Modbus Register Mapping
Controller
PCC 1301PowerCommand 1.1PowerCommand 1.2PowerCommand 2.2PowerCommand 2.3PowerCommand 3.3
English 2−2010 A029X159 (Issue 3)
i
Table of ContentsSECTION TITLE PAGE
SAFETY PRECAUTIONS II. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. PCC 1301/POWERCOMMAND 1.X MODBUS REGISTER MAP 1. . . . . . . . . . . . . . . . . . . . .
2. POWERCOMMAND 2.X/3.X MODBUS REGISTER MAP 9. . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. POWERCOMMAND 2.X/3.X MODBUS FAULT STATUS BITMAPS 297. . . . . . . . . . . . . . . . . . .
4. NFPA 110 & EXTENDED ANNUNCIATION BITMAP 340. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii
Safety Precautions
SAVE THESE INSTRUCTIONS − This manual contains important instructions that should be followed duringinstallation and maintenance of the generator set and batteries.
Before operating the generator set (genset), read the Operator’s Manual and become familiar with it andthe equipment. Safe and efficient operation can be achieved only if the equipment is properly operatedand maintained. Many accidents are caused by failure to follow fundamental rules and precautions.
The following symbols, found throughout this manual, alert you to potentially dangerous conditions to the op-erator, service personnel, or the equipment.
DANGER This symbol warns of immediate hazards which will result in severe personal injury ordeath.
WARNING This symbol refers to a hazard or unsafe practice which can result in severe personal in-jury or death.
CAUTION This symbol refers to a hazard or unsafe practice which can result in personal injury orproduct or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result from improper practices.
• DO NOT fill fuel tanks while engine is running, unless tanks are outside the engine compartment. Fuelcontact with hot engine or exhaust is a potential fire hazard.
• DO NOT permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source near thegenerator set or fuel tank.
• Fuel lines must be adequately secured and free of leaks. Fuel connection at the engine should be madewith an approved flexible line. Do not use zinc coated or copper fuel lines with diesel fuel.
• Natural gas is lighter than air, and will tend to gather under hoods. Propane is heavier than air, and willtend to gather in sumps or low areas. NFPA code requires all persons handling propane to be trained andqualified.
• Be sure all fuel supplies have a positive shutoff valve.
• Be sure battery area has been well-ventilated prior to servicing near it. Lead-acid batteries emit a highlyexplosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
• Provide an adequate exhaust system to properly expel discharged gases away from enclosed or shel-tered areas and areas where individuals are likely to congregate. Visually and audibly inspect the exhaustfor leaks daily or per the maintenance schedule. Make sure that exhaust manifolds are secured and notwarped. Do not use exhaust gases to heat a compartment.
• The exhaust vent should be high enough to help clear gases, avoid accumulation of snow, and in accor-dance with local mechanical codes.
• Be sure the unit is well ventilated.
• Engine exhaust and some of its constituents are known to the state of California to cause cancer, birthdefects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
• Keep your hands, clothing, and jewelry away from moving parts.
iii
• Before starting work on the generator set, disconnect battery charger from its AC source, then disconnectstarting batteries, negative (−) cable first. In lean-burn natural gas (LBNG) gensets, also make sure thestarter’s air supply line is disconnected or completely vented until the generator set is ready to start. Thiswill prevent accidental starting.
• Make sure that fasteners on the generator set are secure. Tighten supports and clamps, keep guardsin position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity of moving parts, or while working on electrical equip-ment. Loose clothing and jewelry can become caught in moving parts.
• If adjustment must be made while the unit is running, use extreme caution around hot manifolds, movingparts, etc.
DO NOT OPERATE IN FLAMMABLE AND EXPLOSIVE ENVIRONMENTS
Flammable vapor can cause an engine to overspeed and become difficult to stop, resulting in possible fire,explosion, severe personal injury and death. Do not operate a genset where a flammable vapor environmentcan be created by fuel spill, leak, etc., unless the genset is equipped with an automatic safety device to blockthe air intake and stop the engine. The owners and operators of the genset are solely responsible for operatingthe genset safely. Contact your authorized Cummins Power Generation distributor for more information.
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
• Remove electric power before removing protective shields or touching electrical equipment. Use rubberinsulative mats placed on dry wood platforms over floors that are metal or concrete when around electricalequipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp whenhandling electrical equipment. Do not wear jewelry. Jewelry can short out electrical contacts and causeshock or burning.
• Use extreme caution when working on electrical components. High voltages can cause injury or death.DO NOT tamper with interlocks.
• Follow all applicable state and local electrical codes. Have all electrical installations performed by a quali-fied licensed electrician. Tag and lock open switches to avoid accidental closure.
• DO NOT CONNECT GENERATOR SET DIRECTLY TO ANY BUILDING ELECTRICAL SYSTEM. Haz-ardous voltages can flow from the generator set into the utility line. This creates a potential for electrocu-tion or property damage. Connect only through an approved isolation switch or an approved parallelingdevice.
MEDIUM VOLTAGE GENERATOR SETS (601V to 15kV)
• Medium voltage acts differently than low voltage. Special equipment and training is required to work onor around medium voltage equipment. Operation and maintenance must be done only by persons trainedand qualified to work on such devices. Improper use or procedures will result in severe personal injuryor death.
• Do not work on energized equipment. Unauthorized personnel must not be permitted near energizedequipment. Due to the nature of medium voltage electrical equipment, induced voltage remains even af-ter the equipment is disconnected from the power source. Plan the time for maintenance with authorizedpersonnel so that the equipment can be de-energized and safely grounded.
GENERAL SAFETY PRECAUTIONS
• Coolants under pressure have a higher boiling point than water. DO NOT open a radiator or heat ex-changer pressure cap while the engine is running. To prevent severe scalding, let engine cool down be-fore removing coolant pressure cap. Turn cap slowly, and do not open it fully until the pressure has beenrelieved.
• Used engine oils have been identified by some state or federal agencies as causing cancer or reproduc-tive toxicity. When checking or changing engine oil, take care not to ingest, breathe the fumes, or contactused oil.
iv
• Keep multi-class ABC fire extinguishers handy. Class A fires involve ordinary combustible materials suchas wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires,live electrical equipment. (ref. NFPA No. 10).
• Make sure that rags or combustible material are not left on or near the generator set.
• Make sure generator set is mounted in a manner to prevent combustible materials from accumulatingunder or near the unit.
• Remove all unnecessary grease and oil from the unit. Accumulated grease and oil can cause overheatingand engine damage which present a potential fire hazard.
• Keep the generator set and the surrounding area clean and free from obstructions. Remove any debrisfrom the set and keep the floor clean and dry.
• Do not work on this equipment when mentally or physically fatigued, or after consuming any alcohol ordrug that makes the operation of equipment unsafe.
• Substances in exhaust gases have been identified by some state or federal agencies as causing canceror reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
• Do not store any flammable liquids, such as fuel, cleaners, oil, etc., near the generator set. A fire or explo-sion could result.
• Wear hearing protection when near an operating generator set.
• To prevent serious burns, avoid contact with hot metal parts such as radiator system, turbo charger sys-tem and exhaust system.
DISPOSE OF THIS UNIT PROPERLY
v
THIS PAGE LEFT INTENTIONALLY BLANK
1
1. PCC 1301/PowerCommand 1.x Modbus Register MapThe genset controller contains data that can be readby a remote device communicating via ModbusRTU protocol on a two−wire RS485 master/slavemulti−drop bus. In this arrangement the remote de-vice is the master and the genset controller is theslave.
For more information about the Modbus protocol,refer to Modbus Application Protocol v1.1a and
Modbus Serial Line Implementation Guide v1.0,both available at www.modbus.org.
Multi−Drop Network Mode Pins:
• Hi (+) TB2-3
• Lo (−) TB2-4
• Shield TB2-1
Note: If an address or bit is not listed in this table it isnot used.
Addr. Description Read / Write Scale Units Type Notes
40004 Save adjustments Read andWrite
− − Unsignedinteger
0=No action1=Save adjustmentsSave adjustments saves tonon volatile memory all thewrite parameters listed inthis table
40010 Genset control run/off/auto switch position
Read − Switchposition
Unsignedinteger
0=off1=Run/Manual2=Auto
40011 Genset operatingstate
Read − Operatingstate
Unsignedinteger
0=Stopped1=Start Pending2=Warm−up at Idle3=Running4=Cool down at Rated5=Cool down at Idle
40012 Fault Code Read − Event code Unsignedinteger
This register contains thefault code number of current-ly active fault. See servicemanual for list of supportedfault codes.
40013 Fault Type Read − Fault type Unsignedinteger
This register contains thefault type of currently activefault 0=Normal1=Warning2=Derate3=Shutdown with Cool down4=Shutdown
40016 NFPA 110 fault regis-ter
Read − bitmap See section 4.
40017 Extended Annunci-ation fault register
Read − bitmap See section 4.
40018 Alternator output volt-age line to neutral (a
phase)
Read 1.0 AC Volts Unsignedinteger
40019 Alternator output volt-age line to neutral (b
phase)
Read 1.0 AC Volts Unsignedinteger
2
Addr. NotesTypeUnitsScaleRead / WriteDescription40020 Alternator output volt-
age line to neutral (cphase)
Read 1.0 AC Volts Unsignedinteger
40022 Alternator output volt-age line to line (a to b
phase)
Read 1.0 AC Volts Unsignedinteger
40023 Alternator output volt-age line to line (b to c
phase)
Read 1.0 AC Volts Unsignedinteger
40024 Alternator output volt-age line to line (c to a
phase)
Read 1.0 AC Volts Unsignedinteger
40025 Alternator output vol-tage (used for voltage
regulation)
Read 1.0 AC Volts Unsignedinteger
40026 Alternator output cur-rent (phase a)
Read 0.1 AC Amps Unsignedinteger
40027 Alternator output cur-rent (phase b)
Read 0.1 AC Amps Unsignedinteger
40028 Alternator output cur-rent (phase c)
Read 0.1 AC Amps Unsignedinteger
40029 Alternator output aver-age current
Read 0.1 AC Amps Unsignedinteger
40040 Alternator output volt−amperes (phase a)
Read 0.1 kVA Unsignedinteger
40041 Alternator output volt−amperes (phase b)
Read 0.1 kVA Unsignedinteger
40042 Alternator output volt−amperes (phase c)
Read 0.1 kVA Unsignedinteger
40043 Alternator output volt−amperes (total)
Read 0.1 kVA Unsignedinteger
40044 Alternator frequency Read 0.1 Hz Unsignedinteger
40058 Alternator output cur-rent (phase a)
Read 0.1 % of nominal Unsignedinteger
40059 Alternator output cur-rent (phase a)
Read 0.1 % of nominal Unsignedinteger
40060 Alternator output cur-rent (phase c)
Read 0.1 % of nominal Unsignedinteger
40061 Control battery volt-age
Read 0.1 DC Volts Unsignedinteger
40062 Engine oil pressure Read 1.0 kPa Unsignedinteger
40064 Engine coolant tem-perature
Read 0.1 Degrees Cel-sius
Unsignedinteger
40068 Engine speed Read 0.1 RPM Unsignedinteger
40069 Number of enginestarts
Read 1.0 Number ofstarts
Unsignedinteger
40070 Engine runtime (highbyte)
Read 1.0 Sec Unsignedinteger
3
Addr. NotesTypeUnitsScaleRead / WriteDescription40071 Engine Runtime (Low
byte)Read 1.0 Sec Unsigned
integer
40300 Genset start stop con-trol via Modbus
Read andWrite
Unsignedinteger
0 − Stop1− Start
40302 Genset E−stop switchvia Modbus
Read andWrite
Unsignedinteger
0 − Estop not active1 − Estop active
43000 Nominal alternatorvoltage setting
Read andWrite
1.0 AC Volts Unsignedinteger
43001 Nominal alternator fre-quency setting
Read andWrite
Hz Unsignedinteger
0 = 601 = 50
43002 Alternator phase set-ting
Read andWrite
# of phases Unsignedinteger
0 = 11 =3
43003 Alternator connectionsetting
Read andWrite
Alternator Unsignedinteger
1=Wye
43004 Glow plug driver fea-ture enable
Read andWrite
Feature en-abled
Unsignedinteger
0 = No1 = Yes
43005 Battery charging alter-nator fault enable
Read andWrite
Feature en-abled
Unsignedinteger
0 = No1 = Yes
43006 Remote start timedelay
Read andWrite
1.0 Sec Unsignedinteger
43007 Remote stop timedelay
Read andWrite
1.0 Sec Unsignedinteger
43008 Engine starting −cycle crank attempts
setting
Read andWrite
1.0 Number of at-tempts
Unsignedinteger
43009 Engine starting −cycle crank time set-ting
Read andWrite
1.0 Sec Unsignedinteger
43010 Engine starting −cycle crank rest time
setting
Read andWrite
1.0 Sec Unsignedinteger
43011 Fault bypass (battleshort) feature enable
Read andWrite
Feature en-abled
Unsignedinteger
0 =Inactive1 = Active
43012 Fault bypass (battleshort) switch input as-
signment
Read andWrite
Switch as-signment
Unsignedinteger
0= None1=Customer Input 12=Customer Input 23=Operator Panel
43013 Automatic voltageregulator Enable
Read andWrite
Feature en-abled
Unsignedinteger
0 = No1 = Yes
43014 Automatic voltageregulator volts per
hertz roll off knee set-ting
Read andWrite
0.1 Hz Unsignedinteger
43015 Automatic voltageregulator volts perhertz roll off slope
setting
Read andWrite
0.1 %V/Hz Unsignedinteger
43016 Automatic voltageregulator gain setting
Read andWrite
1.0 % Unsignedinteger
4
Addr. NotesTypeUnitsScaleRead / WriteDescription43017 Automatic voltage
regulator integral set-ting
Read andWrite
1.0 1.0 Unsignedinteger
43018 Automatic voltageregulator derivative
setting
Read andWrite
1.0 1.0 Unsignedinteger
43019 Electronic governingenable
Read andWrite
1.0 1.0 Unsignedinteger
0 = No1 = Yes
43020 Electronic governinginitial duty cycle set-
ting
Read andWrite
0.1 1.0 Unsignedinteger
43021 Electronic governinginitial duty cycle time
Read andWrite
0.1 Sec Unsignedinteger
43022 Electronic governingstart ramp duty cycle
setting
Read andWrite
0.1 % Unsignedinteger
43023 Electronic governingmaximum duty cycle
setting
Read andWrite
0.1 % Unsignedinteger
43024 Electronic governinggain setting
Read andWrite
1.0 % Unsignedinteger
43025 Electronic governingintegral setting
Read andWrite
1.0 % Unsignedinteger
43026 Electronic governingderivative setting
Read andWrite
1.0 % Unsignedinteger
43027 Electronic governingcrank exit fuel duty
cycle setting
Read andWrite
0.1 % Unsignedinteger
43028 Electronic governingdither factor setting
Read andWrite
1.0 % Unsignedinteger
43029 Electronic governingstart ramp time setting
Read andWrite
0.01 Sec Unsignedinteger
43030 Electronic governingenable engine speed
Read andWrite
1.0 RPM Unsignedinteger
43031 Electronic governingminimum duty cycle
setting
Read andWrite
1.0 % Unsignedinteger
43032 Electronic governingmaximum duty cycle
setting
Read andWrite
1.0 % Unsignedinteger
43033 Model number char-acter #1
Read andWrite
Character
43034 Model number char-acter #2
Read andWrite
Character
43035 Model number char-acter #3
Read andWrite
Character
43036 Model number char-acter #4
Read andWrite
Character
43037 Model number char-acter #5
Read andWrite
Character
5
Addr. NotesTypeUnitsScaleRead / WriteDescription43038 Model number char-
acter #6Read and
WriteCharacter
43039 Model number char-acter #7
Read andWrite
Character
43040 Model number char-acter #8
Read andWrite
Character
43041 Model number char-acter #9
Read andWrite
Character
43042 Model number char-acter #10
Read andWrite
Character
43043 Model number char-acter #11
Read andWrite
Character
43044 Model number char-acter #12
Read andWrite
Character
43045 Model number char-acter #13
Read andWrite
Character
43046 Model number char-acter #14
Read andWrite
Character
43047 Model number char-acter #15
Read andWrite
Character
43048 Model number char-acter #16
Read andWrite
Character
43049 Serial number charac-ter #1
Read andWrite
Character
43050 Serial number charac-ter #2
Read andWrite
Character
43051 Serial number charac-ter #3
Read andWrite
Character
43052 Serial number charac-ter #4
Read andWrite
Character
43053 Serial number charac-ter #5
Read andWrite
Character
43054 Serial number charac-ter #6
Read andWrite
Character
43055 Serial number charac-ter #7
Read andWrite
Character
43056 Serial number charac-ter #8
Read andWrite
Character
43057 Serial number charac-ter #9
Read andWrite
Character
43058 Serial number charac-ter #10
Read andWrite
Character
43059 Serial number charac-ter #11
Read andWrite
Character
43060 Serial number charac-ter #12
Read andWrite
Character
43061 Serial number charac-ter #13
Read andWrite
Character
43062 Serial number charac-ter #14
Read andWrite
Character
6
Addr. NotesTypeUnitsScaleRead / WriteDescription43063 Serial number charac-
ter #15Read and
WriteCharacter
43064 Serial number charac-ter #16
Read andWrite
Character
43065 Configurable input #1type
Read andWrite
Input type Unsignedinteger
0 = Event1 = Warning2 = Shutdown
43066 Configurable input #2type
Read andWrite
Input type Unsignedinteger
0 = Event1 = Warning2 = Shutdown
43067 Configurable output#1 event code number
Read andWrite
1.0 Event code Unsignedinteger
43068 Configurable output#2 fault event number
Read andWrite
1.0 Event code Unsignedinteger
43069 60 Hz alternator out-put voltage adjust %
Read andWrite
1.0 % Unsignedinteger
43070 50 Hz alternator out-put voltage adjust %
Read andWrite
0.1 % Unsignedinteger
43071 Alternator frequencyadjustment %
Read andWrite
0.1 0.1 Unsignedinteger
43072 60 Hz line 1 to neutralmetering voltage cal-
ibration
Read andWrite
0.0001 % Unsignedinteger
43073 60 Hz line 2 to neutralmetering voltage cal-
ibration
Read andWrite
0.0001 % Unsignedinteger
43075 50 Hz line 1 to neutralmetering voltage cal-
ibration
Read andWrite
0.0001 % Unsignedinteger
43076 50 Hz line 2 to neutralmetering voltage cal-
ibration
Read andWrite
0.0001 % Unsignedinteger
43077 50 Hz line 3 to neutralmetering voltage cal-
ibration
Read andWrite
0.0001 % Unsignedinteger
43078 60 Hz line 1 meteringcurrent calibration
Read andWrite
0.001 % Unsignedinteger
43079 60 Hz line 2 meteringcurrent calibration
Read andWrite
0.001 % Unsignedinteger
43080 60 Hz line 3 meteringcurrent calibration
Read andWrite
0.001 % Unsignedinteger
43081 50 Hz line 1 meteringcurrent calibration
Read andWrite
0.001 % Unsignedinteger
43082 50 Hz line 2 meteringcurrent calibration
Read andWrite
0.001 % Unsignedinteger
43083 50 Hz line 3 meteringcurrent calibration
Read andWrite
0.001 % Unsignedinteger
43084 Annunciator configur-able input #1 type
Read andWrite
Input type Unsignedinteger
0 = Event1 = Warning2 = Shutdown
7
Addr. NotesTypeUnitsScaleRead / WriteDescription43085 Annunciator configur-
able input #2 typeRead and
WriteInput type Unsigned
integer0 = Event1 = Warning2 = Shutdown
43086 Annunciator configur-able input #3 type
Read andWrite
Input type Unsignedinteger
0 = Event1 = Warning2 = Shutdown
43087 Annunciator configur-able output #1 event
code number
Read andWrite
1.0 Event code Unsignedinteger
43088 Annunciator configur-able output #2 event
code number
Read andWrite
1.0 Event code Unsignedinteger
43089 Annunciator configur-able output #3 event
code number
Read andWrite
1.0 Event code Unsignedinteger
43090 Annunciator configur-able output #4 event
code number
Read andWrite
1.0 Event code Unsignedinteger
8
THIS PAGE LEFT INTENTIONALLY BLANK
9
2. PowerCommand 2.x/3.x Modbus Register Map
Note: If an address or bit is not listed in this table it is not used.
Addr. Name Parameter Access Description Control40010 GC / Start/
Stop Con-trol
ControlSwitch Posi-tion
ReadOnly
Current position of the genset switch panel Off−Run−Auto switch as seen by the genset control. Modbusmapping shall be in both addresses 40580 and40010. For Modbus Only: 0: Off 1: Auto 2: Manual
PC 2.x, PC3.x
0: Off1: Manual2: Auto
40011 GC / Start/Stop Con-trol
Genset RunSequenceState
ReadOnly
Current genset operating mode. Modbus mappingshall be in both addresses 43500 and 40011
PC 2.x, PC3.x
0: Off1: Time Delay to Start2: Warmup at Idle3: Rated Freq and Voltage4: Cooldown / Stop Delay5: Cooldown at Idle
40013 Modbus /Modbus
Modbus regis-ter 40013
ReadOnly
This register always returns the value 0. This is not as-sociated with any logical. It is made same as 1302 tomake it compatible with iWatch.
PC 2.x, PC3.x
0: None1: Warning2: Shutdown
40012 Modbus /Modbus
Most RecentFault or Warn-ing
ReadOnly
Multiplier:1
Unit: FaultCode
This Modbus Registerdisplays most recentFault or Warning. It is notmapped with any logical.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40014 ACM /GensetCurrentand Power− %
Genset %Standby TotalkW
ReadOnly
Multiplier:0.01
Unit: % Monitors the total gensetstandby KW percentageoutput.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40016 PCCNet /UniversalAnnuncia-tor
NFPA 110Logical Status
ReadOnly
Multiplier:1
Unit: 32−bit number to repre-sent the status of theNFPA 110 logical. Seesection 4.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
10
Addr. ControlDescriptionAccessParameterName40017 PCCNet /
UniversalAnnuncia-tor
NFPA 110Logical Status
ReadOnly
Multiplier:1
Unit: 32−bit number to repre-sent the status of theNFPA 110 logical. Seesection 4.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U40018 ACM /
VoltageGenset L1NVoltage
ReadOnly
Multiplier:1
Unit: Vac Genset L1N voltage PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40019 ACM /
VoltageGenset L2NVoltage
ReadOnly
Multiplier:1
Unit: Vac Genset L2N voltage PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40020 ACM /
VoltageGenset L3NVoltage
ReadOnly
Multiplier:1
Unit: Vac Genset L3N voltage PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40021 ACM /
VoltageGenset LNAverage Volt-age
ReadOnly
Multiplier:1
Unit: Vac Genset Line to Neutralaverage voltage
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40022 ACM /
VoltageGenset L1L2Voltage
ReadOnly
Multiplier:1
Unit: Vac Genset L1L2 voltage PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40023 ACM /
VoltageGenset L2L3Voltage
ReadOnly
Multiplier:1
Unit: Vac Genset L2L3 voltage PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
11
Addr. ControlDescriptionAccessParameterName40024 ACM /
VoltageGenset L3L1Voltage
ReadOnly
Multiplier:1
Unit: Vac Genset L3L1 voltage PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40025 ACM /Voltage
Genset LL Av-erage Voltage
ReadOnly
Multiplier:1
Unit: Vac Genset Line to Line aver-age voltage
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40026 ACM /Current
Genset L1Current
ReadOnly
Multiplier:1
Unit: Amps Monitors the genset L1current value.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40027 ACM /Current
Genset L2Current
ReadOnly
Multiplier:1
Unit: Amps Genset L2 current PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40028 ACM /Current
Genset L3Current
ReadOnly
Multiplier:1
Unit: Amps Genset L3 current PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40029 ACM /Current
Genset Aver-age Current
ReadOnly
Multiplier:1
Unit: Amps Genset average current PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40030 ACM /Current
Genset Neu-tral Current
ReadOnly
Multiplier:1
Unit: Amps Genset neutral current PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40031 ACM /Power
Genset L1 kW ReadOnly
Multiplier:1
Unit: kW Genset L1 kW PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
12
Addr. ControlDescriptionAccessParameterName40032 ACM /
PowerGenset L2 kW Read
OnlyMultiplier:1
Unit: kW Genset L2 kW PC 2.x, PC3.x
Offset: 0 Lower Limit: −32768Size (bits):16
Upper Limit: 32762
Sign: S
40033 ACM /Power
Genset L3 kW ReadOnly
Multiplier:1
Unit: kW Genset L3 kW PC 2.x, PC3.x
Offset: 0 Lower Limit: −32768Size (bits):16
Upper Limit: 32762
Sign: S
40034 ACM /Power
Genset TotalkW
ReadOnly
Multiplier:1
Unit: kW Genset total kW PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40035 ACM /Power
Genset L1kVAR
ReadOnly
Multiplier:1
Unit: kVAR Genset L1 KVAR PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40036 ACM /Power
Genset L2kVAR
ReadOnly
Multiplier:1
Unit: kVAR Genset L2 Kvar PC 2.x, PC3.x
Offset: 0 Lower Limit: −32768Size (bits):16
Upper Limit: 32762
Sign: S
40037 ACM /Power
Genset L3kVAR
ReadOnly
Multiplier:1
Unit: kVAR Genset L3 Kvar PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40038 ACM /Power
Genset TotalkVAR
ReadOnly
Multiplier:1
Unit: kVAR Genset total kVAR PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40039 ACM /Power
Genset TotalPower Factor
ReadOnly
Multiplier:0.01
Unit: PF Genset total power factor(L1+L2+L3)
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: S
13
Addr. ControlDescriptionAccessParameterName40040 ACM /
PowerGenset L1kVA
ReadOnly
Multiplier:1
Unit: kVA Genset L1 kVA PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40041 ACM /
PowerGenset L2kVA
ReadOnly
Multiplier:1
Unit: kVA Genset L2 kVA PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40042 ACM /
PowerGenset L3kVA
ReadOnly
Multiplier:1
Unit: kVA Genset L3 kVA PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40043 ACM /
PowerGenset TotalkVA
ReadOnly
Multiplier:1
Unit: kVA Genset total kVA PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40044 PCCNet /
OperatorPanel
Genset Fre-quency OP
ReadOnly
Multiplier:0.01
Unit: Hz Genset Frequency OP.Modbus has differentmultiplier than PCCnet.For Modbus use only,Multiplier/Units = 0.1 Hz
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40046 ACM / En-
ergyGenset TotalNegative kWh
ReadOnly
Multiplier:1
Unit: kWh Genset total negativekWh accumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U40047 ACM / En-
ergyGenset TotalNegative kWh
ReadOnly
Multiplier:1
Unit: kWh Genset total negativekWh accumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
14
Addr. ControlDescriptionAccessParameterName40048 ACM / En-
ergyGenset TotalPositive kWh
ReadOnly
Multiplier:1
Unit: kWh Genset total positive kWhaccumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967290
Sign: U
40049 ACM / En-ergy
Genset TotalPositive kWh
ReadOnly
Multiplier:1
Unit: kWh Genset total positive kWhaccumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967290
Sign: U
40050 ACM / En-ergy
Genset TotalNet kWh
ReadOnly
Multiplier:1
Unit: kWh Genset total net kWh ac-cumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit: −2147483648Size (bits):32
Upper Limit: 2147483643
Sign: S
40051 ACM / En-ergy
Genset TotalNet kWh
ReadOnly
Multiplier:1
Unit: kWh Genset total net kWh ac-cumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit: −2147483648Size (bits):32
Upper Limit: 2147483643
Sign: S
40052 ACM / En-ergy
Genset TotalNegativekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset total negativekVARh accumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40053 ACM / En-ergy
Genset TotalNegativekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset total negativekVARh accumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40054 ACM / En-ergy
Genset TotalPositivekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset total positivekVARh accumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967290
Sign: U
40055 ACM / En-ergy
Genset TotalPositivekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset total positivekVARh accumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967290
Sign: U
15
Addr. ControlDescriptionAccessParameterName40056 ACM / En-
ergyGenset TotalNet kVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset total net kVARhaccumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit: −2147483648Size (bits):32
Upper Limit: 2147483643
Sign: S40057 ACM / En-
ergyGenset TotalNet kVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset total net kVARhaccumulation
PC 2.x, PC3.x
Offset: 0 Lower Limit: −2147483648Size (bits):32
Upper Limit: 2147483643
Sign: S40058 ACM /
GensetCurrentand Power− %
Genset %Standby L1Current
ReadOnly
Multiplier:0.1
Unit: % Monitors the gensetstandby L1 current per-centage output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40059 ACM /
GensetCurrentand Power− %
Genset %Standby L2Current
ReadOnly
Multiplier:0.1
Unit: % Monitors the gensetstandby L2 current per-centage output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40060 ACM /
GensetCurrentand Power− %
Genset %Standby L3Current
ReadOnly
Multiplier:0.1
Unit: % Monitors the gensetstandby L3 current per-centage output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40061 ASI / Ana-
log InputsBattery Volt-age
ReadOnly
Multiplier:0.001
Unit: Vdc Battery voltage val-ue−−−−−> For Modbususe only multiplier/units =0.1 Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
16
Addr. ControlDescriptionAccessParameterName40062 CAN /
CAN InputMessages
Oil Pressure ReadOnly
Multiplier:0.1
Unit: psi Monitor point for the OilPressure. Modbus andPCCnet have differentmultiplier value. For mod-bus use only, Multiplier/Units = 1kPa
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40063 CAN /CAN InputMessages
Oil Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the OilTemperature
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40064 CAN /CAN InputMessages
Coolant Tem-perature
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for theCoolant Temperature.Modbus mapping shall beto both 46126 and 40064addresses. For Modbususe only, Multiplier/Units= 0.1C
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40065 CAN /CAN InputMessages
Intake Man-ifold Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF To monitor Intake Man-ifold Temperature. Thisparameter represents ”In-take Manifold Tempera-ture 1”.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −40Size (bits):16
Upper Limit: 410
Sign: S
40066 CAN /CAN InputMessages
Fuel Temper-ature
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the FuelTemperature
PC 2.x, PC3.x
Offset: 0 Lower Limit: −40Size (bits):16
Upper Limit: 410
Sign: S
40067 CAN /CAN InputMessages
Fuel Rate ReadOnly
Multiplier:0.05
Unit: gal/hr Monitor point for the FuelRate
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit:
Sign: U
17
Addr. ControlDescriptionAccessParameterName40068 CAN /
CAN InputMessages
Average En-gine Speed
ReadOnly
Multiplier:0.125
Unit: rpm Monitor point for the Av-erage Engine Speed.Modbus and PCCnethave different multipliervalue. For modbus useonly, Multiplier/Units = 1RPM
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 4096
Sign: U
40069 PCCNet /OperatorPanel
Total Start At-tempts OP
ReadOnly
Multiplier:1
Unit: Total number of start at-tempts.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
40070 CAN /CAN InputMessages
Engine Run-ning Time
ReadOnly
Multiplier:0.05
Unit: hours Total engine run time.Modbus has differentmultiplier than PCCnet.For Modbus use only,multiplier/units = 1.0 Sec
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40071 CAN /CAN InputMessages
Engine Run-ning Time
ReadOnly
Multiplier:0.05
Unit: hours Total engine run time.Modbus has differentmultiplier than PCCnet.For Modbus use only,multiplier/units = 1.0 Sec
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40072 CAN /CAN InputMessages
Total FuelConsumption
ReadOnly
Multiplier:0.1
Unit: gal-lons
Total fuel consumptionsince start of engine.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40073 CAN /CAN InputMessages
Total FuelConsumption
ReadOnly
Multiplier:0.1
Unit: gal-lons
Total fuel consumptionsince start of engine.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
18
Addr. ControlDescriptionAccessParameterName40074 DR / Data
RecordingTotal Numberof Runs
ReadOnly
Multiplier:1
Unit: Total number of gensetruns.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967295
Sign: U40075 DR / Data
RecordingTotal Numberof Runs
ReadOnly
Multiplier:1
Unit: Total number of gensetruns.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967295
Sign: U40076 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40077 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
19
Addr. ControlDescriptionAccessParameterName40078 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40079 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40080 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
20
Addr. ControlDescriptionAccessParameterName40081 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40082 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40083 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
21
Addr. ControlDescriptionAccessParameterName40084 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40085 DR / Data
RecordingRuns ResetTime
Read/Write
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40086 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
22
Addr. ControlDescriptionAccessParameterName40087 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40088 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40089 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
23
Addr. ControlDescriptionAccessParameterName40090 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40091 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40092 DR / Data
RecordingRuns ResetTime
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
24
Addr. ControlDescriptionAccessParameterName40096 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40097 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40098 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
25
Addr. ControlDescriptionAccessParameterName40099 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40100 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40101 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
26
Addr. ControlDescriptionAccessParameterName40102 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40103 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40104 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
27
Addr. ControlDescriptionAccessParameterName40105 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40106 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40107 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
28
Addr. ControlDescriptionAccessParameterName40108 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40109 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C40110 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
29
Addr. ControlDescriptionAccessParameterName40111 DR / Data
RecordingStart AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
40112 DR / DataRecording
Start AttemptsReset Time
ReadOnly
Multiplier:1
Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):144
Upper Limit:
Sign: C
40118 ACM /Voltage
Utility L1NVoltage
ReadOnly
Multiplier:1
Unit: Vac Utility L1N voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40119 ACM /Voltage
Utility L2NVoltage
ReadOnly
Multiplier:1
Unit: Vac Utility L2N voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40120 ACM /Voltage
Utility L3NVoltage
ReadOnly
Multiplier:1
Unit: Vac Utility L3N voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
30
Addr. ControlDescriptionAccessParameterName40121 ACM /
VoltageUtility LN Av-erage Voltage
ReadOnly
Multiplier:1
Unit: Vac Utility Line to Neutral av-erage voltage
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40122 ACM /Voltage
Utility L1L2Voltage
ReadOnly
Multiplier:1
Unit: Vac Utility L1L2 voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40123 ACM /Voltage
Utility L2L3Voltage
ReadOnly
Multiplier:1
Unit: Vac Utility L2L3 voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40124 ACM /Voltage
Utility L3L1Voltage
ReadOnly
Multiplier:1
Unit: Vac Utility L3L1 voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40125 ACM /Voltage
Utility LL Av-erage Voltage
ReadOnly
Multiplier:1
Unit: Vac Utility Line to Line aver-age voltage
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40126 ACM /Current
Utility L1 Cur-rent
ReadOnly
Multiplier:1
Unit: Amps Utility L1 current PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40127 ACM /Current
Utility L2 Cur-rent
ReadOnly
Multiplier:1
Unit: Amps Utility L2 current PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40128 ACM /Current
Utility L3 Cur-rent
ReadOnly
Multiplier:1
Unit: Amps Utility L3 current PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
31
Addr. ControlDescriptionAccessParameterName40129 ACM /
CurrentUtility AverageCurrent
ReadOnly
Multiplier:1
Unit: Amps Utility average current PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40131 ACM /Power
Utility L1 kW ReadOnly
Multiplier:1
Unit: kW Utility L1 kW PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40132 ACM /Power
Utility L2 kW ReadOnly
Multiplier:1
Unit: kW Utility L2 kW PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40133 ACM /Power
Utility L3 kW ReadOnly
Multiplier:1
Unit: kW Utility L3 kW PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40134 ACM /Power
Utility TotalkW
ReadOnly
Multiplier:1
Unit: kW Utility total kW PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40135 ACM /Power
Utility L1kVAR
ReadOnly
Multiplier:1
Unit: kVAR Utility L1 Kvar PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40136 ACM /Power
Utility L2kVAR
ReadOnly
Multiplier:1
Unit: kVAR Utility L2 Kvar PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40137 ACM /Power
Utility L3kVAR
ReadOnly
Multiplier:1
Unit: kVAR Utility L3 Kvar PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
32
Addr. ControlDescriptionAccessParameterName40138 ACM /
PowerUtility TotalkVAR
ReadOnly
Multiplier:1
Unit: kVAR Utility total kVAR PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40139 ACM /Power
Utility TotalPower Factor
ReadOnly
Multiplier:0.01
Unit: PF Utility total power factor PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: S
40140 ACM /Power
Utility L1 kVA ReadOnly
Multiplier:1
Unit: kVA Utility L1 kVA PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40141 ACM /Power
Utility L2 kVA ReadOnly
Multiplier:1
Unit: kVA Utility L2 kVA PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40142 ACM /Power
Utility L3 kVA ReadOnly
Multiplier:1
Unit: kVA Utility L3 kVA PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40143 ACM /Power
Utility TotalkVA
ReadOnly
Multiplier:1
Unit: kVA Utility total kVA PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40144 ACM / Fre-quency
Utility Fre-quency
ReadOnly
Multiplier:0.001
Unit: Hz Utility line frequency PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40145 ACM / Fre-quency
Utility Fre-quency
ReadOnly
Multiplier:0.001
Unit: Hz Utility line frequency PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
33
Addr. ControlDescriptionAccessParameterName40146 ACM / En-
ergyUtility TotalNegative kWh
ReadOnly
Multiplier:1
Unit: kWh Utility total negative kWhaccumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40147 ACM / En-ergy
Utility TotalNegative kWh
ReadOnly
Multiplier:1
Unit: kWh Utility total negative kWhaccumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40148 ACM / En-ergy
Utility TotalPositive kWh
ReadOnly
Multiplier:1
Unit: kWh Utility total positive kWhaccumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40149 ACM / En-ergy
Utility TotalPositive kWh
ReadOnly
Multiplier:1
Unit: kWh Utility total positive kWhaccumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40150 ACM / En-ergy
Utility TotalNet kWh
ReadOnly
Multiplier:1
Unit: kWh Utility total net kWh accu-mulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: S
40151 ACM / En-ergy
Utility TotalNet kWh
ReadOnly
Multiplier:1
Unit: kWh Utility total net kWh accu-mulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: S
40152 ACM / En-ergy
Utility TotalNegativekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Utility total negativekVARh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40153 ACM / En-ergy
Utility TotalNegativekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Utility total negativekVARh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
34
Addr. ControlDescriptionAccessParameterName40154 ACM / En-
ergyUtility TotalPositivekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Utility total positivekVARh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40155 ACM / En-ergy
Utility TotalPositivekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Utility total positivekVARh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40156 ACM / En-ergy
Utility TotalNet kVARh
ReadOnly
Multiplier:1
Unit:kVARh
Utility total net kVARh ac-cumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: S
40157 ACM / En-ergy
Utility TotalNet kVARh
ReadOnly
Multiplier:1
Unit:kVARh
Utility total net kVARh ac-cumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: S
40158 ACM /Voltage
Genset BusL1N Voltage
ReadOnly
Multiplier:1
Unit: Vac Genset Bus L1N voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40159 ACM /Voltage
Genset BusL2N Voltage
ReadOnly
Multiplier:1
Unit: Vac Genset Bus L2N voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40160 ACM /Voltage
Genset BusL3N Voltage
ReadOnly
Multiplier:1
Unit: Vac Genset Bus L3N voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40161 ACM /Voltage
Genset BusLN AverageVoltage
ReadOnly
Multiplier:1
Unit: Vac Genset Bus Line to Neu-tral average voltage
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
35
Addr. ControlDescriptionAccessParameterName40162 ACM /
VoltageGenset BusL1L2 Voltage
ReadOnly
Multiplier:1
Unit: Vac Genset Bus L1L2 voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40163 ACM /Voltage
Genset BusL2L3 Voltage
ReadOnly
Multiplier:1
Unit: Vac Genset Bus L2L3 voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40164 ACM /Voltage
Genset BusL3L1 Voltage
ReadOnly
Multiplier:1
Unit: Vac Genset Bus L3L1 voltage PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40165 ACM /Voltage
Genset BusLL AverageVoltage
ReadOnly
Multiplier:1
Unit: Vac Genset Bus Line to Lineaverage voltage
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40166 ACM /Current
Genset BusL1 Current
ReadOnly
Multiplier:1
Unit: Amps Genset Bus L1 current PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40167 ACM /Current
Genset BusL2 Current
ReadOnly
Multiplier:1
Unit: Amps Genset Bus L2 current PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40168 ACM /Current
Genset BusL3 Current
ReadOnly
Multiplier:1
Unit: Amps Genset Bus L3 current PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40169 ACM /Current
Genset BusAverage Cur-rent
ReadOnly
Multiplier:1
Unit: Amps Genset Bus Average cur-rent
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
36
Addr. ControlDescriptionAccessParameterName40171 ACM /
PowerGenset BusL1 kW
ReadOnly
Multiplier:1
Unit: kW Genset Bus L1 kW PC 3.x
Offset: 0 Lower Limit: −32768Size (bits):16
Upper Limit: 32762
Sign: S
40172 ACM /Power
Genset BusL2 kW
ReadOnly
Multiplier:1
Unit: kW Genset Bus L2 kW PC 3.x
Offset: 0 Lower Limit: −32768Size (bits):16
Upper Limit: 32762
Sign: S
40173 ACM /Power
Genset BusL3 kW
ReadOnly
Multiplier:1
Unit: kW Genset Bus L3 kW PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40174 ACM /Power
Genset BusTotal kW
ReadOnly
Multiplier:1
Unit: kW Genset Bus total kW PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40175 ACM /Power
Genset BusL1 kVAR
ReadOnly
Multiplier:1
Unit: kVAR Genset bus L1 Kvar PC 3.x
Offset: 0 Lower Limit: −32678Size (bits):16
Upper Limit: 32672
Sign: S
40176 ACM /Power
Genset BusL2 kVAR
ReadOnly
Multiplier:1
Unit: kVAR Genset bus L2 Kvar PC 3.x
Offset: 0 Lower Limit: −32768Size (bits):16
Upper Limit: 32762
Sign: S
40177 ACM /Power
Genset BusL3 kVAR
ReadOnly
Multiplier:1
Unit: kVAR Genset bus L3 Kvar PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40178 ACM /Power
Genset BusTotal kVAR
ReadOnly
Multiplier:1
Unit: kVAR Genset bus total kVAR PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
37
Addr. ControlDescriptionAccessParameterName40179 ACM /
PowerGenset BusTotal PowerFactor
ReadOnly
Multiplier:0.01
Unit: PF Genset Bus Total powerfactor
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: S
40180 ACM /Power
Genset BusL1 kVA
ReadOnly
Multiplier:1
Unit: kVA Genset Bus L1 kVA PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40181 ACM /Power
Genset BusL2 kVA
ReadOnly
Multiplier:1
Unit: kVA Genset Bus L2 kVA PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40182 ACM /Power
Genset BusL3 kVA
ReadOnly
Multiplier:1
Unit: kVA Genset Bus L3 kVA PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40183 ACM /Power
Genset BusTotal kVA
ReadOnly
Multiplier:1
Unit: kVA Genset bus total kVA PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
40184 ACM / Fre-quency
Genset BusFrequency
ReadOnly
Multiplier:0.001
Unit: Hz Genset bus line frequen-cy
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40185 ACM / Fre-quency
Genset BusFrequency
ReadOnly
Multiplier:0.001
Unit: Hz Genset bus line frequen-cy
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40186 ACM / En-ergy
Genset BusTotal NegativekWh
ReadOnly
Multiplier:1
Unit: kWh Genset bus total negativekWh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
38
Addr. ControlDescriptionAccessParameterName40187 ACM / En-
ergyGenset BusTotal NegativekWh
ReadOnly
Multiplier:1
Unit: kWh Genset bus total negativekWh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40188 ACM / En-ergy
Genset BusTotal PositivekWh
ReadOnly
Multiplier:1
Unit: kWh Genset bus total positivekWh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40189 ACM / En-ergy
Genset BusTotal PositivekWh
ReadOnly
Multiplier:1
Unit: kWh Genset bus total positivekWh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40190 ACM / En-ergy
Genset BusTotal Net kWh
ReadOnly
Multiplier:1
Unit: kWh Genset bus total net kWhaccumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: S
40191 ACM / En-ergy
Genset BusTotal Net kWh
ReadOnly
Multiplier:1
Unit: kWh Genset bus total net kWhaccumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: S
40192 ACM / En-ergy
Genset BusTotal NegativekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset bus total negativekVARh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40193 ACM / En-ergy
Genset BusTotal NegativekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset bus total negativekVARh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40194 ACM / En-ergy
Genset BusTotal PositivekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset bus total positivekVARh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
39
Addr. ControlDescriptionAccessParameterName40195 ACM / En-
ergyGenset BusTotal PositivekVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset bus total positivekVARh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U40196 ACM / En-
ergyGenset BusTotal NetkVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset Bus total netkVARh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: S40197 ACM / En-
ergyGenset BusTotal NetkVARh
ReadOnly
Multiplier:1
Unit:kVARh
Genset Bus total netkVARh accumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: S40198 ACM /
CurrentGround Cur-rent
ReadOnly
Multiplier:0.1
Unit: amps Ground current PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40199 ACM /
CurrentGenset Nega-tive SequenceCurrent %
ReadOnly
Multiplier:0.01
Unit: % Genset Negative Se-quence Current as Per-cent of Standby CurrentRating
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40207 ASI / Ana-
log InputsBattery Char-ger AlternatorFlash Voltage
ReadOnly
Multiplier:0.001
Unit: Vdc The Battery Charger Al-ternator Flash Voltage af-ter all scaling and validitychecks.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 35
Sign: U40201 ASI / Ana-
log Inputs/Outputs
Coolant Tem-peratureSender Type
Read/Write
Either Onan or Cummins sensor. Modbus Access:Read Only
PC 2.x, PC3.x
0: PGBU1: EBU
40
Addr. ControlDescriptionAccessParameterName40210 ASI / Ana-
log InputsExternalSpeed BiasInput
ReadOnly
Multiplier:0.01
Unit: % Monitor point for the ex-ternal speed bias input.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −100Size (bits):16
Upper Limit: 100
Sign: S40211 ASI / Ana-
log InputsExternal Volt-age Bias Input
ReadOnly
Multiplier:0.01
Unit: % Monitor point for the ex-ternal voltage bias input.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −100Size (bits):16
Upper Limit: 100
Sign: S40214 ASI / Ana-
log InputskVAR LoadSetpoint
ReadOnly
Multiplier:0.01
Unit: % EU scaled value for thekVAR load setpoint
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit:
Sign: S40217 ASI / Ana-
log InputskVAR LoadShare Level
ReadOnly
Multiplier:0.01
Unit: % EU Scaled value for thekVAR load share levelanalog input
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S40219 ASI / Ana-
log InputskW Load Set-point
ReadOnly
Multiplier:0.01
Unit: % EU scaled value for thekW load setpoint
PC 3.x
Offset: 0 Lower Limit: −25.01Size (bits):16
Upper Limit: 125.01
Sign: S40222 ASI / Ana-
log InputskW LoadShare Level
ReadOnly
Multiplier:0.01
Unit: % EU Scaled value for thekW load share level ana-log input
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S40224 ASO /
AnalogOutputs
KVAR LoadShare OutputPredictor
ReadOnly
Multiplier:0.1
Unit: uA uA signal being injectedinto a 10K ohm resistornetwork
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
41
Addr. ControlDescriptionAccessParameterName40225 ASO /
AnalogOutputs
KW LoadShare OutputPredictor
ReadOnly
Multiplier:0.1
Unit: uA uA signal being injectedinto a 10K ohm resistornetwork
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40226 ASO /AnalogOutputs
Speed BiasOutput / Con-figurable Ana-log output #1Output Pre-dictor
ReadOnly
Multiplier:0.01
Unit: Vdc Configurable analog out-put voltage output value(predicted)
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40227 ASO /AnalogOutputs
Voltage BiasOutput / Con-figurable Ana-log output #2Output Pre-dictor
ReadOnly
Multiplier:0.01
Unit: Vdc Configurable analog out-put voltage output value(predicted)
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40228 CAN /CAN InputMessages
Amber Warn-ing Lamp Sta-tus
ReadOnly
Engine Control System indicates a warning condition. PC 2.x, PC3.x0: Inactive
1: Active
40229 CAN /CAN InputMessages
BarometricAbsolutePressure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for theBarometric AbsolutePressure. Displayed as”Ambient Pressure” in theHMI.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 37
Sign: U
40230 CAN /CAN InputMessages
Boost Pres-sure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for theBoost Absolute Pressure
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 148
Sign: U
40231 CAN /CANDatalink
CAN DatalinkStatus
ReadOnly
Indicates the status of the CAN datalink PC 2.x, PC3.x0: Inactive
1: Active2: Failed
40232 CAN /CAN InputMessages
CrankcasePressure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for theCrankcase Pressure.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −35.67Size (bits):16
Upper Limit: 38
Sign: S
42
Addr. ControlDescriptionAccessParameterName40235 CAN /
CAN InputMessages
ECM DerateRequest
ReadOnly
Request made by the ECS for a reduction in load PC 2.x, PC3.x0: No Derate Request
1: Derate Request2: Error3: Don’t Care
4023640237
CAN /CAN InputMessages
Engine Ap-plication Type
ReadOnly
Monitor point for the output of the Engine applicationtype. Either ECM (CAN) or Hydro−Mechanical.
