY THERE IS A TEMPORARY RISK OF FLUE GASSES

ESCAPING INTO THE ROOM.

FIG. 2.8

4

Ø 60/100 mm

Fig. 2.10

TERMINAL POSITION mm

A - Directly below an open window or other opening 300B - Below gutters, solid pipes or drain pipes 75C - Below eaves 200D - From vertical drain pipes and soil pipes 75E - From internal or external corners 300F - Above ground on a public walkway or patio 2100G - From a surface facing a terminal 2500H - From a terminal facing a terminal 2500I - Vertically from a terminal in the same wall 1500J - Horizontally from a terminal in the same wall 300K - Horizontally from an opening window 300L - Fixed by vertical flue terminal

EE

FLUE SYSTEM

The provision for satisfactory flue termination must be madeas described in BS 5440-1.The appliance must be installed so that the flue terminal isexposed to outdoor air.The terminal must not discharge into another room or spacesuch as an outhouse or lean-to.It is important that the position of the terminal allows a freepassage of air across it at all times.The terminal should be located with due regard for thedamage or discolouration that might occur on buildings in thevicinity, it must also be located in a place not likely to causenuisance.In cold or humid weather water vapour may condense onleaving the flue terminal.The effect of such “steaming” must be considered.If the terminal is 2.1 metres above a balcony, above groundor above a flat roof to which people have access, then asuitable stainless steel terminal guard must be fitted.

The minimum acceptable spacing from the terminal toobstructions and ventilation openings are specified in Fig.2.9.

FIG. 2.9

Page 13: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

13

WarningThe exhaust gas ducts must not be in contact with or close toinflammable material and must not pass through buildingstructures or walls made of inflammable material.When replacing an old appliance, the flue system must bechanged.

ImportantEnsure that the flue is not blocked.Ensure that the flue is supported andassembled in accordance with theseinstructions.

2.9.1 FITTING THE COAXIAL FLUE(Ø 60 / 100 HORIZONTAL)

SEE PAGE 19 FOR MAX AND MIN FLUE RUNS

Installation without extension

Installation with extension

Fig. 2.11

Fig. 2.12

118

Level

Level

PART NO: 3318073

CONTENTS:1X SILICONE O-RING (60mm)1X ELBOW (90O)2X WALL SEALS (INTERNAL & EXTERNAL)1X FLUE PIPE INCLUDING TERMINAL (1 METRE - 60/100)2X FLUE CLAMPS

4X SCREWS

2x Seals

Once the boiler has been positioned on the wall, insertthe elbow into the socket and rotate to the requiredposition. NOTE: It is possible to rotate the elbow 360o onits vertical axis.

Using the flue clamps, seals and screws supplied (Fig2.13) secure the elbow to the boiler.

The 1 metre horizontal flue kit (3318073) supplied issuitable for an exact X dimension of 823mm.

Measure the distance from the face of the external wallto the face of the flue elbow (X - Fig 2.10), this figuremust now be subtracted from 815mm, you now havethe total amount to be cut from the plain end of the flue.

Draw a circle around the outer flue and cut the flue tothe required length taking care not to cut the inner flue,next cut the inner flue ensuring that the length betweenthe inner and outer flue is maintained. (Fig 2.13).e.g.

X = 555mm 823-555 = 268mm (Length to be cut from the plain end of the flue).

Page 14: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

14

Fig. 2.13

2.9.2 FITTING THE 5” FLUE(Ø 80 / 125 HORIZONTAL/VERTICAL)

SEE PAGE 19 FOR MAX AND MIN FLUE RUNS CONTENTS:

HORIZONTAL KIT - 33180953X SILICONE O-RINGS (60mm, 80mm & 125mm)1X 90O ELBOW (HORIZONTAL ONLY)1X ADAPTOR (60/100 - 80/125MM)1X HORIZONTAL FLUE PIPE (INCLUDING TERMINAL)

(80/125mm)2X WALL SEALS (INTERNAL & EXTERNAL)2X FLUE CLAMPS

2X SEALS

4X SCREWS

VERTICAL KIT - 3318080 (BLACK) / 3318081 (RED)1X VERTICAL FLUE PIPE (INCL.TERMINAL) (80/125MM)1X ADAPTOR (60/100 - 80/125)1X SILICONE O-RING (60MM)

Should the flue require extending, the flue connections arepush fit, however, one flue bracket should be used tosecure each metre of flue.

Once the boiler has been positioned on the wall, it isnecessary to insert the Ø80/125 adaptor (FIG. 2.14)raised horizontal and vertical flue runs into the boiler fluesocket (not supplied with flue kit - Part No 3318095).

Push the adaptor onto the boilers flue connection, greasethe seals then add extensions or elbows as required,secure the adaptor, using the clamp and screws provided.

To fit extensions or elbows it is first necessary to ensurethat the lip seal is fitted correctly into the inner flue, onceverified, it is simply necessary to push them together, no

Screws

Clamp

Seal

Fig. 2.14

Once cut to the required length, ensure that the flue isfree from burrs and reassemble the flue. If fitting theflue from inside of the building attach the grey outerwall seal to the flue terminal and push the flue throughthe hole, once the wall seal has passed through thehole, pull the flue back into the elbow (ensuring that theflue seal is not dislodged) until the external wall seal isflush with the wall, and that the flue is securely locatedinto the elbow, finally secure the flue to the elbow withthe clamp provided. Alternatively, the flue can beinstalled from outside of the building, the grey outerseal being fitted last.

Page 15: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

15

NOTE: SEE PAGE 19 FOR MAXIMUM AND MINIMUM FLUE

RUNS.

PART NO: 33108080 (BLACK) / 3318081 (RED)

CONTENTS:1X SILICONE O-RING (60mm)1X CONICAL ADAPTOR (60/100mm)1X VERTICAL FLUE KIT (80/125mm)

The vertical flue kit is supplied with a speciallydesigned weather proof terminal fitted, it can be usedeither with a flat roof or a pitched roof.

The Vertical flue kits useable lengths with the pitchedroof flashings are indicated in Fig. 2.17.

Before proceeding to fit the flue, ensure that themaximum flue length has not been exceeded (Seethe tables on Page 19) and that all elbows and bendshave been taken into consideration, the maximumflue length is 4 metres, for each additional 90o elbow1 metre must be subtracted from the total flue length,and for each 45o 0.5 metres must be subtracted fromthe total flue length (the height of the verticaladaptor and a 45o bend can be seen in Fig. 2.18).Mark the position of the flue hole in the ceiling and/or

2.9.3. FITTING THE COAXIAL FLUE(Ø 60 / 100 VERTICAL)

Fig. 2.15 Fig. 2.16

Fig. 2.17

clamps are necessary to secure the flue components.Before proceeding to fit the flue, ensure that themaximum flue length has not been exceeded (See thetables on Page 19) and that all elbows and bends havebeen taken into consideration, the maximum flue lengthis 10 metres, for each additional 90o elbow 1 metremust be subtracted from the total flue length, and foreach 45o 0.5 metres must be subtracted from the totalflue length (the height of the vertical adaptor and a45o bend can be seen in Fig. 2.15 and a 90o bend(raised horziontal only) in Fig. 2.16).

NOTE: DO NOT CUT THE VERTICAL FLUE KIT.

Page 16: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

16

2.9.4. FITTING THE TWIN PIPE (Ø80 / 80) NOTE: SEE PAGE 19 FOR MAXIMUM AND MINIMUM FLUE RUNS.

Where it is not possible to terminate the flue within thedistance permitted for coaxial flues, the twin flue pipe canbe used by fitting a special adaptor to the flue connectorand using the aperture for the air intake located on top ofthe combustion chamber.Always ensure that the flue is adequately supported, usingone flue bracket per extension and avoiding low points.(MTS supply suitable clamps as Part No. 705778).

To utilise the exhaust manifold it is necessary to connectthe adaptor (Part No: 3318017) to the exhaust manifoldand secure with the clamp (see FIG. 2.18A), add elbows orextensions as required.

To utilise the air intake it is necessary to:

Remove the ‘knockout’ of the air intake by cutting it with asuitable knife (FIG. 2.18B).

Insert the elbow/flue pipe into the air intake until it stops.

Fig. 2.18

roof (see Fig. 2.16 for distance from the wall to the centreof the flue).

Cut a 120mm diameter hole through the ceiling and/orroof and fit the flashing plate to the roof.

DO NOT cut the vertical flue kit.

To connect the vertical flue kit directly to the boiler, placethe vertical starter kit (Part No. 3318079) (see Fig. 2.17)onto the exhaust manifold and secure with the clamp, fitthe vertical adaptor onto the vertical starter kit (note: thereis no need to use a clamp to secure this as it is a push fitconnection), the vertical flue kit must then be insertedthrough the roof flashing, this will ensure that the correctclearance above the roof is provided as the terminal is afixed height.

Should extensions be required, they are available in 1metre (Part No. 3318077), 500mm (Part No. 3318078)and 160mm lengths, they must be connected directly tothe vertical starter kit before connecting the adaptor toallow the vertical flue kit to be fitted. In the event thatextension pieces need to be shortened, they must onlybe cut at the male end and it must be ensured that theinner and outer flue remain flush.

When utilising the vertical flue system, action must betaken to ensure that the flue is supported adequately toprevent the weight being transferred to the appliance flueconnection by using 1 flue bracket per extension.

When the flue passes through a ceiling or wooden floor,there must be an air gap of 25mm between any part of theflue system and any combustible material. The use of aceiling plate will facilitate this. Also when the flue passesfrom one room to another a fire stop must be fitted toprevent the passage of smoke or fire, irrespective of thestructural material through which the flue passes.

Fig. 2.18A

Page 17: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

17

The twin flue pipes can be fitted with or without additionalelbows and need no clamps, simply ensure that the red o-ring is inserted in the female end of the flue pipe and pushthe extension piece fully into the previous section of flue pipeor elbow, check that the o-ring is not dislodged whenassembling the flue.

The twin flue pipes can be fitted with or without additionalelbows and need no clamps, simply ensure that the red o-ring is inserted in the female end of the flue pipe and pushthe extension piece fully into the previous section of fluepipe or elbow, check that the o-ring is not dislodged whenassembling the flue (greasing the seal will aid assembly).

