KNX GatewayRGK02E5023-01
Operating Instruction
RGK02 Operating Instructions
3
Inhalt
1 General .............................................................................................................41.1 Technical data ...............................................................................................41.2 Intended Use ...............................................................................................41.3 Specifications ...............................................................................................51.4 Compatibility ...............................................................................................51.5 Scopeofdelivery ..............................................................................................5
2 Information about the radio system Easywave ...........................................52.1 Generalinformationandfunctionality ................................................................52.2 Operatingmodes ...............................................................................................6
3 Installation and programming ........................................................................73.1 Assembly ...........................................................................................................73.2 IntegratingthedatabasefileintheETS5 .........................................................73.3 Insertingagatewayintoaproject ......................................................................83.4 Programmingthephysicaladdress ..................................................................9
4 Functionen and Object properties ...............................................................104.1 Systemobjects ................................................................................................11 4.1.1 Teachinginachannel ........................................................................12 4.1.2 Deletingachannel ...........................................................................13 4.1.3 Delete all channels ...........................................................................144.2 Creatingreceiveobjects .................................................................................15 4.2.1 Toggle ................................................................................................16 4.2.2 Switch ................................................................................................17 4.2.3 Dim ....................................................................................................18 4.2.4 Shutters .............................................................................................19 4.2.5 Settingavalue ...................................................................................20 4.2.6 Sendsignal ........................................................................................214.3 Creatingsendobjects ......................................................................................22 4.3.1 1-buttonoperation ............................................................................23 4.3.2 2-buttonoperation .............................................................................24 4.3.3 3-buttonoperation .............................................................................25 4.3.4 Deadman ...........................................................................................26
5 General notices .............................................................................................275.1 Disposal ...........................................................................................................275.2 Warranty ..........................................................................................................275.3 Conformity .......................................................................................................275.4 Customerservice .............................................................................................27
RGK02 Operating Instructions
4
1 GeneralTheEasywaveKNXGatewayRGK02(inthefollowingcalledgateway)isaproductoftheKNXsystemandmeetstheKNXguidelines.SufficienttechnicalknowledgeprovidedthroughKNXtrainingcoursesisrequiredforcomprehension.Thefunctionsofthedevicearesoftware-dependent.Fordetailedin-formationaboutthesoftwarethatiscurrentlyavailablefordownload¬andtheresultingfunctionscope,refertothemanufacturer‘sinternetsite.Planning,installationandcommissioningofthegatewaytakesplacewithasoftwarecertifiedbyKNXAssociation.FundamentalknowledgeoftheEasywaveradiosystemisrequiredforoptimumutilisationofthegate-way.Chapter2,„InformationabouttheEasywaveradiosystem“containsimportantinformationtothisrespect.
1.1 Technical data
CodingNotrequired,asthesendcodeisprogrammed.Upto128transmitterscanbeprogrammed.
Channels 128inputchannels,32outputchannels;Range 150matgoodfreefieldconditions
VoltagesupplyKNXbusvoltage29VDC(noextrabuscouplerrequired)
Operation ViaKNXbusandEasywaveproductsOperatingmodes Easywavereceive:
toggle,switch,dim,shutteroperation,setvalue,sendsignalEasywavesend:ON/OFF(1-buttonoperation),ON/OFF(2-buttonope-ra-tion),UP/STOP/DOWN(3-buttonoperation),dead-manbutton
Protectiontype IP21Operatingtemperature -20°Cto+60°CDimensions 46x46x25mmCurrentconsumption ca.35mAFrequency 868.30 MHz
1.2 Intended UseThebidirectionalgatewaylinkstheKNXsystemandtheEasywaveradiosystem.ItisaKNX-conformdevice,certifiedinacc.withEN50090andEN300220.OnlyusetheEasywaveKNXGatewayRGK02indryindoorrooms.Themanufacturerwillnotbeliablefordamagecausedbyimproperorinappropriateuse.
