Line to Ground Fault

Embed Size (px)

Citation preview

  • 8/6/2019 Line to Ground Fault

    1/17

    In an electric power system, a fault is any abnormal flow ofelectric current. For

    example a short circuit is a fault in which current flow bypasses the normal load.

    An open circuit fault occurs if a circuit is interrupted by some failure. Inthree

    phase systems, a fault may involve one or more phases and ground, or may

    occur only between phases. In a "ground fault" or "earth fault", current flows into

    the earth. The prospective short circuit current of a fault can be calculated for

    power systems. In power systems, protective devices detect fault conditions and

    operate circuit breakersand other devices to limit the loss of service due to a

    failure.

    In a polyphase system, a fault may affect all phases equally which is a

    "symmetrical fault". If only some phases are affected, the resulting "asymmetrical

    fault" becomes more complicated to analyse due to the simplifying assumption of

    equal current magnitude in all phases being no longer applicable. The analysis of

    this type of fault is often simplified by using methods such as symmetrical

    components.

    Transient fault

    A transient fault is a fault that is no longer present if power is disconnected for a

    short time.

    Many faults in overhead powerlines are transient in nature. At the occurrence of

    a fault power system protectionoperates to isolate area of the fault. A transient

    fault will then clear and the powerline can be returned to service. Typical

    examples of transient faults include:

    momentary tree contact

    bird or other animal contact

    lightning strike

    conductor clash

    In electricity transmission and distribution systems an automatic reclose functionis commonly used on overhead lines to attempt to restore power in the event of a

    transient fault. This functionality is not as common on underground systems as

    faults there are typically of a persistent nature. Transient faults may still cause

    damage both at the site of the original fault or elsewhere in the network as fault

    current is generated.

  • 8/6/2019 Line to Ground Fault

    2/17

    [edit]Persistent fault

    A persistent fault does not disappear when power is disconnected. Faults in

    underground power cables are often persistent. Underground power lines are not

    affected by trees orlightning, so faults, when they occur, are probably due todamage. In such cases, if the line is reconnected, it is likely to be only damaged

    further.

    [edit]Symmetric fault

    A symmetric, symmetrical orbalanced fault affects each of the three-phases

    equally. In transmission line faults, roughly 5% are symmetric [citation needed]. This is

    in contrast to an asymmetric fault, where the three phases are not affected

    equally. In practice, most faults in power systems are unbalanced. With this inmind, symmetric faults can be viewed as somewhat of an abstraction; however,

    as asymmetric faults are difficult to analyze, analysis of asymmetric faults is built

    up from a thorough understanding of symmetric faults.

    [edit]Asymetric fault

    An asymmetric orunbalanced fault does not affect each of the three phases

    equally.

    Common types of asymmetric faults, and their causes:

    line-to-line - a short circuit between lines, caused by ionization of air, or when

    lines come into physical contact, for example due to a broken insulator.

    line-to-ground- a short circuit between one line and ground, very often

    caused by physical contact, for example due to lightning or

    otherstorm damage

    double line-to-ground- two lines come into contact with the ground (and each

    other), also commonly due to storm damage

    [edit]Analysis

    Symmetric faults can be analyzed via the same methods as any other

    phenomena in power systems, and in fact manysoftware tools exist to

    accomplish this type of analysis automatically (see power flow study). However,

    there is another method which is as accurate and is usually more instructive.

  • 8/6/2019 Line to Ground Fault

    3/17

    First, some simplifying assumptions are made. It is assumed that all electrical

    generators in the system are in phase, and operating at the nominal voltage of

    the system. Electric motors can also be considered to be generators, because

    when a fault occurs, they usually supply rather than draw power. The voltages

    and currents are then calculated for thisbase case.

    Next, the location of the fault is considered to be supplied with a negative voltage

    source, equal to the voltage at that location in the base case, while all other

    sources are set to zero. This method makes use of the principle ofsuperposition.