Twin pipe can also be converted back to Coaxial flue toenable vertical termination with a coaxial kit by using thepipe bridge (Twin - Coaxial Adaptor - Part No. 3318089).When running the twin flue pipe vertically.

It is not possible to terminate concentrically horizontally.Termination is only possible with separate air and exhaustterminals.

When siting the twin flue pipe, the air intake and exhaustterminals must terminate on the same wall, the centres ofthe terminals must be a minimum of 280 mm apart andthe air intake must not be sited above the exhaustterminal (refer to Fig. 2.22). The air intake pipe can be runhorizontally, however, the terminal and the final 1 metre offlue must be installed either horizontally or with a slight fallaway from the boiler to avoid rain ingress.

It is also strongly recommended that the air intake pipe runbe constructed of insulated pipe to prevent condenseforming on the outside of the tube.

The maximum permissible flue length for twin flue isdependent on the type of run used.For flue runs with the intake and exhaust pipes under thesame atmospheric conditions (TYPE 4) the maximumlength is 40 metres, for runs with the terminals underdifferent atmospheric conditions (TYPE 5) the exhaustterminal must extend 0.5 metres above the ridge of theroof (this is not obligatory if the exhaust and air intakepipes are located on the same side of the building). ForTYPE 5 also, the maximum permissible combined length is40 metres.

The maximum length is reached by combining the totallengths of both the air intake and exhaust pipes. Thereforea maximum length of 40 metres for example, will allow aflue run of 20 metres for the air intake and 20 metres forthe exhaust pipes, also for each 90o elbow 2.2 metres mustbe subtracted from the total length and for each 45o elbow1.4 metres must be subtracted from the total flue length.

Some of the acceptable flue configurations are detailed onpage 20.

For further information relating to flue runs not illustrated,please contact the Technical Department on 0870 2418180.

Fig. 2.18B

Page 18: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

18

For coaxial systems, the maximum development value,mentioned in the table below also takes into account anelbow.For twin flue systems the maximum development value,mentioned in the table includes the exhaust gas/air intaketerminal.

Type 5 outlets should respect the following instructions:1- Use the same ø 80 mm flue pipes for the air intakes

and exhaust gas ducts.2- If you need to insert elbows in the air intake and

exhaust gas ducts, you should consider for each one the equivalent length to be included in the calculation of developed length.

3- The exhaust gas duct should jut above the roof by at least 0.5 m.

4- The intake and exhaust gas ducts in Type 5 must be installed on the same wall, or where the exhaust is vertical and the air intake horizontal, the terminals mustbe on the same side of the building.

ø10

0

60 mm

In the event that twin flue pipes are used, and the boilerhas a side clearance of less than 60mm from the wall, itis necessary to cut a larger diameter hole for the fluepipe, this should be ø10 cm, this will then allow for easierassembly of the air intake elbow and the tube outside thewall (see Fig. 2.20).

Fig. 2.20

In the event that the air intake and exhaust are run to theleft, it will be necessary to reduce the height of the airintake by cutting 20mm from the base of the air intakeelbow (see Fig. 2.19)

Fig. 2.19

The flue restrictor is factory fitted in the exhaust manifoldon the boiler. Please refer to the table on page 19 todetermine whether it will be necessary to remove it.

To remove the restrictor it is simply necessary to lift therestrictor from the exhuast manifold (Fig. 2.20A)

Fig. 2.20A

Page 19: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

19

24 MFFI Exhaust TypeDo not remove the

ø 40 mmRestrictor

Remove theRestrictor(Fig.2.20A)

Maximum FlueLength

LengthReduction 45o

elbow (m)

LengthReduction 90o

elbow (m)

CoaxialSystemsø 60/100

Type 1

Between500 mm - 1 m

Between1 m - 4 m

4 m 0.5 m 1.0 mType 2

Type 3

CoaxialSystemsø 80/125

Type 1

TBC TBC 10 m TBC TBCType 2

Type 3

Twin PipeSystemsø 80/80

Type 4Between

1m - 10 mBetween

10 m - 40 m 40 m 1.4 m 2.2 m

Type 5Between

1m - 10 mBetween

10 m - 40 m 40 m 1.4 m 2.2 m

28 MFFI Exhaust TypeDo not remove the

ø 41 mmRestrictor

Remove theRestrictor(Fig.2.20A)

Maximum FlueLength

LengthReduction 45o

elbow (m)

LengthReduction 90o

elbow (m)

CoaxialSystemsø 60/100

Type 1

Between500 mm - 1 m

Between1 m - 4 m

4 m 0.5 m 1.0 mType 2

Type 3

CoaxialSystemsø 80/125

Type 1

TBC TBC 10 m TBC TBCType 2

Type 3

Twin PipeSystemsø 80/80

Type 4Between

1m - 10 mBetween

10 m - 40 m 40 m 1.4 m 2.2 m

Type 5Between

1m - 10 mBetween

10 m - 40 m 40 m 1.4 m 2.2 m

32 MFFI Exhaust TypeDo not remove the

ø 43 mmRestrictor

Remove theRestrictor(Fig.2.20A)

Maximum FlueLength

LengthReduction 45o

elbow (m)

LengthReduction 90o

elbow (m)

CoaxialSystemsø 60/100

Type 1

Between500 mm - 1 m

Between1 m - 4 m

4 m 0.5 m 1.0 mType 2

Type 3

CoaxialSystemsø 80/125

Type 1

TBC TBC 10 m TBC TBCType 2

Type 3

Twin PipeSystemsø 80/80

Type 4Between

1m - 10 mBetween

10 m - 40 m 40 m 1.4 m 2.2 m

Type 5Between

1m - 10 mBetween

10 m - 40 m 40 m 1.4 m 2.2 m

Page 20: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

20

Fig. 2.22

NOTE: DRAWINGS ARE INDICATIVE OF FLUEING OPTIONS ONLY.

TYPE 1

TYPE 5TYPE 4

TYPE 3TYPE 2

FIG. 2.21

Page 21: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

21

12

3 4

56

12

3 4

56

E C

II

I J KLEGEND:

A - On/Off ButtonB - Domestic Hot Water Temperature AdjustmentC - Central Heating Temperature AdjustmentD - Reset Button/Flue Test analysis mode*E - Comfort Mode Selector F - Summer Mode LED (Green)G - Ignition/Overheat Lockout LED (Red)H - Central Heating (Winter Mode) LED (Green)I - Digital Display (Fault Code/Water Temperature)J - Time ClockK- Central Heating System Pressure Gauge

2.10 CONTROL PANEL

FIG. 2.23FR020A

* Warning the flue analysis mode must only be selected by aqualified service engineer. See Section 3.4 for furtherinstructions

The Control Panel has a 3 digit display, during normaloperation the display will show one of six things on thetwo right hand digits;

During Stand-by (no demand for Central Heating or D.H.W.)‘on’ will be shown on the display and no LEDs will light.

During a demand for Domestic Hot Water, the temperature ofthe outgoing hot water is displayed in oC (e.g. 38) and thesummer mode LED will light (F - FIG. 2.23).

During a demand for Central Heating, the temperature of thecentral heating flow will be displayed in oC (e.g. 65) and thecentral heating mode LED will light (H - FIG. 2.23).

During the operation of the flue analysis mode* thedisplay will show ‘sc’.

Should a fault occur the display will show the fault codeand one of two letters, for a non-volatile shutdown theletter ‘A’ will be shown followed by the two digit code forthe fault eg. ‘A02’ and the red LED (G - FIG. 2.23) willlight, a non-volatile shutdown will require the reset button(D - FIG. 2.23) to be pressed once before the boiler willattempt to relight, should the boiler lockout again, theassistance of an Authorised Service Engineer should besought.

Should the boiler develop a fault that cannot be correctedby resetting the boiler, the letter ‘E ’ will be displayedfollowed by a two digit code (e.g. E33) indicating avolatile shutdown code, in the event of such a shutdown,the boiler will automatically resume operation once thecause behind it is resolved. Should it not, the assistanceof an Authorised Service Engineer would be required.

A list of the fault codes can be found opposite.

2.11 DIGITIAL DISPLAY AND FAULT CODES

DISPLAY CAUSE

AA 0011 No flame after safety time (7 seconds)

AA 0033 The heating flow temperature exceeds 103oCduring operation

AA 7777Condensate Trap full of waterCondensate sensor short circuitedCondensate sensor in open circuit

AA 7755 Problem with the flue stat

AA 9977 Problem with the electronic monitoring

AA 9988 Problem with the electronic monitoring

AA 9999 Problem with the electronic monitoring

EE 0022 Insufficient water pressure

EE 0044 Domestic hot water temperature probe in open circuit

EE 0055 Domestic hot water temperature probe short circuited

EE 0066 Heating flow temperature probe in open circuit

EE 0077 Heating flow temperature probe short circuited

EE 0088 Heating return temperature probe in open circuit

EE 0099 Heating return temperature probe short circuited

EE 2200 Flame detected with gas valve closed

EE 2211 Error in the electrical connection (live and neutral crossed)

EE 3333 The air pressure switch is closed before theignition sequence has begun

EE 3344 The air pressure switch does not close when the fan runs

EE 9999 More than 5 RESETS of the boiler in 15 minutes.

Page 22: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

22

In order to access the inside of the boiler, it is necessaryto unscrew the fastening screws “A” of the control panellocated on the lower part of the panel itself.The control panel moves downward and when pulledforward rotates on two lateral hinges.The panel stays in a horizontal position, which allowsaccess to the inner parts of the boiler.To dismantle the front casing panel it is necessary to:1 - Remove the two screws “B”;2 - Move the front casing panel up and lift forward.

2.12 REMOVING THE FRONT PANEL

To connect a room thermostat, it is necessary to:1. - Open the control panel as indicated in SECTION 2.12.2.- Remove the screws “A1” from the reverse of the

control panel (picture 3).3. - Inser t the thermostat cable through the cable

grommet and fasten it by means of the cable-clampprovided.

4. - Connect the thermostat wires to the terminal blockA2 (Picture 4) (Diagram A - Fig. 2.24).

5.- If a remote time clock is to be fitted, disconnect theintegral time clock from the P.C.B.