RGK02 Operating Instructions
5
1.3 Specifications
Objects/functions 640
Groupaddresses max.335
Associations max.335
Commandbuffer 8commands
Max.separatelyaddressableEasy-wavereceivers
128(32Easywaveserialnumberswithfourkeycodeseach)
Max.executablefunctions
(KNX-side)
335(Limitationthroughmax.groupaddress-es/associations)
1.4 CompatibilityTheEasywaveKNXGatewaycanbeoperatedwiththeengineeringtoolsoftware(ETS)asofversion3.0f.Ontheradioside,itiscompatiblewithalltransmittersandreceiversintheEasywaveproductrange.
1.5 Scope of delivery Easywave-KNXGatewayRGK02E5023-01, Operatinginstruction
2 Information about the radio system Easywave
2.1 General information and functionalityWithitsextensiveproductrange,theradiosystem„Easywave“isthecompletesystemforallapplica-tionsinbuildingservicesengineering.The868MHzwavebandwithitsdivisionintosub-bands(e.g.sub-band868.0MHzto868.6MHz)anddifferentdutycyclesisideallysuitedforsophisticatedtasks.IntheISMwaveband(ISM=Indust-rial,Scientific,Medical),transmissiononlytakesplaceforafewhundredmillisecondswithoutputsoflessthan1milliwatt(max.25milliwattposs.).Tobeabletoaddressaradioreceiver,youfirsthavetoteachintheEasywavesendcode.Aftertheteach-inprocess,thereceivercanbeshutoffbythetransmitterorthegateway.ThesendcodeofanEasywavetransmitterhasalengthof32bitandcontainsaserialnumberaswellasakeycode.Theserialnumberservestoidentifythesender.ThekeycodesA,B,CandDareauto-maticallyassignedtothefunctionsofthesetoperatingmodebythereceiver.Independenceontheselectedoperatingmode,theindividualkeycodesofaserialnumberareauto-maticallyassignedreceiverfunctionsuponteach-in.Forexample,onlyoneoffoursendbuttonsmustbeprogrammedwithareceiverforashuttercontrolinordertobeabletousethefunctionsUP/STOP/DOWN.Fordetailedinformationaboutthekeycodesandthereceiver‘sinterpretationofthekeycodes,seetherespectiveinstructionmanuals.
RGK02 Operating Instructions
6
2.2 Operating modesON/OFF (1-button operation)With1-buttonoperationorso-calledtoggling,theswitchingstatusofthereceiverchangeswitheverypushofthebutton: 1.Send:ON2.Send:OFF3.Send:ON…Eachkeycodecanbeprogrammedandusedseparately.Thereisnoautomaticassignment.
ON/OFF (2-button operation)With2-buttonoperation,thereceiverswitchesdirectlyONandOFF.
KeycodeA:ON KeycodeC:ON
KeycodeB:OFF KeycodeD:OFF
A,BaswellasCandDareassignedautomatically.Onlyoneofthesekeycodesmustbeprogrammed.Bothgroupscanbeusedseparately.
TIMERIntimermode,thereceiverswitchesONfor7minutesafterreceivingaprogrammedsendcodeandOFFagainafterexpirationofthistime.
KeycodeA:ON(for7minutes) KeycodeC:ON(for7minutes)
KeycodeB:ON(for7minutes) KeycodeD:ON(for7minutes)
Eachkeycodecanbeprogrammedandusedseparately.Thereisnoautomaticas-signment.
DEADMAN FUNCTION Indeadman function, the receiverswitches for thedurationof the transmitteroperation.Due to themaximumdutycycle,alltransmittersautomaticallyswitchoffafter36sec-onds.Withthegateway,thesystemswitchesoffafter31secondsalready.
KeycodeA:ON (max.31seconds)
KeycodeB:ON (max.31seconds)
KeycodeC:ON (max.31seconds)
KeycodeD:ON (max.31seconds)
Eachkeycodemustbeprogrammedandusedseparately.Thereisnoautomaticas-signment.Simulta-neoususeofseveralchannelsisnotpossible.
UP/DOWN (2-button operation)Thisoperatingmodeisonlyavailablewithreceiversforshuttercontrolfeaturingtwointerlockedrelayoutputs.Here,UPstandsforswitchingofthe1strelay,DOWNforswitchingofthe2ndrelay.Parallelswitchingofbothoutputsisnotpossible.Therelaysautomaticallycutoffagainafter90seconds.TheSTOPcommandistriggeredbytransmissionofthecounter-direction.Forexample,iftheshuttermovesUP(A),itisstoppedinitiallywhenpressingthebuttonfortheoppositedirection(B)andDOWNwhenpressingthebutton(B)again.
