LV switch-disconnectors
Interpact INS/INV40 to 2500 A
Modularity…the sky is the limit
Building a New Electric World
Schneider Electric 1
Generalcontents
Presentation 2
Functions and characteristics 17
Installation recommendations 63
Dimensions and connection 87
Additionnal characteristics 105
Catalogue numbers 115
Schneider Electric16
Schneider Electric 17
Functions and characteristics
Presentation 2
General characteristics 18Switch-disconnector selection 20Interpact INS40 to 160 20Interpact INS250-100 to 630 24Interpact INS630b to 2500 28Interpact INV100 to 630 32Interpact INV630b to 2500 36
Complete source-changeover assembly selection 40Interpact INS250-100 to 630 40
Installation 44Connection 45Interpact INS40 to 160 45Interpact INS250 to 630 / INV100 to 630 48Interpact INS630b to 2500 / INV630b to 2500 51
Electrical and mechanical accessories 46Interpact INS250 / INV100 to 250 46Interpact INS320 to 630 / INV320 to 630 47Interpact INS630b to 2500 / INV630b to 2500 50
Connection accessories 52Distribution blocks 52One-piece spreader 53Insulation of live parts 54
Auxiliary contacts 55Current measurements 56Rotary handle 57Coupling accessories 58Disabling device closing 59Switching to a replacement source 60Accessories 61
Installation recommendations 63Dimensions and connection 85Additional characteristics 103Catalogue numbers 113
Schneider Electric20
Interpact INS switch-disconnectorsNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current Ithe at 60 °Cin enclosureRated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical AC 50/60 Hz220-240 V380-415 V440-480 V (1)
500 V660-690 V
Electrical DC125 V (2P in series)250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V230 V (NEMA)380-415 V440 V480 V (NEMA)500-525 V660-690 V
Rated duties uninterrupted dutyintermittent duty
Short-circuit making capacity Icm min. (switch-disconnector alone)(kA peak) max. (with upstream protection circuit breaker)
Short-time withstand current Icw (A rms) 1s3 s20 s30 s
Suitability for isolationDurability (category A) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz220-240 V380-415 V440 V500 V690 V
Electrical DC250 V
Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollution
Upstream protectionSee the “Additional characteristics” section, 308E5010
Switch-disconnector selection (cont.)
Interpact INS40 to 160
(1) Suitable for 480 V NEMA.
Functions andcharacteristics
Interpact INS80 switch-disconnector
0521
64_B
0521
68_A
Interpact INS160 switch-disconnector
Interpact INS160 emergency-off switch-disconnector
0592
02_A
Schneider Electric 21
INS40 INS63 INS80 INS100 INS125 INS1603, 4 3, 4 3, 4 3, 4 3, 4 3, 4
40 63 80 100 125 16040 63 80 100 125 160
690 690 690 750 750 7508 8 8 8 8 8500 500 500 690 690 690250 250 250 250 250 250690 690 690 750 750 750
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A40 40 63 63 80 80 100 100 125 125 160 16040 40 63 63 80 72 100 100 125 125 160 16040 40 63 63 80 63 100 100 125 125 160 16040 32 63 40 80 40 100 100 125 125 160 160– – – – – – 100 63 125 80 160 100
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A40 40 63 63 80 80 100 100 125 125 160 16040 40 63 63 80 80 100 100 125 125 160 160
11 15 22 22 37 457.5 15 15 22 37 4520 30 37 45 55 7522 30 37 55 55 9022 30 30 55 75 9018.5 22 22 55 75 110– – – 55 75 90b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % –15 15 15 20 20 2075 75 75 154 154 1543000 3000 3000 5500 5500 55001730 1730 1730 3175 3175 3175670 670 670 1230 1230 1230550 550 550 1000 1000 1000b b b b b b20000 20000 20000 15000 15000 15000
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500– – – – – – 1500 1500 1500 1500 1500 1500
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500b b b b b b– – – – – –b b b b b bIII III III III III III
– – – – – –
Switch-disconnector selection (cont.)
Interpact INS40 to 160 (cont.)
Functions andcharacteristics
Schneider Electric22
Switch-disconnector selection (cont.)
Interpact INS40 to 160 (cont.)
Functions andcharacteristics
Interpact INS switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplate
ConnectionBy cables to bare cable connectorsBy cables with lugs directly to terminals
to spreadersto vertical-connection adapters via cable-lug adapters
Flat-facing bars directly to terminalsto spreaders
Edgewise bars to vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter module
Control, locking and interlockingControl direct front rotary handle
extended front rotary handledirect lateral rotary handleextended lateral rotary handle
Locking by keylockby padlocks
Interlocking by keylockmechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3/4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Enclosure dimensions for ItheH x W x D (mm)
WD
H
E90
489
Schneider Electric 23
Switch-disconnector selection (cont.)
Interpact INS40 to 160 (cont.)
Functions andcharacteristics
INS40 INS63 INS80 INS100 INS125 INS160
b b b b b b– – – b b bb b b – – –b b b b b b
b b b b b b– – – b b b– – – – – –– – – – – –– – – b b b– – – – – –– – – – – –
b b b b b b– – – – – –– – – – – –– – – – – –
b b b b b bb b b b b bb b b b b bb b b b b b– – – – – –b b b b b b– – – – – –b b b b b b– – – b b b0.7 < C < 1.3 0.7 < C < 1.3 0.7 < C < 1.3 1.4 < C < 2 1.4 < C < 2 1.4 < C < 2
b b b b b b– – – – – –– – – – – –– – – – – –– – – – – –b b b b b bb b b b b bb b b b b b– – – – – –– – – – – –8 8 8 8 8 8
90 x 81 x 62.5 90 x 81 x 62.5 90 x 81 x 62.5 135 x 100 x 62.5 135 x 100 x 62.5 135 x 100 x 62.590 x 81 x 62.5 90 x 81 x 62.5 90 x 81 x 62.5 135 x 100 x 62.5 135 x 100 x 62.5 135 x 100 x 62.50.5 0.5 0.5 0.8 0.8 0.80.6 0.6 0.6 0.9 0.9 0.9
115 x 190 x 55 115 x 190 x 55 115 x 190 x 55 160 x 260 x 55 160 x 260 x 55 160 x 260 x 55
Schneider Electric24
Switch-disconnector selection (cont.)
Interpact INS250-100 to 630
(1) Suitable for 480 V NEMA.(2) 550 A (DC).
Functions andcharacteristics
Interpact INS switch-disconnectors INSNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 et EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current Ithe at 60 °Cin enclosureRated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical AC 50/60 Hz220-240 V380-415 V440-480 V (1)
500-525 V660-690 V
Electrical DC125 V (2P in series)250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V230 V (NEMA)380-415 V440 V480 V (NEMA)500-525 V660-690 V
Rated duties uninterrupted dutyintermittent duty
Short-circuit making capacity Icm min. (switch-disconnector alone)(kA peak) max. (with upstream protection circuit breaker)
Short-time withstand current Icw (A rms) 1s3 s20 s30 s
Suitability for isolationDurability (category A) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz440 V500 V690 V
Electrical DC250 V
Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollution
Upstream protectionSee the “Additional characteristics” section, 308E5015
0566
48_A
Interpact INS250 switch-disconnector
Interpact INS250 emergency-off switch-disconnector
0566
52_B
Interpact INS400 switch-disconnector
0594
87_B
Interpact INS400 emergency-off switch-disconnector
0594
88_B
Schneider Electric 25
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS6303, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4
100 160 200 250 320 400 500 630100 160 200 250 320 400 500 630 (2)
750 750 750 750 750 750 750 7508 8 8 8 8 8 8 8690 690 690 690 690 690 690 690250 250 250 250 250 250 250 250750 750 750 750 750 750 750 750
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A/B100 100 160 160 200 200 250 250 320 320 400 400 500 500 550 550/630100 100 160 160 200 200 250 250 320 320 400 400 500 500 550 550/630
22 45 55 75 90 110 132 20022 45 55 75 90 110 150 20045 75 90 132 160 200 250 31555 90 110 150 185 220 250 40055 90 110 150 185 220 250 37555 110 132 160 220 250 355 40055 90 160 210 250 400 500 560b b b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %30 30 30 30 50 50 50 50330 330 330 330 330 330 330 3308500 8500 8500 8500 20000 20000 20000 200004900 4900 4900 4900 11500 11500 11500 115002200 2200 2200 2200 4900 4900 4900 49001800 1800 1800 1800 4000 4000 4000 4000b b b b b b b b15000 15000 15000 15000 10000 10000 10000 10000
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23A DC23A DC23A DC23A1500 1500 1500 1500 1500 1500 1500 1500 1000 1000 1000 1000/200b b b b b b b b– – – – – – – –b b b b b b b bIII III III III III III III III
– – – – – – – –
Switch-disconnector selection (cont.)
Interpact INS250-100 to 630 (cont.)
Functions andcharacteristics
Schneider Electric26
Switch-disconnector selection (cont.)
Interpact INS250-100 to 630 (cont.)
Functions andcharacteristics
Interpact INS switch-disconnectorsInstallationFixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplate
ConnectionBy cables to bare cable connectorsBy cables with lugs directly to terminals
to spreadersto vertical-connection adapters
Flat-facing bars directly to terminalsto spreaders
Edgewise bars to vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter module
Control, locking and interlockingControl direct front rotary handle
extended front rotary handledirect lateral rotary handleextended lateral rotary handle
Locking by keylockby padlocks
Interlocking by keylockmechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3/4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Enclosure dimensions for ItheH x W x D (mm)
WD
H
E90
489
Schneider Electric 27
Switch-disconnector selection (cont.)
Interpact INS250-100 to 630 (cont.)
Fonctions etcaractéristiques
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630
b b b b b b b bb b b b b b b b– – – – – – – –b b b b b b b b
b b b b b b b bb b b b b b b bb b b b b b b b– – – – – – – –b b b b b b b bb b b b b b b b– – – – b b b b
b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b
b b b b b b b bb b b b b b b bb b b b – – – –b b b b – – – –b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b5 < C < 6.2 5 < C < 6.2 5 < C < 6.2 5 < C < 6.2 13.5 < C < 16.5 13.5 < C < 16.5 13.5 < C < 16.5 13.5 < C < 16.5
b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b bb b b b – – – –– – – – – – – –b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b15 15 15 15 50 50 50 50
140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 185 x 205 x 120 185 x 205 x 120 185 x 205 x 120 185 x 205 x 120140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 185 x 205 x 120 185 x 205 x 120 185 x 205 x 120 185 x 205 x 1202 2 2 2 4.6 4.6 4.6 4.62.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9
300 x 400 x 200 300 x 400 x 200 300 x 400 x 200 300 x 400 x 200 400 x 600 x 200 400 x 600 x 200 400 x 600 x 200 400 x 600 x 200
Schneider Electric28
Interpact INS switch-disconnectorsNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current Ithe at 60 °Cin enclosureRated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V)
Rated operational current (A) Ie Electrical AC 50/60 Hz220-240 V380-415 V440-480 V (1)
500-525 V660-690 V
Electrical DC125 V / (2P in series)250 V / (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V230 V (NEMA)380-415 V440 V480 V (NEMA)500-525 V660-690 V
Rated duties uninterrupted dutyintermittent duty
Short-circuit making capacity Icm min. (switch-disconnector alone)(kA peak) max. (with upstream protection circuit breaker)
Short-time withstand current Icw (A rms) 0.5 s1 s3 s20 s30 s
Suitability for isolationDurability (category A) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz220-240 V380-415 V440-480 V (1)
500-525 V660-690 V
Electrical DC125 V / 2 poles250 V / 4 poles
Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollution
Upstream protectionSee the “Additional characteristics” section, 308E5025 and 308E5030
Switch-disconnector selection (cont.)
Interpact INS630b to 2500Functions andcharacteristics
(1) Suitable for 480 V NEMA.(2) For vertical connection busbars only; for horizontalconnection busbars, see derating chart in "Installationrecommendations".
Interpact INS800 switch-disconnector
Interpact INS800 emergency-off switch-disconnector
E59
503_
AE
0000
0
Nouvelle photo à venir
Schneider Electric 29
INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS25003, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4
630 800 1000 1250 1600 (2) 2000 2500630 800 1000 1250 1600 (2) 2000 2500
1000 1000 1000 1000 1000 1000 100012 12 12 12 12 12 12690 690 690 690 690 690 690250 250 250 250 250 250 2501000 1000 1000 1000 1000 1000 1000
AC21A/AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A/B AC22A/B AC23A AC21A/AC22A AC23A AC21A/AC22A AC23A
630 800 800 800 1000 1000 1000 1250 1250 1250 1450/1600 1450/1600 1250 2000 – 2500 –630 800 800 800 1000 1000 1000 1250 1250 1250 1450/1600 1450/1600 1250 2000 – 2500 –630 800 800 800 1000 1000 1000 1250 1250 1250 1250/1600 1250/1600 1250 2000 – 2500 –630 800 800 800 1000 1000 1000 1250 1250 1250 1250/1600 1250/1600 1250 2000 – 2500 –630 800 800 800 1000 1000 1000 1250 1250 1250 1250/1600 1250/1600 1250 2000 – 2500 –
DC21A/DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A/B DC22A DC23A DC21A/DC22A DC23A DC21A/DC22A DC23A
630/2 800/2 800/2 800/2 1000/2 1000/2 1000/2 1250/2 1250/2 1250/2 1600/1600/2 1600/1600/2 1250/2 2000/2 – 2500/2 –630/4 800/4 800/4 800/4 1000/4 1000/4 1000/4 1250/4 1250/4 1250/4 1450/1600/4 1450/1600/4 1250/4 2000/4 – 2500/4 –
200 250 315 400 400 – –200 220 250 375 375 – –315 400 560 710 710 – –400 500 630 800 800 – –375 500 600 750 750 – –400 560 710 900 900 – –560 710 900 900 900 – –b b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %105 105 105 105 105 105 105330 330 330 105 105 105 10550 50 50 50 50 50 5035 35 35 35 35 50 5020 20 20 20 20 30 3020 10 10 10 10 13 138 8 8 8 8 11 11b b b b b b b5000 3000 3000 3000 3000 3000 3000
AC21A/AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A/B AC22A/B AC23A AC21A/AC22A AC21A/AC22A1000 500 500 500 500 500 500 500 500 500 500/100 500/100 500 500 5001000 500 500 500 500 500 500 500 500 500 500/100 500/100 500 500 5001000 500 500 500 500 500 500 500 500 500 500/100 500/100 500 500 5001000 500 500 500 500 500 500 500 500 500 500/100 500/100 500 500 5001000 500 500 500 500 500 500 500 500 500 500/100 500/100 500 500 500
DC21A/DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A/DC22A DC21A/DC22A1000 500 500 500 500 500 500 500 500 500 500 500 500 500 5001000 500 500 500 500 500 500 500 500 500 500 500 500 500 500b b b b b b b– – – – – – –b b b b b – –III III III III III III III
– – – – – – –
Switch-disconnector selection (cont.)
Interpact INS630b to 2500 (cont.)
Functions andcharacteristics
Schneider Electric30
Interpact INS switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplate
ConnectionBy cables to bare cable connectorsBy cables with lugs directly to terminals
to spreadersto vertical-connection adapters via cable-lug adapters
Flat-facing bars directly to terminalsto spreaders
Edgewise bars to vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter module
Control, locking and interlockingControl direct front rotary handle
extended front rotary handledirect lateral rotary handleextended lateral rotary handle
Locking by keylockby padlocks
Interlocking by keylockmechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3/4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Enclosure dimensions for ItheH x W x D (mm)
Switch-disconnector selection (cont.)
Interpact INS630b to 2500 (cont.)
Functions andcharacteristics
WD
H
E90
489
Schneider Electric 31
INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500
b b b b b b bb b b b b b b– – – – – – –b b b b b b b
– – – – – – –– – – – – b b– – – – – – –b b b b b – –b b b b b b bb b b b b – –b b b b b – –
b b b b b b b– – – – – – –– – – – – – –– – – – – – –
b b b b b b bb b b b b b b– – – – – – –– – – – – – –b b b b b b bb b b b b b bb b b b b b b– – – – – – –– – – – – – –30 30 30 30 30 60 60
– – – – – – –– – – – – – –b b b b b b bb b b b b b b– – – – – – –– – – – – – –b b b b b b bb b b b b b bb b b b b b b– – – – – – –50 50 50 50 50 50 50
340 x 300 x 198 340 x 300 x 198 340 x 300 x 198 340 x 300 x 198 340 x 300 x 198 348 x 440 x 325 348 x 440 x 325410 x 300 x 198 410 x 300 x 198 410 x 300 x 198 410 x 300 x 198 410 x 300 x 198 463 x 440 x 325 463 x 440 x 32514 14 14 14 14 35 3518 18 18 18 18 45 45
??? x ??? x ??? ??? x ??? x ??? ??? x ??? x ??? ??? x ??? x ??? ??? x ??? x ??? ??? x ??? x ??? ??? x ??? x ???
Switch-disconnector selection (cont.)
Interpact INS630b to 2500 (cont.)
Functions andcharacteristics
Schneider Electric32
Switch-disconnector selectionInterpact INV100 to 630
Functions andcharacteristics
0566
50_A
Interpact INV250 switch-disconnector
Interpact INV250 emergency-off switch-disconnector
0566
54_A
Interpact INV switch-disconnectorsNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current Ithe at 60 °Cin enclosureRated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical AC 50/60 Hz220-240 V380-415 V440-480 V (1)
500-525 V660-690 V
Electrical DC125 V (2P in series)250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V230 V (NEMA)380-415 V440 V480 V (NEMA)500-525 V660-690 V
Rated duties uninterrupted dutyintermittent duty
Short-circuit making capacity Icm min. (switch-disconnector alone)(kA peak) max. (with upstream protection circuit breaker)
Short-time withstand current Icw (A rms) 1s3 s20 s30 s
Suitability for isolationDurability (category A) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz440 V500 V690 V
Electrical DC250 V
Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollution
Upstream protectionSee the “Additional characteristics” section, 308E5015
(1) Suitable for 480 V NEMA.(2) 550 A (DC).
Schneider Electric 33
Switch-disconnector selection (cont.)
Interpact INV100 to 630 (cont.)