6. - Using a volt-free switching time clock, connect theswitching wires from the time clock following points 1-4 above (Diagram B - Fig. 2.24).

7. - If using an external time clock and room thermostat,these must be connected in series as Diagram C -Fig. 2.24.

Note: Only a low voltage room thermostat capable ofvolt free switching must be used.

Factory fitted integral wiring must not bedisturbed when wiring external controls.

Ensure high voltage and low voltage circuitsare cabled separately to avoid induced voltagein the low voltage circuits.

2.13 ROOM THERMOSTAT / REMOTE CLOCK

CONNECTION

FIG. 2.24

B

1

2

A

A1A1

3

4

A2

Page 23: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

23

2.14. FITTING THE DIGITAL CLOCK

The microGENUS HE boiler is supplied with a factoryfitted mechanical time clock. There is a digital clockavailable as an optional extra (code: 706348).

To fit the digital clock it is necessary to proceed asfollows:-

1. Remove the screws A (FIG. 2.25) and lower the controlpanel;

2. Remove the screws A1 (FIG. 2.26) to gain access tothe PCB,

3. Open the control panel (see Section 2.12);

4. Remove the screws D1 to gain access to themechanical time clock (FIG. 2.27)

5. Unplug the electrical connection from the PCB D7(FIG. 2.28) and unscrew the four screws (FIG. 2.29);

6. Connect the wires supplied with the replacement clockkit to the digital time clock as shown in FIG. 2.30;

7. Reassemble in reverse order.

NOTE: THE MECHANICAL CLOCK HAS FOUR WIRES, THEREFORE

THE HARNESS WILL REQUIRE CHANGING ALSO.

3 2 1

G B R

5 4 3 2 1

G B R

DIGITAL MECHANICAL

DIGITAL MECHANICAL

D6

A

A1

A1

D1

D1

D1

FIG. 2.25

FIG. 2.26

FIG. 2.27 FIG. 2.29

FIG. 2.30

D7

FIG. 2.28

D1

Page 24: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

24

2.15. SETTING THE MECHANICAL TIME CLOCK

2.16. SETTING THE DIGITALTIME CLOCK

12

3 4

56

12

3 4

56

E C

II

FIG. 2.31

1. General layoutThe mechanical clock covers a 24 hour period. Eachtappet represents 15 minutes A (Fig. 2.32). An overrideswitch is located on the clock B (Fig 2.32).

2.To set the timeTo set the time of day, grasp the outer edge of the dialand turn slowly clockwise until the correct time is linedup with the arrow C (Fig. 2.32).

3.To Set the "On" and "Off" timesThe clock uses a 24 hour system. e.g. 8 = 8.00 am and18 = 6.00 pm. "ON" periods are set by sliding alltappets between the "ON" time and the "OFF" time tothe outer edge of the dial.The tappets remaining at thecentre of the dial are the "OFF" periods.

4. For operationPut the selector switch B to the symbol to controlthe central heating by the clock. Put the switch B to «I»to select permanent operation or to «0» to turn thecentral heating off permanently.

112233

44

5566

7788

99

10101111

1212 1313 14141515

1616

17171818

19192020

2121

22222323

2424

99

66

1212

I

A

C

B

FIG. 2.32

Pro

g. hm

Day

Manual switch

Summer and winter time settingReset

Enter weekday/s

Enter the hours

Week- days flash

Enter minutes

Enter switching

times

Imput time

Operating the time switchThe steps marked with the symbol “ ” are necessary tocarry out a switching program.

Preparing for OperationActivate the “Res” switch (=RESET) to reset the timeswitch to its default setting (activate using a pencil orsimilar pointed instrument). Do this:- every time you wish to “reset” the time switch- to erase all switching times and the current time ofday.After approximately two seconds the following displayappears: “– – : – –”.

Enter current time and weekday- Keep the “ ” key pressed downDuring the summer time period press the +/- 1h keyonce.Enter the hour using the “h” keyEnter the minutes using the “m” keyEnter the day using the “Day” key1 = “Monday”..............7 = Sunday- Release the “ ” key.

Page 25: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

25

Automatic Manual Continuous Operation Operation Operation

The switching If the current You can only times corres- switching mode is return to automatic pond to the changed manually, mode from the program the next switching continuously-ON entered. time will be and continuously- carried out auto- OFF switching matically again modes by according to the pressing the " " entered switching key. program.

= ON = ON = Continuously ON

= OFF = OFF = Continuously OFF

Entering the switching timesYou have 20 memory Iocations available. Eachswitching time takes up one memory location.Keep pressing the “Prog” key until a free memorylocation is shown in the display “– –:– –”.Programme ON or OFF with the “ ” key:“ ”= OFF; “ ”= ONEnter the hour using “h”Enter the minutes using “m”If a switching command is to be carried out every day(1 2 3 4 5 6 7) then store using the “ ” key, otherwiseselect the day(s) it is to be carried out by using the“Day” key.When the day seIection is left bIank, the programmedswitching instruction operates at the same time everyday1 2 3 4 5 6 = Monday – Saturday1 2 3 4 5 = Monday – Friday6 7 =Saturday – Sunday

Selection of single days: 1 = Mon. .............. 2 =Tues.Save the switching time with the “ ” key.The time switch enters the automatic operating modeand displays the current time of day.Begin any further entry of a switching time with the“Prog” switch. If your entry is incomplete, thesegments not yet selected will blink in the display.After programming is completed, and you return thetime clock to the current time display with the “ ” key,the time clock wil l not activate any switchinginstruction required for the current time. You may needto manually select the desired switching state with the“ ” key. Thereafter, as the unit encounters furtherswitching instructions in the memory in real time, it willcorrectly activate all subsequent switchinginstructions.

Manual Override Switch “ ”With the “ ” you can change the current setting at anytime. The switching program already entered is notaltered.

Reading the programmed switching timesPressing the “Prog” key displays the programmedswitching times until the first free memory locationappears in the display “– – : – –”.

If you now press the “Prog” key once again, the number offree memory Iocations will be displayed, e.g. “18”. If allmemory locations are occupied, the display “00” appears.

Changing the programmed switching timesPress the “Prog” key repeatedly until the switching timeyou want to change is displayed. You can now enter thenew data. See point “Entering the switching times”.

Notes on storing switching times:If you end your entry of the switching times by pressingthe “Prog” key, then the switching time you have enteredwill be stored and the next memory location displayed.

In addition, a complete switching command is storedautomatically after around 90 seconds provided noother key is pressed. The time switch then enters theautomatic operating mode and displays the current timeagain.Deleting individual switching timesPress the “Prog” key repeatedly until the switching timeyou wish to delete is shown in the display. Then set to “––” using the “h” or “m” key and keep the “ ” key presseddown for around 3 seconds. The switching time is nowerased and the current time is displayed.

AM / PM time display If you press the “+/-1h” and “h” keys at the same time, thetime display switches into the AM/PM mode.

Page 26: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

26

2.17 ELECTRICAL/SYSTEM DIAGRAMS

FU

SE

FU

SE

12456 3

ON

56

AB

CN

203

CN

206

CN

206

CN

205

CN

203

CN

201

CN

303

CN

302

CN

201

CN

300

CN302

CN303

CN

304

CN

205C

N20

0

H L

M

I

NO

P

Q

Blk

Blk

Blk

Blk

Gry

GryGryGry

Gry

Pnk

PnkPnk

Gry or Bl

Wh

WhWh

Rd

Rd

Rd

Rd

Rd

Blk

BlkBlk

BlkBrnBrnBrnBl

Bl

Bl

Bl

Blk

12

34

56

78

A16

WhWh

Wh

FIG. 2.33

Page 27: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

27

A - Dip SwitchesB - Summer/Winter Switch - Central Heating Temperature

RegulationC - Connector for Remote Control (Climate Manager)D - Domestic Hot Water Temperature RegulationE - Soft-light RegulationF - Maximum Central Heating Temperature RegulationG - ON/OFF SelectorH - EEPROMI - Time Clock ConnectorL - Release Push ButtonM - Economy/Comfort SelectorN - EASY Teleservice (optional) P.C.B. SectionO - Display P.C.B. ConnectorP - TransformerQ- Modem Connection (optional - EASY Teleservice)

A01 - Circulation PumpA02 - FanA03 - Spark Generator Power SupplyA04 - Gas Valve Power SupplyA05 - Motorised ValveA07 - Flame SensorA08 - Central Heating Flow NTCA09 - Domestic Hot Water NTCA10 - Domestic Hot Water Flow SwitchA11 - Low Water Pressure SwitchA12 - ModulatorA13 - Air Pressure SwitchA14 - Overheat ThermostatA15 - External Timer/Room ThermostatA16 - Condensate SensorA17 - Fume Sensor

COLOURS:Gy - Grey Wh - WhiteRd - RedBr - BrownBl - BlueBk - BlackPk - Pink

A - Dip Switch:1 - Do Not Use (jumper is factory set in position B)2 - Anti-Cycling Device Adjustment for Heating

Position A = 0 mins Position B = 2 mins3 - Do Not Use (jumper is factory set in position B)4 - Do Not Use (jumper is factory set in position B)5 - Fan over-run selector (after D.H.W. is drawn)

Position A = OFF Position B = ON6 - Do Not Use (jumper is factory set in position A)

ATTENTIONWHEN REPLACING THE PCB, REMOVE THE

EXISITING EEPROM KEY AND REPLACE WITH THE

CORRECT EEPROM SUPPLIED WITH THE SPARE

PART.

H

12

45

63

A B

Page 28: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

28

1

2

3

4

5

67

8

9

10

11A B C D E

12 13 14 15 16

1718

20

19

21

22

23

24

LEGEND:

1. Fan2. Heat Exchanger3. Overheat Thermostat 4. Central Heating Flow NTC5. Burner 6. Detection Electrode7. Ignition Electrodes8. Diverter Valve9. Low Water Pressure Switch10. Drain Valve11. Domestic Hot Water Temperature NTC12. Secondary Heat Exchanger13. Gas Valve14. D.H.W. Flow Switch15. D.H.W. Inlet Filter16. Automatic By-pass17. Safety Valve18. Pressure Gauge19. Circulation Pump with Automatic Air Release Valve20. Condensate Trap21. Expansion Vessel22. Condensate Sensor23. Latent Heat Collector24. Air Pressure Switch

2.18 WATER CIRCUIT DIAGRAM

FIG. 2.34

SI016C

A. Central Heating FlowB. Domestic Hot Water OutletC. Gas InletD. Domestic Cold Water InletE. Central Heating Return

Page 29: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

29

MTS (GB) Limited support the initiative. InSections 11 and 12 of this manual you will find the

commissioning checklist (page 68) and theservice interval record (Page 69), It is important that the

commissioning checklist is completed in thepresence of your customer, they are shown how to use it,and it is signed by them. Please instruct your customerthat they must have this manual with them whenever theycontact a service engineer or us.