RGK02 Operating Instructions
7
+KNX-Systemleitung24VDC
+
KeycodeA:UP/STOPKeycodeC:UP/STOP KeycodeB:DOWN/STOP KeycodeD:DOWN/STOPA,BaswellasCandDareassignedautomatically.Onlyoneofthesekeycodesmustbeprogrammed.Bothgroupscanbeusedseparately.
UP/STOP/DOWN (3-button operation)Thisoperatingmodeisonlyavailablewithreceiversforshuttercontrolfeaturingtwointerlockedrelayoutputs.Here,UPstandsforswitchingofthe1strelay,DOWNforswitchingofthe2ndrelay.Therelaysautomaticallycutoffagainafter90seconds.Parallelswitchingofbothoutputsisnotpossible.
TheSTOPcommandistriggeredbytransmittingthekeycodeCorD.
KeycodeA:UP KeycodeC:STOP
KeycodeB:DOWN KeycodeD:STOP
A,BaswellasCandDareassignedautomatically.Onlyoneofthesekeycodesmustbeprogrammed.
IMPULSEWiththisoperatingmode,therelayoutputisswitchedfor1seconduponreceiptofaprogrammedsendcodeandafterwardsreleasesagain,independentlyofhowlongthemanualtransmitterisoperated.
KeycodeA:ON(1second) KeycodeC:ON(1second)
KeycodeB:ON(1second) KeycodeD:ON(1second)
Eachkeycodecanbeprogrammedandusedseparately.Thereisnoautomaticas-signment.
3 Installation and programming
3.1 AssemblyOnlyqualifiedexpertsmaymountandcom-missionthedevice.Thegatewaycanbeinstalledinaflush-mountedsocket,surfacesocketoranyothertypesofhousing.TheelectricityconnectionisrealisedviatheKNXbusvoltageof29VDC.Whenusingthegateway,observethecurrentconsumptionof35mA.
3.2 IntegratingthedatabasefileintheETS5Fundamentalknowledgeoftheengineeringtoolsoftware(ETS)isrequiredtointegratethedatabase.Downloadthefile„RGK02.vd5“fromtheELDATinternetpagewww.eldat.de. (Products Easywave → Interfaces →RGK02)Importthevd5fileintotheETS5softwarevia
Workplace Catalogs Import RGK02.vd5NowthedeviceinformationisavailableintheETS5.
RGK02 Operating Instructions
8
3.3 Inserting a gateway into a projectOnceyouhavecreatedthedesiredrangeandlineinthemenu„Topology“,youcanaddthegatewaytotheproject.YouwillfindtheGatewayunderthefollowingcategory:
ELDAT Gateway KNX-Easywave-Gateway
Alternatively,youcanalsosearchfor„EasywaveGateway“inthesearchline.Double-clickingthegatewayaddsthedevicetothecurrentlyselectedarealineinthecurrentproject.
Afterwards,thegatewayisdisplayedthemenu„topology“withthefollowingfunctions:(2sendob-jects,2receiveobjectsandthe3systemobjects)
Overview of all available functions
System objects (seechapter4.1)
Receive objects (seechapter4.2)
Send objects (seechapter4.3)
Programminga channel Toggle 1-buttonoperation
Delete channel Switch 2-buttonoperationDelete all channels Dim 3-buttonoperation
Shutters Deadman(max.31seconds)SetvalueSignal
RGK02 Operating Instructions
9
3.4 Programming the physical address AnunequivocalphysicaladdressmustbeassignedtothenewlycreatedgatewayintheKNXbussys-tem.
1. Selectinthemenu„Topology“theEasywave-Gateway.Clickoninthemenubar „Edit“ →“Download“ .The„Program“windowappears.
2. Toprogramthephysicalgatewayaddress,clickonthebutton„DownloadIndividualAddress“.
3. Theprogrammingprocedurestartsandyouwillbepromptedtopresstheprogrammingbuttonof
thegateway.TheredLEDgoesoffafterapprox.4secondsandthephysicaladdressisnowpro-grammed.
