Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
Installation instruction for the
vacuum collectors
SB-1800/58-18, SB-1800/58-22, SB-1800/58-30
1. Technical Data: SB-1800/58-18, SB-1800/58-22, SB-1800/58-30
SB-1800/58 SB-1800/58-22 SB-1800/58-30
amount of pipes 18 22 30
Pipe constriction Vacuum tube with technology HEAT PIPE
and round absorber
Vacuum tube with technology HEAT PIPE
and round absorber
Vacuum tube with technology HEAT PIPE
and round absorber Angle of inclination 15 - 50° 15 - 50° 15 - 50° Pipe diameter 58 mm 58 mm 58 mm Pipe thickness 2,0 mm 2,0 mm 2,0 mm
Permeability > 0,90 > 0,90 > 0,90
height [cm] 2 040 mm 2 040 mm 2 040 mm
width [cm] 1 590 mm 1 920 mm 2 550 mm
depth of collector 182 mm 182 mm 182 mm
weight [kg] 69 kg 82 kg 105,4 kg
liquid content [l] 1,10 L 1,26 L 1,85 L
Connection pipes 22 mm 22 mm 22 mm Maximum pressure 6 bar
6 bar
6 bar
gross area [m2] 2,98 m2
3,61 m2 4,89 m2
absorber area [m2] 2,21 m2 2,70 m2 3,68 m2
Materials Al/Cu/ borosilicate glass / stainless steel
Al/Cu/ borosilicate glass / stainless steel
Al/Cu/ borosilicate glass / stainless steel
Surface Cooper covered in High selective layer
Cooper covered in High selective layer
Cooper covered in High selective layer
Insulation Vacuum / mineral wool Vacuum / mineral wool Vacuum / mineral wool Absorption > 94 % > 94 % > 94 % Emission 6 % 6 % 6 % Optical efficency of absorber / aperture η0
0,937 / 0,582 0,937 / 0,582 0,937 / 0,582
Coefficient of linear loss of absorber / aperture
2,693 W/(m2K) / 1,673 W/(m2K)
2,693 W/(m2K) / 1,673 W/(m2K)
2,693 W/(m2K) / 1,673 W/(m2K)
Balance temperature of pipe
247° 247° 247°
Balance temperature of module
215° 215° 215°
Maximum amount of collectors
5 4 3
Recommended flow
rate for one collector
(l/min)
1,5 - 2 1,75 – 2,75 2,5 - 3,5
Recommended method to determine flow rate = 0,1 l/min on each vacuum pipe.
Example: set of 66 pipes (3 x collector 22) = 6,6 l/min
1.1 supply and return
recommendations:
gross area copper tube corrugated stainless-
steel tube
Do 10 m2 18mm DN16
Do 22 m2 22mm DN20
Od 23 m2 28mm DN25
Connecting the tubes with the collector:
- clamping connection (recommended)
Corrugated stainless-steel tube ( INOFLEX) with insulation:
- simple installation with high temperature sealing fittings.
The tube and the insulation has to show the following characteristics:
- momentary temperature durability over 150°C (e.g. caoutchouc or mineral wool)
- insulation thickness is the diameter of the pipe (based on the heat transfer coefficient
K= 0,04 W/mk)
1.2 Electrical installation, lightning-rod and grounding
The electrical installation should be done by a specialist, in accordance with all current
requirements and standards. In order to compensate potentials all metal parts of the solar
installation should be installed on the main bus, in accordance with electrical regulations. If
the building has a lightning installation, it should be connected to the collectors.
1.3 Safety during installation
ATTENTION !!
Vacuum panels should be covered up during the installation to the moment of filling up
and venting the installation, or the assembly of the vacuum pipes should be done after
the filling up and venting the installation. It is not allowed to fill up the solar installation
when the collector is under direct sunlight. In the solar installation may occur temperatures
above 100°C, which during filling up can cause damage to the installation (this damages are
not covered by the warranty).
To protect the solar installation against freezing you should fill up the installation with an
suitable solar fluid that protects the installation against corrosion and freezing.
Recommended flow of solar fluid: 0.7 L / min per m2 of the absorber surface.
The temperature difference between the supply and return of the installation should be max
10°C.