Carry out preliminary electrical system checks to ensureelectrical safety, this must be carried out by a competentperson i.e. polarity, earth continuity, resistance to earthand short circuit.

FILLING THE HEATING SYSTEM:Lower the control panel and remove the case panels(see SECTION 2.12 for further information).Open the central heating flow and return cockssupplied with the connection kit.Unscrew the cap on the automatic air release valve onefull turn and leave open permanently.Close all air release valves on the central heatingsystem.Gradually open valve(s) at the filling point (filling-loop)connection to the central heating system until water isheard to flow, do not open fully.Open each air release tap starting with the lowest pointand close them only when clear water, free of air, isvisible.Purge the air from the pump by unscrewing thepump plug anticlockwise, also manually rotate thepump shaft in the direction indicated by the pumplabel to ensure the pump is free.Refit the pump plug.Continue fill ing the system until at least 1.5 barregisters on the pressure gauge..Inspect the system for water soundness and remedyany leaks discovered.

FILLING OF THE D.H.W. SYSTEM:Close all hot water draw-off taps.Open the cold water inlet cock supplied with theconnection kit.Open slowly each draw-off tap and close them onlywhen clear water, free of bubbles, is visible.

GAS SUPPLY:Inspect the entire installation including the gas meter,test for tightness and purge the supply as described inBS 6891:1998.Open the gas cock (supplied with the connection kit) tothe appliance and check the gas connections on theappliance for leaks.

WATER TREATMENT

The detailed recommendations for water treatment aregiven in BS 7593:1992 (Treatment of water in domestichot water central heating systems); the following notesare given for general guidance:

3. COMMISSIONING

3.1 INITIAL PREPARATION

Page 30: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

30

- If the boiler is installed in an existing system, anyunsuitable additives must be removed prior to the fittingof the boiler;

- Under no circumstances should the boiler be firedbefore the system has been thoroughly flushed; theflushing procedure must be in line with BS7593:1992.Firstly fill the central heating system and boiler with thepower off, flush through cold and completely drain thesystem, fill the central heating system again, add aflushing detergent, we highly recommend the use of aflushing detergent appropriate for the metals used inthe circuit. These include (Fernox Superfloc,BetzDearborn Sentinel X300 or X400), whose functionis to dissolve any foreign matter that may be in thesystem, and run the boiler on central heating until itreaches its operating temperature, flushand drain thesystem completely, and refill the system with a suitablecorrosion inhibitor such as Fernox Copal MB-1, orBetzDeaborn Sentinel X100 is recommended.

NOTE: FAILURE TO CARRY OUT THE FLUSHING PROCEDURE WILL

RESULT IN THE WARRANTY BECOMING VOID.

Page 31: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

31

3.2 INITIAL START-UP THE CHECKS TO BE RUN BEFORE INITIAL START-UP ARE AS

FOLLOWS:1. Make sure that:

- the screw on the automatic air valve has been loosenedwhen the system is full;

- If the water pressure in the system isbelow 1.5 bar, bring it up to theappropriate level;

-Ensure that the gas cock is closed(FIG. 3.1);

-Make sure that the electr icalconnection has been made properly and that the earthwire is connected to an efficient earthing system;

- Supply power to the boiler by turning the On/Off knob“A” (see FIG. 3.2) - on the display will appear “on”. Turnthe knob “C” to maximum and switch the time clock toconstant.After 7 seconds, the boiler will signal a shutdown due toignition failure. Leave the boiler as it is until all of the airhas been bled from the system.

-Loosen the cap on the head of the pump to eliminateany air pockets;

-Repeat the procedure for bleeding the radiators of air;-Open the hot water taps for a brief period;-Check the system pressure and, if it has dropped, open

the filling loop again to bring the pressure back up to1.5 bar.

2. Make sure that all radiator valves are open;

3. Check the flue system for products ofcombustion, tightness and stability.

4. Fill the boiler condensate trapwith water.N.B. In the event of a prolongedperiod of system shutdown, the condensate trapshould be filled before any renewed use. Ashortage of water in the trap could temporarily leadto fumes leaking into the air.

5. Turn on the gas cock (FIG. 3.3) and check the seals onthe connections with an approved soap solution andeliminate any leaks.

6. Press the reset button “D” (see FIG. 3.4) the boiler willre-attempt ignition. If the burner does not light the firsttime, wait 1 minute, purge the gas and repeat theprocedure.

7. Run the boiler in Hot Water mode and bleed air from thesystem

8. Check the minimum and maximum burner pressurevalues; adjust if necessary using the values indicated inthe table in SECTION 4 (Page 36).

12

3 4

56

12

3 4

56

E C

II

D

12

3 4

56

12

3 4

56

E C

IIA

C

FIG. 3.1

Fig. 3.3

FIG. 3.2

FIG. 3.4

Page 32: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

32

In the boiler, it is possible to monitor the correct operationof the flue exhaust/air intake, checking for a loss ofgeneral pressure in the system. Through the use of adifferential manometer connected to the test points of thecombustion chamber, it is possible to detect the DP ofoperation of the air pressure switch.The value detected should not be less than 0.55 mbarunder conditions of maximum thermal power (see Section3.4), in order for the boiler to function properly andwithout interruption.

The flue connector has two apertures, readings can betaken for the temperature of the combustion products andof the combustion air, as well as of the concentrations ofO2 and CO2, etc.To access these intakes it is necessary to unscrew thefront screw and remove the metal plate with sealinggasket.It is possible to activate the flue test mode (maximumoutput) by pressing and holding the RESET button “D” for10 seconds, “sscc” will be shown on the display. The boilerwill return to normal operation after 5 minutes. The boilercan be returned to normal operation sooner by switchingthe boiler off and on again.

3.4 COMBUSTION ANALYSIS

3.5 PRODUCT OF COMBUSTION

DISCHARGE MONITORING

FU008A

FU009A

To access the areas in which adjustments are made, it isnecessary to open the control panel, as indicated inSECTION 2.12, then remove the rear inspection cover byunscrewing the two screws “A”. Access is therebyprovided to the P.C.B. and to the following components:1. The power supply cable connector;2. The fuses;3. The soft-light potentiometer must be set to ensure

correct ignition;4. The maximum thermal heating power potentiometer

adjustable by the minimum to maximum power(already calibrated in the factory to 70% of themaximum thermal power in Central Heating mode);

5. The dip switch for adjusting the ignition delay (anti-cycling) feature, which can be set from off to 2minutes (set in the factory to off);

6. Fan/Pump Over-run (Electrical Diagram). When thejumper is set to position A the Fan and Pump over-run isactivated. (The jumper is factory set in position B)

7. The time clock connector.

NOTE: SEE PAGE 27 FOR DIP SWITCH LOCATION.

3.3 OPERATIONAL

ADJUSTMENTS

A A

The boiler allows the convenience level to be increased inthe output of domestic hot water by means of the“COMFORT” function. This function keeps the secondaryexchanger warm during the periods in which the boiler isinactive, thereby allowing the initial water drawn to be at ahigher temperature.The function may be activated by pressing turning theCOMFORT switch ‘E’ on the control panel from E to C(see section 2.10).

3.6 COMFORT MODE

Page 33: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

33

3.7 BOILER SAFETY SYSTEMS The boiler is protected from malfunctioning by means ofinternal checks by the P.C.B.,which brings the boiler to a stop ifnecessary.

There are two types of shut-off:• SHUTDOWN (A)• SAFETY SHUTDOWN (E)

SHUTDOWN “AA ”This type of appliance shutdown is called “non-volatile”, andis indicated on the display by a number preceded by theletter (A) , and by the symbol (G FIG. 2.23 Page 21), asillustrated in the table below:

WARNING! The boiler is still powered.

ImportantIf this shutdown occurs frequently, contact anauthorised Service Centre for assistance. For safetyreasons, the boiler will allow a maximum of 5 resetoperations to take place in 15 minutes (pressing theRESET button).If the shutdown is occasional or an isolated event, this isnot necessarily a problem.

12

3 4

56

12

3 4

56

E C

II

D

SAFETY SHUTDOWN “E”In the event of a safety cut-off (displayed with the codeshown in the table), the boiler will automatically try to resetitself and relight. Should this not be the case, contact anauthorised Service Centre for assistance.

12

3 4

56

12

3 4

56

E C

II

DISPLAY CAUSE

AA 0011 No flame after safety time (7 seconds)

AA 0033 The heating flow temperature exceeds 103oCduring operation

AA 7777Condensate Trap full of waterCondensate sensor short circuitedCondensate sensor in open circuit

AA 7755 Flue temperature thermostat overheating

AA 9977 Problem with the electronic monitoring

AA 9988 Problem with the electronic monitoring

AA 9999 Problem with the electronic monitoring

DISPLAY CAUSE

EE 0022 Insufficient water pressure

EE 0044 Domestic hot water temperature probe in open circuit

EE 0055 Domestic hot water temperature probe short circuited

EE 0066 Heating flow temperature probe in open circuit

EE 0077 Heating flow temperature probe short circuited

EE 0088 Heating return temperature probe in open circuit

EE 0099 Heating return temperature probe short circuited

EE 2200 Flame detected with gas valve closed

EE 2211 Error in the electrical connection (live and neutral crossed)

EE 3333 The air pressure switch isclosed before the ignition sequence

EE 3344 The air pressure switch does not close when the fan runs

EE 9999 More than 5 RESETS of the boiler in 15 minutes.

Page 34: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

34

DRAINING THE HEATING SYSTEM

The heating system must be drained as follows:- Turn off the boiler;- Attach a hose pipe and open the drain valve;- Drain the system at the lowest points (where present).