Furtherinformationcanbefoundintheoperatinginstructionsoftherespectivereceiver.
RGK02 Operating Instructions
10
4 Functionen and Object properties
Therearethreetypesofobjects:
System objects ThethreesystemobjectsarerequiredfortheadministrationoftheEasywavesendcodes.KNXprogrammingandassignmentoftheEasywaveradioproductstotheindividualobjects(program-minganddeleting)isdonewiththeETS.
Transmit objectsSendobjectssendanEasywavetelegramfromtheperspectiveoftheKNXgateway.ThetransmissionprocessistriggeredbyKNXsensorsandcontrolsEasywavereceiver.
TRANSMIT OBJECTRGK02
RGK02 receives switching command via the KNX bus.
KNX BUS
Sensor is activated.
Using the group address, a send command is trans-mitted to the RGK02 via the KNX bus.
Receivers can receive the learned telegram and can be controlled via KNX.
RGK02 sends the parameterized Easywave telegram via radio.
RADIO ACTUATORKNX SENSOR
Receive objectsReceiveobjectsreceiveEasywavetelegramsandconvertthemascommandstotheKNXbus.
Easywave transmitter is operated.
RADIO SENSOR
RECEIVE OBJECTRGK02
KNX ACTUATOR
RGK02 receives the radio telegram.
All KNX actuators linked to this group address switch according to the parameterization.
RGK02 transmits the switching command by used the group address via the KNX bus.
Switching command is transmitted by radio to the RGK02.
KNX BUS
RGK02 Operating Instructions
11
4.1 System objects
ThethreesystemobjectsarerequiredfortheadministrationoftheEasywavesendcodes.Theseob-jectsarepermanentlyintegratedinthesystemandcannotbechanged.
Validgroupaddressesmustbeassignedtousethesystemobjects.
Thefollowingsystemobjectsareavailable:
641 (1Byte): „Teachchannel“(seechapter4.1.1)(=„Kanallernen“) Teachinginahandheldtransmitteronthememoryslots1-128
642(1Byte): „Deletechannel“(seechapter4.1.2)(=„Kanallöschen“) Deletingahandheldtransmitteronthememoryslots1-128
643(1Bit): „Deleteallchannels“(seechapter4.1.3)(=„AlleKanälelöschen“) Deletesallprogrammedmanualtransmitters
Aftercreatingandassigningthegroupaddresses,thesecanbeaddresseddirectlyviatheETSgroupmonitor.
RGK02 Operating Instructions
12
4.1.1 Teaching in a channelThesystemobject641servesforteachinginEasywavesendcodes.Theteach-inprocessisinitiatedbytransmittingthedesiredmemoryslotnumber(valuefrom1to128)totherespectivegroupobject.
1. Openthegroupmonitor(Menu →Work place →Group Monitoring)and clickonStart.
2. Inthedialogue„Group Address“,enterthegroupaddressofthesystemobject„Teachchannel““ (e.g.1/1/1).3. In„Data Point Type“,select„21 * 8-bit set“.4. Inthefield„Value“enterthede-siredmemoryslotnumberandclickon„Write“.Pleasenotethat
thenumberofthememoryslotrepresentstheassignmenttothecorrespondingreceiveobjectatthesametime(seepoint4.2).
5. TheLEDonthegatewaylightsupred.Nowpressthedesiredtransmitter. Oncetheteach-inprocessiscompleted,theLEDgoesoff.
6. Repeatthesestepsforeachadditionaltransmitter.
ATTENTION! Ifyouteachinatransmitterdoubleonamemoryslot(value),thealreadyprogrammedsendcodeisoverwritten.Ifyouteachinthesametransmitterondifferentmemoryslots,thegatewaywillonlyexecutethefunc-tionofthelowestchannel.
RGK02 Operating Instructions
13
4.1.2 Deleting a channel Thesystemobject642servesfordeletingspecificEasywavesendcodes.Directdeletionofasendcodeisinitiatedbysendingthevalueforthememoryslot(1-128)tothecor-respondinggroupobject.