PC 2.x, PC3.x
0: ECM1: Hydro−MechanicalECS engine state indication1: Ventilation2: Start3: Run4: Normal Shutdown5: Emergency Shutdown6: Error7: Don’t Care
40242 CAN /CAN InputMessages
AftercoolerTemperature
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Af-tercooler Temperature.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −40Size (bits):16
Upper Limit: 410
Sign: S
40254 CAN /CAN InputMessages
Fuel SupplyPressure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for the FuelSupply Pressure. Dis-played as ”Fuel SupplyPressure” in the HMI.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 145
Sign: U
40257 CAN /CAN InputMessages
Intake Man-ifold 4 Tem-perature
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the In-take Manifold 4 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −40Size (bits):16
Upper Limit: 410
Sign: S
40258 CAN /CAN InputMessages
Fuel OutletPressure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for the FuelOutlet Pressure Pres-sure. Displayed as ”FuelRail Pressure” in theHMI.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 36404
Sign: U
43
Addr. ControlDescriptionAccessParameterName40259 CAN /
CAN InputMessages
Fuel OutletPressure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for the FuelOutlet Pressure Pres-sure. Displayed as ”FuelRail Pressure” in theHMI.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 36404
Sign: U
40260 CAN /CAN InputMessages
Intake Man-ifold 2 Tem-perature
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the In-take Manifold 2 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −40Size (bits):16
Upper Limit: 410
Sign: S
40261 CAN /CAN InputMessages
Intake Man-ifold 3 Tem-perature
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the In-take Manifold 3 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −40Size (bits):16
Upper Limit: 410
Sign: S
40262 CAN /CAN Out-put Mes-sages
KeyswitchCommand
ReadOnly
Driver command that controls the output for thekeyswitch
PC 2.x, PC3.x
0: Inactive1: Active
40263 CAN /CAN InputMessages
Normal Shut-down Request
ReadOnly
Request made by the ECS for a normal shutdown withcooldown
PC 2.x, PC3.x
0: No Shutdown Request1: Normal Shutdown Request2: Error3: Don’t Care
40264 CAN /CAN InputMessages
Percent En-gine Torque/Duty Cycle
ReadOnly
Multiplier:1
Unit: % Monitor point for the per-cent engine torque outputand the governor percentduty cycle output whenused with the HM ECM
PC 2.x, PC3.x
Offset: 0 Lower Limit: −125Size (bits):16
Upper Limit: 125
Sign: S
40276 CAN /CAN InputMessages
Post−Filter OilPressure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for thePost−Filter Oil Pressure
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 145
Sign: U
44
Addr. ControlDescriptionAccessParameterName40277 CAN /
CAN InputMessages
Pre−Filter OilPressure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for the Pre−Filter Oil Pressure
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 145
Sign: U
40278 DSI / Dis-crete In-puts
ConfigurableInput #14Switch
ReadOnly
Configurable Input #14 input software state status.Gives software Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
40279 CAN /CAN InputMessages
Turbocharger1 Speed
ReadOnly
Multiplier:1
Unit: rpm Monitor point for theTurbocharger 1 Speed
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 257000
Sign: U
40280 CAN /CAN InputMessages
Turbocharger1 Speed
ReadOnly
Multiplier:1
Unit: rpm Monitor point for theTurbocharger 1 Speed
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 257000
Sign: U
40281 CAN /CAN InputMessages
Turbocharger2 Boost Pres-sure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for theTurbocharger 2 BoostPressure
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 1160
Sign: U
40282 CAN /CAN InputMessages
Water in FuelIndicator
ReadOnly
Water in Fuel Indication PC 2.x, PC3.x0: No
1: Yes
40283 CM / Con-trollerModes
ControllerMode
ReadOnly
The controller mode PC 2.x, PC3.x0: Off
1: Ready3: Starting4: Idle5: Rated6: Stop Normal7: Stop Emergency8: Factory Test9: Wait to Power Down
40285 CM / Con-trollerModes
Power DownMode Timer
ReadOnly
Multiplier:1
Unit: sec-onds
Timer to count down thetime before the controlgoes to sleep
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 600
Sign: U
45
Addr. ControlDescriptionAccessParameterName40286 CM / Con-
trollerModes
Setup ModeTimer
ReadOnly
Multiplier:1
Unit: Sec-onds
Time spent in SetupMode.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U40287 CM / Con-
trollerModes
Tool Wake−upCommand
ReadOnly
The control output to the common wake−up line towake up other devices
PC 2.x, PC3.x
0: Inactive1: Active
40289 DR / Exer-ciseScheduler
Active Sched-ule
ReadOnly
Indicates the currently active scheduler program orexception.
PC 2.x, PC3.x
0: None1: Program 12: Program 23: Program 34: Program 45: Program 56: Program 67: Program 78: Program 89: Program 910: Program 1011: Program 1112: Program 1213: Exception 114: Exception 215: Exception 316: Exception 417: Exception 518: Exception 6
40290 DR / DataRecording
Controller OnTime
Read/Write
Multiplier:1
Unit: Sec-onds
Controller ON time inseconds. Upper limit is136 years.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967291
Sign: U40291 DR / Data
RecordingController OnTime
Read/Write
Multiplier:1
Unit: Sec-onds
Controller ON time inseconds. Upper limit is136 years.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967291
Sign: U
46
Addr. ControlDescriptionAccessParameterName40298 DR / Data
RecordingRuns SinceReset
Read/Write
Multiplier:1
Unit: Number of runs since thelast reset. Upper limit is2^32 − 1.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967290
Sign: U
40299 DR / DataRecording
Runs SinceReset
Read/Write
Multiplier:1
Unit: Number of runs since thelast reset. Upper limit is2^32 − 1.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967290
Sign: U
40300 Modbus /Modbus
Remote StartSwitch (Mod-bus)
Read/Write
Modbus Remote Start PC 2.x, PC3.x0: Inactive
1: Active
40301 Modbus /Modbus
Fault Reset(Modbus)
Read/Write
Modbus fault reset. PC 2.x, PC3.x0: Inactive
1: Active
40320 DSI / Dis-crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40321 DSI / Dis-crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40322 DSI / Dis-crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
47
Addr. ControlDescriptionAccessParameterName40323 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40324 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40325 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40326 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40327 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
48
Addr. ControlDescriptionAccessParameterName40328 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40329 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40330 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40331 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40332 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
49
Addr. ControlDescriptionAccessParameterName40333 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40334 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40335 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40336 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40337 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
50
Addr. ControlDescriptionAccessParameterName40338 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40339 DSI / Dis-
crete In-puts
Start InhibitNo1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40340 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40341 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40342 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
51
Addr. ControlDescriptionAccessParameterName40343 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40344 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40345 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40346 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40347 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
52
Addr. ControlDescriptionAccessParameterName40348 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40349 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40350 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40351 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40352 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
53
Addr. ControlDescriptionAccessParameterName40353 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40354 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40355 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40356 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40357 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
54
Addr. ControlDescriptionAccessParameterName40358 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40359 DSI / Dis-
crete In-puts
Start InhibitNo2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40360 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40361 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40362 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
55
Addr. ControlDescriptionAccessParameterName40363 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40364 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40365 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40366 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40367 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
56
Addr. ControlDescriptionAccessParameterName40368 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40369 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40370 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40371 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40372 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
57
Addr. ControlDescriptionAccessParameterName40373 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40374 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40375 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40376 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40377 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
58
Addr. ControlDescriptionAccessParameterName40378 DSI / Dis-
crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40379 DSI / Dis-crete In-puts
Start InhibitNo3 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.
PC 3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40400 Modbus /Modbus
Fault StatusBitmap 1
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40401 Modbus /Modbus
Fault StatusBitmap 2
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40402 Modbus /Modbus
Fault StatusBitmap 3
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40403 Modbus /Modbus
Fault StatusBitmap 4
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40404 Modbus /Modbus
Fault StatusBitmap 5
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
59
Addr. ControlDescriptionAccessParameterName40405 Modbus /
ModbusFault StatusBitmap 6
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40406 Modbus /Modbus
Fault StatusBitmap 7
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40407 Modbus /Modbus
Fault StatusBitmap 8
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40408 Modbus /Modbus
Fault StatusBitmap 9
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40409 Modbus /Modbus
Fault StatusBitmap 10
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40410 Modbus /Modbus
Fault StatusBitmap 11
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40411 Modbus /Modbus
Fault StatusBitmap 12
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40412 Modbus /Modbus
Fault StatusBitmap 13
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
60
Addr. ControlDescriptionAccessParameterName40413 Modbus /
ModbusFault StatusBitmap 14
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40414 Modbus /Modbus
Fault StatusBitmap 15
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40415 Modbus /Modbus
Fault StatusBitmap 16
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40416 Modbus /Modbus
Fault StatusBitmap 17
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40417 Modbus /Modbus
Fault StatusBitmap 18
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40418 Modbus /Modbus
Fault StatusBitmap 19
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40419 Modbus /Modbus
Fault StatusBitmap 20
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40420 Modbus /Modbus
Fault StatusBitmap 21
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
61
Addr. ControlDescriptionAccessParameterName40421 Modbus /
ModbusFault StatusBitmap 22
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40422 Modbus /Modbus
Fault StatusBitmap 23
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: S
40430 Modbus /Modbus
Event StatusBitmap 1
ReadOnly
Multiplier:1
Unit: 16 bit fault bitmap for Mo-dus interface.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
40431 Modbus /Modbus
Fault StatusGas Bitmap 1
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40432 Modbus /Modbus
Fault StatusGas Bitmap 2
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40433 Modbus /Modbus
Fault StatusGas Bitmap 3
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40434 Modbus /Modbus
Fault StatusGas Bitmap 4
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40435 Modbus /Modbus
Fault StatusGas Bitmap 5
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
62
Addr. ControlDescriptionAccessParameterName40436 Modbus /
ModbusFault StatusGas Bitmap 6
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40437 Modbus /Modbus
Fault StatusGas Bitmap 7
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40438 Modbus /Modbus
Fault StatusGas Bitmap 8
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40439 Modbus /Modbus
Fault StatusGas Bitmap 9
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40440 Modbus /Modbus
Fault StatusGas Bitmap10
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40441 Modbus /Modbus
Fault StatusGas Bitmap11
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40442 Modbus /Modbus
Fault StatusGas Bitmap12
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40443 Modbus /Modbus
Fault StatusGas Bitmap13
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
63
Addr. ControlDescriptionAccessParameterName40444 Modbus /
ModbusFault StatusGas Bitmap14
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40445 Modbus /Modbus
Fault StatusGas Bitmap15
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40446 Modbus /Modbus
Fault StatusGas Bitmap16
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40447 Modbus /Modbus
Fault StatusGas Bitmap17
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40448 Modbus /Modbus
Fault StatusGas Bitmap18
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40449 Modbus /Modbus
Fault StatusGas Bitmap19
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40450 Modbus /Modbus
Fault StatusGas Bitmap20
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40451 Modbus /Modbus
Fault StatusGas Bitmap21
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
64
Addr. ControlDescriptionAccessParameterName40452 Modbus /
ModbusFault StatusGas Bitmap22
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40453 Modbus /Modbus
Fault StatusGas Bitmap23
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40454 Modbus /Modbus
Fault StatusGas Bitmap24
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40455 Modbus /Modbus
Fault StatusGas Bitmap25
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40456 Modbus /Modbus
Fault StatusGas Bitmap26
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40457 Modbus /Modbus
Fault StatusGas Bitmap27
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40458 Modbus /Modbus
Fault StatusGas Bitmap28
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40459 Modbus /Modbus
Fault StatusGas Bitmap29
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
65
Addr. ControlDescriptionAccessParameterName40460 Modbus /
ModbusFault StatusGas Bitmap30
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40461 Modbus /Modbus
Fault StatusGas Bitmap31
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40462 Modbus /Modbus
Fault StatusGas Bitmap32
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40463 Modbus /Modbus
Fault StatusGas Bitmap33
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40464 Modbus /Modbus
Fault StatusGas Bitmap34
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40465 Modbus /Modbus
Fault StatusGas Bitmap35
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40466 Modbus /Modbus
Fault StatusGas Bitmap36
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40467 Modbus /Modbus
Fault StatusGas Bitmap37
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
66
Addr. ControlDescriptionAccessParameterName40468 Modbus /
ModbusFault StatusGas Bitmap38
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40469 Modbus /Modbus
Fault StatusGas Bitmap39
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40470 Modbus /Modbus
Fault StatusGas Bitmap40
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40471 Modbus /Modbus
Fault StatusGas Bitmap41
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40472 Modbus /Modbus
Fault StatusGas Bitmap42
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40473 Modbus /Modbus
Fault StatusGas Bitmap43
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40474 Modbus /Modbus
Fault StatusGas Bitmap44
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40475 Modbus /Modbus
Fault StatusGas Bitmap45
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
67
Addr. ControlDescriptionAccessParameterName40476 Modbus /
ModbusFault StatusGas Bitmap46
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40477 Modbus /Modbus
Fault StatusGas Bitmap47
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40478 Modbus /Modbus
Fault StatusGas Bitmap48
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40479 Modbus /Modbus
Fault StatusGas Bitmap49
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40480 Modbus /Modbus
Fault StatusGas Bitmap50
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40481 Modbus /Modbus
Fault StatusGas Bitmap51
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40482 Modbus /Modbus
Fault StatusGas Bitmap52
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40483 Modbus /Modbus
Fault StatusGas Bitmap53
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
68
Addr. ControlDescriptionAccessParameterName40484 Modbus /
ModbusFault StatusGas Bitmap54
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40485 Modbus /Modbus
Fault StatusGas Bitmap55
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40486 Modbus /Modbus
Fault StatusGas Bitmap56
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40487 Modbus /Modbus
Fault StatusGas Bitmap57
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40488 Modbus /Modbus
Fault StatusGas Bitmap58
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40489 Modbus /Modbus
Fault StatusGas Bitmap59
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40490 Modbus /Modbus
Fault StatusGas Bitmap60
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40491 Modbus /Modbus
Fault StatusGas Bitmap61
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
69
Addr. ControlDescriptionAccessParameterName40492 Modbus /
ModbusFault StatusGas Bitmap62
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40493 Modbus /Modbus
Fault StatusGas Bitmap63
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40494 Modbus /Modbus
Fault StatusGas Bitmap64
ReadOnly
Multiplier:1
Unit: 16 bit Gas fault bitmapfor Modus interface.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
40500 DSI / Dis-crete In-puts
Low FuelSwitch
ReadOnly
Low Fuel input software state status. Gives softwareInactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
40501 DSI / Dis-crete In-puts
Low Fuel/ConfigurableInput #6Switch
ReadOnly
This is the status of the Configurable Input #6. PC 2.x, PC3.x0: Inactive
1: Active
40502 DSI / Safety WireLoop
ReadOnly
0: Inactive PC 3.x1: Active
40503 DSI / Dis-crete In-puts
DifferentialFault Trip
ReadOnly
Differential fault trip monitor point. PC 3.x0: Inactive1: Active
40504 DSI / Dis-crete In-puts
Master FirstStart Input A
ReadOnly
This is the status of the Master First Start A input. PC 3.x0: Inactive1: Active
40505 DSI / Dis-crete In-puts
Fire Trip ReadOnly
Fire trip monitor point. PC 3.x0: Inactive1: Active
40506 DSI / Dis-crete In-puts
Master FirstStart Input BSwitch
ReadOnly
Masterless Load Demand Enable Switch functionoutput status. Gives software Inactive/Active state
PC 3.x
0: Inactive1: Active
40507 DSI / Dis-crete In-puts
MasterlessLoad DemandEnable Switch
ReadOnly
Masterless Load Demand Enable Switch functionoutput status. Gives software Inactive/Active state
PC 3.x
0: Inactive1: Active
40508 DSI / Dis-crete In-puts
PredictiveLoad EnableSwitch
ReadOnly
Predictive Load Enable Switch function output sta-tus. Gives software Inactive/Active state
PC 3.x
0: Inactive1: Active
70
Addr. ControlDescriptionAccessParameterName40509 DSI / Dis-
crete In-puts
PTC ModeSwitch
ReadOnly
PTC Mode Switch function output status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
40510 DSI / Dis-crete In-puts
Extended Par-allel/Configur-able Input #32Switch
ReadOnly
This is the status of the Configurable Input #32. PC 3.x
0: Inactive
1: Active
40511 DSI / Dis-crete In-puts
Ramp Load/Unload Switch
ReadOnly
Ramp Load/Unload input software state status. PC 3.x0: Load1: Unload
40512 DSI / Dis-crete In-puts
Remote E−stop Switch
ReadOnly
Remote E−stop input software state status. Givessoftware Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
40513 DSI / Dis-crete In-puts
Remote StartSwitch
ReadOnly
Remote Start input software state status. Givessoftware Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
40514 DSI / Dis-crete In-puts
Retransfer In-hibit Switch
ReadOnly
Retransfer Inhibit input software state status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
40515 DSI / Dis-crete In-puts
Retransfer In-hibit/Configur-able Input #21Switch
ReadOnly
This is the status of the Configurable Input #21. PC 3.x
0: Inactive
1: Active
40516 DSI / Dis-crete In-puts
Rupture BasinSwitch
ReadOnly
Rupture Basin input software state status. Givessoftware Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
40517 DSI / Dis-crete In-puts
Rupture Ba-sin/Configur-able Input #12Switch
ReadOnly
This is the status of the Configurable Input #12. PC 2.x, PC3.x0: Inactive
1: Active
40518 DSI / Dis-crete In-puts
Speed DroopEnable Switch
ReadOnly
Monitors the Speed Droop Enable Switch function;Inactive or Active state.
PC 2.x, PC3.x
0: Inactive1: Active
40519 DSI / Dis-crete In-puts
Start TypeSwitch
ReadOnly
Start Type input software state status. Gives soft-ware Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
40520 DSI / Dis-crete In-puts
Sync EnableSwitch
ReadOnly
Sync Enable input software state status. Gives soft-ware Inactive/Active state
PC 3.x
0: Inactive1: Active
71
Addr. ControlDescriptionAccessParameterName40521 DSI / Dis-
crete In-puts
Sync Enable/ConfigurableInput #30Switch
ReadOnly
This is the status of the Configurable Input #30. PC 3.x
0: Inactive
1: Active
40522 DSI / Dis-crete In-puts
Tool Wake−upSwitch
ReadOnly
Tool Wake−up input software state status. Givessoftware Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
40523 DSI / Dis-crete In-puts
Transfer In-hibit Switch
ReadOnly
Transfer Inhibit input software state status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
40524 DSI / Dis-crete In-puts
Transfer In-hibit/Configur-able Input #20Switch
ReadOnly
This is the status of the Configurable Input #20. PC 3.x
0: Inactive
1: Active
40525 DSI / Dis-crete In-puts
Utility CB In-hibit/Configur-able Input #25Switch
ReadOnly
This is the status of the Configurable Input #25. PC 3.x
0: Inactive
1: Active
40526 DSI / Dis-crete In-puts
Utility CB PosB/Configur-able Input #23Switch
ReadOnly
This is the status of the Configurable Input #23. PC 3.x
0: Inactive
1: Active
40527 DSI / Dis-crete In-puts
Utility CBTripped/Confi-gurable Input#24 Switch
ReadOnly
This is the status of the Configurable Input #24. PC 3.x
0: Inactive
1: Active
40528 DSI / Dis-crete In-puts
Utility SingleMode Verify/ConfigurableInput #29Switch
ReadOnly
This is the status of the Configurable Input #29. PC 3.x
0: Inactive
1: Active
40529 DSI / Dis-crete In-puts
Utility CB In-hibit Switch
ReadOnly
Utility CB Inhibit input software state status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
40530 DSI / Dis-crete In-puts
Utility CB PosA Switch
ReadOnly
Utility CB Pos A input software state status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
40531 DSI / Dis-crete In-puts
Utility CB PosB Switch
ReadOnly
Utility CB Pos B input software state status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
40532 DSI / Dis-crete In-puts
Utility CBTrippedSwitch
ReadOnly
Utility CB Tripped input software state status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
72
Addr. ControlDescriptionAccessParameterName40533 DSI / Dis-
crete In-puts
Utility SingleMode VerifySwitch
ReadOnly
Utility Single Mode Verify input software state sta-tus. Gives software Inactive/Active state
PC 3.x
0: Inactive1: Active
40534 DSI / Dis-crete In-puts
Voltage DroopEnable Switch
ReadOnly
Voltage Droop Enable Switch function output sta-tus. Gives software Inactive/Active state.
PC 2.x, PC3.x
0: Inactive1: Active
40535 DSO / Dis-crete Out-puts
ConfigurableOutput #1Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40536 DSO / Dis-crete Out-puts
ConfigurableOutput #2Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40537 DSO / Dis-crete Out-puts
ConfigurableOutput #20Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active
40538 DSO / Dis-crete Out-puts
ConfigurableOutput #21Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active
40539 DSO / Dis-crete Out-puts
ConfigurableOutput #22Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active
40540 DSO / Dis-crete Out-puts
ConfigurableOutput #3Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40541 DSO / Dis-crete Out-puts
ConfigurableOutput #4Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40542 DSO / Dis-crete Out-puts
Delayed Off /ConfigurableOutput #10
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40543 DSO / Dis-crete Out-puts
Fuel ShutoffStatus
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40545 DSO / Dis-crete Out-puts
Genset CBOpen Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active
40546 DSO / Dis-crete Out-puts
Hold PowerOn Driver Sta-tus
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40547 DSO / Dis-crete Out-puts
KeyswitchStatus
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40548 DSO / Dis-crete Out-puts
KW/KVARLoad ShareRelay Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active
73
Addr. ControlDescriptionAccessParameterName40549 DSO / Dis-
crete Out-puts
Load Dump /ConfigurableOutput #11Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40550 DSO / Dis-crete Out-puts
Local Status /ConfigurableOutput #7Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40551 DSO / Dis-crete Out-puts
Master FirstStart OutputStatus
ReadOnly
Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active
40552 DSO / Dis-crete Out-puts
Oil PrimingPump / Confi-gurable Out-put #6 Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40553 DSO / Dis-crete Out-puts
Ready ToLoad /Confi-gurable Out-put #5 Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40554 DSO / Dis-crete Out-puts
Run Relay #1Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40555 DSO / Dis-crete Out-puts
Run Relay #2Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40556 DSO / Dis-crete Out-puts
Speed/Volt-age BiasRelay Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active
40557 DSO / Dis-crete Out-puts
Starter Status ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40558 DSO / Dis-crete Out-puts
Tool Wake−upDriver Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40559 DSO / Dis-crete Out-puts
Utility CBClose Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive
1: Active
40560 DSO / Dis-crete Out-puts
Utility CBOpen Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active
40561 EH / EventHandler
CommonAlarm FaultStatus
ReadOnly
The status of the Common Alarm Fault PC 2.x, PC3.x0: Inactive
1: Active
40562 EH / EventHandler
CommonShutdownCommand
ReadOnly
The status of the common shutdown command PC 2.x, PC3.x0: Inactive
1: Active
40563 EH / EventHandler
CommonShutdownEvent Status
ReadOnly
The status of the Common Shutdown Event PC 2.x, PC3.x0: Inactive
1: Active
74
Addr. ControlDescriptionAccessParameterName40564 EH / Event
HandlerCommonShutdown w/CooldownCommand
ReadOnly
The status of the common shutdown w/Cooldowncommand
PC 3.x
0: Inactive1: Active
40565 EH / EventHandler
CommonWarningEvent Status
ReadOnly
The status of the Common Warning Event PC 2.x, PC3.x0: Inactive
1: Active40566 EH / Event
HandlerDelayed Shut-down Flag
ReadOnly
Monitor point for the Delayed shutdown flag. PC 2.x, PC3.x0: Inactive
1: Active40567 EH / Event
HandlerDelayed Shut-down Timer
ReadOnly
Multiplier:0.1
Unit: sec-onds
Monitor point for theDelayed shutdown timer.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 3
Sign: U40568 EH / Event
HandlerDerate Re-quest
ReadOnly
Multiplier:1
Unit: % The requested % deratefrom the derate requestlogic
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 100
Sign: U40569 EH / Event
HandlerFault Detec-tion Reset
ReadOnly
The status of the Fault Detection Reset logic PC 2.x, PC3.x0: Inactive
1: Active40570 EH / Event
HandlerFault ResetCommand
ReadOnly
One shot due to fault reset switch being active. PC 2.x, PC3.x0: Inactive
1: Active40571 EH / Event
HandlerRemote Shut-down FaultReset Signal
ReadOnly
Becomes active when a remote fault reset signal hasbeen initiated.
PC 2.x, PC3.x
0: Inactive1: Active
40572 EH / EventHandler
ShutdownFault Reset
ReadOnly
The status of the Shutdown Fault reset logic. PC 2.x, PC3.x0: Inactive
1: Active40573 EH / Event
HandlerBattle ShortFlag
ReadOnly
Monitor point indicating the enabled/disabled statusof the battle short function
PC 2.x, PC3.x
0: Not Auto1: Auto
40574 GC / Start/Stop Con-trol
Auto Com-mand
ReadOnly
The output of the Auto Command OR logic PC 2.x, PC3.x0: Not Auto
1: Auto
75
Addr. ControlDescriptionAccessParameterName40575 GC / Start/
Stop Con-trol
Auto Com-mand Inputs
ReadOnly
Multiplier:1
Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
40576 GC / Auto-matic Volt-age Regu-lator
AVR Regula-tion Mode
ReadOnly
The operational mode of the AVR as a voltage or acurrent regulator
PC 2.x, PC3.x
0: Voltage1: Current
40577 GC /SpeedReference
Base Fre-quency
ReadOnly
Multiplier:0.001
Unit: Hz Provides a point to moni-tor the base frequency
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40578 GC /SpeedReference
Base Fre-quency
ReadOnly
Multiplier:0.001
Unit: Hz Provides a point to moni-tor the base frequency
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
40579 GC /ChargingAlternatorProtection
BatteryChargingFault Integra-tor
ReadOnly
Multiplier:0.1
Unit: sec-onds
Time spent while thecharger is sensed asfailed
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 300
Sign: U
40581 GC / Con-trolledShutdownControl
ControlledShutdownStatus
ReadOnly
Indicates status of the controlled shutdown logic PC 3.x0: Inactive1: Pending2: Shutdown
40582 GC / Pre-lube
Crank Al-lowed
ReadOnly
Monitor Point indicates if Cranking is Allowed by thePrelube State Machine
PC 2.x, PC3.x
0: False1: True
40583 GC /CrankingControl
Dead BatteryPreventionCounter
ReadOnly
Multiplier:1
Unit: Tracks the number ofcrank attempts in order tolimit the attempts whenthe battery is so low thatthe control resets
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 250
Sign: U
76
Addr. ControlDescriptionAccessParameterName40584 GC / Out-
putsDelayed OffCommand
ReadOnly
The status of the delayed run command off logic. PC 2.x, PC3.x0: Inactive
1: Active
40585 GC / Start/Stop Con-trol
EmergencyRemote Start
ReadOnly
The output of the Emergency Remote Start logic PC 2.x, PC3.x0: Stop
1: Start
40586 GC / Auto-matic Volt-age Regu-lator
ExcitationState
ReadOnly
Shows the enable status of the excitation enabled =regulator on.
PC 2.x, PC3.x
0: Disabled1: Enabled
40587 GC / Start/Stop Con-trol
ExerciseCommand
ReadOnly
The output of the Exercise Command OR logic PC 2.x, PC3.x0: Inactive
1: Active
40588 GC / Start/Stop Con-trol
ExerciseCommand In-puts
ReadOnly
Multiplier:1
Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 250
Sign: U
40589 GC / Start/Stop Con-trol
Exercise TimeRemaining
ReadOnly
Multiplier:0.1
Unit: hours Time remaining until ex-ercise stop sequence be-gins
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 25
Sign: U
40590 GC / Start/Stop Con-trol
Extended Par-allel SwitchCommand
ReadOnly
The output of the Extended Parallel Switch Com-mand OR logic
PC 3.x
0: Stop1: Start
40591 GC / Start/Stop Con-trol
Extended Par-allel SwitchCommand In-puts
ReadOnly
Multiplier:1
Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
40592 EH / EventHandler
Battle ShortCommand
ReadOnly
Indicates status of battle short inputs PC 2.x, PC3.x0: Inactive
1: Active
40593 EH / EventHandler
ShutdownFault Override
ReadOnly
Indicates whether or not the genset will ignore non−critical shutdown faults
PC 2.x, PC3.x
0: Inactive1: Active
77
Addr. ControlDescriptionAccessParameterName40595 GC /
SpeedReference
Final Fre-quency Refer-ence
ReadOnly
Multiplier:0.001
Unit: Hz The frequency scaledversion of the final speedreference
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 100
Sign: U
40596 GC /SpeedReference
Final Fre-quency Refer-ence
ReadOnly
Multiplier:0.001
Unit: Hz The frequency scaledversion of the final speedreference
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 100
Sign: U
40598 GC / Out-puts
Fuel ShutoffCommand
ReadOnly
The result of the FSO driver output command logic PC 2.x, PC3.x0: Inactive
1: Active
40599 GC / Start/Stop Con-trol
Genset RunCommand
ReadOnly
Genset run / stop states PC 2.x, PC3.x0: Emergency Stop
1: Stop2: Load Demand Stop3: Run
40600 DSI / Dis-crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
40601 DSI / Dis-crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
40602 DSI / Dis-crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
78
Addr. ControlDescriptionAccessParameterName40603 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40604 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40605 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40606 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40607 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
79
Addr. ControlDescriptionAccessParameterName40608 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40609 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40610 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40611 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40612 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
80
Addr. ControlDescriptionAccessParameterName40613 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40614 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40615 DSI / Dis-
crete In-puts
ConfigurableInput #1 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40620 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40621 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
81
Addr. ControlDescriptionAccessParameterName40622 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40623 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40624 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40625 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40626 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
82
Addr. ControlDescriptionAccessParameterName40627 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40628 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40629 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40630 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40631 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
83
Addr. ControlDescriptionAccessParameterName40632 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40633 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40634 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40635 DSI / Dis-
crete In-puts
ConfigurableInput #2 FaultText
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40640 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
84
Addr. ControlDescriptionAccessParameterName40641 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40642 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40643 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40644 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40645 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
85
Addr. ControlDescriptionAccessParameterName40646 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40647 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40648 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40649 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40650 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
86
Addr. ControlDescriptionAccessParameterName40651 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40652 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40653 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40654 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40655 DSI / Dis-
crete In-puts
ConfigurableInput #13Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
87
Addr. ControlDescriptionAccessParameterName40660 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40661 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40662 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40663 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40664 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
88
Addr. ControlDescriptionAccessParameterName40665 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40666 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40667 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40668 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40669 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
89
Addr. ControlDescriptionAccessParameterName40670 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40671 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40672 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40673 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C40674 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
90
Addr. ControlDescriptionAccessParameterName40675 DSI / Dis-
crete In-puts
ConfigurableInput #14Fault Text
Read/Write
Multiplier:1
Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
40800 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40801 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40802 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40803 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40804 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
91
Addr. ControlDescriptionAccessParameterName40805 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40806 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40807 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40808 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40809 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40810 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
92
Addr. ControlDescriptionAccessParameterName40811 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40812 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40813 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40814 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40815 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40816 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
93
Addr. ControlDescriptionAccessParameterName40817 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40818 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40819 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40820 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40821 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40822 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
94
Addr. ControlDescriptionAccessParameterName40823 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40824 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40825 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40826 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40827 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40828 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
95
Addr. ControlDescriptionAccessParameterName40829 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40830 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40831 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40832 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40833 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40834 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
96
Addr. ControlDescriptionAccessParameterName40835 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40836 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40837 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40838 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40839 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40840 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
97
Addr. ControlDescriptionAccessParameterName40841 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40842 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40843 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40844 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40845 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40846 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
98
Addr. ControlDescriptionAccessParameterName40847 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40848 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40849 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40850 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40851 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40852 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
99
Addr. ControlDescriptionAccessParameterName40853 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40854 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40855 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40856 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40857 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40858 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
100
Addr. ControlDescriptionAccessParameterName40859 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40860 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40861 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40862 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40863 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40864 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
101
Addr. ControlDescriptionAccessParameterName40865 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40866 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40867 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40868 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40869 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40870 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
102
Addr. ControlDescriptionAccessParameterName40871 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40872 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40873 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40874 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40875 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40876 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
103
Addr. ControlDescriptionAccessParameterName40877 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40878 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40879 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40880 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40881 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40882 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
104
Addr. ControlDescriptionAccessParameterName40883 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40884 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40885 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40886 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40887 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40888 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
105
Addr. ControlDescriptionAccessParameterName40889 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40890 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40891 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40892 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40893 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40894 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
106
Addr. ControlDescriptionAccessParameterName40895 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40896 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40897 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40898 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40899 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40900 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
107
Addr. ControlDescriptionAccessParameterName40901 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40902 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40903 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40904 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40905 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40906 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
108
Addr. ControlDescriptionAccessParameterName40907 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40908 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40909 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40910 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40911 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40912 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
109
Addr. ControlDescriptionAccessParameterName40913 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40914 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40915 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40916 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40917 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40918 PCCNet /I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
110
Addr. ControlDescriptionAccessParameterName40919 PCCNet /
I/O Module0 Exp.Board
Aux102 0Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40920 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40921 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40922 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40923 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40924 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
111
Addr. ControlDescriptionAccessParameterName40925 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40926 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40927 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40928 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40929 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40930 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
112
Addr. ControlDescriptionAccessParameterName40931 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40932 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40933 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40934 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40935 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40936 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
113
Addr. ControlDescriptionAccessParameterName40937 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40938 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40939 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 9 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40940 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40941 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40942 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
114
Addr. ControlDescriptionAccessParameterName40943 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40944 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40945 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40946 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40947 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40948 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
115
Addr. ControlDescriptionAccessParameterName40949 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40950 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40951 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40952 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40953 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40954 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
116
Addr. ControlDescriptionAccessParameterName40955 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40956 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40957 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40958 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40959 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 10 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40960 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
117
Addr. ControlDescriptionAccessParameterName40961 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40962 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40963 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40964 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40965 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40966 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
118
Addr. ControlDescriptionAccessParameterName40967 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40968 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40969 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40970 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40971 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40972 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
119
Addr. ControlDescriptionAccessParameterName40973 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40974 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40975 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40976 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40977 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40978 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
120
Addr. ControlDescriptionAccessParameterName40979 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 11 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40980 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40981 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40982 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40983 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40984 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
121
Addr. ControlDescriptionAccessParameterName40985 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40986 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40987 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40988 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40989 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40990 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
122
Addr. ControlDescriptionAccessParameterName40991 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40992 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40993 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40994 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40995 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
40996 PCCNet /I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
123
Addr. ControlDescriptionAccessParameterName40997 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40998 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C40999 PCCNet /
I/O Module1 Exp.Board
Aux102 1Fault 12 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C43000 ACM /
GensetCurrentand Power− %
Genset % Ap-plication L1Current
ReadOnly
Multiplier:0.1
Unit: % Monitors the genset ap-plication L1 current per-centage output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43001 ACM /
GensetCurrentand Power− %
Genset % Ap-plication L2Current
ReadOnly
Multiplier:0.1
Unit: % Monitors the genset ap-plication L2 current per-centage output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43002 ACM /
GensetCurrentand Power− %
Genset % Ap-plication L1kVA
ReadOnly
Multiplier:0.1
Unit: % Monitors the genset ap-plication L1 KVA percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
124
Addr. ControlDescriptionAccessParameterName43003 ACM /
GensetCurrentand Power− %
Genset % Ap-plication L3Current
ReadOnly
Multiplier:0.1
Unit: % Monitors the genset ap-plication L3 current per-centage output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43004 ACM /GensetCurrentand Power− %
Genset % Ap-plication L2kVA
ReadOnly
Multiplier:0.1
Unit: % Monitors the genset ap-plication L2 KVA percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43005 ACM /GensetCurrentand Power− %
Genset % Ap-plication L3kVA
ReadOnly
Multiplier:0.1
Unit: % Monitors the genset ap-plication L3 KVA percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43006 ACM /GensetCurrentand Power− %
Genset % Ap-plication L1kW
ReadOnly
Multiplier:0.1
Unit: % Monitors the genset ap-plication L1 KW percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43007 ACM /GensetCurrentand Power− %
Genset % Ap-plication L2kW
ReadOnly
Multiplier:0.1
Unit: % Monitors the genset ap-plication L2 KW percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43008 ACM /GensetCurrentand Power− %
Genset % Ap-plication L3kW
ReadOnly
Multiplier:0.1
Unit: % Monitors the genset ap-plication L3 KW percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43009 ACM /GensetCurrentand Power− %
Genset % Ap-plication TotalkVA
ReadOnly
Multiplier:0.1
Unit: % Monitors the total gensetapplication KVA percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
125
Addr. ControlDescriptionAccessParameterName43010 ACM /
GensetCurrentand Power− %
Genset % Ap-plication TotalkW
ReadOnly
Multiplier:0.1
Unit: % Monitors the total gensetapplication KW percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43011 ACM /GensetCurrentand Power− %
Genset %Standby L1kVA
ReadOnly
Multiplier:0.1
Unit: % Monitors the gensetstandby L1 KVA percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43012 ACM /GensetCurrentand Power− %
Genset %Standby L3kVA
ReadOnly
Multiplier:0.1
Unit: % Monitors the gensetstandby L3 KVA percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43013 ACM /GensetCurrentand Power− %
Genset %Standby L2kVA
ReadOnly
Multiplier:0.1
Unit: % Monitors the gensetstandby L2 KVA percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43014 ACM /GensetCurrentand Power− %
Genset %Standby L1kW
ReadOnly
Multiplier:0.1
Unit: % Monitors the gensetstandby L1 KW percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43015 ACM /GensetCurrentand Power− %
Genset %Standby L2kW
ReadOnly
Multiplier:0.1
Unit: % Monitors the gensetstandby L2 KW percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43016 ACM /GensetCurrentand Power− %
Genset %Standby L3kW
ReadOnly
Multiplier:0.1
Unit: % Monitors the gensetstandby L3 KW percent-age output.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
126
Addr. ControlDescriptionAccessParameterName43017 ACM /
GensetCurrentand Power− %
Genset %Standby TotalkVA
ReadOnly
Multiplier:0.1
Unit: % Monitors the total gensetstandby KVA percentageoutput.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43018 ACM /
GensetRatingsScalars
Genset Ap-plication kVArating
ReadOnly
Multiplier:0.1
Unit: kVA The genset KVA rating. PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43019 ACM /
GensetRatingsScalars
Genset Ap-plication kWrating
ReadOnly
Multiplier:0.1
Unit: kW The genset KW rating. PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43020 ACM /
GensetRatingsScalars
Genset Ap-plication Nom-inal Current
ReadOnly
Multiplier:1
Unit: Amps The value of the gensetapplication nominal cur-rent. Displayed as ”Gen-set Application RatedCurrent” in HMI
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43021 ACM /
VoltageGenset Aver-age Voltage%
ReadOnly
Multiplier:0.01
Unit: % Genset average voltagepercentage.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43030 ACM /
PowerGenset L1Power Factor
ReadOnly
Multiplier:0.01
Unit: PF Genset L1 power factor PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: S43031 ACM /
PhaseGenset L1L2Phase Differ-ence
ReadOnly
Multiplier:0.01
Unit: De-grees
Genset L1L2 voltagephase angle
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
127
Addr. ControlDescriptionAccessParameterName43032 ACM /
VoltageGenset L1L2Voltage%
ReadOnly
Multiplier:0.01
Unit: % Genset L1L2 voltage% PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43033 ACM /Voltage
Genset L1NVoltage%
ReadOnly
Multiplier:0.01
Unit: % Genset L1N voltage% PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43044 ACM /Power
Genset L2Power Factor
ReadOnly
Multiplier:0.01
Unit: PF Genset L2 power factor PC 2.x, PC3.x
Offset: 0 Lower Limit: −1.28Size (bits):8
Upper Limit: 1.27
Sign: S
43045 ACM /Phase
Genset L2L3Phase Differ-ence
ReadOnly
Multiplier:0.01
Unit: De-grees
Genset L2L3 voltagephase angle
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 655.3
Sign: U
43046 ACM /Voltage
Genset L2L3Voltage%
ReadOnly
Multiplier:0.01
Unit: % Genset L2L3 voltage% PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43047 ACM /Voltage
Genset L2NVoltage%
ReadOnly
Multiplier:0.01
Unit: % Genset L2N voltage% PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 655.3
Sign: U
43058 ACM /Power
Genset L3Power Factor
ReadOnly
Multiplier:0.01
Unit: PF Genset L3 power factor PC 2.x, PC3.x
Offset: 0 Lower Limit: −1.28Size (bits):8
Upper Limit: 1.22
Sign: S
43059 ACM /Phase
Genset L3L1Phase Differ-ence
ReadOnly
Multiplier:0.01
Unit: De-grees
Genset L3L1 voltagephase angle
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 655.3
Sign: U
128
Addr. ControlDescriptionAccessParameterName43060 ACM /
VoltageGenset L3L1Voltage%
ReadOnly
Multiplier:0.01
Unit: % Genset L3L1 voltage% PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 655.3
Sign: U43061 ACM /
VoltageGenset L3NVoltage%
ReadOnly
Multiplier:0.01
Unit: % Genset L3N voltage% PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43062 ACM /
GensetRatingsScalars
GensetStandby kVArating
ReadOnly
Multiplier:0.1
Unit: kVA KVA rating for the gensetin Standby configuration.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43063 ACM /
GensetRatingsScalars
GensetStandby kWrating
ReadOnly
Multiplier:0.1
Unit: kW KW rating for the gensetin Standby configuration.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43064 ACM /
GensetRatingsScalars
GensetStandby Nom-inal Current
ReadOnly
Multiplier:1
Unit: Amps The value of the gensetstandby nominal current.Displayed as ”GensetStandby Rated Current”in HMI
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43065 ACM / En-
ergyGenset TotalkVAh
ReadOnly
Multiplier:1
Unit: kVAh Genset total kVAh accu-mulation
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U43066 ACM / En-
ergyGenset TotalkVAh
ReadOnly
Multiplier:1
Unit: kVAh Genset total kVAh accu-mulation
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
129
Addr. ControlDescriptionAccessParameterName43067 ACM /
GensetCurrentand Power− %
Genset TotalkVARs perStandby kVA
ReadOnly
Multiplier:0.01
Unit: % Total KVAR’s per StandbyKVA.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43100 ACM /Voltage
Genset BusAverage Volt-age%
ReadOnly
Multiplier:0.01
Unit: % Genset Bus average volt-age%
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43111 ACM /Power
Genset BusL1 PowerFactor
ReadOnly
Multiplier:0.01
Unit: PF Genset Bus L1 powerfactor
PC 3.x
Offset: 0 Lower Limit: −1.28Size (bits):8
Upper Limit: 1.22
Sign: S
43112 ACM /Phase
Genset BusL1L2 PhaseDifference
ReadOnly
Multiplier:0.01
Unit: De-grees
Genset bus L1L2 voltagephase angle
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43113 ACM /Voltage
Genset BusL1L2 Volt-age%
ReadOnly
Multiplier:0.01
Unit: % Genset Bus L1L2 volt-age%
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43114 ACM /Voltage
Genset BusL1N Voltage%
ReadOnly
Multiplier:0.01
Unit: % Genset Bus L1N volt-age%
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43125 ACM /Power
Genset BusL2 PowerFactor
ReadOnly
Multiplier:0.01
Unit: PF Genset Bus L2 powerfactor
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: S
43126 ACM /Phase
Genset BusL2L3 PhaseDifference
ReadOnly
Multiplier:0.01
Unit: De-grees
Genset bus L2L3 voltagephase angle
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
130
Addr. ControlDescriptionAccessParameterName43127 ACM /
VoltageGenset BusL2L3 Volt-age%
ReadOnly
Multiplier:0.01
Unit: % Genset Bus L2L3 volt-age%
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43128 ACM /Voltage
Genset BusL2N Voltage%
ReadOnly
Multiplier:0.01
Unit: % Genset Bus L2N volt-age%
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43139 ACM /Power
Genset BusL3 PowerFactor
ReadOnly
Multiplier:0.01
Unit: PF Genset Bus L3 powerfactor
PC 3.x
Offset: 0 Lower Limit: −1.28Size (bits):8
Upper Limit: 1.22
Sign: S
43140 ACM /Phase
Genset BusL3L1 PhaseDifference
ReadOnly
Multiplier:0.01
Unit: De-grees
Genset bus L3L1 voltagephase angle
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43141 ACM /Voltage
Genset BusL3L1 Volt-age%
ReadOnly
Multiplier:0.01
Unit: % Genset Bus L3L1 volt-age%
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43142 ACM /Voltage
Genset BusL3N Voltage%
ReadOnly
Multiplier:0.01
Unit: % Genset Bus L3N volt-age%
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43143 ACM / En-ergy
Genset BusTotal kVAh
ReadOnly
Multiplier:1
Unit: kVAh Genset bus total kVAhaccumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
43144 ACM / En-ergy
Genset BusTotal kVAh
ReadOnly
Multiplier:1
Unit: kVAh Genset bus total kVAhaccumulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
131
Addr. ControlDescriptionAccessParameterName43145 ACM /
PhaseSync PhaseDifference
ReadOnly
Multiplier:0.01
Unit: deg Other meter to gensetmeter L1 voltage phaseangle
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43146 ACM / Ap-plicationConfigura-tion
ParallelingApplication
Read/Write
Determines what the function of the Other Meter is. PC 3.x0: None1: Utility2: Genset Bus
43147 ACM /Power
System TotalkVA
ReadOnly
Multiplier:1
Unit: kVA Sum of genset bus andutility bus kVA
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43148 ACM /Power
System TotalkVAR
ReadOnly
Multiplier:1
Unit: kVAR Sum of genset bus andutility bus kVAR
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43149 ACM /Power
System TotalkW
ReadOnly
Multiplier:1
Unit: kW Sum of genset bus andutility bus kW
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43150 ACM /Power
System TotalPower Factor
ReadOnly
Multiplier:0.01
Unit: PF System total power factor(totalized value of utilitybus plus genset bus)
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: S
43151 ACM /Voltage
Utility AverageVoltage%
ReadOnly
Multiplier:0.01
Unit: % Utility average voltage% PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43162 ACM /Power
Utility L1 Pow-er Factor
ReadOnly
Multiplier:0.01
Unit: PF Utility L1 power factor PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: S
132
Addr. ControlDescriptionAccessParameterName43163 ACM /
PhaseUtility L1L2Phase Differ-ence
ReadOnly
Multiplier:0.01
Unit: De-grees
Utility L1L2 voltagephase angle
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43164 ACM /Voltage
Utility L1L2Voltage%
ReadOnly
Multiplier:0.01
Unit: % Utility L1L2 voltage% PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43165 ACM /Voltage
Utility L1NVoltage%
ReadOnly
Multiplier:0.01
Unit: % Utility L1N voltage% PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43176 ACM /Power
Utility L2 Pow-er Factor
ReadOnly
Multiplier:0.01
Unit: PF Utility L2 power factor PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: S
43177 ACM /Phase
Utility L2L3Phase Differ-ence
ReadOnly
Multiplier:0.01
Unit: De-grees
Utility L2L3 voltagephase angle
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43178 ACM /Voltage
Utility L2L3Voltage%
ReadOnly
Multiplier:0.01
Unit: % Utility L2L3 voltage% PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43179 ACM /Voltage
Utility L2NVoltage%
ReadOnly
Multiplier:0.01
Unit: % Utility L2N voltage% PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43190 ACM /Power
Utility L3 Pow-er Factor
ReadOnly
Multiplier:0.01
Unit: PF Utility L3 power factor PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: S
133
Addr. ControlDescriptionAccessParameterName43191 ACM /
PhaseUtility L3L1Phase Differ-ence
ReadOnly
Multiplier:0.01
Unit: De-grees
Utility L3L1 voltagephase angle
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43192 ACM /Voltage
Utility L3L1Voltage%
ReadOnly
Multiplier:0.01
Unit: % Utility L3L1 voltage% PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43193 ACM /Voltage
Utility L3NVoltage%
ReadOnly
Multiplier:0.01
Unit: % Utility L3N voltage% PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43194 ACM / En-ergy
Utility TotalkVAh
ReadOnly
Multiplier:1
Unit: kVAh Utility total kVAh accu-mulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
43195 ACM / En-ergy
Utility TotalkVAh
ReadOnly
Multiplier:1
Unit: kVAh Utility total kVAh accu-mulation
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
43200 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43201 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43202 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
134
Addr. ControlDescriptionAccessParameterName43203 DR / Data
RecordingGenset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43204 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43205 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43206 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43207 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43208 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43209 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43210 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
135
Addr. ControlDescriptionAccessParameterName43211 DR / Data
RecordingGenset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43212 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43213 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43214 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43215 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43216 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43217 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43218 DR / DataRecording
Genset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
136
Addr. ControlDescriptionAccessParameterName43219 DR / Data
RecordingGenset ModelNumber
Read/Write
Multiplier:1
Unit: Number identifying themodel of this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43220 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43221 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43222 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43223 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43224 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43225 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43226 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
137
Addr. ControlDescriptionAccessParameterName43227 DR / Data
RecordingGenset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43228 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43229 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43230 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43231 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43232 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43233 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43234 DR / DataRecording
Genset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
138
Addr. ControlDescriptionAccessParameterName43235 DR / Data
RecordingGenset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C43236 DR / Data
RecordingGenset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C43237 DR / Data
RecordingGenset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C43238 DR / Data
RecordingGenset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C43239 DR / Data
RecordingGenset SerialNumber
Read/Write
Multiplier:1
Unit: Serial number of identify-ing this genset.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C43240 DR / Data
RecordingAlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C43241 DR / Data
RecordingAlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
139
Addr. ControlDescriptionAccessParameterName43242 DR / Data
RecordingAlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43243 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43244 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43245 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43246 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43247 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43248 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
140
Addr. ControlDescriptionAccessParameterName43249 DR / Data
RecordingAlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43250 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43251 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43252 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43253 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43254 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43255 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
141
Addr. ControlDescriptionAccessParameterName43256 DR / Data
RecordingAlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43257 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43258 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43259 DR / DataRecording
AlternatorModel Num-ber
Read/Write
Multiplier:1
Unit: Number identifying thisgensets alternator modelnumber.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43260 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43261 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43262 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
142
Addr. ControlDescriptionAccessParameterName43263 DR / Data
RecordingAlternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43264 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43265 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43266 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43267 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43268 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43269 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
143
Addr. ControlDescriptionAccessParameterName43270 DR / Data
RecordingAlternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43271 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43272 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43273 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43274 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43275 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43276 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
144
Addr. ControlDescriptionAccessParameterName43277 DR / Data
RecordingAlternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43278 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43279 DR / DataRecording
Alternator Se-rial Number
Read/Write
Multiplier:1
Unit: Unique number identify-ing this gensets alterna-tor serial number.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43280 DSI / Dis-crete In-puts
Coolant LevelSwitch
ReadOnly
Coolant Level input software state status. Gives soft-ware Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43281 DSI / Dis-crete In-puts
Coolant Level/ConfigurableInput #5Switch
ReadOnly
This is the status of the Configurable Input #5. PC 2.x, PC3.x0: Inactive
1: Active
43283 DSI / Dis-crete In-puts
Fault ResetSwitch
ReadOnly
Fault Reset input software state status. Gives soft-ware Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43284 DSI / Dis-crete In-puts
Fault Reset/ConfigurableInput #10Switch
ReadOnly
This is the status of the Configurable Input #10. PC 2.x, PC3.x0: Inactive
1: Active
43285 DSI / Dis-crete In-puts
Genset CB In-hibit/Configur-able Input #28Switch
ReadOnly
This is the status of the Configurable Input #28. PC 3.x
0: Inactive
1: Active
43286 DSI / Dis-crete In-puts
Genset CBPos B/Confi-gurable Input#26 Switch
ReadOnly
This is the status of the Configurable Input #26. PC 3.x
0: Inactive
1: Active
43287 DSI / Dis-crete In-puts
Genset CBTripped/Confi-gurable Input#27 Switch
ReadOnly
This is the status of the Configurable Input #27. PC 3.x
0: Inactive
1: Active
145
Addr. ControlDescriptionAccessParameterName43288 DSI / Dis-
crete In-puts
Genset CB In-hibit Switch
ReadOnly
Genset CB Inhibit input software state status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
43289 DSI / Dis-crete In-puts
Genset CBPos A Switch
ReadOnly
Genset CB Pos A input software state status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
43290 DSI / Dis-crete In-puts
Genset CBPos B Switch
ReadOnly
Genset CB Pos B input software state status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
43291 DSI / Dis-crete In-puts
Genset CBTrippedSwitch
ReadOnly
Genset CB Tripped input software state status. Givessoftware Inactive/Active state
PC 3.x
0: Inactive1: Active
43292 DSI / Dis-crete In-puts
Ground FaultSwitch
ReadOnly
Ground Fault Switch function output status. Givessoftware Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43293 DSI / Dis-crete In-puts
High Alt TempSwitch
ReadOnly
High Alt Temp Switch function output status. Givessoftware Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43295 DSI / Dis-crete In-puts
Load DemandStop/Confi-gurable Input#31 Switch
ReadOnly
This is the status of the Configurable Input #31. PC 3.x
0: Inactive
1: Active
43296 DSI / Dis-crete In-puts
Local E−stopSwitch
ReadOnly
Monitors the E−Stop switch. PC 2.x, PC3.x0: Inactive
1: Active
43297 DSI / Dis-crete In-puts
Low Coolant#2 Switch
ReadOnly
Low Coolant #2 Switch function output status. Givessoftware Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43298 DSI / Dis-crete In-puts
Low Fuel InDay TankSwitch
ReadOnly
Low Fuel In Day Tank Switch function output status.Gives software Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43299 DSI / Dis-crete In-puts
Low Fuel InDay TankSwitch
ReadOnly
Low Fuel In Day Tank Switch function output status.Gives software Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43300 ACM / Ap-plicationConfigura-tion
Genset BusDelta/WyeConnection
Read/Write
Delta or Wye for Utility connection PC 3.x
0: Delta
1: Wye
146
Addr. ControlDescriptionAccessParameterName43301 ACM /
VoltageGenset BusNominal Volt-age
Read/Write
Multiplier:1
Unit: Vac Genset Bus nominal volt-age
PC 3.x
Offset: 0 Lower Limit: 110Size (bits):16
Upper Limit: 45000
Sign: U
43302 ACM / Ap-plicationConfigura-tion
Genset Delta/Wye Connec-tion
Read/Write
Delta or Wye for Genset connection PC 2.x, PC3.x0: Delta
1: Wye
43303 ACM /Voltage
Genset Nomi-nal Voltage
Read/Write
Multiplier:1
Unit: Vac Genset nominal line−linevoltage
PC 2.x, PC3.x
Offset: 0 Lower Limit: 110Size (bits):16
Upper Limit: 45000
Sign: U
43304 ACM / Ap-plicationConfigura-tion
Single/3Phase Con-nection
Read/Write
Setup mode interlocked. Genset’s single phase/3phase metering setup configuration.