    To obtain a more accurate result, these calculations should be performed

    separately for three separate time ranges:

    subtransientis first, and is associated with the largest currents

    transientcomes between subtransient and steady-state

    steady-state occurs after all the transients have had time to settle

    An asymmetric fault breaks the underlying assumptions used in three phase

    power, namely that the load is balanced on all three phases. Consequently, it is

    impossible to directlyuse tools such as the one-line diagram, where only one

    phase is considered. However, due to the linearity of power systems, it is usual

    to consider the resulting voltages and currentsas a superposition ofsymmetrical

    components, to which three phase analysis can be applied.

    In the method of symmetric components, the power system is seen as

    a superposition of three components:

    a positive-sequence component, in which the phases are in the same order as

    the original system, i.e., a-b-c

    a negative-sequence component, in which the phases are in the opposite

    order as the original system, i.e., a-c-b

    a zero-sequence component, which is not truly a three phase system, but

    instead all three phases are in phase with each other.To determine the currents resulting from an asymmetrical fault, one must first

    know the per-unit zero-, positive-, and negative-sequence impedances of the

    transmission lines, generators, and transformers involved. Three separate

    circuits are then constructed using these impedances. The individual circuits are

    then connected together in a particular arrangement that depends upon the type

  • 8/6/2019 Line to Ground Fault

    4/17

    of fault being studied (this can be found in most power systems textbooks). Once

    the sequence circuits are properly connected, the network can then be analyzed

    using classical circuit analysis techniques. The solution results in voltages and

    currents that exist as symmetrical components; these must be transformed back

    into phase values by using the A matrix.

    Analysis of the prospective short-circuit current is required for selection of

    protective devices such as fuses and circuit breakers. If a circuit is to be properly

    protected, the fault current must be high enough to operate the protective device

    within as short a time as possible; also the protective device must be able to

    withstand the fault current and extinguish any resulting arcs without itself being

    destroyed or sustaining the arc for any significant length of time.

    The magnitude of fault currents differ widely depending on the type of earthing

    system used, the installation's supply type and earthing system, and its proximity

    to the supply. For example, for a domestic UK 230 V, 60 A TN-S or USA 120

    V/240 V supply, fault currents may be a few thousand amperes. Large low-

    voltage networks with multiple sources may have fault levels of 300,000

    amperes. A high-resistance-grounded system may restrict line to ground fault

    current to only 5 amperes. Prior to selecting protective devices, prospective fault

    current must be measured reliably at the origin of the installation and at the

    furthest point of each circuit, and this information applied properly to the

    application of the circuits.

    [edit]Detecting and locating faults

    Locating faults in a cable system can be done either with the circuit de-

    energized, or in some cases, with the circuit under power. Fault location

    techniques can be broadly divided into terminal methods, which use voltages and

    currents measured at the ends of the cable, and tracer methods, which require

    inspection along the length of the cable. Terminal methods can be used to locate

    the general area of the fault, to expedite tracing on a long or buried cable.[1]

    In very simple wiring systems, the fault location is often found through visual

    inspection of the wires. In complex wiring systems (e.g. aircraft wiring) where the

    electrical wires may be hidden behind cabinets and extended for miles, wiring

    faults are located with a Time-domain reflectometer.[2] The time domain

  • 8/6/2019 Line to Ground Fault

    5/17

    reflectometer sends a pulse down the wire and then analyzes the returning

    reflected pulse to identify faults within the electrical wire.

    In historic submarine telegraph cables, sensitive galvanometers were used to

    measure fault currents; by testing at both ends of a faulted cable, the fault

    location could be isolated to within a few miles, which allowed the cable to be

    grappled up and repaired. The Murrayloop and the Varleyloop were two types of

    connections for locating faults in cables

    Sometimes an insulation fault in a power cable will not show up at lower

    voltages. A "thumper" test set applies a high-energy, high-voltage pulse to the

    cable. Fault location is done by listening for the sound of the discharge at the

    fault. While this test contributes to damage at the cable site, it is practical

    because the faulted location would have to be re-insulated when found in any

    case.[3]

    In a high resistance grounded distribution system, a feeder may develop a fault

    to ground but the system continues in operation. The faulted, but energized,

    feeder can be found with a ring-type current transformer collecting all the phase

    wires of the circuit; only the circuit containing a fault to ground will show a net

    unbalanced current. To make the ground fault current easier to detect, the

    grounding resistor of the system may be switched between two values so that the

    fault current pulses.