Functions andcharacteristics
INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV6303, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4
100 160 200 250 320 400 500 630100 160 200 250 320 400 500 630 (2)
750 750 750 750 750 750 750 7508 8 8 8 8 8 8 8690 690 690 690 690 690 690 690250 250 250 250 250 250 250 250750 750 750 750 750 750 750 750
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/B100 100 100 160 160 160 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630100 100 100 160 160 160 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630100 100 100 160 160 160 200 200 200 250 250 250 320 320 320 400 400 400 500 500 500 630 630 630/630100 100 100 160 160 160 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 630 630 500/630100 100 100 160 160 160 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 630 550 500/630
DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/B100 100 100 160 160 160 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 550 550 550/630100 100 100 160 160 160 200 200 200 250 250 200 320 320 320 400 400 400 500 500 500 550 550 550/630
22 45 55 75 90 110 132 20022 45 55 75 90 110 150 20045 75 90 132 160 200 250 31555 90 110 150 185 220 250 40055 50 110 150 185 220 250 37555 110 132 132 220 250 355 40055 90 160 160 250 400 500 560b b b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %30 30 30 30 50 50 50 50330 330 330 330 330 330 330 3308500 8500 8500 8500 20000 20000 20000 200004900 4900 4900 4900 11500 11500 11500 115002200 2200 2200 2200 4900 4900 4900 49001800 1800 1800 1800 4000 4000 4000 4000b b b b b b b b15000 15000 15000 15000 10000 10000 10000 10000
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/B1500 1500 1500 1500 1500 1500 1500 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/–1500 1500 1500 1500 1500 1500 1500 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/–1500 1500 1500 1500 1500 1500 1500 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/200
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/B1500 1500 1500 1500 1500 1500 1500 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/200b b b b b b b bb b b b b b b bb b b b b b b bIII III III III III III III III
– – – – – – – –
Schneider Electric34
Switch-disconnector selection (cont.)
Interpact INV100 to 630 (cont.)
Functions andcharacteristics
Interpact INV switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplate
ConnectionBy cables to bare cable connectorsBy cables with lugs directly to terminals
to spreadersto vertical-connection adapters via cable-lug adapters
Flat-facing bars directly to terminalsto spreaders
Edgewise bars to vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter module
Control, locking and interlockingControl direct front rotary handle
extended front rotary handledirect lateral rotary handleextended lateral rotary handle
Locking by keylockby padlocks
Interlocking by keylockmechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3/4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Enclosure dimensions for ItheH x W x D (mm)
WD
H
E90
489
Schneider Electric 35
Switch-disconnector selection (cont.)
Interpact INV100 to 630 (cont.)
Functions andcharacteristics
INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630
b b b b b b b bb b b b b b b b– – – – – – – –b b b b b b b b
b b b b b b b bb b b b b b b bb b b b b b b b– – – – – – – –b b b b b b b bb b b b b b b b– – – – b b b b
b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b
b b b b b b b bb b b b b b b bb b b b – – – –b b b b – – – –b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b– – – – – – – –5 < C < 6.2 5 < C < 6.2 5 < C < 6.2 5 < C < 6.2 13.5 < C < 16.5 13.5 < C < 16.5 13.5 < C < 16.5 13.5 < C < 16.5
b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b– – – – – – – –b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b15 15 15 15 50 50 50 50
140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 185 x 205 x 120 185 x 205 x 120 185 x 205 x 120 185 x 205 x 120140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 185 x 205 x 120 185 x 205 x 120 185 x 205 x 120 185 x 205 x 1202 2 2 2 4.6 4.6 4.6 4.62.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9
300 x 400 x 200 300 x 400 x 200 300 x 400 x 200 300 x 400 x 200 400 x 600 x 200 400 x 600 x 200 400 x 600 x 200 400 x 600 x 200
Schneider Electric36
Switch-disconnector selection (cont.)
Interpact INV630b to 2500Functions andcharacteristics
Interpact INV800 switch-disconnector
Interpact INV800 emergency-off switch-disconnector
E00
000
Nouvelle photo à venir
E00
000
Nouvelle photo à venir
(1) Suitable for 480 V NEMA.(2) For vertical connection busbars only; for horizontalconnection busbars, see derating chart in "Installationrecommendations".
Interpact INV switch-disconnectorsNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current Ithe at 60 °Cin enclosureRated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V)
Rated operational current (A) Ie Electrical AC 50/60 Hz220-240 V380-415 V440-480 V (1)
500-525 V660-690 V
Electrical DC125 V (2P in series)250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz220-240 V230 V (NEMA)380-415 V440 V480 V (NEMA)500-525 V660-690 V
Rated duties uninterrupted dutyintermittent duty
Short-circuit making capacity Icm min. (switch-disconnector alone)(kA peak) max. (with upstream protection circuit breaker)
Short-time withstand current Icw (A rms) 0.5 s1 s3 s20 s30 s
Suitability for isolationDurability (category A) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz220-240 V380-415 V440-480 V (1)
500-525 V660-690 V
Electrical DC125 V / 2 pôles250 V / 4 pôles
Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollution
Upstream protectionSee the “Additional characteristics” section, 308E5025 and 308E5030
Schneider Electric 37
Switch-disconnector selection (cont.)
Interpact INV630b to 2500 (cont.)
Functions andcharacteristics
INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV25003, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4
630 800 1000 1250 1600 (2) 2000 2500630 800 1000 1250 1600 (2) 2000 2500
1000 1000 1000 1000 1000 1000 100012 12 12 12 12 12 12690 690 690 690 690 690 690250 250 250 250 250 250 2501000 1000 1000 1000 1000 1000 1000
AC21A/AC22A/AC23B AC21A/AC22A/AC23B AC21A/AC22A/AC23B AC21A/AC22A/AC23B AC21A/B-AC22A/B AC23B AC21A/AC22A AC23B AC21A/AC22A AC23B630 800 1000 1250 1450/1600 1250 2000 – 2500 –630 800 1000 1250 1450/1600 1250 2000 – 2500 –630 800 1000 1250 1250/1600 1250 2000 – 2500 –630 800 1000 1250 1250/1600 1250 2000 – 2500 –630 800 1000 1250 1250/1600 1250 2000 – 2500 –
DC21A/DC22A/DC23B DC21A/DC22A/DC23B DC21A/DC22A/DC23B DC21A/DC22A/DC23B DC21A/DC22A DC23B DC21A/DC22A DC23B DC21A/DC22A DC23B630/2 800/2 1000/2 1250/2 1600/1600/2 1250/2 2000/2 – 2500/2 –630/4 800/4 1000/4 1250/4 1450/1600/4 1250/4 2000/4 – 2500/4 –
200 250 315 400 400 – –200 220 250 375 375 – –315 400 560 710 710 – –400 500 630 800 800 – –375 300 600 750 750 – –400 560 710 900 900 – –560 710 900 900 900 – –b b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %105 105 105 105 105 105 105330 330 330 105 105 105 10550 50 50 50 50 50 5035 35 35 35 35 50 5020 20 20 20 20 30 3010 10 10 10 10 13 138 8 8 8 8 11 11b b b b b b b5000 3000 3000 3000 3000 3000 3000
AC21A/AC22A AC23B AC21A/AC22A AC23B AC21A/AC22A AC23B AC21A/AC22A AC23B AC21A/B-AC22A/B AC23B AC21A/AC22A AC23B AC21A/AC22A AC23B1000 200 500 100 500 100 500 100 500/100 100 500 – 500 –1000 200 500 100 500 100 500 100 500/100 100 500 – 500 –1000 200 500 100 500 100 500 100 500/100 100 500 – 500 –1000 200 500 100 500 100 500 100 500/100 100 500 – 500 –1000 200 500 100 500 100 500 100 500/100 100 500 – 500 –
DC21A/DC22A DC23B DC21A/DC22A DC23B DC21A/DC22A DC23B DC21A/DC22A DC23B DC21A/DC22A DC23B DC21A/DC22A DC23B DC21A/DC22A DC23B1000 200 500 100 500 100 500 100 500 100 500 – 500 –1000 200 500 100 500 100 500 100 500 100 500 – 500 –b b b b b b bb b b b b b bb b b b b – –III III III III III III III
– – – – – – –
Schneider Electric38
Interpact INV switch-disconnectorsInstallation
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplate
ConnectionBy cables to bare cable connectorsBy cables with lugs directly to terminals
to spreadersto vertical-connection adapters via cable-lug adapters
Flat-facing bars directly to terminalsto spreaders
Edgewise bars to vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter module
Control, locking and interlockingControl direct front rotary handle
extended front rotary handledirect lateral rotary handleextended lateral rotary handle
Locking by keylockby padlocks
Interlocking by keylockmechanical
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3/4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Enclosure dimensions for ItheH x W x D (mm)
Switch-disconnector selection (cont.)
Interpact INV630b to 2500 (cont.)
Functions andcharacteristics
WD
H
E90
489
Schneider Electric 39
INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500
b b b b b b bb b b b b b b– – – – – – –b b b b b b b
– – – – – – –– – – – – b b– – – – – – –b b b b b – –b b b b b b bb b b b b – –b b b b b – –
b b b b b b b– – – – – – –– – – – – – –– – – – – – –
b b b b b b bb b b b b b b– – – – – – –– – – – – – –b b b b b b bb b b b b b bb b b b b b b– – – – – – –– – – – – – –30 30 30 30 30 60 60
– – – – – – –– – – – – – –b b b b b b bb b b b b b b– – – – – – –– – – – – – –b b b b b b bb b b b b b bb b b b b b b– – – – – – –50 50 50 50 50 50 50
340 x 300 x 198 340 x 300 x 198 340 x 300 x 198 340 x 300 x 198 340 x 300 x 198 348 x 440 x 325 348 x 440 x 325410 x 300 x 198 410 x 300 x 198 410 x 300 x 198 410 x 300 x 198 410 x 300 x 198 463 x 440 x 325 463 x 440 x 32514 14 14 14 14 35 3518 18 18 18 18 45 45
??? x ??? x ??? ??? x ??? x ??? ??? x ??? x ??? ??? x ??? x ??? ??? x ??? x ??? ??? x ??? x ??? ??? x ??? x ???
Switch-disconnector selection (cont.)
Interpact INV630b to 2500 (cont.)
Functions andcharacteristics
Schneider Electric40
Complete source-changeoverassembly selectionInterpact INS250-100 to 630 (cont.)
Functions andcharacteristics
Interpact INS switch-disconnectorsNumber of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3Conventional thermal current (A) Ith at 60 °CConventional thermal current Ithe at 60 °Cin enclosureRated insulation level (V) Ui AC 50/60 HzImpulse-withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz
DCRated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical AC 50/60 Hz220-240 V380-415 V440-480 V (1)
500-525 V660-690 V
Electrical DC125 V (2P in series)250 V (4P in series)
Rated duties uninterrupted dutyintermittent duty
Short-circuit making capacity Icm min. (switch-disconnector alone)(kA peak) max. (with upstream protection circuit breaker)
Short-time withstand current Icw (A rms) 1 s3 s20 s30 s
Suitability for isolationDurability (category A) (O - C-O cycles) Mechanical
Electrique AC 50/60 Hz440 V500 V690 V
Electrique DC250 V
Positive contact indicationVisible breakEmergency-off switch disconnectorDegree of pollution
Upstream protectionSee the “Additional characteristics” section, 308E5015
Complete assembly ????
Complete assembly ????
E00
000
Nouvelle photo à venir
E00
000
Nouvelle photo à venir
(1) Suitable for 480 V NEMA.
Schneider Electric 41
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS6303, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4
100 160 200 250 320 400 500 630100 160 200 250 320 400 500 630
750 750 750 750 750 750 750 7508 8 8 8 8 8 8 8690 690 690 690 690 690 690 690250 250 250 250 250 250 250 250750 750 750 750 750 750 750 750
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630100 100 160 160 200 200 250 250 320 320 400 400 500 500 630 630
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A/B100 100 160 160 200 200 250 250 320 320 400 400 500 500 550 550/630100 100 160 160 200 200 250 250 320 320 400 400 500 500 550 550/630b b b b b b b bclass 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %30 30 30 30 50 50 50 50330 330 330 330 330 330 330 3308500 8500 8500 8500 20000 20000 20000 200004900 4900 4900 4900 11500 11500 11500 115002200 2200 2200 2200 4900 4900 4900 49001800 1800 1800 1800 4000 4000 4000 4000b b b b b b b b15000 15000 15000 15000 10000 10000 10000 10000
AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 15001500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
DC22A DC23A DC22A DC23A DC22A DC23A DC22A DC23A DC23A/B DC23A/B DC23A/B DC23A/B1500 1500 1500 1500 1500 1500 1500 1500 1000/– 1000/– 1000/– 1000/200b b b b b b b b– – – – – – – –– – – – – – – –III III III III III III III III
– – – – – – – –
Complete source-changeoverassembly selection (cont.)
Interpact INS250-100 to 630 (cont.)
Functions andcharacteristics
Schneider Electric42
Complete source-changeoverassembly selection (cont.)
Interpact INS250-100 to 630 (cont.)
Functions andcharacteristics
Interpact INS switch-disconnectorsInstallation and connection
Fixed, front connectionFixed, rear connectionOn symmetrical railsOn a backplate
ConnectionBy cables to bare cable connectorsBy cables with lugs directly to terminals
to spreadersto vertical-connection adapters via cable-lug adapters
Flat-facing bars directly to terminalsto spreaders
Edgewise bars to vertical-connection adapters
Indication and measurement auxiliariesAuxiliary contactsVoltage-presence indicatorCurrent-transformer moduleAmmeter module
Control, locking and interlockingControl direct front rotary handle
extended front rotary handledirect lateral rotary handleextended lateral rotary handle
Locking by keylockby padlocks
Complete source-changeover assemblyOperating torque (Nm) (typical value for 3/4 poles with front handle)
Installation and connection accessoriesBare cable connectorsRear connectorsTerminal extensionsSpreadersOne-piece spreaderTerminal shroudsTerminal shieldsInterphase-barrierFront panel escutcheonsCoupling accessoriesTightening torque for electrical connections (Nm)
Dimensions and weightsOverall dimensions H x W x D (mm) 3 poles
4 polesApproximate weight (kg) 3 poles
4 poles
Schneider Electric 43
Complete source-changeoverassembly selection (cont.)
Interpact INS250-100 to 630 (cont.)
Functions andcharacteristics
INS250-100 INS250-160 INS250-200 INS250 INS320 NS400 INS500 INS630
b b b b b b b bb b b b b b b b– – – – – – – –b b b b b b b b
b b b b b b b bb b b b b b b bb b b b b b b b– – – – – – – –b b b b b b b bb b b b b b b b– – – – b b b b
b b b b b b b bb b b b b b b bb b b b b b b bb b b b b b b b
b b b b b b b bb b b b b b b b– – – – – – – –– – – – – – – –b b b b b b b bb b b b b b b bb b b b b b b b5 < C < 6.2 5 < C < 6.2 5 < C < 6.2 5 < C < 6.2 13.5 < C < 16.5 13.5 < C < 16.5 13.5 < C < 16.5 13.5 < C < 16.5
b b b b b b b bb b b b b b b b– – – – – – – –b b b b b b b b– – – – – – – –– – – – – – – –b b b b b b b bb b b b b b b b– – – – – – – –b b b b b b b b15 15 15 15 50 50 50 50
140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 185 x 205 x 120 185 x 205 x 120 185 x 205 x 120 185 x 205 x 120140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 140 x 136 x 86 185 x 205 x 120 185 x 205 x 120 185 x 205 x 120 185 x 205 x 1206.4 6.4 6.4 6.4 13.5 13.5 13.5 13.56.4 6.4 6.4 6.4 ??? ??? ??? 13.5
Schneider Electric44
Installation
Heavy-duty individualenclosure (sheet metal orplastic)
E90
491
Pragma modular enclosuresb the enclosures in the Pragma range are:v made of self-extinguishing insulating materialv supplied with all accessories (terminal blocks,blanking plates, etc.)v rated class 2.
Functions andcharacteristics
Interpact INS and INV switch-disconnectors offer a number of rational installationsolutions to optimise available space inside enclosures. They may be installed inindividual enclosures or as incomers in power distribution or control panels.b Interpact INS40 to 160 switch-disconnectors have a standard 45 mm high frontand may be clipped onto a Multifix or symmetrical rail. They may be installed in allMulti 9 modular enclosures, including Pragma, Prisma, etc.b Interpact INS250 to 630 and INV100 to 630 switch-disconnectors may beinstalled on mounting plates or rails. Installation as incomers in Prisma powerdistribution cubicles is very flexible:v the mounting plates are the same as those used for Compact NS circuit breakersand are identical for direct and extended handlesv installation in 300 mm ducts is possible for ratings up to 630 A.
Prisma metal cubicles and enclosuresb the metal cubicles and enclosures in the Prismarange are highly adaptable to the type of installation:v basic cubicle or enclosurev multifix railv modular front platesv distribution accessoriesv ducts for running cables or installing terminalsv plain or transparent doors.
E54
453
E54
454
Interpact INS40 on asymmetrical rail
Installation in a 300 mmduct
Local isolation enclosure
E56
047_
A
Power distribution incomer in a Prisma cubicle
Individual enclosuresb each individual enclosure includes:v a door with a cut-outv a mounting platev accessories required for extended front or lateralrotary handlev removable plates (without holes) for cable entry.The Interpact INS switch-disconnector must be orderseparately.
0527
60_A
Power distribution incomer in a Prisma GK cubicle
0566
99_A
Schneider Electric 45
.1 .2 .4
N
.1
N
E54
455
E38
888
Interpact INS40 to INS80Interpact INS40 to INS80 switch-disconnectors areequipped as standard with connectors for bare copperor aluminium cables.
Distribution connectorThis connector screws directly into the switch-disconnector terminals for connection of three cablesof the following types:b 1 to 10 mm2 flexible cables (1)
b 1.5 to 16 mm2 rigid cables.
Interpact INS100 to INS160
Connection of bars or cables with lugsInterpact INS100 to INS160 switch-disconnectors areequipped as standard with terminals comprising nutswith M6 screws for direct connection of insulated barsor cables with lugs.
LugsThe special lugs for copper cables may be used forcables with cross-sectional areas up to 95 mm2.Secure the lugs by hexagonal crimping or punching.Lugs are supplied with interphase-barrier and arecompatible with the terminal shields.
Connection of bare cables (Cu or Al)b 1-cable connectors for Interpact INS100/125/160 snapdirectly onto the terminals, for cables 1.5 to 95 mm2 (1).b distribution connectors are designed for four cableswith cross-section areas 1.5 to 25 mm2 rigid or 1.5 to16 mm2 flexible (1). They screw directly to theterminals. The interphase-barrier supplied with thedistribution connectors may be replaced by longterminal shields.
E54
463
E38
889
Lug for copper cable
E32
423 E
3242
4E54
457
E30
707
E54
456
ConnectionInterpact INS40 to 160
1-cable Distributionconnector connector
N
.1 .2.4 E
3943
2
Functions andcharacteristics
E92
189
Terminal shields
InterpactINS40 to 160
Interphasebarrier
Sealable long terminalshield
Terminal shroud
Auxiliary contact
Emergency-offextended rotarycontrol
Extended lateralcontrol
Extended rotarycontrol
1-cableconnector
Distributionconnector
Lateral controlon functionalenclosure
ON I
OFF 0
ON I
OFF 0
Lateral rotarycontrol
Emergency-off
(1) Connection of 1.5 to 4 mm2 flexible cables requirescrimped or auto-crimping ferrules.