PC 2.x, PC3.x
0: Single Phase1: Three Phase
43306 ACM / Ap-plicationConfigura-tion
Utility Delta/Wye Connec-tion
Read/Write
Delta or Wye for Utility connection PC 3.x
0: Delta
1: Wye
43307 ACM /Voltage
Utility NominalVoltage
Read/Write
Multiplier:1
Unit: Vac Utility nominal voltage PC 3.x
Offset: 0 Lower Limit: 110Size (bits):16
Upper Limit: 45000
Sign: U
43309 AP / Fre-quencyProtection
Overfrequen-cy Enable
Read/Write
Enables overfrequency diagnostic witness test. PC 2.x, PC3.x0: Disabled
1: Enabled
43310 AP / PowerFlow Moni-tor
OverloadWarning SetTime
Read/Write
Multiplier:1
Unit: sec-onds
The time delay until anoverload condition is re-ported as a fault
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 120
Sign: U
43311 AP / PowerFlow Moni-tor
OverloadWarningThreshold
Read/Write
Multiplier:0.01
Unit: % Sets the Overload Warn-ing fault trip threshold aspercentage of genset ap-plication kW rating.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 80Size (bits):16
Upper Limit: 140
Sign: U
147
Addr. ControlDescriptionAccessParameterName43338 CAN /
CANDatalink
CAN FailureRetries
Read/Write
Multiplier:1
Unit: Sets the maximum num-ber of CAN communica-tion retries
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 10
Sign: U
43340 CM / Con-trollerModes
Max SetupMode Time
Read/Write
Multiplier:1
Unit: Sec-onds
Max time allowed in Set-up Mode.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 30Size (bits):16
Upper Limit: 3600
Sign: U
43341 CM / Con-trollerModes
Power DownMode Enable
Read/Write
Trim to enable sleep mode PC 2.x, PC3.x0: Disable
1: Enable
43342 CM / Con-trollerModes
Power DownMode TimeDelay
Read/Write
Multiplier:1
Unit: sec-onds
Timer setting for the Pow-er Down delay feature
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 600
Sign: U
43343 CM / Con-trollerModes
Setup ModeEnable
Read/Write
Volatile to allow entry into Setup Mode PC 2.x, PC3.x0: Disable
1: Enable
43344 DR / RealTime Clock
Clock Date Read/Write
Multiplier:1
Unit: Use to set or read thecurrent date.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 31
Sign: U
43345 DR / RealTime Clock
Clock Hour Read/Write
Multiplier:1
Unit: Use to set or read thecurrent hour.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 23
Sign: U
43346 DR / RealTime Clock
Clock Minute Read/Write
Multiplier:1
Unit: Use to set or read thecurrent minute.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 59
Sign: U
43347 DR / RealTime Clock
Clock Mode Read/Write
Use to set the real time clock and save settings.0: Normal PC 2.x, PC
3.x1: Set Clock2: Save Clock
148
Addr. ControlDescriptionAccessParameterName43348 DR / Real
Time ClockClock Month Read/
WriteMultiplier:1
Unit: Use to set or read thecurrent month.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 12
Sign: U
43349 DR / RealTime Clock
Clock Second Read/Write
Multiplier:1
Unit: Use to set or read thecurrent second.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 59
Sign: U
43350 DR / RealTime Clock
Clock Year Read/Write
Multiplier:1
Unit: Use to set or read thecurrent year.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 99
Sign: U
43351 DR / RealTime Clock
Daylight Sav-ings End Hour
Read/Write
Multiplier:1
Unit: Use to set the hour of theday when daylight sav-ings time ends.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 2Size (bits):8
Upper Limit: 19
Sign: U
43352 DR / RealTime Clock
Daylight Sav-ings EndMonth
Read/Write
Multiplier:1
Unit: Use to set the monthwhen daylight savingstime ends.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 12
Sign: U
43353 DR / RealTime Clock
Daylight Sav-ings EndWeek Occur-rence inMonth
Read/Write
Use to set the week of the month when daylight sav-ings time ends.
PC 2.x, PC3.x
0: First Occurrence1: Second Occurrence2: Third Occurrence3: Fourth Occurrence4: Last Occurrence
43354 DR / RealTime Clock
Daylight Sav-ings Start Day
Read/Write
Use to set the day of the week when daylight savingstime starts.
PC 2.x, PC3.x
0: Sunday1: Monday2: Tuesday3: Wednesday4: Thursday5: Friday6: Saturday
149
Addr. ControlDescriptionAccessParameterName43355 DR / Real
Time ClockDaylight Sav-ings StartHour
Read/Write
Multiplier:1
Unit: Use to set the hour of theday when daylight sav-ings time starts.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 2Size (bits):8
Upper Limit: 19
Sign: U
43356 DR / RealTime Clock
Daylight Sav-ings StartMonth
Read/Write
Multiplier:1
Unit: Use to set the monthwhen daylight savingstime starts.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 12
Sign: U
43357 DR / RealTime Clock
Daylight Sav-ings StartWeek Occur-rence inMonth
Read/Write
Use to set the week of the month when daylight sav-ings time starts.
PC 2.x, PC3.x
0: First Occurrence1: Second Occurrence2: Third Occurrence3: Fourth Occurrence4: Last Occurrence
43358 DR / RealTime Clock
Daylight Sav-ings Time Ad-justment
Read/Write
Multiplier:1
Unit: Min-utes
Use to set the amount ofdaylight savings time ad-justment applied.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 120
Sign: U
43359 DR / RealTime Clock
Daylight Sav-ings Time En-able
Read/Write
Use to enable the daylight savings time feature. PC 2.x, PC3.x0: Disabled
1: Enabled
43360 DR / Exer-ciseScheduler
ExerciseScheduler En-able
Read/Write
Enables the exercise scheduler. PC 2.x, PC3.x0: Disabled
1: Enabled
43361 DR / DataRecording
Reset FuelConsumption
Read/Write
The reset trip fuel consumption command. PC 2.x, PC3.x0: Inactive
1: Active
43362 DR / DataRecording
Reset Runs Read/Write
The reset runs command. PC 2.x, PC3.x0: Inactive
1: Active
43363 DR / DataRecording
Reset StartAttempts
Read/Write
The reset start attempts command. PC 2.x, PC3.x0: Inactive
1: Active
43364 DR / Exer-ciseScheduler
Scheduler Ex-ception Select
Read/Write
Multiplier:1
Unit: Used to select an excep-tion to adjust.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 6
Sign: U
150
Addr. ControlDescriptionAccessParameterName43365 DR / Exer-
ciseScheduler
Scheduler Ex-ception x Date
Read/Write
Multiplier:1
Unit: Used to adjust the datefor the selected excep-tion.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 31
Sign: U43366 DR / Exer-
ciseScheduler
Scheduler Ex-ception xDuration Days
Read/Write
Multiplier:1
Unit: Used to adjust the lengthin days for the selectedexception.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 44
Sign: U43367 DR / Exer-
ciseScheduler
Scheduler Ex-ception xDurationHours
Read/Write
Multiplier:1
Unit: Used to adjust the lengthin hours for the selectedexception.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 23
Sign: U43368 DR / Exer-
ciseScheduler
Scheduler Ex-ception xDuration Min-utes
Read/Write
Multiplier:1
Unit: Used to adjust the lengthin minutes for the se-lected exception.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 59
Sign: U43369 DR / Exer-
ciseScheduler
Scheduler Ex-ception x En-able
Read/Write
Used to enable or disable the selected exception. PC 2.x, PC3.x0: Disable
1: Enable43370 DR / Exer-
ciseScheduler
Scheduler Ex-ception xHour
Read/Write
Multiplier:1
Unit: Used to adjust the start-ing hour for the selectedexception.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 23
Sign: U43371 DR / Exer-
ciseScheduler
Scheduler Ex-ception x Min-ute
Read/Write
Multiplier:1
Unit: Used to adjust the start-ing minute for the se-lected exception.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 59
Sign: U
151
Addr. ControlDescriptionAccessParameterName43372 DR / Exer-
ciseScheduler
Scheduler Ex-ception xMonth
Read/Write
Multiplier:1
Unit: Used to adjust the start-ing month for the se-lected exception.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 12
Sign: U
43373 DR / Exer-ciseScheduler
Scheduler Ex-ception x Re-peat
Read/Write
Used to adjust the repeat interval for the selected ex-ception.
PC 2.x, PC3.x
0: Once Only1: Every Year
43374 DR / Exer-ciseScheduler
SchedulerProgram Se-lect
Read/Write
Multiplier:1
Unit: Used to select a programto adjust.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 12
Sign: U
43375 DR / Exer-ciseScheduler
SchedulerProgram xDurationHours
Read/Write
Multiplier:1
Unit: Used to adjust the lengthin hours for the selectedprogram.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 23
Sign: U
43376 DR / Exer-ciseScheduler
SchedulerProgram xDuration Min-utes
Read/Write
Multiplier:1
Unit: Used to adjust the lengthin minutes for the se-lected program.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 59
Sign: U
43377 DR / Exer-ciseScheduler
SchedulerProgram xEnable
Read/Write
Used to enable or disable the selected program. PC 2.x, PC3.x0: Disable
1: Enable
43378 DR / Exer-ciseScheduler
SchedulerProgram xRepeat Inter-val
Read/Write
Used to adjust the repeat interval for the selected pro-gram.
PC 2.x, PC3.x
0: Once1: Every Week2: Every 2 Weeks3: Every 3 Weeks4: Every 4 Weeks5: Every 5 Weeks6: First Week of Month7: Second Week of Month8: Third Week of Month9: Fourth Week of Month10: Last Week of Month
152
Addr. ControlDescriptionAccessParameterName43379 DR / Exer-
ciseScheduler
SchedulerProgram xRun Mode
Read/Write
Used to adjust the run mode for the selected program. PC 2.x, PC3.x0: No Load
1: With Load2: Extended Parallel
43380 DR / Exer-ciseScheduler
SchedulerProgram xStart Day
Read/Write
Used to adjust the start day of the week for the se-lected program.
PC 2.x, PC3.x
0: Sunday1: Monday2: Tuesday3: Wednesday4: Thursday5: Friday6: Saturday
43381 DR / Exer-ciseScheduler
SchedulerProgram xStart Hour
Read/Write
Multiplier:1
Unit: Used to adjust the starthour for the selected pro-gram.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 23
Sign: U43382 DR / Exer-
ciseScheduler
SchedulerProgram xStart Minute
Read/Write
Multiplier:1
Unit: Used to adjust the startminute for the selectedprogram.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 59
Sign: U43383 DR / Real
Time ClockDaylight Sav-ings End Day
Read/Write
Use to set the day of the week when daylight savingstime ends.
PC 2.x, PC3.x
0: Sunday1: Monday2: Tuesday3: Wednesday4: Thursday5: Friday6: Saturday
43501 GC / Start/Stop Con-trol
Genset RunType
ReadOnly
Source or type of current genset run (if running) orprevious genset run (if stopped)
PC 2.x, PC3.x
0: Emergency Remote Start1: Non Emergency Remote Start2: Load Demand Start3: Manual Run4: Exercise
43502 GC / Start/Stop Con-trol
Idle RatedCommand
ReadOnly
The output command of the Idle/Rated Logic PC 2.x, PC3.x0: Idle
1: Rated
153
Addr. ControlDescriptionAccessParameterName43503 GC / Start/
Stop Con-trol
Idle Request ReadOnly
Indicates a request to go to manual idle. Manual idleallowed if breaker is open or not controlled
PC 2.x, PC3.x
0: False1: True
43506 GC / Over-loadProtection
Load DumpCommand
ReadOnly
Monitors the software command to the load dumpdriver output
PC 2.x, PC3.x
0: Inactive1: Active
43507 GC / Over-loadProtection
Load DumpOverloadCondition
ReadOnly
Monitors the state of the load dump overload detec-tion algorithm
PC 2.x, PC3.x
0: Inactive1: Active
43508 GC / Over-loadProtection
Load DumpUnderfre-quency Con-dition
ReadOnly
The state of the load dump underfrequency detectionalgorithm
PC 2.x, PC3.x
0: Inactive1: Active
43509 GC / Bat-teryProtection
Low BatteryVoltage Run-ning Thresh-old
ReadOnly
Multiplier:0.1
Unit: Vdc The low battery voltagethreshold when the gen-set is in rated mode
PC 2.x, PC3.x
Offset: 0 Lower Limit: 12Size (bits):16
Upper Limit: 28
Sign: U
43510 GC / Bat-teryProtection
Low BatteryVoltageStoppedThreshold
ReadOnly
Multiplier:0.1
Unit: Vdc The low battery voltagethreshold when the gen-set is not in rated mode
PC 2.x, PC3.x
Offset: 0 Lower Limit: 11Size (bits):16
Upper Limit: 26
Sign: U
43511 GC / Bat-teryProtection
Low BatteryVoltageThreshold
ReadOnly
Multiplier:0.1
Unit: Vdc The selection of the run-ning or stopped threshold
PC 2.x, PC3.x
Offset: 0 Lower Limit: 11Size (bits):16
Upper Limit: 28
Sign: U
43512 GC / Start/Stop Con-trol
Manual Com-mand
ReadOnly
The output of the Manual Command OR logic PC 2.x, PC3.x0: Not Manual
1: Manual
43513 GC / Start/Stop Con-trol
Manual Com-mand Inputs
ReadOnly
Multiplier:1
Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
154
Addr. ControlDescriptionAccessParameterName43515 GC / Pre-
lubeOil PrimingPump Com-mand
ReadOnly
The Prelube Driver Command. PC 2.x, PC3.x0: Inactive
1: Active
43516 GC / Pre-lube
Prelube Mode ReadOnly
Set to a required mode based on the type of startingrequirement
PC 2.x, PC3.x
0: Crank After Prelube1: Crank With Prelube2: Prelube Only
43517 GC / Pre-lube
Prelube State ReadOnly
The monitor point for the prelube state. PC 2.x, PC3.x0: Complete
1: Armed2: Prelube Output ON3: Prelube Output OFF4: Enable Crank
43518 GC / Start/Stop Con-trol
PTC GensetOperatingMode
ReadOnly
Current mode for the genset operation part of the PTCfunction
PC 3.x
0: Off1: Manual2: Normal3: Normal Override4: Test5: Exercise6: Utility Fail7: Extended Parallel
43519 GC / Start/Stop Con-trol
PTC ModeSwitch Com-mand
ReadOnly
The output of the PTC Mode Switch Command ORlogic
PC 3.x
0: Inactive1: Active
43520 GC / Start/Stop Con-trol
PTC ModeSwitch Com-mand Inputs
ReadOnly
Multiplier:1
Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on.
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
43521 GC / Start/Stop Con-trol
PTC Status ReadOnly
Indicates what the current state is of PTC control ac-tion
PC 3.x
0: Off/ Not Enabled1: Manual Mode2: Normal Utility3: Retransfer4: Retransfer Override5: Emergency Test6: Normal Test7: Exercise8: Utility Failure9: Extended Parallel
155
Addr. ControlDescriptionAccessParameterName43522 GC / Start/
Stop Con-trol
PTC TransferPair Operat-ing Mode
ReadOnly
operation mode for the breaker pair portion of thePTC function
PC 3.x
0: Off1: Manual2: Normal3: Normal Override4: Test5: Exercise6: Utility Fail7: Extended Parallel
43523 GC / Out-puts
Ready toLoad Com-mand
ReadOnly
The state that the Ready to Load Driver output is be-ing commanded to
PC 2.x, PC3.x
0: Inactive1: Active
43524 GC / Start/Stop Con-trol
Remote StartCommand
ReadOnly
The output of the Remote Start Command OR logic PC 2.x, PC3.x0: Stop
1: Start
43525 GC / Start/Stop Con-trol
Remote StartCommand In-puts
ReadOnly
Multiplier:1
Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
43526 GC / Start/Stop Con-trol
Remote StartState
ReadOnly
Status of remote start and load demand stop inputs PC 2.x, PC3.x0: Off
1: Remote Start2: Load Demand Stop3: Load Demand Start
43527 GC / Auto-matic Volt-age Regu-lator
RMS Regula-tion Error
ReadOnly
Multiplier:0.01
Unit: % The RMS voltage (or cur-rent) error at the AVR
PC 2.x, PC3.x
Offset: 0 Lower Limit: −100Size (bits):16
Upper Limit: 100
Sign: S
43528 GC / Start/Stop Con-trol
Run Com-mand
ReadOnly
The signal that is commanding a change to the runmode
PC 2.x, PC3.x
0: Off1: Run
43529 GC / Start/Stop Con-trol
Run RelayCommand
ReadOnly
0: Inactive PC 2.x, PC3.x
1: Active
43530 GC / Out-puts
Speed andVoltage BiasRelay Com-mand
ReadOnly
Monitor point for the command which closes the on−board relay enabling the voltage and speed bias out-puts.
PC 3.x
0: Inactive1: Active
156
Addr. ControlDescriptionAccessParameterName43531 GC /
SpeedReference
Speed BiasCommand
ReadOnly
Multiplier:0.01
Unit: % Indicates amount ofspeed bias offset GCS iscommanding to ECS gov-ernor or external gover-nor
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit:
Sign: S43533 GC / Start/
Stop Con-trol
Start Count-down
ReadOnly
Multiplier:1
Unit: sec-onds
Time remaining until startis initiated
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 300
Sign: U43534 GC /
CrankingControl
Start Discon-nect Logic
ReadOnly
Monitor point for the Start Disconnect logic. True =genset sensed above start disconnect speed.
PC 2.x, PC3.x
0: False1: True
43536 GC / Start/Stop Con-trol
Start TypeCommand
ReadOnly
The output of the Start Type Command OR logic PC 2.x, PC3.x0: Emergency
1: Non Emergency43537 GC / Start/
Stop Con-trol
Start TypeCommand In-puts
ReadOnly
Multiplier:1
Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U43538 GC /
CrankingControl
Starter Com-mand
ReadOnly
The state the Starter Command output from thecranking algorithm is being commanded to
PC 2.x, PC3.x
0: Inactive1: Active
43539 GC / Start/Stop Con-trol
Stop Count-down
ReadOnly
Multiplier:1
Unit: sec-onds
Time remaining until gen-set stops
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 5000
Sign: U43540 GC / Start/
Stop Con-trol
Switch PanelRun Request
ReadOnly
Status of run and exercise commands from displaypanel
PC 2.x, PC3.x
0: None1: Manual2: Exercise
157
Addr. ControlDescriptionAccessParameterName43542 GC / Volt-
age Set-point
Target Voltage ReadOnly
Multiplier:0.01
Unit: % The target voltage with-out ramping and torquematch voltage rolloff ef-fects
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 150
Sign: U
43543 GC / Start/Stop Con-trol
Time At NoLoad
ReadOnly
Multiplier:1
Unit: sec-onds
Amount of time the gen-set has run at no load
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 600
Sign: U
43544 GC / Start/Stop Con-trol
Time at RatedCooldown
ReadOnly
Multiplier:1
Unit: sec-onds
Amount of time spend inRated Cooldown
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 5000
Sign: U
43546 GC / Auto-matic Volt-age Regu-lator
Voltage BiasCommand
ReadOnly
Multiplier:0.01
Unit: % Indicates amount of volt-age bias offset GCS iscommanding to an exter-nal regulator
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit:
Sign: S
43547 GC / Volt-age Set-point
Voltage Set-point
ReadOnly
Multiplier:0.01
Unit: % The voltage setpointcommand
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 150
Sign: U
43550 GC / Bat-teryProtection
Weak BatteryThreshold
ReadOnly
Multiplier:0.1
Unit: Vdc Monitor point for theweak battery voltagethreshold
PC 2.x, PC3.x
Offset: 0 Lower Limit: 6Size (bits):16
Upper Limit: 16
Sign: U
43551 GC / Bat-teryProtection
Weak BatteryVoltage SetTime
Read/Write
Multiplier:1
Unit: sec-onds
The time delay until aweak battery condition isreported as a fault
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):16
Upper Limit: 5
Sign: U
158
Addr. ControlDescriptionAccessParameterName43552 PARCTL /
Meteringand Refer-enceSelection
ParallelingVoltage RefOffset
ReadOnly
Multiplier:0.01
Unit: % voltage offset to voltageregulator for parallelingfunction
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43553 PARCTL /Synchro-nizer
SynchronizerStatus
ReadOnly
indicates whether synchronizer is on or off PC 3.x0: Synchronizer Off1: Synchronizer On
43554 PARST /PTC Tim-ers
Active Transi-tion Timer
ReadOnly
Multiplier:0.1
Unit: sec-onds
countdown value of theactive transition timer
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43555 PARST /PTC Tim-ers
Active Transi-tion Type
ReadOnly
indicates the active transition type for PTC PC 3.x0: None1: Programmed Transition2: Transfer3: Retransfer4: Max Parallel
43556 PARST /First Start
ArbitrationState
ReadOnly
indicates current arbitration state PC 3.x0: Off1: Arbitrate02: Winner3: Arbitrate14: Sleep
43557 PARST /First Start
ArbitrationTimer
ReadOnly
Multiplier:1
Unit: msec arbitration loop count-down timer
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43558 PARST /ParallelingControlMode
ES State ReadOnly
internal paralleling status variable PC 3.x0: Standby1: Dead Bus2: Synchronize3: Load Share4: Load Govern
43559 PARST /First Start
First StartState
ReadOnly
indicates status of the first start system PC 3.x0: First Start Not Allowed1: First Start Requested2: First Start Permitted
43560 PARST /CircuitBreaker
Genset CBClose Com-mand
ReadOnly
genset cb close command status PC 3.x0: Inactive1: Active
159
Addr. ControlDescriptionAccessParameterName43561 PARST /
CircuitBreaker
Genset CBFail To CloseLockout
ReadOnly
status of gen fail to close lockout function PC 3.x0: Inactive1: Active
43562 PARST /CircuitBreaker
Genset CBPosition Sta-tus
ReadOnly
indicates genset breaker position PC 3.x0: Open1: Closed2: Not Available
43563 PARST /PTCSourceAvailability
Genset Avail-ability Status
ReadOnly
indicates status of the genset source PC 3.x0: Not Available1: Available2: Unknown
43564 PARST /Dead BusClose
Bus Status ReadOnly
indicates status of the bus PC 3.x0: Unavailable1: Dead2: Live
43565 PARST /CircuitBreaker
Genset CB In-hibit Com-mand
ReadOnly
genset cb inhibit command PC 3.x0: Inactive1: Active
43566 PARST /CircuitBreaker
Genset CBTripped Com-mand
ReadOnly
genset cb tripped command PC 3.x0: Inactive1: Active
43567 PARST /CircuitBreaker
Genset Cur-rent BasedBreaker Posi-tion
ReadOnly
indicates genset breaker position based on current PC 3.x
0: Unknown
1: Closed
43568 PARST /PTC Sen-sors
Genset Fre-quency LowerDrop−OutThreshold
ReadOnly
Multiplier:0.1
Unit: Hz indicates the lower drop−out threshold in Hz forgenset frequency sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43569 PARST /
PTC Sen-sors
Genset Fre-quency LowerPick−UpThreshold
ReadOnly
Multiplier:0.1
Unit: Hz indicates the lower pick−up threshold in Hz forgenset frequency sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43570 PARST /
PTC Sen-sors
Genset Fre-quency Sen-sor Status
ReadOnly
indicates genset frequency sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out
160
Addr. ControlDescriptionAccessParameterName43571 PARST /
PTC Sen-sors
Genset Fre-quency UpperDrop−OutThreshold
ReadOnly
Multiplier:0.1
Unit: Hz indicates the upper drop−out threshold in Hz forgenset frequency sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43572 PARST /PTC Sen-sors
Genset Fre-quency UpperPick−UpThreshold
ReadOnly
Multiplier:0.1
Unit: Hz indicates the upper pick−up threshold in Hz forgenset frequency sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43573 PARST /PTC Sen-sors
Genset Lossof Phase Sen-sor Status
ReadOnly
indicates genset loss of phase sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out
43574 PARST /PTC Sen-sors
Genset Over-voltage Drop−Out Threshold
ReadOnly
Multiplier:1
Unit: Vac indicates the drop−outthreshold in volts for gen-set overvoltage sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43575 PARST /PTC Sen-sors
Genset Over-voltage Pick−Up Threshold
ReadOnly
Multiplier:1
Unit: Vac indicates the pick−upthreshold in volts for gen-set overvoltage sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43576 PARST /PTC Sen-sors
Genset Over-voltage Sen-sor Status
ReadOnly
indicates genset overvoltage sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out
43577 PARST /PTC Sen-sors
Genset PhaseRotation Sen-sor Status
ReadOnly
indicates genset phase rotation sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out
43578 PARST /PTC Sen-sors
Genset Un-dervoltageDrop−OutThreshold
ReadOnly
Multiplier:1
Unit: Vac indicates the drop−outthreshold in volts for gen-set undervoltage sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
161
Addr. ControlDescriptionAccessParameterName43579 PARST /
PTC Sen-sors
Genset Un-dervoltagePick−UpThreshold
ReadOnly
Multiplier:1
Unit: Vac indicates the pick−upthreshold in volts for gen-set undervoltage sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43580 PARST /PTC Sen-sors
Genset Un-dervoltageSensor Status
ReadOnly
indicates genset undervoltage sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out
43581 PARST /First Start
Master FirstStart OutputCommand
ReadOnly
status of the first start output command PC 3.x0: Inactive1: Active
43582 PARST /PTC Tim-ers
MaximumParallel Timer
ReadOnly
Multiplier:0.1
Unit: sec-onds
countdown value of themaximum parallel timer
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43583 PARST /PTC Tim-ers
MaximumParallel TimerStatus
ReadOnly
indicates status of the maximum parallel timer PC 3.x0: Not Timing1: Timing2: Expired
43584 PARST /ParallelingControlMode
ParallelingSpeed ControlMode
ReadOnly
indicates which speed control algorithm is in effect PC 2.x, PC3.x0: Isochronous
1: Droop2: Synchronize3: Load Share4: Load Govern
43585 PARST /ParallelingControlMode
ParallelingVoltage Con-trol Mode
ReadOnly
indicates which voltage control algorithm is in effect PC 2.x, PC3.x0: Isochronous
1: Droop2: Synchronize3: Load Share4: Load Govern
43586 PARST /PTC Tim-ers
ProgrammedTransitionTimer
ReadOnly
Multiplier:0.1
Unit: sec-onds
countdown value of theprogrammed transitiontimer
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43587 PARST /PTC Tim-ers
ProgrammedTransitionTimer Status
ReadOnly
indicates status of the programmed transition timer PC 3.x0: Not Timing1: Timing2: Expired
162
Addr. ControlDescriptionAccessParameterName43588 PARST /
PTC En-ables
PTC EnableStatus
ReadOnly
indicates if PTC functions are running PC 3.x0: Disable1: Enable
43589 PARST /PTC StateMachine
PTC Operat-ing TransitionType
ReadOnly
indicates the transition type currently in effect PC 3.x0: Open Transition1: Hard Closed Transition2: Soft Closed Transition
43590 PARST /PTC StateMachine
PTC State ReadOnly
indicates the connected state of the Power TransferControl
PC 3.x
0: PTC Not Enabled1: No Source Connected2: Utility Connected3: Genset Connected4: Paralleled
43591 PARST /PTC Tim-ers
RetransferTimer
ReadOnly
Multiplier:0.1
Unit: sec-onds
countdown value of theretransfer timer
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43592 PARST /PTC Tim-ers
RetransferTimer Status
ReadOnly
indicates status of the retransfer timer PC 3.x0: Not Timing1: Timing2: Expired
43593 PARST /ParallelingControlMode
Speed DroopEnable Com-mand
ReadOnly
command value of speed droop enable PC 2.x, PC3.x0: Inactive
1: Active
43594 PARST /ParallelingControlMode
Speed DroopStatus
ReadOnly
indicates whether or not speed droop is in effect PC 2.x, PC3.x0: Droop Disabled
1: Droop Enabled
43595 PARST /PTC Tim-ers
Transfer Tim-er
ReadOnly
Multiplier:0.1
Unit: sec-onds
countdown value of thetransfer timer
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43596 PARST /PTC Tim-ers
Transfer Tim-er Status
ReadOnly
indicates status of the transfer timer PC 3.x0: Not Timing1: Timing2: Expired
43597 PARST /CircuitBreaker
Utility CBClose Com-mand
ReadOnly
utility cb close command status PC 3.x0: Inactive1: Active
43598 PARST /CircuitBreaker
Utility CBOpen Com-mand
ReadOnly
utility cb open command status PC 3.x0: Inactive1: Active
163
Addr. ControlDescriptionAccessParameterName43599 PARST /
CircuitBreaker
Utility CBPosition Sta-tus
ReadOnly
indicates utility breaker position PC 3.x0: Open1: Closed2: Not Available
43600 PARCTL /Load Gov-ern
Load GovernkW Method
Read/Write
Use to select how genset kW output will be controlledwhen paralleled to utility.
PC 3.x
0: Genset kW1: Genset kW w/Utility Constraint2: Utility kW
43608 DSO / Dis-crete Out-puts
ConfigurableOutput #1Event Code
Read/Write
Multiplier:1
Unit: The event code for thisoutput.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43610 DSO / Dis-
crete Out-puts
ConfigurableOutput #2Event Code
Read/Write
Multiplier:1
Unit: The event code for thisoutput.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43613 DSO / Dis-
crete Out-puts
ConfigurableOutput #20Event Code
Read/Write
Multiplier:1
Unit: The event code for thisoutput.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43616 DSO / Dis-
crete Out-puts
ConfigurableOutput #21Event Code
Read/Write
Multiplier:1
Unit: The event code for thisoutput.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43619 DSO / Dis-
crete Out-puts
ConfigurableOutput #22Event Code
Read/Write
Multiplier:1
Unit: The event code for thisoutput.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43622 DSO / Dis-
crete Out-puts
ConfigurableOutput #3Event Code
Read/Write
Multiplier:1
Unit: The event code for thisoutput.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
164
Addr. ControlDescriptionAccessParameterName43625 DSO / Dis-
crete Out-puts
ConfigurableOutput #4Event Code
Read/Write
Multiplier:1
Unit: The event code for thisoutput.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
43641 EH / EventHandler
Delayed Shut-down Enable
Read/Write
Enables the Delayed Shutdown feature. PC 2.x, PC3.x0: Disabled
1: Enabled
43642 EH / EventHandler
Delayed Shut-down TimeDelay
Read/Write
Multiplier:0.1
Unit: sec-onds
Sets the shutdown faultdelayed time delay forthe Delayed Shutdownfeature.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 3
Sign: U
43643 EH / EventHandler
Remote FaultReset En-abled
Read/Write
Trim to enable Remote Fault Reset. Can only reset”Warning” Faults
PC 2.x, PC3.x
0: Disable1: Enable
43644 EH / FaultHandling
Fail To Shut-down Delay
Read/Write
Multiplier:1
Unit: sec-onds
Trim to set the time for ashutdown fault to be ac-tive and the genset notshutting down before theFail to Shutdown fault oc-curs.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 30
Sign: U
43645 EP / LowCoolantLevel
LCL DetectionResponse
Read/Write
Sets low coolant level fault response to None Warningor Shutdown.