When the heating system is unused for an extendedperiod of time, it is recommended that you addantifreeze with an ethylene glycol base to the water inthe heating pipe work and radiators if the ambienttemperature drops below 0°C during the winter.This makes repeated draining of the entire systemunnecessary.

DRAINING THE DOMESTIC HOT WATER SYSTEM

Whenever there is the danger of the temperaturedropping below the freezing point, the domestic hotwater system must be drained as follows:

- Turn off the general water valve for the householdplumbing system;

- Turn on all the hot water taps;- Empty the remaining water from the lowest points in

the system (where present).

3.8 DRAINING THE SYSTEM

ANTI-FROST DEVICE:The boiler is equipped with an anti-frost device which,operates in two ways depending on the water temperature:

Temperature @ Flow Sensor below 8oC;The pump will run at speed 2 for 2 mins (1 minute in CHand 1 minute in DHW).After 2 minutes the PCB will check the temperature at theReturn Sensor, should the temperature be 8oC or higherthe boiler will return to stand-by.Should the temperature remain between 5oC & 8oC thepump will continue to operate for a further 2 minutes, withthe diverter valve switching between CH and DHW asbefore, this will continue for a maximum of 10 minutes,after 10 minutes of this operation the burner will fire atminumum power unti l the Return Sensor reads atemperature of 33oC, there will then be 2 minutes of pumpover-run in the DHW circuit.

Temperature @ Flow Sensor below 5oC;The burner will fire at minimum power in CH until theReturn Sensor reads a temperature of 33oC, onceachieved there will be 2 minutes of pump over-run in theDHW circuit.

NOTE: IN THE EVENT OF FLAME FAILURE, AND THE TEMPERATURE

IS BELOW 5OC THE PUMP WILL OPERATE FOR 2 MINS

(1 MIN CH AND 1 MIN DHW).

This device only operates if the boiler is functioningperfectly and:- the system pressure is sufficient;- the boiler is powered electrically;- the gas is turned on.

PUMP / DIVERTER VALVE PROTECTION:To prevent the pump and diverter valve from siezing theboiler will activate the pump for 20 seconds every 21 hoursafter it’s last operation and activate the diverter valve once.

Page 35: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

35

3.9 COMPLETION For the Republic of Ireland it is necessary to complete a“Declaration of Conformity” to indicate compliance to I.S.813. An example of this is given in the current edtion ofI.S. 813. In addition it is necessary to complete the

Commissioning Checklist, (Section 11, page 68).

3.10 OPERATIONAL CHECKS 1. The flue system must be visibly checked forsoundness.

2. On Central Heating allow the system to warm up andmanipulate the Central Heating temperature controlknob, check the burner modulates up and downbetween the high and low settings;

3. Range rate the thermal power for Central Heating, asdetailed in SECTION 4.2 (page 39);

4. Check and adjust the soft-light setting, as detailed inSECTION 4.2 (page 39);

5. Run the Domestic Hot Water, manipulate the DomesticHot Water temperature control knob to check theburner modulates up and down between the high andlow settings and check the gas rate at the meter;

6. Set the Domestic Hot Water flow rate;

7. Balance the Central Heating system until all returntemperatures are correct and equal;

8. Turn the ON/OFF button OFF, disconnect the gaspressure gauge, retighten screw test for sondness andrelight boiler.

9. Re-examine Central Heating, Domestic Hot Water andCold Water supplies for soundness.

10.Check the appearance of the gas flame to assess theadequacy of the combustion air supply.

11. If external controls have been disconnected, reconnect and test.

12. Refit boiler casing.

Page 36: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

36

1. Hand over the copy of the End User Instructionssupplied with the appliance, together with theseinstructions, and explain how to use the timeclock androom thermostat if fitted.

2. Show the End User how to switch the appliance offquickly, and indicate the position of the electric supplyisolator.

3. Inform the End User of the location of all drains,isolating valves and air vents.

4. Explain how to turn the appliance off for both shortand long periods and advise on the precautionsnecessary to prevent damage in the event that theappliance is inoperative when freezing conditionsoccur.

5. Finally advise the End User that, for continued safeand efficient operation, the appliance must beserviced by a competent person at least once a year,ensuring that the Service Interval Record is completed(Section 12, page 69).

3.11 INSTRUCTING THE END USER

Page 37: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

37

4. GAS ADJUSTMENTS

CATEGORY II2H3+ Methane GasG20

Liquid Butane GasG31

Liquid Propane GasG30

Lower Wobbe Index (15°C;1013mbar) MJ/m3hNominal Delivery Pressure mbarMinimum Delivery Pressure mbar

45.672020

80.582928

80.583736

0.70---

2.86 - 0.85

35.6 - 6.8

0.78---

2.17 - 0.93

36.0 - 7.1

0.78---

2.45 - 0.93

36.0 - 7.0

0.70---

1.89 - 0.87

29.0 - 5.5

0.74---

2.21 - 0.95

27.5 - 5.4

0.74---

2.48 - 0.95

28.0 - 5.4

1.302.54 - 1.16

---

7.5 - 1.7

1.302.96 - 1.27

---

9.5 - 1.8

1.303.33 - 1.27

---

12.0 - 1.8

microGENUS HE 24 MFFIMain Burner: n. 14 jets (ø) mmConsumption (15°C; 1013mbar) max - min m3/hConsumption (15°C; 1013mbar) max - min Kg/hGas Burner Pressuremax - min mbarmicroGENUS HE 28 MFFIMain Burner: n. 14 jets (ø) mmConsumption (15°C; 1013mbar) max - min m3/hConsumption (15°C; 1013mbar) max - min Kg/hGas Burner Pressuremax - min mbarmicroGENUS HE 32 MFFIMain Burner: n. 14 jets (ø) mmConsumption (15°C; 1013mbar) max - min m3/hConsumption (15°C; 1013mbar) max - min Kg/hGas Burner Pressuremax - min mbar

The boiler can be converted to use either methane(natural) gas (G20) or L.P.G. (G30 - G31) by a CORGIregistered Gas Engineer.

The operations that must be performed are the following:

1. Replace the jets on the main burner (see Table A);

2. Adjust the maximum and minimum thermal capacityvalues for the boiler (Section 4.2 Adjusting the GasPressures);

3. Adjust the maximum thermal power setting (Page 39and TABLE B 40);

4. Adjust the soft-light feature (see Table opposite forrecommended pressure and Fig. 4.1 see page 39);

5. Adjust the ignition delay feature for the heating systemby adjusting the dip switch as indicated in Section 2.17(FIG. 2.34). It can be turned on or off.

4.1 CHANGING THE TYPE OF GAS

CATEGORYII2H3+

Methane

GasG20

LiquidButane

GasG31

LiquidPropane

GasG30

Soft-lightPressure (mbar)

24 kW Model

28 kW Model

32 kW Model

5.0

5.5

5.5

12.0

12.0

12.0

12.0

12.0

12.0

TABLE A

SOFT LIGHT PRESSURES

Page 38: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

38

Setting the minimum and the maximum power of theboiler1. Check that the supply pressure and dynamic working

pressure to the gas valve is a minimum of 20 mbar fornatural gas and 29 and 37 mbar for LPG (G30 or G31).

2. To do this, loosen the screw “A”.Fit the pipe of the pressure gauge to the inlet pressureconnection of the gas valve “B” and check for thecorrect standing pressure, then operate the applianceand check for the correct working pressure.When you have completed this operation, replace thescrew “A” securely into its housing to seal off the gas(check for tightness).

3. To check the pressure supplied by the gas valve to theburner, loosen the screw “C”. Fit the pipe of thepressure gauge to the pressure outlet test point of thegas valve “D”.Disconnect the compensation pipe “D1” either fromthe gas valve or from the sealed chamber.

4. Turn the On/Off knob to “ON” position -green light- andensure that the hot water temperature control knob isset to maximum.Turn on the boiler by running a hot water tap.Adjust the 10mm nut “E” on the modureg to set themaximum gas pressure, turn the nut clockwise toincrease and anti clockwise to decrease the pressureuntil the required pressure is achieved (see TABLE APage 37).

5. To set the minimum power, disconnect a supplyterminal “F1” from the modureg and adjust screw “F”(ensure that the 10mm nut is held in position). Turn thescrew clockwise to increase the pressure and anti-clockwise to decrease the pressure (displayed on thepressure gauge) corresponding to the minimum power(see TABLE A Page 36).

IMPORTANT!Whenever you disassemble and reassemble the gasconnections, always check for leaks using a leakdetection fluid.

4.2 ADJUSTING THE GAS PRESSURES

AA

BB

C D

1

2

E

F

3

4

B

C

E

F

D

D1

F1

A

Page 39: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

39

12

45

63

ON

A B

CN203 CN206

CN201

CN200

Soft-light Adjustment

Max Heating Power

6. When you have completed the above operations, turnoff the hot water tap, reconnect the supply terminal tothe modureg on the gas valve, reconnect thecompensation pipe and replace the cap on the screwof the modureg.

Setting the maximum heating circuit power

1. To set the maximum heating circuit power, turn theOn/Off knob to the “ON” position and set the time clockand any external controls to the “ON” position. Turn theknob of the heating thermostat clockwise to maximum.

2. Remove the inspection panel of the P.C.B. and fit asmall cross-head screwdriver in to the right handpotentiometer (max. heating power).Turn clockwise to increase the pressure or anti-clockwise to reduce the pressure. Adjust the setting tothe required heating value (displayed on the pressuregauge), as indicated in Table B shown on Page 40.

3. Turn off the boiler by placing the main switch to the"OFF" position.

Setting the pressure for soft-light ignition.