1. Openthegroupmonitor(Menu →Work place →Group Monitoring)andclickonStart.
2. Inthedialogue„Group Address“,enterthegroupaddressofthesystemobject„Deletechannel“(e.g.1/1/2).
3. In„Data Point Type“,select„21.* 8-Bit set“.4. Inthefield„Value“enterthememoryslotnumbertobedeletedandclickon„Write“.
Thecorrespondingmemoryslotisdeletedandthegatewaywillnolongerreacttothecorrespon-dingtransmitter.
5. Repeatthesestepsforeachadditionalchanneltobedeleted.
RGK02 Operating Instructions
14
4.1.3 Delete all channelsThesystemobject643servesfordeletingallprogrammedEasywavesendcodes.Deletionofallsendcodesisinitiatedbysending[1]tothecorrespondinggroupobject.
1. Openthegroupmonitor(Menu →Work place →Group Monitoring)and clickonStart.
2. Inthepoint“Group Address”,enterthesystemobject“Deletealltransmitters”(e.g.1/1/3)
3. In„Data Point Type“,select„1.015 Reset“.4. Changethevalueto„reset command (trigger)“andclickon„Write“.5. Nowallsendcodesaredeletedandthegatewaywillno longerre-acttoradiosignalsuntilnew
transmittersareprogrammed.
ATTENTION!Thereisnopromptforconfirmation!Alltransmittersarepermanentlydeleted!Arestorationoftheassignmentisnotpossible.Therefore,onlyassignagroupaddresstoobject643ifyoureallyneeditandthendeletethegroupaddressagain!
RGK02 Operating Instructions
15
4.2 Creating receive objects ThereceiveobjectsservefortheimplementationofEasywaveoperatingmodesintheKNXBus.Alto-gether128memoryslotsareavailableforEasywaveserialnumbers.Thereceiveobjectsaredivided into16groups(EtoT);eachgrouphaseightreceivefunctions.Bydefault,onlythe8receivefunctionsofgroupEareactivated.Ifmorere-ceivefunctionsarerequired,furthergroupsinthemenu„Receivegroups“mustbesetto„Use“.Afterwards,thenewlyselectedreceivegroupisavailableforfunctionassignment.
Thereceivefunctionsarenumberedconsecutively(1to128).Therespectivechannelnumberisper-manentlyassignedtothememoryslotsfortheEasywavesendcodes.Forexample,thefunctionsofreceiveobject4canonlybecontrolledbytheEasywavetransmitterpro-grammedonslot4.ThereceiveobjectscanbeassignedtooneofthefollowingKNXfunctions:
• Toggle• Switch• Dim• Shutters• Setvalue• Signal
RGK02 Operating Instructions
16
4.2.1 Toggle
Datatype 1Bit
Numberofobjects 4 (A)Toggle,(B)Toggle, (C)Toggle,(D)Toogle
Objectbehaviouruponreceiving
(A):Toggle[1]or[0](B):Toggle[1]or[0](C):Toggle[1]or[0](D):Toggle[1]or[0]
Inthisoperatingmode,four1bitobjectsarecreatedfortherespectivechannel.TheserepresentthekeycodesA,B,CandDofoneEasywaveserialnumber.Ifoneofthekeycodesisreceived,thegatewayalternatelysends[1]or[0]totherespectivegroupob-jectsoftheKNXbus.Afterpressingthecorrespondingbuttonofaprogrammedtransmitter,thefunctionsaretransferredtotheKNXbusbythegateway.Acorresponding4-channeltransmitterisrequiredtobeabletouseallfourobjectsofachannel.
RGK02 Operating Instructions
17
4.2.2 Switch
Datatype 1Bit
Numberofobjects 2 (A/B)switch,(C/D)switch
Objectbehaviouruponreceiving
(A/B): (A=[1];B=[0])(C/D): (C=[1];D=[0])
Inthisoperatingmode,two1-bitobjectsarecreatedfortherespectivechannel.TheserepresentthekeycodesA,B,CandDofoneEasywaveserialnumber.IfthekeycodeAorCisreceived,thegatewaysends[1]totherespectivegroupobjectsoftheKNXbus.IfthekeycodeBorDisreceived,thegatewaysends[0]totherespec-tivegroupobjectsoftheKNXbus.Afterpressingthecorrespondingbuttonofaprogrammedtransmitter,thefunctionsaretransferredtotheKNXbusbythegateway.Acorresponding4-channeltransmitterisrequiredtobeabletouseallfourobjectsofachannel.