Schneider Electric46
Electrical and mechanicalaccessoriesInterpact INS250Interpact INV100 to 250
Functions andcharacteristics
E72
527 Sealable long terminal shield
for spreaders
Lateral rotarycontrol
Interphasebarrier
Current transformermodule
One-piece spreader
Ammeter module
Sealable shortterminal shield
Locking bykeylock
Auxiliarycontacts
Rear connections
Extended lateralrotary control
Emergency-offextended rotary control
Direct lateralrotary control
Emergency-off
Emergency-offextendedrotary control
Visible break (INV)
Coupling accessory
Escutcheon
Spreader
InterpactINS250
Handlesupport
ION
OFF
O
ON I
OFF 0
ION
OOFF
ION
OOFF
ION
OOFF
ION
OOFF
ION
OOFF
ION
O
ION
OOFF
A16
12
8
4
160/5
0
ON I
OFF 0
ION
OFF
O
E72
527
Schneider Electric 47
Electrical and mechanicalaccessories (cont.)
Interpact INS320 to 630Interpact INV320 to 630
Functions andcharacteristics
E92
190
A16
12
8
4
160/5
0
Sealable shortterminal shield
Bare cableconnectors
Current transformermodule
Ammeter module
Auxiliarycontacts
Lockingby keylock
Extended rotarycontrol
Right-angleterminalextension
Edgewiseteminalextension
Coupling accessory
Escutcheon
Emergency-off
InterpactINS400 to 630
Visible break (INV)
Sealable longterminal shield
Interphasebarrier
Rear connections
Spreader
Emergency-offextended rotarycontrol
Schneider Electric48
ConnectionInterpact INS250 to 630Interpact INV100 to 630
Front connection of bars or cableswith lugsInterpact INS250 to INS630 and INV100 to INV630switch-disconnectors are equipped as standard withterminals receiving snap-in nuts and screws(M8 for INS/INV up to 250, M10 from 320 upwards) fordirect connection of insulated bars or cables with lugs.Terminal extensions (right-angle, edgewise,spreaders) are available to solve all connectionproblems. For Interpact INS/INV630 switch-disconnectors, connection most often requires the52.5 or 70 mm pitch spreaders.
LugsLugs are different for copper and aluminium cables.They are supplied with interphase-barrier and arecompatible with the long terminal shields.b the small lugs for copper cables may be used forcables with the following cross-sectional areas:v 120, 150 or 185 mm2 (INS/INV up to 250)v 240 or 300 mm2 (INS/INV up to 630).Secure the lugs by hexagonal crimping or punching.b the small lugs for aluminium cables may be used forcables with the following cross-sectional areas:v 150 or 185 mm2 (INS/INV up to 250)v 240 or 300 mm2 (INS/INV up to 630).Secure the lugs by hexagonal crimping.
SpreadersSpreaders increase the pitch of the terminals.They are not compatible with terminal shields.The one-piece spreader increases the pitch tocorrespond to that of the upstream device andprovides protection against direct contact(see 308E2060).
ø5...8
ø5...8
E54
459
E54
460
Functions andcharacteristics
ø5...8
E54
461
E54
456
E54
462
ø5...8
Lug for aluminium cables
E30
907
Spreaders
E18
599
One-piece spreader
E54
464
Lug for copper cables
E54
463
Edgewise terminalextensions for INS/INV320to 630
E21
276
Straight terminal extensionsfor INS/INV250
E18
601
Right-angle terminalextensions
E18
600
Schneider Electric 49
Front connection of bare cablesBare-cable connectors for Interpact INS/INV switch-disconnectors may be used for both copper andaluminium cables.
1-cable connectors for Interpact INS250and INV100 to 250The connectors snap directly on to the deviceterminals or clip onto right-angle and straight terminalextensions as well as spreaders.
1-cable and 2-cable connectors for InterpactINS/INV320 to 630The connectors are screwed to device terminals orright-angle terminal extensions.
Distribution connectors for Interpact INS250and INV100 to 250These connectors are screwed directly to deviceterminals. Interphase-barrier are supplied withdistribution connectors, but may be replaced by longterminal shields. Each connector can receive sixcables with cross-sectional areas ranging from 1.5 to35 mm2 each.
Polybloc distribution block for Interpact INS250and INV100 to 250The Polybloc connects directly to the device terminalsand is used to connect up to six or nine flexible or rigidcables with cross-sectional areas not exceeding10 mm2, to each pole. Connection is made to springterminals without screws.
Rear connectionRear connections for bars or cables with lugs areavailable in two lengths. Bars may be positioned flat,on edge or at 45° angles depending on how the rearconnections are positioned.The rear connections are simply fitted to the deviceconnection terminals. All combinations of rearconnection lengths and positions are possible on agiven switch-disconnector. The switch-disconnector ismounted on a backplate.For the connection of cables without lugs, the 1-cableconnectors for Interpact INS250 and INV100 to 250may be simply clipped onto the rear connections.
E54
465
E54
466
E54
456
E54
471
E54
472
E54
470
E54
469
E54
468
E54
457
1-cable connector forINS250 and INV100-250
1-cable connectorfor INS/INV320 to 630
2-cable connectorfor INS/INV320 to 630
Distribution connector forINS250 and INV100 to 250
Polybloc distribution block forINS250 and INV100 to 250
Four positions
Two lengths
E94
208
E54
473
ø5...8
ø5...8
E54
467
Connection (cont.)
Interpact INS250 to 630Interpact INV100 to 630 (cont.)
Functions andcharacteristics
Schneider Electric50
Electrical and mechanicalaccessoriesInterpact INS630b to 2500Interpact INV630b to 2500
Functions andcharacteristics
E92
191
Terminal shield
Extended rotarycontrol
Spreader
Interphase-barrier
Auxiliary contacts
Emergency-off (y 1600)
Escutcheon
Vertical connectionadapter
OFF O
tripped
reset
OFF 0
ON I
tripped
reset ON I
OFF 0
OFF OOFF OOFF O
OFF OOFF OFF OFF O
Cable lug adapter
Base for terminal shield
Visible break (INV)
Lockingby keylock
Emergency-offextendedrotary control
InterpactINS800 to 1600
Schneider Electric 51
Direct connectionBarsInterpact switch-disconnectors are equipped withterminals and captive screws for direct connectionof bars.
Connection with accessoriesSpreadersSpreaders increase the pole pitch of a switch-disconnector for greater clearance between the bars.They are not compatible with terminal shields.
ConnectionInterpact INS630b to 2500Interpact INV630b to 2500
Functions andcharacteristics
Vertical connection adaptersFor connection of edgewise bars.
Adapters for cables with crimped lugsCable-lug adapters are used in conjunction withvertical connection adapters. They may be usedto connect one to four cables (y 300 mm2)with crimped lugs.To ensure adequate mechanical strength, the cable-lug adapters must be secured together by spacers.
E88
666
E88
668
E88
663
E88
887
E88
865
E88
867
E88
868
E88
869
E88
661
Schneider Electric52
Distribloc is a four-pole distribution block offering:b 13 outgoing terminals per phase (12 spring terminals and 1 tunnel terminal)b 1 incoming tunnel terminal for 35 mm2 flexible cable (50 mm2 rigid).Distribloc exists in two versions:v Distribloc 125, for switch-disconnectors rated up to 125 Av Distribloc 160, supplied with prefabricated connections, for direct connection toswitch-disconnectors INS100 to INS160.Distribloc is supplied with a modular cover that fulfils a number of functions:b circuit identification: a protected label identifies the various circuitsb aesthetics: the cover has the same design as the associated Interpact INSswitch-disconnectorb user information: all required information is indicated on the cover.Distribloc can be installed:b on a symmetrical rail or a backplateb to the left, the right or under the switch-disconnector, depending on the desiredlayout of the switchboard. Installation to the left is particularly useful when the INSswitch-disconnector is equipped with a lateral handle.
Electrical characteristicsb rated short-time withstand current (Icw) = 4.5 kA rms / 1 second.b rated peak withstand current (Ipk) = 20 kA peak.b rated insulation voltage (Ui) = 690 V AC.
Multi-stage distribution block 125 A (40°)b 4 x 10 holes (5 x 10 mm2, 4 x 16 mm2, 1 x 35 mm2)dimensions: width 88 mm, height 92 mm, depth 51 mm,distance between fixing centres 68 mm.b 4 x 17 holes (8 x 10 mm2, 8 x 16 mm2, 1 x 35 mm2)dimensions: width 125 mm, height 92 mm, depth 51 mm,distance between fixing centres 105 mm.v supplied with insulating coverv easy mounting on Multifix or symmetrical railv mounting on slotted plate using screws.
Electrical characteristicsb rated short-time withstand current (Icw) = 3.5 kA rms / 1 secondb rated peak withstand current (Ipk) = 20 kA peakb rated insulation voltage (Ui) = 500 V AC.
E54
475
Connection accessoriesDistribution blocks
E54
477
0411
53_A
Distribloc
Distribloc 125 A
0539
97_A
Circuitidentification
Modularcover
Clips ontosymmetricalrail
Mountingon backplate
2 outgoingspring terminals1 to 10 flexible1 to 16 rigid
1 incomingtunnel terminal 356 to 35 flexible10 to 50 rigid
1 outgoingtunnel terminal 254 to 16 flexible4 to 25 rigid
3 outgoingspring terminals1 to 6 flexible or rigid
7 outgoingspring terminals1 to 4 flexibleor rigid
N
N
N
Functions andcharacteristics
Schneider Electric 53
Connection accessories (cont.)
One-piece spreaderFunctions andcharacteristics
Connection of large cables may require an increase inthe distance between the switch-disconnector terminals.The one-piece spreader is an accessory that can also befitted on Compact NS circuit breakers. It offers thefollowing features:b increases the pitch of the switch-disconnectorterminals to correspond to that of the upstream deviceb compatible with all the connection and insulationaccessories available for the upstream device(connectors, terminal extensions, etc.)b enhances insulation between phases in comparisonwith standard spreaders.
INS250 INS320 to 630INV100 to 250 INV320 to 630
Pitch without 35 45spreaders (mm)Pitch with 45 52.5 or 70standardspreaders (mm)Pitch with 45 –one-piecespreader (mm)
MountingWhen equipped with a one-piece spreader, INS and INVswitch-disconnectors may be installed either at the backof a switchboard or on the front panel with a frontalignment base.b devices with different frame sizes can thus bealigned in the switchboardb the same mounting plate can be used for all devices(including Compact NS circuit breakers).
Mounting at the back of aswitchboard
Mounting on the front panelwith a front alignment base
E54
548
E54
541
E54
200
Connection and insulationaccessories are identical tothose for Compact NS
One-piece spreader
0563
84_A
ø5...8
Schneider Electric54
Connection accessories (cont.)
Insulation of live parts
E54
476
E54
542
Terminal shields for INS and INV switch-disconnectorsLead-sealable insulation accessories used to protectagainst direct contact with power circuits.b degree of protection: IP40.5b supplied with lead-sealing accessories.
Interphase-barrier for INS/INVb safety accessories providing maximum insulationbetween the phases of the power connectionb easy installation by snapping into the caseb may be combined with all other connectionaccessories, except the terminal shields and terminalshrouds.
Terminal shrouds for INS40 to INS160These insulation accessories are used for protectionagainst direct contact with live connection screws. It isalso possible to attach an insulating plate (notsupplied) to the shrouds to avoid any contact with thepower conductors.
Spare viewport for Interpact INV switch-disconnectorsViewports are darkened by the electrical arc. A newviewport may be installed to maintain the visible-breakfunction.
Terminal shields for InterpactINS and INV
Interphase-barrier forInterpact INS and INV
Spare viewport forInterpact INV
E51
003
Terminal shrouds forInterpact INS40 to 160(with insulating plate to avoidcontact with the conductors)
E54
543
N
.1 .2.4
55 88ØØ
N
.1 .2.4
N
.1 .2.4
55 88ØØ
N
.1 .2.4
N
.1 .2.4
N
.1 .2.4
0560
63_A
Functions andcharacteristics
Schneider Electric 55
Auxiliary contact for InterpactINS and INV
0443
14_A
Auxiliary contacts
Interpact INS and INVOne or four common-point changeover contacts can be used to remote switch-disconnector status information for indications, electrical interlocking, relays, etc.
FunctionsEach contact may be used for the following functions:b OF (ON/OFF): indicates the position of the switch-disconnector polesb CAM (early-make or early-break function): indicates the position of the handle.Used in particular for:v CAO early-break switch (auxiliary contacts open before the main contacts), used,for example, to automatically open a circuit breaker or a contactor before openingthe Interpact INSv CAF early-make switch (auxiliary contacts close before the main contacts).b switching of very small loads. A “low-level” version of the auxiliary contacts existsfor switching very small loads (for example, to control a PLC or electronic circuits).
StandardsThe auxiliary contacts comply with international standard IEC 60947-5.1.
InstallationThey simply snap in under the auxiliaries cover (supplied as standard) of theswitch-disconnector.
InsulationSealable auxiliary shield to protect against direct contact with power circuits.
Electrical characteristics of auxiliary contacts for Interpact INS and INVStandard Low level
Rated thermal current (A) 6 5Minimum load 10 mA at 24 V 1 mA at 4 V
AC DC AC DCUtilisation category AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14(IEC 60947-5-1)Operational current (A) 24 V 6 6 2.5 1 5 3 5 1
48 V 6 6 2.5 0.2 5 3 2.5 0.2110 V 6 5 0.8 0.05 5 2.5 0.8 0.05220/240 V 6 4 5 2250 V 0.3 0.03 0.3 0.03380/415 V 6 3 5 1.5440 V 6 3 5 1.5660/690 V 6 0.1
Interpact INS40 to 2500, INV100 to 2500Possible combinations
Interpact OF block CAM block (CAO or CAF)INS40 to 160 2 or 2INS250 2 or 2INS400/630 3 and 1INS630b/1600 3 and 1INS2000/2500 3 and 1
Functions andcharacteristics
N
55 8ØØ
CAOor CAFor OF
CAOor CAFor OF
E54
504
Interpact INS40 to 160
E54
500
Interpact INS/INV320 to 630
OF1OF2
OF3CAO or CAF
E88
715
OF1OF2
OF3CAO or CAF
Interpact INS/INV800 to 1600
ø5...8
CAOor CAFor OF
Interpact INS250and INV100 to 250
E54
499
OF1OF2
OF3CAO or CAF
Interpact INS/INV2000 to 2500
E88
929
Schneider Electric56
Current measurementsFunctions andcharacteristics
Ammeter moduleFor Interpact INS250 to 630 and INV100 to 630.
FunctionMeasures and displays the current of each phase (phase selection by a three-position switch on the front) on a dial-type ammeter.
Installationb connects directly to the downstream terminals of the switch-disconnector(except on a INS250 with a direct handle)b the ammeter clips into the module housing in any of four 90° positions, i.e. theswitch-disconnector may be installed horizontally or verticallyb degree of protection: IP40 IK 07b class II insulation between front and power circuits.
Electrical characteristicsAccuracy class 4.5.
Current-transformer moduleFor Interpact INS250 to 630 and INV100 to 630.
FunctionMeasure phase currents for display by an ammeter or a Digipact IM or PM module(not supplied, see the corresponding catalogue).
Installationb connects directly to the downstream terminals of the switch-disconnectorb degree of protection: IP40.3b class II insulation between front and power circuitsb connection via six built-in terminals for cables with a cross-sectional areaof 2.5 mm2.
Electrical characteristicsb current transformer with 5 A secondary windingb accuracy class 3 for the following values of consumed output power:v 100 A rating - 1.6 VAv 150 A rating - 3 VAv 250 A rating - 5 VAv 400/630 A rating - 8 VA.
Interpact INV250 with ammeter module
0573
55_A
Schneider Electric 57
INS40-160 INS250 INS320-630 INS630b-1600 INS2000-2500
INV100-250 INV320-630 INV630b-1600 INV2000-2500
Standard rotary handle
Front direct Standard Standard Standard Standard Standard
Lateral direct Standard With conversion No No No
Front extended Optional Optional Optional Optional Optional
Lateral extended Optional (2) Optional No No No
Red and yellow rotary handle for emergency-off switch-disconnectors
Front direct Standard Standard Standard Standard No (3)
Lateral direct Standard With conversion No No No
Front extended Optional Optional Optional Optional No (3)
Lateral extended Optional (1) (2) Optional (1) No No No
(1) The basic switch-disconnector must be the emergency-off (red and yellow) version(2) Two models for universal enclosures and for Prisma G enclosures(3) Emergency-off versions not available for INS/INV2000-2500.
ø5...8
or
E54
501
Interpact INS630 with front extended rotary handle
Interpact INS250 with lateral extended rotary handle
0521
71_A
0594
95_A
0566
56_A
Interpact INS and INVDirect rotary handleb degree of protection IP40.5b the switch-disconnector may be locked in the OFFposition by one to three padlocks, hasp diameter 5 to8 mm (not supplied).
Modelsb standard with black handleb emergency-off version with red handle and yellowfront for machine-tool control.
Extended rotary handleMakes it possible to operate the switch-disconnector,installed inside a switchboard, from the front or side ofthe switchboard. The extended rotary handle may beinstalled on the front or the side of the switch-disconnector. Degree of protection IP55.7.
Operationb suitability for isolation is maintainedb door opening is prevented when the switch-disconnector is in ON position (for front handle only)b the switch-disconnector may be locked in the OFFposition by one to three padlocks, hasp diameter 5 to8 mm (not supplied). Locking prevents opening of theswitchboard door (for front handle only).
Modelsb standard: with black handleb emergency-off: with red handle and yellow front formachine-tool control.
InstallationThe extended rotary handle is made up of:b an assembly that replaces the direct rotary handleon the Interpact switch-disconnector (secured byscrews)b an assembly (handle and front plate) to be mountedon the door or the side of the switchboard. Thisassembly is always secured in the same position,whether the switch-disconnector is installed verticallyor horizontallyb an adjustable extension shaft (see pages308E4040).
Rotary handle
Direct rotary handleon INS40 to 160
Direct rotary handle onINS250 and INV100 to 250
Direct rotary handleon INS/INV320 to 630
N
.1 .2.4
or
E54
502
E54
503
Interpact INS160 with lateral direct rotary handle
Interpact INS250 emergency-off version with front directrotary handle
0566
52_A
Functions andcharacteristics
E88
716
Direct rotary handleon INS/INV800 to 1600
Schneider Electric58
Coupling accessoriesFunctions andcharacteristics
Coupling accessoryThis accessory simplifies connection of bars or cables with lugs when coupling twoCompact NS100 to 630 circuit breakers or two Interpact INS/INV100 to 630 switch-disconnectors of the same size.Pitch between outgoing terminals:b Interpact INS250 and INV100 to 250: 35 mmb Interpact INS/INV320 to 630: 52.5 mmb Compact NS100 to 250: 35 mmb Compact NS400 to 630: 52.5 mm.
Connection and insulation accessoriesThe coupling accessory may be fitted with the same connection and insulationaccessories as the coupled circuit breakers or switch-disconnectors.
E88
932
Possible combinations Downstream couplingpossible pitch of outgoing
terminals (mm)
Manual source-changeoverINS250 (100 to 250 A) with rotary handle b 35NS100/250 with rotary handle b 35NS100/250 on mounting plate with toggle b 35INS400/630 (320 to 630 A) with rotary handle b 52.5NS400/630 with rotary handle b 52.5NS400/630 on mounting plate with rotary handle b 52.5
Complete source-changeover assemblyINS250 (100 to 250 A) complete assembly b 35INS400/630 (320 to 630 A) complete assembly b 52.5
Remote-operated source changeoverNS100/250 b 35NS400/630 b 52.5
Schneider Electric 59
Padlocked Interpact INS250 switch-disconnector
Padlockingb INS40 to 2500 Ab INV100 to 2500 Ab complete source-changeover assembly from 100 to 630 A.