1. Disconnect the detection electrode connection close tothe P.C.B. (FIG. 4.1);

2. Start the boiler and during the ignition sequence adjustthe left hand potentiometer until the gas pressurereads the required gas pressure (Soft-light pressuretable - Page 37);

3. Once the gas pressure is set turn off the boiler and re-connect the detection electrode to the P.C.B.NB.: It may be necessary to reset the flame failurereset a number of times during this operation;

4. Remove the pipe from the test point and tighten thescrew “C” and test for tightness;

5. Carefully check the pressure test points for gas leaks(both inlet and outlet).

FIG. 4.1

Page 40: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

40

Regulating the heatingpower for natural gas (G20)

Regulating the heatingpower for butane gas (G30)

Regulating the heatingpower for propane gas (G31)

3434363638384040

model 24

model 28

model 32

model 24

model 28

model 32

model 24

model 28

model 32

Bu

rner

pre

ssu

reB

urn

er p

ress

ure

Bu

rner

pre

ssu

re

TABLE B

Page 41: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

41

It is recommended that the following inspections becarried out on the boiler at least once a year:

1. Visually check the appliance for correct installation;

2. Check the appliance for the correct operation;

3. Check the flue and flue installation for correct siting, installation and that it is in good condition.;

4. Remove the casing as described in Section 7.2;

5. Check the operation of the safety devices:- Air Pressure Switch;- Overheat Thermostat;- Safety Valve;- Pump Pressure Switch;- Ionisation (Flame Detection);

6. Drain the boiler and check the pressure in the expansion vessel, ensuring it is 0.7 bar;

7. Remove the diverter valve motor and clean the actuators, replacing any damaged seals as necessary (see Exploded View on Pages 63 & 64 for more details);

8. Remove, clean and refill the condensate trap and condensate hoses (see Section 6.3.10), check the drain system for correct discharge of condensate and clean if necessary;

9. Remove and clean the DHW flow switch;

10. Remove and clean the fan;

11. Remove and clean the electrodes with an emery cloth;

12. Remove and clean the burner;

13. Check and clean the primary heat exchanger as necessary;

14. Refill the boiler and check the following;

15. Check gas inlet pressure and correct working pressure;

17. Check the gas rate;

18. Check the correct operations of the timeclock and room thermostat;

19. Check the DHW flow rates;

20. Advise the customer on the correct use of the appliance (clock setting and operation, repressurising etc.);

21. Complete the Service Interval Record (Section 12, page 69).

5. MAINTENANCE

Page 42: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

42

FIG. 6.3

B

FIG. 6.4

6. SERVICING INSTRUCTIONS

The life of individual components vary and they will needservicing or replacing as and when faults develop.The fault finding sequence chart in SECTION 7 will help tolocate which component is the cause of any malfunction,and instructions for removal, inspection and replacementof the individual parts are given in the following pages.

6.1 REPLACEMENT OF PARTS

6.2 TO GAIN GENERAL ACCESS

All testing and maintenance operations on the boilerrequire the control panel to be lowered. This will alsorequire the removal of the casing.

6.2.1 Removing the front panel

1. Loosen the fastening screws “A” of the control panellocated on the lower part of the panel itself. (FIG. 6.1);

2. The control rotates on two lateral hinges; the panelstays in a horizontal position, which allows access tothe inner parts of the boiler (FIG. 6.2);

3. Remove the screws “B” from the front panel bottom lip (FIG. 6.3);

4. Lift the front panel up and forward from the raised screwsat the the top of the casing (FIG. 6.4).

A

FIG. 6.1

FIG. 6.2

To ensure efficient safe operation, it is recommended thatthe boiler is serviced annually by a competent person.

Before starting any servicing work, ensure both thegas and electrical supplies to the boiler are isolatedand the boiler is cool and suitable protective clothingis worn.Before and after servicing, a combustion analysis shouldbe made via the flue sampling point (please refer toSECTION 3.4 for further details).

After servicing, preliminary electrical system checks mustbe carried out to ensure electrical safety (i.e. polarity,earth continuity, resistance to earth and short circuit).

Page 43: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

43

6.2.2 Removing the sealed chamber front cover

1. Remove the screws “C” (FIG. 6.5);2. Lift the sealed chamber front cover from the locating

pins (FIG. 6.6).

FIG. 6.5

C C

FIG. 6.6

6.2.3 Removing the side panels

1. Remove the four screws “D” for each side panel(FIG.6.7);

2. Pull the panel away from the boiler at the base, then liftthe panel up and remove from the boiler.

D

D

D

FIG. 6.7

D

Page 44: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

44

6.3.3 Removing the electrodes

Before carrying out this procedure, unscrew and slide theburner forward (see previous section).1. Remove rubber gasket “G” (FIG. 6.11);2. To remove the detection electrode disconnect the cable at

its connection point close to the P.C.B. (FIG. 6.12);3. Remove screw “H” (FIG. 6.13);4. Gently slide the electrode downward (FIG. 6.14).

6.3.2 Removing the burner and jets

1. Remove the screws “F” from the burner (FIG. 6.9);2. Remove the burner (FIG. 6.10);3. Disconnect the electrodes (see SECTION 6.3.3);4. Remove the jets using a No. 7 socket spanner;5. Replace in reverse order.

6.3.1 Removing the combustion cover

1. Remove the screws “E” (FIG. 6.8);2. Lift off the combustion cover.

6.3 ACCESS TO THE COMBUSTION CHAMBER

EE

FIG. 6.8

E E

FIG. 6.9

F

F

FIG. 6.10

FIG. 6.11

FIG. 6.12

G

Page 45: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

45

To replace, repeat the steps in reverse order, payingparticular attention to the following:a - Centre the electrode in the positioning hole carefully,

otherwise the electrode may break;b -Ensure that the left hand and right hand electrodes are

located the correct way round (facing each other), togive the correct spark gap;

c - Check that the cables have been connected correctly;d -Check that the rubber gasket seals the cable/

electrode connection point completely.

FIG. 6.13

FIG. 6.14

H

1. Drain the boiler of water;2. Remove the side panels (see 6.2.3)3. Remove the overheat thermostat sensor “H” (FIG. 6.15);4. Remove the clips “I” (FIG. 6.15);5. Release the connection nut “J” (FIG. 6.16);6. Release the connection nut “K” (FIG. 6.17);7. Pull down the pipe (FIG. 6.18);8. Pull it straight out (FIG. 6.19).

6.3.4 Removing the main heat exchanger

FIG. 6.15

FIG. 6.16

FIG. 6.17

H

I

J

K

I

Page 46: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

46

1. Disconnect the electrical connections “L” and siliconepipes “M” from their connection points (FIG. 6.20);

2. Remove screws “N” on the top of the sealed chamber(FIG. 6.21);

3. Lift out the air pressure switch;4. Unscrew the two screws “O” to remove the switch from

the plate (FIG. 6.22 - 6.23);5. Reassemble in reverse order.

6.3.5 Removing the air pressure switch

FIG. 6.18

FIG. 6.19

FIG. 6.20

M L

FIG. 6.21

FIG. 6.22

FIG. 6.23

N

O

Page 47: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

47

1. Remove screw “P” (FIG.6.24);2. Disconnect electrical connections “Q” and silicone pipe

“Q1” (FIG.6.25);3. Remove fan and gasket “R” (FIG.6.26).4. Reassemble in reverse order, ensuring the gasket “R”

is seated correctly.

6.3.6 Removing the fan

1. To remove the flue sensor, disconnect electricalconnections “S” (FIG.6.27);

2. Remove screws “T” and remove the flue sensor (FIG.6.28 - 6.29).

3. To remove the condensate sensor, remove screws “T1”and remove the condensate sensor (resistor wire)(FIG.6.27);

6.3.7 Removing the flue sensor and condensate sensor

FIG. 6.24

FIG. 6.25

FIG. 6.26

R

Q

Q

P

FIG. 6.27

FIG. 6.28

FIG. 6.29

S

T

S1

Q1

Page 48: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

48

1. Remove the U-clips “U” (FIG.6.30);2. Remove the clamp “V” to disconnect the condensate

trap tube (FIG.6.31);3. Loosen the nut “W” (FIG.6.32);4. Remove the four screws “X” (FIG.6.33);5. Remove the recuperator (FIG.6.34 - 6.35);6. Reassembled in reverse order.

6.3.8 Removing the Recuperator

FIG. 6.32

FIG. 6.33

FIG. 6.31

V

W

FIG. 6.30

U

X

X

FIG. 6.34

FIG. 6.35

Page 49: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

49

1. Remove the recuperator - see paragraph. 6.3.82. Unscrew the two screws “Y” (FIG.6.36);3. Remove the recuperator housing (FIG.6.37);4. Reassemble in reverse order.

THE SIDE COVER OF THE RECUPERATOR MUST NOT BE REMOVED,THE TWO SCREWS ARE COVERED BY SECURITY PAINT, THERE IS A

DANGER THAT FLUE GASSES COULD LEAK INTO THE ROOM IF THE

FRONT COVER IS REMOVED.

SHOULD IT BE NECESSARY TO REMOVE THE RECUPERATOR, THE

WHOLE UNIT MUST BE REMOVED.

6.3.9 Removing the Recuperator Housing

FIG. 6.36

Y

Y

FIG. 6.37

1. Remove the clamp “Z” (FIG.6.38);2. Remove the clamp “A1” (FIG.6.39);3. Unscrew and remove the trap from the boiler (FIG.6.40);3. Remove the trap (FIG.6.41).4. Reassemble in reverse order

6.3.10 Removing the Condensate Trap

FIG. 6.38

Z

FIG. 6.39

FIG. 6.40

FIG. 6.41

A1

Page 50: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

50

FIG. 6.46

FIG. 6.47

A5A5

6.4.2 Removing the gas valve (Honeywell)

Important! Before removing the gas valve, ensure thegas supply is turned off.

1. Disconnect all the cables from the solenoid andmodureg;

2. Remove the spark generator (see previous section);3. Release the nuts “A4” (FIG. 6.45);4. Remove the screws “A5” from the bottom of the gas

valve (FIG. 6.46);5. Remove the gas valve (FIG. 6.47).

FIG. 6.45

A4

A4

6.4.1. Removing the spark generator

1. Disconnect the ignition leads “A2” by pulling upward(FIG. 6.42);

2. Remove the screw “A3” (FIG. 6.43);3. Remove the spark generator by pulling forward from

the gas valve (FIG. 6.44).

FIG. 6.42

FIG. 6.43

FIG. 6.44

A2

A3

6.4 ACCESS TO THE GAS VALVE

Page 51: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

51

Important! Before any component is removed, the boilermust be drained of all water.