PC 2.x, PC3.x
0: None1: Warning2: Shutdown
43646 EP / LowCoolantTemp
LCT WarningClear Time
Read/Write
Multiplier:1
Unit: Min-utes
Sets time to clear the lowcoolant temp fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 30
Sign: U
43647 EP / LowCoolantTemp
LCT WarningSet Time
Read/Write
Multiplier:1
Unit: Min-utes
Sets time to set the lowcoolant temp fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 30
Sign: U
165
Addr. ControlDescriptionAccessParameterName43648 EP / Low
CoolantTemp
LCT WarningThreshold
Read/Write
Multiplier:1
Unit: degF Sets threshold for the lowcoolant temp fault warn-ing.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −20Size (bits):16
Upper Limit: 100
Sign: S43649 GC / Volt-
age Set-point
V/Hz KneeFrequency
Read/Write
Multiplier:0.1
Unit: Hz The voltage will roll off(decrease) proportionallyto the V/Hz setup oncethe frequency drops be-low the set point in theV/Hz Knee Frequency.This allows the genset torecover faster when thefrequency drops.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: U43650 GC / Volt-
age Set-point
V/Hz RolloffSlope
Read/Write
Multiplier:0.1
Unit: % /Hz
The amount of voltageroll off when the frequen-cy is below the knee fre-quency
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: U43651 GC / Bat-
teryProtection
12 V HighBattery Volt-age Threshold
Read/Write
Multiplier:0.1
Unit: Vdc Sets 12V high batteryvoltage fault threshold.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 14Size (bits):16
Upper Limit: 17
Sign: U43652 GC / Bat-
teryProtection
12 V Low Bat-tery VoltageRunningThreshold
Read/Write
Multiplier:0.1
Unit: Vdc Sets 12V low battery volt-age fault threshold forgenset operation while inrated mode
PC 2.x, PC3.x
Offset: 0 Lower Limit: 12Size (bits):16
Upper Limit: 16
Sign: U43653 GC / Bat-
teryProtection
12 V Low Bat-tery VoltageStoppedThreshold
Read/Write
Multiplier:0.1
Unit: Vdc Sets 12V low battery volt-age fault threshold forgenset operation in allmodes except rated
PC 2.x, PC3.x
Offset: 0 Lower Limit: 11Size (bits):16
Upper Limit: 13
Sign: U
166
Addr. ControlDescriptionAccessParameterName43654 GC / Bat-
teryProtection
12 V WeakBattery Volt-age Threshold
Read/Write
Multiplier:0.1
Unit: Vdc Sets 12V weak batteryvoltage fault threshold
PC 2.x, PC3.x
Offset: 0 Lower Limit: 6Size (bits):16
Upper Limit: 10
Sign: U43655 GC / Bat-
teryProtection
24 V HighBattery Volt-age Threshold
Read/Write
Multiplier:0.1
Unit: Vdc Sets 24V high batteryvoltage fault threshold
PC 2.x, PC3.x
Offset: 0 Lower Limit: 28Size (bits):16
Upper Limit: 34
Sign: U43656 GC / Bat-
teryProtection
24 V Low Bat-tery VoltageRunningThreshold
Read/Write
Multiplier:0.1
Unit: Vdc Sets 24V low battery volt-age fault threshold forgenset operation while inrated mode
PC 2.x, PC3.x
Offset: 0 Lower Limit: 24Size (bits):16
Upper Limit: 28
Sign: U43657 GC / Bat-
teryProtection
24 V Low Bat-tery VoltageStoppedThreshold
Read/Write
Multiplier:0.1
Unit: Vdc Sets 24V low battery volt-age fault threshold forgenset operation in allmodes except rated
PC 2.x, PC3.x
Offset: 0 Lower Limit: 22Size (bits):16
Upper Limit: 26
Sign: U43658 GC / Bat-
teryProtection
24 V WeakBattery Volt-age Threshold
Read/Write
Multiplier:0.1
Unit: Vdc Sets 24V weak batteryvoltage fault threshold
PC 2.x, PC3.x
Offset: 0 Lower Limit: 12Size (bits):16
Upper Limit: 16
Sign: U43659 GC /
SpeedReference
AdjustableFreq/SpeedGain
Read/Write
Multiplier:0.01
Unit: rpm/Hz
Sets the rpm/Hz conver-sion factor when the Freqto Speed Gain Select trimis set to this trim
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 240
Sign: U43660 GC /
SpeedReference
Alternate Fre-quencySwitch
Read/Write
Sets the genset nominal frequency. PC 2.x, PC3.x0: 50 Hz
1: 60 Hz
167
Addr. ControlDescriptionAccessParameterName43661 GC / Auto-
matic Volt-age Regu-lator
AVR Gain Ad-just Trim
Read/Write
Multiplier:0.01
Unit: A trim that allows theuser to modify the overallgains of the AVR.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0.05Size (bits):16
Upper Limit: 10
Sign: U43662 GC /
ChargingAlternatorProtection
Charging Al-ternator FaultTime Delay
Read/Write
Multiplier:0.1
Unit: sec-onds
Sets the time delay forthe charging alt failurefault
PC 2.x, PC3.x
Offset: 0 Lower Limit: 2Size (bits):16
Upper Limit: 300
Sign: U43663 GC /
CrankingControl
ContinuousCrank EngageTime
Read/Write
Multiplier:1
Unit: sec-onds
Sets the maximumamount of time to engagethe starter when usingthe continuous crankingmethod
PC 2.x, PC3.x
Offset: 0 Lower Limit: 40Size (bits):16
Upper Limit: 100
Sign: U43664 GC / Con-
trolledShutdownControl
ControlledShutdown Ad-vance NoticeDelay
Read/Write
Multiplier:1
Unit: sec-onds
Delay allowed for a shut-down with cooldown faultprior to shutting down thegenset
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 300
Sign: U43665 GC /
CrankingControl
Crank At-tempts
Read/Write
Multiplier:1
Unit: Sets the maximum num-ber of times to engagethe starter when attempt-ing to start engine usingthe cycle cranking meth-od
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):16
Upper Limit: 7
Sign: U43666 GC /
CrankingControl
Cycle / ContCrank Select
Read/Write
Selects whether to use continuous cranking or cyclecranking when attempting to start engine
PC 2.x, PC3.x
0: Cycle1: Continuous
168
Addr. ControlDescriptionAccessParameterName43667 GC /
CrankingControl
Cycle CrankEngage Time
Read/Write
Multiplier:1
Unit: sec-onds
Sets the maximumamount of time to engagethe starter during a singlecrank attempt when usingthe cycle cranking meth-od
PC 2.x, PC3.x
Offset: 0 Lower Limit: 2Size (bits):16
Upper Limit: 20
Sign: U43668 GC /
CrankingControl
Cycle CrankRest Time
Read/Write
Multiplier:1
Unit: sec-onds
Sets the amount of timeto wait between crank at-tempts
PC 2.x, PC3.x
Offset: 0 Lower Limit: 7Size (bits):16
Upper Limit: 40
Sign: U43669 GC / Out-
putsDelayed OffFSO RelayTime
Read/Write
Multiplier:0.1
Unit: sec-onds
Time delay betweenwhen the Delayed OffCommand turns off andRun Command turns off
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 120
Sign: U43670 GC / Volt-
age Set-point
External AVRKnee Fre-quency
Read/Write
Multiplier:0.1
Unit: Hz Sets the knee frequencyfor the fixed knee freqlogic.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: U43671 GC / Volt-
age Set-point
External BiasCommandsEnable
Read/Write
Enables the external bias (speed and voltage com-mands) to the hardware outputs.
PC 3.x
0: Disabled1: Enabled
43672 GC /SpeedReference
FrequencyAdjust
Read/Write
Multiplier:0.01
Unit: Hz A method of adding in afrequency offset to thebase frequency subject tohigh and low limit calibra-tions
PC 2.x, PC3.x
Offset: 0 Lower Limit: −6Size (bits):16
Upper Limit: 6
Sign: S
169
Addr. ControlDescriptionAccessParameterName43673 GC / Start/
Stop Con-trol
Genset Exer-cise Time
Read/Write
Multiplier:0.1
Unit: hours Sets the total exercisetime not including war-mup at idle or idle cool-down time
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 25
Sign: U43674 GC / Gov-
ernorGovernorGain Adjust
Read/Write
Multiplier:0.01
Unit: A trim that allows theuser to modify the overallgain of the governor
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0.05Size (bits):16
Upper Limit: 10
Sign: U43675 GC / Bat-
teryProtection
High BatteryVoltage SetTime
Read/Write
Multiplier:1
Unit: sec-onds
The time delay until ahigh battery voltage con-dition is reported as afault.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 2Size (bits):16
Upper Limit: 60
Sign: U43676 GC / Bat-
teryProtection
High BatteryVoltageThreshold
ReadOnly
Multiplier:0.1
Unit: Vdc The high battery voltagethreshold
PC 2.x, PC3.x
Offset: 0 Lower Limit: 14Size (bits):16
Upper Limit: 34
Sign: U43677 GC / Start/
Stop Con-trol
Idle CooldownTime
Read/Write
Multiplier:0.25
Unit: min-utes
Sets time to run at idlebefore shutting downgenset on normal stops
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 60
Sign: U43678 GC /
SpeedReference
Idle Speed Read/Write
Multiplier:1
Unit: rpm Sets the speed at whichthe engine will idle sub-ject to high and low limitcalibrations
PC 2.x, PC3.x
Offset: 0 Lower Limit: 700Size (bits):16
Upper Limit: 1100
Sign: U
170
Addr. ControlDescriptionAccessParameterName43679 GC /
SpeedReference
Idle to RatedRamp Time
Read/Write
Multiplier:0.1
Unit: sec-onds
The time over which thespeed reference is toramp from idle speed torated speed
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 30
Sign: U43680 GC / Start/
Stop Con-trol
Idle WarmupCoolant Temp
Read/Write
Multiplier:1
Unit: degF Coolant temperaturethreshold to end idle war-mup time
PC 2.x, PC3.x
Offset: 0 Lower Limit: −40Size (bits):16
Upper Limit: 300
Sign: S43681 GC / Start/
Stop Con-trol
Idle WarmupTime
Read/Write
Multiplier:1
Unit: sec-onds
Sets maximum idle war-mup time. Warmup timemay be less if coolanttemperature exceedsthreshold
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 3600
Sign: U43682 GC / Over-
loadProtection
Load DumpActivationMethod
Read/Write
Enables the load dump output as a function of theoverload and underfrequency conditions
PC 2.x, PC3.x
0: Overload1: Underfrequency2: Overload or Underfrequency3: Disabled
43683 GC / Over-loadProtection
Load DumpOverload SetTime
Read/Write
Multiplier:1
Unit: sec-onds
The time delay until theload dump overload con-dition is set active
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 120
Sign: U43684 GC / Over-
loadProtection
Load DumpOverloadThreshold
Read/Write
Multiplier:1
Unit: % The load dump overloadthreshold as a percent-age of the genset ap-plication rating
PC 2.x, PC3.x
Offset: 0 Lower Limit: 80Size (bits):16
Upper Limit: 140
Sign: U
171
Addr. ControlDescriptionAccessParameterName43685 GC / Over-
loadProtection
Load DumpUnderfre-quency Offset
Read/Write
Multiplier:1
Unit: Hz The frequency amountwhich the load dump un-derfrequency threshold isbelow the final frequencyreference
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: S
43686 GC / Over-loadProtection
Load DumpUnderfre-quency SetTime
Read/Write
Multiplier:1
Unit: sec-onds
The time delay until theload dump underfrequen-cy condition is set active
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 20
Sign: U
43687 GC / Over-loadProtection
Load DumpUnderfre-quencyThreshold
ReadOnly
Multiplier:0.1
Unit: Hz The frequency tripthreshold for the loaddump underfrequencycondition
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 90
Sign: U
43688 GC / Bat-teryProtection
Low BatteryVoltage SetTime
Read/Write
Multiplier:1
Unit: sec-onds
The time delay until a lowbattery voltage conditionis reported as a fault
PC 2.x, PC3.x
Offset: 0 Lower Limit: 2Size (bits):16
Upper Limit: 60
Sign: U
43689 GC / Out-puts
Low Fuel inDay TankTime
Read/Write
Multiplier:1
Unit: sec-onds
Low Fuel in Day TankFault time delay fromswitch input.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 20
Sign: U
43690 GC / Out-puts
Low Fuel Set/Clear Time
Read/Write
Multiplier:1
Unit: sec-onds
A trim that sets the delaytime for generating the in-active and active faults.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 2Size (bits):16
Upper Limit: 60
Sign: U
43691 GC / Start/Stop Con-trol
Manual War-mup Bypass
Read/Write
Use to command idle speed or to bypass idle warmupduring a manual run
PC 2.x, PC3.x
0: Normal1: Bypass Warmup
172
Addr. ControlDescriptionAccessParameterName43692 GC / Start/
Stop Con-trol
Max Idle Time Read/Write
Multiplier:0.1
Unit: min-utes
Sets the fault time for theToo Long in Idle fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 20
Sign: U43693 GC / Bat-
teryProtection
Nominal Bat-tery Voltage
Read/Write
Selects the genset_s nominal battery operating volt-age
PC 2.x, PC3.x
0: 12V1: 24V
43694 GC / Pre-lube
Prelube CycleEnable
Read/Write
Enables Or Disables the cyclic mode of prelube op-eration
PC 2.x, PC3.x
0: Disabled1: Enabled
43695 GC / Pre-lube
Prelube CycleTime
Read/Write
Multiplier:0.1
Unit: hours Sets the period of thePrelube Cycle Iteration
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):16
Upper Limit: 1000
Sign: U43696 GC / Pre-
lubePrelube Func-tion Enable
Read/Write
Selects whether the Prelube function is enabled ordisabled. This is Setup mode interlocked
PC 2.x, PC3.x
0: Disabled1: Enabled
43697 GC / Pre-lube
Prelube OilPressureThreshold
Read/Write
Multiplier:0.1
Unit: psig The oil pressure valuewhich when reached theprelube driver will turn off
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: U43698 GC / Pre-
lubePrelube Time-out Period
Read/Write
Multiplier:0.1
Unit: sec-onds
Sets the maximum timefor which the PrelubeDriver will Remain ON
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 30
Sign: U43699 GC /
SpeedReference
Rated to IdleRamp Time
Read/Write
Multiplier:0.1
Unit: sec-onds
The time over which thespeed reference is toramp from rated speed toidle speed
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 30
Sign: U
173
Addr. ControlDescriptionAccessParameterName43700 PARST /
PTCSourceAvailability
Utility Avail-ability Status
ReadOnly
indicates status of the utility source PC 3.x0: Not Available1: Available2: Unknown
43701 PARST /CircuitBreaker
Utility CB In-hibit Com-mand
ReadOnly
utility cb inhibit command PC 3.x0: Inactive1: Active
43702 PARST /CircuitBreaker
Utility CBTripped Com-mand
ReadOnly
utility cb tripped command PC 3.x0: Inactive1: Active
43703 PARST /CircuitBreaker
Utility CurrentBased Break-er Position
ReadOnly
indicates utility breaker position based on current PC 3.x0: Unknown1: Closed
43704 PARST /PTC Sen-sors
Utility Fre-quency LowerDrop−OutThreshold
ReadOnly
Multiplier:0.1
Unit: Hz indicates the lower drop−out threshold in Hz forutility frequency sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43705 PARST /PTC Sen-sors
Utility Fre-quency LowerPick−UpThreshold
ReadOnly
Multiplier:0.1
Unit: Hz indicates the lower pick−up threshold in Hz for util-ity frequency sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43706 PARST /PTC Sen-sors
Utility Fre-quency Sen-sor Status
ReadOnly
indicates utility frequency sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out
43707 PARST /PTC Sen-sors
Utility Fre-quency UpperDrop−OutThreshold
ReadOnly
Multiplier:0.1
Unit: Hz indicates the upper drop−out threshold in Hz forutility frequency sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43708 PARST /PTC Sen-sors
Utility Fre-quency UpperPick−UpThreshold
ReadOnly
Multiplier:0.1
Unit: Hz indicates the upper pick−up threshold in Hz for util-ity frequency sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43709 PARST /PTC Sen-sors
Utility Loss ofPhase SensorStatus
ReadOnly
indicates utility loss of phase sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out
174
Addr. ControlDescriptionAccessParameterName43710 PARST /
PTC Sen-sors
Utility Over-voltage Drop−Out Threshold
ReadOnly
Multiplier:1
Unit: Vac indicates the drop−outthreshold in volts for util-ity overvoltage sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43711 PARST /PTC Sen-sors
Utility Over-voltage Pick−Up Threshold
ReadOnly
Multiplier:1
Unit: Vac indicates the pick−upthreshold in volts for util-ity overvoltage sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43712 PARST /PTC Sen-sors
Utility Over-voltage Sen-sor Status
ReadOnly
indicates utility overvoltage sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out
43713 PARST /PTC Sen-sors
Utility PhaseRotation Sen-sor Status
ReadOnly
indicates utility phase rotation sensor status PC 3.x0: Un-known1: Picked Up2: Dropped Out
43714 PARST /PTC Sen-sors
Utility Under-voltage Drop−Out Threshold
ReadOnly
Multiplier:1
Unit: Vac indicates the drop−outthreshold in volts for util-ity undervoltage sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43715 PARST /PTC Sen-sors
Utility Under-voltage Pick−Up Threshold
ReadOnly
Multiplier:1
Unit: Vac indicates the pick−upthreshold in volts for util-ity undervoltage sensor
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
43716 PARST /PTC Sen-sors
Utility Under-voltage Sen-sor Status
ReadOnly
indicates utility undervoltage sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out
43717 PARST /ParallelingControlMode
Voltage DroopEnable Com-mand
ReadOnly
Command value of voltage droop enable PC 2.x, PC3.x0: Inactive
1: Active
43718 PARST /ParallelingControlMode
Voltage DroopStatus
ReadOnly
indicates whether or not voltage droop is in effect PC 2.x, PC3.x0: Droop Disabled
1: Droop Enabled
175
Addr. ControlDescriptionAccessParameterName43719 PCCNet /
I/O Module0 MainBoard
AlternatorTemperature1 (Aux101)
ReadOnly
Multiplier:1
Unit: degF Monitor point for the Al-ternator Temp 1 inputfrom the Aux 101 I/OModule.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −32767Size (bits):16
Upper Limit: 32762
Sign: S43720 PCCNet /
I/O Module0 MainBoard
AlternatorTemperature2 (Aux101)
ReadOnly
Multiplier:1
Unit: degF Monitor point for the Al-ternator Temp 2 inputfrom the Aux 101 I/OModule.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −32767Size (bits):16
Upper Limit: 32762
Sign: S43721 PCCNet /
I/O Module0 MainBoard
AlternatorTemperature3 (Aux101)
ReadOnly
Multiplier:1
Unit: degF Monitor point for the Al-ternator Temp 3 inputfrom the Aux 101 I/OModule.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −32767Size (bits):16
Upper Limit: 32762
Sign: S43722 PCCNet /
I/O Module0 MainBoard
Ambient Tem-perature(Aux101)
ReadOnly
Multiplier:1
Unit: degF Monitor point for the Am-bient Temp input from theAux 101 I/O Module.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −32767Size (bits):16
Upper Limit: 32762
Sign: S43723 PCCNet /
I/O Module0 MainBoard
Aux101 0Analog Input1 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 0 analog input 1in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit: −500Size (bits):16
Upper Limit: 500
Sign: S43724 PCCNet /
I/O Module0 MainBoard
Aux101 0Analog Input2 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 0 analog input 2in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit: −500Size (bits):16
Upper Limit: 500
Sign: S
176
Addr. ControlDescriptionAccessParameterName43725 PCCNet /
I/O Module0 MainBoard
Aux101 0Analog Input3 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 0 analog input 3in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43726 PCCNet /I/O Module0 MainBoard
Aux101 0Analog Input4 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 0 analog input 4in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43727 PCCNet /I/O Module0 MainBoard
Aux101 0Analog Input5 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 0 analog input 5in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43728 PCCNet /I/O Module0 MainBoard
Aux101 0Analog Input6 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 0 analog input 6in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43729 PCCNet /I/O Module0 MainBoard
Aux101 0Analog Input7 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 0 analog input 7in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43730 PCCNet /I/O Module0 MainBoard
Aux101 0Analog Input8 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 0 analog input 8in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43731 PCCNet /I/O Module1 MainBoard
Aux101 1Analog Input1 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 1 analog input 1in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit: −500Size (bits):16
Upper Limit: 500
Sign: S
177
Addr. ControlDescriptionAccessParameterName43732 PCCNet /
I/O Module1 MainBoard
Aux101 1Analog Input2 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 1 analog input 2in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit: −500Size (bits):16
Upper Limit: 500
Sign: S
43733 PCCNet /I/O Module1 MainBoard
Aux101 1Analog Input3 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 1 analog input 3in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43734 PCCNet /I/O Module1 MainBoard
Aux101 1Analog Input4 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 1 analog input 4in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43735 PCCNet /I/O Module1 MainBoard
Aux101 1Analog Input5 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 1 analog input 5in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43736 PCCNet /I/O Module1 MainBoard
Aux101 1Analog Input6 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 1 analog input 6in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43737 PCCNet /I/O Module1 MainBoard
Aux101 1Analog Input7 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 1 analog input 7in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43738 PCCNet /I/O Module1 MainBoard
Aux101 1Analog Input8 Voltage
ReadOnly
Multiplier:0.01
Unit: Vdc Monitor point for themodule 1 analog input 8in Volts
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
178
Addr. ControlDescriptionAccessParameterName43739 PCCNet /
UniversalAnnuncia-tor
Battery Char-ger AC Failu-re (HMI113)
ReadOnly
Monitor point for the battery charger failure input fromthe PCCNet Annunciator.
PC 2.x, PC3.x
0: Inactive1: Active
43740 PCCNet /I/O Module0 MainBoard
Drive EndBearing Tem-perature(Aux101)
ReadOnly
Multiplier:1
Unit: degF Monitor point for theDrive End Bearing Tempinput from the I/O Mod-ule.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −32767Size (bits):16
Upper Limit: 32762
Sign: S
43741 PCCNet /I/O Module0 MainBoard
Exhaust StackTemperature1 (Aux101)
ReadOnly
Multiplier:1
Unit: degF Monitor point for the Ex-haust Stack Temp1 inputfrom the I/O Module.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −32767Size (bits):16
Upper Limit: 32762
Sign: S
43742 PCCNet /I/O Module0 MainBoard
Exhaust StackTemperature2 (Aux101)
ReadOnly
Multiplier:1
Unit: degF Monitor point for the Ex-haust Stack Temp2 inputfrom the I/O Module.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −32768Size (bits):16
Upper Limit: 32762
Sign: S
43743 PCCNet /I/O Module0 MainBoard
ExternalSpeed BiasInput(PCCNet)
ReadOnly
Multiplier:0.01
Unit: % Monitor point for theSpeed Bias input fromthe I/O Module.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −100Size (bits):16
Upper Limit: 100
Sign: U
43744 PCCNet /I/O Module0 MainBoard
External Volt-age Bias Input(PCCNet)
ReadOnly
Multiplier:0.01
Unit: % Monitor point for the Volt-age Bias input from theI/O Module.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −100Size (bits):16
Upper Limit: 100
Sign: U
43745 PCCNet /I/O Module0 MainBoard
Fuel Level %(PCCNet)
ReadOnly
Multiplier:0.1
Unit: % Monitor point for the %fuel level input from theI/O Module.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
179
Addr. ControlDescriptionAccessParameterName43746 PCCNet /
I/O Module0 MainBoard
Fuel Level(PCCNet)
ReadOnly
Multiplier:1
Unit: Monitor point for the fuellevel (in gallons) inputfrom the I/O Module.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43747 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Status
ReadOnly
Monitor point for input #1 from the Annunciator. PC 2.x, PC3.x0: Inactive
1: Active
43748 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Status
ReadOnly
Monitor point for input #2 from the Annunciator. PC 2.x, PC3.x0: Inactive
1: Active
43749 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Status
ReadOnly
Monitor point for the input #3 from the Annunciator. PC 2.x, PC3.x0: Inactive
1: Active
43750 PCCNet /I/O Module0 MainBoard
Intake Man-ifold Tempera-ture 1(Aux101)
ReadOnly
Multiplier:1
Unit: degF Monitor point for the In-take Manifold Temp 1 in-put from the I/O Module.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −32768Size (bits):16
Upper Limit: 32762
Sign: S
43751 PCCNet /UniversalAnnuncia-tor
Low CoolantLevel(HMI113)
ReadOnly
Monitor point for the Low Coolant Level input from thePCCNet Annunciator.
PC 2.x, PC3.x
0: Inactive1: Active
43752 PCCNet /UniversalAnnuncia-tor
Low Fuel Le-vel (HMI113)
ReadOnly
Monitor point for the Low Fuel Level input from thePCCNet Annunciator.
PC 2.x, PC3.x
0: Inactive1: Active
43755 PCCNet /I/O Module0 MainBoard
Non−DriveEnd BearingTemperature(Aux101)
ReadOnly
Multiplier:1
Unit: degF Monitor point for theNon−Drive End BearingTemp input from the I/OModule.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −65534Size (bits):16
Upper Limit: 65535
Sign: S
43756 PCCNet /Monitoringand Diag-nostics
Number ofConnectedBargraphModules
ReadOnly
Multiplier:1
Unit: Used to monitor theamount of connectedBargraph modules.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 255
Sign: U
180
Addr. ControlDescriptionAccessParameterName43757 PCCNet /
I/O Module0 MainBoard
Oil Tempera-ture (Aux101)
ReadOnly
Multiplier:1
Unit: degF Monitor point for the OilTemp input from the I/OModule.
PC 2.x, PC3.x
Offset: 0 Lower Limit: −65534Size (bits):16
Upper Limit: 65535
Sign: S43758 Modbus /
ModbusModbus BusMessageCount
ReadOnly
Multiplier:1
Unit: Modbus bus messagecount
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43759 Modbus /
ModbusModbus CRCErrors Count
ReadOnly
Multiplier:1
Unit: Modbus CRC errorscount
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43760 Modbus /
ModbusModbus Ex-ception Count
ReadOnly
Multiplier:1
Unit: Modbus exception count PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43761 Modbus /
ModbusModbus NoResponseCount
ReadOnly
Multiplier:1
Unit: Modbus no responsecount
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43762 Modbus /
ModbusModbus SlaveMessageCount
ReadOnly
Multiplier:1
Unit: Modbus slave messagecount
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U43763 PARCTL /
Synchro-nizer
FrequencyMatch Error
ReadOnly
Multiplier:0.001
Unit: Hz frequency match errorvalue used by frequencymatch PI loop
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
181
Addr. ControlDescriptionAccessParameterName43764 PARCTL /
Synchro-nizer
FrequencyMatch Offset
ReadOnly
Multiplier:0.001
Unit: Hz offset to the frequencymatch error calculation
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43765 PARCTL /Derate
Load DumpRequest
ReadOnly
indicates a load dump is desired due to load exceed-ing derate level.
PC 2.x, PC3.x
0: Inactive1: Active
43766 PARCTL /Load Gov-ern
Load GovernkVAR RampState
ReadOnly
indicates status of load govern kVAR ramping control PC 3.x0: Not Applicable1: Ramp Load2: Track Target3: Ramp Unload4: Ramp Unload Complete
43767 PARCTL /Load Gov-ern
Load GovernkVAR Target
ReadOnly
Multiplier:0.01
Unit: % indicates the final targetsetpoint for genset kVARoutput when paralleled toutility
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43768 PARCTL /Load Gov-ern
Load GovernkW RampState
ReadOnly
indicates status of load govern kW ramping control PC 3.x0: Not Applicable1: Ramp Load2: Track Target3: Ramp Unload4: Ramp Unload Complete
43769 PARCTL /Load Gov-ern
Load GovernkW Target
ReadOnly
Multiplier:0.01
Unit: % indicates the final targetsetpoint for genset kWoutput when paralleled toutility
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
43770 PARCTL /Synchro-nizer
PermissiveClose Allowed
ReadOnly
indicates when permissive sync check conditionshave been met
PC 3.x
0: Not Allowed1: Allowed
43772 PARCTL /Synchro-nizer
PermissivePhase MatchError
ReadOnly
Multiplier:0.01
Unit: deg phase error signal for thepermissive sync check al-gorithm
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
182
Addr. ControlDescriptionAccessParameterName43773 PARCTL /
Synchro-nizer
Phase MatchError
ReadOnly
Multiplier:0.01
Unit: deg phase error signal for thesynchronizer control al-gorithm
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S43774 PARCTL /
LoadShare
Ramp Load/Unload Com-mand
ReadOnly
indicates overall status of ramp load unload inputs PC 3.x0: Load1: Unload
43775 PARCTL /Load Gov-ern
Utility Un-loaded Status
ReadOnly
indicates unloaded status of the utility source PC 3.x0: Not Available1: Not Unloaded2: Unloaded
43776 DSO / Dis-crete Out-puts
Genset CBClose Status
ReadOnly
Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active
43777 DSI / Dis-crete In-puts
Start Type/ConfigurableInput #11Switch
ReadOnly
This is the status of the Configurable Input #11. PC 2.x, PC3.x0: Inactive
1: Active
43778 DR / Exer-ciseScheduler
SchedulerRun Com-mand
ReadOnly
Indicates the current run command coming from thescheduler.
PC 2.x, PC3.x
0: Off1: No Load2: With Load3: Extended Parallel
43789 DSI / Dis-crete In-puts
Backup StartDisconnect/ConfigurableInput #33Switch
ReadOnly
This is the status of the Configurable Input #33. PC 3.x
0: Inactive
1: Active
43790 DSI / Dis-crete In-puts
Backup StartDisconnectSwitch
ReadOnly
Status of the Backup Start Disconnect Switch Input PC 3.x0: Inactive1: Active
43791 DSI / Dis-crete In-puts
Battery Char-ger FailedSwitch
ReadOnly
Battery Charger Failed Switch function output status;gives software Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43785 DR / DataRecording
Start AttemptsSince Reset
Read/Write
Multiplier:1
Unit: Number of start attemptssince the last reset.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967290
Sign: U
183
Addr. ControlDescriptionAccessParameterName43786 DR / Data
RecordingStart AttemptsSince Reset
Read/Write
Multiplier:1
Unit: Number of start attemptssince the last reset.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967290
Sign: U43787 DR / Data
RecordingTotal Start At-tempts
Read/Write
Multiplier:1
Unit: Total number of start at-tempts.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967295
Sign: U43788 DR / Data
RecordingTotal Start At-tempts
Read/Write
Multiplier:1
Unit: Total number of start at-tempts.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4294967295
Sign: U43792 DSI / Dis-
crete In-puts
Battle ShortSwitch
ReadOnly
Battle Short Switch function output status (Active orInactive).
PC 2.x, PC3.x
0: Inactive1: Active
43793 DSI / Dis-crete In-puts
ConfigurableInput #1Switch
ReadOnly
Configurable Input #1 input software state status.Gives software Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43794 DSI / Dis-crete In-puts
ConfigurableInput #2Switch
ReadOnly
Configurable Input #2 input software state status.Gives software Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43795 DSI / Dis-crete In-puts
ConfigurableInput #13Switch
ReadOnly
Configurable Input #13 input software state status.Gives software Inactive/Active state
PC 2.x, PC3.x
0: Inactive1: Active
43796 PARST /CircuitBreaker
Genset CBOpen Com-mand
ReadOnly
genset cb open command status PC 3.x0: Inactive1: Active
43797 PCCNet /Monitoringand Diag-nostics
Number ofConnectedBattery Char-gers
ReadOnly
Multiplier:1
Unit: Used to monitor theamount of connectedBattery Chargers.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 255
Sign: U
184
Addr. ControlDescriptionAccessParameterName43800 GC / Start/
Stop Con-trol
Rated Cool-down Time
Read/Write
Multiplier:1
Unit: sec-onds
Minimum time to spendat rated speed less than10% load before normalshutdown is allowed
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 600
Sign: U43801 GC / Start/
Stop Con-trol
Rated to IdleTransitionDelay
Read/Write
Multiplier:0.1
Unit: sec-onds
Sets the delay time fortransitioning from Ratedto Idle speed. 0 seconds= feature is disabled.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: U43802 GC / Out-
putsRupture BasinTime
Read/Write
Multiplier:0.1
Unit: sec-onds
Rupture Basin fault timedelay
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 20
Sign: U43803 GC / Start/
Stop Con-trol
Start TimeDelay
Read/Write
Multiplier:1
Unit: sec-onds
Sets the time to wait fromreceiving a valid remotestart signal until startingthe genset
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 300
Sign: U43804 GC /
SpeedReference
Starting toRated RampTime
Read/Write
Multiplier:0.1
Unit: sec-onds
The time over which thespeed reference is toramp from starting speedto rated speed
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 30
Sign: U43805 GC / Start/
Stop Con-trol
Time Delay toStop
Read/Write
Multiplier:1
Unit: sec-onds
Sets time to run at ratedspeed before going tocooldown at idle. Doesnot apply to manual runs
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 600
Sign: U
185
Addr. ControlDescriptionAccessParameterName43806 GC / Volt-
age Set-point
Voltage Adjust Read/Write
Multiplier:0.01
Unit: % A trim that allows theuser to add/subtract anoffset to the nominal volt-age when calculating thevoltage setpoint
PC 2.x, PC3.x
Offset: 0 Lower Limit: −5Size (bits):16
Upper Limit: 5
Sign: S
43807 GC / Volt-age Set-point
Voltage RampTime
Read/Write
Multiplier:0.01
Unit: sec-onds
The time period overwhich the voltage set-point command shouldrise from 0% to the targetvoltage
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 5
Sign: U
43810 Modbus /Modbus
Battle ShortSwitch (Mod-bus)
Read/Write
Trim to enable Battle Short via Modbus. PC 2.x, PC3.x0: Inactive
1: Active
43811 Modbus /Modbus
ExerciseSwitch (Mod-bus)
Read/Write
Modbus exercise switch PC 2.x, PC3.x0: Inactive
1: Active
43813 Modbus /Modbus
Extended Par-allel Switch(Modbus)
Read/Write
Modbus extended parallel switch PC 2.x, PC3.x0: Inactive
1: Active
43814 Modbus /Modbus
PTC ModeSwitch (Mod-bus)
Read/Write
Modbus PTC Mode switch PC 3.x0: Inactive1: Active
43815 Modbus /Modbus
Start Type(Modbus)
Read/Write
Modbus start type switch PC 2.x, PC3.x0: Emergency
1: Non Emergency
43816 PARCTL /Synchro-nizer
Sync Disable Read/Write
use to turn off synchronizer for testing purposes PC 3.x0: Inactive1: Active
43817 PARST /CircuitBreaker
Genset CB In-hibit Switch(Modbus)
Read/Write
genset cb inhibit from Modbus PC 3.x0: Inactive1: Active
43818 PARST /ParallelingControlMode
Isolated BusSpeed ControlMethod
Read/Write
Sets the speed control method for isolated bus paral-leling. Parameter is also known as Load Share SpeedDroop Control Method
PC 2.x, PC3.x
0: Constant1: Droop
43819 PARST /ParallelingControlMode
Isolated BusVoltage Con-trol Method
Read/Write
Sets the voltage control method for isolated bus par-alleling.
PC 2.x, PC3.x
0: Constant1: Droop
186
Addr. ControlDescriptionAccessParameterName43820 PARST /
PTC Tim-ers
MaximumParallel Time(TDMP)
Read/Write
Multiplier:0.1
Unit: sec-onds
Sets the maximum timethat the genset can re-main paralleled to theutility during closed tran-sition transfers.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 1800
Sign: U
43821 PARST /PTC Tim-ers
ProgrammedTransition De-lay (TDPT)
Read/Write
Multiplier:0.1
Unit: sec-onds
Sets the time delay fromwhen one source opensuntil the other closes dur-ing open transition trans-fers.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 60
Sign: U
43822 PARST /PTC Tim-ers
RetransferDelay (TDEN)
Read/Write
Multiplier:0.1
Unit: sec-onds
Sets the amount of timethat the utility sourcemust be available beforethe control will retransferto that source.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 1800
Sign: U
43823 PARST /ParallelingControlMode
SynchronizerSpeed ControlMethod
Read/Write
Sets the speed control method for synchronizing. PC 3.x0: Phase Match1: Slip Frequency2: External
43824 PARST /ParallelingControlMode
SynchronizerVoltage Con-trol Method
Read/Write
Sets the voltage control method for synchronizing. PC 3.x
0: Voltage Match
1: External
43825 PARST /PTC Tim-ers
Transfer De-lay (TDNE)
Read/Write
Multiplier:0.1
Unit: sec-onds
Sets the amount of timethat the genset sourcemust be available beforethe control will transfer tothat source.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 120
Sign: U
43826 PARST /PTC StateMachine
TransitionType
Read/Write
Sets the load transfer transition type for use whenGenset Application Type = Power Transfer Control.
PC 3.x
0: Open Transition1: Hard Closed Transition2: Soft Closed Transition
187
Addr. ControlDescriptionAccessParameterName43827 PARST /
PTC Inhib-its
Retransfer In-hibit Switch(Modbus)
Read/Write
retransfer inhibit switch input status from Modbus PC 3.x0: Inactive1: Active
43828 PARST /CircuitBreaker
Utility CB In-hibit Switch(Modbus)
Read/Write
utility cb inhibit from Modbus PC 3.x0: Inactive1: Active
43829 PARST /ParallelingControlMode
Utility ParallelSpeed ControlMethod
Read/Write
Sets the speed control method for utility paralleling. PC 3.x
0: Load Govern
1: Droop
43830 PARST /ParallelingControlMode
Utility ParallelVoltage Con-trol Method
Read/Write
Sets the voltage control method for utility paralleling. PC 3.x0: Load Govern1: Droop2: Load Govern with Droop Feed Forward
43831 PCCNet /I/O Module0 MainBoard
Aux101 De-vice 0PCCNet Fail-ure ResponseType
Read/Write
Selects the genset reaction to a loss of a Device 0 I/OModule as critical (Shutdown) or non−critical (Warn-ing).
PC 2.x, PC3.x
0: Critical Device Response1: Non−Critical Device Response
43832 PCCNet /I/O Module1 MainBoard
Aux101 De-vice 1PCCNet Fail-ure ResponseType
Read/Write
Selects the genset reaction to a loss of a Device 1 I/OModule as critical (Shutdown) or non−critical (Warn-ing).
PC 2.x, PC3.x
0: Critical Device Response1: Non−Critical Device Response
43834 PCCNet /UniversalAnnuncia-tor
HMI113 An-nunciatorPCCNet Fail-ure ResponseType
Read/Write
Selects the genset reaction to a loss of an Annuncia-tor as critical or non−critical. Selecting Critical willcause a shutdown when the Annunciator looses com-munication.
PC 2.x, PC3.x
0: Critical Device Response1: Non−Critical Device Response
43835 PCCNet /OperatorPanel
HMI1xxPCCNet Fail-ure ResponseType
Read/Write
Selects the genset reaction to a loss of an HMI1xx Op-erator Panel as critical or non−critical. A critical re-sponse will shutdown the genset when PCCNet com-munication is lost.
PC 2.x, PC3.x
0: Critical Device Response1: Non−Critical Device Response
43836 PCCNet /OperatorPanel
HMI220PCCNet Fail-ure ResponseType
Read/Write
Selects the genset reaction to a loss of an HMI220Operator Panel as critical or non−critical.. A critical re-sponse will shutdown the genset when PCCNet com-munication is lost.
PC 2.x, PC3.x
0: Critical Device Response1: Non−Critical Device Response
43837 PCCNet /OperatorPanel
HMI320PCCNet Fail-ure ResponseType
Read/Write
Selects the genset reaction to a loss of an HMI320Operator Panel as critical or non−critical.. A critical re-sponse will shutdown the genset when PCCNet com-munication is lost.
PC 2.x, PC3.x
0: Critical Device Response1: Non−Critical Device Response
188
Addr. ControlDescriptionAccessParameterName43838 PCCNet /
OperatorPanel
HMI4xxPCCNet Fail-ure ResponseType
Read/Write
Selects the genset reaction to a loss of an HMI4xx Op-erator Panel as critical or non−critical.. A critical re-sponse will shutdown the genset when PCCNet com-munication is lost.
PC 2.x, PC3.x
0: Critical Device Response1: Non−Critical Device Response
43839 PCCNet /Monitoringand Diag-nostics
PCCNet De-vice FailureTime Delay
Read/Write
Multiplier:1
Unit: sec-onds
Selects the time allowedfor arbitration to occurbefore a PCCNet failurefault is generated.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):8
Upper Limit: 250
Sign: U43840 PARST /
PTC En-ables
Test WithLoad Enable
Read/Write
Use to choose whether a test is with load or withoutload.
PC 3.x
0: Disabled1: Enabled
43841 PARST /PTC Inhib-its
Transfer In-hibit Switch(Modbus)
Read/Write
transfer inhibit switch input status from Modbus PC 3.x0: Inactive1: Active
43845 Modbus /Modbus
Modbus Fail-ure TimeDelay
Read/Write
Multiplier:1
Unit: sec-onds
Time delay before thecontrol activates the Mo-dus failure fault after themaster is sensed as nolonger present.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: U43846 Modbus /
ModbusModbus Com-municationsLost Re-sponse Meth-od
Read/Write
When set to Reset Commands will reset the Moduscontrol logics to an inactive state when Modbus com-munications are lost
PC 2.x, PC3.x
0: Do Nothing1: Reset Commands
43847 Modbus /Modbus
Modbus ClearCounters
Read/Write
Resets all Modus counters including J14 if applicable. PC 2.x, PC3.x0: Do Nothing
1: Clear Counters43848 PARCTL /
Load Gov-ern
ControlledShutdownMax RampUnload Time
Read/Write
Multiplier:1
Unit: sec-onds
maximum ramp unloadtime during a shutdownwith cooldown
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 300
Sign: U
189
Addr. ControlDescriptionAccessParameterName43849 PARCTL /
Load Gov-ern
Genset kVARSetpoint
Read/Write
Multiplier:1
Unit: kVAR Sets the genset load gov-ern kVAR base load inter-nal operating setpoint inunits of kVAR. Requiresthat Load Govern kVARSetpoint Source = Inter-nal and Load GovernkVAR Method = GensetkVAR.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 20000
Sign: S
43850 PARCTL /Load Gov-ern
Genset kVARSetpoint Per-cent
Read/Write
Multiplier:0.01
Unit: % Sets the genset load gov-ern kVAR base load inter-nal operating setpoint in% of standby kVA rating.Requires that Load Gov-ern kVAR SetpointSource = Internal andLoad Govern kVAR Meth-od = Genset kVAR.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 60
Sign: S
43851 PARCTL /Load Gov-ern
Genset kWSetpoint
Read/Write
Multiplier:1
Unit: kW Sets the genset load gov-ern kW base load internaloperating setpoint in unitsof kW. Requires thatLoad Govern kW Set-point Source = Internaland Load Govern kWMethod = Genset kW.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 20000
Sign: S
43852 PARCTL /Load Gov-ern
Genset kWSetpoint Per-cent
Read/Write
Multiplier:0.01
Unit: % Sets the genset load gov-ern kW base load internaloperating setpoint in % ofstandby rating. Requiresthat Load Govern kWSetpoint Source = Inter-nal and Load Govern kWMethod = Genset kW.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 100
Sign: S
190
Addr. ControlDescriptionAccessParameterName43853 PARCTL /
Load Gov-ern
Genset PowerFactor Set-point
Read/Write
Multiplier:0.01
Unit: PF Sets the load govern set-point for genset powerfactor control. Requiresthat Load Govern kVARSetpoint Source = Inter-nal and Load GovernkVAR Method = GensetPower Factor.
PC 3.x
Offset: 0 Lower Limit: 0.7Size (bits):8
Upper Limit: 1
Sign: S43854 PARCTL /
Load De-mand
Load DemandStop (Mod-bus)
Read/Write
Modbus input for activating load demand stop on thegenset
PC 3.x
0: Inactive1: Active
43855 PARCTL /Load Gov-ern
Load GovernkVAR Method
Read/Write
Use to select how genset kVAR output will be con-trolled when paralleled to utility.
PC 3.x
0: Genset kVAR1: Genset Power Factor2: Utility kVAR3: Utility Power Factor
43856 PARCTL /Load Gov-ern
Load GovernkVAR RampLoad Time
Read/Write
Multiplier:1
Unit: sec-onds
Sets load govern kVARramp load rate = GensetStandby kVA * 0.6/ thistime.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 900
Sign: U43857 PARCTL /
Load Gov-ern
Load GovernkVAR RampUnload Time
Read/Write
Multiplier:1
Unit: sec-onds
Sets load govern kVARramp unload rate = Gen-set Standby KVA * 0.6/this time.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 900
Sign: U43859 PARCTL /
Load Gov-ern
Load GovernkW RampLoad Time
Read/Write
Multiplier:1
Unit: sec-onds
Sets load govern kWramp load rate = GensetStandby kW rating/ thistime.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 900
Sign: U
191
Addr. ControlDescriptionAccessParameterName43860 PARCTL /
Load Gov-ern
Load GovernkW Ramp Un-load Time
Read/Write
Multiplier:1
Unit: sec-onds
Sets load govern kWramp unload rate = Gen-set Standby kW rating/this time.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 900
Sign: U43861 PARCTL /
LoadShare
Ramp Load/Unload (Mod-bus)
Read/Write
use to control ramp load and unload via Modbus PC 3.x0: Load1: Unload
43862 PARCTL /Synchro-nizer
Slip Frequen-cy
Read/Write
Multiplier:0.001
Unit: Hz Sets the synchronizer slipfrequency. Requires thatSync Speed ControlMethod = Slip Frequency.
PC 3.x
Offset: 0 Lower Limit: −3Size (bits):16
Upper Limit: 3
Sign: S43863 PARCTL /
Load Gov-ern
Utility kVARSetpoint
Read/Write
Multiplier:1
Unit: kVAR Sets the utility kVAR peakshave internal operatingsetpoint in units of kVAR.Requires that Load Gov-ern kVAR SetpointSource = Internal andLoad Govern kVAR Meth-od = Utility kVAR
PC 3.x
Offset: 0 Lower Limit: −20000Size (bits):16
Upper Limit: 20000
Sign: S43864 PARCTL /
Load Gov-ern
Utility kVARSetpoint Per-cent
Read/Write
Multiplier:0.01
Unit: % Sets the utility kVAR peakshave internal operatingsetpoint in % of gensetstandby kVA rating. Re-quires that Load GovernkVAR Setpoint Source =Internal and Load GovernkVAR Method = UtilitykVAR.
PC 3.x
Offset: 0 Lower Limit: −320Size (bits):16
Upper Limit: 320
Sign: S
192
Addr. ControlDescriptionAccessParameterName43865 PARCTL /
Load Gov-ern
Utility kWConstraint
Read/Write
Multiplier:1
Unit: kW Sets the utility kW mini-mum load level forconstrained base loadmode of operation. Re-quires that Load GovernkW Setpoint Source = In-ternal and Load GovernkW Method = Genset kWw/Utility Constraint.
PC 3.x
Offset: 0 Lower Limit: −20000Size (bits):16
Upper Limit: 20000
Sign: S
43866 PARCTL /Load Gov-ern
Utility kWConstraintPercent
Read/Write
Multiplier:0.01
Unit: % Sets utility kW minimumload level for constrainedbase load mode in % ofgenset standby rating.Requires that Load Gov-ern kW Setpoint Source =Internal and Load GovernkW Method = Genset kWw/Utility Constraint.
PC 3.x
Offset: 0 Lower Limit: −320Size (bits):16
Upper Limit: 320
Sign: S
43867 PARCTL /Load Gov-ern
Utility kW Set-point
Read/Write
Multiplier:1
Unit: kW Sets the utility kW peakshave internal operatingsetpoint in units of kW.Requires that Load Gov-ern kW Setpoint Source =Internal and Load GovernkW Method = Utility kW.
PC 3.x
Offset: 0 Lower Limit: −20000Size (bits):16
Upper Limit: 20000
Sign: S
43868 PARCTL /Load Gov-ern
Utility kW Set-point Percent
Read/Write
Multiplier:0.01
Unit: % Sets the utility kW peakshave internal operatingsetpoint in % of gensetstandby rating. Requiresthat Load Govern kWSetpoint Source = Inter-nal and Load Govern kWMethod = Utility kW.