Switch-disconnectors may be locked in the OFF position:The handle is designed for locking by up to three padlocks (not supplied).Locking in the OFF position guarantees isolation as defined by the IEC 60947-3standard. The handle may also be lead-sealed in the OFF position.
Disabling device closingFunctions andcharacteristics
0566
49_A
INS/INV switch disconnectors
INS40 to 80 INS100 to 160 INS250-100 to 250 INS320 to 630 INS630b to 1600 INS2000 to 2500INV100 to 250 INV320 to 630 INV630b to 1600 INV2000 to 2500
OFF ON OFF ON OFF ON OFF ON OFF ON OFF ONLocking by padlocks b v b v b v b v b v b vLocking by keylock – – – – b v b v b v b vDoor locking (2) – b – b – b – b – b – bDoor lock defeat (2) – b (1) – b (1) – b (1) – b (1) – b (1) – b (1)
Door locking, b – b – b – b – b – b –device padlocked (2)
Lead-sealable handle b v b v b v b v b v b v
Complete source changeover assembly
INS250-100 to 250 INS320 to 630Normal ON OFF Replacement ON Normal ON OFF Replacement ON
Locking by padlocks v b v v b vLocking by keylock v b v v b vDoor locking (2) b – b b – bDoor lock defeat (2) b (1) – b (1) b (1) – b (1)
Door locking, – b – – b –device padlocked (2)
Lead-sealable handle v b v v b vv by simple modification of the standard rotary handle.b (1) using a special tool.(2) with extended rotary control.
Keylockingb INS250-100 to 2500 Ab INV100 to 2500 Ab complete source-changeover assembly from 100 to 630 A.INS250 to 630, INV100 to 630 or INV1000 to 2500 switch-disconnectors may belocked in the OFF position using a keylock (optional) that may be installed in thehole prepared for that purpose on the front of the devices.The key may not be removed when the switch-disconnector is in the ON position.Keylocks can also be fitted on switch-disconnectors equipped with extended rotaryhandles.
N
.1 .2.4
55 88ØØ
E32
426
E89
551
ø5...8
E54
544
E89
552
Schneider Electric60
bb
b
bb
bbb
bb
bb
bb
bb
bb
bb
b
bb
bb
bb
bb
b bb
bb
b
bb
bb
b
bbb
bb
b
b
bb
b
bbb
bb
bb
bb
bb
bb
b
b
bb
bb
bb
bb
bb
b
Switching to a replacement source
Possible positions
Normal 1 0 0Replacement 0 1 0
Source INS40...160 INS250 INS320...630 INS630b…2500changeover INV100...250 INV320...630
By keylock b b bMechanical b b bComplete assembly b b
A source-changeover system is made up oftwo switch-disconnectors or circuit breakersthat are mechanically interlocked.The mechanism prevents the simultaneousconnection (even transient) of both sources.Switching from one source to the other canbe achieved by:b a keylock-type interlocking systemb a mechanical interlocking systemb a complete source-changeover assembly.
E55
460
Functions andcharacteristics
ø5...8
ø5...8
ø5...8
ø5...8
ON
OFF
OFFO
ION
O
I
ø5...8
ø5...8
E88
930
E89
553
Interlocking of two devices using keylocks and a captive keyInterlocking is based on two identical keylocks with a single key and a keylockadapter (different for each device). This solution enables interlocking between twodevices that are physically distant or that have very different characteristics.
Interlocking of two devices with rotary handlesThe direct or extended rotary handles are padlocked with the devices in the OFFposition. The mechanism prevents simultaneous closing of the devices, but allowsthem to be opened.
Possible combinations of “Normal” and “Replacement” source switch-disconnectors
rating “Normal” N “Replacement” R
Interpact INS (1)
40 INS40 INS4063 INS63 INS6380 INS80 INS80100 INS100 INS100125 INS125 INS125160 INS160 INS160
Interpact INS/INV (2)
100 INS250-100/INV100 INS250-100/INV100160 INS250-160/INV160 INS250-160/INV160200 INS250-200/INV200 INS250-200/INV200250 INS250-250/INV250 INS250-250/INV250320 INS320/INV320 INS320/INV320400 INS400/INV400 INS400/INV400500 INS500/INV500 INS500/INV500630 INS630/INV630 INS630/INV630
(1) With extended rotary handlesonly.(2) Possible with INV, but visible-break function is significantlyimpaired.
Complete source-changeover assembly for two switch-disconnectorsThese assemblies provide an easy way to implement source changeover functions with:b a single 3-position rotary handle that controls the two switch-disconnectors(Normal source ON, OFF, Replacement source ON)b a smaller size, taking up less room in the switchboard.
A complete source changeover assembly can be ordered with a single cataloguenumber.Possible combinations of “Normal” and “Replacement” source switch-disconnectors
ratings “Normal” N “Replacement” R100 INS250 -100 INS250 -100160 INS250 -160 INS250 -160200 INS200 -200 INS250 -200250 INS250 -250 INS250 -250320 INS320 INS320400 INS400 INS400500 INS500 INS500630 INS630 INS630
Schneider Electric 61
Accessories
Front-panel escutcheonsEscutcheons for switch-disconnectors and ammeter modulesMounted on switchboard panel from the front using four screws.
Identification labelsInterpact INS40 to 160 switch-disconnectors may receive Telemecaniqueprefabricated labels, catalogue number AB1- (eight characters). Interpact INS250to 630 and INV100 to 630 switch-disconnectors are supplied as standard with aclip-on label for handwritten indications.These devices also come with a nameplate into which a label can be inserted.
Individual enclosuresInterpact INS and INV switch-disconnectors equipped with a front handle may beinstalled in individual enclosures.All fixed, front connections are possible, except right-angle and edgewise terminalextensions. Spreaders may be installed in the enclosures intended for InterpactINS250 to 630 and INV100 to 630 switch-disconnectors.
Heavy-duty metal individual enclosure for Interpact INS (IP557)b metal enclosureb door with keylock and cut-out for switch-disconnector rotary handleb extended rotary front handleb device mounting plateb removable plate (without holes) for cable entry through bottom.
Heavy-duty insulating individual enclosure for Interpact INS and INV (IP557)b metal enclosureb transparent cover, screwed, lead sealable, with cut-out for switch-disconnectorrotary handleb extended rotary front handleb device mounting plateb removable plates (without holes) for cable entry through bottom and/or top.
Dimensions
Metal enclosures W x H x DInterpact INS40 to 160 350 x 350 x 250Interpact INS250 350 x 450 x 250Interpact INV100 to 250Interpact INS320 to 630 350 x 650 x 250Interpact INV320 to 630
Insulating enclosures W x H x DInterpact INS40 to 160 270 x 180 x 185Interpact INS250 270 x 360 x 235Interpact INV100 to 250Interpact INS320 to 630 360 x 720 x 235Interpact INV320 to 630
E55
275
E55
276
Escutcheon for switch-disconnectors
Escutcheon for ammetermodules
D E P. P O M PPP.ED
pushto
trip
O
E18
595
ø5...8
A160
120
80
40
160/5A
0
0527
60_A
Functions andcharacteristics
Schneider Electric62
Schneider Electric 63
Presentation 2Functions and characteristics 17
Operating principle 64Possible installation positions and mountingtechniques 66Implementation 67Interpact INS40 to 80 68Interpact INS100 to 160 69Interpact INS250-100 to 250, Interpact INV100 to 250 70Complete source-changeover assemblyINS250-100 to 250Interpact INS320 to 630, Interpact INV320 to 630 74Complete source-changeover assemblyINS320 to 630Connection 78INS630b to 1600 and INV630b to 1600 78INS2000 to 2500 and INV2000 to 2500 82
Use at high temperatures 84
Dimensions and connection 85Additional characteristics 103Catalogue numbers 113
Installation recommendations
Schneider Electric64
Installationrecommendations
INS250-100 to 250INV100 to 250
E94
150
CAOF
OFF ON OFF
OFF ON OFF
OFF ON OFF
CAM
OF
OFF ON OFF
OFF ON OFF
OFF ON OFF
OFF ON OFF
Operating principleE
9415
1
INS320 to 630INV320 to 630
Schneider Electric 65
Installationrecommendations
Operating principle (cont.)
OFF ON OFFCAM
OF
OFF ON OFF
OFF ON OFF
OFF ON OFF
OFFON ON
E90
497
INS630b to 2500INV630b to 2500
Schneider Electric66
Installationrecommendations
Possible installation positions
Possible mountingINS40 to 160
Symmetrical rail Plain mounting plate Slotted mounting plate
INS250-100 to 630 - INV100 to 630
Rails Plain mounting plate Slotted mounting plate
INS/INV800 to 2500
Rails Plain mounting plate
ø5...8
E55
416
Possible installation positionsand mounting techniques
ø5...8
ø5...8
ø5...8
E55
417
E55
418
ø5...8
ø5...8
E55
419
E55
420
ø5...8
E55
422
ø5...8
E55
423
E55
416
N
.1 .2.4
55 88Ø
N
.1 .2.4
55 88Ø
N
.1 .2.4
55 88ØE
5559
7
E55
421
E55
596
E88
862
E88
863
Schneider Electric 67
Installationrecommendations
ø5...8
to the busbars
outgoing cables
E55
424
E55
425
Implementation
Reverse supplyInterpact switch-disconnectors may be supplied indifferently via the top or bottomterminals, without any reduction in performance.
Neutral pole positionOn Merlin Gerin switch-disconnectors, the neutral pole is traditionally located onthe left-hand side. On the INS and INV ranges, the four poles are identical and theneutral pole can therefore be located on the right-hand side simply by adding anappropriate label.
Conductor materials and electrodynamic forcesInterpact switch-disconnectors may be connected using either bare copper, tinnedcopper or tinned aluminium conductors (flexible or rigid bars, cables).In the event of a short-circuit, thermal and electrodynamic forces are exerted on theconductors. The conductors must therefore be adequately sized and suitablysupported.Note that the terminals of electrical devices (switch-disconnectors, contactors,circuit breakers, etc.) should not be considered to contribute to the support of theconductors.
Cables ties and flexible barsThe table below indicates the maximum distances between cable ties dependingon the prospective short-circuit current.Care must be taken not to exceed a distance of 400 mm between ties mechanicallysecured to the switchboard frame.
Type of tie "Panduit" type "Sarel" typeWidth: 4,5 mm Width: 9 mmMax. load: 22 kg Max. load: 90 kgColour: white Colour: black
Max. distance 200 100 50 350 200 100 70 50 (doublebetween ties (mm) ties)Short-circuit 10 15 20 20 27 35 45 100current (kA rms)
Note: for cables u 50 mm2, 9 mm wide ties must be used.
Schneider Electric68
Installationrecommendations
Interpact INS40 to 80
Front connection of bare copper andaluminium cablesb Interpact INS40 to INS80 switch-disconnectors are equipped as standard withconnectors for bare copper and aluminium cablesb distribution connectors may be screwed directly to the switch-disconnectorterminals and can be used to connect three cables.Pole pitch
18 mm
Standard With distributiondevice connector
Bars e (mm) y 5 -L (mm) 13 13
Cables L (mm) y 10 y 10S (mm2) 1.5 to 50 rigid 1.5 to 16 rigidCu / Al 1.5 to 35 flexible 1 to 10 flexible (1)
Torque 5 Nm 2 Nm
(1) Connection of 1.5 to 4 mm2 flexible cables requires crimped or auto-crimping ferrules.
Insulation of live partsb with long terminal shieldsb with terminal shrouds.
E38
888
N
.1 .2.4
Distribution connector
E39
432
E89
682
L
e
LS
If 500 V y U y 690 V,interphase-barrier orlong terminal shieldsare mandatory
E89
674
E88
935
Terminal shields Terminal shrouds
Schneider Electric 69
Installationrecommendations
E38
889
.1
N
E54
463
Small lugs for copper cables
If 500 V y U y 690 V,interphase-barrier orlong terminal shieldsare mandatory Bar
E89
683
Front connection of bare copper andaluminium cablesb 1-cable connectors snap directly onto the device terminalsb distribution connectors for 4 flexible cables are screwed directly to the deviceterminals. These connectors are supplied with interphase-barrier (mandatoryinstallation) which may be replaced by long terminal shieldsb Distribloc distribution block supplied via tunnel terminals. Provides 12 screwlessspring type and 1 screw type outgoing terminals.
1-cable Distributionconnector connector
Lugs L (mm) 15 15S (mm2) 10 to 95 rigid 1.5 to 25 rigidCu / Al 10 to 95 flexible 1.5 to 16 flexible (1)
Torque (Nm) 10 3
DistriblocTorque (Nm) Supply 5 Nm
Distribution 3 Nm(1) Connection of 1.5 to 4 mm2 flexible cables requires crimped or auto-crimping ferrules.
Front connection of insulated bars andcables with crimped lugsInterpact INS100 to INS160 switch-disconnectors are equipped as standard withterminals comprising nuts with M6 screws, for direct connection of insulated barsand cables with crimped lugs.
LugsThe small lugs for copper cables may be used for cables with cross-sectional areasup to 95 mm2. Secure the lugs by hexagonal crimping or punching.Lugs are supplied with interphase-barrier and are compatible with the terminalshields.Pole pitch
30 mm
DimensionsBars d (mm) y 10
e (mm) 2…6.4L (mm) y 21
Lugs L (mm) 15ø (mm) u 6.2
Torque (Nm) 8
E32
424
E30
707
1-cableconnector
Distributionconnector
.1 .2 .4
N
E32
423
E54
545
L
S
If 500 V y U y 690 V,interphase-barrier orlong terminal shieldsare mandatory
Distribloc
E55
598
Interpact INS100 to 160E
8967
4
Insulation of live partsAccessoriesInterphase-barrierb distribution blocks, lugs, right-angle/straight/edgewise terminal extensions andspreaders are supplied with interphase-barrierb interphase-barrier may be positioned horizontally or verticallyb they may be replaced by long terminal shields.
Ø
L
d
L
e
E90
303
E89
675
Terminal shields
E88
935
Interphase-barrier
Terminal shrouds
Schneider Electric70
Installationrecommendations
Front connection of bare copper andaluminium cablesb 1-cable connectors snap directly on to the device terminals or are clipped on tothe right-angle or straight terminal extensions or spreaders.These connectors are supplied with interphase-barrier.Material: steel I y 160 A and tinned aluminium I y 250 A.b 6-cable distribution connectors are screwed directly to the device terminals.These connectors are supplied with interphase-barrier (mandatory installation)which may be replaced by long terminal shields.Material: tinned aluminium.b Polybloc distribution blocks, for 6 or 9 rigid or flexible cables, are connecteddirectly to the device terminals. Cable connection is made in spring type terminalsand does not require screws.
1-cable steel Aluminiumconnector yyyyy 160A yyyyy 250AL (mm) 20 20S (mm2) Cu / Al 1.5…95 (1) 10…16 25…35 50…185Torque (Nm) 12 15 20 26
Distribution connector, 6 cables Cu or AlL (mm) 15 ou 30S (mm2) Cu / Al 1.5…6 (1) 8...35Torque (Nm) 4 6
Polybloc distribution block, 6 or 9 cablesL (mm) 12S (mm2) Cu / Al 1.5…10
(1) Connection of 1.5 to 4 mm2 flexible cables requires crimped or auto-crimping ferrules.
E54
471
E54
472
E54
468
1-cable connector
Distribution connector
Polybloc distribution block
E54
465
E54
545
L
S
If 500 V y U y 690 V,interphase-barrier orlong terminal shieldsare mandatory
X
Y
98,5
16666,5
Z
Dimensions1-cable connector
Distribution connector, 6 cables
E55
426
E55
341
E55
427
25,5
57,5
XZ
44Z
X
19
57,5
E55
450
Interpact INS250-100 to 250Interpact INV100 to 250Complete source-changeoverassembly INS250-100 to 250
¯5...8
¯5...8
Schneider Electric 71
Installationrecommendations
Interpact INS250-100 to 250Interpact INV100 to 250Complete source-changeoverassembly INS250-100 to 250 (cont.)
Front connection of insulated bars andcables with crimped lugsInterpact INS250-100 to INS250 and INV100 to 250 switch-disconnectors areequipped as standard with terminals receiving snap-in nuts and screws (M8 forINS/INV up to 250, M10 from 320 upwards) for direct connection of insulated barsor cables with lugs.
LugsLugs are different for copper and aluminium cables. They are supplied withinterphase-barrier and are compatible with the long terminal shields.b the small lugs for copper cables may be used for cables with the following cross-sectional areas:v 120, 150 or 185 mm2 (INS/INV up to 250)Secure the lugs by hexagonal crimping or punching.b the small lugs for aluminium cables may be used for cables with the followingcross-sectional areas:v 150 or 185 mm2 (INS/INV up to 250)Secure the lugs by hexagonal crimping.
Pole pitch35 mm
DimensionsBars d (mm) y 10
e (mm) y 6L (mm) y 25Ø (mm) u 10
Lugs L (mm) y 25Ø (mm) u 10
Torque (Nm) 15
Dimensions
E54
463
Small lugs for copper cables
Small lugs for aluminiumcables
E30
907
E54
459
10,5
57,5
XZ
E55
434
Ø
L
d
L
e
E90
303
If 500 V y U y 690 V,interphase-barrier orlong terminal shieldsare mandatory
Insulation of live partsAccessoriesInterphase-barrierb distribution blocks, lugs, right-angle/straight/edgewise terminal extensions andspreaders are supplied with interphase-barrierb interphase-barrier may be positioned horizontally or verticallyb they may be replaced by long terminal shields.
E55
445
E54
476
Bar
E89
683
¯5...8
¯5...8
Interphase-barrier Terminal shields
Schneider Electric72
Installationrecommendations
DimensionsRight-angle terminal extensions Spreader and straight terminal extensions
One-piece spreader 3P/4P
Pole pitch45 mm
DimensionsBars L (mm) y 25
d (mm) y 10e (mm) y 6Ø (mm) 8.5
Cosses L (mm) y 25Ø (mm) 8.5
Torque (Nm) 15 (1)
(1) Tightening torque for spreader
Spreaders, straight terminal extensions and right-angle terminal extensions aresupplied with interphase-barrier.
E50
303
Ø
L
d
L
e
17,5
98,5
Y
114
45 45
Y
159
45 45 45
30
Z
19,5
X
Y
45 4545 9898
24
43,5
125,5
X
180,5 ZZ
Insulation stripping lengths and tightening torques for cables, bare bars and cableswith lugs are identical to those for direct connection to devices.
Interpact INS250-100 to 250Interpact INV100 to 250Complete source-changeoverassembly INS250-100 to 250 (cont.)