    A time-domain reflectometer(TDR) is an electronic instrument used to

    characterize and locate faults in metallic cables (for example, twisted wire

    pairs, coaxial cables).[1] It can also be used to locate discontinuities in a

    connector, printed circuit board, or any other electrical path. The equivalent

    device foroptical fiberis an optical time-domain reflectometer.

    Description

    A TDR transmits a short rise timepulse along the conductor. If the conductor is

    of a uniform impedance and is properlyterminated, the entire transmitted pulse

    will be absorbed in the far-end termination and no signal will be reflected toward

    the TDR. Any impedance discontinuities will cause some of the incident signal to

    be sent back towards the source. This is similar in principle to radar.

  • 8/6/2019 Line to Ground Fault

    6/17

    Increases in the impedance create a reflection that reinforces the original pulse

    whilst decreases in the impedance create a reflection that opposes the original

    pulse.

    The resulting reflected pulse that is measured at the output/input to the TDR is

    displayed or plotted as a function of time and, because the speed of signal

    propagation is almost constant for a given transmission medium, can be read as

    a function ofcable length.

    Because of this sensitivity to impedance variations, a TDR may be used to verify

    cable impedance characteristics,splice and connectorlocations and associated

    losses, and estimate cable lengths.

    [edit]Example Traces

    These traces were produced by the Time Domain Reflectometer made from

    common lab equipment connected to approximately 100 feet of 50 ohm coaxial

    cable. The propagation velocity of this cable is approximately 66% of the speed

    of light in a vacuum.

    Simple TDR made from lab equipment

  • 8/6/2019 Line to Ground Fault

    7/17

    Simple TDR made from lab equipment

    TDR trace of a transmission line

    with an open termination.

    TDR trace of a transmission line

    with a short circuit termination.

    TDR trace of a transmission line

    with a 1nF capacitor termination.

  • 8/6/2019 Line to Ground Fault

    8/17

    TDR trace of a transmission line with an almost

    ideal termination.

    TDR trace of a transmission line terminated on an

    oscilloscope high impedance input. The blue trace is

    the pulse as seen at the far end. It is offset so that

    the baseline of each channel is visible.

    [edit]ExplanationConsider the case where the far end of the cable is shorted (that is, it is

    terminated into zero ohms impedance). When the rising edge of the pulse is

    launched down the cable, the voltage at the launching point "steps up" to a given

    value instantly and the pulse begins propagating down the cable towards theshort. When the pulse hits the short, no energy is absorbed at the far end.

    Instead, an opposing pulse reflects back from the short towards the launching

    end. It is only when this opposing reflection finally reaches the launch point that

    the voltage at this launching point abruptly drops back to zero, signaling the fact

    that there is a short at the end of the cable. That is, the TDR had no indication

    that there is a short at the end of the cable until its emitted pulse can travel down

    the cable at roughly the speed of light and the echo can return back up the cable

    at the same speed. It is only after this round-trip delay that the short can be

    perceived by the TDR. Assuming that one knows the signal propagation speed in

    the particular cable-under-test, then in this way, the distance to the short can be

    measured.

    A similar effect occurs if the far end of the cable is an open circuit (terminated

    into an infinite impedance). In this case, though, the reflection from the far end is

  • 8/6/2019 Line to Ground Fault

    9/17

    polarized identically with the original pulse and adds to it rather than cancelling it

    out. So after a round-trip delay, the voltage at the TDR abruptly jumps to twice

    the originally-applied voltage.

    Note that a theoretical perfect termination at the far end of the cable would

    entirely absorb the applied pulse without causing any reflection. In this case, it

    would be impossible to determine the actual length of the cable. Luckily, perfect

    terminations are very rare and some small reflection is nearly always caused.