RGK02 Operating Instructions
18
4.2.3 Dim
Datatype 4Bit
Numberofobjects 2 (A/B)dim;(C/D)dim
Optionalobjects 1 (A/B)switch
Objectbehaviouruponreceiving
Dim
Dim and Switch
(A/B): (A=[UP];B=[DOWN])(C/D):(C=[UP];D=[DOWN])Short-timeobject: Pressbutton<1,6s(A/B): (A=[1];B=[0])Switch(C/D): (C=[UP];D=[DOWN])DimLong-timeobject: Pressbutton>1,6s(A/B): (A=[UP];B=[DOWN])Dim
Parameters DimstagesFunctionA/B:
[1to64][Dim]or[Dimandswitch]
ThisoperatingmodeservestoaddressKNXdimmers.WhenreceivingthekeycodeAorC,thecom-manddimupissenttothebus,whenreceivingthekeycodeBorD,thecommanddimdown. Bysettingtheparameter[dimandswitch],ashort-timeobjectforswitchcommandsforchannelA/Biscreatedinadditiontothedimobject.TheswitchcommandforthekeycodesA/Bisthentriggeredwhenthebuttonispushed<1.6seconds.Ifthebuttonispressedlonger,thedimfunctionisused.Attention! Iftheexecutionofthisfunctionshouldleadtointerferenceontheradioline,thesecuredis-tinctionbetweenlong-timeandshort-timeobjectscannotbeguaranteed.Incaseofanerror,aswitchcommandwouldbesentinsteadofadimcommand.Thisleadstothecom-pleteON/OFFoftheKNXactor,independentofthecurrentdimstage.ThisoptionisnotavailablefordimmingwiththebuttonsC/D.Afterpressingthecorrespondingbuttonofaprogrammedtransmitter,thefunctionsaretransferredtotheKNXbusbythegateway.
RGK02 Operating Instructions
19
4.2.4 Shutters
Datatype 1Bit
Numberofobjects 2 (A/B)shuttershort-time; (A/B)shutterlong-time
Optionalobjects 3 (C)shutterstop;(C/D)shuttershort-time;(C/D)shutterlong-time
Objectbehaviouruponreceiving
Short-timeobject:Pressbutton<1.6s(A/B): (A=[0];B=[1])(C): (C=[0])(C/D):(C=[0];D=[1])Long-timeobject:Pressbutton>1.6s(A/B): (A=[0];B=[1])(C/D):(C=[0];D=[1])
Parameters Shutter command
ButtonC
Long-timecommand;short-timecommand;shortandlong-timecommand
Extrastopcommand;additionalshortandlong-timecommand;noutilisation
ThisoperatingmodeservestoaddressKNXshutteractors.Ashort-timeobjectA/Bandalong-timeobjectA/Baregeneratedbydefault,whereby[0]issentwhenreceivingakeycodeAand[1]whenreceivingakeycodeBtotherespectivegroupobjectsoftheKNXbus.Intheoperatingmode[shortandlong-timecommand],thesystemevaluatesPRIORtotriggeringtheKNXcommandwhethertherespectiveobjectisalongorashort-timeobject.Pressingthebuttonfor<1.6sisinterpretedasashort-timecommand,pressingthebuttonfor>1.6sasalong-timecommand.Optionally,youcandefineonlyashortoronlyalong-timecommandforthebuttonsA/B,whichisthenexecuteddirectly.Thiswayitisnotnecessarytopressabuttonfor1.6stotriggeralong-timecommand.Inaddition,itisalsopossibletodefinebothanothershortandalong-timeobjectforthesendcodeC/DORaseparateSTOPcommand(Conly).Bydefault,thisoptionissetto„noutilisation“.Afterpressingthecorrespondingbuttonofaprogrammedtransmitter,thefunctionsaretransferredtotheKNXbusbythegateway.