Front connection with accessoriesStraight terminal Right-angleextensions extensionsMaterial: tinned copper. Material: tinned copper
Installation on upstreamterminals
E54
460
E18
601
If 500 V y U y 690 V,interphase-barrier orlong terminal shieldsare mandatory Spreader
Material: tinned copper.
E18
599
Separate parts
E55
599
Connection of two cableswith lugs
E90
490
E18
600
Connection of twocables with lugs
E90
490
E55
436
E55
440
20,5
39,5
57,5
4
XZ
E55
342
One-piece spreader
¯5...8
Schneider Electric 73
Installationrecommendations
Interpact INS250-100 to 250Interpact INV100 to 250Complete source-changeoverassembly INS250-100 to 250 (cont.)
E55
459
E25
969
Connection of bars or cableswith lugs
E25
967 Rear connection
Bars or cables with crimped lugsInterpact INS250-100 to INS250 and INV100 to 250 switch-disconnectors may beequipped with long or short rear connections, or a mix of the two. The connectionsmay be positioned flat, on edge or at 45° angles, or any combination thereof.Material of rear connections: tinned copper.
DimensionsBars L (mm) y 25
d (mm) y 10e (mm) y 6Ø (mm) > 8
Lugs L (mm) y 25Ø (mm) > 8
Torque (Nm) 5 (1)
(1) Tightening torque for rear connections.
Dimensions
Bare cables (copper or aluminium)switch-disconnectors, the rear connections may be equipped with 1-cableconnectors secured by clips.
1-cable steel Aluminiumconnector yyyyy 160A yyyyy 250AL (mm) 20 20S (mm2) Cu / Al 1.5…95 (1) 10…16 25…35 50…185torque (Nm) 12 15 20 26
Distribution connector, 6 cables Cu or AlL (mm) 15 or 30S (mm2) Cu / Al 1.5…6 (1) 8...35torque (Nm) 4 6
(1) Connection of 1.5 to 4 mm2 flexible cables requires crimped or auto-crimping ferrules.
Insulation stripping lengths and tightening torques for cables, bare bars and cableswith lugs are identical to those for direct connection to devices.
E55
446
Two lenghts
E54
474
E54
473
Ø
L
d
L
e
E90
303
E55
447
18
10
∅ 8,6 ∅ 20
6
57,5
XZ
13
43 short RC88 long RC
Four positions
If 500 V y U y 690 V,short terminal shieldsare mandatory
If 500 V y U y 690 V,short terminal shieldsare mandatory
E54
545
L
S
Bar
E89
683
¯5...8
¯5...8
Schneider Electric74
Installationrecommendations
E54
470
1-cable connector
2-cable connector
E54
469 Front connection of bare copper and
aluminium cables1-cable and 2-cable connectors, made of tinned aluminium for copper andaluminium cables, are screwed to the device terminals or to right-angle terminalextensions. These connectors are supplied with interphase-barrier.
1-cable 2-cableconnector connector
Torque (Nm) 31 31
Dimensions1-cable connector
2-cable connector
Z4449
88,5
X
Z
X
46,5
88,5
X
14
88,5
Z
E55
428
L
SE
5454
5E
5542
9
E55
431
E55
430
If 500 V y U y 690 V,interphase-barrier orlong terminal shieldsare mandatory
Interpact INS320 to 630Interpact INV320 to 630Complete source-changeoverassembly INS320 to 630
Insulation of live partsAccessoriesInterphase-barrierb distribution blocks, lugs, right-angle/straight/edgewise terminal extensions andspreaders are supplied with interphase-barrierb interphase-barrier may be positioned horizontally or verticallyb they may be replaced by long terminal shields.
E88
874
E54
476
Terminal shieldsInterphase-barrier
Schneider Electric 75
Installationrecommendations
Front connection of bars and cables withcrimped lugsInterpact INS320 à 630 et INV320 à 630 switch-disconnectors are equipped asstandard with terminals receiving snap-in nuts and screws (INS/INV from 320 :M10) for direct connection of bars or cables with lugs.
LugsLugs are different for copper and aluminium cables. They are supplied withinterphase-barrier and are compatible with the long terminal shields.b the small lugs for copper cables may be used for cables with the following cross-sectional areas:v 240 or 300 mm2 (INS/INV up to 630).Secure the lugs by hexagonal crimping or punching.b the small lugs for aluminium cables may be used for cables with the followingcross-sectional areas:v 240 or 300 mm2 (INS/INV up to 630).Secure the lugs by hexagonal crimping.Pole pitch
45 mm
DimensionsBars d (mm) y 15
e (mm) 3 y e y 10L (mm) y 32Ø (mm) u 10
Lugs L (mm) y 32Ø (mm) u 10
Torque (Nm) 50
DimensionsINS320 to 630 - INV320 to 630
Interpact INS320 to 630Interpact INV320 to 630Complete source-changeoverassembly INS320 to 630 (cont.)
E54
463
Small lugs for copper cables
Small lugs for aluminiumcables
E30
907
E88
872
Ø
L
d
L
e
E90
303
If 500 V y U y 690 V,interphase-barrier orlong terminal shieldsare mandatory
88,5
X
14
Z
E55
433
Bar
E89
683
Schneider Electric76
Installationrecommendations
Interpact INS320 to 630Interpact INV320 to 630Complete source-changeoverassembly INS320 to 630 (cont.)
E88
873
Front connection with accessoriesSpreader Straight terminal Right-angle
extensions terminal extensionsMaterial: tinned copper. Material: tinned copper. Material: tinned copper.
Installation on upstreamterminals
Pole pitchWithout spreader 45 mmWith spreader 52.5 or 70 mmDimensions with with edgewise
spreader terminal ext.Bars L (mm) y 40 y 32
d (mm) y 20 y 15e (mm) 3 y e y 10 3 y e y 10Ø (mm) 12.5 > 10.5
Lugs L (mm) y 40 y 32Ø (mm) 12.5 10.5
Torque (Nm) 50 (1) 50 (1)
(1) Tightening torque for spreader
Spreaders, straight terminal extensions and right-angle terminal extensions aresupplied with interphase-barrier.
DimensionsEdgewise terminal extensions Right-angle terminal extensions
Spreader
Ø
L
d
L
e
E88
877E
8887
6
E88
875
E90
303
If 500 V y U y 690 V,interphase-barrier orlong terminal shieldsare mandatory
Type K8 K9 K10Spreader width in mod. of 52.5 mm 52.5 187.5 135
width in mod. of 70 mm 70 240 170
88,5
X
5842
Z
F
8
88,5
X
5842
Z
F vue F
8
vue F
E55
444
E55
438
E55
442
Z34
61
88,5
8
X
BarE
8968
3
K10K8K8 K8
K9
39
108
X
26K8 K8
22,5Y ZY
Schneider Electric 77
Installationrecommendations
Interpact INS320 to 630Interpact INV320 to 630Complete source-changeoverassembly INS320 to 630 (cont.)
E88
871
Connection of bars or cableswith lugs
E25
967
Rear connection of bars or cables withcrimped lugsInterpact INS320 to 630 and INV320 to 630 switch-disconnectors may be equippedwith long or short rear connections, or a mix of the two. The connections may bepositioned flat, on edge or at 45° angles, or any combination thereof.Material of rear connections: tinned copper.
DimensionsBars L (mm) y 32
d (mm) y 15e (mm) 3 y e y 10Ø (mm) > 10.5
Lugs L (mm) y 32Ø (mm) > 10.5
Torque (Nm) 20 (1)
(1) Tightening torque for rear connections.
DimensionsINS320 to 630 - INV320 to 630
Bare cables (copper or aluminium)Interpact INS320 to 630 and INV320 to 630, switch-disconnectors,the rear connections may be equipped with 1-cable connectors secured by clips.Insulation stripping lengths and tightening torques for cables are identical to thosefor direct connection to devices.
E88
870
Two lenghts
E88
880
E88
879
Ø
L
d
L
e
E90
303
E55
447
E55
449
18
10
∅ 8,6 ∅ 20
6
57,5
XZ
13
43 short RC88 long RC
30
15 ∅ 13 ∅ 23,2
8
88,5
XZ
14
50 short RC115 long RC
Four positions
If 500 V y U y 690 V,short terminal shieldsare mandatory
If 500 V y U y 690 V,short terminal shieldsare mandatory
E25
969
Bar
E89
683
Schneider Electric78
Installationrecommendations
ConnectionINS630b to 1600 andINV630b to 1600
Front connection of insulated bars
Connection of barsInterpact switch-disconnectors are equipped with terminals for direct connectionof bars.
2 Ø12 maxi
12,5 50
25
12,53 Ø12 maxi
1580
12,5
25 25
E88
865
E88
888
E88
889
Insulation of live parts
AccessoriesInterphase-barrierb interphase-barrier may be positioned horizontally or verticallyb they may be replaced by long terminal shields.
E88
866
E88
682
Interphase-barrier Terminal shield
Compatibility of terminal shields + base for connectionsBase Terminal Spreader Interphase-barrier
shieldsBase – YES YES NOTerminal shields YES – NO NOSpreader NO NO – YESInterphase-barrier NO NO YES –
Schneider Electric 79
Installationrecommendations
Connection (cont.)
INS630b to 1600 andINV630b to 1600 (cont.)
ConnectionsThere are many solutions to connect bars:b vertical connection adapters to connect edgewise barsb spreaders with a 95 mm pole pitch to increase the clearance between bars.
E88
867
E88
868
E88
869
E88
663
Spreaders
Cable lug adapters
E88
668
Connection of cables with lugsCable-lug adapters are used in conjunction with vertical connection adapters.Thwey may be used to connect one to four cables (y 300 mm2) with crimped lugs.To ensure adequate mechanical strength, the cable-lug adapters must be securedtogether by spacers.
Vertical connection adapters
Lugs for copper cables
E89
547
E88
666
Schneider Electric80
Installationrecommendations
X
Y
187
187202
202
12,5
70
12,5
70 70
95 95 9597,5
Connection (cont.)
INS630b to 1600 andINV630b to 1600 (cont.)
E88
670
E88
669
Connection with vertical connection adapters
E88
671
Dimensions
Connection with spreaders
X
56,5 15
X
187
187202
202
Y
70 70
95 95110
Spreader details
X
50,5 12
171
171206
206
221
221
X
Y
15
7070135
X
Y
15
7070 70135
12,5=25 =
89
15
21
17
10113
15
E88
673
E88
674
E88
675
E88
676
Note:2 connection possibilities on vertical connection adapters(21 mm between centres)Recommended connection screws: M10 class 8.8.Tightening torque: 50 Nm with contact washer.
5 Ø11
13,5=25 =
38,5
77
15
305282
25
52
E89
549
E88
672
52
13,5=25 =
38,5
77
15
305282
25
13,5=25 =
38,5
77
5282 15
30
25
52
5 Ø11
E89
548
5 Ø11
13,5=25 =
38,5
77
15
305282
25
52
E89
550
For 3P switch-disconnectors For 4P switch-disconnectors
Connector details
Schneider Electric 81
Installationrecommendations
Connection (cont.)
INS630b to 1600 andINV630b to 1600 (cont.)
Connection using vertical connection adapters and cable-lug adapters
X
191
191206
206
256
256
12155
X
Y
15
7070
10
135
X
Y
15
7070
10
70135
E88
677
E88
678
E88
679
50
50 50 50 17
184
80
5 Ø13 5 Ø11
15E
8868
0
Cable lug adapter detail
Schneider Electric82
Installationrecommendations
Connection (cont.)
INS2000 to 2500 andINV2000 to 2500
Front connection of insulated bars
Connection of barsInterpact switch-disconnectors are equipped with terminals for direct connectionof bars.
2 Ø12 maxi
12,5 50
25
12,53 Ø12 maxi
1580
12,5
25 25
E88
888
E88
889
Insulation of live parts
AccessoriesInterphase-barrier
E94
444
E94
445
Schneider Electric 83
Installationrecommendations
Connection (cont.)
INS2000 to 2500 andINV2000 to 2500 (cont.)
Y
115
180X
11567,5
347,5
90
270
205
205
440
E94
153
115
180
Y
X
11511567,5
90
462,5
270
205
205
440X
76 24
E94
154
E94
155
E94
157
E94
156
E94
158
Dimensions
Connection with spreaders
Spreader details
For switch-disconnectors 3P For switch-disconnectors 4P
E94
152
Schneider Electric84
Installationrecommendations
Interpact INS/INV 630b 800 1000 1250 1600 (4 bars 50 x 5) 2000 2500with or without with or without with without with without without withoutterm. shield term. shield term. shield term. shield term. shield term. shield term. shield term. shield
Direct connection by flat-facing barsThermal current Ith at 40 °C 630 800 1000 1250 1250 1600 1600 2000 2500
45 °C 630 800 1000 1250 1250 1570 1600 2000 250050 °C 630 800 1000 1250 1250 1500 1550 2000 250055 °C 630 800 1000 1250 1250 1420 1470 2000 250060 °C 630 800 1000 1250 1250 1340 1390 2000 250065 °C 630 800 1000 1250 1250 1250 1300 2000 250070 °C 630 800 1000 1060 1210 1060 1210 2000 2400
Interpact INS/INV 630b 800 1000 1250 1600 (3 bars 80 x 5)Connection by flat-facing bars via spreaders, WITHOUT terminal shields
Thermal current Ith at 40 °C 630 800 1000 1250 160045 °C 630 800 1000 1250 160050 °C 630 800 1000 1250 158055 °C 630 800 1000 1250 150060 °C 630 800 1000 1250 142065 °C 630 800 1000 1250 133070 °C 630 800 1000 1240 1240
Interpact INS/INV 630b 800 1000 1250 1600with withoutterm. shield term. shield
Connection of edgewise bars via vertical connection adapters or cables via vertical connection adapters with cable-lug adaptersThermal current Ith at 40 °C 630 800 1000 1250 1600 1600
45 °C 630 800 1000 1250 1600 160050 °C 630 800 1000 1250 1600 160055 °C 630 800 1000 1250 1600 160060 °C 630 800 1000 1250 1600 160065 °C 630 800 1000 1250 1520 156070 °C 630 800 1000 1250 1410 1450
Thermal current Ith in Amps (QA)
Use at high temperatures
Power dissipated and resistance per poleInterpact INS 40 63 80 100 125 160
Rating (A) 40 63 80 100 125 160Resistance per pole (mΩ) 0.3 0.3 0.3 0.2 0.2 0.2Power dissipated per pole (W) 0.5 1.2 1.9 2 3.1 5.1
Interpact INS/INV 100 160 200 250 320 400 500 630Rating (A) 100 160 200 250 320 400 500 630Resistance per pole (mΩ) 0.15 0.15 0.15 0.15 0.06 0.06 0.06 0.06Power dissipated per pole (W) 1.5 4 6 9.5 6.1 9.6 15 24
Interpact INS/INV 800 1000 1250 1600 2000 2500Rating (A) 800 1000 1250 1600 2000 2500Resistance per pole (mΩ) 0.024 0.024 0.024 0.024 0.012 0.012Power dissipated per pole (W) 16 24 38 62 48 75
Temperature deratingInterpact INS 40 63 80 100 125 160Front connection with bare-cable connectors or lugs
Thermal current Ith at 60 °C 40 63 80 100 125 16065 °C 40 63 80 100 125 16070 °C 40 63 80 100 125 150
Interpact INS/INV 100 160 200 250 320 400 500 630Front connection / rear connection
Thermal current Ith at 60 °C 100 160 200 250 320 400 500 63065 °C 100 160 200 250 320 400 500 59070 °C 100 160 200 250 320 400 500 550
Front connection with right-angle terminal extension + bare-cable connectorsThermal current Ith at 55 °C 100 160 200 250 320 400 500 630
60 °C 100 160 200 250 320 400 500 59065 °C 100 160 200 250 320 400 500 55070 °C 100 160 200 240 320 400 500 510
Front connection / rear connection with ammeter or CT moduleThermal current Ith at 40 °C 100 160 200 250 320 400 500 600
50 °C 100 160 200 250 320 400 500 57555 °C 100 160 200 250 320 400 500 54060 °C 100 160 200 240 320 400 500 50565 °C 100 160 200 230 320 400 480 48070 °C 100 160 200 210 320 400 450 450
Schneider Electric 85
Presentation 2Functions and characteristics 17Installation recommendations 63
Interpact INS40 to 160 86Interpact INS250-100 to 630 90Interpact INV100 to 630 90Interpact INS630b to 1600 94Interpact INV630b to 1600 94Interpact INS2000 to 2500 96Interpact INV2000 to 2500 96Mechanical interlocks for direct 98and extended handles (INS40 to 630, INV100 to 630)
Complete source-changeover assembly 99INS250-100 to 250 A and INS320 to 630 99
Installation of downstream coupling 100(INS250-100 to 630, INV100 to 630)
Front panel accessories (INS250-100 to 2500, INV100 to 630) 101
Additional characteristics 103Calalogue numbers 113
Dimensions and connection
Schneider Electric86
e
X
B 47Z
A
Dimensions (mm)
Type H H1 H2 H3 H4 H5 H6 H7 K K1 L L1 L2 P P1 P2 P3 P4 P5INS40/63/80 22.5 45 40.5 81 42.5 85 73.5 147 1 18 46 73 90 21.3 43 47 62.5 79 5INS100/125/160 22.5 45 50 100 50 100 110 220 7.5 30 67.5 119 135 18.5 45 47 62.5 79 5
Interpact INS40 to 160
H3
HH2 H4
P5
P4P3
H6
H7
H5
PP1P2
(a)(b)
Z
X H1 X
Y
L1L
L2
KK1 K1 K1
E32
250
E32
252
E32
261
X
Y
120°
K
(a) Terminal shields INS40/63/80(b) Terminal shields INS100/125/160
E32
255
Dimensionsand connection
Dimensions
Front handle
Extended front handle
E32
610
Dimensions (mm)
Type A (on back plate) B (on rail)mini maxi mini maxi
INS40/63/80 128 519 123 514INS100/125/160 128 519 123 514
Type e K Lengthof shaft
INS40/63/80 1…3 1 A – 69INS100/125/160 1…3 7.5 A – 69
E32
609
Door or front panel cutout for front handleDirect Extended
Dimensions (mm)
Type C R KINS40/63/80 47 92 1INS100/125/160 47 137 7.5
E32
611
=
=
XC
= =Y
R
Schneider Electric 87
Interpact INS40 to 160 (cont.)Dimensionsand connection
Z
X
P7P6
E32
254
X
Y
L3
E32
253
120°
60°
E32
256
Dimensions
Standard lateral handle
Dimensions (mm)
Type L3 P6 P7INS40/63/80 109 40 66.1INS100/125/160 154 42.5 69.3
Dimensions (mm)
Type B e P6 LengthWith shaft mini maxi of shaft
INS40/63/80 155 396 1…3 40 B – 95INS100/125/160 200 441 1…3 42.5 B – 140
Without shaft B e P6INS40/63/80 102 1…3 40INS100/125/160 147 1…3 42.5
Extended lateral handle
Y
B
e
X
33
E32
613
E38
890
Dimensions (mm)
Type Enclosure Type B e P6length of shaft
INS40/63/80 550 mm short 149 1…3 41.5600 mm long 174 1…3 41.5
INS100/125/160 550 mm short 194 1…3 41.5600 mm long 219 1…3 41.5
Lateral handle for functional enclosure
Y
B
e
X
33
O
I
6532,5
X
75
37,5
120°
ZP6
O
I
6532,5
X
75
37,5
120°
ZP6
E38
891
E38
890
Note:Lines X and Y indicate the axes of symmetry of theswitch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
Schneider Electric88
Interpact INS40 to 160 (cont.)Dimensionsand connection
sur rail symétrique
X
Y
C2
C1
R2R1
ØT
E32
259
E32
452
Dimensions (mm)
Type C1 C2 R1 R2 ØT UINS40/63/80 40 80 10 36 4.5 35INS100/125/160 37.5 75 22.5 60 4.5 35
Installation
On a backplate On rail
X
Z
P6
R = 36
Ø50
Ø6
23,423,4
55°
E38
892
Dimensions (cont.)
