Liquid Cooling Guidelines

Michael K Patterson, PhD, PE, DCEP

Data Center and Connected Systems Group

Page 2: Liquid Cooling Guidelines

2

What’s

Next?

Ice Cooled System

(Circa 1890) General Electric Room Cooler

(Circa 1932) Computer Room Air Conditioner

(Circa 1970)

ASHRAE Overview

1. ASHRAE (American Society of Heating Refrigerating, & Air conditioning Engineering) formed in 1894 is a technical society; specializing in cooling.

2. ASHRAE has over 50,000 members & has members in 135 countries

3. ASHRAE focuses on maintaining an unbiased role within the industry

4. ASHRAE actively writes standards, guidelines, model codes, etc.

Page 3: Liquid Cooling Guidelines

3

ASHRAE and Datacenters

• ASHRAE – American Society of Heating, Refrigeration and Air-conditioning

Engineers

•Technical Committee 9.9 – Mission Critical Facilities, Technology Spaces and

Electronic Equipment – Datacom Equipment producers,

(manufacturers of computer hardware, HVAC equipment, software vendors, etc)

– User of Datacom Equipment

(facility owners, operators, managers, etc)

– General Interest

(government agencies, utilities, consultants, academia, testing laboratories, etc.)

• Mission Statement: To be recognized by ALL areas of the datacom

industry as the unbiased engineering leader in HVAC and an effective

provider of technical information for the datacom industry.

Page 4: Liquid Cooling Guidelines

4

ASHRAE Datacom Book Series

Page 5: Liquid Cooling Guidelines

5

2011 ASHRAE Air-Cooled Thermal Guidelines

A1

A2

A3 A4

ASHRAE – Recommended

*Envelopes Represent Conditions at IT Equipment Inlet

Degrees C 27 32 35 40 45 Class R A1 A2 A3 A4

Why not something similar

for liquid cooling?

Page 6: Liquid Cooling Guidelines

6

ASHRAE Datacom Book Series

Page 7: Liquid Cooling Guidelines

7

2006 book now supplemented by 2011 WP

Page 8: Liquid Cooling Guidelines

8

2011 ASHRAE Liquid Cooling Guidelines

• Drivers for More Detailed Liquid Guidelines – Improve and Increase Liquid

Cooling Use and Reduce Confusion among users and suppliers

• HPC Challenges with more and more power per node and per rack, pushing

to and past air-cooling limits

• Range of cooling architectures not well aligned to IT requirements

• ASHRAE TC 9.9 Response – Enable Opportunity for Innovation

• Defined liquid cooling classes with temperature ranges

• Created guidance to effectively implement liquid cooling through new

White Paper

• ASHRAE TC 9.9 IT Subcommittee: Bull, Cisco, Cray, Dell, EMC, Fujitsu, HP,

IBM, Intel, Juniper, Lucent, Nortel Networks, Oracle/Sun, Seagate, SGI,

Teradata

Cross HPC-IT Team collaboratively authors WP on liquid cooling

Page 9: Liquid Cooling Guidelines

9

What is liquid cooling? Which liquid are we talking about?

Page 10: Liquid Cooling Guidelines

10

Classes

Typical Infrastructure Design Facility Supply

Water Temp (C) IT Equipment Availability Main Cooling

Equipment

Supplemental Cooling

Equipment W1

Chiller/Cooling Tower Water-side Economizer

Chiller

2 – 17 Now available

W2 2 – 27

W3 Cooling Tower Chiller 2 – 32 Not generally

available, dependent on future demand

W4

Water-side Economizer (with

drycooler or cooling tower)

Nothing 2 – 45

W5 Building Heating

System Cooling Tower

> 45

Specialized systems

Required Cooling Infrastructure: Balance of

Silicon/Datacenter

2011 ASHRAE Liquid-Cooled Thermal Guidelines

Page 11: Liquid Cooling Guidelines

11

ASHRAE Classes

Page 12: Liquid Cooling Guidelines

12

More from the White Paper

Operational Considerations

• Condensation

• Flow and differential

pressure limits

• Class specific limits

Water flow rates vs capacity

Velocity Limits

• By size / material

System Design

• Materials

• Connections

• Heat Rejection devices

Water Quality

• Corrosion

• Fouling

• Scaling

• Micro

Bibliography

Page 13: Liquid Cooling Guidelines

13

As advertised earlier… don’t miss these

Birds of Feather: "'Hot' for Warm Water Cooling"

• Tuesday, 5:30-7:00PM WSCC 613/614

State of the Practice: "'Hot' for Warm Water Cooling"

• Wednesday, 4:00-4:30PM TC 202

Page 14: Liquid Cooling Guidelines

14

Wet and Dry Bulb Temperatures

ASHRAE CD, 99.6% of yearly hours, National Laboratory HPC Locations.

60

65

70

75

80

85

Tem

pe

ratu

re (°

F)Wet Bulb Temperature - 99.6% of hours per ASHRAE CD - U.S. National Laboratories

Selected Max. = 79.7 °F (26.5°C)

16

18

21

24

27

29

Tem

pe

ratu

re (°

C)

75

80

85

90

95

100

Tem

pe

ratu

re (°

F)

Dry Bulb Temperature - 99.6% of hours per ASHRAE CD - U.S. National Laboratories

Max. = 99.5 °F (37.5°C)38

35

32

24

27

29

Tem

pe

ratu

re (°

C)

Page 15: Liquid Cooling Guidelines

15

Air Cooled Server Dry Cooler or Cooling Tower

Using Dry Cooler Only Water Temp. Supply to Building

109°F (43°C)

Chip Thermal Margin 7°F (4°C)

Using Dry Cooler Only

Chip Thermal Margin 26°F (15°C)

Using Cooling Tower Only

Using Cooling Tower Only Water Temp. Supply to Building

89°F (32°C)

Page 16: Liquid Cooling Guidelines

16

EEHPCWG ASHRAE

L1 17 °C Legacy systems w/ chiller 2-17 °C

W1

Cooling tower & Chiller based Rack level cooling

2-27 °C

W2

L2 32 °C

Cooling tower & Chiller based Rack/Component level cooling

2-32 °C

W3

L3 43 °C

Dry cooler based Component level cooling

2-45 °C

W4

Heat re-use opportunity Component level cooling

>45 °C

W5

Infrastructure In

IT Out

Two liquid cooling activities meeting in the middle