PC 3.x
Offset: 0 Lower Limit: −320Size (bits):16
Upper Limit: 320
Sign: S
193
Addr. ControlDescriptionAccessParameterName43869 PARCTL /
Load Gov-ern
Utility PowerFactor Set-point
Read/Write
Multiplier:0.01
Unit: PF Sets the internal setpointfor utility power factorcontrol mode when paral-leled to utility. Requiresthat Load Govern kVARSetpoint Source = Inter-nal and Load GovernkVAR Method = UtilityPower Factor.
PC 3.x
Offset: 0 Lower Limit: 0.7Size (bits):8
Upper Limit: 1
Sign: S
43870 PCCNet /I/O Module0 MainBoard
Aux101 0Output 2Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
43871 PCCNet /I/O Module0 MainBoard
Aux101 0Output 4Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
43872 PCCNet /I/O Module0 MainBoard
Aux101 0Output 5Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
43873 PCCNet /I/O Module0 MainBoard
Aux101 0Output 6Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
194
Addr. ControlDescriptionAccessParameterName43874 PCCNet /
I/O Module0 MainBoard
Aux101 0Output 7Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U43875 PCCNet /
I/O Module1 MainBoard
Aux101 1Output 1Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43876 PCCNet /
I/O Module1 MainBoard
Aux101 1Output 2Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43877 PCCNet /
I/O Module1 MainBoard
Aux101 1Output 3Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43878 PCCNet /
I/O Module1 MainBoard
Aux101 1Output 4Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
195
Addr. ControlDescriptionAccessParameterName43879 PCCNet /
I/O Module1 MainBoard
Aux101 1Output 5Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43880 PCCNet /
I/O Module1 MainBoard
Aux101 1Output 6Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43881 PCCNet /
I/O Module1 MainBoard
Aux101 1Output 7Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43882 PCCNet /
I/O Module1 MainBoard
Aux101 1Output 8Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43883 PCCNet /
I/O Module0 Exp.Board
Aux102 0Output 10Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
196
Addr. ControlDescriptionAccessParameterName43884 PCCNet /
I/O Module0 Exp.Board
Aux102 0Output 11Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43885 PCCNet /
I/O Module0 Exp.Board
Aux102 0Output 12Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43886 PCCNet /
I/O Module0 Exp.Board
Aux102 0Output 13Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43887 PCCNet /
I/O Module0 Exp.Board
Aux102 0Output 14Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43888 PCCNet /
I/O Module0 Exp.Board
Aux102 0Output 15Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
197
Addr. ControlDescriptionAccessParameterName43889 PCCNet /
I/O Module0 Exp.Board
Aux102 0Output 16Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43890 PCCNet /
I/O Module0 Exp.Board
Aux102 0Output 9Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43891 PCCNet /
I/O Module1 Exp.Board
Aux102 1Output 10Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43892 PCCNet /
I/O Module1 Exp.Board
Aux102 1Output 11Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43893 PCCNet /
I/O Module1 Exp.Board
Aux102 1Output 12Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
198
Addr. ControlDescriptionAccessParameterName43894 PCCNet /
I/O Module1 Exp.Board
Aux102 1Output 13Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43895 PCCNet /
I/O Module1 Exp.Board
Aux102 1Output 14Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43896 PCCNet /
I/O Module1 Exp.Board
Aux102 1Output 15Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43897 PCCNet /
I/O Module1 Exp.Board
Aux102 1Output 16Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43898 PCCNet /
I/O Module1 Exp.Board
Aux102 1Output 9Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
199
Addr. ControlDescriptionAccessParameterName43900 PCCNet /
UniversalAnnuncia-tor
HMI113 Out-put 1 Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
43901 PCCNet /UniversalAnnuncia-tor
HMI113 Out-put 2 Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
43902 PCCNet /UniversalAnnuncia-tor
HMI113 Out-put 3 Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
43903 PCCNet /UniversalAnnuncia-tor
HMI113 Out-put 4 Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
43906 PARST /ParallelingControlMode
Speed DroopEnable Switch(Modbus)
Read/Write
speed droop enable switch input status from Modbus PC 2.x, PC3.x0: Inactive
1: Active
43907 PARST /ParallelingControlMode
Voltage DroopEnable Switch(Modbus)
Read/Write
Voltage droop enable switch input status from Mod-bus
PC 2.x, PC3.x
0: Inactive1: Active
43908 PARST /CircuitBreaker
Genset CBTrippedSwitch (Mod-bus)
Read/Write
genset cb tripped from Modbus PC 3.x
0: Inactive
1: Active
200
Addr. ControlDescriptionAccessParameterName43909 PARST /
CircuitBreaker
Utility CBTrippedSwitch (Mod-bus)
Read/Write
utility cb tripped switch input from Modbus PC 3.x
0: Inactive
1: Active
43910 PC Tool /Non−View-able
Save Trims Read/Write
The save trims command. PC 2.x, PC3.x0: Do Nothing
1: Save Trims43911 PCCNet /
I/O Module0 MainBoard
Aux101 0Output 3Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43912 PCCNet /
I/O Module0 MainBoard
Aux101 0Output 1Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U43913 PCCNet /
I/O Module0 MainBoard
Aux101 0Output 8Fault/Event
Read/Write
Multiplier:1
Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U43915 GC / Start/
Stop Con-trol
Extended Par-allel Enable
Read/Write
use to enable the extended paralleling mode of PTC PC 3.x0: Disabled1: Enabled
201
Addr. ControlDescriptionAccessParameterName43916 GC / Volt-
age Set-point
V/Hz KneeFrequency50Hz
Read/Write
Multiplier:0.1
Unit: Hz The voltage will roll off(decrease) proportionallyto the V/Hz setup oncethe frequency drops be-low the set point in theV/Hz Knee Frequency.This allows the genset torecover faster when thefrequency drops. This isfor 50Hz frequency.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: U
43917 GC / Volt-age Set-point
V/Hz KneeFrequency60Hz
Read/Write
Multiplier:0.1
Unit: Hz The voltage will roll off(decrease) proportionallyto the V/Hz setup oncethe frequency drops be-low the set point in theV/Hz Knee Frequency.This allows the genset torecover faster when thefrequency drops. This isfor 60Hz frequency.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: U
43918 GC / Volt-age Set-point
V/Hz RolloffSlope 50Hz
Read/Write
Multiplier:0.1
Unit: % /Hz
The amount of voltageroll off when the frequen-cy is below the knee fre-quency
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: U
43919 GC / Volt-age Set-point
V/Hz RolloffSlope 60Hz
Read/Write
Multiplier:0.1
Unit: % /Hz
The amount of voltageroll off when the frequen-cy is below the knee fre-quency
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 10
Sign: U
43920 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
202
Addr. ControlDescriptionAccessParameterName43921 ACM / Ap-
plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43922 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43923 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43924 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43925 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43926 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43927 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43928 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
203
Addr. ControlDescriptionAccessParameterName43929 ACM / Ap-
plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43930 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43931 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43932 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43933 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43934 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43935 ACM / Ap-plicationConfigura-tion
GensetSource Name
Read/Write
Multiplier:1
Unit: Name for the gensetsource.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43936 ACM / Ap-plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
204
Addr. ControlDescriptionAccessParameterName43937 ACM / Ap-
plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43938 ACM / Ap-plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43939 ACM / Ap-plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43940 ACM / Ap-plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43941 ACM / Ap-plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43942 ACM / Ap-plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43943 ACM / Ap-plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
43944 ACM / Ap-plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
205
Addr. ControlDescriptionAccessParameterName43945 ACM / Ap-
plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C43946 ACM / Ap-
plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C43947 ACM / Ap-
plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C43948 ACM / Ap-
plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C43949 ACM / Ap-
plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C43950 ACM / Ap-
plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C43951 ACM / Ap-
plicationConfigura-tion
Utility SourceName
Read/Write
Multiplier:1
Unit: Name for the Utilitysource
PC 3.x
Offset: 0 Lower Limit:Size (bits):136
Upper Limit:
Sign: C
206
Addr. ControlDescriptionAccessParameterName43952 GC /
SpeedReference
Speed/Fre-quency Delay
Read/Write
Multiplier:0.1
Unit: sec-onds
Sets the delay time forgenerating the Speed/Frequency mismatchfault
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0.5Size (bits):16
Upper Limit: 10
Sign: U
43953 GC /SpeedReference
Speed/Fre-quencyThreshold
Read/Write
Multiplier:0.1
Unit: Hz Sets the threshold forgenerating the Speed/Frequency mismatchfault
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0.5Size (bits):16
Upper Limit: 20
Sign: U
43954 PARCTL /Synchro-nizer
Sync Enable(Modbus)
Read/Write
Modbus input for enabling the synchronizer PC 3.x0: Inactive1: Active
43955 GC / Start/Stop Con-trol
Genset IdleEnable
Read/Write
Enables or Disable idling of genset with external gov-ernor.
PC 2.x, PC3.x
0: Disabled1: Enabled
43956 PARCTL /Synchro-nizer
PermissiveFrequencyMatch Error
ReadOnly
Multiplier:0.001
Unit: Hz frequency match errorvalue used by permissivesync check
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
43957 PARCTL /Synchro-nizer
PermissiveFrequencyMatch Error
ReadOnly
Multiplier:0.001
Unit: Hz frequency match errorvalue used by permissivesync check
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
43958 PARCTL /Synchro-nizer
Sync EnableCommand
ReadOnly
indicates overall status of sync enable inputs PC 3.x0: Inactive1: Active
43959 PARCTL /Load Gov-ern
Utility Un-loaded Level
Read/Write
Multiplier:1
Unit: kW Sets threshold at whichutility source is consid-ered as unloaded.
PC 3.x
Offset: 0 Lower Limit: −32768Size (bits):16
Upper Limit: 32767
Sign: S
207
Addr. ControlDescriptionAccessParameterName43960 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43961 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43962 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43963 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43964 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43965 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
208
Addr. ControlDescriptionAccessParameterName43966 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43967 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43968 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43969 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43970 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43971 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
209
Addr. ControlDescriptionAccessParameterName43972 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43973 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43974 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43975 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43976 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43977 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
210
Addr. ControlDescriptionAccessParameterName43978 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43979 PCCNet /UniversalAnnuncia-tor
HMI113 Fault1 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43980 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43981 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43982 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43983 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
211
Addr. ControlDescriptionAccessParameterName43984 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43985 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43986 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43987 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43988 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43989 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
212
Addr. ControlDescriptionAccessParameterName43990 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43991 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43992 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43993 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43994 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43995 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
213
Addr. ControlDescriptionAccessParameterName43996 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43997 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43998 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
43999 PCCNet /UniversalAnnuncia-tor
HMI113 Fault2 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
45999 CAN /CANDatalink
UnrecognizedSPN/FMI Sta-tus
ReadOnly
Indicates whether or not all pairs in current DM1 arerecognized
PC 2.x, PC3.x
0: All Pairs Recognized1: Pair Not Recognized
46000 ACM /Phase
Genset PhaseRotation
ReadOnly
Genset phase rotation PC 2.x, PC3.x0: L1−L2−L3
1: L1−L3−L22: Not Available
46001 ACM /Phase
Utility PhaseRotation
ReadOnly
Utility phase rotation PC 3.x0: L1−L2−L31: L1−L3−L22: Not Available
46002 ACM /Phase
Genset BusPhase Rota-tion
ReadOnly
Genset bus phase rotation PC 3.x0: L1−L2−L31: L1−L3−L22: Not Available
214
Addr. ControlDescriptionAccessParameterName46003 GC /
SpeedReference
Base Speed ReadOnly
Multiplier:0.0625
Unit: rpm Provides a point to moni-tor the base speed
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U46004 GC /
SpeedReference
Base Speed ReadOnly
Multiplier:0.0625
Unit: rpm Provides a point to moni-tor the base speed
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U46005 GC /
SpeedReference
Final SpeedReference
ReadOnly
Multiplier:0.0625
Unit: rpm Provides a point to moni-tor the final speed refer-ence
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U46006 GC /
SpeedReference
Final SpeedReference
ReadOnly
Multiplier:0.0625
Unit: rpm Provides a point to moni-tor the final speed refer-ence
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U46008 CAN /
CAN InputMessages
Exhaust Port1 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 1 Temperature
PC 2.x, PC3.x
Offset: 0 Lower Limit: −459Size (bits):16
Upper Limit: 3155
Sign: S46009 CAN /
CAN InputMessages
Exhaust Port2 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 2 Temperature
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S46010 CAN /
CAN InputMessages
Exhaust Port3 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 3 Temperature
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S
215
Addr. ControlDescriptionAccessParameterName46011 CAN /
CAN InputMessages
Exhaust Port4 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 4 Temperature
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S46012 CAN /
CAN InputMessages
Exhaust Port5 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 5 Temperature
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S46013 CAN /
CAN InputMessages
Exhaust Port6 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 6 Temperature
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S46014 CAN /
CAN InputMessages
Exhaust Port7 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 7 Temperature
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S46015 CAN /
CAN InputMessages
Exhaust Port8 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 8 Temperature
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S46016 CAN /
CAN InputMessages
Exhaust Port9 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 9 Temperature
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S46017 CAN /
CAN InputMessages
Exhaust Port10 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 10 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S
216
Addr. ControlDescriptionAccessParameterName46018 CAN /
CAN InputMessages
Exhaust Port11 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 11 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S
46019 CAN /CAN InputMessages
Exhaust Port12 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 12 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S
46020 CAN /CAN InputMessages
Exhaust Port13 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 13 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S
46021 CAN /CAN InputMessages
Exhaust Port14 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 14 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S
46022 CAN /CAN InputMessages
Exhaust Port15 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 15 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S
46023 CAN /CAN InputMessages
Exhaust Port16 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 16 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S
46024 CAN /CAN InputMessages
Exhaust Port17 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 17 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S
217
Addr. ControlDescriptionAccessParameterName46025 CAN /
CAN InputMessages
Exhaust Port18 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 18 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S46026 CAN /
CAN InputMessages
Exhaust Port19 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 19 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S46027 CAN /
CAN InputMessages
Exhaust Port20 Tempera-ture
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the Ex-haust Port 20 Tempera-ture
PC 2.x, PC3.x
Offset: 0 Lower Limit: −460Size (bits):16
Upper Limit: 3155
Sign: S46028 CAN_LBN
G / CANGas InputMessages
Knock LevelCylinder 1
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder1
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U46029 CAN_LBN
G / CANGas InputMessages
Knock LevelCylinder 2
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder2
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U46030 CAN_LBN
G / CANGas InputMessages
Knock LevelCylinder 3
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder3
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U46031 CAN_LBN
G / CANGas InputMessages
Knock LevelCylinder 4
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder4
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
218
Addr. ControlDescriptionAccessParameterName46032 CAN_LBN
G / CANGas InputMessages
Knock LevelCylinder 5
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder5
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46033 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 6
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder6
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46034 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 7
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder7
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46035 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 8
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder8
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46036 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 9
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder9
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46037 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 10
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder10
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46038 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 11
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder11
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46039 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 12
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder12
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
219
Addr. ControlDescriptionAccessParameterName46040 CAN_LBN
G / CANGas InputMessages
Knock LevelCylinder 13
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder13
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46041 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 14
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder14
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46042 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 15
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder15
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46043 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 16
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder16
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46044 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 17
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder17
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46045 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 18
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder18
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46046 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 19
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder19
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
46047 CAN_LBNG / CANGas InputMessages
Knock LevelCylinder 20
ReadOnly
Multiplier:1
Unit: % Knock Level for cylinder20
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
220
Addr. ControlDescriptionAccessParameterName46048 CAN_LBN
G / CANGas InputMessages
Knock CountCyl 1
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 1
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46049 CAN_LBNG / CANGas InputMessages
Knock CountCyl 2
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 2
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46050 CAN_LBNG / CANGas InputMessages
Knock CountCyl 3
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 3
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46051 CAN_LBNG / CANGas InputMessages
Knock CountCyl 4
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 4
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46052 CAN_LBNG / CANGas InputMessages
Knock CountCyl 5
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 5
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46053 CAN_LBNG / CANGas InputMessages
Knock CountCyl 6
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 6
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46054 CAN_LBNG / CANGas InputMessages
Knock CountCyl 7
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 7
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46055 CAN_LBNG / CANGas InputMessages
Knock CountCyl 8
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 8
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
221
Addr. ControlDescriptionAccessParameterName46056 CAN_LBN
G / CANGas InputMessages
Knock CountCyl 9
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 9
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46057 CAN_LBNG / CANGas InputMessages
Knock CountCyl 10
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 10
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46058 CAN_LBNG / CANGas InputMessages
Knock CountCyl 11
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 11
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46059 CAN_LBNG / CANGas InputMessages
Knock CountCyl 12
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 12
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46060 CAN_LBNG / CANGas InputMessages
Knock CountCyl 13
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 13
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46061 CAN_LBNG / CANGas InputMessages
Knock CountCyl 14
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 14
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46062 CAN_LBNG / CANGas InputMessages
Knock CountCyl 15
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 15
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46063 CAN_LBNG / CANGas InputMessages
Knock CountCyl 16
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 16
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
222
Addr. ControlDescriptionAccessParameterName46064 CAN_LBN
G / CANGas InputMessages
Knock CountCyl 17
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 17
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46065 CAN_LBNG / CANGas InputMessages
Knock CountCyl 18
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 18
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46066 CAN_LBNG / CANGas InputMessages
Knock CountCyl 19
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 19
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46067 CAN_LBNG / CANGas InputMessages
Knock CountCyl 20
ReadOnly
Multiplier:1
Unit: Knock count value forCylinder 20
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65530
Sign: U
46068 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 1
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 1
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46069 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 2
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 2
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46070 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 3
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 3
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46071 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 4
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 4
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
223
Addr. ControlDescriptionAccessParameterName46072 CAN_LBN
G / CANGas InputMessages
Spark TimingCyl 5
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 5
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46073 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 6
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 6
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46074 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 7
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 7
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46075 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 8
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 8
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46076 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 9
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 9
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46077 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 10
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 10
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46078 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 11
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 11
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46079 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 12
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 12
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
224
Addr. ControlDescriptionAccessParameterName46080 CAN_LBN
G / CANGas InputMessages
Spark TimingCyl 13
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 13
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46081 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 14
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 14
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46082 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 15
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 15
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46083 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 16
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 16
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46084 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 17
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 17
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46085 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 18
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 18
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46086 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 19
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 19
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46087 CAN_LBNG / CANGas InputMessages
Spark TimingCyl 20
ReadOnly
Multiplier:0.1
Unit: De-grees
Spark timing degrees forcylinder 20
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
225
Addr. ControlDescriptionAccessParameterName46088 CAN_LBN
G / CANGas InputMessages
InternalSSM558 1Temperature
ReadOnly
Multiplier:0.1
Unit: degF Temperature of the en-gine electronic controlunit SSM558 1
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S46089 CAN_LBN
G / CANGas InputMessages
InternalSSM558 2Temperature
ReadOnly
Multiplier:0.1
Unit: degF Temperature of the en-gine electronic controlunit SSM558 2
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S46090 CAN_LBN
G / CANGas InputMessages
InternalMCM700Temperature
ReadOnly
Multiplier:0.1
Unit: degF Temperature of the en-gine electronic controlunit MCM700
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S46091 CAN_LBN
G / CANGas InputMessages
Derate Autho-rization
ReadOnly
Derate authorization request from customer. PC 3.x0: NO1: YES2: Reserved3: N/A
46092 CAN_LBNG / CANGas InputMessages
Start SystemStatus
ReadOnly
Start system status monitor point. PC 3.x0: Not Tripped1: Tripped2: Reserved3: N/A
46093 CAN_LBNG / CANGas InputMessages
Ventilator FanStatus
ReadOnly
Vent Fan status monitor point. PC 3.x0: OFF1: ON2: TRIPPED3: N/A
46094 CAN_LBNG / CANGas InputMessages
Louvres Sta-tus
ReadOnly
Louvres Closed monitor point. PC 3.x0: Open1: Closed2: Reserved3: N/A
46095 CAN_LBNG / CANGas InputMessages
Radiator FanStatus
ReadOnly
Radiator Fan status monitor point. PC 3.x0: OFF1: ON2: TRIPPED3: N/A
226
Addr. ControlDescriptionAccessParameterName46096 CAN_LBN
G / CANGas InputMessages
GIB IsolatorOpen(Aux101)
ReadOnly
GIB Isolator Open monitor point. PC 3.x0: Close1: Open2: Reserved3: N/A
46097 AD_LBNG/ LBNGAuxiliaryDevices
AlternatorHeater Status
ReadOnly
Alternator Heater status monitor point. PC 3.x0: OFF1: ON2: TRIPPED3: N/A
46099 CAN_LBNG / CANGas InputMessages
Gearbox OilPressure(Aux101)
ReadOnly
Gearbox Oil Pressure monitor point. PC 3.x
0: No
1: Yes
46100 CAN_LBNG / CANGas InputMessages
Gearbox OilTemperature(Aux101)
ReadOnly
Gearbox Oil Temperature monitor point. PC 3.x
0: No
1: Yes
46101 CAN_LBNG / CANGas InputMessages
Start InhibitNo1 (Aux101)
ReadOnly
Start Inhibit No1 monitor point. PC 3.x0: Inactive1: Active2: Reserved3: N/A
46102 CAN_LBNG / CANGas InputMessages
Start InhibitNo2 (Aux101)
ReadOnly
Start Inhibit No2 monitor point. PC 3.x0: Inactive1: Active2: Reserved3: N/A
46103 CAN_LBNG / CANGas InputMessages
Start InhibitNo3 (Aux101)
ReadOnly
Start Inhibit No3 monitor point. PC 3.x0: Inactive1: Active2: Reserved3: N/A
46104 CAN_LBNG / CANGas InputMessages
DC PSU Un-available(Aux101)
ReadOnly
Engine PSU Not Available monitor point. PC 3.x
0: No
1: Yes
46105 CAN_LBNG / CANGas InputMessages
Ventilator FanTrip (Aux101)
ReadOnly
Ventilator Fan Trip monitor point. PC 3.x
0: No
1: Yes
46106 CAN_LBNG / CANGas InputMessages
Aux101−3Software Ver-sion
ReadOnly
Multiplier:0.01
Unit: Software version of thefirmware for theAux101−3
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
227
Addr. ControlDescriptionAccessParameterName46107 CAN_LBN
G /Aux101−4Software Ver-sion
ReadOnly
Multiplier:0.01
Unit: Software version of thefirmware for theAux101−4
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46108 CAN_LBN
G /Aux101−5Software Ver-sion
ReadOnly
Multiplier:0.01
Unit: Software version of thefirmware for theAux101−5
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46109 CAN_LBN
G / CANGas InputMessages
Engine Oper-ating State
ReadOnly
Indicate current state or mode of operation by the en-gine
PC 3.x
0: Engine Stopped1: Pre−Start2: Starting3: Warm−Up4: Running5: Cool−Down6: Engine Stopping7: Post−Run
46110 CAN_LBNG / CANGas InputMessages
Fuel PumpControl Status
ReadOnly
Fuel pump state PC 3.x
0: Inactive
1: Active
46111 CAN_LBNG / CANGas InputMessages
Time Remain-ing in EngineOperatingState
ReadOnly
Multiplier:1
Unit: sec-onds
Indicate time remaining inthe current engine state
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46112 CAN_LBN
G / CANGas InputMessages
Fuel ShutoffVent Valvestatus
ReadOnly
Fuel shutoff valve status PC 3.x
0: Closed
1: Open
46113 CAN_LBNG / CANGas InputMessages
DownstreamValve Com-mand Status
ReadOnly
The result of the FSO driver output command logic forfuel shutoff valve 1
PC 3.x
0: Closed1: Open2: Reserved3: N/A
46114 CAN_LBNG / CANGas InputMessages
UpstreamValve Com-mand Status
ReadOnly
The result of the FSO driver output command logic forfuel shutoff valve 2
PC 3.x
0: Closed1: Open2: Reserved3: N/A
228
Addr. ControlDescriptionAccessParameterName46115 CAN_LBN
G / CANGas InputMessages
VPS Status ReadOnly
Control setting for fuel shutoff valve proving systemtest
PC 3.x
0: Not Tested1: Pass2: Reserved3: FAIL
46116 CAN_LBNG / CANGas InputMessages
Gas SupplyPressure
ReadOnly
Multiplier:0.1
Unit: psi Gage Pressure of gassupply to fuel meteringdevice.
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46117 CAN_LBNG / CANGas InputMessages
Engine OilPreHeater CtrlStatus
ReadOnly
Engine Oil pre heater command status PC 3.x0: OFF1: ON2: Reserved3: N/A
46118 CAN_LBNG / CANGas InputMessages
Engine PowerConservationCtrl Status
ReadOnly
Control setting for cutting power to various deviceswhen the engine is not in use
PC 3.x
0: OFF1: ON
46119 CAN_LBNG / CANGas InputMessages
Engine Cool-ant PreHeaterCtrl Status
ReadOnly
Engine coolant PreHeater states PC 3.x0: OFF1: ON2: Reserved3: N/A
46120 CAN_LBNG / CANGas InputMessages
Engine Cool-ant Pump CtrlStatus
ReadOnly
Engine coolant circulating pump status PC 3.x0: OFF1: ON2: Reserved3: N/A
46121 CAN_LBNG / CANGas InputMessages
Engine Con-trolled Shut-down Request
ReadOnly
Active when the engine control request a controlledshutdown (shutdown with cooldown)
PC 3.x
0: Inactive1: Active
46122 CAN_LBNG / CANGas InputMessages
EmergencyShutdown Re-quest
ReadOnly
Active when the engine control request an emergen-cy shutdown (immediate shutdown)
PC 3.x
0: Inactive1: Active
46123 CAN_LBNG / CANGas InputMessages
Engine DerateRequest
ReadOnly
Multiplier:0.4
Unit: Per-cent
Derate request in percentmade by the engine con-trol
PC 3.x
Offset: 0 Lower Limit:Size (bits):8
Upper Limit:
Sign: U
229
Addr. ControlDescriptionAccessParameterName46124 CAN /
CAN InputMessages
Coolant Pres-sure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for theCoolant Pressure.
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 145
Sign: U46125 CAN_LBN
G / CANGas InputMessages
Coolant 2Pressure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for theCoolant 2 Pressure.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 145
Sign: U46127 CAN_LBN
G / CANGas InputMessages
Coolant 2Temperature
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for theCoolant 2 Temperature
PC 3.x
Offset: 0 Lower Limit: −40Size (bits):16
Upper Limit: 260
Sign: S46128 CAN_LBN
G / CANGas InputMessages
CompressorBypass Posi-tion
ReadOnly
Multiplier:0.1
Unit: % Engine turbochargercompressor bypass ac-tuator position
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46129 CAN_LBN
G / CANGas InputMessages
Engine Oil Fil-ter OutletPressure
ReadOnly
Multiplier:0.1
Unit: psi Engine oil pressure at theoutlet of the filter
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46130 CAN_LBN
G / CANGas InputMessages
Oil PrimingPump ControlStatus
ReadOnly
Status for the priming pump (ON or OFF) PC 3.x0: OFF1: ON2: Reserved3: N/A
46131 CAN_LBNG / CANGas InputMessages
Oil PrimingState
ReadOnly
Status of the engine before start (Pre−Lubed or Not) PC 3.x0: Low1: Optimum2: Reserved3: N/A
46132 CAN_LBNG / CANGas InputMessages
Oil Pre−Heated State
ReadOnly
Status of the engine oil before start (Pre−Heated orNot)
PC 3.x
0: Heated1: Cold2: Not Available
230
Addr. ControlDescriptionAccessParameterName46133 CAN_LBN
G / CANGas InputMessages
Coolant Pre−Heated State
ReadOnly
Status of the engine coolant before start (Pre−Heatedor Not)
PC 3.x
0: Heated1: Cold2: Not Available
46134 CAN_LBNG / CANGas InputMessages
VentilationStatus
ReadOnly
Engine Ventilation Status (Vented or Not) PC 3.x0: Vented1: Not Vented2: Ventilation Delay3: Currently Venting4: Not Able To Determine5: Not Available
46135 CAN_LBNG / CANGas InputMessages
Intake Man-ifold Pressure1
ReadOnly
Multiplier:0.1
Unit: psi Intake Manifold Pressure1
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46136 CAN_LBN
G / CANGas InputMessages
CompressorOutlet Pres-sure
ReadOnly
Multiplier:0.1
Unit: kPa Absolute Pressure at theoutlet of the compressor.
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46137 CAN_LBN
G / CANGas InputMessages
Turbocharger1 Boost Pres-sure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for theTurbocharger 1 BoostPressure
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 1160
Sign: U46138 CAN_LBN
G / CANGas InputMessages
Genset AvgAC Frequency
ReadOnly
Multiplier:0.1
Unit: Hz Average Genset AC fre-quency
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46139 CAN_LBN
G / CANGas InputMessages
Fuel Valve 1Inlet AbsolutePressure
ReadOnly
Multiplier:0.1
Unit: psi Absolute Pressure of Gason the inlet side of thefirst system control valve
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
231
Addr. ControlDescriptionAccessParameterName46140 CAN_LBN
G / CANGas InputMessages
Fuel Valve 1Outlet Abso-lute Pressure
ReadOnly
Multiplier:0.1
Unit: psi Absolute Pressure of Gason the outlet side of thefirst system control valve
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46141 CAN_LBNG / CANGas InputMessages
Fuel Valve 1Position
ReadOnly
Multiplier:0.1
Unit: % PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46142 CAN_LBNG / CANGas InputMessages
Fuel Valve 2Inlet AbsolutePressure
ReadOnly
Multiplier:0.1
Unit: psi Absolute Pressure of Gason the inlet side of thesecond system controlvalve
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46143 CAN_LBNG / CANGas InputMessages
Fuel Valve 2Outlet Abso-lute Pressure
ReadOnly
Multiplier:0.1
Unit: psi Absolute Pressure of Gason the outlet side of thesecond system controlvalve
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46144 CAN_LBNG / CANGas InputMessages
Fuel Valve 2Position
ReadOnly
Multiplier:0.1
Unit: % PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46145 CAN_LBNG / CANGas InputMessages
Gas MassFlow
ReadOnly
Multiplier:0.1
Unit:Poundsper hour
Gas Mass Flow value ofthe engine.
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
46146 CAN_LBNG / CANGas InputMessages
Gas MassFlow
ReadOnly
Multiplier:0.1
Unit:Poundsper hour
Gas Mass Flow value ofthe engine.
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
232
Addr. ControlDescriptionAccessParameterName46147 CAN_LBN
G / CANGas InputMessages
Throttle 1Position
ReadOnly
Multiplier:0.1
Unit: % Position of the throttle 1. PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46148 CAN_LBNG / CANGas InputMessages
Throttle 2Position
ReadOnly
Multiplier:0.1
Unit: % Position of the throttle 2. PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46149 CAN_LBNG / CANGas InputMessages
Raw Value DERTD Bearing
ReadOnly
Multiplier:1
Unit:Count
Raw Value for the DERTD Bearing from theAux101
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46150 CAN_LBNG / CANGas InputMessages
Raw Value Al-ternator RTDL1
ReadOnly
Multiplier:1
Unit:Count
Raw Value AlternatorRTD L1 from Aux101 (10bits raw data)
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46151 CAN_LBNG / CANGas InputMessages
Raw Value Al-ternator RTDL2
ReadOnly
Multiplier:1
Unit:Count
Raw Value AlternatorRTD L2 from Aux101 (10bits raw data)
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46152 CAN_LBNG / CANGas InputMessages
Raw Value Al-ternator RTDL3
ReadOnly
Multiplier:1
Unit:Count
Raw Value AlternatorRTD L3 from Aux101 (10bits raw data)
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46153 CAN_LBNG / CANGas InputMessages
Raw ValueNDE RTDBearing
ReadOnly
Multiplier:1
Unit:Count
Raw Value NDE RTDBearing from Aux101 (10bits raw data)
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
233
Addr. ControlDescriptionAccessParameterName46154 CAN_LBN
G / CANGas InputMessages
LBNG Key-switch Com-mand
ReadOnly
Driver command that controls the output for the key-switch
PC 3.x
0: Inactive1: Active
46155 CAN_LBNG / CANGas InputMessages
MCM700 Bat-tery Voltage
ReadOnly
Multiplier:0.1
Unit: Vdc Engine Control ModuleBattery Voltage.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
46156 CAN_LBNG / CANGas InputMessages
MCM700 Iso-lated BatteryVoltage
ReadOnly
Multiplier:0.1
Unit: Vdc Engine Control ModuleIsolated Battery Voltage.
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46157 CAN_LBNG / CANGas InputMessages
CM700 Sen-sor Voltage A
ReadOnly
Multiplier:0.1
Unit: Vdc Engine Control ModuleCM700 Sensor Voltage A
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46158 CAN_LBNG / CANGas InputMessages
CM700 Sen-sor Voltage B
ReadOnly
Multiplier:0.1
Unit: Vdc Engine Control ModuleCM700 Sensor Voltage B
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46159 CAN_LBNG / CANGas InputMessages
CM700 Sen-sor Voltage C
ReadOnly
Multiplier:0.1
Unit: Vdc Engine Control ModuleCM700 Sensor Voltage C
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46160 CAN_LBNG / CANGas InputMessages
SSM558 1Battery Volt-age
ReadOnly
Multiplier:0.1
Unit: Vdc SSM558 1 Engine Con-trol Module Battery Volt-age.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
46161 CAN_LBNG / CANGas InputMessages
SSM558 1Isolated Bat-tery Voltage
ReadOnly
Multiplier:0.1
Unit: Vdc SSM558 1 Engine Con-trol Module Isolated Bat-tery Voltage.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
234
Addr. ControlDescriptionAccessParameterName46162 CAN_LBN
G / CANGas InputMessages
SSM558 2Battery Volt-age
ReadOnly
Multiplier:0.1
Unit: Vdc SSM558 2 Engine Con-trol Module Battery Volt-age.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U46163 CAN_LBN
G / CANGas InputMessages
SSM558 2Isolated Bat-tery Voltage
ReadOnly
Multiplier:0.1
Unit: Vdc SSM558 2 Engine Con-trol Module Isolated Bat-tery Voltage.
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U46164 CAN_LBN
G / CANGas InputMessages
Intake Man-ifold Pressure2
ReadOnly
Multiplier:0.1
Unit: psi Intake Manifold Pressure2
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46165 CAN_LBN
G / CANGas InputMessages
Intake Man-ifold Tempera-ture 2
ReadOnly
Multiplier:0.1
Unit: degF Monitor point for the In-take Manifold Tempera-ture 2
PC 3.x
Offset: 0 Lower Limit: −40Size (bits):16
Upper Limit: 410
Sign: S46166 CAN_LBN
G / CANGas InputMessages
Exhaust BackPressure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for exhaustback pressure value
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46168 CAN_LBN
G / CANGas InputMessages
Air Filter Dif-ferential Pres-sure
ReadOnly
Multiplier:0.1
Unit: psi Monitor point for air filterdifferential pressure value
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S46170 CAN_LBN
G / CANGas InputMessages
Gas MassFlow 2
ReadOnly
Multiplier:0.1
Unit:Poundsper hour
Gas Mass Flow 2 valueof the engine.
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
235
Addr. ControlDescriptionAccessParameterName46171 CAN_LBN
G / CANGas InputMessages
Gas MassFlow 2
ReadOnly
Multiplier:0.1
Unit:Poundsper hour
Gas Mass Flow 2 valueof the engine.
PC 3.x
Offset: 0 Lower Limit:Size (bits):32
Upper Limit:
Sign: U
46272 CAN_LBNG / CANGas InputMessages
Engine ECMInternal Tem-perature
ReadOnly
Multiplier:0.1
Unit: degF Temperature of the en-gine electronic controlunit
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: S
46175 AD_LBNG/ Gearbox
Gearbox OilPressure Low
ReadOnly
Occurs when Gearbox Low Oil Pressure switch be-comes active.
PC 3.x
0: Inactive1: Active
46176 AD_LBNG/ Gearbox
GearboxPresent
Read/Write
Enables gearbox protection. PC 3.x0: No1: Yes
46180 AD_LBNG/ DiscreteInputs
E−Stops dis-engaged
ReadOnly
Monitors the E−Stops switches. PC 3.x0: Inactive1: Active
46182 AD_LBNG/ LBNGAuxiliaryDevices
Radiator Fancontrol
ReadOnly
Radiator fan control command PC 3.x
0: Inactive
1: Active
46183 AD_LBNG/ LBNGAuxiliaryDevices
Ventilator Fanmode
Read/Write
Vent fan control mode limited or continuous PC 3.x
0: Limited
1: Continuous
46184 AD_LBNG/ LBNGAuxiliaryDevices
Louvre Con-trol
ReadOnly
Louvre control PC 3.x
0: Inactive
1: Active
46191 AD_LBNG/ LBNGAuxiliaryDevices
Ventilator Fancontrol
ReadOnly
Ventilator fan control command PC 3.x
0: Inactive
1: Active
46273 CAN_LBNG / CANGas InputMessages
AlternatorHeater ON(Aux101)
ReadOnly
Alternator Heater monitor point. PC 3.x
0: No
1: Yes
46288 CAN_LBNG / CANGas InputMessages
DE/NDE Cyl-inder View-point Refer-ence
Read/Write
Gives reference point for engine cylinder numbering PC 3.x0: Drive End1: Non−Drive End2: Reserved3: N/A
236
Addr. ControlDescriptionAccessParameterName46289 CAN_LBN
G / CANGas InputMessages
Start SystemTrip (Aux 101)
ReadOnly
Start system trip monitor point. PC 3.x0: Not Tripped1: Tripped2: Reserved3: N/A
46290 CAN_LBNG / CANGas InputMessages
LouvresClosed (Aux101)
ReadOnly
Louvres Closed monitor point. PC 3.x0: Open1: Closed2: Reserved3: N/A
46291 CAN_LBNG / CANGas InputMessages
Radiator FanTrip (Aux 101)
ReadOnly
Radiator Fan Trip monitor point. PC 3.x0: Not Tripped1: Tripped2: Reserved3: N/A
46300 CAN_LBNG / Con-trollerModes
LBNG GensetEnable
Read/Write
Switch to enable or disable the gas specific featuresand parameters
PC 3.x
0: Disable1: Enable
46301 CAN_LBNG / CANGas InputMessages
Aux101−3 En-able
Read/Write
Enable the processing for Aux101−3 messages PC 3.x
0: Disable
1: Enable
46302 CAN_LBNG / CANGas InputMessages
Aux101−4 En-able
Read/Write
Enable the processing for Aux101−4 messages PC 3.x
0: Disable
1: Enable
46303 CAN_LBNG / CANGas InputMessages
Aux101−5 En-able
Read/Write
Enable the processing for Aux101−5 messages PC 3.x
0: Disable
1: Enable
46304 CAN_LBNG / CANGas InputMessages
Aux101−6 En-able
Read/Write
Enable the processing for Aux101−6 messages PC 3.x
0: Disable
1: Enable
46308 CAN_LBNG / CANGas InputMessages
Aux101−3 In-put Port Con-fig
Read/Write
Multiplier:1
Unit: Input Port configurationbye for the Aux101−3
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 255
Sign: U
46309 CAN_LBNG / CANGas InputMessages
Aux101−4 In-put Port Con-fig
Read/Write
Multiplier:1
Unit: Input Port configurationbye for the Aux101−4
PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 255
Sign: U
237
Addr. ControlDescriptionAccessParameterName46310 CAN_LBN
G / CANGas InputMessages
Aux101−5 In-put Port Con-fig
Read/Write
Multiplier:1
Unit: Input Port configurationbye for the Aux101−5
PC 3.x
Offset: 0 Lower Limit: 0
Size (bits):16
Upper Limit: 255
Sign: U
46311 CAN_LBNG / CANGas InputMessages
Aux101−3 DIActive High/Low Selection
Read/Write
Multiplier:1
Unit: Digital Input Port configu-ration active High or ac-tive low for the Aux101−3
PC 3.x
Offset: 0 Lower Limit: 0
Size (bits):16
Upper Limit: 255
Sign: U
46312 CAN_LBNG / CANGas InputMessages
Aux101−4 DIActive High/Low Selection
Read/Write
Multiplier:1
Unit: Digital Input Port configu-ration active High or ac-tive low for the Aux101−4
PC 3.x
Offset: 0 Lower Limit: 0
Size (bits):16
Upper Limit: 255
Sign: U
46313 CAN_LBNG / CANGas InputMessages
Aux101−5 DIActive High/Low Selection
Read/Write
Multiplier:1
Unit: Digital Input Port configu-ration active High or ac-tive low for the Aux101−5
PC 3.x
Offset: 0 Lower Limit: 0
Size (bits):16
Upper Limit: 255
Sign: U
46314 CAN_LBNG / CANGas InputMessages
Aux101−3 DIConfig Mask
Read/Write
Multiplier:1
Unit: Discrete Input configura-tion bit mask for theAux101−3
PC 3.x
Offset: 0 Lower Limit: 0
Size (bits):16
Upper Limit: 255
Sign: U
46315 CAN_LBNG / CANGas InputMessages
Aux101−4 DIConfig Mask
Read/Write
Multiplier:1
Unit: Discrete Input configura-tion bit mask for theAux101−4
PC 3.x
Offset: 0 Lower Limit: 0
Size (bits):16
Upper Limit: 255
Sign: U
238
Addr. ControlDescriptionAccessParameterName46316 CAN_LBN
G / CANGas InputMessages
Aux101−5 DIConfig Mask
Read/Write
Multiplier:1
Unit: Discrete Input configura-tion bit mask for theAux101−5
PC 3.x
Offset: 0 Lower Limit: 0
Size (bits):16
Upper Limit: 255
Sign: U
46317 CAN_LBNG / CANGas InputMessages
Rated OilTemperatureThreshold
Read/Write
Multiplier:0.015625
Unit: degF Oil temperature thresholdfor the engine to be ableto run at rated speed
PC 3.x
Offset: 0 Lower Limit: 0
Size (bits):16
Upper Limit: 60
Sign: S
46318 CAN_LBNG / CANGas InputMessages
Alternator Effi-ciency
Read/Write
Multiplier:0.0025
Unit: % Alternator efficiency PC 3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 1
Sign: U
46323 CAN_LBNG / CANGas InputMessages
Vehicle Elec-trical Power 2PGN65165Enable
Read/Write
A trim that enables the Vehicle Electrical Power 2message
PC 3.x
0: Disabled1: Enabled
46326 CAN_LBNG / CANGas InputMessages
Gaseous FuelPressurePGN65163Enable
Read/Write
A trim that enables the Gaseous Fuel Pressure mes-sage
PC 3.x
0: Disabled1: Enabled
46327 CAN_LBNG / CANGas InputMessages
Fuel Informa-tion 3 − Gas-eousPGN64930Enable
Read/Write
A trim that enables the Fuel Information 3 − Gaseousmessage
PC 3.x
0: Disabled
1: Enabled
46328 CAN_LBNG / CANGas InputMessages
Fuel Informa-tion 2 − Gas-eousPGN65153Enable
Read/Write
A trim that enables the Fuel Information 2 − Gaseousmessage
PC 3.x
0: Disabled
1: Enabled
46332 CAN_LBNG / CANGas InputMessages
Inlet/ExhaustConditionsPGN65270Enable
Read/Write
A trim that enables the Inlet/Exhaust Conditions mes-sage
PC 3.x
0: Disabled1: Enabled
46333 CAN_LBNG / CANGas InputMessages
Knock Count1 PGN65336Enable
Read/Write
A trim that enables Knock Count 1 message PC 3.x
0: Disabled
1: Enabled
239
Addr. ControlDescriptionAccessParameterName46334 CAN_LBN
G / CANGas InputMessages
Knock Count2 PGN65337Enable
Read/Write
A trim that enables Knock Count 2 message PC 3.x
0: Disabled
1: Enabled
46335 CAN_LBNG / CANGas InputMessages
Knock Count3 PGN65338Enable
Read/Write
A trim that enables Knock Count 3 message PC 3.x
0: Disabled
1: Enabled
46336 CAN_LBNG / CANGas InputMessages
Knock Count4 PGN65339Enable
Read/Write
A trim that enables Knock Count 4 message PC 3.x
0: Disabled
1: Enabled
46337 CAN_LBNG / CANGas InputMessages
Knock Count5 PGN65340Enable
Read/Write
A trim that enables Knock Count 5 message PC 3.x
0: Disabled
1: Enabled
46338 CAN_LBNG / CANGas InputMessages
Ignition Tim-ing 1PGN65154Enable
Read/Write
A trim that enables the Ignition Timing 1 message PC 3.x
0: Disabled
1: Enabled
46339 CAN_LBNG / CANGas InputMessages
Ignition Tim-ing 2PGN65155Enable
Read/Write
A trim that enables the Ignition Timing 2 message PC 3.x
0: Disabled
1: Enabled
46340 CAN_LBNG / CANGas InputMessages
Ignition Tim-ing 3PGN65156Enable
Read/Write
A trim that enables the Ignition Timing 3 message PC 3.x
0: Disabled
1: Enabled
46341 CAN_LBNG / CANGas InputMessages
Ignition Tim-ing 4PGN65157Enable
Read/Write
A trim that enables the Ignition Timing 4 message PC 3.x
0: Disabled
1: Enabled
46342 CAN_LBNG / CANGas InputMessages
Ignition Tim-ing 5PGN65158Enable
Read/Write
A trim that enables the Ignition Timing 5 message PC 3.x
0: Disabled
1: Enabled
46344 GC /LBNGStart−En-able Func-tion
Start−Enable(MODBUS In-put)
Read/Write
Remote MODBUS Start−Enable input. PC 3.x
0: Disable
1: Enable
46346 CAN_LBNG / CANGas InputMessages
Cylinder Iden-tification Start-ing Point
Read/Write
Parameter to define on which end is the numbering ofthe cylinder starting on the HMI (NDE or DE)
PC 3.x
0: Drive End1: Non Drive End2: N/A
240
Addr. ControlDescriptionAccessParameterName46348 GC /
SpeedReference
Target Speed ReadOnly
Multiplier:0.0625
Unit: rpm The speed referencefunction desired speedbefore ramping
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4000
Sign: U46349 GC /
SpeedReference
Target Speed ReadOnly
Multiplier:0.0625
Unit: rpm The speed referencefunction desired speedbefore ramping
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):32
Upper Limit: 4000
Sign: U46367 Modbus /
ModbusModbus BusMessageCount (J14)
ReadOnly
Multiplier:1
Unit: The number of Modusmessages with no re-sponse for J14 port only
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46366 Modbus /
ModbusModbus StopBits (J14)
Read/Write
Sets the Modus number of stop bits for this node Lim-ited to 1 bit if parity = Odd or Even
PC 3.x
0: 011: 02
46368 Modbus /Modbus
Modbus CRCError Count(J14)
ReadOnly
Multiplier:1
Unit: The number of ModusCRC errors for J14 only.