Front panel cutout for extended handle
Schneider Electric 89
Schneider Electric90
AZ
X
e
47
Interpact INS250-100 to 630Interpact INV100 to 630
E51
177
(a) Terminal shields(b) Interphase-barrier
Dimensionsand connection
Dimensions
E51
178
E51
179
Door or front panel cutout for front handleStandard without escutcheon Standard with escutcheon Extended
E54
508
Extended front handleWith escutcheon
E54
513
E54
514
E51
184
Front handle
Dimensions (mm)
Type H H1 H2 H3 H4 H5 H6 H7 H8 H11 K K1 L L1 P P1 P2 P3 P4INS250 40 80 68 136 148 296 166 332 115 57.5 17.5 35 70 140 21.5 86 96 131 138INV100/250INS320/630 61.5 123 102.5 205 215 430 – – 177 88.5 22.5 45 92.5 185 26 120 130 160.4 162INV320/630
E90
480
Dimensions (mm)
Type C6 C7 H9 L3 L4 R6 R7INS250 51.5 103 82 65.5 131 81 162INS320/630 76.5 153 127 85.5 171 101 202
E90
484
Dimensions (mm)
Type A e
mini maxiINS250 185 600 1…3INS320/630 204 600 1…3
Type K P5 P6INS250 17.5 86 88INS320/630 22.5 110 112
Type Length of shaft AINS250 101INS320/630 124
H
H1
H2
H3
H4
H5
H6
H7
P
X
P1P2P3P4Z
(a)(b)
H8X
K1Y
K1K1
LKL1
X
P5P6Z
=
=H9
L3
X
L4
Y
C6
X C7
R6R7
Y
Schneider Electric 91
Ø5
H11
H10
X
L5L6
Y
X
Y152,5 mini577 maxi
1...3
48
Note:Lines X and Y indicate the axes of symmetry of theswitch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
Installation
On panel fixed/FC On panel fixed/RC On rail
E51
183
Interpact INS250-100 to 630Interpact INV100 to 630 (cont.)
Dimensionsand connection
Standard lateral handle for INS250-100 to 250 and INV100 to 250
E56
575
E56
576
Dimensions
Extended lateral handle for INS250-100 to 250 and INV100 to 250
E90
472
E90
473
Y
X
203
50
100
91
K1 K1 K1
H11
H8X
Y
L6L5
H10
H11X
Y
E56
573
E56
574
Door or front panel cutout for lateral handle
E56
577
Schneider Electric92
Dimensionsand connection
DimensionsSwitch-disconnector with ammeter module Switch-disconnector equippedDirect handle (*) Extended handle with current transformer
Front panel cutoutSwitch-disconnector with ammeter moduleDirect handle (*) Extended handle
E94
201 E90
475
E90
476
P1P2P3 (1)P4 (2)
Z
X
H17
H14 H16
H15 H19
H18
Z
X
P43
X
Y
C22
C23
R14R15
C28
C27
R17R16
C27
C29(*)
Interpact INS250-100 to 630Interpact INV100 to 630 (cont.)
(1) To front of direct handle.(2) To front of key.
E90
474
P2
H11
H8 H10
H9
Z
X
H13
P47
P1
H12
(*) Only for INS250/INV100 to 250.
E94
202
Note:lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
P2
H17
H14 H16
H15
Z
X
H19
P47
P1
H18
Z
X
185 y A y 600
E90
477
(*) Only for INS250/INV100 to 250 withdirect handle and ammeter module.
Schneider Electric 93
Dimensionsand connection
Interpact INS250-100 to 630Interpact INV100 to 630 (cont.)
Dimensions (mm)
Type C22 C23 C27 C28 C29 G G1 G6 G7 G8 G9 G10 G11 G12 G13INS/INV100 to 250 41 82 56.5 187 ?? 62.5 125 137.5 200 145 215 ?? ?? ?? ??INS/INV320 to 630 63.5 127 56.5 162 ?? 100 200 200 300 213.5 327 ?? ?? ?? ??
Type H8 H9 H10 H11 H12 H13 H14 H15 H16 H17 H18 H19INS/INV100 to 250 216 282 231.5 ?? ?? ?? ?? ?? ?? ?? ?? ??INS/INV320 to 630 202.5 305 217.5 ?? ?? ?? ?? ?? ?? ?? ?? ??
Type K K1 K2 P1 P2 P3 P4 P43 P47 R14 R15 R16 R17 ØT ØT4 U(e)INS/INV100 to 250 17.5 35 70 81 86 131 138 89 137 48.5 97 46.5 93 6 22 y 32INS/INV320 to 630 22.5 45 90 95.5 110 160.4 162 112 162 64.5 129 64.5 93 6 32 y 32
E90
479
E90
478
E21
521
K2K
X
Y
G
G1
G6
G7
ØTK1 K1 K1
X
Y
G8
G9
ØT4
Y
X
KK2
G
G1
ØT
G6
U(e)
G7
Connection (for direct rotary handle equipped with ammeter module)
On a backplate On railsFixed front connection Fixed rear connection
Connection (for extended rotary handle equipped with ammeter module)
On a backplate On railsFixed front connection Fixed rear connection
K2K
X
Y
G
G1
G10
G11
ØTK1 K1 K1
X
Y
G12
G13
ØT4
Y
X
KK2
G
G1
ØT
G10
U(e)
G11
E94
256
E94
257
E94
258
Schneider Electric94
Dimensions
Direct front handle3 poles 4 poles
Interpact INS630b to 1600Interpact INV630b to 1600
E88
687
E88
688
Dimensionsand connection
X
Z
117,5150
300
56,5
247
247
260,5
260,5
105,5
140,5
198
270
146,5
185
(a)
(b)
X
Y
70 70
210
340
105 20
270
(a)(b)
X
Y
70 70 70
175
280
410
20
270
(a) Terminal shields(b) Interphase-barrier
E88
689
Extended front handle
Z
X
A
e
X
Y
30°
K
R100
30°H
H1
E88
693
E88
692 Dimensions (mm)
Type A e K Length
mini maxi of shaft AINS630b/1600 210 583.5 1…3 87 ?
Note:Lines X and Y indicate the axes of symmetry of theswitch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
Schneider Electric 95
Installation
On backplate On rail
X
Y
320 (3P)390 (4P)
90
180
Ø9
115 (3P)185 (4P)
Door or front panel cutout for extended handleDirect front handle Extended front handle
E88
690
E88
690
E88
884
E88
694
X
Y
320 (3P)390 (4P)
90
180
115 (3P)185 (4P)
Interpact INS630b to 1600Interpact INV630b to 1600 (cont.)
Dimensionsand connection
X
Z
A
B
CD
X
Y
F
G
E
E90
471
E90
305
Cutout for switch-disconnector cover (mm)
Type A D E F G3P 107 299 103 108 2164P 107 369 173 108 216
Cutout for switch-disconnector front (mm)
Type B D E F G3P 142 268 85 95.5 1914P 142 228 155 95.5 191
Cutout for escutcheon (mm)
Type C D E F G3P 132 327 110 121.5 2434P 132 397 180 121.5 243
Schneider Electric96
Interpact INS2000 to 2500Interpact INV2000 to 2500
Dimensionsand connection
Y
410X
17,5
132,5177,5
347,551
X
186,5
221,5
227,5
320
440235
210185
410
Y
X
62,5390
247,5177,5
462,551
Dimensions
Direct front handle3 poles 4 poles
E94
161
E94
160
E94
162
Schneider Electric 97
Interpact INS2000 to 2500Interpact INV2000 to 2500 (cont.)
Dimensionsand connection
Door or front panel cutout for extended handleDirect front handle
Extended front handle
E88
694
D
X
Y
F
G
E
E90
471
E94
163
Cutout for switch-disconnector cover (mm)
Type A D E F G3P 188 299 103 108 2164P 188 369 173 108 216
Cutout for switch-disconnector front (mm)
Type B D E F G3P 223 268 85 95.5 1914P 223 228 155 95.5 191
Cutout for escutcheon (mm)
Type C D E F G3P 213 327 110 121.5 2434P 213 397 180 121.5 243
Installation
On backplate
X
Y
320 (3P)390 (4P)
90
180
Ø9
115 (3P)185 (4P)
E88
690
E88
690
e
X
Z
A 64
E94
451
Schneider Electric98
FY Y
X
H H
X
GZ
47
Mechanical interlocks for directand extended handles(INS40 to 630, INV100 to 630)
Dimensions for direct handle (INS250-100 to 630 and INV100 to 630)
E54
510
E54
511
Door cutout for direct handle
E54
512
Dimensionsand connection
Dimensions for extended handle (INS40 to 630 and INV100 to 630)
Door cutout for extended handle
E55
452
E55
451
E55
453
GZ
X X
B
A
C
D
F
Y YE
P
Q
Y Y
X
N
M
H H
LF
K
X
BA
C
D
F
Y YE
P
Q
Dimensions (mm)
Type A B C D E F H K L M N G P QINS250 325 90 87.5 175 70 156 17.5 295 75.5 150 75 106 68 136INV100/250INS320/630 416 115 100 200 92.5 210 22.5 386 100 175 74.5 130 102.5 205INV320/630
Dimensions (mm)
Type A B C D E F G H P Qmini maxi
INS40/80 325 90 87.5 175 46 156 155 396 0 45 90INS100/160 325 90 87.5 175 70 156 200 441 0 50 100INS250 325 90 87.5 175 70 156 185 600 17.5 68 136INV100/250INS320/630 416 115 100 200 92.5 210 204 600 22.5 102.5 205INV320/630
Note:lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
99Schneider Electric 99
Complete source changeoverassemblyINS250-100 to 250 Aand INS320 to 630
Dimensionsand connection
Dimensions of the complete source-changeover assembly with a direct handle
B
A
C
D
EX
Y Y
G
H
I
JX
YK
Y
E68
354
E68
355
Dimensions (mm)
Type A B C D E F G H I J KINS250 60.4 130.4 296 68 136 131 61.8 279.3 42 84 156INS320/630 82.5 175 395 102.5 205 155 87 383.7 64 128 210
E68
356
Front cutout
Dimensions of the complete source-changeover assembly with an extended handle
Door cutout Dimensions (mm)
Type A B C D E F G H I JINS250 136 631 35 70 295.4 50 100 132 60.4 155.7INV100/250INS320/630 163 658 45 90 395 75 150 205 82.5 210INV320/630
Note:lines X and Y indicate the axes of symmetry of the switch-disconnector.Reference plane Z corresponds to the back of the switch-disconnector.
A
Z
X
B
J
X
YI
Y
E90
485
E90
486
E90
487
D
C
E
F
GX
Y Y
H
Schneider Electric100
X
Y
G2
Y
G3
L33
L32
L30
L28
L31
L29
L34
G28
L40
L39
G29
G30
G52
X
Y
K8
K1 K1 K1 K1 K1 K1
Y
K3K4
K9
K2 K2 K2K16
Installation of downstreamcoupling(INS250-100 to 630, INV100 to 630)
L35L36
Dimensions
E55
454
E55
455
E55
456
E55
457 E55
458
Dimensions Connection
L38
X
Dimensionsand connection
X
Y Y
L37
Dimensions (mm)
Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16INS250 105.5 169 225.2 83.5 127.5 143.5 35 35 51 156 57.5 157.5 25.4INV100/250INS320/630 141 240.7 315 118.4 163.4 202.5 45 52.5 75 210 88.5 225.7 26.1INV320/630
Type L28 L29 L30 L31 L32 L33 L34 L35 L36 L37 L38 L39 L40INS250 320 82.2 300 72.2 16.4 123 139.5 74.5 19.5 70 21.5 24.9 140INV100/250INS320/630 420 105.2 400 95.2 11.1 187.5 184.7 96.5 24 92.5 26 22.4 210INV320/630
Schneider Electric 101
D2D1
M7M6
A2
Front-panel escutcheon
For switch-disconnectors
E56
500
E56
501
E56
502
For ammeter module
93,5
157 6,53,5
80,5
Dimensions (mm)
Type A2 D1 D2 M6 M7INS250 174 3.5 6.5 114 101INV100/250INS320/630 215.5 3.5 6.5 164 151INV320/630INS630b/2500 3P 346 3.5 11.5 257.5 242 x 326.5INV630b/2500 4P 416 3.5 11.5 257.5 242 x 396.5
E21
650
E21
651
E21
652
Front-panel accessories(INS250-100 to 2500, INV100 to 2500)
Dimensionsand connection
Front alignment (only for INS/INV250-100)
E94
164
E94
165
Schneider Electric102
Schneider Electric 103
Presentation 2Functions and characteristics 17Installation recommendations 63Dimensions and connection 85
Protection of switch-disconnectors 104INS40 to 160 by Compact NS circuit breaker or fuse 104INS/INV100 to 630 by Compact NS circuit breaker or fuse 106INS/INV630b to 2500 by Compact NS circuit breaker or fuse 108INS/INV630b to 2500 by Masterpact circuit breakers NT and NW 110
Catalogue numbers 113
Additional characteristics
Schneider Electric104
ø5...8
Interpact INS switch-disconnectorsUpstream protection
By circuit breaker type / max. rating (A)380/415 V Isc max. kA rms
making capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peak
By circuit breaker type / max. rating (A)440/480 V (*) Isc max. kA rms
making capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peak
By circuit breaker type / max. rating (A)500 V (INS40 to INS80) Isc max. kA rms500/525 V (INS100 to INS160) making capacity kA peak
type / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peak
By circuit breaker type / max. rating (A)690 V Isc max. kA rms
making capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peaktype / max. rating (A)Isc max. kA rmsmaking capacity kA peak
Per fuse type aM (1) / max. rating (A)500 V Isc max. kA rms.
making capacity kA peaktype gG (2) / max. rating (A)Isc max. kA rms.making capacity kA peaktype gG (1) / max. rating (A)Isc max. kA rms.making capacity kA peaktype BS (2) / max. rating (A)Isc max. kA rms.making capacity kA peaktype BS (1) / max. rating (A)Isc max. kA rms.making capacity kA peak
(*) Applicable for 480 VNEMA.(1) Mandatory protectionby an external thermalrelay.(2) No external thermalprotection.
Protectionof switch-disconnectorsINS40 to 160 by Compact NS circuitbreaker or fuse
Additional characteristicsE
8871
0
Schneider Electric 105
INS40 INS63 INS80 INS100 INS125 INS160
NS100N / 40 NS100N / 63 NS100N / 80 NS100N / 10025 25 25 2552 52 52 52NS100H-L / 40 NS100H-L / 63 NS100H-L / 80 NS100H-L / 10036 36 36 7075 75 75 154NS160N / 40 NS160N / 63 NS160N / 80 NS160-250N / 100 NS160-250N / 125 NS160-250N / 16025 25 25 36 36 3652 52 52 75 75 75NS160H-L / 40 NS160H-L / 63 NS160H-L / 80 NS160-250H-L / 100 NS160-250H-L / 125 NS160-250H-L /16025 25 25 70 70 7052 52 52 154 154 154NSC100N / 40 NSC100N / 63 NSC100N / 80 NSC100N / 10018 18 18 1837 37 37 37NG125N / 40 NG125N / 63 NG125N / 80 NG125N / 100 NG125N / 12525 25 25 25 2552 52 52 52 52NG125H / 40 NG125H / 63 NG125H / 8036 36 3675 75 75NG125L / 40 NG125L / 63 NG125L / 8050 50 50105 105 105NSA160N / 40 NSA160N / 63 NSA160N / 80 NSA160N / 100 NSA160N / 125 NS160N / 16030 30 30 30 30 3063 63 63 63 63 63NS100N / 40 NS100N / 63 NS100N / 80 NS100N / 10025 25 25 2552 52 52 52NS100H-L / 40 NS100H-L / 63 NS100H-L / 80 NS100H-L / 10035 35 35 6573 73 73 143NS160N / 40 NS160N / 63 NS160N / 80 NS160-250N / 100 NS160-250N / 125 NS160-250N / 16025 25 25 35 35 3552 52 52 73 73 73NS160H-L / 40 NS160H-L / 63 NS160H-L / 80 NS160-250H-L / 100 NS160-250H-L / 125 NS160-250H-L /16025 25 25 65 65 6552 52 52 143 143 143NSC100N / 40 NSC100N / 63 NSC100N / 80 NSC100N / 10018 18 18 1837 37 37 37NS100N / 40 NS100N / 63 NS100N / 80 NS100N / 10018 18 18 1836 36 36 36NS100H-L / 40 NS100H-L / 63 NS100H-L / 80 NS100H-L / 10018-25 18-25 18-25 35-10036-53 36-53 36-53 73-220NS160N / 40 NS160N / 63 NS160N / 80 NS160-250N / 100 NS160-250N / 125 NS160-250N / 16015 15 15 22 22 2230 30 30 46 46 46NS160H-L / 40 NS160H-L / 63 NS160H-L / 80 NS160-250H-L / 100 NS160-250H-L / 125 NS160-250H-L /16015 15 15 22 22 2230 30 30 46 46 46NSC100N / 40 NSC100N / 63 NSC100N / 80 NSC100N / 10010 10 10 1017 17 17 17– – – NS100N / 100– – – 8– – – 14– – – NS100H-L / 100– – – 10-75– – – 17-165– – – NS160-250N / 100 NS160-250N / 125 NS160-250N / 160– – – 8 8 8– – – 14 14 14– – – NS160-250H-L / 100 NS160-250H-L / 125 NS160-250H-L /160– – – 10-20 10-20 10-20– – – 17-40 17-40 17-4040 63 80 100 125 16080 80 80 80 55 33176 176 176 176 121 6932 50 63 80 100 125100 100 100 100 100 100220 220 220 220 220 220125 125 125 160 160 160100 100 100 100 100 100220 220 220 220 220 22032 50 & 32M50 63 & 32M63 80 & 63M80 100 & 63M100 125 & 100M12580 80 80 80 80 80176 176 176 176 176 176125 & 100M125 125 & 100M125 125 & 100M125 160 & 100M160 160 & 100M160 160 & 100M16080 80 80 80 80 80176 176 176 176 176 176
Protectionof switch-disconnectors (cont.)
INS40 to 160 by Compact NS circuitbreaker or fuse (cont.)
Additional characteristics
Schneider Electric106
(*) Applicable for 480 V NEMA.(1) Mandatory protection by an external thermal relay.(2) No external thermal protection.