RGK02 Operating Instructions
20
4.2.5 Setting a value
Datatype 1byte
Numberofobjects 1 (A)valueA
Objectbehaviouruponreceiving
(A): (A=[VALUE])
Parameters Valuein% Adjustablein5%-steps
Thisoperatingmodeallowsyoutosendavalueinpercentinarangefrom0%to100%totheKNXbus.Thevaluecanbeselectedin5%-steps.ThecommandisuniquelytriggeredbykeycodeAoftheprogrammedsendtelegram.Afterpressingthecorrespondingbuttonofaprogrammedtransmitter,thefunctionistransferredtotheKNXbusbythegateway.
RGK02 Operating Instructions
21
4.2.6 Send signal
Datatype 1bit
Numberofobjects 4 (A)signal,(B)signal, (C)signal,(D)signal
Optionalobjectse none
Objectbehaviouruponreceiving
(A): (A=[1]|[0])(C): (C=[1]|[0])(B): (B=[1]|[0])(D): (D=[1]|[0])
Parameters Signaltype [0]or[1]
Four1-bitobjects(oneobjectforeachkeycode)aregeneratedinthisoperatingmode.Thisoperatingmodeallowsyoutosend[1]or[0]totheKNXbus.Thecommandistriggeredwitheachkeycode(A,B,CorD)ofaprogrammedEasywaveserialnumber.PerprogrammedEasywaveserialnumber,youcannowsendeither[1]or[0]tothebus.AllkeycodesalwayssendthesamevaluetotheKNXbus,butarerepresentedbydifferentgroupobjects.Afterpressingthecorrespondingbuttonofaprogrammedtransmitter,theob-jects/functionsaretrans-ferredtotheKNXbusbythegateway.
RGK02 Operating Instructions
22
4.3 Creating send objectsThe send objects serve to address Easywave receivers from the KNX bus. Altogether 32 send objects are available in the gateway. Each object can send out an Easywave serial number with up to four different keycodes depending on the selected function. EvaluationofthetransmittedsendcodesisdonebytheEasywavereceiversdependingontheirselec-tedoperatingmode.Thesendobjectsaredividedintofourgroups(A,B,CandD).Eachgroupcontainseightsendchannelstowhichonefunctioneachcanbeassigned.OnlysendgroupAisactivatedbydefault.Ifmoresendfunctionsarerequired,furthergroupsmustbeactivatedinthemenu„Sendgroups“.Assoonasasendgroupwassetto„Utilise“inthemenuitem„Sendgroups“,,thisap-pearsasanewparametersettingoptionintheparameterdialog:Afteractivationofanadditionalsendgroup,thisisdisplayedintheconfigurationmenu,howevertheeightfunctionsofthegrouparesetto“Noutilisation”.Soinordertoaddadditionalgroupobjects,thesemustbeassignedafunctionfirst.Thesendobjectscanbeprogrammedtooneofthefollowingoperatingmodes.Theoperatingmodesethereshouldcorrespondtotheoperatingmodeoftheaddressedreceiver.− 1-buttonoperation(A,B,C,D)− 2-buttonoperation(A/B,C/D)− 3-buttonoperation(A/C,B/C)− Deadman(A,B,C,D)
RGK02 Operating Instructions
23
4.3.1 1-button operation
Datatype 1bit
Numberofobjects 4 (A)1-button,(B)1-button,(C)1-button,(D)1-button
Objectbehaviour at[0] Sendingoftherespectivekeycode
at[1] Sendingoftherespectivekeycode
Easywave operatingmodes
Impulse,timerON/OFF(1-buttonoperation)
Inthisoperatingmode,four1bitobjectsarecreatedfortherespectivechannel.TheserepresentthekeycodesA,B,CandDofoneEasywaveserialnumber.IfanassignedKNXsensorisoperated,thegatewaysendstherespectivesendcode.Here,theindividualobjectsand/orkeycodesdonotdependoneachotherandcanbeassigned toseparategroupaddresses.
RGK02 Operating Instructions
24
4.3.2 2-button operation
Datatype 1Bit
Numberofobjects 2 (A/B)2-button+(C/D)2-button
Objectbehaviour at[0] Sendingof[B]or[D]
at[1] Sendingof[A]or[C]
Easywave operatingmodes
ON/OFF(2-buttonoperation) UP/DOWN(2-buttonoperation)
Twoobjects(A/BandC/D)aregeneratedinthisoperatingmodefortherespectivechannel.Theserepresentthekeycodes(A/B)or(C/D)ofoneEasywaveserialnumber.IfanassignedKNXsensorisoperated,thegatewaysendstherespectivesendcode.IftheKNXbusreceivesa[1],thekeycodeAorCissentoutdependingontheselectedobject. Whenreceivinga[0],thekeycodeBorDissentanalogue.