2. Installation of a collector
To each vacuum collectors set there is a suitable mounting set attached. Each set is adjusted to
a proper installation of the collectors on the flat roof or foundation, inclined tile roof or
roofing made of sheet, tar paper, bituminous shingle or metal tiling. Each collector is mounted
separately
2.1 Completeness of delivery
2.2 Collector with 18 pipes with the mounting system adapted to the inclined roofing:
1. manifold – 1 pcs
2. bottom supporting frame – 1 pcs
3. side mounting profiles – 5 pcs
4. vacuum pipes support – 18 pcs
5. heat transfer paste – 1 pcs
6. set of mounting screws – 1 pcs
7. footing 2 pcs
8. heat pipes - 18 pcs.
2.3 Collector with 22 pipes with the mounting system adapted to the inclined roofing:
1. manifold – 1 pcs
2. bottom supporting frame – 1 pcs
3. side mounting profiles – 7 pcs
4. vacuum pipes support – 22 pcs
5. heat transfer paste – 1 pcs
6. set of mounting screws – 1 pcs
7. footing 3 pcs
8. heat pipes - 22 pcs.
2.4 Collector with 30 pipes with the mounting system adapted to the inclined roofing:
1 manifold – 1 pcs
2 bottom supporting frame – 1 pcs
3 side mounting profiles – 9 pcs
4 vacuum pipes support – 30 pcs
5 heat transfer paste – 1 pcs
6 set of mounting screws – 1 pcs
7 footing 3 pcs
8 heat pipes - 30 pcs.
3. Installation scheme
3.1 Spacing and number of vertical mounting profiles
Number of Tubes Number of profiles spacing profiles [mm]
18 2 1408
22 3 863
30 3 1183
* middle profile No. 3 applies only to the mounting set for collectors SB-1800/58-22 oraz SB-1800/58-30
The manifold (1) and the bottom supporting frame are mounted to the side mounting
profiles with the mounting screws (6)
4. Installation on the inclined tile roof
The collector should be fixed with the roof hooks, that can be attached directly to the side
mounting profiles.
reinforcing sleeve
To determine the spacing between the roof hooks, you should use the side mounting profiles
(3) and the bottom supporting frame.
Side spacing is determined by the location of the tile holes.
In the SB-1800/58-22 oraz SB-1800/58-30 collector the middle support profile is centered in
accordance with the location of the tile holes.
4.1 Installation scheme on the inclined tile roof
5. Installation on the inclined roof with roofing made of sheet, tar paper, bituminous shingle or metal tiling. The collector should be fixed with the roof screws, that can be attached directly to the side
mounting profiles.
To determine the spacing between the roof screws, you should use the side mounting profiles
(3) and the bottom supporting frame (2). In the SB-1800/58-30 collector the middle support
profile is centered in accordance with the location of the tile holes
reinforcing sleeve
6. Installation on a flat roof or foundation.
Supporting triangles are the base of the assembly set. All triangles are assembled in the same
way. Before commencing the assembly of a supporting triangle you should lay out all its
components according to the figure presented below.
After planning out the location of all the components you can start bolting together an
assembly triangle.
To mount collector SB-1800/58-18 and SB-1800/58-22 it is required to assembly 2 supporting
triangles. Collector SB-1800/58-30 is mounted on supporting construction made of 3
triangles.
After fixing together all elements of supporting triangle, it is necessary to mound side profiles
to supporting triangle as on the photo below.
5. Installation of the vacuum pipes
After the assembly of the supporting construction you can begin the installation of the heat
pipes. First attach the heat pipe supports.
`
Before installation, be sure to apply heat transfer paste on the end of the heat pipe
After inserting the heat pipes to the manifold you should lay out and close them in the bottom
vacuum pipes support. Repeat until all the heat pipes are mounted.