6.5.1 Removing the D.H.W. (secondary) exchanger

1.Remove the condensate trap - see Section. 6.3.10;2.Remove the screws “A6” (FIG 6.48);3.Disconnect the cable “A7” (FIG 6.49);4.Push the insulation of the exchanger towards the rear

of the boiler, and lift upwards and remove from thefront of the boiler (FIG 6.50);

5.Push the exchanger towards the rear of the boiler, andlift upwards and remove from the front of the boiler (FIG 6.51);

6.Before replacing the exchanger ensure that the O-ringsare in good condition and replace if necessary.

6.5 ACCESS TO THE WATER CIRCUIT

FIG. 6.48

A6A6

FIG. 6.49

FIG. 6.50

A7

FIG. 6.51

Page 52: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

52

6.5.2 Removing the pump pressure switch

1.Remove the pump pressure switch electrical connections“A8” (FIG 6.52);

2.Unscrew the pump pressure switch by using a spanner onthe nut (FIG 6.53);

3.Remove the pump pressure switch (FIG 6.54).

FIG. 6.52

A8 A8

FIG. 6.53

FIG. 6.54

6.5.3 Removing the safety valve

1. Disconnect the discharge pipe work from below theboiler;

2. Unscrew the fixing screw “A9” (FIG. 6.56)3. Pull the valve upwards to remove (FIG. 6.57).

FIG. 6.55

FIG. 6.56

FIG. 6.57

A9

Page 53: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

53

6.5.4 Removing the automatic air vent

1. Remove the U-clip “B1” (FIG. 6.58);2. Remove valve complete with float using a screwdriver

(FIG 6.59-FIG 6.60).

FIG. 6.58

FIG. 6.59

FIG. 6.60

B1

6.5.5 Removing the pump

1. Remove the electrical connetction “ B2” (FIG. 6.61);2. Release the nut “B3” (FIG. 6.62);3. Remove the retainig clip “B4” from the side of the

pump housing (FIG. 6.63);4. Remove the screw “B5” (FIG. 6.64);5. Remove the U-clip “B6” and remove the pressure

gauge connection (FIG. 6.65);6. Remove the U-clip “B7” and remove the automatic air

vent (FIG. 6.66);7. Remove the pump.

FIG. 6.61

B2

FIG. 6.62

B3

FIG. 6.63

B4

Page 54: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

54

FIG. 6.64

FIG. 6.66

FIG. 6.65

B5

B6

B7

6.5.6 Removing the pressure gauge

1. Remove the U-clip “B8” (FIG. 6.67)2. Push the pressure gauge through the control panel

from the rear using a screwdriver (FIG. 6.68-6.69).

B8

FIG. 6.68

FIG. 6.69

FIG. 6.67

Page 55: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

55

6.5.7 Removing the expansion vessel

1. If rear exit flue, remove the flue;2. Release nut “B9” (FIG. 6.70);3. Remove back-nut “C1” (FIG. 6.71);4. Remove the expansion vessel (FIG. 6.72).

FIG. 6.70

B9

FIG. 6.71

FIG. 6.72

C1

6.5.8 Removing the overheat thermostat

1. Disconnect the overheat thermostat electr icalconnections “C2” (FIG. 6.73);

2. Then remove the thermostat from its mounting byreleasing the securing clip (FIG. 6.74-6.75).

FIG. 6.73

FIG. 6.74

C2

FIG. 6.75

Page 56: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

56

6.5.10 Removing the D.H.W. temperature sensor (N.T.C.)

1. Pull off the electrical connector and unscrew thesensor probe using a suitable spanner (FIG. 6.78).

6.5.11 Removing the diverter valve actuator

1. Unplug the electrical connector “C3” (FIG. 6.79);2. Release the retaining clip “C4” and remove the diverter

valve actuator

6.5.9 Removing the C.H. temperature sensor (N.T.C.)

1. Pull off the electrical connector and remove the sensorprobe using a suitable spanner (FIG. 6.76-6.77).

FIG. 6.76

FIG. 6.77

FIG. 6.78

FIG. 6.79

C3

C4

Page 57: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

57

FIG. 6.80

FIG. 6.81

FIG. 6.82

C5

6.5.12 Removing the D.H.W. flow switch

1. Unplug the electrical connector “C5” (FIG. 6.80);2. Remove the D.H.W. flow switch using a screwdriver

(FIG. 6.81-6.82).

6.6 ACCESS TO THE CONTROL SYSTEM

6.6.1 Checking the fuses

1. Remove the inspection cover on the reverse of thecontrol panel and unscrew the screws “C6”(FIG. 6.83);

2. Remove the fuses (FIG. 6.84).

Important! Isolate the electrical supply to the boilerbefore accessing the control panel.

FIG. 6.83

FIG. 6.84

C6

C6

Page 58: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

58

6.6.2 Removing the P.C.B.

1. Isolate electricity;2. Remove the inspection cover from the reverse of the

control panel, unscrew the screws “C7” (FIG. 6.85);3. Unplug all electrical connections from the recuperator

P.C.B on the reverse of inspection cover (FIG. 6.86);4. Unscrew the recuperator P.C.B mounting screws “C8”

(FIG. 6.87);5. Unplug the electrical connection from the P.C.B.;6. Unplug carefully the EEPROM “C9” (FIG. 6.88);7. Remove the screws “D1” (FIG. 6.89);8. Separate the facia panel from the rear of the control

panel ;9. Remove the main P.C.B., unscrew the screws “D2”,

and disconnect the P.C.B. connection cable “D3” (FIG.6.90)

10. Unscew the display P.C.B. mounting screws “D4”(FIG. 6.91);

11. Remove the display P.C.B. (FIG. 6.92);12. Replace either P.C.B. in reverse order;13. Use the correct EEPROM key “C9” supplied with the

new spare part.

FIG. 6.85

C7

C7

FIG. 6.86

FIG. 6.87

FIG. 6.89

FIG. 6.90

D1

D1

D1

D1

C8

C8

FIG. 6.88

C9

D2 D2 D2

D3

Page 59: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

59

FIG. 6.91

D4

D4

FIG. 6.92

6.6.3 Removing the time clock

1. Disconnect the electrical connections “D5” from theclock (FIG. 6.93);

2. Remove screws “D6” (FIG. 6.93);3. Lift out the time clock from the control panel (FIG. 6.94).

FIG. 6.93

FIG. 6.94

D5

D6

Page 60: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

60

7. FAULT FINDING These fault finding guides are not exhaustive. However, itis possible to detect and correct many defects by usingthe standard fault finding diagrams described in thischapter, ensure these guides are carried out in the setorder.7.1 FAULT FINDING GUIDE

(FLOW-CHARTS)

PRELIMINARY CHECKS MAKE SURE THAT:

IS THE POWER

DISPLAY ON?

POSTION OF THE

SELECTOR

NONO

NONO

WINTERWINTERESTAT ESUMMER

NONO

YESYES

YESYES

YESYESYESYES

YESYES

NONO

NONONONO

NONONONO

NONO

NONO

YESYES

YESYES

YESYES

TURN ON THE ON/OFF SWITCH

IS D.H.W. BEING DRAWN?

IS D.H.W. BEING DRAWN?

BUILT-IN ELECTRONIC

ANTI-FROST DEVICE: Is there a condition for it to be active

(flow temp between 3C & 8C)

ARE THE TIME CLOCK

AND/OR ROOM THERMOSTAT

ACTIVATED

A

ECONOMY/ COMFORT SELECTOR

TEMP. C.H. < 42°C

ComfortComfort

Economy

Economy

1 - There is sufficient water in the system 2 - The gas is turned on 3 - The electrical supply is turned on

1 - Check/reset system pressure 2 - Check/restore gas supply 3 - Check/replace short- circuited heating probe 4 - Check/replace siezed pump

1 - Check/reset the system pressure 2 - Check/restore gas supply 3 - Check/replace short- circuited heating probe 4 - Check/replace siezed pump

TEMP. C.H. < 42°C

ECONOMY/ COMFORT SELECTOR

YESYES DOES AN ERROR CODE APPEAR ON THE DISPLAY?

1. Check the fuses2. Check the power supply to the control panel3. Check/replace the ON/OFF button4. Check the connection between the main and display P.C.B.s

see section 3.7 5. Check/replace the main and display P.C.B.s

BUILT-IN ELECTRONIC

ANTI-FROST DEVICE: Is there a condition for it to be active

(flow temp between 3C & 8C)

To ensure that the external controls donot interfere with the fault f inding,disconnect the wires from the terminalblock on the rear of the control panel andprovide a solid l ink between theterminals (Section 2.13, page 22).

Page 61: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

61

YESYES

YESYES

NONOIS THE

PUMP RUNNING?

1. Check if there is air in the system2. Check the main circuit flow switch operation3. Check the pressure on the water gauge and fill system to 1 bar

1. Check pump cable2. Check/replace main P.C.B.

Release/replacepump

Turn theON/OFF button

POWER TOTHE PUMP?

YESYES

YESYES

ISTHE LOW WATER

PRESSURE SWITCH WORKING CORRECTLY?

E02: does not close

NONO

NONO

A

B

Page 62: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

62

1. Check the fan cable2. Replace the fan3. Replace the main P.C.B.

1. Check/replace ignition electrode2. Check ignition cable3. Check/replace the main P.C.B.

Replace the main P.C.B.

IS THE FANRUNNING?

DOES CODEE33 APPEAR?

IGNITIONSPARKS ARE GENERATED

REGULARLY?

YESYES NONO

NONO

YESYES

YESYES

NONO

1. Check the power supply of the gas valve.2. Check for an air pressure signal3. Check the gas pressure on the burner4. Check the soft-light adjustment5. Replace the gas valve6. Check/replace the main P.C.B.

1. See section 3.72. Press RESET

1. See section 3.7

IS THE BURNERALIGHT?

BOILER HAS SHUTDOWN?

YESYES

YESYES

NONO

NONO

IS THERE STILLA PROBLEM?