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46369 Modbus /
ModbusModbus Ex-ception Count(J14)
ReadOnly
Multiplier:1
Unit: Modbus exception countfor J14 only.
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46370 Modbus /
ModbusModbus NoResponseCount (J14)
ReadOnly
Multiplier:1
Unit: Modbus no responsecount for J14 only.
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
241
Addr. ControlDescriptionAccessParameterName46371 Modbus /
ModbusModbus SlaveMessageCount (J14)
ReadOnly
Multiplier:1
Unit: The number of Modbusslave messages for J14only.
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U46372 Modbus /
ModbusModbus NodeAddress (J14)
Read/Write
Multiplier:1
Unit: Sets the Modus addressfor this node for J14 only.
PC 3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 247
Sign: U46373 Modbus /
ModbusModbus BaudRate (J14)
Read/Write
Sets the baud rate for Modus communications for J14only.
PC 3.x
1.666666663.3756.753: 19200
46374 Modbus /Modbus
Modbus Parity(J14)
Read/Write
Sets the Modus parity for this node for J14 only. PC 3.x0: Even1: Odd2: None
46376 Modbus /Modbus
Modbus BaudRate
Read/Write
Sets the Modus baud rate. PC 2.x, PC3.x0: 2400 Baud
1: 4800 Baud2: 9600 Baud3: 19200 Baud4: 38400 Baud
46377 Modbus /Modbus
Modbus Parity Read/Write
Sets the Modus parity for this node PC 2.x, PC3.x0: Even
1: Odd2: None
46378 Modbus /Modbus
Modbus NodeAddress
Read/Write
Multiplier:1
Unit: Sets the Modus addressfor this node
PC 2.x, PC3.x
Offset: 0 Lower Limit: 1Size (bits):8
Upper Limit: 247
Sign: U46379 Modbus /
ModbusModbus StopBits
Read/Write
Sets the Modus number of stop bits for this node Lim-ited to 1 bit if parity = Odd or Even
PC 2.x, PC3.x
0: 011: 02
242
Addr. ControlDescriptionAccessParameterName46380 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46381 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46382 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46383 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46384 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46385 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
243
Addr. ControlDescriptionAccessParameterName46386 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46387 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46388 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46389 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46390 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46391 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
244
Addr. ControlDescriptionAccessParameterName46392 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46393 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46394 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46395 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46396 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46397 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
245
Addr. ControlDescriptionAccessParameterName46398 PCCNet /
UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46399 PCCNet /UniversalAnnuncia-tor
HMI113 Fault3 Text
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46561 PCCNet /OperatorPanel
Operator Pan-el Status
ReadOnly
Multiplier:1
Unit: 16−bit number to repre-sent the status of opera-tor panel indications.
PC 3.x
Offset: 0 Lower Limit:Size (bits):16
Upper Limit:
Sign: U
46600 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46601 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46602 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
246
Addr. ControlDescriptionAccessParameterName46603 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46604 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46605 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46606 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46607 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46608 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
247
Addr. ControlDescriptionAccessParameterName46609 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46610 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46611 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46612 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46613 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46614 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
248
Addr. ControlDescriptionAccessParameterName46615 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46616 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46617 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46618 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46619 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46620 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
249
Addr. ControlDescriptionAccessParameterName46621 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46622 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46623 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46624 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46625 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46626 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
250
Addr. ControlDescriptionAccessParameterName46627 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46628 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46629 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46630 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46631 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46632 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
251
Addr. ControlDescriptionAccessParameterName46633 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46634 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46635 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46636 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46637 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46638 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
252
Addr. ControlDescriptionAccessParameterName46639 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46640 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46641 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46642 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46643 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46644 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
253
Addr. ControlDescriptionAccessParameterName46645 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46646 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46647 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46648 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46649 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46650 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
254
Addr. ControlDescriptionAccessParameterName46651 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46652 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46653 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46654 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46655 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46656 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
255
Addr. ControlDescriptionAccessParameterName46657 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46658 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46659 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 1 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46660 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46661 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46662 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
256
Addr. ControlDescriptionAccessParameterName46663 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46664 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46665 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46666 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46667 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46668 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
257
Addr. ControlDescriptionAccessParameterName46669 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46670 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46671 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46672 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46673 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46674 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
258
Addr. ControlDescriptionAccessParameterName46675 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46676 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46677 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46678 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46679 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 2 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46800 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
259
Addr. ControlDescriptionAccessParameterName46801 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46802 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46803 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46804 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46805 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46806 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
260
Addr. ControlDescriptionAccessParameterName46807 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46808 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46809 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46810 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46811 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46812 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
261
Addr. ControlDescriptionAccessParameterName46813 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46814 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46815 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46816 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46817 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46818 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
262
Addr. ControlDescriptionAccessParameterName46819 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46820 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46821 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46822 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46823 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46824 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
263
Addr. ControlDescriptionAccessParameterName46825 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46826 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46827 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46828 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46829 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46830 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
264
Addr. ControlDescriptionAccessParameterName46831 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46832 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46833 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46834 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46835 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46836 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
265
Addr. ControlDescriptionAccessParameterName46837 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46838 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46839 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46840 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46841 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46842 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
266
Addr. ControlDescriptionAccessParameterName46843 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46844 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46845 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46846 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46847 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46848 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
267
Addr. ControlDescriptionAccessParameterName46849 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46850 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46851 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46852 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46853 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46854 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
268
Addr. ControlDescriptionAccessParameterName46855 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46856 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46857 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46858 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46859 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46860 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
269
Addr. ControlDescriptionAccessParameterName46861 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46862 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46863 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46864 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46865 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46866 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
270
Addr. ControlDescriptionAccessParameterName46867 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46868 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46869 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46870 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46871 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46872 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
271
Addr. ControlDescriptionAccessParameterName46873 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46874 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46875 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46876 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46877 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46878 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
272
Addr. ControlDescriptionAccessParameterName46879 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46880 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46881 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46882 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46883 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46884 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
273
Addr. ControlDescriptionAccessParameterName46885 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46886 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46887 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46888 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46889 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46890 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
274
Addr. ControlDescriptionAccessParameterName46891 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46892 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46893 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46894 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46895 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46896 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
275
Addr. ControlDescriptionAccessParameterName46897 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46898 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46899 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 3 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46900 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46901 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46902 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
276
Addr. ControlDescriptionAccessParameterName46903 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46904 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46905 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46906 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46907 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46908 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
277
Addr. ControlDescriptionAccessParameterName46909 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46910 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46911 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46912 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46913 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46914 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
278
Addr. ControlDescriptionAccessParameterName46915 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46916 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46917 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46918 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46919 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 4 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46920 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
279
Addr. ControlDescriptionAccessParameterName46921 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46922 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46923 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46924 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46925 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46926 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
280
Addr. ControlDescriptionAccessParameterName46927 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46928 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46929 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46930 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46931 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46932 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
281
Addr. ControlDescriptionAccessParameterName46933 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46934 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46935 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46936 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46937 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46938 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
282
Addr. ControlDescriptionAccessParameterName46939 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 5 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46940 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46941 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46942 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46943 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46944 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
283
Addr. ControlDescriptionAccessParameterName46945 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46946 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46947 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46948 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46949 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46950 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
284
Addr. ControlDescriptionAccessParameterName46951 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46952 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46953 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46954 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46955 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46956 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
285
Addr. ControlDescriptionAccessParameterName46957 PCCNet /
I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46958 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46959 PCCNet /I/O Module1 MainBoard
Aux101 1 In-put 6 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46960 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46961 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46962 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
286
Addr. ControlDescriptionAccessParameterName46963 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46964 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46965 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46966 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46967 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46968 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
287
Addr. ControlDescriptionAccessParameterName46969 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46970 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46971 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46972 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46973 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46974 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
288
Addr. ControlDescriptionAccessParameterName46975 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46976 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46977 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46978 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46979 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 7 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46980 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
289
Addr. ControlDescriptionAccessParameterName46981 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46982 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46983 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46984 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46985 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46986 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
290
Addr. ControlDescriptionAccessParameterName46987 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46988 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46989 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46990 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46991 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46992 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
291
Addr. ControlDescriptionAccessParameterName46993 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46994 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46995 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46996 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46997 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
46998 PCCNet /I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
292
Addr. ControlDescriptionAccessParameterName46999 PCCNet /
I/O Module0 MainBoard
Aux101 0 In-put 8 FaultText
Read/Write
Multiplier:1
Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.
PC 2.x, PC3.x
Offset: 0 Lower Limit:Size (bits):168
Upper Limit:
Sign: C
47001 GC / Gov-ernor
ElectronicGovernor En-able
Read/Write
Disable for mechanical governed genset. MODBUSAccess: Ready Only
PC 2.x, PC3.x
0: Disable1: Enable
47002 GC / Gov-ernor
GK1 (60Hz) Read/Write
Multiplier:1
Unit: The governor 60Hz K1gain adjust. MODBUSAccess: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
47003 GC / Gov-ernor
GK2 (60Hz) Read/Write
Multiplier:1
Unit: The governor 60Hz inte-gral gain adjust. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
47004 GC / Gov-ernor
GK3 (60Hz) Read/Write
Multiplier:1
Unit: The governor 60Hz K3gain adjust. MODBUSAccess: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 32768
Sign: U
47005 GC / Gov-ernor
GovernorDamping Ef-fect (60Hz)
Read/Write
Multiplier:1.52587890625E−05
Unit: The governor 60Hzdamping adjust. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0.6Size (bits):16
Upper Limit: 0.95
Sign: U
47006 GC / Gov-ernor
GK1 (50Hz) Read/Write
Multiplier:1
Unit: The governor 50Hz K1gain adjust. MODBUSAccess: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
293
Addr. ControlDescriptionAccessParameterName47007 GC / Gov-
ernorGK2 (50Hz) Read/
WriteMultiplier:1
Unit: The governor 50Hz inte-gral gain adjust. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U47008 GC / Gov-
ernorGK3 (50Hz) Read/
WriteMultiplier:1
Unit: The governor 50Hz K3gain adjust. MODBUSAccess: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 32768
Sign: U47009 GC / Gov-
ernorGovernorDamping Ef-fect (50Hz)
Read/Write
Multiplier:1.52587890625E−05
Unit: The governor 50Hzdamping adjust. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0.6Size (bits):16
Upper Limit: 0.95
Sign: U47010 GC / Gov-
ernorGK1 (Idle) Read/
WriteMultiplier:1
Unit: This trim is used to adjustgk1 in idle mode. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U47011 GC / Gov-
ernorGK2 (Idle) Read/
WriteMultiplier:1
Unit: This trim is used to adjustgk2 in idle mode. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U47012 GC / Gov-
ernorGK3 (Idle) Read/
WriteMultiplier:1
Unit: This trim is used to adjustgk3 in idle mode. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 32768
Sign: U
294
Addr. ControlDescriptionAccessParameterName47013 GC / Gov-
ernorGov DampingEffect (Idle)
Read/Write
Multiplier:1.52587890625E−05
Unit: The governor dampingadjust for idle rating.MODBUS Access: ReadOnly
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0.6Size (bits):16
Upper Limit: 0.95
Sign: U
47014 GC / Gov-ernor
Gain Window-ing Enable
Read/Write
Either enables or disables Gain Windowing feature.MODBUS Access: Read Only
PC 2.x, PC3.x
0: Disable1: Enable
47015 GC / Gov-ernor
GK1 Low(50Hz)
Read/Write
Multiplier:1
Unit: The governor 50Hz K1low gain adjust. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
47016 GC / Gov-ernor
GK1 Low(60Hz)
Read/Write
Multiplier:1
Unit: The governor 60Hz K1low gain adjust. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
47017 GC / Gov-ernor
GK1 High(50Hz)
Read/Write
Multiplier:1
Unit: The governor 50Hz K1high gain adjust. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
47018 GC / Gov-ernor
GK1 High(60Hz)
Read/Write
Multiplier:1
Unit: The governor 60Hz K1high gain adjust. MOD-BUS Access: Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 65535
Sign: U
47019 GC / Gov-ernor
GovernorSpeed DeltaHigh
Read/Write
Multiplier:1
Unit: The speed error higherlimit. MODBUS Access:Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 50Size (bits):16
Upper Limit: 1000
Sign: U
295
Addr. ControlDescriptionAccessParameterName47020 GC / Gov-
ernorGovernorSpeed DeltaLow
Read/Write
Multiplier:1
Unit: The speed error lowerlimit. MODBUS Access:Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 50Size (bits):16
Upper Limit: 1000
Sign: U47021 ASI / Ana-
log Inputs/Outputs
Intake Man-ifold Tempera-ture SenderType
Read/Write
Either Onan or Cummins sensor. MODBUS Access:Read Only
PC 2.x, PC3.x
0: PGBU1: EBU
47022 ASI / Ana-log Inputs/Outputs
Intake Man-ifold Tempera-ture SensorEnable
Read/Write
Intake Manifold Temp Sensor available or not. MOD-BUS Access: Read Only
PC 2.x, PC3.x
0: Disable1: Enable
47023 ASI / Ana-log Inputs/Outputs
Oil Tempera-ture SenderType
Read/Write
Either Onan or Cummins sensor. PC 2.x, PC3.x0: PGBU
1: EBU47024 ASI / Ana-
log Inputs/Outputs
Oil Tempera-ture SensorEnable
Read/Write
High Oil Temperature Sensor available or not. PC 2.x, PC3.x0: Disable
1: Enable47025 GC / Auto-
matic Volt-age Regu-lator
AVR PWMCommand
ReadOnly
Multiplier:0.01
Unit: % The AVR PWM softwarecommand. Linear rela-tionship between countsand % duty cycle with10000 counts=100% dutycycle. MODBUS Access:Read Only
PC 2.x, PC3.x
Offset: 0 Lower Limit: 0Size (bits):16
Upper Limit: 100
Sign: U
296
THIS PAGE LEFT INTENTIONALLY BLANK
297
3. PowerCommand 2.x/3.x Modbus Fault Status BitmapsNote: If an address or bit is not listed in this table it is not used.
Addr. Bit # Name FaultCode
Event Name Response Control
40400 0 Fault Status Bit-map 1
115 Engine Magnetic Crankshaft Speed/Position
Shutdown PC 2.x, PC3.x
40400 1 Fault Status Bit-map 1
122 Intake Manifold 1 Pressure: Vtg AboveNormal
Warning PC 2.x, PC3.x
40400 2 Fault Status Bit-map 1
123 Intake Manifold 1 Pressure: Vtg BelowNormal
Warning PC 2.x, PC3.x
40400 3 Fault Status Bit-map 1
124 Intake Manifold 1 Pressure: Moderate-ly Severe
Warning PC 2.x, PC3.x
40400 4 Fault Status Bit-map 1
135 Engine Oil Rifle Pressure 1: Vtg AboveNormal
Warning PC 2.x, PC3.x
40400 5 Fault Status Bit-map 1
141 Engine Oil Rifle Pressure 1: Vtg BelowNormal
Warning PC 2.x, PC3.x
40400 6 Fault Status Bit-map 1
143 Engine Oil Rifle Pressure −ModeratelySevere
Warning PC 2.x, PC3.x
40400 7 Fault Status Bit-map 1
144 Engine Coolant Temp 1: Vtg AboveNormal
Warning PC 2.x, PC3.x
40400 8 Fault Status Bit-map 1
145 Engine Coolant Temp 1: Vtg BelowNormal
Warning PC 2.x, PC3.x
40400 9 Fault Status Bit-map 1
146 Engine Coolant Temp: ModeratelyAbove Normal
Derate PC 2.x, PC3.x
40400 10 Fault Status Bit-map 1
151 Engine Coolant Temp: Severely AboveNormal
Shutdown PC 2.x, PC3.x
40400 11 Fault Status Bit-map 1
153 Intake Manifold 1 Temp: Vtg AboveNormal
Warning PC 2.x, PC3.x
40400 12 Fault Status Bit-map 1
154 Intake Manifold 1 Temp: Vtg BelowNormal
Warning PC 2.x, PC3.x
40400 13 Fault Status Bit-map 1
155 Intake Manifold 1 Temp: SeverelyAbove Normal
Shutdown PC 2.x, PC3.x
40400 14 Fault Status Bit-map 1
187 Sensor Supply 2: Vtg Below Normal Warning PC 2.x, PC3.x
40400 15 Fault Status Bit-map 1
195 Coolant Level Sensor 1: Vtg AboveNormal
Warning PC 2.x, PC3.x
40401 0 Fault Status Bit-map 2
196 Coolant Level Sensor 1: Vtg BelowNormal
Warning PC 2.x, PC3.x
40401 1 Fault Status Bit-map 2
197 Coolant Level: Below Normal − Moder-ately Severe
Warning PC 2.x, PC3.x
40401 2 Fault Status Bit-map 2
212 Engine Oil Temp Sensor 1: Vtg AboveNormal
Warning PC 2.x, PC3.x
40401 3 Fault Status Bit-map 2
213 Engine Oil Temp Sensor 1: Vtg belowNormal
Warning PC 2.x, PC3.x
40401 4 Fault Status Bit-map 2
214 Engine Oil Temp: Above Normal −Most severe
Shutdown PC 2.x, PC3.x
40401 5 Fault Status Bit-map 2
221 Barometric Pressure: Vtg Above Nor-mal
Warning PC 2.x, PC3.x
40401 6 Fault Status Bit-map 2
222 Barometric Pressure Sensor: Vtg Be-low Normal
Warning PC 2.x, PC3.x
40401 7 Fault Status Bit-map 2
223 Eng Oil Burn Valve Solenoid: Vtg Be-low Normal
Warning PC 2.x, PC3.x
298
Addr. ControlResponseEvent NameFaultCode
NameBit #
40401 8 Fault Status Bit-map 2
224 Engine Oil Burn Valve Solenoid: VtgAbove Normal
Warning PC 2.x, PC3.x
40401 9 Fault Status Bit-map 2
227 Sensor Supply 2: Vtg Above Normal Warning PC 2.x, PC3.x
40401 10 Fault Status Bit-map 2
228 Coolant Pressure: Below Normal−Most Severe
Shutdown PC 2.x, PC3.x
40401 11 Fault Status Bit-map 2
231 Coolant Pressure Sensor: Vtg AboveNormal
Warning PC 2.x, PC3.x
40401 12 Fault Status Bit-map 2
232 Coolant Pressure Sensor: Vtg BelowNormal
Warning PC 2.x, PC3.x
40401 13 Fault Status Bit-map 2
234 Engine Crankshaft Speed/Posn:Above Normal
Shutdown PC 2.x, PC3.x
40401 14 Fault Status Bit-map 2
235 Coolant Level: Below Normal−MostSevere
Shutdown PC 2.x, PC3.x
40401 15 Fault Status Bit-map 2
238 Sensor Supply 3: Vtg Below Normal Warning PC 2.x, PC3.x
40402 0 Fault Status Bit-map 3
239 Voltage Supply C High Error Warning PC 2.x, PC3.x
40402 1 Fault Status Bit-map 3
245 Radiator Fan Control Driver Low Error Warning PC 2.x, PC3.x
40402 2 Fault Status Bit-map 3
261 Engine Fuel Temp: Above Normal−Moderately Severe
Warning PC 2.x, PC3.x
40402 3 Fault Status Bit-map 3
263 Engine Fuel Temp Sensor 1: VtgAbove Normal
Warning PC 2.x, PC3.x
40402 4 Fault Status Bit-map 3
265 Engine Fuel Temp Sensor 1: Vtg Be-low Normal
Warning PC 2.x, PC3.x
40402 5 Fault Status Bit-map 3
266 Engine Fuel Temp: Above Normal−Most severe
Shutdown PC 2.x, PC3.x
40402 6 Fault Status Bit-map 3
271 Fuel Pump Pressurizing Assembly 1:Vtg Below Normal
Warning PC 2.x, PC3.x
40402 7 Fault Status Bit-map 3
272 Fuel Pump Pressurizing Assembly 1:Vtg Above Normal
Warning PC 2.x, PC3.x
40402 8 Fault Status Bit-map 3
281 APC_DIESEL_CYL_PRS_IMBAL_ER-ROR
Warning PC 2.x, PC3.x
40402 9 Fault Status Bit-map 3
285 SAE J1939 Muxing PGN Timeout: Ab-normal Update Rate
Warning PC 2.x, PC3.x
40402 10 Fault Status Bit-map 3
286 SAE J1939 Muxing Config: Out of Cal-ibration
Warning PC 2.x, PC3.x
40402 13 Fault Status Bit-map 3
295 AMBIENT_AIR_PRESS_KEYON_ER-ROR
Warning PC 2.x, PC3.x
40402 14 Fault Status Bit-map 3
319 RTC PWR Intr: Data Erratic Intermit-tent or Wrong
Warning PC 2.x, PC3.x
40402 15 Fault Status Bit-map 3
322 Injector Solenoid Driver Cylinder 1:UnderCurrent
Warning PC 2.x, PC3.x
40403 0 Fault Status Bit-map 4
323 Injector Solenoid Driver Cylinder 5:UnderCurrent
Warning PC 2.x, PC3.x
40403 1 Fault Status Bit-map 4
324 Injector Solenoid Driver Cylinder 3:UnderCurrent
Warning PC 2.x, PC3.x
40403 2 Fault Status Bit-map 4
325 Injector Solenoid Driver Cylinder 6:UnderCurrent
Warning PC 2.x, PC3.x
299
Addr. ControlResponseEvent NameFaultCode
NameBit #
40403 3 Fault Status Bit-map 4
331 Injector Solenoid Driver Cylinder 2:UnderCurrent
Warning PC 2.x, PC3.x
40403 4 Fault Status Bit-map 4
332 Injector Solenoid Driver Cylinder 4:UnderCurrent
Warning PC 2.x, PC3.x
40403 6 Fault Status Bit-map 4
342 Electronic Calibration Code: Out ofCalibration
Shutdown PC 2.x, PC3.x
40403 7 Fault Status Bit-map 4
343 Eng Ctrl: internal h/w failure−Bad De-vice/Component
Warning PC 2.x, PC3.x
40403 8 Fault Status Bit-map 4
351 Injector Power Supply: Bad Device/Component
Warning PC 2.x, PC3.x
40403 9 Fault Status Bit-map 4
352 Sensor Supply 1: Vtg Below Normal Warning PC 2.x, PC3.x
40403 10 Fault Status Bit-map 4
359 Fail To Start Fault Shutdown PC 2.x, PC3.x
40403 11 Fault Status Bit-map 4
386 Sensor Supply 1: Vtg Above Normal Warning PC 2.x, PC3.x
40403 12 Fault Status Bit-map 4
415 Eng Oil Rifle Pressure: Below Normal−Most Severe
Shutdown PC 2.x, PC3.x
40403 13 Fault Status Bit-map 4
418 Water in Fuel Indicator: Above Nor-mal−Least Severe
Warning PC 2.x, PC3.x
40403 14 Fault Status Bit-map 4
421 Eng Oil Temp: Above Normal−Moder-ately Severe
Warning PC 2.x, PC3.x
40403 15 Fault Status Bit-map 4
422 COOLANT_LEVEL_READING_IN-CORRECT
Warning PC 2.x, PC3.x
40404 0 Fault Status Bit-map 5
425 OIL_TEMPERA-TURE_IN_RANGE_ERROR
Warning PC 2.x, PC3.x
40404 1 Fault Status Bit-map 5
426 J1939 Datalink: Data Erratic/Intermit-tent/Wrong
NONE PC 2.x, PC3.x
40404 2 Fault Status Bit-map 5
427 CAN Datalink Degraded Warning PC 2.x, PC3.x
40404 3 Fault Status Bit-map 5
435 OIL_PRESSURE_SWITCH_ERROR Warning PC 2.x, PC3.x
40404 4 Fault Status Bit-map 5
441 Low Battery Voltage Warning PC 2.x, PC3.x
40404 5 Fault Status Bit-map 5
442 High Battery Voltage Warning PC 2.x, PC3.x
40404 6 Fault Status Bit-map 5
449 Injector Metering Rail 1 Pressure:Above Normal
Shutdown PC 2.x, PC3.x
40404 7 Fault Status Bit-map 5
451 Injector Metering Rail 1 Pressure: VtgAbove Normal
Warning PC 2.x, PC3.x
40404 8 Fault Status Bit-map 5
452 Injector Metering Rail 1 Pressure: VtgBelow Normal
Warning PC 2.x, PC3.x
40404 9 Fault Status Bit-map 5
488 Intake Manifold 1 Temp: Above Nor-mal−Moderate
Derate PC 2.x, PC3.x
40404 10 Fault Status Bit-map 5
546 Fuel Delivery Pressure: Vtg AboveNormal
Warning PC 2.x, PC3.x
40404 11 Fault Status Bit-map 5
547 Fuel Delivery Pressure: Vtg BelowNormal
Warning PC 2.x, PC3.x
40404 12 Fault Status Bit-map 5
553 APC_DIESEL_HIGH_PRS_ERROR Warning PC 2.x, PC3.x
300
Addr. ControlResponseEvent NameFaultCode
NameBit #
40404 13 Fault Status Bit-map 5
554 APC_DIESEL_PRS_SIR_ERROR Warning PC 2.x, PC3.x
40404 14 Fault Status Bit-map 5
556 Crankcase Pressure: Above Normal−Most Severe
Shutdown PC 2.x, PC3.x
40404 15 Fault Status Bit-map 5
559 Injector Metering Rail 1 Pressure: Be-low Normal
Warning PC 2.x, PC3.x
40405 1 Fault Status Bit-map 6
611 Engine Shut Down Hot Condition Ex-ists
Warning PC 2.x, PC3.x
40405 3 Fault Status Bit-map 6
689 Eng Crankshaft Speed/Pos Warning Warning PC 2.x, PC3.x
40405 4 Fault Status Bit-map 6
731 Eng Speed: Cam/Crankshaft Misalign-ment
Warning PC 2.x, PC3.x
40405 7 Fault Status Bit-map 6
1117 Power Lost With Ignition On Warning PC 2.x, PC3.x
40405 8 Fault Status Bit-map 6
1122 Rated to Idle Transition NONE PC 2.x, PC3.x
40405 9 Fault Status Bit-map 6
1124 Delayed Shutdown Fault Warning PC 2.x, PC3.x
40405 10 Fault Status Bit-map 6
1131 Battle Short Mode Active Warning PC 2.x, PC3.x
40405 11 Fault Status Bit-map 6
1132 Controlled Shutdown In Process Warning PC 3.x
40405 13 Fault Status Bit-map 6
1243 Engine Derate Derate PC 2.x, PC3.x
40405 14 Fault Status Bit-map 6
1244 Engine Normal Shutdown Shutdownw/Cool-down
PC 2.x, PC3.x
40405 15 Fault Status Bit-map 6
1245 Engine Shutdown Shutdown PC 2.x, PC3.x
40406 0 Fault Status Bit-map 7
1246 Unrecognized Engine Fault Warning PC 2.x, PC3.x
40406 1 Fault Status Bit-map 7
1247 Engine Shutdown _ Unannounced Shutdown PC 2.x, PC3.x
40406 2 Fault Status Bit-map 7
1248 Engine Warning Warning PC 3.x
40406 3 Fault Status Bit-map 7
1256 Ctrl Module ID Input State Warning Er-ror
Warning PC 2.x, PC3.x
40406 4 Fault Status Bit-map 7
1257 Ctrl Module ID I/P State shutdown Er-ror
Shutdown PC 2.x, PC3.x
40406 5 Fault Status Bit-map 7
1322 kW Load Setpoint OOR High Warning PC 3.x
40406 6 Fault Status Bit-map 7
1323 kW Load Setpoint OOR Low Warning PC 3.x
40406 7 Fault Status Bit-map 7
1324 kVAR Load Setpoint OOR High Warning PC 3.x
40406 8 Fault Status Bit-map 7
1325 kVAR Load Setpoint OOR Low Warning PC 3.x
40406 9 Fault Status Bit-map 7
1336 Cooldown Completed Fault Shutdown PC 2.x, PC3.x
301
Addr. ControlResponseEvent NameFaultCode
NameBit #
40406 10 Fault Status Bit-map 7
1357 Eng Oil Lvl Remote Reservoir: BelowNormal
Warning PC 2.x, PC3.x
40407 0 Fault Status Bit-map 8
1376 Eng Camshaft Speed/Pos Warning Warning PC 2.x, PC3.x
40407 1 Fault Status Bit-map 8
3611 Custom Overcurrent Fault Warning PC 3.x
40407 2 Fault Status Bit-map 8