    The magnitude of the reflection is referred to as the reflection coefficient or .

    The coefficient ranges from 1 (open circuit) to -1 (short circuit). The value of zero

    means that there is no reflection. The reflection coefficient is calculated as

    follows:

    Where Zo is defined as the characteristic impedance of the transmission medium

    and Zt is the impedance of the termination at the far end of the transmission line.

    Any discontinuity can be viewed as a termination impedance and substituted as

    Zt. This includes abrupt changes in the characteristic impedance. As an example,

    a trace width on a printed circuit board doubled at its midsection would constitute

    a discontinuity. Some of the energy will be reflected back to the driving source;

    the remaining energy will be transmitted. This is also known as a scatteringjunction.

    [edit]Usage

    Time domain reflectometers are commonly used for in-place testing of very long

    cable runs, where it is impractical to dig up or remove what may be a kilometers-

    long cable. They are indispensable forpreventive

    maintenance oftelecommunication lines, as they can reveal growing resistance

    levels on joints and connectors as they corrode, and

    increasing insulation leakage as it degrades and absorbs moisture long before

    either leads to catastrophic failures. Using a TDR, it is possible to pinpoint a fault

    to within centimetres.

    TDRs are also very useful tools fortechnical surveillance counter-measures,

    where they help determine the existence and location ofwire taps. The slight

  • 8/6/2019 Line to Ground Fault

    10/17

    change in line impedance caused by the introduction of a tap or splice will show

    up on the screen of a TDR when connected to a phone line.

    TDR equipment is also an essential tool in the failure analysis of modern high-

    frequency printed circuit boards whose signal traces are carefully crafted to

    emulate transmission lines. By observing reflections, any unsoldered pins of

    a ball grid array device can be detected. Additionally, short circuited pins can

    also be detected in a similar fashion.

    The TDR principle is used in industrial settings, in situations as diverse as the

    testing ofintegrated circuit packages to measuring liquid levels. In the former, the

    time domain reflectometer is used to isolate failing sites in the same. The latter is

    primarily limited to the process industry.

    [edit]TDR in level measurementIn a TDR-based level measurement device, a low-energy electromagnetic

    impulse generated by the sensors circuitry is propagated along a thin wave

    guide (also referred to as a probe) usually a metal rod or a steel cable. When

    this impulse hits the surface of the medium to be measured, part of the impulse

    energy is reflected back up the probe to the circuitry which then calculates the

    fluid level from the time difference between the impulse sent and the impulse

    reflected (in nanoseconds). The sensors can output the analyzed level as a

    continuous analog signal or switch output signals. In TDR technology, the

    impulse velocity is primarily affected by the permittivity of the medium through

    which the pulse propagates, which can vary greatly by the moisture content and

    temperature of the medium. In most cases, this can be corrected for without

    undue difficulty. However, in complex environments, such as in boiling and/or

    high temperature environments, this can be a significant signal processing

    dilemma. In particular, determining the froth(foam) height and true collapsed

    liquid level in a frothy / boiling medium can be very difficult.

    [edit]TDR used in Anchor Cables in Dams

    The Dam Safety Interest Group of CEA Technologies, Inc. (CEATI), a consortium

    of electrical power organizations, has applied Spread-spectrum time-domain

    reflectometry to identify potential faults in concrete dam anchor cables. The key

    benefit of Time Domain reflectometry over other testing methods is the non-

    destructive method of these tests.

  • 8/6/2019 Line to Ground Fault

    11/17

    [edit]TDR used in the earth and agricultural sciences

    TDR is used to determine moisture content in soil and porous media, where over

    the last two decades substantial advances have been made; including in soils,

    grains and food stuffs, and in sediments. The key to TDRs success is its ability

    to accurately determine the permittivity (dielectric constant) of a material from

    wave propagation, and the fact that there is a strong relationship between the

    permittivity of a material and its water content, as demonstrated in the pioneering

    works of Hoekstra and Delaney (1974) and Topp et al. (1980). Recent reviews

    and reference work on the subject include, Topp and Reynolds (1998), Noborio

    (2001), Pettinellia et al. (2002), Topp and Ferre (2002) and Robinson et al.