6. Connecting the collectors
6.1 Connection of the collectors power
1 – connector pipe of the collector
2 – strengthening sleeve
3 – nut
4 – clamping ring
5 – elbow body
6 – gasket
7 – insulated flexible hose
strengthening sleeve (2) in the connector pipe of the
collector (1), elbow nut (3) should be put on the connector pipe of the collector (1),
- clamping ring (4) should be placed on the connector pipe of the collector (1),
- screw the nut (3) onto the elbow (5),
- flexible hose (6) needs to be screwed on the elbow (5),
- connect the flexible hose to the solar system (7)
6.2 Connection of the collector return
1 – connector pipe of the collector,
2 – strengthening sleeve,
3 – clamp nut,
4 – clamping ring,
5 – complete cross fitting with a manual vent and
immersion sleeve,
6 – insulated flexible hose
7 – insulated flexible hose
- place the strengthening sleeve (2) in the connector pipe of the collector (1),
- put the clamp nut (3) on the connector pipe of the collector (1),
- place the clamping ring (4) on the connector pipe of the collector (1),
- immersion sleeve with the complete cross fitting (5) needs to be placed in the
connector pipe of the collector (1),
- screw the clamp nut (3) onto the cross fitting (5) at the left side,
- screw the insulated flexible hose (6) at the bottom of the pipe-cross (5),
- connect the flexible conduit to the solar system. (7)
6.3 Connecting the collectors with a clamping pipe union. 1 – connector pipe of the collector
2 – strengthening sleeve
3 – pipe union nut
4 – clamping ring
5 – compensator
Mount the compensator on the first collector, then move the second collector
closer and fasten the pipe union on both collectors.
− place the strengthening sleeve (2) in the connector pipe of the collector (1),
− pipe union nut (3) should be put on the connector pipe of the collector (1),
− clamping ring (4) should be placed on the connector pipe of the collector,
− screw the nut (3) onto the pipe union body,
− place the strengthening sleeve in the connector pipe of the second collector,
− put the nut on the connector pipe of the second collector,
− place the clamping ring on the connector pipe of the second collector,
− move the second collector closer to the compensator,
− screw the nut onto the compensator
6.4 Option for mounting an automatic air escape. If there is not any space for an automatic air escape a manual air escape
should be installed.
7 – adapter ¾ '' x 3/8 ''
8 – ball valve 3/8 ''
9 – automatic air escape 3/8 ''_
- unscrew the manual air escape from
the top of the pipe-cross (5),
- successively screw the adapter (7),
valve (8) and automatic air escape
(9) at the top of the pipe-cross.
Directions!
Due to high temperatures in the solar systems it is necessary to use
air escapes made completely of metal.
6.5 Connection of the temperature sensor
Damage to the system
In case of wrong installation of a temperature sensor or damage to
the signal cable there is a risk of damage to the system.
- signal cable must be protected against damage (e.g. damage caused by
birds, rodents) using a protective coat.
Temperature sensor should be installed
in an immersion sleeve.
− insert the temperature sensor into
the immersion sleeve,
− protect with a clamping spring against
moving out.
6.6 Connection of collecting conduits
Hydraulic connection with collecting pipes should be executed by means of
an insulated flexible conduit. It is not allowed to connect stiff collective
pipes directly to the collector.
The connection of flexible conduits with the system must be done below the
level of the air escape.
Directions!
Universal roof ventilators and antenna penetration should be used to execute
the passage of conduits across the roof.
Directions!
A cable for the temperature sensor should be laid together with the flexible
return conduit.
7. Finishing work
7.1 Inspection of the installation
Upon completion of the installation work it is necessary to:
− inspect the installation correctness of all elements of the system,
− check the system by means of a pressure test,
− flush the system with water,
− fill in the system with the solar agent.
After the pressure test and water flushing of the system it must be immediately filled
up with the solar agent. Otherwise, the tightness test and flushing need to be carried
out directly before filling up the installation with the solar agent.
7.2 Insulation work
Insulation work should be done after performing all inspection operations.
Directions!
− High temperature and weather resistant insulation must be used to insulate
the conduits which are outside the building.
If necessary, protect the insulation against damage caused by birds.
− High temperature resistant insulation must be used to insulate the conduits
inside the building.
8. Maintenance and Service
During the maintenance and other kind of work a collector must be placed firmly
to exclude the danger of tripping over and falling down,
It is not allowed to perform any repair and maintenance work under a lifted
collector which has not been protected against casual falling down.
- Repair and maintenance work should be done by means of suitable tools and the
servicing personnel should wear protective gloves and shoes,.
- Overhaul of the solar system needs to be done in accordance with warranty
recommendations for particular elements of the system.
In order to guarantee failure-free operation of the whole system it is
recommended to carry out the following maintenance work at least once a Year
The control and protection system should also be inspected along with the
structure for supporting and fixing a collector on the roof.
In order to guarantee the proper operation of the whole system, every time we
recommend you to enter into a contract for maintenance work with a specialist.
Copyrights ENERGETYKA SOLARNA ENSOL Sp. z o.o.
Copying, reproduction and use of the study,
or its elements without the permission of the authors strictly prohibited.
03/2016