3513 Negative Sequence Overcurrent Warning PC 3.x
40407 3 Fault Status Bit-map 8
1416 Fail to Shutdown Warning PC 2.x, PC3.x
40407 4 Fault Status Bit-map 8
1417 Power Down Failure Warning PC 2.x, PC3.x
40407 5 Fault Status Bit-map 8
1433 Local E−Stop Shutdown PC 2.x, PC3.x
40407 6 Fault Status Bit-map 8
1434 Remote E−Stop Shutdown PC 2.x, PC3.x
40407 7 Fault Status Bit-map 8
1435 Low Coolant Temperature Warning PC 2.x, PC3.x
40407 8 Fault Status Bit-map 8
1438 Fail To Crank Fault Shutdown PC 2.x, PC3.x
40407 9 Fault Status Bit-map 8
1439 Low Fuel in Day Tank Warning PC 2.x, PC3.x
40407 10 Fault Status Bit-map 8
1441 Low Fuel Level Warning PC 2.x, PC3.x
40407 11 Fault Status Bit-map 8
1442 Weak Battery Warning PC 2.x, PC3.x
40407 12 Fault Status Bit-map 8
1443 Dead Battery Shutdown PC 2.x, PC3.x
40407 13 Fault Status Bit-map 8
1444 Overload Warning PC 2.x, PC3.x
40407 14 Fault Status Bit-map 8
1445 Short Circuit Shutdown PC 2.x, PC3.x
40407 15 Fault Status Bit-map 8
1446 High AC Voltage Shutdown PC 2.x, PC3.x
40408 0 Fault Status Bit-map 9
1447 Low AC Voltage Shutdown PC 2.x, PC3.x
40408 1 Fault Status Bit-map 9
1448 Underfrequency Shutdown PC 2.x, PC3.x
40408 2 Fault Status Bit-map 9
1449 Overfrequency Warning PC 2.x, PC3.x
40408 3 Fault Status Bit-map 9
1459 Reverse kW Shutdown PC 2.x, PC3.x
40408 4 Fault Status Bit-map 9
1461 Loss of Field Shutdown PC 2.x, PC3.x
40408 5 Fault Status Bit-map 9
1463 Not In Auto NONE PC 2.x, PC3.x
40408 6 Fault Status Bit-map 9
1464 Load Dump Warning PC 2.x, PC3.x
40408 7 Fault Status Bit-map 9
1465 Ready To Load NONE PC 2.x, PC3.x
302
Addr. ControlResponseEvent NameFaultCode
NameBit #
40408 8 Fault Status Bit-map 9
1469 Speed/Frequency Mismatch Fault Warning PC 2.x, PC3.x
40408 9 Fault Status Bit-map 9
1471 High Current Warning Warning PC 2.x, PC3.x
40408 10 Fault Status Bit-map 9
1472 Overcurrent Shutdown Shutdown PC 2.x, PC3.x
40408 11 Fault Status Bit-map 9
1483 Common Alarm None PC 2.x, PC3.x
40408 12 Fault Status Bit-map 9
1548 Injector Solenoid Driver Cylinder 7:UnderCurrent
Warning PC 2.x, PC3.x
40408 13 Fault Status Bit-map 9
1549 Injector Solenoid Driver Cylinder 8:UnderCurrent
Warning PC 2.x, PC3.x
40408 14 Fault Status Bit-map 9
1551 Injector Solenoid Driver Cylinder 10:UnderCurrent
Warning PC 2.x, PC3.x
40408 15 Fault Status Bit-map 9
1552 Injector Solenoid Driver Cylinder 11:UnderCurrent
Warning PC 2.x, PC3.x
40409 0 Fault Status Bit-map 10
1553 Injector Solenoid Driver Cylinder 12:UnderCurrent
Warning PC 2.x, PC3.x
40409 1 Fault Status Bit-map 10
1554 Injector Solenoid Driver Cylinder 13:UnderCurrent
Warning PC 2.x, PC3.x
40409 2 Fault Status Bit-map 10
1555 Injector Solenoid Driver Cylinder 14:UnderCurrent
Warning PC 2.x, PC3.x
40409 3 Fault Status Bit-map 10
1556 Injector Solenoid Driver Cylinder 15:UnderCurrent
Warning PC 2.x, PC3.x
40409 4 Fault Status Bit-map 10
1557 Injector Solenoid Driver Cylinder 16:UnderCurrent
Warning PC 2.x, PC3.x
40409 7 Fault Status Bit-map 10
1622 Injector Solenoid Driver Cylinder 9:UnderCurrent
Warning PC 2.x, PC3.x
40409 8 Fault Status Bit-map 10
1689 Real Time Clock Power Interrupt Fault Warning PC 2.x, PC3.x
40409 9 Fault Status Bit-map 10
1695 SENSOR_SUPPLY_5_VOLT-AGE_HIGH_ERROR
Warning PC 2.x, PC3.x
40409 10 Fault Status Bit-map 10
1696 SENSOR_SUPPLY_5_VOLT-AGE_LOW_ERROR
Warning PC 2.x, PC3.x
40409 11 Fault Status Bit-map 10
1843 Crankcase Pressure: Vtg Above Nor-mal
Warning PC 2.x, PC3.x
40409 12 Fault Status Bit-map 10
1844 Crankcase Pressure: Vtg Below Nor-mal
Warning PC 2.x, PC3.x
40409 13 Fault Status Bit-map 10
1845 Water in Fuel Indicator: Vtg AboveNormal
Warning PC 2.x, PC3.x
40409 14 Fault Status Bit-map 10
1846 Water in Fuel Indicator: Vtg BelowNormal
Warning PC 2.x, PC3.x
40409 15 Fault Status Bit-map 10
1847 Eng Coolant Temp − Shutdown w/Cool Shutdownw/Cool-down
PC 2.x, PC3.x
40410 0 Fault Status Bit-map 11
1852 Water in Fuel Indicator: Above Nor-mal−Moderate
Warning PC 2.x, PC3.x
40410 1 Fault Status Bit-map 11
1853 HMI113 Fault 1 NONE PC 2.x, PC3.x
303
Addr. ControlResponseEvent NameFaultCode
NameBit #
40410 2 Fault Status Bit-map 11
1854 HMI113 Fault 2 NONE PC 2.x, PC3.x
40410 3 Fault Status Bit-map 11
1855 HMI113 Fault 3 NONE PC 2.x, PC3.x
40410 5 Fault Status Bit-map 11
1891 Eng Oil Change Interval Warning PC 2.x, PC3.x
40410 6 Fault Status Bit-map 11
1893 J39_EGR_VALVE_COMM_TIME-OUT_ERROR
Warning PC 2.x, PC3.x
40410 7 Fault Status Bit-map 11
1894 J39_VGT_COMM_TIMEOUT_ERROR Warning PC 2.x, PC3.x
40410 8 Fault Status Bit-map 11
1896 EGR_DL_VALVE_STUCK_ERROR Warning PC 2.x, PC3.x
40410 9 Fault Status Bit-map 11
1899 EGR_DELTA_P_IR_LOW_ERROR Warning PC 2.x, PC3.x
40410 11 Fault Status Bit-map 11
1912 Utility Loss Of Phase Warning PC 3.x
40410 12 Fault Status Bit-map 11
1913 Genset Loss Of Phase Warning PC 3.x
40410 13 Fault Status Bit-map 11
1914 Utility Phase Rotation Warning PC 3.x
40410 14 Fault Status Bit-map 11
1915 Genset Phase Rotation Warning PC 3.x
40410 15 Fault Status Bit-map 11
1916 Sync Check OK NONE PC 3.x
40411 0 Fault Status Bit-map 12
1917 High Fuel Level Warning PC 2.x, PC3.x
40411 1 Fault Status Bit-map 12
1918 Very Low Fuel Level Shutdown PC 2.x, PC3.x
40411 2 Fault Status Bit-map 12
1933 EGR_DL_VOLTAGE_HIGH_ERROR Warning PC 2.x, PC3.x
40411 3 Fault Status Bit-map 12
1934 EGR_DL_VOLTAGE_LOW_ERROR Warning PC 2.x, PC3.x
40411 4 Fault Status Bit-map 12
1935 EGR_DL_COMMAND_SOURCE_ER-ROR
Warning PC 2.x, PC3.x
40411 5 Fault Status Bit-map 12
1942 BEYOND_THD_AZ_ERROR Warning PC 2.x, PC3.x
40411 6 Fault Status Bit-map 12
1943 CBR_DENSITY_DERATE_ER-ROR_ID
NONE PC 2.x, PC3.x
40411 7 Fault Status Bit-map 12
1944 HMI113 Output Configuration Fault Warning PC 2.x, PC3.x
40411 8 Fault Status Bit-map 12
1961 EGR_DL_EDU_TMPTR_HIGH_ER-ROR
Warning PC 2.x, PC3.x
40411 9 Fault Status Bit-map 12
1974 CRANKCASE_PRES-SURE_LEAST_SEV_HIGH
Warning PC 2.x, PC3.x
40411 10 Fault Status Bit-map 12
1992 Eng Crankshaft Speed/Posn: AboveNormal
Shutdown PC 2.x, PC3.x
40411 11 Fault Status Bit-map 12
1999 Maximum Parallel Time Warning PC 3.x
40411 12 Fault Status Bit-map 12
2185 Sensor Supply 4: Vtg Above Normal Warning PC 2.x, PC3.x
304
Addr. ControlResponseEvent NameFaultCode
NameBit #
40411 13 Fault Status Bit-map 12
2186 Sensor Supply 4: Vtg Below Normal Warning PC 2.x, PC3.x
40411 14 Fault Status Bit-map 12
2215 Fuel Pump Delivery Pressure: BelowNormal
Warning PC 2.x, PC3.x
40411 15 Fault Status Bit-map 12
2249 APC_DIESEL_LOW2_PRS_ERROR Warning PC 2.x, PC3.x
40412 0 Fault Status Bit-map 13
2261 Fuel Pump Delivery Pressure: AboveNormal
Warning PC 2.x, PC3.x
40412 1 Fault Status Bit-map 13
2262 Fuel Pump Delivery−Below Normal Warning PC 2.x, PC3.x
40412 2 Fault Status Bit-map 13
2265 Electric Lift Pump for Eng Fuel: VtgAbove Normal
Warning PC 2.x, PC3.x
40412 3 Fault Status Bit-map 13
2266 Electric Lift Pump for Eng Fuel: VtgBelow Normal
Warning PC 2.x, PC3.x
40412 4 Fault Status Bit-map 13
2292 APC_DIESEL_FLOW_HIGH_ERROR Warning PC 2.x, PC3.x
40412 5 Fault Status Bit-map 13
2293 APC_DIESEL_FLOW_LOW_ERROR Warning PC 2.x, PC3.x
40412 6 Fault Status Bit-map 13
2311 Electronic Fuel Injection Control Valve Warning PC 2.x, PC3.x
40412 7 Fault Status Bit-map 13
2328 Utility Available NONE PC 3.x
40412 8 Fault Status Bit-map 13
2331 Utility Undervoltage Warning PC 3.x
40412 9 Fault Status Bit-map 13
2332 Utility Connected NONE PC 3.x
40412 10 Fault Status Bit-map 13
2333 Genset Connected NONE PC 3.x
40412 11 Fault Status Bit-map 13
2335 Excitation/Loss of AC Voltage Sensing Shutdown PC 2.x, PC3.x
40412 12 Fault Status Bit-map 13
2336 Checksum Fault Shutdown PC 2.x, PC3.x
40412 13 Fault Status Bit-map 13
2342 Too Long in Idle Warning PC 2.x, PC3.x
40412 14 Fault Status Bit-map 13
2358 Utility Overvoltage Warning PC 3.x
40412 15 Fault Status Bit-map 13
2377 Fan Control: Vtg Above Normal Warning PC 2.x, PC3.x
40413 0 Fault Status Bit-map 14
2396 Utility Breaker Fail To Close Warning PC 3.x
40413 1 Fault Status Bit-map 14
2397 Utility Breaker Fail To Open Warning PC 3.x
40413 2 Fault Status Bit-map 14
3226 Base Load NONE PC 3.x
40413 3 Fault Status Bit-map 14
3227 Peak Shave NONE PC 3.x
40413 4 Fault Status Bit-map 14
2555 GHC_LOW_VOLTAGE_ERROR_1 Warning PC 2.x, PC3.x
40413 5 Fault Status Bit-map 14
2556 GHC_HIGH_VOLTAGE_ERROR_1 Warning PC 2.x, PC3.x
305
Addr. ControlResponseEvent NameFaultCode
NameBit #
40413 6 Fault Status Bit-map 14
2678 Charging Alternator Failure Fault Warning PC 2.x, PC3.x
40413 7 Fault Status Bit-map 14
2965 Genset Available NONE PC 3.x
40413 8 Fault Status Bit-map 14
2971 Test/Exercise is Active Fault NONE PC 2.x, PC3.x
40413 9 Fault Status Bit-map 14
2972 Field Overload Shutdown PC 2.x, PC3.x
40413 10 Fault Status Bit-map 14
2973 CHARGE_PRESS_IR_ERROR Warning PC 2.x, PC3.x
40413 11 Fault Status Bit-map 14
2943 Manual Switch Configuration Fault Warning PC 2.x, PC3.x
40413 12 Fault Status Bit-map 14
2944 Auto Switch Configuration Fault Warning PC 2.x, PC3.x
40413 13 Fault Status Bit-map 14
2914 Genset AC Meter Failed Shutdown PC 2.x, PC3.x
40413 14 Fault Status Bit-map 14
2915 Genset Bus AC Meter Failed Warning PC 3.x
40413 15 Fault Status Bit-map 14
2916 Utility AC Meter Failed Warning PC 3.x
40414 0 Fault Status Bit-map 15
2814 Genset CT Ratio Too Small Shutdown PC 2.x, PC3.x
40414 1 Fault Status Bit-map 15
2815 Genset CT Ratio Too Large Warning PC 2.x, PC3.x
40414 2 Fault Status Bit-map 15
2816 Genset PT Ratio Too Small Shutdown PC 2.x, PC3.x
40414 3 Fault Status Bit-map 15
2817 Genset PT Ratio Too Large Warning PC 2.x, PC3.x
40414 4 Fault Status Bit-map 15
2818 Genset Bus PT Ratio Too Small Shutdown PC 3.x
40414 5 Fault Status Bit-map 15
2819 Genset Bus PT Ratio Too Large Warning PC 3.x
40414 6 Fault Status Bit-map 15
2821 Utility PT Ratio Too Small Shutdown PC 3.x
40414 7 Fault Status Bit-map 15
2822 Utility PT Ratio Too Large Warning PC 3.x
40414 8 Fault Status Bit-map 15
2619 Aux101 0 Input 1 Fault Warning PC 2.x, PC3.x
40414 9 Fault Status Bit-map 15
2621 Aux101 0 Input 2 Fault Warning PC 2.x, PC3.x
40414 10 Fault Status Bit-map 15
2622 Aux101 0 Input 3 Fault Warning PC 2.x, PC3.x
40414 11 Fault Status Bit-map 15
2623 Aux101 0 Input 4 Fault Warning PC 2.x, PC3.x
40414 12 Fault Status Bit-map 15
2624 Aux101 0 Input 5 Fault Warning PC 2.x, PC3.x
40414 13 Fault Status Bit-map 15
2625 Aux101 0 Input 6 Fault Warning PC 2.x, PC3.x
40414 14 Fault Status Bit-map 15
2626 Aux101 0 Input 7 Fault Warning PC 2.x, PC3.x
306
Addr. ControlResponseEvent NameFaultCode
NameBit #
40414 15 Fault Status Bit-map 15
2627 Aux101 0 Input 8 Fault Warning PC 2.x, PC3.x
40415 0 Fault Status Bit-map 16
2882 Aux101 1 Input 1 Fault Warning PC 2.x, PC3.x
40415 1 Fault Status Bit-map 16
2883 Aux101 1 Input 2 Fault Warning PC 2.x, PC3.x
40415 2 Fault Status Bit-map 16
2884 Aux101 1 Input 3 Fault Warning PC 2.x, PC3.x
40415 3 Fault Status Bit-map 16
2885 Aux101 1 Input 4 Fault Warning PC 2.x, PC3.x
40415 4 Fault Status Bit-map 16
2886 Aux101 1 Input 5 Fault Warning PC 2.x, PC3.x
40415 5 Fault Status Bit-map 16
2887 Aux101 1 Input 6 Fault Warning PC 2.x, PC3.x
40415 6 Fault Status Bit-map 16
2888 Aux101 1 Input 7 Fault Warning PC 2.x, PC3.x
40415 7 Fault Status Bit-map 16
2889 Aux101 1 Input 8 Fault Warning PC 2.x, PC3.x
40415 8 Fault Status Bit-map 16
2628 Aux102 0 Expansion Input 9 Fault Warning PC 2.x, PC3.x
40415 9 Fault Status Bit-map 16
2629 Aux102 0 Expansion Input 10 Fault Warning PC 2.x, PC3.x
40415 10 Fault Status Bit-map 16
2631 Aux102 0 Expansion Input 11 Fault Warning PC 2.x, PC3.x
40415 11 Fault Status Bit-map 16
2632 Aux102 0 Expansion Input 12 Fault Warning PC 2.x, PC3.x
40415 12 Fault Status Bit-map 16
2891 Aux102 1 Expansion Input 9 Fault Warning PC 2.x, PC3.x
40415 13 Fault Status Bit-map 16
2892 Aux102 1 Expansion Input 10 Fault Warning PC 2.x, PC3.x
40415 14 Fault Status Bit-map 16
2893 Aux102 1 Expansion Input 11 Fault Warning PC 2.x, PC3.x
40415 15 Fault Status Bit-map 16
2894 Aux102 1 Expansion Input 12 Fault Warning PC 2.x, PC3.x
40416 0 Fault Status Bit-map 17
2895 PCCnet Device Failed Warning Warning PC 2.x, PC3.x
40416 1 Fault Status Bit-map 17
2896 PCCnet Device Failed Shutdown Shutdown PC 2.x, PC3.x
40416 2 Fault Status Bit-map 17
2917 Genset Bus Voltage OOR Warning Warning PC 3.x
40416 3 Fault Status Bit-map 17
2918 Utility Voltage OOR Warning Warning PC 3.x
40416 4 Fault Status Bit-map 17
2919 Utility Current OOR Warning Warning PC 3.x
40416 5 Fault Status Bit-map 17
2921 Genset Bus Current OOR Warning Warning PC 3.x
40416 6 Fault Status Bit-map 17
2922 Genset Neutral Current OOR Warning Warning PC 3.x
40416 7 Fault Status Bit-map 17
2923 Genset Bus kW OOR Warning Warning PC 3.x
307
Addr. ControlResponseEvent NameFaultCode
NameBit #
40416 8 Fault Status Bit-map 17
2924 Genset Bus kVAR OOR Warning Warning PC 3.x
40416 9 Fault Status Bit-map 17
2925 Genset Bus kVA OOR Warning Warning PC 3.x
40416 10 Fault Status Bit-map 17
2926 Utility kW OOR Warning Warning PC 3.x
40416 11 Fault Status Bit-map 17
2927 Utility kVAR OOR Warning Warning PC 3.x
40416 12 Fault Status Bit-map 17
2928 Utility kVA OOR Warning Warning PC 3.x
40416 13 Fault Status Bit-map 17
3599 Ground Current OOR Warning Warning PC 3.x
40416 14 Fault Status Bit-map 17
2931 AUX101 Device ID Fault Shutdown PC 2.x, PC3.x
40416 15 Fault Status Bit-map 17
2779 Utility Unloaded Event NONE PC 3.x
40417 3 Fault Status Bit-map 18
2932 AUX101 Oil Temp OOR Hi Warning PC 2.x, PC3.x
40417 4 Fault Status Bit-map 18
2933 AUX101 Oil Temp OOR Low Warning PC 2.x, PC3.x
40417 5 Fault Status Bit-map 18
2657 Exhaust Stack Temp 1 OOR High Warning PC 2.x, PC3.x
40417 6 Fault Status Bit-map 18
2947 Exhaust Stack Temp 1 OOR Low Warning PC 2.x, PC3.x
40417 7 Fault Status Bit-map 18
2949 High Exhaust Stack Temperature 1 Warning PC 2.x, PC3.x
40417 8 Fault Status Bit-map 18
2653 Exhaust Stack Temp 2 OOR High Warning PC 2.x, PC3.x
40417 9 Fault Status Bit-map 18
2946 Exhaust Stack Temp 2 OOR Low Warning PC 2.x, PC3.x
40417 10 Fault Status Bit-map 18
2948 High Exhaust Stack Temperature 2 Warning PC 2.x, PC3.x
40417 11 Fault Status Bit-map 18
2934 Ambient Temp OOR High Warning PC 2.x, PC3.x
40417 12 Fault Status Bit-map 18
2935 Ambient Temp OOR Low Warning PC 2.x, PC3.x
40417 13 Fault Status Bit-map 18
2936 Fuel Level OOR High Warning PC 2.x, PC3.x
40417 14 Fault Status Bit-map 18
2937 Fuel Level OOR Low Warning PC 2.x, PC3.x
40417 15 Fault Status Bit-map 18
2951 Alternator Temp 1 OOR High Warning PC 2.x, PC3.x
40418 0 Fault Status Bit-map 19
2952 Alternator Temp 1 OOR Low Warning PC 2.x, PC3.x
40418 1 Fault Status Bit-map 19
2953 High Alternator Temp 1 Warning PC 2.x, PC3.x
40418 2 Fault Status Bit-map 19
2954 Alternator Temp 2 OOR High Warning PC 2.x, PC3.x
40418 3 Fault Status Bit-map 19
2955 Alternator Temp 2 OOR Low Warning PC 2.x, PC3.x
308
Addr. ControlResponseEvent NameFaultCode
NameBit #
40418 4 Fault Status Bit-map 19
2956 High Alternator Temp 2 Warning PC 2.x, PC3.x
40418 5 Fault Status Bit-map 19
2957 Alternator Temp 3 OOR High Warning PC 2.x, PC3.x
40418 6 Fault Status Bit-map 19
2958 Alternator Temp 3 OOR Low Warning PC 2.x, PC3.x
40418 7 Fault Status Bit-map 19
2959 High Alternator Temp 3 Warning PC 2.x, PC3.x
40418 8 Fault Status Bit-map 19
2992 Intake Manifold Temp 1 OOR High Warning PC 2.x, PC3.x
40418 9 Fault Status Bit-map 19
2978 Intake Manifold Temp 1 OOR Low Warning PC 2.x, PC3.x
40418 10 Fault Status Bit-map 19
2981 Drive End Bearing Temp OOR High Warning PC 2.x, PC3.x
40418 11 Fault Status Bit-map 19
2982 Drive End Bearing Temp OOR Low Warning PC 2.x, PC3.x
40418 12 Fault Status Bit-map 19
2983 High Drive End Bearing Temperature Warning PC 2.x, PC3.x
40418 13 Fault Status Bit-map 19
2984 Non−Drive End Bearing Temp OORHigh
Warning PC 2.x, PC3.x
40418 14 Fault Status Bit-map 19
2985 Non−Drive End Bearing Temp OORLow
Warning PC 2.x, PC3.x
40418 15 Fault Status Bit-map 19
2986 High Non−Drive End Bearing Temper-ature
Warning PC 2.x, PC3.x
40419 0 Fault Status Bit-map 20
2945 Rupture Basin Warning PC 2.x, PC3.x
40419 1 Fault Status Bit-map 20
2979 High Alternator Temp Switch fault Warning PC 2.x, PC3.x
40419 2 Fault Status Bit-map 20
2993 Battery Charger Failed Fault Warning PC 2.x, PC3.x
40419 3 Fault Status Bit-map 20
2938 Earth/Ground Fault Warning PC 2.x, PC3.x
40419 4 Fault Status Bit-map 20
2939 Modbus Failure Fault Warning PC 2.x, PC3.x
40419 5 Fault Status Bit-map 20
2977 Low Coolant Level #2 Warning PC 2.x, PC3.x
40419 6 Fault Status Bit-map 20
1978 Speed Bias OOR High Warning PC 2.x, PC3.x
40419 7 Fault Status Bit-map 20
2541 Voltage Bias OOR Low Warning PC 2.x, PC3.x
40419 8 Fault Status Bit-map 20
2539 Voltage Bias OOR High Warning PC 2.x, PC3.x
40419 9 Fault Status Bit-map 20
1573 Configurable Input #1 NONE PC 2.x, PC3.x
40419 10 Fault Status Bit-map 20
1312 Configurable Input #2 NONE PC 2.x, PC3.x
40419 11 Fault Status Bit-map 20
1317 Configurable Input #13 NONE PC 2.x, PC3.x
40419 12 Fault Status Bit-map 20
1318 Configurable Input #14 NONE PC 2.x, PC3.x
309
Addr. ControlResponseEvent NameFaultCode
NameBit #
40419 13 Fault Status Bit-map 20
1979 Speed Bias OOR Low Warning PC 2.x, PC3.x
40419 14 Fault Status Bit-map 20
236 Both Engine Speed Signals Lost: MostSevere Level
Shutdown PC 2.x, PC3.x
40419 15 Fault Status Bit-map 20
3629 Less Severe Response−Warning Warning PC 3.x
40420 0 Fault Status Bit-map 21
3631 Most Severe−Shutdown Shutdown PC 3.x
40430 0 Event Status Bit-map 1
1540 Common Warning NONE PC 2.x, PC3.x
40430 1 Event Status Bit-map 1
1541 Common Shutdown NONE PC 2.x, PC3.x
40431 0 Fault Status GasBitmap 1
121 EPS Main Channel Lost Error Warning PC 3.x
40431 1 Fault Status GasBitmap 1
136 Oil Inlet Pressure High Error Warning PC 3.x
40431 2 Fault Status GasBitmap 1
137 Oil Inlet Pressure Low Error Warning PC 3.x
40431 3 Fault Status GasBitmap 1
142 Oil Overpressure Error Warning PC 3.x
40431 4 Fault Status GasBitmap 1
156 Intake Manifold Temp 2 OORH Warning PC 3.x
40431 5 Fault Status GasBitmap 1
157 Intake Manifold Temp 2 OORL Warning PC 3.x
40431 6 Fault Status GasBitmap 1
158 Intake Manifold Temp 2 High Shutdown PC 3.x
40431 7 Fault Status GasBitmap 1
159 Intake Manifold 3 Temp OORH Warning PC 3.x
40431 8 Fault Status GasBitmap 1
161 Intake Manifold 3 Temp OORL Warning PC 3.x
40431 9 Fault Status GasBitmap 1
162 Intake Manifold 3 Temp High Shutdown PC 3.x
40431 10 Fault Status GasBitmap 1
163 Intake Manifold 4 Temp OORH Warning PC 3.x
40431 11 Fault Status GasBitmap 1
164 Intake Manifold 4 Temp OORL Warning PC 3.x
40431 12 Fault Status GasBitmap 1
165 Intake Manifold 4 Temp High Shutdown PC 3.x
40431 13 Fault Status GasBitmap 1
175 Throttle_Driver_Feedback_High_Error Shutdownw/Cool-down
PC 3.x
40431 14 Fault Status GasBitmap 1
176 Throttle_Driver_Feedback_Low_Error Shutdownw/Cool-down
PC 3.x
40431 15 Fault Status GasBitmap 1
177 Throttle_Actuator_Error Shutdownw/Cool-down
PC 3.x
40432 0 Fault Status GasBitmap 2
219 Eng Oil Level Remote Reservoir:Least Severe Level
Warning PC 2.x, PC3.x
310
Addr. ControlResponseEvent NameFaultCode
NameBit #
40432 1 Fault Status GasBitmap 2
233 HT Coolant Pressure Moderate Low Warning PC 2.x, PC3.x
40432 2 Fault Status GasBitmap 2
244 Red Stop Lamp Driver OORL Warning PC 3.x
40432 3 Fault Status GasBitmap 2
246 Exhaust Gas Temp Sensor 1 OORH Warning PC 3.x
40432 4 Fault Status GasBitmap 2
247 Exhaust Gas Temp Sensor 1 OORL Warning PC 3.x
40432 5 Fault Status GasBitmap 2
248 Exhaust Gas Temp Sensor 1 High Warning PC 3.x
40432 6 Fault Status GasBitmap 2
253 Oil Level Low Error Shutdownw/Cool-down
PC 3.x
40432 7 Fault Status GasBitmap 2
254 FSO NON Low Control Error Shutdown PC 2.x, PC3.x
40432 8 Fault Status GasBitmap 2
277 Fuel Control Valve Out of Adj Warning PC 3.x
40432 9 Fault Status GasBitmap 2
346 Powerdown Data Lost Error Warning PC 3.x
40432 10 Fault Status GasBitmap 2
354 Manifold_Absolute_Pres-sure_1_High_Error
Warning PC 3.x
40432 11 Fault Status GasBitmap 2
355 Manifold_Absolute_Pres-sure_1_Low_Error
Warning PC 3.x
40432 12 Fault Status GasBitmap 2
412 J1708 Link Cannot Transmit Error NONE PC 3.x
40432 13 Fault Status GasBitmap 2
414 J1708 Link Not Fast Enough Error NONE PC 3.x
40432 14 Fault Status GasBitmap 2
453 Gas_Mass_Flow_High_Error Warning PC 3.x
40432 15 Fault Status GasBitmap 2
454 Gas_Mass_Flow_Low_Error Warning PC 3.x
40433 0 Fault Status GasBitmap 3
458 Spark_Timing_B_Error Shutdownw/Cool-down
PC 3.x
40433 1 Fault Status GasBitmap 3
459 Spark_Timing_A_Error Shutdownw/Cool-down
PC 3.x
40433 2 Fault Status GasBitmap 3
461 Spark_Reference_B_Error Shutdownw/Cool-down
PC 3.x
40433 3 Fault Status GasBitmap 3
462 Spark_Reference_A_Error Shutdownw/Cool-down
PC 3.x
40433 4 Fault Status GasBitmap 3
477 Isolated Battery Voltage Low Error Warning PC 3.x
40433 5 Fault Status GasBitmap 3
478 Isolated Battery Voltage High Error Warning PC 3.x
40433 6 Fault Status GasBitmap 3
512 Throttle Pos 1 Feedback OOR High Warning PC 3.x
311
Addr. ControlResponseEvent NameFaultCode
NameBit #
40433 7 Fault Status GasBitmap 3
513 Throttle Pos 1 Feedback OOR Low Warning PC 3.x
40433 8 Fault Status GasBitmap 3
557 Fuel Control Valve 2 OORH Shutdownw/Cool-down
PC 3.x
40433 9 Fault Status GasBitmap 3
558 Fuel Control Valve 2 OORL Warning PC 3.x
40433 10 Fault Status GasBitmap 3
561 Heavy_Knock_Error_1_(A1) Shutdownw/Cool-down
PC 3.x
40433 11 Fault Status GasBitmap 3
562 Heavy_Knock_Error_2_(B1) Shutdownw/Cool-down
PC 3.x
40433 12 Fault Status GasBitmap 3
563 Heavy_Knock_Error_3_(A2) Shutdownw/Cool-down
PC 3.x
40433 13 Fault Status GasBitmap 3
564 Heavy_Knock_Error_4_(B2) Shutdownw/Cool-down
PC 3.x
40433 14 Fault Status GasBitmap 3
565 Heavy_Knock_Error_5_(A3) Shutdownw/Cool-down
PC 3.x
40433 15 Fault Status GasBitmap 3
566 Heavy_Knock_Error_6_(B3) Shutdownw/Cool-down
PC 3.x
40434 0 Fault Status GasBitmap 4
567 Heavy_Knock_Error_7_(A4) Shutdownw/Cool-down
PC 3.x
40434 1 Fault Status GasBitmap 4
568 Heavy_Knock_Error_8_(B4) Shutdownw/Cool-down
PC 3.x
40434 2 Fault Status GasBitmap 4
569 Heavy_Knock_Error_9_(A5) Shutdownw/Cool-down
PC 3.x
40434 3 Fault Status GasBitmap 4
571 Knock Cyl 1 (A1) OORL Warning PC 3.x
40434 4 Fault Status GasBitmap 4
572 Knock Cyl 2 (B1) OORL Warning PC 3.x
40434 5 Fault Status GasBitmap 4
573 Knock Cyl 3 (A2) OORL Warning PC 3.x
40434 6 Fault Status GasBitmap 4
574 Knock Cyl 4 (B2) OORL Warning PC 3.x
40434 7 Fault Status GasBitmap 4
575 Knock Cyl 5 (A3) OORL Warning PC 3.x
40434 8 Fault Status GasBitmap 4
576 Knock Cyl 6 (B3) OORL Warning PC 3.x
40434 9 Fault Status GasBitmap 4
577 Knock Cyl 7 (A4) OORL Warning PC 3.x
40434 10 Fault Status GasBitmap 4
578 Knock Cyl 8 (B4) OORL Warning PC 3.x
312
Addr. ControlResponseEvent NameFaultCode
NameBit #
40434 11 Fault Status GasBitmap 4
579 Knock Cyl 9 (A5) OORL Warning PC 3.x
40434 12 Fault Status GasBitmap 4
584 High Side DRV3 High Control Error Warning PC 3.x
40434 13 Fault Status GasBitmap 4
585 High Side DRV3 Low Control Error Warning PC 3.x
40434 14 Fault Status GasBitmap 4
591 Exhaust_Backpressure_High_Error Warning PC 3.x
40434 15 Fault Status GasBitmap 4
592 Exhaust_Backpressure_Low_Error Warning PC 3.x
40435 0 Fault Status GasBitmap 5
595 Turbo 1 Overspeed Warning Error Warning PC 3.x
40435 1 Fault Status GasBitmap 5
618 Turbo 1 Inlet Pressure High Warning PC 3.x
40435 2 Fault Status GasBitmap 5
619 Turbo 2 Inlet Press High Warning PC 3.x
40435 3 Fault Status GasBitmap 5
641 Exhaust Temp 1 (A1) High Serious Er-ror
Shutdownw/Cool-down
PC 3.x
40435 4 Fault Status GasBitmap 5
642 Exhaust Temp 3 (A2) High Serious Er-ror
Shutdownw/Cool-down
PC 3.x
40435 5 Fault Status GasBitmap 5
643 Exhaust Temp 5 (A3) High Serious Er-ror
Shutdownw/Cool-down
PC 3.x
40435 6 Fault Status GasBitmap 5
644 Exhaust Temp 7 (A4) High Serious Er-ror
Shutdownw/Cool-down
PC 3.x
40435 7 Fault Status GasBitmap 5
645 Exhaust Temp 9 (A5) High Serious Er-ror
Shutdownw/Cool-down
PC 3.x
40435 8 Fault Status GasBitmap 5
646 Exhaust Temp 11 (A6) High SeriousError
Shutdownw/Cool-down
PC 3.x
40435 9 Fault Status GasBitmap 5
647 Exhaust Temp 13 (A7) High SeriousError
Shutdownw/Cool-down
PC 3.x
40435 10 Fault Status GasBitmap 5
648 Exhaust Temp 15 (A8) High SeriousError
Shutdownw/Cool-down
PC 3.x
40435 11 Fault Status GasBitmap 5
651 Exhaust Temp 17 (A9) High SeriousError
Shutdownw/Cool-down
PC 3.x
40435 12 Fault Status GasBitmap 5
652 Exhaust Temp 2 (B1) High Serious Er-ror
Shutdownw/Cool-down
PC 3.x
40435 13 Fault Status GasBitmap 5
653 Exhaust Temp 4 (B2) High Serious Er-ror
Shutdownw/Cool-down
PC 3.x
313
Addr. ControlResponseEvent NameFaultCode
NameBit #
40435 14 Fault Status GasBitmap 5
654 Exhaust Temp 6 (B3) High Serious Er-ror
Shutdownw/Cool-down
PC 3.x
40435 15 Fault Status GasBitmap 5
655 Exhaust Temp 8 (B4) High Serious Er-ror
Shutdownw/Cool-down
PC 3.x
40436 0 Fault Status GasBitmap 6
656 Exhaust Temp 10 (B5) High SeriousError
Shutdownw/Cool-down
PC 3.x
40436 1 Fault Status GasBitmap 6
657 Exhaust Temp 12 (B6) High SeriousError
Shutdownw/Cool-down
PC 3.x
40436 2 Fault Status GasBitmap 6
658 Exhaust Temp 14 (B7) High SeriousError
Shutdownw/Cool-down
PC 3.x
40436 3 Fault Status GasBitmap 6
671 Exhaust Gas Temp Cyl 1 (A1) OORL Warning PC 3.x
40436 4 Fault Status GasBitmap 6
672 Exhaust Gas Temp Cyl 3 (A2) OORL Warning PC 3.x
40436 5 Fault Status GasBitmap 6
673 Exhaust Gas Temp Cyl 5 (A3) OORL Warning PC 3.x
40436 6 Fault Status GasBitmap 6
674 Exhaust Gas Temp Cyl 7 (A4) OORL Warning PC 3.x
40436 7 Fault Status GasBitmap 6
675 Exhaust Gas Temp Cyl 9 (A5) OORL Warning PC 3.x
40436 8 Fault Status GasBitmap 6
676 Exhaust Gas Temp Cyl 11 (A6) OORL Warning PC 3.x
40436 9 Fault Status GasBitmap 6
677 Exhaust Gas Temp Cyl 13 (A7) OORL Warning PC 3.x
40436 10 Fault Status GasBitmap 6
678 Exhaust Gas Temp Cyl 15 (A8) OORL Warning PC 3.x
40436 11 Fault Status GasBitmap 6
683 Turbo 2 Speed Moderate High Warning PC 3.x
40436 12 Fault Status GasBitmap 6
684 Turbo 2 Speed Moderate Low Warning PC 3.x
40436 13 Fault Status GasBitmap 6
685 Turbo 2 Speed Incorrect Warning PC 3.x
40436 14 Fault Status GasBitmap 6
686 Turbo 1 Speed Incorrect Warning PC 2.x, PC3.x
40436 15 Fault Status GasBitmap 6
687 Turbo 1 Speed Low Warning PC 3.x
40437 0 Fault Status GasBitmap 7
697 ECM Internal Temperature High Error Warning PC 2.x, PC3.x
40437 1 Fault Status GasBitmap 7
698 ECM Internal Temperature Low Error Warning PC 2.x, PC3.x
40437 2 Fault Status GasBitmap 7
721 Exhaust Gas Temp 2 (B1) OORL Warning PC 3.x
40437 3 Fault Status GasBitmap 7
722 Exhaust Gas Temp 4 (B2) OORL Warning PC 3.x
314
Addr. ControlResponseEvent NameFaultCode
NameBit #
40437 4 Fault Status GasBitmap 7
723 Exhaust Gas Temp 6 (B3) OORL Warning PC 3.x
40437 5 Fault Status GasBitmap 7
724 Exhaust Gas Temp 8 (B4) OORL Warning PC 3.x
40437 6 Fault Status GasBitmap 7
725 Exhaust Gas Temp 10 (B5) OORL Warning PC 3.x
40437 7 Fault Status GasBitmap 7
726 Exhaust Gas Temp 12 (B6) OORL Warning PC 3.x
40437 8 Fault Status GasBitmap 7
727 Exhaust Gas Temp 14 (B7) OORL Warning PC 3.x
40437 9 Fault Status GasBitmap 7
728 Exhaust Gas Temp 16 (B8) OORL Warning PC 3.x
40437 10 Fault Status GasBitmap 7
736 Starter Air Pressure OORL Warning PC 3.x
40437 11 Fault Status GasBitmap 7
737 Starter Air Pressure OORH Warning PC 3.x
40437 12 Fault Status GasBitmap 7
738 Starter Air Press Underpressure Error Warning PC 3.x
40437 13 Fault Status GasBitmap 7
741 Air Filter Restriction Pressure High Er-ror
Warning PC 3.x
40437 14 Fault Status GasBitmap 7
742 Air Filter Restriction Pressure Low Er-ror
Warning PC 3.x
40437 15 Fault Status GasBitmap 7
751 Gas_Mass_Flow_In_Range_Error Warning PC 3.x
40438 0 Fault Status GasBitmap 8
752 Exhaust_Gas_Oxygen_In_Range_Er-ror
Warning PC 3.x
40438 1 Fault Status GasBitmap 8
783 Intake Manifold 1 Temp Abnormal Shutdownw/Cool-down
PC 3.x
40438 2 Fault Status GasBitmap 8
1213 COP_Overboost_Error Shutdownw/Cool-down
PC 3.x
40438 3 Fault Status GasBitmap 8
1274 Heavy_Knock_Error_10_(B5) Shutdownw/Cool-down
PC 3.x
40438 4 Fault Status GasBitmap 8
1281 Heavy_Knock_Error_12_(B6) Shutdownw/Cool-down
PC 3.x
40438 5 Fault Status GasBitmap 8
1285 Continuous_Light_Knock_Er-ror_13_(A7)
Shutdownw/Cool-down
PC 3.x
40438 6 Fault Status GasBitmap 8
1286 Heavy_Knock_Error_13_(A7) Shutdownw/Cool-down
PC 3.x
40438 7 Fault Status GasBitmap 8
1291 Heavy_Knock_Error_14_(B7) Shutdownw/Cool-down
PC 3.x
40438 8 Fault Status GasBitmap 8
1295 Continuous_Light_Knock_Er-ror_15_(A8)
Shutdownw/Cool-down
PC 3.x
315
Addr. ControlResponseEvent NameFaultCode
NameBit #
40438 9 Fault Status GasBitmap 8
1296 Heavy_Knock_Error_15_(A8) Shutdownw/Cool-down
PC 3.x
40438 10 Fault Status GasBitmap 8
1311 Heavy_Knock_Error_18_(B9) Shutdownw/Cool-down
PC 3.x
40438 11 Fault Status GasBitmap 8
1362 Oil Filter Restriction Error Warning PC 3.x
40438 12 Fault Status GasBitmap 8
1452 Genset Breaker Fail To Close Shutdown PC 3.x
40438 13 Fault Status GasBitmap 8
1457 Fail To Synchronize Warning PC 3.x
40438 14 Fault Status GasBitmap 8
1458 Sync Phase Rotation Mismatch Warning PC 3.x
40438 15 Fault Status GasBitmap 8
1474 ECM Software mismatch Shutdownw/Cool-down
PC 3.x
40439 0 Fault Status GasBitmap 9
1521 Exhaust Gas Temp 3 (A2) OORH Warning PC 3.x
40439 1 Fault Status GasBitmap 9
1522 Exhaust Gas Temp 5 (A3) OORH Warning PC 3.x
40439 2 Fault Status GasBitmap 9
1523 Exhaust Gas Temp 7 (A4) OORH Warning PC 3.x
40439 3 Fault Status GasBitmap 9
1524 Exhaust Gas Temp 9 (A5) OORH Warning PC 3.x
40439 4 Fault Status GasBitmap 9
1525 Exhaust Gas Temp 11 (A6) OORH Warning PC 3.x
40439 5 Fault Status GasBitmap 9
1526 Exhaust Gas Temp 13 (A7) OORH Warning PC 3.x
40439 6 Fault Status GasBitmap 9
1527 Exhaust Gas Temp 15 (A8) OORH Warning PC 3.x
40439 7 Fault Status GasBitmap 9
1528 Exhaust Gas Temp 17 (A9) OORH Warning PC 3.x
40439 8 Fault Status GasBitmap 9
1529 Exhaust Gas Temp 2 (B1) OORH Warning PC 3.x
40439 9 Fault Status GasBitmap 9
1531 Exhaust Gas Temp 6 (B3) OORH Warning PC 3.x
40439 10 Fault Status GasBitmap 9
1532 Exhaust Gas Temp 8 (B4) OORH Warning PC 3.x
40439 11 Fault Status GasBitmap 9
1533 Exhaust Gas Temp 10 (B5) OORH Warning PC 3.x
40439 12 Fault Status GasBitmap 9
1534 Exhaust Gas Temp 12 (B6) OORH Warning PC 3.x
40439 13 Fault Status GasBitmap 9
1535 Exhaust Gas Temp 14 (B7) OORH Warning PC 3.x
40439 14 Fault Status GasBitmap 9
1536 Exhaust Gas Temp 16 (B8) OORH Warning PC 3.x
40439 15 Fault Status GasBitmap 9
1537 Exhaust Gas Temp 18 (B9) OORH Warning PC 3.x
316
Addr. ControlResponseEvent NameFaultCode
NameBit #
40440 0 Fault Status GasBitmap 10
1545 EPS Backup Channel Lost Warning PC 3.x
40440 1 Fault Status GasBitmap 10
1546 EPS Main Channel Lost Warning PC 3.x
40440 2 Fault Status GasBitmap 10
1579 Continuous_Light_Knock_Er-ror_12_(B6)
Shutdownw/Cool-down
PC 3.x
40440 3 Fault Status GasBitmap 10
1581 Continuous_Light_Knock_Er-ror_14_(B7)
Shutdownw/Cool-down
PC 3.x
40440 4 Fault Status GasBitmap 10
1582 Continuous_Light_Knock_Er-ror_16_(B8)
Shutdownw/Cool-down
PC 3.x
40440 5 Fault Status GasBitmap 10
1583 Heavy_Knock_Error_16_(B8) Shutdownw/Cool-down
PC 3.x
40440 6 Fault Status GasBitmap 10
1587 Continuous_Light_Knock_Er-ror_17_(A9)
Shutdownw/Cool-down
PC 3.x
40440 7 Fault Status GasBitmap 10
1588 Heavy_Knock_Error_17_(A9) Shutdownw/Cool-down
PC 3.x
40440 8 Fault Status GasBitmap 10
1593 Continuous_Light_Knock_Er-ror_18_(B9)
Shutdownw/Cool-down
PC 3.x
40440 9 Fault Status GasBitmap 10
1618 Exhaust Gas Temp Cyl 1 (A1) OORH Warning PC 3.x
40440 10 Fault Status GasBitmap 10
1619 Exhaust Gas Temp Cyl 4 (B2) OORH Warning PC 3.x
40440 11 Fault Status GasBitmap 10
1636 Intake Manif Press 2 OORH Warning PC 3.x
40440 12 Fault Status GasBitmap 10
1637 Intake Manif Press 2 OORL Warning PC 3.x
40440 13 Fault Status GasBitmap 10
1737 CAN_Throttle_Internal_Failure_Error Shutdownw/Cool-down
PC 3.x
40440 14 Fault Status GasBitmap 10
1738 CAN_Throttle_Internal_Fault_Error Warning PC 3.x
40440 15 Fault Status GasBitmap 10
1739 Engine Throttle Control Condition Ex-ists
Warning PC 3.x
40441 0 Fault Status GasBitmap 11
1741 CAN_Throttle_High_Temp_Warn-ing_Error
Warning PC 3.x
40441 1 Fault Status GasBitmap 11
1742 CAN_Throttle_Temp_Limiting_Error Warning PC 3.x
40441 2 Fault Status GasBitmap 11
1743 Throttle Ctrl 2 OOR High Shutdownw/Cool-down
PC 3.x
40441 3 Fault Status GasBitmap 11
1744 Throttle Ctrl 2 OOR Low Shutdownw/Cool-down
PC 3.x
317
Addr. ControlResponseEvent NameFaultCode
NameBit #
40441 4 Fault Status GasBitmap 11
1745 Throttle Ctrl 2 Incorrect Shutdownw/Cool-down
PC 3.x
40441 5 Fault Status GasBitmap 11
1746 Throttle Ctrl 2 Out of Adjustment Shutdownw/Cool-down
PC 3.x
40441 6 Fault Status GasBitmap 11
1747 Throttle Ctrl 2 Bad Device Shutdownw/Cool-down
PC 3.x
40441 7 Fault Status GasBitmap 11
1748 Throttle Ctrl 2 Root Unknown Warning PC 3.x
40441 8 Fault Status GasBitmap 11
1749 Throttle Ctrl 2 Condition Exists Warning PC 3.x
40441 9 Fault Status GasBitmap 11
1751 Throttle Ctrl 2 Warning High Warning PC 3.x
40441 10 Fault Status GasBitmap 11
1752 Throttle Ctrl 2 Moderate High Warning PC 3.x
40441 11 Fault Status GasBitmap 11
1753 Fuel Shutoff 2 OOR High Warning PC 3.x
40441 12 Fault Status GasBitmap 11
1754 Fuel Tmp 2 OOR High Warning PC 3.x
40441 13 Fault Status GasBitmap 11
1755 Fuel Tmp 2 OOR Low Warning PC 3.x
40441 14 Fault Status GasBitmap 11
1756 Gas Flow 2 OOR High Warning PC 3.x
40441 15 Fault Status GasBitmap 11
1757 Gas Flow 2 OOR Low Warning PC 3.x
40442 0 Fault Status GasBitmap 12
1758 Gas Flow 2 Incorrect Data Warning PC 3.x
40442 1 Fault Status GasBitmap 12
1759 FCV 2 Pos Feedback Incorrect Shutdownw/Cool-down
PC 3.x
40442 2 Fault Status GasBitmap 12
1761 FCV_Actuator_Error_1761 Shutdownw/Cool-down
PC 3.x
40442 3 Fault Status GasBitmap 12
1984 Int Man 2 Tmp Moderate High Warning PC 3.x
40442 4 Fault Status GasBitmap 12
1765 FCV 2 In Pr OOR High Warning PC 3.x
40442 5 Fault Status GasBitmap 12
1766 FCV 2 In Pr OOR Low Warning PC 3.x
40442 6 Fault Status GasBitmap 12
1767 FCV 2 Out Pr OOR High Warning PC 3.x
40442 7 Fault Status GasBitmap 12
1768 FCV 2 Out Pr OOR Low Warning PC 3.x
40442 8 Fault Status GasBitmap 12
1769 E_Shutd Indication OORH Warning PC 3.x
40442 9 Fault Status GasBitmap 12
1771 E_Shutd Indication OORL Warning PC 3.x
318
Addr. ControlResponseEvent NameFaultCode
NameBit #
40442 10 Fault Status GasBitmap 12
1772 Eng Derate Request OORH Warning PC 3.x
40442 11 Fault Status GasBitmap 12
1773 Eng Derate Request OORL Warning PC 3.x
40442 12 Fault Status GasBitmap 12
1774 Oil Priming Pump OORH Warning PC 3.x
40442 13 Fault Status GasBitmap 12
1775 Oil Priming Pump OORL Warning PC 3.x
40442 14 Fault Status GasBitmap 12
3362 Power Conservation Control OORH Warning PC 3.x
40442 15 Fault Status GasBitmap 12
3363 Power Conservation Control OORL Warning PC 3.x
40443 0 Fault Status GasBitmap 13
1778 Engine_Heater_Control_Driv-er_High_Error
Warning PC 3.x
40443 1 Fault Status GasBitmap 13
1779 Engine_Heater_Control_Driv-er_Low_Error
Warning PC 3.x
40443 2 Fault Status GasBitmap 13
1781 Shutd Request OOR High Warning PC 3.x
40443 3 Fault Status GasBitmap 13
1782 Shutd Request OOR Low Warning PC 3.x
40443 4 Fault Status GasBitmap 13
1783 Coolant_Pump_Control_Driv-er_High_Error
Warning PC 3.x
40443 5 Fault Status GasBitmap 13
1784 Coolant_Pump_Control_Driv-er_Low_Error
Warning PC 3.x
40443 6 Fault Status GasBitmap 13
1785 Oil_Priming_Pump_Manual_Over-ride_Input_On
Warning PC 3.x
40443 7 Fault Status GasBitmap 13
1786 Oil_Priming_Pump_Stuck_On_Error Warning PC 3.x
40443 8 Fault Status GasBitmap 13
1787 Post_Lube_Oil_Priming_Error Warning PC 3.x
40443 9 Fault Status GasBitmap 13
1788 Maintenance_Lube_Oil_Priming_Error Warning PC 3.x
40443 10 Fault Status GasBitmap 13
1789 Pre_Start_Lube_Oil_Priming_Error Shutdownw/Cool-down
PC 3.x
40443 11 Fault Status GasBitmap 13
1791 Failure_To_Meet_Load_Speed_Error Shutdownw/Cool-down
PC 3.x
40443 12 Fault Status GasBitmap 13
1792 Idle when CB Closed Warning PC 3.x
40443 13 Fault Status GasBitmap 13
1793 Speed/Posit sensor out of Adj Warning PC 3.x
40443 14 Fault Status GasBitmap 13
1794 Fire Detected Shutdownw/Cool-down
PC 3.x
40443 15 Fault Status GasBitmap 13
1795 Compressor_Bypass_Posi-tion_High_Error
Warning PC 3.x
40444 0 Fault Status GasBitmap 14
1796 Compressor_Bypass_Posi-tion_Low_Error
Warning PC 3.x
319
Addr. ControlResponseEvent NameFaultCode
NameBit #
40444 1 Fault Status GasBitmap 14
1797 Compressor Bypass ctrl OORH Warning PC 3.x
40444 2 Fault Status GasBitmap 14
1798 Compressor Bypass ctrl OORL Warning PC 3.x
40444 3 Fault Status GasBitmap 14
1799 CB_Position_Err_Status Warning PC 3.x
40444 4 Fault Status GasBitmap 14
1811 HIGH_SIDE_DRV2_High_Control_Er-ror (VPS)
Warning PC 3.x
40444 5 Fault Status GasBitmap 14
1812 HIGH_SIDE_DRV2_Low_Control_Er-ror (VPS)
Warning PC 3.x
40444 6 Fault Status GasBitmap 14
1813 Valve_Proving_Sys-tem_Test_Failed_Warning_Error
Warning PC 3.x
40444 7 Fault Status GasBitmap 14
1814 Valve_Proving_Sys-tem_Test_Failed_Shutdown_Error
Shutdownw/Cool-down
PC 3.x
40444 8 Fault Status GasBitmap 14
1815 RLY14_High_Control_Error Warning PC 3.x
40444 9 Fault Status GasBitmap 14
1816 Oil PreHtr Ctrl OOR Low Warning PC 3.x
40444 10 Fault Status GasBitmap 14
1817 Oil_Pre−Heater_Tripped_Error Warning PC 3.x
40444 11 Fault Status GasBitmap 14
1818 Oil_Pre−Heater_Not_Warming_Error Warning PC 3.x
40444 12 Fault Status GasBitmap 14
1819 Common AC Aux CB tripped Warning PC 3.x
40444 13 Fault Status GasBitmap 14
1821 Min_FSO_Speed_Error Shutdownw/Cool-down
PC 3.x
40444 14 Fault Status GasBitmap 14
1822 LT Coolant Level Low Shutdown Error Shutdownw/Cool-down
PC 3.x
40444 15 Fault Status GasBitmap 14
1823 LT Coolant Level Low Warning Error Warning PC 3.x
40445 0 Fault Status GasBitmap 15