    (2003). The TDR method is a transmission line technique, and determines an

    apparent TDR permittivity (Ka) from the travel time of an electromagnetic wave

    that propagates along a transmission line, usually two or more parallel metal rodsembedded in a soil or sediment. TDR probes are usually between 10 and 30 cm

    in length and connected to the TDR via a coaxial cable.

    [edit]TDR in geotechnical usage

    Time domain reflectometry has also been utilized to monitor slope movement in a

    variety of geotechnical settings including highway cuts, rail beds, and open pit

    mines (Dowding & O'Connor, 1984, 2000a, 2000b; Kane & Beck, 1999). In

    stability monitoring applications using TDR, a coaxial cable is installed in a

    vertical borehole passing through the region of concern. The electrical

    impedance at any point along a coaxial cable changes with deformation of the

    insulator between the conductors. A brittle grout surrounds the cable to translate

    earth movement into an abrupt cable deformation that shows up as a detectable

    peak in the reflectance trace. Until recently, the technique was relatively

    insensitive to small slope movements and could not be automated because it

    relied on human detection of changes in the reflectance trace over time.

    Farrington and Sargand (2004) developed a simple signal processing technique

    using numerical derivatives to extract reliable indications of slope movement fromthe TDR data much earlier than by conventional interpretation.

    [edit]TDR in semiconductor device analysis

    Time domain reflectometry is used in semiconductorfailure analysis as a non-

    destructive method for the location of defects in semiconductor device packages.

  • 8/6/2019 Line to Ground Fault

    12/17

    The TDR provides an electrical signature of individual conductive traces in the

    device package, and is useful for determining the location of opens and shorts.

    [edit]TDR in aviation wiring maintenance

    Time domain reflectometry, specifically spread spectrum time domainreflectometry is used for aviation wiring for both preventative maintenance and

    intermittent fault location.[2] The spread spectrum time domain reflectometry has

    the advantage of precisely locating the fault location within thousands of miles of

    aviation wiring. Additionally, this technology is being considering for live aviation

    monitoring as the spread spectrum reflectometry works on a live wire.

    Utah State conducted research[3] on use of time domain reflectometry for

    identifying chafing of electrical wires in aircraft. This chafing is known to cause

    electrical failures on aircraft so the ability to identify potential problems prior to afailure that has life-ending implications.

    In communications and electronic engineering, a transmission line is a

    specialized cable designed to carry alternating current ofradio frequency, that is,

    currents with a frequency high enough that its wave nature must be taken into

    account. Transmission lines are used for purposes such as connecting radio

    transmitters and receivers with theirantennas, distributing cable

    television signals, and computer network connections.

    Ordinary electrical cables suffice to carry low frequency AC, such as mains

    power, which reverses direction 100 to 120 times per second (cycling 50 to 60

    times per second). However, they cannot be used to carry currents in the radio

    frequency range or higher, which reverse direction millions to billions of times per

    second, because the energy tends to radiate off the cable as radio waves,

    causing power losses. Radio frequency currents also tend to reflect from

    discontinuities in the cable such as connectors, and travel back down the cable

    toward the source. These reflections act as bottlenecks, preventing the powerfrom reaching the destination. Transmission lines use specialized construction

    such as precise conductor dimensions and spacing, and impedance matching, to

    carry electromagnetic signals with minimal reflections and power losses. Types

    of transmission line include ladder line, coaxial cable, dielectric

    slabs,stripline, optical fiber, and waveguides. The higher the frequency, the

  • 8/6/2019 Line to Ground Fault

    13/17

    shorter are the waves in a transmission medium. Transmission lines must be

    used when the frequency is high enough that the wavelength of the waves

    begins to approach the length of the cable used. To conduct energy at

    frequencies above the radio range, such as millimeter waves, infrared, and light,

    the waves become much smaller than the dimensions of the structures used toguide them, so transmission line techniques become inadequate and the

    methods ofoptics are used.