NORMALOPERATION

NONO

YESYES

B

Page 63: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

63

8. SHORT SPARE PART LIST

2

3

4

1

22

2041

13

14

15

1415

85

86

84

84

87

2724 25

23

192826

18

31 34 36 36 3732

17

16

19

21

10

60 56 5567 636566 62

10

64

68

10

9794

58

38

42

47

51

52

29

100

103

78

76

7777

79

120

115

22

48

49

50

117

116

35

45

46

106

108

107

8382

80

81

43105

4444

104

102

92113

9396

95

22

98

99 40

39

33

109

110

111

101

119

90

88

8

7

5

12

11

10

910

61

10

301 302 303

304305

305

123124

122

53

53

118 44

91

89

89

716

53

53

6970

128

31

126

114

5758

54

129

58

59

74

72

30

112

73

75

125

114

121

2019

31

127

MICROGENUS 32 MFFI HE (UK) NG 3300026 2320429900001 C

MICROGENUS 28 MFFI HE (UK) NG 3300015 2320429900001 B

MICROGENUS 24 MFFI HE (UK) NG 3300025 2320429900001 A

MODEL CODE SERIAL NO.VALIDITY

REF.

Page 64: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

64

401

402

403

code 65100547

code 65101257

503502

501

504

601

606

604

601

602

610

601

611

609603

607603

608

605

602

701

705

701

701702

703

704

701

701

code 65102576

Page 65: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

65

Keyno.

G.C. partno.

Description ARISTONPart. No.

18 Motor (3-Way Valve) 99714719 O-Ring 99842422 Gasket (3/4”) 57352025 Gasket (1/4”) 56939026 Low Water Pressure Switch 99845827 Temperature probe (DHW) 99845830 Spark Generator 6510024932 Pump 6510141743 Clock 99959946 Pressure Gauge 6510069554 Air Pressure Switch 6510216472 Fan (24 kW) 6510256672 Fan (28 / 32 kW) 6510256773 Seal (Silicone) 99036880 Main Exchanger (24kW) 6510258680 Main Exchanger (28 / 32 kW) 6510258581 Temperature Probe & Clip 99068682 Overheat Thermostat 99060584 O-Ring (Secondary Exchanger) 57382587 Safety Valve (3 bar) 99708889 Gasket (3/8”) 57352190 Gasket (1/2”) 57352893 Silicone Seal 569443106 P.C.B. (CMP3 - display) 65100709108 P.C.B. (main) 65102571110 Electrode Ignition (R.H.) 65100693111 Electrode Ignition (L.H.) 65100694112 Electrode (detection) 65100692118 P.C.B. (condense sensor) 65102572126 Gasket (Fan/Recuperator) 573343127 Gasket (Recuperator/Flue Outlet) 65102565

Page 66: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

66

9. TECHNICAL INFORMATION

NameCE CertificationFlue Type

Heat Input max/min kWHeat Output max/min kWEfficiency of Nominal Heat Input (60/80°C) %Efficiency of Nominal Heat Input (30/50°C) %Efficiency at 30% of Nominal Heat Input (30°C) %Efficiency at Minimum Input %Efficiency (Dir. 92/42/EEC)** SEDBUK Rating Band (%)

Heat Loss to the Casing (DT=50°C) %

Gen

eral

Info

En

erg

y P

erfo

rman

ce

Max Discharge of Products of Combustion (G20) Kg/hResidual Discharge Head mbarTemp. of exhaust fumes at nominal capacity °CCO2 Content %O2 Content %CO Content ppmNox Class

Em

issi

on

s

Head Loss on Water Side (max) (DT=20°C) mbarResidual Head of System barExpansion Vessel Pre-load Pressure barMaximum Heating Pressure barExpansion Vessel Capacity lMaximum Water Content of System lHeating Temperature max/min (High temperature) °CHeating Temperature max/min (Low Temperature) °C

Cen

tral

Hea

ting

Domestic Hot Water Temperature (approx) max/min °CSpecific Flow Rate (10 minutes/DT 30°C) l/minD.H.W. Flow Rate DT=25°C l/minD.H.W. Flow Rate DT=35°C l/minD.H.W. Minimum Flow Rate l/minPressure of Domestic Hot Water max/min bar

Dom

estic

Hot

Wat

er

Nominal Pressure Natural Gas (G20) barLPG (G30 / G31) bar

Consumption at Nominal Capacity (G20) m3/h(G30 / G31) kg/h

Gas Consumption after 10 Minutes* m3

Gas

Electrical Supply V/HzPower Consumption WMinimum Ambient Temperature °CProtection Grade of Electrical System IPInternal Fuse RatingE

lettr

ical

Dat

a

Weight KgDimensions (W/D/H) mm

G.C. Number

microGENUS HE 24 MFFI0051BP2805

C12-C32-C42-C52-C82-B22-B32

26.7 / 12.223.3 / 10.4

87.487.487.185.3

B (87.6)0.2

43.80.6872

7.626.8443

2000.250.737

13082 / 4244 / 38

56 / 3611.113.49.52.5

6 / 0.2

2028-30/37

2.541.89 / 1.86

0.30

1.74

1.84

230/50120+5

24D2A FAST 250Vac

37700/400/315

47-116-37

microGENUS HE 28 MFFI0051BP2805

C12-C32-C42-C52-C82-B22-B32

31.1 / 13.327.0 / 11.4

86.786.786.585.2

B (87.1)0.9

57.20.7365

6.798.325.8

3

2000.250.737

13082 / 4244 / 38

56 / 3612.915.511.02.5

6 / 0.2

2028-30/37

2,962.21 / 2.17

0.35

230/50148+5

24D2A FAST 250Vac

38700/400/315

47-116-38

* Calculated at 70% maximum output** Calculated on Upper calorific value

Max. Condensate produced l/hPH of condensate

Page 67: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

67

NameCE CertificationFlue Type

Heat Input max/min kWHeat Output max/min kWEfficiency of Nominal Heat Input (60/80°C) %Efficiency of Nominal Heat Input (30/50°C) %Efficiency at 30% of Nominal Heat Input (30°C) %Efficiency at Minum Input %Efficiency (Dir. 92/42/EEC)** SEDBUK Rating Band (%)Heat Loss to the Casing (∆T=50°C) %

Gen

eral

Info

En

erg

y P

erfo

rman

ce

Max Discharge of Products of Combustion (G20) Kg/hResidual Discharge Head mbarTemp. of exhaust fumes at nominal capacity °CCO2 Content %O2 Content %CO Content ppmNox Class

Em

issi

on

s

Head Loss on Water Side (max) (DT=20°C) mbarResidual Head of System barExpansion Vessel Pre-load Pressure barMaximum Heating Pressure barExpansion Vessel Capacity lMaximum Water Content of System lHeating Temperature max/min (High temperature) °CHeating Temperature max/min (Low Temperature) °C

Cen

tral

Hea

ting

Domestic Hot Water Temperature (approx) max/min °CSpecific Flow Rate (10 minutes/DT 30°C) l/minD.H.W. Flow Rate DT=25°C l/minD.H.W. Flow Rate DT=35°C l/minD.H.W. Minimum Flow Rate l/minPressure of Domestic Hot Water max/min bar

Dom

estic

Hot

Wat

er

Nominal Pressure Natural Gas (G20) mbarLPG (G30 / G31) mbar

Consumption at Nominal Capacity (G20) m3/h(G30 / G31) kg/h

Gas Consumption after 10 Minutes* m3

Gas

Electrical Supply V/HzPower Consumption WMinimum Ambient Temperature °CProtection Grade of Electrical System IPInternal Fuse RatingE

lettr

ical

Dat

a

Weight KgDimensions (W/D/H) mm

G.C. Number

microGENUS HE 32 MFFI0051BP2805

C12-C32-C42-C52-C82-B22-B32

35.0 / 13.330.5 / 11.3

87.187.186.984.8

B (87.3)0.7

59.21.1564.57.397.257.8

3

2000.250.737

13082 / 4244 / 38

56 / 3614.617.512.52.5

6 / 0.2

2028-30/37

3,332.48 / 2.45

0.39

2.24

230/50148+5

24D2A FAST 250Vac

39700/400/315

47-116-39

* Calculated at 70% maximum output** Calculated on Upper calorific value

Max. Condensate produced l/hPH of condensate

Page 68: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

68

10. BENCHMARK COMMISSIONING CHECKLIST

Page 69: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

69

11. SERVICE INTERVAL RECORD

Page 70: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

70

Page 71: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

71

Page 72: Installation and Servicing Instructions Type C Boilers - Ariston HE...Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance

0998

4183

2212

b -

03/

2005

MTS

ar e

con

tinuo

usly

im

prov

ing

thei

r pr

oduc

ts a

nd t

here

fore

res

erve

the

rig

ht t

o ch

ange

spe

cific

atio

ns w

ithou

t pr

ior

notic

e an

dac

cept

s no

liab

ility

for

any

erro

rs o

r om

issi

on in

the

info

rmat

ion

cont

aine

d in

thi

s do

cum

ent.

Manufacturer: Merloni TermoSanitari SpA - ItalyCommercial subsidiary: MTS (GB) Limited, MTS Building, Hughenden Avenue, High Wycombe, Bucks HP13 5FT

Please read these terms and conditions which are inaddition to any terms and conditions detailed in this bookor any registration card supplied with your appliance.

A charge will be made to the owner of the appliance if:

· The reason for any service visit is as a direct result of a failure to install the appliance in accordance with the manufacturer’s instructions.

· Your installer does not complete the necessary commissioning process and procedure as detailed inthe Installation and Operating Instructions.

· Your appliance is not serviced on or before the 12 month anniversary of installation - this only applies toappliances with a 2 and 5 year guarantee.

· Our service engineer calls as requested and the failure is a non-manufacturing defect.

Failure to pay an invoice for any such occurence will beassumed by MTS that you accept that your appliancehas not been installed correctly and understand that any

manufacturer’s guarantee has been withdrawn.On the 12 month anniversary of the applianceinstallation, you must have it serviced to continue anyguarantee offered into the following year. Failure to doso will invalidate your guarantee and should an MTSengineer be required to attend and no proof of servicedocumentation is made available, then MTS will charge.

As part of the commissioning process, it is a legalrequirement to register all boiler installations orreplacements with CORGI. Upon registration a“Certification Number” will be issued followed by a“Declaration of Safety” Certificate. MTS (GB) Ltd cannotbe called upon to carry out any work under themanufacturer’s guarantee without proof of registration.The registration number must be quoted whenrequesting a service visit, and the “Declaration of Safety”Certficate subsequently shown to the service engineer.If the certificate is not made available, the engineer willnot work on the appliance and a wasted call charge willbe made.