1824 Idle_Rated_Trans_Oil_Temp_Low_Er-ror
Warning PC 3.x
40445 1 Fault Status GasBitmap 15
1825 Dirty_Oil_Level_Error Warning PC 3.x
40445 2 Fault Status GasBitmap 15
1826 ECM Software incompatible Shutdownw/Cool-down
PC 3.x
40445 3 Fault Status GasBitmap 15
1827 Fuel_Inlet_Pressure_High_Error Warning PC 3.x
40445 4 Fault Status GasBitmap 15
1828 Fuel_Inlet_Pressure_Low_Error Warning PC 3.x
40445 5 Fault Status GasBitmap 15
1829 Vent_Gas_Valve_Error Shutdownw/Cool-down
PC 3.x
40445 6 Fault Status GasBitmap 15
1831 Upstream_FSO_Valve_Error Shutdownw/Cool-down
PC 3.x
320
Addr. ControlResponseEvent NameFaultCode
NameBit #
40445 7 Fault Status GasBitmap 15
1832 Downstream_FSO_Valve_Error Shutdownw/Cool-down
PC 3.x
40445 8 Fault Status GasBitmap 15
1833 Engine_Heater_Trip_Error Warning PC 3.x
40445 9 Fault Status GasBitmap 15
1834 Coolant_Pump_Trip_Error Warning PC 3.x
40445 10 Fault Status GasBitmap 15
1835 Oil_Priming_Pump_Tripped_Error Warning PC 3.x
40445 11 Fault Status GasBitmap 15
1836 LCP_(LT)_Low_Serious_Error Shutdownw/Cool-down
PC 3.x
40445 12 Fault Status GasBitmap 15
1837 Permanent_FS_Cam_Sync_Lost_Er-ror
Shutdownw/Cool-down
PC 3.x
40445 13 Fault Status GasBitmap 15
1838 Partial_Engine_Overload_Shut-down_Error
Shutdownw/Cool-down
PC 3.x
40445 14 Fault Status GasBitmap 15
1839 Fuel_Supply_Pressure_High_Error Warning PC 3.x
40445 15 Fault Status GasBitmap 15
1841 Fuel_Supply_Pressure_Low_Error Warning PC 3.x
40446 0 Fault Status GasBitmap 16
1842 Radiator_Fan_Trip_Error Warning PC 3.x
40446 1 Fault Status GasBitmap 16
1858 Exhaust Aft Inlet O2 OOR High Warning PC 3.x
40446 2 Fault Status GasBitmap 16
1859 Exhaust Aft Inlet O2 OOR Low Warning PC 3.x
40446 3 Fault Status GasBitmap 16
1861 Exhaust Aft Inlet O2 Incorrect Warning PC 3.x
40446 4 Fault Status GasBitmap 16
1862 Exhaust Aft Out O2 OOR High Warning PC 3.x
40446 5 Fault Status GasBitmap 16
1863 Exhaust Aft Outlet O2 OOR Low Warning PC 3.x
40446 6 Fault Status GasBitmap 16
1864 Exhaust Aft Outlet O2 Incorrect Warning PC 3.x
40446 7 Fault Status GasBitmap 16
1985 Int Man 3 Tmp Moderate High Warning PC 3.x
40446 8 Fault Status GasBitmap 16
1986 Int Man 4 Tmp Moderate High Warning PC 3.x
40446 9 Fault Status GasBitmap 16
2111 Coolant_Inlet_Temperatu-re_(LT)_High_Error
Warning PC 3.x
40446 10 Fault Status GasBitmap 16
2112 Coolant_Inlet_Temperatu-re_(LT)_Low_Error
Warning PC 3.x
40446 11 Fault Status GasBitmap 16
2113 CIT_(LT)_High_Warning_Error Warning PC 3.x
40446 12 Fault Status GasBitmap 16
2114 CIT_(LT)_High_Serious_Error Shutdownw/Cool-down
PC 3.x
321
Addr. ControlResponseEvent NameFaultCode
NameBit #
40446 13 Fault Status GasBitmap 16
2115 LT_Coolant_Pressure_High_Error Warning PC 3.x
40446 14 Fault Status GasBitmap 16
2116 LT_Coolant_Pressure_Low_Error Warning PC 3.x
40446 15 Fault Status GasBitmap 16
2117 LCP_(LT)_Low_Warning_Error Warning PC 3.x
40447 0 Fault Status GasBitmap 17
2121 Exhaust_Temp_1_(A1)_High_Warn-ing_Error
Warning PC 3.x
40447 1 Fault Status GasBitmap 17
2122 Exhaust_Temp_3_(A2)_High_Warn-ing_Error
Warning PC 3.x
40447 2 Fault Status GasBitmap 17
2123 Exhaust_Temp_5_(A3)_High_Warn-ing_Error
Warning PC 3.x
40447 3 Fault Status GasBitmap 17
2124 Exhaust_Temp_7_(A4)_High_Warn-ing_Error
Warning PC 3.x
40447 4 Fault Status GasBitmap 17
2125 Exhaust_Temp_9_(A5)_High_Warn-ing_Error
Warning PC 3.x
40447 5 Fault Status GasBitmap 17
2126 Exhaust_Temp_11_(A6)_High_Warn-ing_Error
Warning PC 3.x
40447 6 Fault Status GasBitmap 17
2127 Exhaust_Temp_13_(A7)_High_Warn-ing_Error
Warning PC 3.x
40447 7 Fault Status GasBitmap 17
2128 Exhaust_Temp_15_(A8)_High_Warn-ing_Error
Warning PC 3.x
40447 8 Fault Status GasBitmap 17
2129 Exhaust_Temp_17_(A9)_High_Warn-ing_Error
Warning PC 3.x
40447 9 Fault Status GasBitmap 17
2131 Exhaust_Temp_2_(B1)_High_Warn-ing_Error
Warning PC 3.x
40447 10 Fault Status GasBitmap 17
2132 Exhaust_Temp_4_(B2)_High_Warn-ing_Error
Warning PC 3.x
40447 11 Fault Status GasBitmap 17
2133 Exhaust_Temp_6_(B3)_High_Warn-ing_Error
Warning PC 3.x
40447 12 Fault Status GasBitmap 17
2134 Exhaust_Temp_8_(B4)_High_Warn-ing_Error
Warning PC 3.x
40447 13 Fault Status GasBitmap 17
2135 Exhaust_Temp_10_(B5)_High_Warn-ing_Error
Warning PC 3.x
40447 14 Fault Status GasBitmap 17
2136 Exhaust_Temp_12_(B6)_High_Warn-ing_Error
Warning PC 3.x
40447 15 Fault Status GasBitmap 17
2137 Exhaust_Temp_14_(B7)_High_Warn-ing_Error
Warning PC 3.x
40448 0 Fault Status GasBitmap 18
2138 Exhaust_Temp_16_(B8)_High_Warn-ing_Error
Warning PC 3.x
40448 1 Fault Status GasBitmap 18
2139 Exhaust_Temp_18_(B9)_High_Warn-ing_Error
Warning PC 3.x
40448 2 Fault Status GasBitmap 18
2141 Start_Air_Pressure_High_Error Warning PC 3.x
40448 3 Fault Status GasBitmap 18
2142 Start_Air_Pressure_Low_Error Warning PC 3.x
40448 4 Fault Status GasBitmap 18
2143 SAP_Overpressure_Error Warning PC 3.x
322
Addr. ControlResponseEvent NameFaultCode
NameBit #
40448 5 Fault Status GasBitmap 18
2144 Exhaust Temp 16 (B8) High SeriousError
Shutdownw/Cool-down
PC 3.x
40448 6 Fault Status GasBitmap 18
2145 Exhaust Temp 18 (B9) High SeriousError
Shutdownw/Cool-down
PC 3.x
40448 7 Fault Status GasBitmap 18
2146 EGT 17 (A9) OOR Low Warning PC 3.x
40448 8 Fault Status GasBitmap 18
2147 EGT 18 (B9) OOR Low Warning PC 3.x
40448 9 Fault Status GasBitmap 18
2154 Oil_Filter_Outlet_Pressure_High_Error Warning PC 3.x
40448 10 Fault Status GasBitmap 18
2155 Oil_Filter_Outlet_Pressure_Low_Error Warning PC 3.x
40448 11 Fault Status GasBitmap 18
2157 Int Man 2 Tmp Abnormal Rate Shutdownw/Cool-down
PC 3.x
40448 12 Fault Status GasBitmap 18
2158 Int Man 3 Tmp Abnormal Rate Shutdownw/Cool-down
PC 3.x
40448 13 Fault Status GasBitmap 18
2159 Int Man 4 Tmp Abnormal Rate Shutdownw/Cool-down
PC 3.x
40448 14 Fault Status GasBitmap 18
2188 Exhaust O2 OOR High Warning PC 3.x
40448 15 Fault Status GasBitmap 18
2191 ST_Throttle_Press_Err_Status Warning PC 3.x
40449 0 Fault Status GasBitmap 19
2192 Exhaust O2 OOR Low Warning PC 3.x
40449 1 Fault Status GasBitmap 19
2217 RAM_Image_Word_Error Warning PC 3.x
40449 2 Fault Status GasBitmap 19
2219 Exhaust O2 Moderate High Warning PC 3.x
40449 3 Fault Status GasBitmap 19
2221 Exhaust O2 Moderate Low Warning PC 3.x
40449 4 Fault Status GasBitmap 19
2281 Knock 11 (A6) Moderate High Shutdownw/Cool-down
PC 3.x
40449 5 Fault Status GasBitmap 19
2282 Knock 11 (A6) Critical High Shutdownw/Cool-down
PC 3.x
40449 6 Fault Status GasBitmap 19
2298 Fuel Shutoff 2 OOR Low Warning PC 3.x
40449 7 Fault Status GasBitmap 19
2315 Red Lamp OOR High Warning PC 3.x
40449 8 Fault Status GasBitmap 19
2316 Amber Lamp OOR High Warning PC 3.x
40449 9 Fault Status GasBitmap 19
2317 Amber Lamp OOR Low Warning PC 3.x
323
Addr. ControlResponseEvent NameFaultCode
NameBit #
40449 10 Fault Status GasBitmap 19
2427 Fuel_Outlet_Pressure_High_Error Warning PC 3.x
40449 11 Fault Status GasBitmap 19
2428 Fuel_Outlet_Pressure_Low_Error Warning PC 3.x
40449 12 Fault Status GasBitmap 19
2453 Total Real Power Circuit OORH Warning PC 3.x
40449 13 Fault Status GasBitmap 19
2454 Total Real Power Circuit OORL Warning PC 3.x
40449 14 Fault Status GasBitmap 19
2455 Speed_Bias_Low_Error Warning PC 3.x
40449 15 Fault Status GasBitmap 19
2456 Speed_Bias_High_Error Warning PC 3.x
40450 0 Fault Status GasBitmap 20
2457 Max_Total_Misfire_Error Shutdownw/Cool-down
PC 3.x
40450 1 Fault Status GasBitmap 20
2458 Cylinder_2_(B1)_Total_Misfire_Error Warning PC 3.x
40450 2 Fault Status GasBitmap 20
2459 Cylinder_4_(B2)_Total_Misfire_Error Warning PC 3.x
40450 3 Fault Status GasBitmap 20
2461 Cylinder_6_(B3)_Total_Misfire_Error Warning PC 3.x
40450 4 Fault Status GasBitmap 20
2462 Cylinder_8_(B4)_Total_Misfire_Error Warning PC 3.x
40450 5 Fault Status GasBitmap 20
2463 Cylinder_10_(B5)_Total_Misfire_Error Warning PC 3.x
40450 6 Fault Status GasBitmap 20
2464 Cylinder_12_(B6)_Total_Misfire_Error Warning PC 3.x
40450 7 Fault Status GasBitmap 20
2465 Cylinder_14_(B7)_Total_Misfire_Error Warning PC 3.x
40450 8 Fault Status GasBitmap 20
2466 Cylinder_16_(B8)_Total_Misfire_Error Warning PC 3.x
40450 9 Fault Status GasBitmap 20
2467 Cylinder_18_(B9)_Total_Misfire_Error Warning PC 3.x
40450 10 Fault Status GasBitmap 20
2469 Cylinder_1_(A1)_Total_Misfire_Error Warning PC 3.x
40450 11 Fault Status GasBitmap 20
2471 Cylinder_3_(A2)_Total_Misfire_Error Warning PC 3.x
40450 12 Fault Status GasBitmap 20
2472 Cylinder_5_(A3)_Total_Misfire_Error Warning PC 3.x
40450 13 Fault Status GasBitmap 20
2473 Cylinder_7_(A4)_Total_Misfire_Error Warning PC 3.x
40450 14 Fault Status GasBitmap 20
2475 Cylinder_9_(A5)_Total_Misfire_Error Warning PC 3.x
40450 15 Fault Status GasBitmap 20
2476 Cylinder_11_(A6)_Total_Misfire_Error Warning PC 3.x
40451 0 Fault Status GasBitmap 21
2477 Cylinder_13_(A7)_Total_Misfire_Error Warning PC 3.x
40451 1 Fault Status GasBitmap 21
2478 Cylinder_15_(A8)_Total_Misfire_Error Warning PC 3.x
324
Addr. ControlResponseEvent NameFaultCode
NameBit #
40451 2 Fault Status GasBitmap 21
2479 Cylinder_17_(A9)_Total_Misfire_Error Warning PC 3.x
40451 3 Fault Status GasBitmap 21
2482 Start_Before_Ready_Error Shutdownw/Cool-down
PC 3.x
40451 4 Fault Status GasBitmap 21
2483 Continuous_Starter_Failure_Error Shutdownw/Cool-down
PC 3.x
40451 5 Fault Status GasBitmap 21
2484 Exhaust Temperature 1 (A1) AbnormalRate
Shutdownw/Cool-down
PC 3.x
40451 6 Fault Status GasBitmap 21
2485 Exhaust Temperature 3 (A2) AbnormalRate
Shutdownw/Cool-down
PC 3.x
40451 7 Fault Status GasBitmap 21
2486 Exhaust Temperature 5 (A3) AbnormalRate
Shutdownw/Cool-down
PC 3.x
40451 8 Fault Status GasBitmap 21
2487 Exhaust Temperature 7 (A4) AbnormalRate
Shutdownw/Cool-down
PC 3.x
40451 9 Fault Status GasBitmap 21
2488 Exhaust Temperature 9 (A5) AbnormalRate
Shutdownw/Cool-down
PC 3.x
40451 10 Fault Status GasBitmap 21
2489 Exhaust Temperature 11 (A6) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
40451 11 Fault Status GasBitmap 21
2491 Exhaust Temperature 13 (A7) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
40451 12 Fault Status GasBitmap 21
2492 Exhaust Temperature 15 (A8) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
40451 13 Fault Status GasBitmap 21
2493 Exhaust Temperature 17 (A9) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
40451 14 Fault Status GasBitmap 21
2494 Exhaust Temperature 2 (B1) AbnormalRate
Shutdownw/Cool-down
PC 3.x
40451 15 Fault Status GasBitmap 21
2495 Exhaust Temperature 4 (B2) AbnormalRate
Shutdownw/Cool-down
PC 3.x
40452 0 Fault Status GasBitmap 22
2496 Exhaust Temperature 6 (B3) AbnormalRate
Shutdownw/Cool-down
PC 3.x
40452 1 Fault Status GasBitmap 22
2497 Exhaust Temperature 8 (B4) AbnormalRate
Shutdownw/Cool-down
PC 3.x
40452 2 Fault Status GasBitmap 22
2498 Exhaust Temperature 10 (B5) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
325
Addr. ControlResponseEvent NameFaultCode
NameBit #
40452 3 Fault Status GasBitmap 22
2499 Exhaust Temperature 12 (B6) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
40452 4 Fault Status GasBitmap 22
2511 Exhaust Temperature 14 (B7) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
40452 5 Fault Status GasBitmap 22
2512 Exhaust Temperature 16 (B8) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
40452 6 Fault Status GasBitmap 22
2513 Exhaust Temperature 18 (B9) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
40452 7 Fault Status GasBitmap 22
2517 Compressor_Outlet_Pres-sure_High_Error
Warning PC 3.x
40452 8 Fault Status GasBitmap 22
2518 Compressor_Outlet_Pres-sure_Low_Error
Warning PC 3.x
40452 9 Fault Status GasBitmap 22
2521 Bank_Id_Error Shutdownw/Cool-down
PC 3.x
40452 10 Fault Status GasBitmap 22
2522 Continuous_Light_Knock_Er-ror_1_(A1)
Shutdownw/Cool-down
PC 3.x
40452 11 Fault Status GasBitmap 22
2523 Continuous_Light_Knock_Er-ror_2_(B1)
Shutdownw/Cool-down
PC 3.x
40452 12 Fault Status GasBitmap 22
2524 Continuous_Light_Knock_Er-ror_3_(A2)
Shutdownw/Cool-down
PC 3.x
40452 13 Fault Status GasBitmap 22
2525 Continuous_Light_Knock_Er-ror_4_(B2)
Shutdownw/Cool-down
PC 3.x
40452 14 Fault Status GasBitmap 22
2526 Continuous_Light_Knock_Er-ror_5_(A3)
Shutdownw/Cool-down
PC 3.x
40452 15 Fault Status GasBitmap 22
2527 Continuous_Light_Knock_Er-ror_6_(B3)
Shutdownw/Cool-down
PC 3.x
40453 0 Fault Status GasBitmap 23
2528 Continuous_Light_Knock_Er-ror_7_(A4)
Shutdownw/Cool-down
PC 3.x
40453 1 Fault Status GasBitmap 23
2529 Continuous_Light_Knock_Er-ror_8_(B4)
Shutdownw/Cool-down
PC 3.x
40453 2 Fault Status GasBitmap 23
2531 Continuous_Light_Knock_Er-ror_9_(A5)
Shutdownw/Cool-down
PC 3.x
40453 3 Fault Status GasBitmap 23
2532 Continuous_Light_Knock_Er-ror_10_(B5)
Shutdownw/Cool-down
PC 3.x
326
Addr. ControlResponseEvent NameFaultCode
NameBit #
40453 4 Fault Status GasBitmap 23
2544 ECM_Overtemp_Error Shutdownw/Cool-down
PC 3.x
40453 5 Fault Status GasBitmap 23
2567 DG_Air_Compressor_Trip_Error Warning PC 3.x
40453 6 Fault Status GasBitmap 23
2643 Throttle Pos 2 Feedback OOR High Warning PC 3.x
40453 7 Fault Status GasBitmap 23
2644 Throttle Pos 2 Feedback OOR Low Warning PC 3.x
40453 8 Fault Status GasBitmap 23
2661 At Least One ACK: Most Severe Fault Shutdown PC 2.x, PC3.x
40453 9 Fault Status GasBitmap 23
2724 Gas Supply Pr Moderate High Warning PC 3.x
40453 10 Fault Status GasBitmap 23
2725 Gas Supply Pr Moderate Low Warning PC 3.x
40453 11 Fault Status GasBitmap 23
2737 Exh Gas Tmp Critical High Shutdownw/Cool-down
PC 3.x
40453 12 Fault Status GasBitmap 23
2766 Bank_A_CCD_Failed_Error Shutdownw/Cool-down
PC 3.x
40453 13 Fault Status GasBitmap 23
2767 Bank_B_CCD_Failed_Error Shutdownw/Cool-down
PC 3.x
40453 14 Fault Status GasBitmap 23
2768 CAN Parent Communication Incorrect Shutdownw/Cool-down
PC 3.x
40453 15 Fault Status GasBitmap 23
2769 CAN Child Com Incorrect Shutdownw/Cool-down
PC 3.x
40454 0 Fault Status GasBitmap 24
2789 COT_Low_Error Warning PC 3.x
40454 1 Fault Status GasBitmap 24
2793 COT_Low_Serious_Error Shutdownw/Cool-down
PC 3.x
40454 2 Fault Status GasBitmap 24
2794 Ign Shutd Relay OOR High Warning PC 3.x
40454 3 Fault Status GasBitmap 24
2795 Ign Shutd Relay OOR Low Warning PC 3.x
40454 4 Fault Status GasBitmap 24
2796 Partial_Engine_Overload_Warn-ing_Error
Warning PC 3.x
40454 5 Fault Status GasBitmap 24
2797 Inlet Gas Diff Pressure OOR High Warning PC 3.x
40454 6 Fault Status GasBitmap 24
2798 Inlet Gas Diff Pressure OOR Low Warning PC 3.x
40454 7 Fault Status GasBitmap 24
2799 IMOP_Compressor_Outlet_Pres-ure_Delta_Error
Shutdownw/Cool-down
PC 3.x
327
Addr. ControlResponseEvent NameFaultCode
NameBit #
40454 8 Fault Status GasBitmap 24
2811 IMOP_Compressor_Outlet_Pres-sure_Maximum_Error
Shutdownw/Cool-down
PC 3.x
40454 9 Fault Status GasBitmap 24
2837 Exhaust_Temp_1_(A1)_Deviation_Er-ror
Warning PC 3.x
40454 10 Fault Status GasBitmap 24
2838 Exhaust_Temp_3_(A2)_Deviation_Er-ror
Warning PC 3.x
40454 11 Fault Status GasBitmap 24
2839 Exhaust_Temp_5_(A3)_Deviation_Er-ror
Warning PC 3.x
40454 12 Fault Status GasBitmap 24
2841 Exhaust_Temp_7_(A4)_Deviation_Er-ror
Warning PC 3.x
40454 13 Fault Status GasBitmap 24
2842 Exhaust_Temp_9_(A5)_Deviation_Er-ror
Warning PC 3.x
40454 14 Fault Status GasBitmap 24
2843 Exhaust_Temp_11_(A6)_Devi-ation_Error
Warning PC 3.x
40454 15 Fault Status GasBitmap 24
2844 Exhaust_Temp_13_(A7)_Devi-ation_Error
Warning PC 3.x
40455 0 Fault Status GasBitmap 25
2845 Exhaust_Temp_15_(A8)_Devi-ation_Error
Warning PC 3.x
40455 1 Fault Status GasBitmap 25
2846 Exhaust_Temp_17_(A9)_Devi-ation_Error
Warning PC 3.x
40455 2 Fault Status GasBitmap 25
2847 Exhaust_Temp_2_(B1)_Deviation_Er-ror
Warning PC 3.x
40455 3 Fault Status GasBitmap 25
2848 Exhaust_Temp_4_(B2)_Deviation_Er-ror
Warning PC 3.x
40455 4 Fault Status GasBitmap 25
2849 Exhaust_Temp_6_(B3)_Deviation_Er-ror
Warning PC 3.x
40455 5 Fault Status GasBitmap 25
2851 Exhaust_Temp_8_(B4)_Deviation_Er-ror
Warning PC 3.x
40455 6 Fault Status GasBitmap 25
2852 Exhaust_Temp_10_(B5)_Devi-ation_Error
Warning PC 3.x
40455 7 Fault Status GasBitmap 25
2853 Exhaust_Temp_12_(B6)_Devi-ation_Error
Warning PC 3.x
40455 8 Fault Status GasBitmap 25
2854 Exhaust_Temp_14_(B7)_Devi-ation_Error
Warning PC 3.x
40455 9 Fault Status GasBitmap 25
2855 Exhaust_Temp_16_(B8)_Devi-ation_Error
Warning PC 3.x
40455 10 Fault Status GasBitmap 25
2856 Exhaust_Temp_18_(B9)_Devi-ation_Error
Warning PC 3.x
40455 11 Fault Status GasBitmap 25
2857 Turbo_1_Overspeed_Critical_Error Shutdownw/Cool-down
PC 3.x
40455 12 Fault Status GasBitmap 25
2858 Turbo_2_Overspeed_Critical_Error Shutdownw/Cool-down
PC 3.x
40455 13 Fault Status GasBitmap 25
2859 Alt Heater Ctrl OOR High Warning PC 3.x
40455 14 Fault Status GasBitmap 25
2861 Alt Heater Ctrl OOR Low Warning PC 3.x
328
Addr. ControlResponseEvent NameFaultCode
NameBit #
40455 15 Fault Status GasBitmap 25
2862 Gen Alternator 1st Start Cond Exists Warning PC 3.x
40456 0 Fault Status GasBitmap 26
2863 Genset to Engine Com Incorrect Shutdownw/Cool-down
PC 3.x
40456 1 Fault Status GasBitmap 26
2864 FSO_NON_High_Control_Error Shutdownw/Cool-down
PC 3.x
40456 2 Fault Status GasBitmap 26
3364 Power Conservation Control Cond Ex-ists
Warning PC 3.x
40456 3 Fault Status GasBitmap 26
2866 FCV_Position_High_Error Warning PC 3.x
40456 4 Fault Status GasBitmap 26
2867 FCV_Position_Low_Error Warning PC 3.x
40456 5 Fault Status GasBitmap 26
2868 Engine_Heater_Over−Tempera-ture_Alarm_Error
Warning PC 3.x
40456 6 Fault Status GasBitmap 26
2869 HT Cool Temp Driver OOR High Warning PC 3.x
40456 7 Fault Status GasBitmap 26
2871 HT Cool Temp Driver OOR Low Warning PC 3.x
40456 8 Fault Status GasBitmap 26
2872 HT Cool Temp Driver Cond Exists Warning PC 3.x
40456 9 Fault Status GasBitmap 26
2873 LT Cool Temp Driver OOR High Warning PC 3.x
40456 10 Fault Status GasBitmap 26
2874 LT Cool Temp Driver OOR Low Warning PC 3.x
40456 11 Fault Status GasBitmap 26
2875 LT Cool Temp Driver Cond Exists Warning PC 3.x
40456 12 Fault Status GasBitmap 26
2876 Comp_Surge_Shutdown_Error Shutdownw/Cool-down
PC 3.x
40456 13 Fault Status GasBitmap 26
2877 Comp_Surge_Derate_Error Warning PC 3.x
40456 14 Fault Status GasBitmap 26
2994 MC68302_Error Warning PC 3.x
40456 15 Fault Status GasBitmap 26
2995 Int Man Pressure 1 Critical High Shutdownw/Cool-down
PC 3.x
40457 0 Fault Status GasBitmap 27
2996 Int Man Pressure 1 Moderate High Warning PC 3.x
40457 1 Fault Status GasBitmap 27
2997 Exhaust O2 Critical Low Shutdownw/Cool-down
PC 3.x
40457 2 Fault Status GasBitmap 27
3111 Excessive_Mech_Vibration_1_(A1) Shutdownw/Cool-down
PC 3.x
40457 3 Fault Status GasBitmap 27
3112 Excessive_Mech_Vibration_2_(B1) Shutdownw/Cool-down
PC 3.x
329
Addr. ControlResponseEvent NameFaultCode
NameBit #
40457 4 Fault Status GasBitmap 27
3113 Excessive_Mech_Vibration_3_(A2) Shutdownw/Cool-down
PC 3.x
40457 5 Fault Status GasBitmap 27
3114 Excessive_Mech_Vibration_4_(B2) Shutdownw/Cool-down
PC 3.x
40457 6 Fault Status GasBitmap 27
3115 Excessive_Mech_Vibration_5_(A3) Shutdownw/Cool-down
PC 3.x
40457 7 Fault Status GasBitmap 27
3116 Excessive_Mech_Vibration_6_(B3) Shutdownw/Cool-down
PC 3.x
40457 8 Fault Status GasBitmap 27
3117 Excessive_Mech_Vibration_7_(A4) Shutdownw/Cool-down
PC 3.x
40457 9 Fault Status GasBitmap 27
3118 Excessive_Mech_Vibration_8_(B4) Shutdownw/Cool-down
PC 3.x
40457 10 Fault Status GasBitmap 27
3119 Excessive_Mech_Vibration_9_(A5) Shutdownw/Cool-down
PC 3.x
40457 11 Fault Status GasBitmap 27
3121 Excessive_Mech_Vibration_10_(B5) Shutdownw/Cool-down
PC 3.x
40457 12 Fault Status GasBitmap 27
3122 Excessive_Mech_Vibration_11_(A6) Shutdownw/Cool-down
PC 3.x
40457 13 Fault Status GasBitmap 27
3123 Excessive_Mech_Vibration_12_(B6) Shutdownw/Cool-down
PC 3.x
40457 14 Fault Status GasBitmap 27
3124 Excessive_Mech_Vibration_13_(A7) Shutdownw/Cool-down
PC 3.x
40457 15 Fault Status GasBitmap 27
3125 Excessive_Mech_Vibration_14_(B7) Shutdownw/Cool-down
PC 3.x
40458 0 Fault Status GasBitmap 28
3126 Excessive_Mech_Vibration_15_(A8) Shutdownw/Cool-down
PC 3.x
40458 1 Fault Status GasBitmap 28
3127 Excessive_Mech_Vibration_16_(B8) Shutdownw/Cool-down
PC 3.x
40458 2 Fault Status GasBitmap 28
3128 Excessive_Mech_Vibration_17_(A9) Shutdownw/Cool-down
PC 3.x
40458 3 Fault Status GasBitmap 28
3129 Excessive_Mech_Vibration_18_(B9) Shutdownw/Cool-down
PC 3.x
40458 4 Fault Status GasBitmap 28
1275 Knock Cyl 10 (B5) OORL Warning PC 3.x
330
Addr. ControlResponseEvent NameFaultCode
NameBit #
40458 5 Fault Status GasBitmap 28
1277 Knock Cyl 11 (A6) OORL Warning PC 3.x
40458 6 Fault Status GasBitmap 28
1282 Knock Cyl 12 (B6) OORL Warning PC 3.x
40458 7 Fault Status GasBitmap 28
1287 Knock Cyl 13 (A7) OORL Warning PC 3.x
40458 8 Fault Status GasBitmap 28
1292 Knock Cyl 14 (B7) OORL Warning PC 3.x
40458 9 Fault Status GasBitmap 28
1297 Knock Cyl 15 (A8) OORL Warning PC 3.x
40458 10 Fault Status GasBitmap 28
1584 Knock Cyl 16 (B8) OORL Warning PC 3.x
40458 11 Fault Status GasBitmap 28
1589 Knock Cyl 17 (A9) OORL Warning PC 3.x
40458 12 Fault Status GasBitmap 28
1338 Knock Cyl 18 (B9) OORL Warning PC 3.x
40459 0 Fault Status GasBitmap 29
189 HT Coolant Temperature Root CauseUnknown
Shutdownw/Cool-down
PC 3.x
40459 1 Fault Status GasBitmap 29
229 HT Coolant Pressure Incorrect Warning PC 3.x
40459 2 Fault Status GasBitmap 29
334 HT Coolant Temperature Incorrect Warning PC 3.x
40459 4 Fault Status GasBitmap 29
831 Spark Plug 1 (A1) OORL Warning PC 3.x
40459 5 Fault Status GasBitmap 29
832 Spark Plug 2 (B1) OORL Warning PC 3.x
40459 6 Fault Status GasBitmap 29
833 Spark Plug 3 (A2) OORL Warning PC 3.x
40459 7 Fault Status GasBitmap 29
834 Spark Plug 4 (B2) OORL Warning PC 3.x
40459 8 Fault Status GasBitmap 29
835 Spark Plug 5 (A3) OORL Warning PC 3.x
40459 9 Fault Status GasBitmap 29
836 Spark Plug 6 (B3) OORL Warning PC 3.x
40459 10 Fault Status GasBitmap 29
837 Spark Plug 7 (A4) OORL Warning PC 3.x
40459 11 Fault Status GasBitmap 29
838 Spark Plug 8 (B4) OORL Warning PC 3.x
40459 12 Fault Status GasBitmap 29
839 Spark Plug 9 (A5) OORL Warning PC 3.x
40459 13 Fault Status GasBitmap 29
841 Spark Plug 10 (B5) OORL Warning PC 3.x
40459 14 Fault Status GasBitmap 29
842 Spark Plug 11 (A6) OORL Warning PC 3.x
40459 15 Fault Status GasBitmap 29
843 Spark Plug 12 (B6) OORL Warning PC 3.x
40460 0 Fault Status GasBitmap 30
844 Spark Plug 13 (A7) OORL Warning PC 3.x
331
Addr. ControlResponseEvent NameFaultCode
NameBit #
40460 1 Fault Status GasBitmap 30
845 Spark Plug 14 (B7) OORL Warning PC 3.x
40460 2 Fault Status GasBitmap 30
846 Spark Plug 15 (A8) OORL Warning PC 3.x
40460 3 Fault Status GasBitmap 30
847 Spark Plug 16 (B8) OORL Warning PC 3.x
40460 4 Fault Status GasBitmap 30
848 Spark Plug 17 (A9) OORL Warning PC 3.x
40460 5 Fault Status GasBitmap 30
849 Spark Plug 18 (B9) OORL Warning PC 3.x
40460 7 Fault Status GasBitmap 30
891 Spark Plug 1 (A1) Root Cause Un-known
Warning PC 3.x
40460 8 Fault Status GasBitmap 30
892 Spark Plug 2 (B1) Root Cause Un-known
Warning PC 3.x
40460 9 Fault Status GasBitmap 30
893 Spark Plug 3 (A2) Root Cause Un-known
Warning PC 3.x
40460 10 Fault Status GasBitmap 30
894 Spark Plug 4 (B2) Root Cause Un-known
Warning PC 3.x
40460 11 Fault Status GasBitmap 30
895 Spark Plug 5 (A3) Root Cause Un-known
Warning PC 3.x
40460 12 Fault Status GasBitmap 30
896 Spark Plug 6 (B3) Root Cause Un-known
Warning PC 3.x
40460 13 Fault Status GasBitmap 30
897 Spark Plug 7 (A4) Root Cause Un-known
Warning PC 3.x
40460 14 Fault Status GasBitmap 30
898 Spark Plug 8 (B4) Root Cause Un-known
Warning PC 3.x
40460 15 Fault Status GasBitmap 30
899 Spark Plug 9 (A5) Root Cause Un-known
Warning PC 3.x
40461 0 Fault Status GasBitmap 31
911 Spark Plug 10 (B5) Root Cause Un-known
Warning PC 3.x
40461 1 Fault Status GasBitmap 31
912 Spark Plug 11 (A6) Root Cause Un-known
Warning PC 3.x
40461 2 Fault Status GasBitmap 31
913 Spark Plug 12 (B6) Root Cause Un-known
Warning PC 3.x
40461 3 Fault Status GasBitmap 31
914 Spark Plug 13 (A7) Root Cause Un-known
Warning PC 3.x
40461 4 Fault Status GasBitmap 31
915 Spark Plug 14 (B7) Root Cause Un-known
Warning PC 3.x
40461 5 Fault Status GasBitmap 31
916 Spark Plug 15 (A8) Root Cause Un-known
Warning PC 3.x
40461 6 Fault Status GasBitmap 31
917 Spark Plug 16 (B8) Root Cause Un-known
Warning PC 3.x
40461 7 Fault Status GasBitmap 31
918 Spark Plug 17 (A9) Root Cause Un-known
Warning PC 3.x
40461 8 Fault Status GasBitmap 31
919 Spark Plug 18 (B9) Root Cause Un-known
Warning PC 3.x
40461 10 Fault Status GasBitmap 31
1276 Knock Cyl 10 (B5) OORH Warning PC 3.x
40461 11 Fault Status GasBitmap 31
1278 Knock Cyl 11 (A6) OORH Warning PC 3.x
332
Addr. ControlResponseEvent NameFaultCode
NameBit #
40461 12 Fault Status GasBitmap 31
1279 Knock 12 (B6) High Warning Warning PC 3.x
40461 13 Fault Status GasBitmap 31
1283 Knock Cyl 12 (B6) OORH Warning PC 3.x
40461 14 Fault Status GasBitmap 31
1284 Knock 13 (A7) High Warning Warning PC 3.x
40461 15 Fault Status GasBitmap 31
1288 Knock Cyl 13 (A7) OORH Warning PC 3.x
40462 0 Fault Status GasBitmap 32
1289 Knock 14 (B7) High Warning Warning PC 3.x
40462 1 Fault Status GasBitmap 32
1293 Knock Cyl 14 (B7) OORH Warning PC 3.x
40462 2 Fault Status GasBitmap 32
1294 Knock 15 (A8) High Warning Warning PC 3.x
40462 3 Fault Status GasBitmap 32
1298 Knock Cyl 15 (A8) OORH Warning PC 3.x
40462 4 Fault Status GasBitmap 32
1299 Knock 16 (B8) High Warning Warning PC 3.x
40462 6 Fault Status GasBitmap 32
1339 Knock Cyl 18 (B9) OORH Warning PC 3.x
40462 7 Fault Status GasBitmap 32
1352 Knock 20 (B10) High Warning Warning PC 3.x
40462 8 Fault Status GasBitmap 32
1353 Continuous_Light_Knock_Er-ror_20_(B10)
Shutdownw/Cool-down
PC 3.x
40462 9 Fault Status GasBitmap 32
1354 Heavy_Knock_Error_20_(B10) Shutdownw/Cool-down
PC 3.x
40462 10 Fault Status GasBitmap 32
1355 Knock Cyl 20 (B10) OORL Warning PC 3.x
40462 11 Fault Status GasBitmap 32
1356 Knock Cyl 20 (B10) OORH Warning PC 3.x
40462 12 Fault Status GasBitmap 32
1572 Continuous_Light_Knock_Er-ror_19_(A10)
Shutdownw/Cool-down
PC 3.x
40462 13 Fault Status GasBitmap 32
1574 Heavy_Knock_Error_19_(A10) Shutdownw/Cool-down
PC 3.x
40462 14 Fault Status GasBitmap 32
1575 Knock Cyl 19 (A10) OORL Warning PC 3.x
40462 15 Fault Status GasBitmap 32
1576 Knock Cyl 19 (A10) OORH Warning PC 3.x
40463 0 Fault Status GasBitmap 33
1585 Knock Cyl 16 (B8) OORH Warning PC 3.x
40463 1 Fault Status GasBitmap 33
1586 Knock 17 (A9) High Warning Warning PC 3.x
40463 2 Fault Status GasBitmap 33
1591 Knock Cyl 17 (A9) OORH Warning PC 3.x
40463 3 Fault Status GasBitmap 33
1592 Knock 18 (B9) High Warning Warning PC 3.x
333
Addr. ControlResponseEvent NameFaultCode
NameBit #
40463 4 Fault Status GasBitmap 33
1594 Knock 19 (A10) High Warning Warning PC 3.x
40463 6 Fault Status GasBitmap 33
2193 HT Coolant Level Moderate High Warning PC 3.x
40463 7 Fault Status GasBitmap 33
2231 Knock Cyl 1 (A1) OORH Warning PC 3.x
40463 8 Fault Status GasBitmap 33
2232 Knock Cyl 2 (B1) OORH Warning PC 3.x
40463 9 Fault Status GasBitmap 33
2233 Knock Cyl 3 (A2) OORH Warning PC 3.x
40463 10 Fault Status GasBitmap 33
2234 Knock Cyl 4 (B2) OORH Warning PC 3.x
40463 11 Fault Status GasBitmap 33
2235 Knock Cyl 5 (A3) OORH Warning PC 3.x
40463 12 Fault Status GasBitmap 33
2236 Knock Cyl 6 (B3) OORH Warning PC 3.x
40463 13 Fault Status GasBitmap 33
2237 Knock Cyl 7 (A4) OORH Warning PC 3.x
40463 14 Fault Status GasBitmap 33
2238 Knock Cyl 8 (B4) OORH Warning PC 3.x
40463 15 Fault Status GasBitmap 33
2239 Knock Cyl 9 (A5) OORH Warning PC 3.x
40464 0 Fault Status GasBitmap 34
2279 Knock 11 (A6) High Warning Warning PC 3.x
40464 1 Fault Status GasBitmap 34
2431 Knock 1 (A1) High Warning Warning PC 3.x
40464 2 Fault Status GasBitmap 34
2432 Knock 2 (B1) High Warning Warning PC 3.x
40464 3 Fault Status GasBitmap 34
2433 Knock 3 (A2) High Warning Warning PC 3.x
40464 4 Fault Status GasBitmap 34
2434 Knock 4 (B2) High Warning Warning PC 3.x
40464 5 Fault Status GasBitmap 34
2435 Knock 5 (A3) High Warning Warning PC 3.x
40464 6 Fault Status GasBitmap 34
2436 Knock 6 (B3) High Warning Warning PC 3.x
40464 7 Fault Status GasBitmap 34
2437 Knock 7 (A4) High Warning Warning PC 3.x
40464 8 Fault Status GasBitmap 34
2438 Knock 8 (B4) High Warning Warning PC 3.x
40464 9 Fault Status GasBitmap 34
2439 Knock 9 (A5) High Warning Warning PC 3.x
40464 10 Fault Status GasBitmap 34
2441 Knock 10 (B5) High Warning Warning PC 3.x
40464 11 Fault Status GasBitmap 34
2514 Exhaust Temperature 19 (A10) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
40464 12 Fault Status GasBitmap 34
2515 Exhaust Temperature 20 (B10) Abnor-mal Rate
Shutdownw/Cool-down
PC 3.x
334
Addr. ControlResponseEvent NameFaultCode
NameBit #
40464 13 Fault Status GasBitmap 34
2553 Engine Oil Level Low Warning Error Warning PC 3.x
40464 14 Fault Status GasBitmap 34
2568 Gas Supply Pressure Critical High Shutdownw/Cool-down
PC 3.x
40464 15 Fault Status GasBitmap 34
2569 Gas Supply Pressure Critical Low Shutdownw/Cool-down
PC 3.x
40465 0 Fault Status GasBitmap 35
2586 Spark Plug 1 (A1) High Warning NONE PC 3.x
40465 1 Fault Status GasBitmap 35
2587 Spark Plug 2 (B1) High Warning NONE PC 3.x
40465 2 Fault Status GasBitmap 35
2588 Spark Plug 3 (A2) High Warning NONE PC 3.x
40465 3 Fault Status GasBitmap 35
2589 Spark Plug 4 (B2) High Warning NONE PC 3.x
40465 4 Fault Status GasBitmap 35
2591 Spark Plug 5 (A3) High Warning NONE PC 3.x
40465 5 Fault Status GasBitmap 35
2592 Spark Plug 6 (B3) High Warning NONE PC 3.x
40465 6 Fault Status GasBitmap 35
2593 Spark Plug 1 (A1) Low Warning NONE PC 3.x
40465 7 Fault Status GasBitmap 35
2594 Spark Plug 2 (B1) Low Warning NONE PC 3.x
40465 8 Fault Status GasBitmap 35
2595 Spark Plug 3 (A2) Low Warning NONE PC 3.x
40465 9 Fault Status GasBitmap 35
2596 Spark Plug 4 (B2) Low Warning NONE PC 3.x
40465 10 Fault Status GasBitmap 35
2597 Spark Plug 5 (A3) Low Warning NONE PC 3.x
40465 11 Fault Status GasBitmap 35
2598 Spark Plug 6 (B3) Low Warning NONE PC 3.x
40465 12 Fault Status GasBitmap 35
2646 HT Coolant Temperature ConditionExists
Warning PC 3.x
40465 13 Fault Status GasBitmap 35
2963 HT Coolant Temperature WarningHigh
NONE PC 2.x, PC3.x
40466 0 Fault Status GasBitmap 36
3262 Spark Plug 7 (A4) High Warning NONE PC 3.x
40466 1 Fault Status GasBitmap 36
3263 Spark Plug 7 (A4) Low Warning NONE PC 3.x
40466 2 Fault Status GasBitmap 36
3264 Spark Plug 8 (B4) High Warning NONE PC 3.x
40466 3 Fault Status GasBitmap 36
3265 Spark Plug 8 (B4) Low Warning NONE PC 3.x
40466 4 Fault Status GasBitmap 36
3266 Spark Plug 9 (A5) High Warning NONE PC 3.x
40466 5 Fault Status GasBitmap 36
3267 Spark Plug 9 (A5) Low Warning NONE PC 3.x
40466 6 Fault Status GasBitmap 36
3268 Spark Plug 10 (B5) High Warning NONE PC 3.x
335
Addr. ControlResponseEvent NameFaultCode
NameBit #
40466 7 Fault Status GasBitmap 36
3269 Spark Plug 10 (B5) Low Warning NONE PC 3.x
40466 8 Fault Status GasBitmap 36
3271 Spark Plug 11 (A6) High Warning NONE PC 3.x
40466 9 Fault Status GasBitmap 36
3272 Spark Plug 11 (A6) Low Warning NONE PC 3.x
40466 10 Fault Status GasBitmap 36
3273 Spark Plug 12 (B6) High Warning NONE PC 3.x
40466 11 Fault Status GasBitmap 36
3274 Spark Plug 12 (B6) Low Warning NONE PC 3.x
40466 12 Fault Status GasBitmap 36
3275 Spark Plug 13 (A7) High Warning NONE PC 3.x
40466 13 Fault Status GasBitmap 36
3276 Spark Plug 13 (A7) Low Warning NONE PC 3.x
40466 14 Fault Status GasBitmap 36
3277 Spark Plug 14 (B7) High Warning NONE PC 3.x
40466 15 Fault Status GasBitmap 36
3278 Spark Plug 14 (B7) Low Warning NONE PC 3.x
40467 0 Fault Status GasBitmap 37
3279 Spark Plug 15 (A8) High Warning NONE PC 3.x
40467 1 Fault Status GasBitmap 37
3281 Spark Plug 15 (A8) Low Warning NONE PC 3.x
40467 2 Fault Status GasBitmap 37
3282 Spark Plug 16 (B8) High Warning NONE PC 3.x
40467 3 Fault Status GasBitmap 37
3283 Spark Plug 16 (B8) Low Warning NONE PC 3.x
40467 4 Fault Status GasBitmap 37
3284 Spark Plug 17 (A9) High Warning NONE PC 3.x
40467 5 Fault Status GasBitmap 37
3285 Spark Plug 17 (A9) Low Warning NONE PC 3.x
40467 6 Fault Status GasBitmap 37
3286 Spark Plug 18 (B9) High Warning NONE PC 3.x
40467 7 Fault Status GasBitmap 37
3287 Spark Plug 18 (B9) Low Warning NONE PC 3.x
40467 8 Fault Status GasBitmap 37
3288 Exhaust Aft Outlet Oxygen RelayOORH
Warning PC 3.x
40467 9 Fault Status GasBitmap 37
3289 Exhaust Aft Outlet Oxygen RelayOORL
Warning PC 3.x
40467 10 Fault Status GasBitmap 37
3291 Exhaust Aft Inlet Oxygen Relay OORH Warning PC 3.x
40467 11 Fault Status GasBitmap 37
3292 Exhaust Aft Inlet Oxygen Relay OORL Warning PC 3.x
40467 12 Fault Status GasBitmap 37
3293 Exhaust Oxygen Relay OORH Warning PC 3.x
40467 13 Fault Status GasBitmap 37
3294 Exhaust Oxygen Relay OORL Warning PC 3.x
40468 3 Fault Status GasBitmap 38
3365 External Air Pressure Low Warning Er-ror
Warning PC 3.x
40468 4 Fault Status GasBitmap 38
3384 Manifold_Absolute_Pres-sure_2_High_Error
Warning PC 3.x
336
Addr. ControlResponseEvent NameFaultCode
NameBit #
40468 5 Fault Status GasBitmap 38
3391 Manifold_Absolute_Pres-sure_2_Low_Error
Warning PC 3.x
40468 6 Fault Status GasBitmap 38
3392 Int Man Pressure 2 Critical High Shutdownw/Cool-down
PC 3.x
40468 7 Fault Status GasBitmap 38
3393 Int Man Pressure 2 Moderate High Warning PC 3.x
40468 9 Fault Status GasBitmap 38
3397 Low Gearbox Oil Pressure − ConditionExists
Shutdownw/Cool-down
PC 3.x
40468 10 Fault Status GasBitmap 38
3398 High Gearbox Oil Temperature − Con-dition Exists
Shutdownw/Cool-down
PC 3.x
40468 11 Fault Status GasBitmap 38
3399 Differential Fault − Condition Exists Shutdownw/Cool-down
PC 3.x
40468 12 Fault Status GasBitmap 38
3411 DC Power Supply Fault − ConditionExists
Warning PC 3.x
40468 13 Fault Status GasBitmap 38
3412 GIB Isolator Open Fault − ConditionExists
Warning PC 3.x
40468 14 Fault Status GasBitmap 38
3413 Radiator Fan Trip Fault − ConditionExists
Warning PC 3.x
40468 15 Fault Status GasBitmap 38
3414 Ventilator Fan Trip Fault − ConditionExists
Warning PC 3.x
40469 0 Fault Status GasBitmap 39
3415 Louvres Closed Fault − Condition Ex-ists
Warning PC 3.x
40469 1 Fault Status GasBitmap 39
3416 Start System Fault − Condition Exists Warning PC 3.x
40469 2 Fault Status GasBitmap 39
3417 Alternator Heater Trip Fault − Condi-tion Exists
Warning PC 3.x
40469 4 Fault Status GasBitmap 39
9971 ECM Derate Fault NONE PC 3.x
40469 5 Fault Status GasBitmap 39
3479 Start−Inhibit Shutdown Fault Shutdown PC 3.x
40469 6 Fault Status GasBitmap 39
3481 Start−Inhibit Warning Fault Event Warning PC 3.x
40469 7 Fault Status GasBitmap 39
3483 High Alternator Temperature 1 Shut-down Fault
Shutdown PC 2.x, PC3.x
40469 8 Fault Status GasBitmap 39
3484 High Alternator Temperature 2 Shut-down Fault
Shutdown PC 2.x, PC3.x
40469 9 Fault Status GasBitmap 39
3485 High Alternator Temperature 3 Shut-down Fault
Shutdown PC 2.x, PC3.x
40469 10 Fault Status GasBitmap 39
3486 High Drive End Bearing TemperatureShutdown Fault
Shutdown PC 2.x, PC3.x
40469 11 Fault Status GasBitmap 39
3487 High Non−Drive End Bearing TempShutdown Fault
Shutdown PC 2.x, PC3.x
40469 12 Fault Status GasBitmap 39
3482 Off Load Running Fault Shutdown PC 3.x
40469 14 Fault Status GasBitmap 39
463 Exhaust_Gas_Oxygen_High_Error Warning PC 3.x
337
Addr. ControlResponseEvent NameFaultCode
NameBit #
40469 15 Fault Status GasBitmap 39
464 Exhaust_Gas_Oxygen_Low_Error Warning PC 3.x
40470 0 Fault Status GasBitmap 40
3491 Oil Filter Restriction High Shutdownw/Cool-down
PC 3.x
40470 1 Fault Status GasBitmap 40
2313 Fuel Control Valve Error Warning PC 3.x
40470 2 Fault Status GasBitmap 40
3475 Engine Electronic Fuel Valve #2OORH
Warning PC 3.x
40470 3 Fault Status GasBitmap 40
3476 Engine Electronic Fuel Valve #2 OORL Warning PC 3.x
40470 4 Fault Status GasBitmap 40
2812 Throttle Control Actuator Error Shutdownw/Cool-down
PC 3.x
40470 5 Fault Status GasBitmap 40
3489 Compressor Bypass Actuator Error Warning PC 3.x
40470 6 Fault Status GasBitmap 40
3458 Knock Engine Derate Warning PC 3.x
40470 7 Fault Status GasBitmap 40
781 CAN Datalink Failed Shutdown PC 2.x, PC3.x
40470 8 Fault Status GasBitmap 40
3499 Throttle Actuator 2− Special Instruc-tion
Shutdownw/Cool-down
PC 3.x
40470 9 Fault Status GasBitmap 40
3511 Throttle Actuator 2− Shorted High Shutdownw/Cool-down
PC 3.x
40470 10 Fault Status GasBitmap 40
3512 Throttle Actuator 2− Shorted Low Shutdownw/Cool-down
PC 3.x
40470 11 Fault Status GasBitmap 40
2752 Throttle Actuator − Shorted High Shutdownw/Cool-down
PC 3.x
40470 12 Fault Status GasBitmap 40
3514 Throttle Actuator − Shorted Low Shutdownw/Cool-down
PC 3.x
40470 13 Fault Status GasBitmap 40
3515 Throttle Actuator − Special instruction Shutdownw/Cool-down
PC 3.x
40470 14 Fault Status GasBitmap 40
3521 Throttle Actuator − Temperature low Warning PC 3.x
40470 15 Fault Status GasBitmap 40
3522 Throttle Actuator 2− Temp low Warning PC 3.x
338
THIS PAGE LEFT INTENTIONALLY BLANK
339
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
340
4. NFPA 110 & Extended Annunciation BitmapNFPA110 bitmap (Register 40016)
BIT DESCRIPTION0 (MSB) Common Alarm
1 Genset Supplying Load
2 Genset Running
3 Not in Auto
4 High Battery Voltage
5 Low Battery Voltage
6 Charger AC Failure
7 Fail to Start
8 Low Coolant Temperature
9 Pre-high Engine Temperature
10 High Engine Temperature
11 Pre-low Oil Pressure
12 Low Oil Pressure
13 Overspeed
14 Low Coolant Level
15 (LSB) Low Fuel Level
Extended Annunciation Bitmap (Register 40017)
BIT DESCRIPTION0 (MSB) Check Genset
1 Ground Fault
2 High AC Voltage
3 Low AC Voltage
4 Under Frequency
5 Overload
6 Overcurrent
7 Short Circuit
8 Reverse KW
9 Reverse KVAR
10 Fail to Sync
11 Fail to Close
12 Load Demand
13 Genset Circuit Breaker Tripped
14 Utility Circuit Breaker Tripped
15 (LSB) Emergency Stop
341
THIS PAGE LEFT INTENTIONALLY BLANK
Cummins Power Generation1400 73rd Ave. NEMinneapolis, MN 55432 USA