    The theory ofsound wave propagation is very similar mathematically to that of

    electromagnetic waves, so techniques from transmission line theory are also

    used to build structures to conduct acoustic waves; and these are also called

    transmission lines.

    Transient fault

    A transient fault is a fault that is no longer present if power is disconnected for a

    short time.

    Many faults in overhead powerlines are transient in nature. At the occurrence of

    a fault power system protectionoperates to isolate area of the fault. A transient

    fault will then clear and the powerline can be returned to service. Typical

    examples of transient faults include:

    momentary tree contact

    bird or other animal contact

    lightning strike

    conductor clash

    In electricity transmission and distribution systems an automatic reclose function

    is commonly used on overhead lines to attempt to restore power in the event of a

    transient fault. This functionality is not as common on underground systems as

    faults there are typically of a persistent nature. Transient faults may still cause

    damage both at the site of the original fault or elsewhere in the network as fault

    current is generated.

    [edit]Persistent fault

  • 8/6/2019 Line to Ground Fault

    14/17

    A persistent fault does not disappear when power is disconnected. Faults in

    underground power cables are often persistent. Underground power lines are not

    affected by trees orlightning, so faults, when they occur, are probably due to

    damage. In such cases, if the line is reconnected, it is likely to be only damaged

    further.

    [edit]Symmetric fault

    A symmetric, symmetrical orbalanced fault affects each of the three-phases

    equally. In transmission line faults, roughly 5% are symmetric [citation needed]. This is

    in contrast to an asymmetric fault, where the three phases are not affected

    equally. In practice, most faults in power systems are unbalanced. With this in

    mind, symmetric faults can be viewed as somewhat of an abstraction; however,

    as asymmetric faults are difficult to analyze, analysis of asymmetric faults is builtup from a thorough understanding of symmetric faults.

    [edit]Asymetric fault

    An asymmetric orunbalanced fault does not affect each of the three phases

    equally.

    Common types of asymmetric faults, and their causes:

    line-to-line - a short circuit between lines, caused by ionization of air, or when

    lines come into physical contact, for example due to a broken insulator.

    line-to-ground- a short circuit between one line and ground, very often

    caused by physical contact, for example due to lightning or

    otherstorm damage

    double line-to-ground- two lines come into contact with the ground (and each

    other), also commonly due to storm damage

    [edit]Analysis

    Symmetric faults can be analyzed via the same methods as any other

    phenomena in power systems, and in fact manysoftware tools exist to

    accomplish this type of analysis automatically (see power flow study). However,

    there is another method which is as accurate and is usually more instructive.

    First, some simplifying assumptions are made. It is assumed that all electrical

    generators in the system are in phase, and operating at the nominal voltage of

  • 8/6/2019 Line to Ground Fault

    15/17

    the system. Electric motors can also be considered to be generators, because

    when a fault occurs, they usually supply rather than draw power. The voltages

    and currents are then calculated for thisbase case.

    Next, the location of the fault is considered to be supplied with a negative voltage

    source, equal to the voltage at that location in the base case, while all other

    sources are set to zero. This method makes use of the principle ofsuperposition.

    To obtain a more accurate result, these calculations should be performed

    separately for three separate time ranges:

    subtransientis first, and is associated with the largest currents

    transientcomes between subtransient and steady-state

    steady-state occurs after all the transients have had time to settle

    An asymmetric fault breaks the underlying assumptions used in three phase

    power, namely that the load is balanced on all three phases. Consequently, it is

    impossible to directlyuse tools such as the one-line diagram, where only one

    phase is considered. However, due to the linearity of power systems, it is usual

    to consider the resulting voltages and currentsas a superposition ofsymmetrical

    components, to which three phase analysis can be applied.

    In the method of symmetric components, the power system is seen as

    a superposition of three components:

    a positive-sequence component, in which the phases are in the same order as

    the original system, i.e., a-b-c

    a negative-sequence component, in which the phases are in the opposite

    order as the original system, i.e., a-c-b

    a zero-sequence component, which is not truly a three phase system, but

    instead all three phases are in phase with each other.