RGK02 Operating Instructions
25
4.3.3 3-button operation
Datentyp 1Bit
Numberofobjects 2 (A/C)3-buttonand(B/C)3-button
Objectbehaviour at[0] Sendingof[C]
at[1] Sendingof[A]or[B] (dependingontheobject)
Easywave operatingmodes
UP/STOP/DOWN (3-buttonoperation)
Twoobjects(A/CandB/C)aregeneratedinthisoperatingmodefortherespectivechannel.TheserepresentthekeycodesA,BandCofoneEasywaveserialnumber.IfanassignedKNXsensorisoperated,thegatewaysendstherespectivesendcode.IftheKNXbusreceivesa[1],thekeycodeAorBissentoutdependingontheselectedobject. Whenreceivinga[0],thekeycodeDissentanalogue.
RGK02 Operating Instructions
26
4.3.4 Deadman
Datatype 1Bit
Numberofobjects 4 (A)deadman,(B)deadman,(C)deadman,(D)deadman
Objectbehaviour at[0] Stopsending
at[1] Startsendingtherespectivekeycode forthesetduration
Easywave operatingmodes
Deadman
Parameters Deadmanduration
[1-31]inseconds
Inthisoperatingmode,four1bitobjectsarecreatedfortherespectivechannel.TheserepresentthekeycodesA,B,CandDofanEasywavesendcode.IfanassignedKNXsensorisoperated,thegatewaysendsthecorrespondingsendcodeforthedura-tionthebuttonispressed,howeveratmostuptothesetsendduration.
IMPORTANT!TheKNXsensormustbeconfiguredinsuchawaythatitsends[1]whenoperatedand[0]whenreleasedtotheKNXbusand/ortotherespectivegroupobject!Au-tomatedperma-nent transmission is not admissible!Themaximumsenddurationissettoavaluebetween1and31secondsinthepa-rameters.Thestan-dardvalueis3seconds.Whenreceiving[1],thegatewaystartstransmittingthesendcodeandstopswhenreceiving[0].Afterexpirationofthesetmaximumsendduration,thegatewayautomaticallystopsthetransmissionprocess.
ATTENTION! Duringthetransmissionprocess,thegatewaycannotprocessanyothercommands!Thetransmissionprocessisstoppedbysending[0]tothedeadmanobject.Allincom-ingKNXcommandsarebuffered.Atmosteightcommandscanbebuffered;ifmorecommandscomein,theseexpire.Easywavecommandscannotbereceivedduringtheentiretransmissiondurationandexpiregenerally.
RGK02 Operating Instructions
27
5 General notices
5.1 DisposalObsolete devices may not be disposed of in the household waste!Pleasedisposeofobsoletedevicesatacollectionpointforelectronicwasteoryourretailers.Disposeofpackagingmaterialsinspecialcontainersforcard-board,paperandplastic.
5.2 WarrantyWewillremedydefectsonthedevicebasedonmaterialorproductionerrorswithinthestatutorywarrantyperiodorexchangethedevice.Incaseofunauthorisedtamperingwiththedevice,thewarrantyisvoid.
5.3 ConformityTheproductfulfilstheessentialrequirementsoftheREDdirective2014/53/EUaswellasEN50090-2-2.ThedeclarationofconformitycanbecalleduponthefollowingInternetpage:www.eldat.de
isaregisteredtrademarkofKONNEXASSOCIATION.
ETSTM isaregisteredtrademarkofEIBAcvba.
5.4 Customer serviceIfthedevicedoesnotworkproperlydespiteproperhandlingorincaseofdamage,pleasecontactyourretailer.
ELDAT GmbHImGewerbepark1415711KönigsWusterhausenGermany
Phone: +49(0)3375/9037-0Fax: +49(0)3375/9037-90Internet: www.eldat.deE-Mail: [email protected]
UM95313B
0318D