Protectionof switch-disconnectors (cont.)
INS/INV100 to 630 by Compact NScircuit breaker or fuse
Additional characteristics
pushto
trip
STR 23 SE
90105
alarm
test
%Ir
E88
711
Interpact INS switch-disconnectors INS250-100 INS250-160Upstream protection INV100 INV160
By circuit breaker type / max. rating (A) NS100-160-250N/100 NS160-250N/160380/415 V Isc max. kA rms 25-36-36 36
making capacity kA peak 53-75-75 75type / max. rating (A) NS100-160-250H/100 NS160-250H/160Isc max. kA rms 70 70making capacity kA peak 154 154type / max. rating (A) NS100-160-250L/100 NS160-250L/160Isc max. kA rms 150 150making capacity kA peak 330 330
By circuit breaker type / max. rating (A) NS100-160-250N/100 NS160-250N/160440/480 V (*) Isc max. kA rms 25-25-35 35
making capacity kA peak 53-53-73 73type / max. rating (A) NS100-160-250H/100 NS160-250H/160Isc max. kA rms 65 65making capacity kA peak 143 143type / max. rating (A) NS100-160-250L/100 NS160-250L/160Isc max. kA rms 130 130making capacity kA peak 286 286
By circuit breaker type / max. rating (A) NS100-160-250N/100 NS160-250N/160500 V Isc max. kA rms 18 30
making capacity kA peak 36 63type / max. rating (A) NS100-160-250H/100 NS160-250H/160Isc max. kA rms 50 50making capacity kA peak 105 105type / max. rating (A) NS100-160-250L/100 NS160-250L/160Isc max. kA rms 100-70-70 70making capacity kA peak 220-154-154 154
By circuit breaker type / max. rating (A) NS100-160-250N/100 NS160-250N/160525 V Isc max. kA rms 18 22
making capacity kA peak 36 46type / max. rating (A) NS100-160-250H/100 NS160-250H/160Isc max. kA rms 35 35making capacity kA peak 73 73type / max. rating (A) NS100-160-250L/100 NS160-250L/160Isc max. kA rms 100-50-50 50making capacity kA peak 220-105-105 105
By circuit breaker type / max. rating (A) NS100-160-250N/100 NS160-250N/160690 V Isc max. kA rms 8 8
making capacity kA peak 14 14type / max. rating (A) NS100-160-250H/100 NS160-250H/160Isc max. kA rms 10 10making capacity kA peak 17 17type / max. rating (A) NS100-160-250L/100 NS160-250L/160Isc max. kA rms 75-20-20 20making capacity kA peak 165-40-40 40
By fuse type aM (1) max. rating (A) 100 160500 V Isc max. kA rms. 100 100
making capacity kA peak 220 220type gG (2) max. rating (A) 80 125Isc max. kA rms. 100 100making capacity kA peak 220 220type gG (1) max. rating (A) 100 160Isc max. kA rms. 100 100making capacity kA peak 220 220type BS (2) max. rating (A) 80 and 63M80 125 and 100M125Isc max. kA rms. 80 80making capacity kA peak 176 176type BS (1) max. rating (A) 250 and 200M250 250 and 200M250Isc max. kA rms. 80 80making capacity kA peak 176 176
Schneider Electric 107
INS250-200 INS250 INS320 INS400 INS500 INS630INV200 INV250 INV320 INV400 INV500 INV630NS250N/200 NS250N/250 NS400-630N/320 NS400-630N/400 NS630N/500 NS630N/63036 36 45 45 45 4575 75 94 94 94 94NS250H/200 NS250H/250 NS400-630H/320 NS400-630H/400 NS630H/500 NS630H/63050070 70 70 70 70 70154 154 154 154 154 154NS250L/200 NS250L/250 NS400-630L/320 NS400-630L/400 NS630L/500 NS630L/630150 150 150 150 150 150330 330 330 330 330 330NS250N/200 NS250N/250 NS400-630N/320 NS400-630N/400 NS630N/500 NS630N/63035 35 42 42 42 4273 73 88 88 88 88NS250H/200 NS250H/250 NS400-630H/320 NS400-630H/400 NS630H/500 NS630H/63065 65 65 65 65 65143 143 143 143 143 143NS250L/200 NS250L/250 NS400-630L/320 NS400-630L/400 NS630L/500 NS630L/630130 130 130 130 130 130286 286 286 286 286 286NS250N/200 NS250N/250 NS400-630N/320 NS400-630N/400 NS630N/500 NS630N/63030 30 30 30 30 3063 63 63 63 63 63NS250H/200 NS250H/250 NS400-630H/320 NS400-630H/400 NS630H/500 NS630H/63050 50 50 50 50 50105 105 105 105 105 105NS250L/200 NS250L/250 NS400-630L/320 NS400-630L/400 NS630L/500 NS630L/63070 70 100-70 100-70 70 70154 154 220-154 220-154 154 154NS250N/200 NS250N/250 NS400-630N/320 NS400-630N/400 NS630N/500 NS630N/63022 22 22 22 22 2246 46 46 46 46 46NS250H/200 NS250H/250 NS400-630H/320 NS400-630H/400 NS630H/500 NS630H/63035 35 35 35 35 3573 73 73 73 73 73NS250L/200 NS250L/250 NS400-630L/320 NS400-630L/400 NS630L/500 NS630L/63050 50 100-50 100-50 50 50105 105 220-105 220-105 105 105NS250N/200 NS250N/250 NS400-630N/320 NS400-630N/400 NS630N/500 NS630N/6308 8 10 10 10 1014 14 17 17 17 17NS250H/200 NS250H/250 NS400-630H/320 NS400-630H/400 NS630H/500 NS630H/63010 10 20 20 20 2017 17 40 40 42 42NS250L/200 NS250L/250 NS400-630L/320 NS400-630L/400 NS630L/500 NS630L/63020 20 75-35 75-35 35 3540 40 165-73 165-73 73 73200 250 320 400 500 500100 100 100 100 100 100220 220 220 220 220 220160 160 250 315 400 500100 100 100 100 100 100220 220 220 220 220 220200 200 320 400 500 630100 100 100 100 100 100220 220 220 220 220 220160 and 100M160 200 and 100M200 250 and 200M250 315 and 200M315 400 50080 80 80 80 80 80176 176 176 176 176 176250 and 200M250 250 and 200M250 355 and 315M355 355 and 315M355 450 and 400M450 450 and 400M45080 80 80 80 80 80176 176 176 176 176 176
Protectionof switch-disconnectors (cont.)
INS/INV100 to 630 by Compact NScircuit breaker or fuse
Additional characteristics
Schneider Electric108
(*) Applicable for 480 V NEMA.(1) Mandatory protection by an external thermal relay.(2) No external thermal protection.
Protectionof switch-disconnectors (cont.)
INS/INV630b to 2500 by Compact NScircuit breaker or fuse
Additional characteristics
E88
712
Interpact INS/INV switch-disconnectorsUpstream protectionBy circuit breaker Compact NSBy circuit breaker type / max. rating (A)380/415 V Isc max. kA rms.
making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peak
By circuit breaker type / max. rating (A)440/480 V (*) Isc max. kA rms.
making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peak
By circuit breaker type / max. rating (A)500 V/525 V Isc max. kA rms.
making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peak
By circuit breaker type / max. rating (A)690 V Isc max. kA rms.
making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peak
By fuseBy fuse Type aM (1) / max. rating (A)500V Isc max. kA rms.
making capacity kA peakType gG (2) / max. rating (A)Isc max. kA rms.making capacity kA peakType gG (1) / max. rating (A)Isc max. kA rms.making capacity kA peakType BS (2) / max. rating (A)Isc max. kA rms.making capacity kA peakType BS (1) / max. rating (A)Isc max. kA rms.making capacity kA peak
Schneider Electric 109
INS/INV630b INS/INV800 INS/INV1000 INS/INV1250 INS/INV1600 INS/INV2000 INS/INV2500
NS630bN/630 NS800N/800 NS1000N/1000 NS1250N/1250 NS1600N - NS1600bN/1600 NS2000N/2000 NS2500N/250050 50 50 50 50 50 50105 105 105 105 105 105 105NS630bH/630 NS800H/800 NS1000H/1000 NS1250H/1250 NS1600H - NS1600bH/1600 NS2000H/2000 NS2500H/250050 50 50 50 50 50 50105 105 105 105 105 105 105NS630bL/630 NS800L/800 NS1000L/1000 – – – –150 150 150 – – – –330 330 330 – – – –NS630bN/630 NS800N/800 NS1000N/1000 NS1250N/1250 NS1600N - NS1600bN/1600 NS2000N/2000 NS2500N/250050 50 50 50 50 50 50105 105 105 105 105 105 105NS630bH/630 NS800H/800 NS1000H/1000 NS1250H/1250 NS1600H - NS1600bH/1600 NS2000H/2000 NS2500H/250050 50 50 50 50 50 50105 105 105 105 105 105 105NS630bL/630 NS800L/800 NS1000L/1000 – – – –130 130 130 – – – –286 286 286 – – – –NS630bN/630 NS800N/800 NS1000N/1000 NS1250N/1250 NS1600N - NS1600bN/1600 NS2000N/2000 NS2500N/250040 40 40 40 40 50 5084 84 84 84 84 105 105NS630bH/630 NS800H/800 NS1000H/1000 NS1250H/1250 NS1600H - NS1600bH/1600 NS2000H/2000 NS2500H/250050 50 50 50 50 50 50105 105 105 105 105 105 105NS630bL/630 NS800L/800 NS1000L/1000 – – – –100 100 100 – – – –220 220 220 – – – –NS630bN/630 NS800N/800 NS1000N/1000 NS1250N/1250 NS1600bN/1600 NS2000N/2000 NS2500N/250030 30 30 30 30 50 5063 63 63 63 63 105 105NS630bH/630 NS800H/800 NS1000H/1000 NS1250H/1250 NS1600bH/1600 NS2000H/2000 NS2500H/250042 42 42 42 42 50 5088 88 88 88 88 105 105NS630bL/630 NS800L/800 NS1000L/1000 – – – –25 25 25 – – – –53 53 53 – – – –
630 800 1000 1250 1250 – –100 100 100 100 100 – –220 220 220 220 220 – –630 630 800 1000 1250 – –100 100 100 100 100 – –220 220 220 220 220 –1250 1250 1250 1250 1250 – –100 100 100 100 100 – –220 220 220 220 220 – –630 630 800 1000 1250 – –80 80 80 80 80 – –176 176 176 176 176 – –1250 1250 1250 1250 1250 – –80 80 80 80 80 – –176 176 176 176 176 – –
Protectionof switch-disconnectors (cont.)
INS/INV630b to 2500 by Compact NScircuit breaker or fuse (cont.)
Additional characteristics
Schneider Electric110
Protectionof switch-disconnectors (cont.)
INS/INV630b to 2500 by Masterpactcircuit breakers NT and NW
Additional characteristics
Opush OFF
Ipush ON
O OFF
discharged
E88
713
Interpact INS/INV switch-disconnectors Upstream protection By Masterpact circuit breaker NT H1By circuit breaker type / max. rating (A)220/690 V Isc max. kA rms.
making capacity kA peak
By Masterpact circuit breaker NT L1By circuit breaker type / max. rating (A)220/525 V Isc max. kA rms.
making capacity kA peakBy circuit breaker type / max. rating (A)690 V Isc max. kA rms.
making capacity kA peak
By Masterpact circuit breaker NW N1-H1-H2-H3By circuit breaker type / max. rating (A)220/440-480 V (*) Isc max. kA rms.
making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peak
By circuit breaker type / max. rating (A)500 V/525 V Isc max. kA rms.
making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peak
By circuit breaker type / max. rating (A)690 V Isc max. kA rms.
making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peaktype / max. rating (A)Isc max. kA rms.making capacity kA peak
By Masterpact circuit breaker NW L1By circuit breaker type / max. rating (A)220/690 V Isc max. kA rms. DIN OFF / DIN ON
making capacity kA peak DIN OFF / DIN ON
(*) Applicable for 480 V NEMA.
Schneider Electric 111
INS/INV630b INS/INV800 INS/INV1000 INS/INV1250 INS/INV 1600 INS/INV2000 INS/INV2500
NT08H1/630 NT08H1/800 NT10H1/1000 NT12H1/1000 NT16H1/1600 – –43 42 42 42 42 – –88 88 88 88 88 – –
NT08L1/630 NT08L1/800 NT10L1/1000 NT12L1/1250 NT16L1/1600 – –100 100 100 100 100 – –220 220 220 220 220 – –NT08L1/630 NT08L1/800 NT10L1/1000 NT12L1/1250 NT16L1/1600 – –25 25 25 25 25 – –53 53 53 53 53 – –
NW08/N1/630 NW08/N1/800 NW10N1/1000 NW12N1/1250 NW16N1/1600 – –42 42 42 42 42 – –88 88 88 88 88 – –NW08H1/630 NW08H1/800 NW10H1/1000 NW12H1/1250 NW16H1/1600 NW20H1/2000 NW25H1/250050 50 50 50 50 50 50105 105 105 105 105 105 105NW08H2/630 NW08H2/800 NW10H2/1000 NW12H2/1250 NW16H2/1600 NW20H2/2000 NW25H2/250050 50 50 50 50 50 50105 105 105 105 105 105 105– – – – – NW20H3/2000 NW25H3/2500– – – – – 50 50– – – – – 105 105NW08/N1/630 NW08/N1/800 NW10N1/1000 NW12N1/1250 NW16N1/1600 – –42 42 42 42 42 – –88 88 88 88 88 – –NW08H1/630 NW08H1/800 NW10H1/1000 NW12H1/1250 NW16H1/1600 NW20H1/2000 NW25H1/250050 50 50 50 50 50 50105 105 105 105 105 105 105NW08H2/630 NW08H2/800 NW10H2/1000 NW12H2/1250 NW16H2/1600 NW20H2/2000 NW25H2/250050 50 50 50 50 50 50105 105 105 105 105 105 105– – – – – NW20H3/2000 NW25H3/2500– – – – – 50 50– – – – – 105 105NW08/N1/630 NW08/N1/800 NW10N1/1000 NW12N1/1250 NW16N1/1600 – –50 50 50 50 50 – –105 105 105 105 105 – –NW08H1/630 NW08H1/800 NW10H1/1000 NW12H1/1250 NW16H1/1600 NW20H1/2000 NW25H1/250050 50 50 50 50 50 50105 105 105 105 105 105 105NW08H2/630 NW08H2/800 NW10H2/1000 NW12H2/1250 NW16H2/1600 NW20H2/2000 NW25H2/250050 50 50 50 50 50 50105 105 105 105 105 105 105– – – – – NW20H3/2000 NW25H3/2500– – – – – 50 50– – – – – 105 105
NW08L1/630 NW08L1/800 NW10L1/1000 NW12L1/1250 NW16L1/1600 NW20L1/2000 –50 50 50 50 50 50 –105 105 105 105 105 105 –
Protectionof switch-disconnectors (cont.)
INS/INV630b to 2500 by Masterpactcircuit breakers NT and NW (cont.)
Additional characteristics
Schneider Electric112
Schneider Electric 113
Presentation 2Functions and characteristics 17Installation recommandations 63Dimensions and connection 85Additional characteristics 103
INS40 to 160 114Complete fixed/FC device and accessories 114Accessories 115
INS250-100 to 630 117Complete fixed/FC device and accessories 117
INV100 to 630 118Complete fixed/FC device and specific accessories 118
INS250-100 to 250 and INV100 to 250 119Accessories 119
INS320 to 630 and INV320 to 630 122Accessories 122
INS630b to 2500 124Complete fixed/FC device and accessories 124
INV630b to 2500 125Complete fixed/FC device and specific accessories 125
INS630b to 2500 and INV630b to 2500 126Accessories 126
Catalogue numbers
308E6010.fm/114 Schneider Electric2 août 2002 10:15
Catalogue numbers INS40 to 160 Complete fixed/FC device and accessories
Interpact INS40 to 160 standard version with black handle
E33
365
3P 4PInterpact INS40 28900 28901Interpact INS63 28902 28903Interpact INS80 28904 28905
E33
366
3P 4PInterpact INS100 28908 28909Interpact INS125 28910 28911Interpact INS160 28912 28913
Interpact INS40 to 160 with red handle and yellow front
E33
365
3P 4PInterpact INS40 28916 28917Interpact INS63 28918 28919Interpact INS80 28920 28921
E33
366
3P 4PInterpact INS100 28924 28925Interpact INS125 28926 28927Interpact INS160 28928 28929
Individual enclosuresIP55 heavy-duty sheetmetal enclosure
E90
492
For INS40 to INS160 with extended standard rotary handle 31208For INS40 to INS160 with extended red handle on yellow front 31209
IP55 heavy-duty insulating enclosure
E32
419
For INS40 to INS160 with extended standard rotary handle 28967For INS40 to INS160 with extended red handle on yellow front 28968
Connection accessoriesDistribloc distribution block (for bare cables)
E33
404
INS40 to 125 125 A, 12 outgoing spring terminals (7 x 4 mm2 + 3 x 6 mm2 (2)
+ 2 x 10 mm2) + 1 outgoing tunnel terminal (25 mm2)07105
INS100 to 160 160 A, 12 outgoing spring terminals (7 x 4 mm2 + 3 x 6 mm2 (2)
+ 2 x 10 mm2) + 1 outgoing tunnel terminal (25 mm2) with prefabricated connections
07106
Multi-stage distribution block (for bare cables)
E26
801
INS40 to 125 125 A, 4 x 10 holes (5 x 10 mm2 + 4 x 16 mm2 + 1 x 35 mm2) (2) 13512INS40 to 125 125 A, 4 x 17 holes (8 x 10 mm2 + 8 x 16 mm2 + 1 x 35 mm2) (2) 13514
Connectors for bare Cu or Al cables
E32
424
Snap-on INS100 to 160 S < 95 mm2 Set of 3 28947Set of 4 28948
E39
432
Distribution connector for3 rigid cables up to 16 mm2 or 3 flexible cables up to 10 mm2
INS40 to 80 Set of 3 19096 Set of 4 19091
E30
707
Distribution connector for4 rigid cables up to 25 mm2 or 4 flexible cables up to 16 mm2
INS100 to 160 Set of 3 28949Set of 4 28950
(2) Product sold by MGA
.1 .2.4
.1 .2.4
N
308E6010.fm/115Schneider Electric 2 août 2002 10:15
Catalogue numbers INS40 to 160 (cont.)