    To determine the currents resulting from an asymmetrical fault, one must first

    know the per-unit zero-, positive-, and negative-sequence impedances of thetransmission lines, generators, and transformers involved. Three separate

    circuits are then constructed using these impedances. The individual circuits are

    then connected together in a particular arrangement that depends upon the type

    of fault being studied (this can be found in most power systems textbooks). Once

    the sequence circuits are properly connected, the network can then be analyzed

  • 8/6/2019 Line to Ground Fault

    16/17

    using classical circuit analysis techniques. The solution results in voltages and

    currents that exist as symmetrical components; these must be transformed back

    into phase values by using the A matrix.

    Analysis of the prospective short-circuit current is required for selection of

    protective devices such as fuses and circuit breakers. If a circuit is to be properly

    protected, the fault current must be high enough to operate the protective device

    within as short a time as possible; also the protective device must be able to

    withstand the fault current and extinguish any resulting arcs without itself being

    destroyed or sustaining the arc for any significant length of time.

    The magnitude of fault currents differ widely depending on the type of earthing

    system used, the installation's supply type and earthing system, and its proximity

    to the supply. For example, for a domestic UK 230 V, 60 A TN-S or USA 120

    V/240 V supply, fault currents may be a few thousand amperes. Large low-

    voltage networks with multiple sources may have fault levels of 300,000

    amperes. A high-resistance-grounded system may restrict line to ground fault

    current to only 5 amperes. Prior to selecting protective devices, prospective fault

    current must be measured reliably at the origin of the installation and at the

    furthest point of each circuit, and this information applied properly to the

    application of the circuits.

    [edit]Detecting and locating faults

    Locating faults in a cable system can be done either with the circuit de-

    energized, or in some cases, with the circuit under power. Fault location

    techniques can be broadly divided into terminal methods, which use voltages and

    currents measured at the ends of the cable, and tracer methods, which require

    inspection along the length of the cable. Terminal methods can be used to locate

    the general area of the fault, to expedite tracing on a long or buried cable.[1]

    In very simple wiring systems, the fault location is often found through visual

    inspection of the wires. In complex wiring systems (e.g. aircraft wiring) where theelectrical wires may be hidden behind cabinets and extended for miles, wiring

    faults are located with a Time-domain reflectometer.[2] The time domain

    reflectometer sends a pulse down the wire and then analyzes the returning

    reflected pulse to identify faults within the electrical wire.

  • 8/6/2019 Line to Ground Fault

    17/17

    In historic submarine telegraph cables, sensitive galvanometers were used to

    measure fault currents; by testing at both ends of a faulted cable, the fault

    location could be isolated to within a few miles, which allowed the cable to be

    grappled up and repaired. The Murrayloop and the Varleyloop were two types of

    connections for locating faults in cables

    Sometimes an insulation fault in a power cable will not show up at lower

    voltages. A "thumper" test set applies a high-energy, high-voltage pulse to the

    cable. Fault location is done by listening for the sound of the discharge at the

    fault. While this test contributes to damage at the cable site, it is practical

    because the faulted location would have to be re-insulated when found in any

    case.[3]

    In a high resistance grounded distribution system, a feeder may develop a fault

    to ground but the system continues in operation. The faulted, but energized,

    feeder can be found with a ring-type current transformer collecting all the phase

    wires of the circuit; only the circuit containing a fault to ground will show a net

    unbalanced current. To make the ground fault current easier to detect, the

    grounding resistor of the system may be switched between two values so that the

    fault current pulses.

    [edit]Batteries

    The prospective fault current of larger batteries, such as deep-cyclebatteries used in stand-alone power systems, is often given by the manufacturer.

    In Australia, when this information is not given, the prospective fault current in

    amperes "should be considered to be 6 times the nominal battery capacity at

    the C120 Ah rate," according to AS 4086 part 2 (Appendix H).