Accessories
Connection accessories (cont.)Crimp lugs for copper cables
E27
797
For 95 mm2 cables with interphase barriers
INS100 to 160 Set of 3 28951Set of 4 28952
Terminal shrouds
E24
075
INS40 to 80 3P/4P Set of 2 28955INS100 to 160 3P/4P Set of 2 28956
Terminal shields
E32
457
INS40 to 80 3P/4P Set of 2 28957INS100 to 160 3P/4P Set of 2 28958
Interphase barriers
E88
893
INS100 to 160 3P/4P Set of 6 28959
Special connection accessories for INS100DC
E94
166
Terminal extensions for series or parallel connection of two poles (1) 1 terminal ext. 29498(1) Series connection of: 2 poles = 1 terminal extension
3 poles = 2 terminal extensions4 poles = 3 terminal extensions
Parallel connection of: 2 poles = 2 terminal extensions3 poles = set of 2 terminal extensions (29499)4 poles = 4 terminal extensions
E94
206
Terminal extensions for parallel connection of three poles Set of 2 terminal extensions
29499
4P terminal shields for series connection of poles Set of 1 294964P terminal shields for parallel connection of poles (2P/4P) Set of 1 29497
Electrical auxiliaries Auxiliary contacts
E18
608
1 OF / CAF / CAO (standard) INS40 to 160 294501 OF / CAF / CAO (low level) INS40 to 160 29452
Rotary handlesAccessories for conversion to extended rotary handles
E33
405
Front control Black handle INS40 to 160 28941Red handle on yellow front
INS40 to 160 28942
Lateral control Black handle INS40 to 160 28943
E51
011
Red handle on yellow front (1) INS40 to 160 28944Lateral control on G, GX or PRAGMA F functional enclosure
Black handle INS40 to 160 28945
Red handle on yellow front (1) INS40 to 160 28946
308E6010.fm/116 Schneider Electric2 août 2002 10:15
Catalogue numbers INS40 to 160 (cont.)
Accessories (cont.)
Locking and interlockingHandle locking
E32
426
By 1 to 3 padlocks (OFF position), hasp dia. 5 to 8 mm, or by lead seals Built-in
Interlocking for extended rotary handles
E89
637
Mechanical 28953
Spare parts
E32
411
Black handle 28962Red handle (1) 28963
(1) For red/yellow switch versions only.
N
.1 .2.4
55 88ØØ
¿5...8
N
.1 .2
.4
or
308E6010.fm/117Schneider Electric 2 août 2002 10:15
Catalogue numbers INS250-100 to 630 Complete fixed/FC device and accessories
Interpact INS250 to 630 standard version with black handle
E50
995
3P 4PInterpact INS250-100A 31100 31101Interpact INS250-160A 31104 31105Interpact INS250-200A 31102 31103Interpact INS250 31106 31107
E50
996
3P 4PInterpact INS320 31108 31109Interpact INS400 31110 31111Interpact INS500 31112 31113Interpact INS630 31114 31115
Interpact INS250 to 630 with red handle and yellow front
E50
995
3P 4PInterpact INS250-100A 31120 31121Interpact INS250-160A 31124 31125Interpact INS250-200A 31122 31123Interpact INS250 31126 31127
E50
996
3P 4PInterpact INS320 31128 31129Interpact INS400 31130 31131Interpact INS500 31132 31133Interpact INS630 31134 31135
Source changeover systemsComplete assembly
E89
638
3P 4PWith Interpact INS250-100A 31140 31141With Interpact INS250-160A 31144 31145With Interpact INS250-200A 31142 31143With Interpact INS250 31146 31147With Interpact INS320 31148 31149With Interpact INS400 31150 31151With Interpact INS500 31152 31153With Interpact INS630 31154 31155
Downstream coupling accessories
E50
998
3P 4PFor Interpact INS250 29358 29359Long downstream 3P/4P terminal shields (set of 2) 29324For Interpact INS320 to 630 32619 32620 Long downstream 3P/4P terminal shields (set of 2) 32565
Individual enclosuresIP55 heavy-duty sheetmetal enclosure
E90
492
For INS250-100 to 250 with extended standard rotary handle 31210For INS250-100 to 250 with extended red rotary handle on yellow front 31211For INS320 to 630 with extended standard rotary handle 31212For INS320 to 630 with extended red rotary handle on yellow front 31213
IP55 heavy-duty insulating enclosure
E32
419
For INS250-100 to 250 with extended standard rotary handle 31204For INS250-100 to 250 with extended red rotary handle on yellow front 31205For INS320 to 630 with extended standard rotary handle 31206For INS320 to 630 with extended red rotary handle on yellow front 31207
N
308E6010.fm/118 Schneider Electric2 août 2002 10:15
Catalogue numbers INV100 to 630Complete fixed/FC device and specific accessories
Interpact INV100 to 630 standard version with black handle
E51
001
3P 4PInterpact INV100 31160 31161Interpact INV160 31164 31165Interpact INV200 31162 31163Interpact INV250 31166 31167
E51
002
3P 4PInterpact INV320 31168 31169Interpact INV400 31170 31171Interpact INV500 31172 31173Interpact INV630 31174 31175
Interpact INV100 to 630 with red handle and yellow front
E51
001
3P 4PInterpact INV100 31180 31181Interpact INV160 31184 31185Interpact INV200 31182 31183Interpact INV250 31186 31187
E51
002
3P 4PInterpact INV320 31188 31189Interpact INV400 31190 31191Interpact INV500 31192 31193Interpact INV630 31194 31195
Individual enclosuresIP55 heavy-duty insulating enclosure
E32
419
For INV100 to 250 with extended standard rotary handle 31204For INV100 to 250 with extended red rotary handle on yellow front 31205For INV320 to 630 with extended standard rotary handle 31206For INV320 to 630 with extended red rotary handle on yellow front 31207
Combination with Compact NS devices for "tarif jaune / tarif vert"
E89
642
INV100 to 250 combination with NS250 31066INV320 to 630 combination with NS250 31067Front alignment base for INV320 to 630 combination with NS250 31064INV320 to 630 combination with NS400/630 31068
E89
641
Flexible connection assembly for vertical INV100 to 250 with horizontal NS250 31069Flexible connection assembly for vertical INV320 to 630 with horizontal NS250 31092Flexible connection assembly for vertical INV100 to 250 with vertical NS250 beside 31071Flexible connection assembly for vertical INV320 to 630 with vertical NS400/630 beside 31072Flexible connection assembly for vertical INV320 to 630 with vertical NS250 beside 31093
N
¿5...8
308E6010.fm/119Schneider Electric 2 août 2002 10:15
Catalogue numbers INS250-100 to 250 and INV100 to 250Accessories
Connection accessoriesRear connections
E18
579
Short (1 pair) 29235Long (1 pair) 29236
Bare cable connectors
E18
572
Snap-on, for cables: 1.5 to 95 mm2 ; < 160 A Set of 3 29242Set of 4 29243
10 to 185 mm2 ; < 250 A Set of 3 29259Set of 4 29260
E18
598
Tab connector for voltage tap on 185 mm2bare cable connector Set of 2 29348Clip for bare cable connector Set of 10 29241Distribution connector for six 1.5 to 35 mm2 cables with interphase barriers
Set of 3 29248Set of 4 29249
Polybloc distribution block (for bare cables)
E24
076
160 A (40°C), for 6 cables up to < 10 mm2 (2) 07100250 A (40°C), for 6 cables up to < 10 mm2 (2) 07101* consult us
Terminal extensions (supplied with 2 or 3 interphase barriers)
E18
600 Right-angle terminal extensions Set of 3 29261
Set of 4 29262
E18
601 Straight terminal extensions Set of 3 29263
Set of 4 29264
Spreaders (for upstream or downstream connection)
E18
599
Separate for each pole 3P 315634P 31564
E51
006
One-piece 3/4P 31061Front alignment base for one-piece spreader
3/4P 31064
Crimp lugs for copper cables (supplied with 2 or 3 interphase barriers)
E18
602
For 120 mm2 cables Set of 3 29252Set of 4 29256
For 150 mm2 cables Set of 3 29253Set of 4 29257
For cable 185 mm2 cables Set of 3 29254Set of 4 29258
Crimp lugs for aluminium cables (supplied with 2 or 3 interphase barriers)
E30
908
For 150 mm2 cables Set of 3 29504Set of 4 29505
For 185 mm2 cables Set of 3 29506Set of 4 29507
Terminal shields
E51
007
Short 3/4 P Set of 2 29322Long 3/4 P Set of 2 29324
Interphase barriers
E18
606
Set of 6 29329
(2) Product sold by MGA
308E6010.fm/120 Schneider Electric2 août 2002 10:15
Catalogue numbers INS250-100 to 250 and INV100 to 250 (cont.) Accessories (cont.)
Special connection accessories for INS100DC
E94
166
Terminal extensions for series or parallel connection of two poles (1) 1 terminal ext. 29498(1) Series connection of: 2 poles = 1 terminal extension
3 poles = 2 terminal extensions4 poles = 3 terminal extensions
Parallel connection of: 2 poles = 2 terminal extensions3 poles = set of 2 terminal extensions (29499)4 poles = 4 terminal extensions
E94
206
Terminal extensions for parallel connection of three poles Set of 2 terminal extensions
29499
4P terminal shields for series connection of poles Set of 1 294964P terminal shields for parallel connection of poles (2P/4P) Set of 1 29497
Electrical auxiliariesAuxiliary contacts (changeover type)
E18
608
OF or CAM (early make or break) 29450Low level OF or CAM (early make or break) 29452
Indication and measurement modulesAmmeter module (4P)
E51
008
Adaptation kit (necessary for devices with direct front handles) 31081Rating (A) 100 29456
150 30556250 31566
Current transformer module (4P)
E51
009
Rating (A) 100 29458150 30558250 31568
Rotary handlesExtended front control
E33
405
For INS250 with standard rotary handle 31050For INS250 with red handle on yellow front (1) 31051For complete source changeover assembly 31055
Lateral control
E89
607
Direct lateral control for INS and INV250Lateral support 31054+ standard lateral control assembly 31057or + red and yellow lateral control assembly (1) 31058Extended lateral control for INS and INV250
Standard lateral control assembly 31057Red and yellow lateral control assembly (1) 31058
Locking and interlocking for INS/INV and source changeover systemsLocking for INS/INV
E51
012
Handle locking by 1 to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31087
+ Ronis 1351B.500 keylock 41940or + Profalux KS5 B24 D4Z keylock 42888
Locking for INS complete source changeover assembly
E42
629
Handle locking by 1 to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31097
+ Ronis 1351B.500 keylock 41940or + Profalux KS5 B24 D4Z keylock 42888
Interlocking for INS/INV with direct or extended rotary handle
E50
997
Mechanical interlocking for INS250 31073By keylock Keylocking device 2x 31087
+ Ronis 1351B.500 keylock (2 keylocks / 1 key) 41950or + Profalux KS5 B24 D4Z keylock (1 keylocks / 1 key) 42878
(1) For red/yellow switch versions only.
A16
12
8
4
160/5
0
flfl
flfl
¿5...8
¿5...8
¿5...8
308E6010.fm/121Schneider Electric 2 août 2002 10:15
Catalogue numbers INS250-100 to 250 and INV100 to 250 (cont.) Accessories (cont.)
Installation accessoriesFront panel escutcheons
E18
591
For INS/INV 31079For ammeter module, IP40 29318
Lead seal accessories29375
Spare parts12 snap-in nuts for fixed/FC(M8) 30554100 identification labels 29314Bag of screws 29312Black handle 31082Red handle (1) 31083Viewport for INV100/160/250 31089
(1) For red/yellow switch versions only.
308E6010.fm/122 Schneider Electric2 août 2002 10:15
Catalogue numbers INS320 to 630 and INV320 to 630 Accessories
Connection accessoriesRear connections
E18
579
Short (1 pair) 32475Long (1 pair) 32476
Bare cable connectors
E22
040 For 1 cable, 35 mm2 to 300 mm2 Set of 3 32479
Set of 4 32480
E22
041 For 2 cables, 35 mm2 to 240 mm2 Set of 3 32481
Set of 4 32482Tab connector for voltage tap on bare cable connector Set of 2 29348
Terminal extensions (supplied with 2 or 3 interphase barriers)
E18
600 Right-angle terminal extensions Set of 3 32484
Set of 4 32485
E21
276
Edgewise terminal extensions Set of 3 32486Set of 4 32487
Spreaders (for upstream or downstream connection)
E18
599
One-piece 52.5 mm 3P 324904P 32491
70 mm 3P 324924P 32493
Crimp lugs for copper cables (supplied with 2 or 3 interphase barriers)
E18
602
For 240 mm2 cables Set of 3 32500Set of 4 32501
For 300 mm2 cables Set of 3 32502Set of 4 32503
Crimp lugs for aluminium cables (supplied with 2 or 3 interphase barriers)
E30
908
For 240 mm2 cables Set of 3 32504Set of 4 32505
For 300 mm2 cables Set of 3 32506Set of 4 32507
Terminal shields
E51
007
Short 3/4P Set of 2 32563Long 3/4P Set of 2 32565Long for 52.5 mm spreader (supplied with insulating plate) 3/4P Set of 2 32583
Interphase barriers
E89
622
Set of 6 32570
Special connection accessories for INS320 to 630DC
E94
207
Terminal extensions for series or parallel connection of two poles (1) 1 terminal ext. 32868(1) Series connection of: 2 poles = 1 terminal extension
3 poles = 2 terminal extensions4 poles = 3 terminal extensions
Parallel connection of: 2 poles = 2 terminal extensions4 poles = 4 terminal extensions
4P terminal shields for series connection of poles Set of 1 328664P terminal shields for parallel connection of poles Set of 1 32867
308E6010.fm/123Schneider Electric 2 août 2002 10:15
Catalogue numbers INS320 to 630 and INV320 to 630 (cont.)
Accessories (cont.)
Electrical auxiliariesAuxiliary contacts (changeover type)
E18
608
OF or CAM (early make or break) 29450OF or CAM low level (early make or break) 29452
Indication and measurement modulesAmmeter module (4P)
E51
008
Rating (A) 400 32656600 32856
Current transformer module (4P)
E51
009
Rating (A) 400 32658600 32858
Rotary handlesExtended front control
E89
617
For INS320/400/630 with standard rotary handle 31052For INS320/400/630 with red handle on yellow front (1) 31053For complete source changeover assembly 31055
Locking and interlocking for INS/INV and source changeover systemsLocking for INS/INV
E89
618
Handle locking by 1 to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31088
+ Ronis 1351B.500 keylock 41940or + Profalux KS5 B24 D4Z keylock 42888
Locking for INS complete source changeover assembly
E42
629
Handle locking by 1 to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31097
+ Ronis 1351B.500 keylock 41940or + Profalux KS5 B24 D4Z keylock 42888
Interlocking for INS/INV with direct or extended rotary handle
E89
624
Mechanical interlocking for INS320/400/630 31074By keylock Keylocking device 2x 31088
+ Ronis 1351B.500 keylock (1 keylocks / 1 key) 41950or + Profalux KS5 B24 D4Z keylock (1 keylocks / 1 key) 42878
Installation accessoriesFront panel escutcheons
E18
591
For INS/INV 31080For ammeter module, IP40 29318
Lead seal accessories29375
Spare parts100 labels 29314Bag of screws 32552Black handle 31084Red handle (1) 31085Viewport for INV320/400/630 31090
(1) For red/yellow switch versions only.
A16
12
8
4
160/5
0
¿5...8
308E6010.fm/124 Schneider Electric2 août 2002 10:15
Catalogue numbers INS630b to 2500 Complete fixed/FC device and accessories
Interpact INS630b to 2500 standard version with black handle
E88
699
3P 4PInterpact INS630b 31342 31343Interpact INS800 31330 31331Interpact INS1000 31332 31333Interpact INS1250 31334 31335Interpact INS1600 31336 31337Interpact INS2000 31338 31339Interpact INS2500 31340 31341
E89
623
Interpact INS630b to 2500 with red handle and yellow front
E88
699
3P 4PInterpact INS630b 31356 31357Interpact INS800 31344 31345Interpact INS1000 31346 31347Interpact INS1250 31348 31349Interpact INS1600 31350 31351
308E6010.fm/125Schneider Electric 2 août 2002 10:15
Catalogue numbers INV630b to 2500Complete fixed/FC device and specific accessories
Interpact INV630b to 2500 standard version with black handle
E89
639
3P 4PInterpact INV630b 31370 31371Interpact INV800 31358 31359Interpact INV1000 31360 31361Interpact INV1250 31362 31363Interpact INV1600 31364 31365Interpact INV2000 31366 31367Interpact INV2500 31368 31369
E89
640
Interpact INV630b to 2500 with red handle and yellow front
E89
639
3P 4PInterpact INV630b 31387 31388Interpact INV800 31372 31373Interpact INV1000 31374 31375Interpact INV1250 31376 31377Interpact INV1600 31378 31379
Combination with Compact NS devices (for "tarif vert")
E89
619
3P 4PINV630b/1000/1250/1600 combination withNS800/1000/1250/1600
31385 31386
INV2000/2500 combination with NS2000/2500 31317 31318
308E6010.fm/126 Schneider Electric2 août 2002 10:15
Catalogue numbers INS630b to 2500 and INV630b to 2500Accessories
Connection accessoriesVertical connection adapters
E88
701
INS/INV630b/1600 3P Set of 3 313014P Set of 4 31302
Cable lug adapters
E88
702
INS/INV630b/1600 3P Set of 3 336444P Set of 4 33645
Spreaders
E88
703
INS/INV630b/1600 3P Set of 3 313054P Set of 4 31306
Insulation accessoriesBase for terminal shield (incompatible avec séparateur de phases)
E88
704
INS/INV630b/1600 3P 313074P 31308
Terminal shield (nécessite l’embase)
E88
705
INS/INV630b/1600 3P 336284P 33629
Interphase barriers (incompatible avec embase et cache-raccordement)
E89
625
INS/INV630b/1600 3P/4P Set of 6 31315INS/INV2000/2500 3P/4P Set of 6 31319
Electrical auxiliariesAuxiliary contacts (changeover type)
E18
608
OF or CAM (early make or break) 29450OF or CAM low level (early make or break) 29452
Extended front control
E88
708
INS630b/1600 For standard rotary handle 31286For red handle on yellow front (1) 31287
INS2000/2500 For standard rotary handle 31288
Locking and interlockingLocking for INS/INV630b to 1600
E89
620
Handle locking by 1 to 3 padlocks (in OFF position) Built-inBy keylock Keylocking device 31291
+ Ronis 1351B.500 keylock 41940or + Profalux KS5 B24 D4Z keylock 42888
Interlocking for INS/INV630b to 1600
E89
626
By keylock Keylocking device 2 x 31291+ Ronis 1351B.500 keylock (1 keylocks / 1 key) 41950or + Profalux KS5 B24 D4Z keylock (1 keylocks / 1 key) 42878
(1) For red/yellow switch versions only.
308E6010.fm/127Schneider Electric 2 août 2002 10:15
Catalogue numbers INS630b to 2500 and INV630b to 2500 (cont.)
Accessories (cont.)
Installation accessoriesEscutcheon
E88
707
INS630b/1600 3P/4P 31295
Lead seal accessories31316
Spare parts
E88
709
INS630b/1600 and INV630b Black handle 31296Red handle (1) 31297
INS2000/2500 and INV2000/2500 Black handle 31298
E88
700
Viewport for INV630b/2500 3P 312934P 31294
(1) For red/yellow switch versions only.
DBTP308E 07-2002
As standards, specifications and designs change from time to time, please ask for confirmationof the information given in this publication.
This document has been printedon ecological paper.